Emerson 23-23-220-8, 23-13-060-2, 23-23-230-8, 23-22-112-2, 23-23-250-8 User Manual

...
CVS Hardwired Series – 60 Hz
User Manual
Contents
1.0 Important Safety Instructions .................................................................................................................................. 3
2.0 Warnings Defined ..................................................................................................................................................... 3
3.0 Introduction .............................................................................................................................................................. 3
4.0 Installation Instructions ............................................................................................................................................ 3
4.1 Receiving .................................................................................................................................................................................. 3
4.2 Mounting & Ventilation .............................................................................................................................................................3
4.3 Mechanical Drawings & Dimensions ........................................................................................................................................ 4
4.4 Electrical ................................................................................................................................................................................... 6
5.0 Parallel & Three-Phase Connections ....................................................................................................................... 9
5.1 Parallel Operation ..................................................................................................................................................................... 9
5.2 Three-Phase Connection Operation ......................................................................................................................................... 9
6.0 Operating Notes & Data ......................................................................................................................................... 10
6.1 Checking with Voltmeters .......................................................................................................................................................10
6.2 Load Regulation ..................................................................................................................................................................... 10
6.3 Effect of Load Power Factor .................................................................................................................................................. 10
6.4 Operation with Switch-Mode Power Supplies ....................................................................................................................... 10
6.5 Effect of Frequency ................................................................................................................................................................ 10
6.6 Response Time ....................................................................................................................................................................... 10
6.7 Input Characteristics .............................................................................................................................................................. 10
6.8 Current Limitations ................................................................................................................................................................. 11
6.9 Operation with Motor Loads .................................................................................................................................................. 11
7.0 Service & Maintenance .......................................................................................................................................... 11
7.1 Service & Maintenance ........................................................................................................................................................... 11
7.2 Field Replacement of Capacitors ........................................................................................................................................... 11
8.0 Troubleshooting ...................................................................................................................................................... 11
9.0 Specifications ......................................................................................................................................................... 12
10.0 Warranty & Support .............................................................................................................................................. 12
10.1 Warranty Information ............................................................................................................................................................ 12
10.2 Technical Support ................................................................................................................................................................. 12
While every precaution has been taken to ensure accuracy and completeness in this manual, Appleton Group, LLC. assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions. The SolaHD and Emerson logos are registered in the U.S. Patent and Trademark Ofce. All other product or service names are the property of their registered owners. ©2016 Appleton Group, LLC. All rights reserved. Specications are subject to change without notice.
1.0 Important Safety Instructions
Please read all safety, installation, and operating instructions before attempting to install or operate the unit.
2.0 Warnings Defined
!
!
!
3.0 Introduction
4.0 Installation Instructions
!
DANGER! High voltages are present inside the unit. Do not reach inside while it is energized. This unit contains no
user-serviceable parts.
DANGER! Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. This signal
word is limited to the most extreme situations.
WARNING! Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION! Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury. It may also
be used to alert against unsafe practices.
The SolaHD Constant Voltage Sinusoidal (CVS) transformer provides voltage regulation and isolation from both transverse and common mode noise for any type of load. It also suppresses transients with ferroresonant, protects overloads, and serves as a dedicated line. It is the ultimate in ac power conditioning equipment.
4.1 Receiving
Upon receipt, immediately inspect the unit for obvious signs of shipping damage and/or mishandling. If damaged, photograph the unit, inform the carrier, and contact your SolaHD representative.
4.2 Mounting & Ventilation
These units are for use in an indoor humidity and temperature controlled environment. Mount the unit in either a horizontal or vertical position. The unit should be located where contact with the transformer’s hot surface is unlikely. If mounted in a vertical position (e.g. on a wall), steel mounting hardware must be selected in accordance with Table 1. The wiring compartment should also be facing up.
Table 1: Mounting Hardware
CVS Rated VA Steel Mounting Screws (Minimum Diameter)
30–120 VA #10 machine screws
250 VA 1/4 in. bolts
500–1000 VA 5/16 in. bolts
1500–10000 VA 3/8 in. bolts
15000 VA 1/2 in. bolts
All regulators generate a considerable amount of heat and depend on natural convection for adequate cooling. It is important that ventilation openings not be obstructed. Mounting in a conned or poorly ventilated space should be avoided, unless special provisions have been made for ventilation. For proper ventilation, allow a minimum of 12 inches of clearance above the unit and minimum of 6 inches of clearance on each side.
CVS HARDWIRED SERIES USER MANUAL | 3
4.3 Mechanical Drawings & Dimensions
FIGURE 1
Table 2: Dimensions—Figure 1
Catalog
Hz
Number
60 23-13-030-2 6.12 [155.4] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 1.75 [44.4]
60 23-13-060-2 6.94 [176.3] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 1.75 [44.4]
60 23-22-112-2 8.12 [206.2] 5.19 [131.8] 3.47 [88.1] 4.00 [101.6] 3.50 [88.9] 3.00 [76.2] 2.44 [62.0]
60 23-23-125-8 10.50 [266.7] 7.56 [192.0] 4.75 [120.6] 5.63 [143.0] 4.75 [120.6] 4.12 [104.6] 3.03 [77.0]
60 23-23-150-8 13.00 [330.2] 6.50 [165.1] 8.12 [206.2] 9.00 [228.6] 8.12 [206.2] 5.62 [142.7] 3.06 [77.7]
60 23-23-210-8 17.25 [438.2] 6.81 [173.0] 8.12 [206.2] 9.00 [228.6] 8.12 [206.2] 5.62 [142.7] 5.25 [133.4]
A B C D E F G H
Dimensions in inches [mm]
0.22 x 0.59 [5.6 x 15.0]
0.22 x 0.59 [5.6 x 15.0]
0.22 x 0.59 [5.6 x 15.0]
0.31 x 0.69 [7.9 x 17.5]
0.38 x 0.81 [9.7 x 20.6]
0.38 x 0.81 [9.7 x 20.6]
Ship Weight
lb. [kg]
7.0 [3.2]
9.0 [4.1]
13.0 [5.9]
28.0 [12.7]
37.0 [16.8]
63.0 [28.6]
FIGURE 2
Table 3: Dimensions—Figure 2
Catalog
Hz
Number
60 23-23-220-8 17.58 [446.5] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 3.88 [98.6] 5.19 [131.8]
60 23-23-230-8 18.96 [481.6] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 5.25 133.4] 5.19 [131.8]
60 23-23-250-8 28.53 [724.7] 9.44 [239.8] 10.56 [268.2] 12.75 [323.8] 11.75 [298.5] 8.25 [209.5] 8.88 [225.6]
4 | CVS HARDWIRED SERIES USER MANUAL
A B C D E F G H
Dimensions in inches [mm]
0.44 x 0.69
[11.2 x 17.5]
0.44 x 0.69
[11.2 x 17.5]
0.44 x 0.69
[11.2 x 17.5]
Ship Weight
lb. [kg]
109.0 [49.4]
142.0 [64.4]
222.0 [100.7]
FIGURE 3
Table 4: Dimensions—Figure 3
Catalog
Hz
Number
60 23-28-275-6 26.91 [683.5] 9.27 [235.6] 23.55 [598.2] 25.81 [655.6] 24.81 [630.2] 6.62 [168.1] 8.88 [225.6]
A B C D E F G H
Dimensions in inches [mm]
0.44 x 0.69
[11.2 x 17.5]
Ship Weight
lb. [kg]
365.0 [165.6]
CVS HARDWIRED SERIES USER MANUAL | 5
4.4 Electrical
!
Caution! All hardwired units should be installed in accordance with local and national electrical codes.
FIGURE 4
Table 5: Electrical Connections—Figure 4
Catalog Number Primary Voltage Interconnect Connect Lines to
23-13-030-2 120 H3 and H4 are NOT used H1 and H2 23-13-060-2 120 H3 and H4 are NOT used H1 and H2
23-22-112-2
23-28-275-6
Catalog Number Secondary Voltage Interconnect Connect Lines to
23-13-030-2 120 --- X1 and X2 23-13-060-2 120 --- X1 and X2 23-22-112-2 120 --- X1 and X2
23-28-275-6
120
240 H2 to H3 H1 and H4
240
480 H2 to H3 H1 and H4
120 --- X1 and X2 OR X3 and X2 240 --- X1 and X3
H1 to H3 H2 to H4
H1 to H3 H2 to H4
H1 and H4
H1 and H4
NOTE: Secondaries are not grounded. Ground X2 per code.
Table 6: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-13-030-2 30 60 23-13-060-2 60 85 23-22-112-2 120 136 23-28-275-6 7500 2407
Table 7: Fusing & Wiring
Catalog Number
23-13-030-2 1 A/14 AWG --- --- --- --- 14 AWG --- --­23-13-060-2 2 A/14 AWG --- --- --- --- 14 AWG --- --­23-22-112-2 3 A/14 AWG --- 3 A/14 AWG --- --- 14 AWG --- --­23-28-275-6 --- --- 60 A/6 AWG 30 A/10 AWG --- 4 AWG 8 AWG 8 AWG
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Input Voltage Output Voltage
95–130 175–235 190–260 380–520 475–650 120 208 240
6 | CVS HARDWIRED SERIES USER MANUAL
FIGURE 5
Table 8: Electrical Connections—Figure 5
Catalog Numbers Primary Voltage Interconnect Connect Lines to
23-23-125-8
Table 9: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-23-125-8 250 225
120
240
480
Secondary Voltage Interconnect Connect Lines to
120 --- X1 and X2
H1 to H3 to H5 to H7 H2 to H4 to H6 to H8
H2 to H3 H6 to H7 H1 to H5 H4 to H8
H2 to H3 H4 to H5
H6 to H7
H1 and H2
H1 and H4
H1 and H8
Table 10: Fusing & Wiring
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Catalog Number
95–130 175–235 190–260 380–520 475–650 120 208 240
23-23-125-8 6 A/14 AWG --- 3 A/14 AWG 1 A/14 AWG --- 14 AWG --- ---
Input Voltage Output Voltage
CVS HARDWIRED SERIES USER MANUAL | 7
FIGURE 6
Table 11: Electrical Connections—Figure 6
Catalog Number Primary Voltage Interconnect Connect Lines to
H1 to H3 to H6 to H8
H2 to H5 to H7 to H10
H2 to H3 H7 to H8 H1 to H6 H4 to H9
H2 to H3 H7 to H8
H1 to H6 H5 to H10
H2 to H3 H5 to H6
H7 to H8
H1 and H2
H1 and H4
H1 and H5
H1 and H10
23-23-150-8 23-23-210-8 23-23-220-8 23-23-230-8 23-23-250-8
120
208
240
480
Secondary Voltage Interconnect Connect Lines to
120 --- X1 and X2 OR X3 and X2 240 --- X1 and X3
Table 12: Product Parameters
Catalog Number VA BTU Output at Full load, +40°C Ambient
23-23-150-8 500 280 23-23-210-8 1000 519 23-23-220-8 2000 1229 23-23-230-8 3000 1331 23-23-250-8 5000 2117
Table 13: Fusing & Wiring
Required Circuit Protection/Minimum Gauge for 90°C Wire Minimum Gauge for 90°C Wire
Catalog
Number
95–130 175–235 190–260 380–520 475–650 120 208 240
23-23-150-8 10 A/14 AWG 6 A/14 AWG 6 A/14 AWG 3 A/14 AWG --- 14 AWG 23-23-210-8 15 A/14 AWG 10 A/14 AWG 10 A/14 AWG 6 A/14 AWG --- 14 AWG 23-23-220-8 30 A/10 AWG 20 A/12 AWG 15 A/14 AWG 10 A/14 AWG --- 10 AWG 14 AWG 23-23-230-8 45 A/8 AWG 25 A/10 AWG 25 A/10 AWG 15 A/14 AWG --- 8 AWG 12 AWG 23-23-250-8 80 A/4 AWG 40 A/8 AWG 40 A/8 AWG 20 A/12 AWG --- 8 AWG* 10 AWG
*Leads in the wiring compartment must have 105°C sleeving
8 | CVS HARDWIRED SERIES USER MANUAL
Input Voltage Output Voltage
5.0 Parallel & Three-Phase Connections
5.1 Parallel Operation
!
In Grounded WYE
Units of the same SolaHD catalog number may be connected in parallel to obtain a larger load capacity. Both input and output connections must be made in parallel (see Figure 6). The SolaHD catalog number must end in -8 or -C8 and must be larger than 1 kVA. No portable units can be paralleled.
All input and output paralleling wires must be tied together in an external paralleling “box” provided by the user. Do not attempt to jumper the wires of one unit to the terminal block of the other unit. The terminal block may not be rated to carry the total currents of both units. The input of each unit must be properly and separately fused.
CAUTION! Failure to adhere to these requirements may damage the windings.
For units smaller than 5 kVA: When connecting in parallel the 208 Volt windings, other output voltage ratings (120 V, 240 V) can’t be paralleled at the same time and vice versa. It is suggested that the installer remove X2 grounding on each unit, then connect X2 from each unit to one location and ground at that location only.
5.2 Three-Phase Connection Operation
Loads requiring 4-wire WYE connection may be served by three ferroresonant power conditioners with the same SolaHD catalog number. The inputs must be connected in Delta. Input fuses must be connected in the primary of each unit, not in the three-phase lines. The outputs must be connected in WYE with the neutral solidly connected to a WYE load. Alternatively, these three outputs may serve three independent single-phase loads. Phase angles may vary somewhat from 120 degrees even with balanced loading.
This circuit arrangement is not intended to serve single-phase line-to-line loading or three-phase Delta loading. Outputs must serve three independent, single-phase loads of the same total Volt-Amphere (VA) rating. Connections should be made in one of two ways as shown in Figure 6.
The outputs of the unit are isolated from the input lines. Voltage generated by internal leakage currents will occur with respect to ground, which can have undesirable effects in electronic equipment. Therefore, if circuit “B” is used, it is suggested that the installer remove X2 grounding on -8 units, then connect all X2 from each phase to one location and ground at that location only. This is not required for circuit “A” and will not affect regulation or the ability to reject power line noise or transients.
FIGURE 6
B
A
CV
Trans
Load
(A) Isolated Single-Phase Loads
CV
Trans
Load
(B) Separte Single-Phase Loads
Trans
Load
A
Trans
Load
CV
B
CV
C
CV
Trans
Load
C
CV
Trans
Load
Ac Single-Phase Input
Input
Input
Unit A
Unit B
Output
Output
CVS HARDWIRED SERIES USER MANUAL | 9