5.9. Compliance with Standards .......................................................................................... 83
7
MAN-G-BELIG (Ve r. 1.004)
Chapter 1: Safety Information
Warning:
Caution:
Gold Bell Installation Guide
In order to achieve the optimum, safe operation of the Gold Bell servo drive, it is imperative
that you implement the safety procedures included in this installation guide. This information is
provided to protect you and to keep your work area safe when operating the Gold Bell and
accompanying equipment.
Please read this chapter carefully before you begin the installation process.
Before you start, ensure that all system components are connected to earth ground. Electrical
safety is provided through a low-resistance earth connection.
Only qualified personnel may install, adjust, maintain and repair the servo drive. A qualified
person has the knowledge and authorization to perform tasks such as transporting, assembling,
installing, commissioning and operating motors.
The Gold Bell servo drive contains electrostatic-sensitive components that can be damaged if
handled incorrectly. To prevent any electrostatic damage, avoid contact with highly insulating
materials, such as plastic film and synthetic fabrics. Place the product on a conductive surface
and ground yourself in order to discharge any possible static electricity build-up.
8
To avoid any potential hazards that may cause severe personal injury or damage to the product
during operation, keep all covers and cabinet doors shut.
The following safety symbols are used in this manual:
This information is needed to avoid a safety hazard, which might cause bodily
injury.
This information is necessary for preventing damage to the product or to
other equipment.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideSafety Information
1.1. Warnings
• To avoid electric arcing and hazards to personnel and electrical contacts, never
connect/disconnect the servo drive while the power source is on.
• Power cables can carry a high voltage, even when the motor is not in motion. Disconnect
the Gold Bell from all voltage sources before it is opened for servicing.
• The Gold Bell servo drive contains grounding conduits for electric current protection. Any
disruption to these conduits may cause the instrument to become hot (live) and dangerous.
• After shutting off the power and removing the power source from your equipment, wait at
least 1 minute before touching or disconnecting parts of the equipment that are normally
loaded with electrical charges (such as capacitors or contacts). Measuring the electrical
contact points with a meter, before touching the equipment, is recommended.
1.2. Cautions
• The Gold Bell servo drive contains hot surfaces and electrically-charged components during
operation.
9
• The maximum DC power supply connected to the instrument must comply with the
parameters outlined in this guide.
• When connecting the Gold Bell to an approved isolated 12–95 VDC auxiliary power supply,
connect it through a line that is separated from hazardous live voltages using reinforced or
double insulation in accordance with approved safety standards.
• Before switching on the Gold Bell, verify that all safety precautions have been observed
and that the installation procedures in this manual have been followed.
• Do not clean any of the Gold Bell drive's soldering with solvent cleaning fluids of pH greater
than 7 (8 to 14). The solvent corrodes the plastic cover causing cracks and eventual damage
to the drive's PCBs.
Elmo recommends using the cleaning fluid Vigon-EFM which is pH Neutral (7).
For further technical information on this recommended cleaning fluid, select the link:
The Gold Bell conforms to the following industry safety standards:
Safety Standard Item
10
In compliance with
Adjustable speed electrical power drive systems
IEC/EN 61800-5-1, Safety
Recognized UL 508CPower Conversion Equipment
In compliance with UL 840Insulation Coordination Including Clearances and
Creepage Distances for Electrical Equipment
In compliance with UL 60950-1 (formerly UL 1950)
Safety of Information Technology Equipment
Including Electrical Business Equipment
In compliance with EN 60204-1 Low Voltage Directive 73/23/EEC
The Gold Bell servo drive has been developed, produced, tested and documented in
accordance with the relevant standards. Elmo Motion Control is not responsible for any
deviation from the configuration and installation described in this documentation.
Furthermore, Elmo is not responsible for the performance of new measurements or ensuring
that regulatory requirements are met.
1.4. CE Marking Conformance
The Gold Bell servo drive is intended for incorporation in a machine or end product. The actual
end product must comply with all safety aspects of the relevant requirements of the European
Safety of Machinery Directive 98/37/EC as amended, and with those of the most recent
versions of standards EN 60204-1 and EN 292-2 at the least.
According to Annex III of Article 13 of Council Directive 93/68/EEC, amending Council Directive
73/23/EEC concerning electrical equipment designed for use within certain voltage limits, the
Gold Bell meets the provisions outlined in Council Directive 73/23/EEC. The party responsible
for ensuring that the equipment meets the limits required by EMC regulations is the
manufacturer of the end product.
1.5. Warranty Information
The products covered in this manual are warranted to be free of defects in material and
workmanship and conform to the specifications stated either within this document or in the
product catalog description. All Elmo drives are warranted for a period of 12 months from the
time of installation, or 18 months from time of shipment, whichever comes first. No other
warranties, expressed or implied — and including a warranty of merchantability and fitness for
a particular purpose — extend beyond this warranty.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Chapter 2: Product Description
Gold Bell Installation Guide
2.1. Functional Description
The Gold Bell is an advanced high power density servo drive. It provides top servo
performance, advanced networking and built in safety, all in a small PCB mountable package.
The Gold Bell has a fully featured motion controller and local intelligence.
The Gold Bell operates from a DC power source. The drive can operate as a stand-alone device
or as part of a multi-axis system in a distributed configuration on a real-time network.
The Gold Bell drive is easily set up and tuned using the Elmo Application Studio (EAS) software
tools. As part of the Gold product line, it is fully programmable with the Elmo motion control
language. For more information about software tools refer to the Elmo Application Studio
Software Manual.
The Gold Bell is available in a variety of models. There are multiple power rating options, two
different communications options, a number of feedback options and different I/O
configuration possibilities.
11
2.2. Product Features
Note: The features described in this chapter relate to the range of Gold Bell models.
Depending on the model you have purchased, not all features are available.
To see the features for your model, look at the product label on the Gold Bell and use the
product catalog number schematic that appears at the beginning of this manual and on
page 24 to determine which specific features are available to you.
2.2.1. High Power Density
The Gold Bell delivers up to 1.6 kW of continuous power or 3.2 kW of peak power in a 49.4 cc
(3.02 in
3
) package (55 x 59 x 15 mm or 2.17” x 2.32” x 0.6”)
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
2.2.2. Supply Input
• Single DC Power Supply: Power to the Gold Bell is provided by a single 12 V to 95 V isolated
DC power source (not included with the Gold Bell). A “smart” control-supply algorithm
enables the Gold Bell to operate with only one power supply with no need for an auxiliary
power supply for the logic.
• Optional Backup Supply: If backup functionality is required in case of power loss, e.g., to
keep the original position, an external 12 V to 95 V isolated supply should be connected.
This is more flexible than the requirement for 24 VDC supply.
If backup is not needed, a single power supply is used for both the power and logic circuits.
There are multiple voltage ratings of the Gold Bell (12 V to 95 V), so you must use the correct
power supply according to the maximum operating voltage of the Gold Bell. See Section
Chapter 3: Technical Information.
2.2.3. Servo Control
12
• Advanced and extremely fast vector control algorithm (current loop bandwidth: 4 kHz)
• Current/Torque sampling rate: up to 25 kHz (40 μs)
• Velocity sampling rate: up to 12.5 kHz (80 μs)
• Position sampling rate: up to 12.5 kHz (80 μs)
• Electrical commutation frequency: up to 4 kHz
• Current closed loop bandwidth exceeds 4 kHz
• Position/Velocity/Acceleration command range – full 32 bit
• Position over velocity, with full dual loop support
• Current gain scheduling to compensate for the motor’s non-linear characteristics
• Advanced filtering: Low pass, Notch, General Biquad
• Current loop gain scheduling to compensate for bus voltage variations
• Velocity gain scheduling for ultimate velocity loop performance
• Gains and filter scheduling vs. position for mechanical coupling optimization, speed and
position tracking errors
• High order filters gain scheduling vs. speed and position
• S-curve Profile Smoothing
• Cogging, BEMF and
ωxL compensation
• Dual Loop Operation supported by Auto Tuning
• Fast, easy and efficient advanced Auto Tuning
• Incremental encoder frequency of up to 75 Megacounts/sec
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
• Motion profiler numeric range:
9
Position up to ±2 x 10
Velocity up to 2 x 10
Acceleration up to 2 x 10
counts
9
counts/sec
9
counts/sec2
2.2.4. Advanced Filters and Gain Scheduling
• “On-the-Fly” gain scheduling of current and velocity
• Velocity and position with “1-2-2” PIP controllers
• Automatic commutation alignment
• Automatic motor phase sequencing
• Current gain scheduling to compensate for the motor's non-linear characteristics
• Advanced filtering: Low pass, Notch, General Biquad
• Current loop gain scheduling to compensate for bus voltage variations
13
• Velocity gain scheduling for reliable velocity loop performance
• Gains & filter scheduling vs. position for mechanical coupling optimization, speed and
position tracking errors
• High order filters gain scheduling vs. speed and position
2.2.5. Motion Control
• Motion control programming environment
• Motion modes: PTP, PT, PVT, ECAM, Follower, Dual Loop, Current Follower, Fast event
capturing inputs
• Full DS-402 motion mode support, in both the CANopen and CANopen over EtherCAT (CoE)
protocols, including Cyclic Position/Velocity modes. Fast (Hardware) event capturing
inputs, supporting < 1 μs latch latency
• Fast (hardware) Output Compare, with < 1 μs latency
• Output compare repetition rate:
Fixed Gap: Unlimited
Table based: 4 kHz
• Motion Commands: Analog current and velocity, Pulse-Width Modulation (PWM) current
and velocity, digital (software), Pulse and Direction
• Distributed Motion Control
• EAS (Elmo Application Studio) software: an efficient and user friendly auto tuner
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
2.2.6. Fully Programmable
• Third generation programming structure
• Event capturing interrupts
• Event triggered programming
2.2.7. Feedback Ports Options
• There are Port A and Port B feedback input ports that are flexible and configurable. Each
• Port A supports the following sensors, depending on the specific model:
Incremental encoder
Incremental encoder and digital Hall
Absolute serial encoder
Absolute serial encoder and digital Hall (for dual loop)
14
• Port B supports the following sensors, depending on the specific model:
Incremental encoder
Analog encoder
Analog Hall
Resolver
• Port C is a flexible and configurable feedback output port. It supports the Encoder
emulation outputs of Port A or Port B or internal variables
• Analog input (±10 V ptp) support:
Velocity feedback (tachometer)
Position feedback (potentiometer)
2.2.8. Feedback Sensor Specifications
• Incremental Encoder – up to 75 Megacounts per second (15 MHz on A/B)
• Digital Halls:
Up to 4 kHz commutation frequency
5 V logic
Input voltage up to 15 VDC
• Incremental encoder with digital Halls for commutation – up to 75 Megacounts per second
for encoder
• Interpolated Analog (Sine/Cosine) Encoder:
Supports 1 V PTP Sin/Cos
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
Sin/Cos frequency: up to 500 kHz
Internal interpolation: up to ×8192
Automatic correction of amplitude mismatch, phase mismatch, signal offset
Emulated encoder output of the analog encoder
• Analog Hall Sensor:
One feedback electrical cycle = one electrical cycle of the motor
Supports 1 V PTP Sin/Cos
Sin/Cos Frequency: up to 500 kHz
Internal Interpolation: up to ×8192
Automatic correction of amplitude mismatch, phase mismatch, signal offset
• Resolver
14-bit resolution
Up to 512 revolutions per second (RPS)
Emulated encoder outputs of the resolver
The Gold Bell can provide power (5 V, 2x200 mA max) for encoders, resolvers or Halls.
2.2.9. Communications
• Fast and efficient EtherCAT and CAN networking
• EtherCAT Slave:
CoE (CANopen over EtherCAT)
EoE (Ethernet over EtherCAT)
FoE (File over EtherCAT) for firmware download
Supports Distributed Clock
EtherCAT cyclic modes supported down to a cycle time of 250 μs
• CANopen (DS-301, DS-305, DS-402)
• Ethernet TCP/IP
UDP
Telnet
• USB 2.0
• RS-232 (TTL logic level)
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
2.2.10. Safety
• IEC 61800-5-2, Safe Torque Off (STO)
Two STO (Safe Torque Off) inputs
Optically isolated
TTL Level (5 V logic)
Open collector and open emitter
• UL 508C recognition
• UL 60950 compliance
• CE EMC compliance
2.2.11. Digital Outputs
• Two separate programmable digital outputs
Optically isolated sink and source for TTL level
16
• Pulse and Direction inputs (single-ended)
• PWM current command output for torque and velocity
• Optional functions:
Fast output compare
Brake control
Amplifier fault indication
General purpose
Servo enable indication
Output level: up to 30 V
Open collector and open emitter
2.2.12. Differential Outputs
• Three differential outputs:
Port C EIA-422 differential output line transmitters
Response time < 1 μs
Output current: ± 15 mA.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
2.2.13. Digital Inputs
• Six separate programmable digital inputs
TTL Level (5 V logic)
Optically isolated
Fast digital capture data <5 μs
• Optional functions:
Fast event capture
Inhibit/Enable motion
Stop motion under control (hard stop)
Motion reverse and forward limit switches
Begin on input
Abort motion
Homing
General purpose
17
2.2.14. Differential Inputs
• Six very fast differential event capture inputs 5 V logic
Via Port A or B (three on each port, depending on model)
EIA-422 Differential input line receiver
Response time < 1 μs
2.2.15. Analog Input
• One Analog Input – up to 14-bit resolution
• Input: ±10 V
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
2.2.16. Built-In Protection
• Software error handling
• Abort (hard stops and soft stops)
• Extensive Status reporting
• Protection against:
Shorts between motor power outputs
Shorts between motor power outputs and power input/return
Failure of internal power supplies
Overheating
Over temperature
Motor current
2
i
t motor current
• Continuous temperature measurement. Temperature can be read on-the-fly; a warning can
be initiated x degrees before temperature disable is activated.
18
Over/under voltage
Loss of feedback
Following error
Current limits
2.2.17. Status Indication
• Output for a bi-color LED
2.2.18. Automatic Procedures
• Commutation alignment
• Phase sequencing
• Current loop offset adjustment
• Current loop gain tuning
• Current gain scheduling
• Velocity loop offset adjustment
• Velocity gain tuning
• Velocity gain scheduling
• Position gain tuning
2.2.19. Accessories
• External heatsink. See Section 4.4 for details. Catalog number: WHI-HEATSINK-2.
• Cable Kit (TBD)
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
2.3. System Architecture
19
Figure 1: Gold Bell System Block Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideProduct Description
2.4. How to Use this Guide
In order to install and operate your Elmo Gold Bell servo drive, you will use this manual in
conjunction with a set of Elmo documentation. Installation is your first step; after carefully
reading the safety instructions in the first chapter, the following chapters provide you with
installation instructions as follows:
• Chapter 4 - Technical Specifications, lists all the drive ratings and specifications.
Upon completing the instructions in this guide, your Gold Bell servo drive should be
successfully mounted and installed. From this stage, you need to consult higher-level Elmo
documentation in order to set up and fine-tune the system for optimal operation.
• The Gold Product Line Software Manual, which describes the comprehensive software used
with the Gold Bell.
• The Gold Product Line Command Reference Manual, which describes, in detail, each
software command used to manipulate the Gold Bell motion controller.
20
• The Elmo Application Studio Software Manual, which includes explanations of all the
software tools that are part of the Elmo Application Studio software environment.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Chapter 3: Technical Information
Gold Bell Installation Guide
21
3.1. Technical Data
Feature Units 1/100 2.5/100 5/100 10/100 15/100 20/100
Minimum supply voltage VDC 12
Nominal supply voltage VDC 85
Maximum supply voltage VDC 95
Maximum continuous power
W 80 200 400 800 1200 1600
output
Efficiency at rated power (at
% > 99
nominal conditions)
Maximum output voltage > 95% of DC bus voltage at f = 22 kHz
Auxiliary power supply VDC 12 to 95 VDC
(up to 6 VA inc. 5 V/2 x 200 mA for encoder)
Amplitude sinusoidal/DC
A 1.0 2.5 5 10 15 20
continuous current
Sinusoidal continuous RMS
A 0.7 1.8 3.5 7 10.6 14.1
current limit (Ic)
Peak current limit A 2 x Ic
Weight g (oz) 55 g (1.94 oz)
Dimensions mm
(in)
(55 x 59 x 15 mm or 2.17” x 2.32” x 0.6”)
49.4 cc (3.02 in3) package
Digital in/Digital out/Analog in 6/2/1
Mounting method PCB mount
Table 1: Technical Data
Note on current ratings: The current ratings of the Gold Bell are given in units of DC
amperes (ratings that are used for trapezoidal commutation or DC motors). The RMS
(sinusoidal commutation) value is the DC value divided by 1.41.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Information
3.1.1. Auxiliary Supply
Feature Details
Auxiliary power supply Isolated DC source only
Auxiliary supply input voltage 12 V to 95 V
Auxiliary supply input power ≤4 VA without external loading
≤6 VA with full external loading
22
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Chapter 4: Installation
Gold Bell Installation Guide
The Gold Bell must be installed in a suitable environment and properly connected to its voltage
supplies and the motor.
4.1. Site Requirements
You can guarantee the safe operation of the Gold Bell by ensuring that it is installed in an
appropriate environment.
Feature Value
23
Ambient operating temperature
Maximum non-condensing humidity 90%
Operating area atmosphere No flammable gases or vapors permitted in area
Models for extended environmental conditions are available.
Caution:
The Gold Bell dissipates its heat by convection. The maximum ambient
operating temperature of 40 °C (104 °F) must not be exceeded.
0 °C to 40 °C (32 °F to 104 °F)
4.2. Unpacking the Drive Components
Before you begin working with the Gold Bell, verify that you have all of its components, as
follows:
• The Gold Bell servo drive
• The Elmo Application Studio (EAS) software and software manual
The Gold Bell is shipped in a cardboard box with Styrofoam protection.
To unpack the Gold Bell:
1. Carefully remove the servo drive from the box and the Styrofoam.
2. Check the drive to ensure that there is no visible damage to the instrument. If any damage
has occurred, report it immediately to the carrier that delivered your drive.
3. To ensure that the Gold Bell you have unpacked is the appropriate type for your
requirements, locate the part number sticker on the side of the Gold Bell. It looks like this:
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4. Verify that the Gold Bell type is the one that you ordered, and ensure that the voltage
meets your specific requirements.
The part number at the top gives the type designation as follows:
24
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.3. Connectors
The Gold Bell has nine connectors.
4.3.1. Connector Types
Port Pins Type Function
25
J2 2x24 1.27 mm pitch
0.41 mm sq
Feedbacks, Digital Halls, Analog Inputs,
Communications
J1 2x12 I/O, LEDs, STO
M4 1x2 2 mm pitch
M3 1x2 Motor power output 3
0.51 mm sq
Motor power output 4
M2 1x2 Motor power output 2
M1 1x2 Motor power output 1
PE 1x2 Protective earth
PR 1x2 Power input return
VP+ 1x2 Positive power input
VL+ 1x1 Auxiliary power input
Connector Location
Table 2: Connector Types
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.3.2. Pinouts
The pinouts in this section describe the function of each pin in the Gold Bell connectors that are
listed in Table 2.
4.3.2.1. Motor Power
For full details see Section 4.7.1.
Pin Function Cable
Brushless Motor Brushed DC Motor Stepper Motor
PE Protective Earth Motor Motor Motor
M1 Motor phase Motor No Connection Motor
M2 Motor phase Motor Motor Motor
M3 Motor phase Motor Motor Motor
M4 Motor phase No Connection No Connection Motor
26
Pin Positions
Table 3: Motor Connector
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.3.2.2. Main Power
For full details see Section 4.7.2.
Pin Function Cable Pin Positions
VP+ Pos. Power input Power
PR Power return Power
PE Protective earth Power
Connector Type: 2 mm pitch 0.51 mm sq
27
Table 4: Connector for Main Power
4.3.2.3. Auxiliary Power Connector
For full details see Section 4.7.3.
Pin Function Pin Positions
VL+ Auxiliary Supply Input
PR Auxiliary Supply Return
Connector Type: 2 mm pitch 0.51 mm sq
Table 5: Auxiliary Supply Pins
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Feedback A/B/C, Digital Halls – see
Gold Bell Installation Guide Installation
4.3.2.4. Connector J2
Section 4.9.
Analog Inputs – see Section 4.9.4.
RS-232, EtherCAT, USB – see Section 4.11.
Connector Type: 1.27 mm pitch 0.41 mm
sq
Note regarding the EtherCAT and CAN communication options:
28
The J2 Connector exports all supported communication links. However, note that CAN and
EtherCAT are not available in the same version of the Gold Bell and are thus not operational
simultaneously. See the part number diagram in Section 4.2 above for the different Gold Bell
configurations.
Pin (J2) Signal Function
1 PortA_ENC_A+ /ABS_CLK+ Port A- channel A/ Absolute encoder
2 PortC_ENCO_A- Port C- channel A complement output
3 PortA_ENC_A-/ABS_CLK- Port A- channel A complement /
4 PortC_ENCO_A+ Port C- channel A output
5 PortA_ENC_B+/ABS_DATA+ Port A - channel B/ Absolute encoder
6 PortC_ENCO_B- Port C - channel B complement output
7 PortA_ENC_B-/ABS_DATA- Port A - channel B complement /
clock+
Absolute encoder clock-
Data+
Absolute encoder Data-
8 PortCENCO_B+ Port C - channel B output
9 PortA_ENC_INDEX+ Port A – index
10 PortC_ENCO_INDEX- Port C - index complement output
11 PortA_ENC_INDEX- Port A - index complement
12 PortC_ENCO_INDEX+ Port C - index output
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
Pin (J2) Signal Function
13 PortB_ENC_A+/SIN+ Port B - channel A
14 HC Hall sensor C input
15 PortB_ENC_A-/SIN- Port B - channel A complement
16 HB Hall sensor B input
17 PortB_ENC_B+/COS+ Port B - channel B
18 HA Hall sensor A input
19 PortB_ENC_B-/COS- Port B - channel B complement
20 ANARET Analog return
21 PortB_ENC_INDEX+/ANALOG_I+ Port B – index
RESOLVER_OUT+ Vref
22 ANALOG1+ Analog input 1
29
23 PortB_ENC_INDEX-/ANALOG_I- Port B – index complement
RESOLVER_OUT- Vref complement
24 ANALOG1- Analog input 1 complement
25 COMRET Common return
26 +3.3V 3.3 V supply voltage for EtherCAT LEDs
Note: The pin connector should only
be used for the 3.3V EtherCAT LED and
EtherCAT RJ-45.
27 PHY_IN_RX+ EtherCAT In receive
28 EtherCAT: PHY_OUT_RX+ EtherCAT Out receive
CAN: Reserved Reserved
29 PHY_IN_RX- EtherCAT In receive complement
30 PHY_OUT_RX- EtherCAT Out receive complement
31 COMRET Common return
32 COMRET Common return
33 PHY_IN_TX+ EtherCAT In transmit
34 EtherCAT: PHY_OUT_TX+ EtherCAT Out transmit complement
CAN: Reserved Reserved
35 PHY_IN_TX- EtherCAT In transmit complement
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
Pin (J2) Signal Function
36 EtherCAT: PHY_OUT_TX- EtherCAT Out transmit complement
CAN: Reserved Reserved
37 PHY_IN_LINK_ACT EtherCAT In active LED
38 EtherCAT: PHY_OUT_LINK_ACT EtherCAT Out active LED
CAN: CAN_L CAN_L BUS Line(dominant low)
39 PHY_IN_SPEED EtherCAT In Speed LED
40 EtherCAT: PHY_OUT_SPEED EtherCAT Out Speed LED
CAN: CAN_H CAN_H BUS Line(dominant high)
41 USBD- USB data complement
42 USBD+ USB data
43 COMRET Common return
30
44 USB_VBUS USB VBUS 5V
45 RS232_RX RS232 receive
46 COMRET Common return
47 +5VE Encoder +5 V supply
48 RS232_TX RS232 transmit
Table 6: Connector J2 – Feedback and Analog Input
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.3.2.5. Connector J1
31
I/O, LEDs, STO (safety)
For full details on user I/Os, see
Section 4.10.
For full details on STO, see Section
Connector Type: 1.27 mm pitch 0.41 mm sq
Pin (J1) Signal Function
1 Reserved Reserved
2 Reserved Reserved
3 INRET1_6 Programmable digital inputs 1–6 return
4 IN1 Programmable digital input 1
5 IN2 Programmable digital input 2
4.8.
6 IN3 Programmable digital input 3
7 IN4 Programmable digital input 4
8 IN5 Programmable digital input 5
9 IN6 Programmable digital input 6
10 STO_RET Safety signal return
11 STO2 Safety 2 input
12 STO1 Safety 1 input
13 LED_ETHERCAT ERR LED Status EtherCAT ERR
14 LED_ETHERCAT RUN LED Status EtherCAT RUN
15 OUT2 Programmable output 2
16 OUT1 Programmable output 1
17 OUTRET2 OUT 2 return
18 OUTRET1 OUT 1 return
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
Pin (J1) Signal Function
19 LED2 Bi-color indication output 2 (Cathode)
20 LED1 Bi-color indication output 1 (Anode)
21 OUT4 Programmable output 4 not isolated
(3.3V TTL level)
22 OUT3 Programmable output 3 not isolated
(3.3V TTL level)
23 COMRET Common return
24 Reserved Reserved
Table 7: Connector J1 – I/O, LEDs
32
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.4. Mounting the Gold Bell
The Gold Bell was designed for mounting on a printed circuit board (PCB) via 1.27 mm pitch
0.41 mm square pins and 2 mm pitch 0.51 mm square pins. When integrating the Gold Bell into
a device, be sure to leave about 1 cm (0.4") outward from the heat sink to enable free air
convection around the drive. We recommend that the Gold Bell be soldered directly to the
board. Alternatively, though this is not recommended, the Gold Bell can be attached to socket
connectors mounted on the PCB. If the PCB is enclosed in a metal chassis, we recommend that
the Gold Bell be screw-mounted to it as well to help with heat dissipation. The Gold Bell has
screw-mount holes on each corner of the heat sink for this purpose – see below.
33
All measurements are in mm.
Figure 2: Gold Bell Dimensions
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.5. Integrating the Gold Bell on a PCB
The Gold Bell is designed to be mounted on a PCB, either by soldering its pins directly to the
PCB or by using suitable socket connectors. In both cases the following rules apply:
4.5.1. Traces
1. The size of the traces on the PCB (thickness and width) is determined by the current
carrying capacity required by the application.
•The rated continuous current limit (Ic) of the Gold Bell is the current used for sizing
the motor traces (M1, M2, M3, M4 and PE) and power traces (VP+, PR and PE).
•For control, feedbacks and Input/Output conductors, the actual current is very small
but a greater thickness and width of the conductors will contribute to better
performance and less interference.
2. The traces should be as short as possible to minimize EMI and also to minimize the heat
generated by the conductors.
3. The spacing between the high voltage conductors (VP+, PR, M1, M2, M3, M4, VL) must be
at least:
34
• Surface layer:1.5 mm
• Internal layer: 0.10 mm
Complying with the rules above will help satisfy UL safety standards, MIL-STD-275 and the IPCD-275 standard for non-coated conductors, operating at voltages lower than 200 VDC.
4.5.2. Grounds and Returns
The returns in each functional block are listed below:
Functional Block Return Pin
Power PR (Power Return)
Internal Switch Mode P. S. PR (Power Return)
Analog input return ANLRET (J2/20)
Common return COMRET (J2/25,31,32,43,46; J1/23)
STO safety signal return STO_RET (J1/10)
Input Return IN_RET (J1/3)
Table 8: Grounds and Returns
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
The returns above are all shorted within the Gold Bell in a topology that results in optimum
performance.
Caution:
Follow these instructions to ensure safe and proper implementation. Failure to
meet any of the below-mentioned requirements can result in drive, controller or
host failure.
1. When wiring the traces of the above functions, on the Integration Board, the Returns of
each function must be wired separately to its designated terminal on the Gold Bell. DO NOT USE A COMMON GROUND PLANE. Shorting the commons on the Integration Board
may cause performance degradation (ground loops, etc.).
2. Inputs: The six digital inputs are optically isolated from the other parts of the Gold Bell. All
six inputs share one return line, INRET. To retain isolation, the Input Return pin and all
other conductors on the input circuit must be laid out separately.
3. STO: The two digital STO inputs are optically isolated from the other parts of the Gold Bell.
All six inputs share one return line, INRET. To retain isolation, the Input Return pin and all
other conductors on the input circuit must be laid out separately
35
4. Outputs: The two digital outputs are optically isolated from the other parts of the Gold
Bell. To retain isolation, all the output circuit conductors must be laid out separately.
5. Return Traces: The return traces should be as large as possible, but without shorting each
other, and with minimal cross-overs.
6. Main Power Supply and Motor Traces: The power traces must be kept as far away as
possible from the feedback, control and communication traces.
7. PE Terminal: The PE (Protective Earth) terminal is connected directly to the Gold Bell’s
heat-sink which serves as an EMI common plane. The PE terminal should be connected to
the system's Protective Earth. Any other metallic parts (such as the chassis) of the assembly
should be connected to the Protective Earth as well.
8. Under normal operating conditions, the PE trace carries no current. The only time these
traces carry current is under abnormal conditions (such as when the device has become a
potential shock or fire hazard while conducting external EMI interferences directly to
ground). When connected properly the PE trace prevents these hazards from affecting the
drive.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.6. The Gold Bell Connection Diagram
36
Figure 3: The Gold Bell Connection Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.7. Main Power, Auxiliary Power and Motor Power
The Gold Bell receives power from main and auxiliary supplies and delivers power to the motor
that it controls.
4.7.1. Motor Power
Note: When connecting several drives to several similar motors, all should be wired in an
identical manner. This will enable the same settings to run on all drives.
Pin Function Cable
Brushless Motor Brushed DC Motor Stepper Motor
PE Protective Earth Motor Motor Motor
M1 Motor phase Motor No Connection Motor
M2 Motor phase Motor Motor Motor
M3 Motor phase Motor Motor Motor
37
M4 Motor phase No Connection No Connection Motor
Pin Positions
Table 9: Motor Connector
Connect the M1, M2, M3, M4 and PE pins on the Gold Bell in the manner described in Section
4.3.2.1. The phase connection is arbitrary as the Elmo Application Software (EAS) will
automatically establish the proper commutation during setup. However, if you plan to copy the
setup to other drives, then the phase order on all the drives must be the same.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
38
Figure 4: Brushless Motor Power Connection Diagram
Figure 5: DC Brushed Motor Power Connection Diagram
Figure 6: Stepper Motor Power Connection Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.7.2. Main Power
Pin Function Cable Pin Positions
VP+ Pos. Power input Power
PR Power return Power
PE Protective earth Power
39
Table 10: Connector for Main Power
Connect the VP+, PR and PE pins on the Gold Bell in the manner described in Section 4.3.2.1.
Note: The source of the Main Power Supply must be isolated.
Figure 7: Main Power Supply Connection Diagram (no Auxiliary Supply)
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.7.3. Auxiliary Power Supply (Optional)
Note: The source of the Auxiliary Supply must be isolated.
Connect the VL+ and PR pins on the Gold Bell in the manner described in Section 4.3.2.1.
Pin Function Pin Positions
VL+ Auxiliary Supply Input
PR Auxiliary Supply Return
40
Table 11: Auxiliary Supply Pins
Caution:
Power from the Gold Bell to the motor must come from the Main Supply and
not from the Auxiliary Supply.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.7.4. Single Supply
A single isolated DC power supply can provide power for both the main power and the Auxiliary
(Drive Logic) Supply. The drawing below shows how a single supply is connected.
41
Figure 8: Single Supply for both the Main Power Supply and the Auxiliary Supply
4.7.5. Separate Auxiliary (Backup) Supply
Power to the Auxiliary Supply can be provided by a separate Auxiliary Supply.
Figure 9: Separate Auxiliary Supply Connection Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.7.6. Shared Supply
A Main DC Power Supply can be designed to supply power to the drive’s logic as well as to the
Main Power (see Figure 8 and the upper portion of Figure 10). If backup functionality is
required for continuous operation of the drive’s logic in the event of a main power-out, a
backup supply can be connected by implementing “diode coupling” (see the Aux. Backup
Supply in Figure 10).
42
Figure 10: Shared Supply Connection Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.8. STO (Safe Torque Off) Inputs
Activation of Safe Torque Off causes the drive to stop providing power that can cause rotation
(or motion in the case of a linear motor) to the motor.
This function may be used to prevent unexpected motor rotation (of brushless DC motors)
without disconnecting the drive from the power supply.
The motor is active only as long as 5 V is provided to both STO1 and STO2. Whenever any input
voltage is no longer present, power is not provided to the motor and the motor shaft continues
to rotate to an uncontrolled stop.
The STO inputs are latched which means that the motor can be re-enabled by a software
command only.
In circumstances where external influences (for example, falling of suspended loads) are
present, additional measures such as mechanical brakes are necessary to prevent any hazard.
This function corresponds to an uncontrolled stop in accordance with Stop Category 0 of IEC
60204-1.
43
Note: This function does not protect against electrical shock, and additional measures to
turn the power off are necessary.
The following table defines the behavior of the motor as a function of the state of the STO
inputs:
Signal – STO1 Signal – STO2 Function
Not Active Not Active Motor is disabled
Not Active Active Motor is disabled
Active Not Active Motor is disabled
Active Active Motor can be enabled
Table 12: Motor Behavior According to Safety Inputs
Note : In the Gold Bell, STO1 also latches a software disable condition.
Pin (J1) Signal Function
12 STO1 Safety 1 input
11 STO2 Safety 2 input
10 STO_RET STO return
Table 13: STO Inputs Pin Assignments
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
Figure 11: STO Input Functionality – Schematic Drawing
The figure below is for the TTL level.
44
Figure 12: STO Input Connection – TTL Level
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
The figure below is for PLC.
45
Figure 13: STO Input Connection – PLC
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.9. Feedback
Figure 14: Feedback Ports on J2
The Gold Bell has two configurable motion sensor input ports, namely, Port A and Port B,
together with the emulated buffered output Port C. Motion sensors from the motor are
controlled from other sources and can be connected to any of the available inputs on Port A or
Port B.
46
The software configuration designates a role to each input, e.g., the incremental encoder on
port B is the controlled motor position feedback, the Hall sensors on port A are commutation
feedback, and the incremental encoder on port A is follower input.
For more information, about sensors and their use refer to the Gold Line Software Manual.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.9.1. Port A (J2)
Port A supports the following sensor inputs:
• Digital Hall sensors
• Incremental encoder or absolute serial encoder, depending on the specific model
Differential pulse-width modulation (PWM) signal input can be connected to port A in the
models that support input from an incremental encoder. The PWM signal can be connected to
the applicable pair of matching + and – encoder channels and is configurable by software.
Differential pulse and direction signal inputs can be connected to port A in the models that
support input from an incremental encoder. The signals can be connected to the applicable pair
of matching + and – encoder channels and are configurable by software.
Figure 17: Absolute Serial Encoder – Recommended Connection Diagram for Sensors
Supporting Data Line Only (NRZ types, e.g., Panasonic / Mitutoyo / etc.)
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.9.1.3. Hall Sensors
50
Figure 18: Hall Sensors Connection Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.9.2. Port B (J2)
Port B supports any of the following sensors:
• Incremental encoder, interpolated analog encoder or analog Hall sensors
Or
• Resolver (separate hardware option)
Differential PWM signal input can be connected to port B in the models that support input from
an incremental encoder. The PWM signal can be connected to the applicable pair of matching +
and – encoder channels and is configurable by software.
Differential pulse and direction signal inputs can be connected to port B in the models that
support input from an incremental encoder. The signals can be connected to the applicable pair
of matching + and – encoder channels and are configurable by software.
51
Port B - Incremental or
Port B - Resolver
Interpolated Analog Encoder
Pin (J2) Signal Function Signal Function
47 +5V Encoder +5V
NC
supply
25 SUPRET Supply return SUPRET Supply return
13 PortB_ENC_A+/
SIN+
15 PortB_ENC_A-/
Channel A+ /
SIN+ Sine+
Sine+
Channel A- / Sine- SIN- Sine-
SIN-
17 PortB_ENC_B+/
COS+
19 PortB_ENC_B-/
COS-
21 PortB_ENC_INDEX
+/ Analog_Index+
23 PortB_ENC_INDEX-
/ Analog_Index-
Channel B+ /
Cosine+
Channel B - /
Cosine -
Index +/
Analog_Index+
Index -/
Analog_Index-
COS+ Cosine+
COS- Cosine-
RESOLVER_OUT+
Vref f=1/TS,
50 mA Max.
RESOLVER_OUT-
Vref complement
f= 1/TS, 50 mA
Maximum
Table 15: Port B Pin Assignments
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.9.2.1. Incremental Encoder
52
Figure 19: Port B Incremental Encoder Input – Recommended Connection Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.9.2.2. Interpolated Analog Encoder
53
Figure 20: Port B - Interpolated Analog Encoder Connection Diagram
4.9.2.3. Resolver
Figure 21: Port B – Resolver Connection Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.9.3. Port C – Emulated Encoder Output (J2)
Port C provides emulated encoder output derived from port A or port B feedback inputs, or
from internal variables. The output options are:
• Port A/B daisy chain (1:1) for incremental encoder
• Encoder emulation: Emulate any input sensor, digital or analog, or use to emulate an
internal variable such as virtual profiler.
• PWM output: any pair of outputs that is used as an encoder channel (e.g., channel A+ and
channel A-) can be configured by software to become PWM output.
• Pulse & Direction output: The output pins that are assigned as channel A and channel B
when used as encoder out can be configured by software to become pulse and direction
outputs, respectively.
This port is used when:
• The Gold Bell is used as a current amplifier to provide position data to the position
controller.
54
• The Gold Bell is used in velocity mode to provide position data to the position controller.
• The Gold Bell is used as a master in follower or ECAM mode.
An analog user input can be configured by software to be used as either tachometer velocity
sensor input or potentiometer position feedback. For connection diagrams refer to
Section 4.10.3.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.10. User I/Os
The Gold Bell has six programmable digital inputs (J1), four digital outputs (J1) and one analog
input (J2).
4.10.1. Digital Inputs (J1)
Each of the pins below can function as an independent input. The inputs conform to the TTL
level.
Pin (J1) Signal Function
3 INRET1-6 Programmable inputs 1 - 6 return
4 IN1 Programmable digital input 1
(event capture, home, general purpose, RLS, FLS, INH, PWM & dir
input, pulse & dir input)
5 IN2 Programmable digital input 2
(event capture, home, general purpose, RLS, FLS, INH, PWM & dir
input, pulse & dir input)
56
6 IN3 Programmable digital input 3
(event capture, home, general purpose, RLS, FLS, INH, PWM & dir
input, pulse & dir input)
7 IN4 Programmable digital input 4
(event capture, home, general purpose, RLS, FLS, INH, PWM & dir
input, pulse & dir input)
8 IN5 Programmable digital input 5
(event capture, home, general purpose, RLS, FLS, INH, PWM & dir
input, pulse & dir input)
9 IN6 Programmable digital input 6
(event capture, home, general purpose, RLS, FLS, INH, PWM & dir
input, pulse & dir input)
Table 17: Digital Input Pin Assignments
See Figure 23 for the TTL connection.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
57
Figure 23: Digital Input Connection Diagram – TTL Level
See the figure below for the PLC connection.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
58
Figure 24: Digital Input Connection Diagram – PLC
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.10.2. Digital Outputs (J1)
The outputs conform to the TTL level.
Pin (J1) Signal Function
16 OUT1 High speed programmable digital output 1, output
compare
15 OUT2 High speed programmable digital output 2, output
compare
18 OUTRET1 OUT 1 Return
17 OUTRET2 OUT 2 Return
Table 18: Digital Output Pin Assignment
59
Figure 25: Digital Output Connection Diagram – TTL Connection
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.10.3. Analog Input
Pin (J2) Signal Function
22 ANALOG1+ Analog input 1+
24 ANALOG1- Analog input 1-
20 ANARET Analog return
Table 19: Analog Input Pin Assignment
60
Figure 26: Analog Input with Single-Ended Source
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.11. Communications
The communication interface may differ according to the user’s hardware. The Gold Bell can
communicate using the following options:
Standard EtherCAT
G-BELXXX/YYYSXG-BELXXX/YYYEX
CAN EtherCAT
USB 2.0 USB 2.0
Ethernet RS-232 (TTL Logic Level)
RS-232 (TTL Logic Level)
Table 20: Gold Bell Communication Options
For ease of setup and diagnostics of CAN communication, RS-232 and CAN can be used
simultaneously.
61
Note:When the EtherCAT is connected, and FoE in operation, the USB cable connection
must be disconnected.
4.11.1. RS-232 Communication (J2)
RS-232 communication requires a cable connected from the Gold Bell to a serial interface on
the PC. The interface is selected and set up in the Elmo Application Studio (EAS) software.
RS-232 communication of the Gold Bell is at the TTL logic level. It requires an RS-232 Line
Driver/Receiver in order to translate the TTL logic level to the standard RS-232 voltage level.
Notes for connecting the RS-232 communication cable:
• Connect the shield to the ground of the host (PC). Usually, this connection is soldered
internally inside the connector at the PC end. You can use the drain wire to facilitate
connection.
• The RS-232 communication port is non-isolated.
• Ensure that the shield of the cable is connected to the shield of the connector used for
RS-232 communications. The drain wire can be used to facilitate the connection.
Pin (J2) Signal Function
45 RS232_Rx RS-232 receive (TTL logic level)
48 RS232_Tx RS-232 transmit (TTL logic level)
46 RS232_COMRET Communication return
Table 21: RS-232 Pin Assignments
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
Figure 27 describes the RS-232 connection diagram:
Figure 27: RS-232 Connection Diagram
Note that Elmo does not recommend a specific manufacturer. The following is an example of
an RS-232 Line Driver/Receiver. The RS-232 Line Driver/Receiver operates with 3.3 V to 5 V VCC
Supply.
62
Figure 28: RS-232 – Translator Block Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.11.2. CAN Communication (J2)
Note that CAN functionality is not available if you have the EtherCAT version.
In order to benefit from CAN communication, the user must have an understanding of the basic
programming and timing issues of a CAN network.
Notes for connecting the CAN communication cable:
• Connect the shield to the ground of the host (PC). Usually, this connection is soldered
internally inside the connector at the PC end. You can use the drain wire to facilitate
connection.
• Ensure that the shield of the cable is connected to the shield of the connector used for
communications. The drain wire can be used to facilitate the connection.
• Make sure to have a 120-Ohm resistor termination at each of the two ends of the network
cable.
• The Gold Bell’s CAN port is non-isolated.
63
Pin (J2) Signal Function
32 CAN_COMRET CAN Communication Return
38 CAN_L CAN_L bus line (dominant low)
40 CAN_H CAN_H bus line (dominant high)
Table 22: CAN Pin Assignments
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
64
Figure 29: CAN Network Diagram
Caution: When installing CAN communication, ensure that each servo drive
is allocated a unique ID. Otherwise, the CAN network may “hang”.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.11.3. USB 2.0 Communication (J2)
The USB network consists of a Host controller and multiple devices. The Gold Bell is a USB
device.
Notes for connecting the USB communication cable:
• Connect the shield to the ground of the host (PC). Usually, this connection is soldered
internally inside the connector at the PC end. You can use the drain wire to facilitate
connection.
• Ensure that the shield of the cable is connected to the shield of the connector used for
communications. The drain wire can be used to facilitate the connection.
Pin (J2) Signal Function
41 USBD- USB _N line
42 USBD+ USB _P line
43 USB COMRET USB Communication return
65
44 USB VBUS USB VBUS 5 V
Table 23: USB 2.0 Pin Assignments
Figure 30: USB Network Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.11.4. EtherCAT Communication (J2)
To use EtherCAT and Ethernet communication with the Gold Bell, it is required to use an
isolation transformer. The most common solution is to use RJ-45 connectors that include
transformer isolation.
This section describes how to connect the Gold Bell’s EtherCAT interface using the above
mentioned connectors.
For other available options, please see Section 4.11.6.
Notes for EtherCAT Communication:
• The EtherCAT IN port can be configured as an Ethernet port for TCP/IP – see the EtherCAT
Manual.
• It is recommended to use CAT5e (or higher) cable. Category 5e cable is a high signal
integrity cable with four twisted pairs.
66
Pin (J/2) Signal Function
26 +3.3V 3.3 V for EtherCAT LEDs
27 PHY_IN_RX+ EtherCAT IN RX+ Line
29 PHY_IN_RX- EtherCAT IN RX- Line
31 PHY_IN_COMRET EtherCAT IN Communication Return
33 PHY_IN_TX+ EtherCAT IN TX+ Line
35 PHY_IN_TX- EtherCAT IN TX- Line
37 PHY_IN_LINK_ACT Indicates EtherCAT LINK
39 PHY_IN_SPEED Indicates EtherCAT Speed
28 PHY_OUT_RX+ EtherCAT OUT RX+ Line
30 PHY_OUT_RX- EtherCAT OUT RX- Line
32 PHY_OUT_ COMRET EtherCAT OUT Communication return
34 PHY_OUT_TX+ EtherCAT OUT TX+ Line
36 PHY_OUT_TX- EtherCAT OUT TX- Line
38 PHY_OUT_LINK_ACT Indicates EtherCAT LINK
40 PHY_OUT_SPEED Indicates EtherCAT Speed
Table 24: EtherCAT - Pin Assignments
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
67
Figure 31: EtherCAT Connection Schematic Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
The diagram above ignores line interface for simplicity.
When connecting several EtherCAT devices in a network, the EtherCAT master must always be
the first device in the network. The output of each device is connected to the input of the next
device. The output of the last device may remain disconnected. If redundancy is required, the
output of the last device should be connected to the input of the EtherCAT master.
Figure 32: EtherCAT Network with no Redundancy
68
Figure 33: EtherCAT Network with Redundancy
4.11.5. Ethernet Communication (J2)
To use EtherCAT and Ethernet communication with the Gold Bell, it is required to use an
isolation transformer. The most common solution is to use RJ-45 connectors that include
transformer isolation.
This section describes how to connect the Gold Bell Ethernet interface using the above
mentioned connectors.
For other available options, please see Section 4.11.6.
Notes for Ethernet Communication:
• The EtherCAT IN port can be configured as an Ethernet port for TCP/IP – see the EtherCAT
Manual.
• It is recommended to use CAT5e (or higher) cable. Category 5e cable is a high signal
integrity cable with four twisted pairs.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
Pin (J2) Signal Function
26 +3.3V 3.3 V supply voltage for LEDs
27 PHY_IN_RX+ Ethernet In receive
29 PHY_IN_RX- Ethernet In receive complement
31 PHY_IN_COMRET Ethernet In Communication return
33 PHY_IN_TX+ Ethernet In transmit
35 PHY_IN_TX- Ethernet In transmit complement
37 PHY_IN_LINK_ACT Ethernet In Link/Active LED
39 PHY_IN_SPEED Ethernet In Speed LED
Table 25: Ethernet - Pin Assignments
69
Figure 34: Ethernet Network Schematic Diagram
The diagram above ignores line interface for simplicity.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideInstallation
4.11.6. EtherCAT/Ethernet Line Interface
Ethernet transceivers require either isolation transformers or capacitor coupling for proper
functioning. The Gold Bell unit does not include such isolation, therefore you must take this
into consideration when designing the integration board.
In Sections 4.11.4 and 4.11.5, a schematic connection with a standard RJ-45 connector that
includes transformer isolation is described.
Other recommended connection options are:
• Gold Bell to an RJ-45 connector without an integrated magnetic isolation (e.g., M12
connectors). An isolation transformer is required.
• Connecting two EtherCAT ports on the same board can be done using capacitive coupling
or transformer coupling.
For more detailed explanations, including layout recommendations and component selection
guidelines contact Elmo’s technical support.
4.12. Powering Up
70
After the Gold Bell is connected to its device, it is ready to be powered up.
Caution:
Before applying power, ensure that the DC supply is within the specified range
and that the proper plus-minus connections are in order.
4.13. Initializing the System
After the Gold Bell has been connected and mounted, the system must be set up and
initialized. This is accomplished using the Composer, Elmo’s Windows-based software
application. Install the application and then perform setup and initialization according to the
directions in the ComposerSoftware Manual.
4.14. Heat Dissipation
The best way to dissipate heat from the Gold Bell is to mount it so that its heatsink faces up.
For best results leave approximately 10 mm of space between the Gold Bell's heatsink and any
other assembly.
4.14.1. Thermal Data
• Heat dissipationcapability (θ): Approximately 10 °C/W.
• Thermal time constant: Approximately 240 seconds (thermal time constant means that the
Bell will reach two-thirds of its final temperature after 4 minutes.)
• Shut-off temperature: 86 °C – 88 °C (measured on the heatsink).
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Whistle100 Series Power Dissipation
0.0
1.0
2.0
3.0
4.0
5.0
6.0
0
0.5
1
1.5
2
2.533.544.5
5
Peak Current (A)
Power Dissipation (W)
85VDC
70VDC
50VDC
Standard 40 °C Ambient Temp.
Heatsink
Heatsink
Gold Bell
Gold Bell Installation Guide Installation
4.14.2. Heat Dissipation Data
Heat dissipation is shown graphically below:
71
Required
not Required
4.14.3.How to Use the Charts
The charts above are based upon theoretical worst-case conditions. Actual test results show
30% – 50% better power dissipation.
To determine if your application needs a heatsink:
1. Allow the maximum heatsink temperature to be 80 °C or less.
2. Determine the ambient operating temperature of the Gold Bell.
3. Calculate the allowable temperature increase as follows:
For an ambient temperature of 40 °C, ΔT= 80 °C – 40 °C = 40 °C.
4. Use the chart to find the actual dissipation power of the drive. Follow the voltage curve to
the desired output current and then find the dissipated power.
5. If the dissipated power is below 4 W, the Gold Bell will not need additional cooling.
Note: The chart above shows that no heatsink is needed when the heatsink temperature is
80°C, the ambient temperature is 40 °C and the heat dissipated is 4 W.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Chapter 5: Technical Specifications
Gold Bell Installation Guide
This chapter provides detailed technical information regarding the Gold Bell. This includes its
dimensions, power ratings, the environmental conditions under which it can be used, the
standards to which it complies and other specifications.
5.1. Dimensions
72
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.2. Environmental Conditions
Feature Details
Ambient operating temperature 0 °C to 40 °C(32 °F to 104 °F)
Storage temperature -20 °C to +85 °C ( -4 °F to +185 °F)
Maximum non-condensing humidity 90%
Maximum Operating Altitude 2,000 m (6562 feet)
Protection level IP64
5.3. Control Specifications
5.3.1. Current Loop
Feature Details
73
Controller type Vector, digital
Compensation for bus voltage
“On-the-fly” automatic gain scheduling
variations
Motor types
• Stepper motors
• AC brushless (sinusoidal)
• DC brushless (trapezoidal)
• DC brush
• Linear motors
• “Voice” coils
Current control
• Fully digital
• Sinusoidal with vector control
• Programmable PI control filter based on a
pair of PI controls of AC current signals and
constant power at high speed
Current loop bandwidth > 4 kHz closed loop
Current sampling time
Programmable 40 to 120 µsec
Current sampling rate Up to 25 kHz; default 20 kHz
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.3.2. Velocity Loop
Feature Details
Controller type PI + Four advanced filters + Two advanced gain
scheduling filters
74
Velocity control
• Fully digital
• Programmable PI and feed forward control
filters
• On-the-fly gain scheduling according to either
speed or position command or feedback
• Automatic, quick, advanced or expert tuning
Velocity and position feedback options
• Incremental Encoder
• Digital Halls
• Interpolated Analog (sin/cos) Encoder (optional)
• Resolver (optional)
• Absolute serial encoder
Note: With all feedback options, 1/T with
automatic mode switching is activated (gap,
frequency and derivative).
Velocity loop bandwidth < 500 Hz
Velocity sampling time
80 to 240 µsec (2x current loop sample time)
Velocity sampling rate Up to 12.5 kHz; default 10 kHz
Velocity command options Internally calculated by either jogging or step
Note: All software-calculated profiles support
on-the-fly changes.
5.3.3. Position Loop
Feature Details
Controller type “1-2-2” PIP + three advanced filters + one
advanced gain scheduling filter
Position command options
Position loop bandwidth < 200 Hz
Position sampling time
Position sampling rate Up to 12.5 kHz; default 10 kHz
• Software
• Pulse and Direction
80 to 240 µsec (2x current loop sample time)
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.4. Feedbacks
5.4.1. Feedback Supply Voltage
The Gold Bell has two feedback ports (Main and Auxiliary). The Gold Bell supplies voltage only
to the main feedback device and to the auxiliary feedback device if needed.
Feature Details
Encoder supply voltage 5 V ± 5% @ 2 x 200 mA (maximum)
5.4.2. Feedback Options
The Gold Bell can receive and process feedback input from diverse types of devices.
5.4.2.1. Incremental Encoder Input
Feature Details
75
Encoder format
• A, B and Index
• Differential
• Quadrature
Interface RS-422
Input resistance
Differential: 120 Ω
Maximum incremental encoder frequency Maximum absolute: 75 Megacounts per
second (18 MHz on A/B)
Minimum quadrature input period (PIN) 53 nsec
Minimum quadrature input high/low period
26 nsec
(PHL)
Minimum quadrature phase period (PPH) 13 nsec
Maximum encoder input voltage range
Common mode: ± 7 V
Differential mode: ± 7 V
Figure 35: Main Feedback - Encoder Phase Diagram
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.4.2.2. Digital Halls
Feature Details
76
Hall inputs
• H
, HB, HC
A
• Single ended inputs
• Built in hysteresis of 1 V for noise
immunity
Input voltage Nominal operating range: 0 V < V
Maximum absolute: -1 V < V
High level input voltage: V
Low level input voltage: V
InLow
In_Hall
InHigh
In_Hall
< 15 V
> 2.5 V
< 1 V
Input current Sink current (when input pulled to the
common): 5 mA
Maximum frequency f
MAX
: 4 kHz
5.4.2.3. Interpolated Analog (Sine/Cosine) Encoder
Feature Details
Analog encoder format Sine and Cosine signals
Analog input signal level
• Offset voltage: 2.2 V to 2.8 V
< 5 V
• Differential, 1 V peak to peak
Input resistance
Maximum analog signal frequency f
Differential: 120 Ω
: 500 kHz
MAX
Interpolation multipliers Programmable: x4 to x8192
Maximum “counts” frequency 2 x 10
Automatic error correction
9
counts/sec
• Signal amplitudes mismatch
• Signal phase shift
• Signal offsets
Encoder outputs See Port C Encoder Outputs Specifications,
Section 5.4.3.
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.4.2.4. Resolver
Feature Details
77
Resolver format
• Sine/Cosine
• Differential
Input resistance
Differential 2.49 kΩ
Resolution Programmable: 10 to 15 bits
Maximum electrical frequency (RPS) 512 revolutions/sec
Resolver transfer ratio 0.5
Reference frequency 1/Ts (Ts = sample time in seconds)
Reference voltage Supplied by the Gold Bell
Reference current up to ±50 mA
Encoder outputs See Port C Encoder Output Specifications,
Section 5.4.3.
5.4.2.5. Absolute Serial Encoder
Feature Details
Encoder format
• NRZ (Panasonic, Tamagawa, Mitutoyo,
etc.)
• EnDAT 2.2
• BiSS/SSI
Interface
• RS-485
• Clock – Differential output line
• Data – Differential bidirectional line
Input Resistance
Differential 120 Ω
Transmission Rate Up to 2.5 MHz
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.4.3. Port C Feedback Output
Feature Details
78
Emulated output
• A, B, Index
• Differential
Interface RS-422
Output current capability Maximum output current: IOH (max) = 2 mA
> 3.0 V
OH
= 2 mA
OL
< 0.4 V
OL
Available as options
High level output voltage: V
Minimum output current: I
Low level output voltage: V
• Emulated encoder output of any sensor
on Port A or Port B
• Daisy chain Port A or Port B
• Emulated encoder output of internal
variables
• Emulated encoder outputs of the
tachometer
• Emulated encoder outputs of the
potentiometer
Maximum frequency f
: 8 MHz pulses/output
MAX
Edge separation between A & B Programmable number of clocks to allow
adequate noise filtering at remote receiver
of emulated encoder signals (default 2 MHz)
Index (marker) Length of pulse is one quadrature (one
quarter of an encoder cycle) and
synchronized to A&B
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.5. I/Os
The Gold Bell has:
• 6 Digital Inputs
• 2 Digital Outputs
• 1 Analog Input
5.5.1. Digital Input Interfaces – TTL Mode
Feature Details
Type of input Optically isolated
Input current for all inputs Iin = 3.8 mA @ Vin = 5 V
High-level input voltage 2.4 V < Vin < 15 V, 5 V typical
Low-level input voltage 0 V < Vin < 0.8 V
79
Minimum pulse width
Execution time (all inputs):
the time from application of voltage on
input until execution is complete
High-speed inputs – 1–6 minimum pulse
width, in high-speed mode
> 250 µsec
0 < T < 250 µsec
T > 5 µsec if the input functionality is set to
latch/capture (index/strobe).
Notes:
• Home mode is high-speed mode and can
be used for fast capture and precise
homing.
• Highest speed is achieved when turning
on optocouplers.
Capture with differential input
Port A, Port B Index
Figure 36: Digital Input Schematic
T > 0.1 µsec if the differential input functionality is set
to touch probe/capture (index/strobe).
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.5.2. Digital Output Interface – TTL Mode
Feature Details
80
Type of output
• Optically isolated
• Source/Sink
Supply output (VDD) 5 V to 15 V
Max. output current
I
(max) (V
out
= Low)
out
VOL at maximum output voltage (low level) V
10 mA
(on) ≤ 0.4 V
out
RL The external resistor RL must be selected to
limit the output current to no more than 10
mA.
Executable time
0 < T < 250 µsec
Figure 37: Digital Output Schematic
5.5.3. Analog Input
Feature Details
Maximum operating differential voltage ± 10 V
Maximum absolute differential input
voltage
Differential input resistance 3.74 kΩ
Analog input command resolution 14-bit
± 16 V
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.6. Safe Torque Off (STO)
The Gold Bell has two STO (Safe Torque Off) inputs.
5.6.1. STO Input Interfaces – TTL Mode
Feature Details
Type of input Optically isolated
Input current for all inputs Iin = 3.8 mA @ Vin = 5 V
High-level input voltage 2.4 V < Vin < 15 V, 5 V typical
Low-level input voltage 0 V < Vin < 0.8 V
Minimum pulse width >3 ms
81
Figure 38: STO Input Schematic
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.7. Communications
Specification Details
82
RS-232
CAN
EtherCAT
Signals:
• RxD , TxD , COMRET
• Full duplex, serial communication for
setup and control
• Baud Rate of 9,600 to 57,600 bit/sec
CAN bus Signals:
• CAN_H, CAN_L, CAN_RET
• Maximum Baud Rate of 1 Mbit/sec.
Version:
• DS 301 v4.01
Layer Setting Service and Protocol Support:
• DS 305
Device Profile (drive and motion control):
• DS 402
• 100base-T
• Baud Rate: 100 Mbit/sec
• CAT5 Cable
• CoE, FoE, EoE
Ethernet
• 100base-T
• Baud Rate: 100 Mbit/sec
• CAT5 Cable
• UDP, Telnet
USB
• USB 2.0 Device mode
5.8. Pulse-Width Modulation (PWM)
Feature Details
PWM resolution Minimum 10-bit
Default 12-bit
Maximum 14-bit
PWM switching frequency on the load 2/Ts (factory default 40 kHz on the motor)
www.elmomc.com
MAN-G-BELIG (Ve r. 1.004)
Gold Bell Installation GuideTechnical Specifications
5.9. Compliance with Standards
Specification Details
Quality Assurance
ISO 9001:2008 Quality Management
Design
Approved IEC/EN 61800-5-1, Safety Printed wiring for electronic equipment