Emerson 299H Installation Guide

D102684XUS2
Installation Guide English – September 2012
299H Series
!
Introduction
This Installation Guide provides instructions for installation, startup, and adjustment of 299H Series regulators. To receive a copy of the Instruction
Manual, contact your local Sales Ofce or view a copy at www.sherregulators.com. For further
information refer to: 299H Series Instruction Manual, form 5497, D102684X012.
P.E.D. Categories
This product may be used as a safety accessory
with pressure equipment in the following Pressure Equipment Directive 97/23/EC categories. It may also be used outside of the Pressure Equipment Directive using sound engineering practice (SEP) per table below.
product size category fluid type
DN 40, 50 / NPS 1-1/2, 2 I 1
Specications
Available Congurations
Type 299H: Pilot-operated pressure reducing
regulator with a pilot integrally mounted to the
actuator casing
Type 299HR: A Type 299H with a token internal
relief valve to relieve minor overpressure caused by thermal expansion
Type 299HS: Same as the Type 299H
with a Type VSX-2 slam-shut valve which
provides overpressure or overpressure and underpressure protection
Type 299HSR: Same as the Type 299HS with an internal token relief valve
Body Size and End Connection Styles
See Table 1
Maximum Operating Inlet Pressure by Orice Size
6.4 x 9.5 mm / 1/4 x 3/8 inch – 12.1 bar / 175 psig
9.5 mm / 3/8 inch – 12.1 bar / 175 psig 13 mm / 1/2 inch – 12.1 bar / 175 psig 19 mm / 3/4 inch – 10.3 bar / 150 psig 22 mm / 7/8 inch 25 mm / 1 inch 30 mm / 1-3/16 inch
1. The pressure/temperature limits in this Installation Guide and any applicable
standard or code limitation should not be exceeded.
2. For optimum performance, a pilot supply regulator may be installed in the pilot supply tubing between the main valve and pilot.
3. This orice size is not available for Types 299HS and 299HSR.
(3)
– 8.6 bar / 125 psig
(3)
– 6.9 bar / 100 psig
(3)
– 5.5 bar / 80 psig
(1)
Maximum Casing and Emergency Outlet Pressure
(1)
4.5 bar / 66 psig
Proof Test Pressure
All Pressure Retaining Components have been
proof tested per Directive 97/23/EC - Annex 1,
Section 7.4
Outlet (Control) Pressure Ranges
(1)(2)
See Table 2
Minimum Differential Pressure For Full Stroke
0.10 bar / 1.5 psi
Maximum Set Pressure for Type 299HS
(1)
1.1 bar / 16 psig
Maximum Set Pressure for Type VSX-2 Slam-Shut Device
(1)
1.6 bar / 23 psig
Minimum and Maximum Trip Pressure Ranges
(1)
See Table 3
Temperature Capabilities
-29 to 66°C / -20 to 150°F
(1)
Installation
Warning
Only qualied personnel should install or service a regulator. Regulators should be installed, operated, and maintained in accordance with international and applicable codes and regulations, and Emerson Process Management Regulator Technologies Inc. (Regulator Technologies) instructions.
If the regulator vents uid or a leak develops in the system, it indicates that service is required. Failure to take the regulator out of service immediately may create a hazardous condition.
Personal injury, equipment damage, or leakage due to escaping uid or bursting of pressure-containing parts may result if this regulator is overpressured or is installed where service conditions could exceed the limits given in the Specications section, or where conditions exceed any ratings of the adjacent piping or piping connections.
www.sherregulators.com
299H Series
!
To avoid such injury or damage, provide pressure-relieving or pressure­limiting devices (as required by the appropriate code, regulation, or standard) to prevent service conditions from exceeding limits.
Additionally, physical damage to the regulator could result in personal injury and property damage due to escaping uid. To avoid such injury and damage, install the regulator in a safe location.
Clean out all pipelines before installation of the regulator and check to be sure the regulator has
not been damaged or has collected foreign material
during shipping. For NPT bodies, apply pipe compound to the external pipe threads. For anged bodies, use suitable line gaskets and approved
piping and bolting practices. Install the regulator
in any position desired, unless otherwise specied, but be sure ow through the body is in the direction indicated by the arrow on the body.
Note
It is important that the regulator be installed so that the vent hole in the spring case is unobstructed at all times. For outdoor installations, the regulator should be located away from vehicular trafc and positioned so that water, ice, and other foreign materials cannot enter the spring case through the vent. Avoid placing the regulator beneath eaves or downspouts, and be sure it is above the probable snow level.
Overpressure Protection
The recommended pressure limitations are stamped on the regulator nameplate. Some type of overpressure protection is needed if the actual inlet pressure exceeds the maximum operating outlet pressure rating. Overpressure protection should also be provided if the regulator inlet
pressure is greater than the safe working pressure of the downstream equipment.
Regulator operation below the maximum pressure
limitations does not preclude the possibility of damage from external sources or debris in the line. The regulator should be inspected for damage after any overpressure condition.
Startup
The regulator is factory set at approximately the midpoint of the spring range or at the pressure
requested, so an initial adjustment may be required
to give the desired results. With proper installation
completed and relief valves properly adjusted, slowly open the upstream and downstream shutoff valves.
Adjustment
To change the outlet pressure, remove the closing
cap or loosen the locknut and turn the adjusting screw clockwise to increase outlet pressure or counterclockwise to decrease pressure. Monitor the outlet pressure with a test gauge during the adjustment. Replace the closing cap or tighten the locknut to maintain the desired setting.
Type VSX-2 Installation
Warning
If the Type VSX-2 is exposed to an overpressure condition, it should be inspected for any damage that may have occurred. Operation below these limits does not preclude the possibility of damage from external sources or from debris in the pipeline.
The Type VSX-2 may be shipped separately from
the regulator. To install the unit on a regulator, place
the new O-rings (keys 2 and 3, Figure 1) on the Type VSX-2 and slide the module into the regulator body. Secure the Type VSX-2 to the regulator body with the four set screws (key 4). The unit may be oriented in any direction with respect to the sensor
line connection.
2
Type VSX-2 Trip Adjustment
Note
An adjustment tool is included with the Type VSX-2. Use only this tool to make adjustments to the unit. To make adjustments, the overpressure trip spring is found under the outer adjusting screw and the underpressure trip spring is found under the inner adjusting screw.
To adjust the Overpressure Trip Spring:
1. Adjust the overpressure trip setting to its maximum compression.
2. If present, adjust the underpressure spring to its minimum compression.
3. Backpressure the unit with the desired overpressure trip pressure.
4. Reduce the overpressure trip spring compression until the Type VSX-2 trips.
299H Series
Table 1. Body Sizes and End Connection Styles
Body size Body Material and end connection style
dn Inch
(For Types 299H and 299HR only)
32 1-1/4 NPT - - - - - - - -
40 1-1/2 NPT NPT NPT
50 2 NPT and CL125 FF
1. This ange is available with a face-to-face dimension of 191 mm / 7.5 inches or 254 mm / 10 inches.
outlet (control) pressure range type
mbar Inch w.c. 299H 299HR, 299HS, and 299HSR
(1)
9 to 15
(1)
12 to 22 17 to 50 40 to 99
(1)
(1)
69 mbar to 0.22 bar
0.19 to 0.41 bar
0.35 to 1.1 bar
0.97 to 2.4 bar
2.1 to 4.1 bar
1. Use a pilot supply regulator if actual inlet pressure varies more than ±1.4 bar / 20 psi and the published accuracy is required.
Cast Iron
(1)
anged
NPT, CL125 FF, CL250 RF, and
Table 2. Outlet Pressure Ranges
(1)
3.5 to 6
(1)
5 to 9
(1)
7 to 20
(1)
16 to 40
1 to 3.25 psig
2.75 to 6 psig 5 to 16 psig
14 to 35 psig 30 to 60 psig
Ductile Iron
PN 10/16 anged
X X X X
X X X X X
(For Types 299H and 299HR only)
NPT, CL150 RF, and PN 16 anged
Steel
X X X X
X X X
- - - -
- - - -
Table 3. Type VSX-2 High and Low Trip Pressure Ranges
setpoint
ranges
SLAM-SHUT TYPE
High Pressure Trip LP
Low Pressure Trip LP
Note: Other spring combinations are available, please contact your local Sales Ofce for additional information.
FOR USE WITH MAIN VALVE SPRING RANGE MINIMUM TO MA XIMUM TRI P PRESSURE
mbar Inch w.c. mbar Inch w.c.
9 to 15 3.5 to 6
12 to 22 5 to 9
9 to 15 3.5 to 6
17 to 50 7 to 20
17 to 50 7 to 20
40 to 99 16 to 40
40 to 99 16 to 40
0.19 to 0.41 bar 2.75 to 6 psig
0.19 to 0.41 bar 2.75 to 6 psig
0.35 to 1.1 bar 5 to 16 psig
0.35 to 1.1 bar 5 to 16 psig 800 to 1586 11.6 to 23 psig
12 to 22 5 to 9
17 to 50 7 to 20
17 to 50 7 to 20
40 to 99 16 to 40
69 mbar to 0.22 bar 1 to 3.25 psig
0.19 to 0.41 bar 2.75 to 6 psig
0.19 to 0.41 bar 2.75 to 6 psig
0.35 to 1.1 bar 5 to 16 psig
30 to 62 12 to 25
50 to 129 20 to 5212 to 22 5 to 9
97 to 269 1.4 to 3.9 psig
262 to 600 3.8 to 8.7 psig 69 mbar to 0.22 bar 1 to 3.25 psig
400 to 1103 5.8 to 16 psig
5 to 30 2 to 12
10 to 75 4 to 30
25 to 159 0.36 to 2.3 psig
103 to 745 1.5 to 10.8 psig
3