Efd ValveMate 7000 Operating Manual

ValveMate
7000 Controller
Operating Manual
POWER
RUN
SETUP
Test
Clear
Purge
Run
Setup Program
Fast Slow
Time Set
Steady
Fast Slow
Time Set
STOP
Pressure
Time
®
A NORDSON COMPANY
VALVEMATE 7000
Electronic pdf files of EFD®manuals are also available at www.efd-inc.com/manuals.html
USA: 800-556-3484 or +1-401-434-1680 Europe: 0800 585733 or +44 (0) 1582 666334 Asia: +86 (21) 5854 2345 technical@efd-inc.com www.efd-inc.com
A NORDSON COMPANY
EFD ONE YEAR LIMITED WARRANTY
All components of the EFD ValveMate 7000 are warranted for one year from date of purchase to be free from defects in material and workmanship (but not against damage caused by misuse, abrasion, corrosion, negligence, accident, faulty installation or by dispensing material incompatible with equipment) when the equipment is installed and operated in accordance with factory recommen­dations and instructions. EFD will repair or replace free of charge any part of the equipment thus found to be defective, on authorized return of the part prepaid to our factory during the warranty period.
In no event shall any liability or obligation of EFD arising from this warranty exceed the purchase price of the equipment. This warranty is valid only when oil-free, clean, dry, filtered air is used.
EFD makes no warranty of merchantability or fitness for a particular purpose. In no event shall EFD be liable for incidental or consequential damages.
Contents
Warranty ....................................................inside cover
Introduction..................................................................2
Specifications ..............................................................3
Features and Controls ..............................................4-5
Indicator Lamps .......................................................... 6
Typical Setup................................................................7
Setup ......................................................................8-10
Installing the Valve ....................................................11
Schematic and Replacement Parts List ....................12
Troubleshooting..........................................................13
Input/Output Connection Instructions..................14-15
Connecting More than One 7000 ........................16-17
IMPORTANT: The primary
control of deposit size is the valve open time. The ValveMate 7000 provides easy access and “on the fly” adjustment of valve open time.
2 / Introduction
Introduction
The ValveMate 7000 is an EFD dispense valve controller, incorporating programmable dispense time, digital time and air pressure readout, microprocessor interface, small size and universal mounting.
Other features include:
• Push-button time setting input or one­touch time programming.
• Floating decimal, providing dispense time ranges of 0.001 to 9.999 and 00.01 to
99.99 seconds.
• Bright red LED that displays both time setting and dispensing pressure in psi or bar scale.
• Push-button purge feature.
• Low air-pressure alarm and End-of-Cycle feedback signals.
The ValveMate 7000 has been designed with the machine builder and operator in mind. The objectives are to bring dispens­ing control close to the point of application, and to provide the features necessary to make setup and operation as easy and precise as possible.
The ValveMate is easy to operate. Once you have reviewed the features, you will understand the benefits and the ease of control the ValveMate provides.
As with all EFD products, the ValveMate has been produced to exacting specifications and thoroughly tested prior to shipment.
To obtain maximum performance from this equipment, please read the instructions carefully.
Note: Specifications and technical
details are subject to engineering changes without prior notification.
Size: 14 cm W x 14 cm D x 6 cm H (5.5”W x 5.6” D x 2.5” H)
Weight: 1.0 kg (2.3 lb)
Cabinet: Aluminum
Input Voltage: Selectable 100/120/220 VAC 50/60 Hz 10/9VA
Internal Voltage: 12 VDC
Feedback Circuits: 5 to 24 VDC NC solid-state switch 250mA maximum
Initiate Circuit: 5 to 24 VDC signal or foot pedal
Air Input: 70 psi (4.8 bar)
Air Consumption: Approximately 1.5 SCFM at 400 cycles per minute
Cycle Rate: Exceeds 600 per minute
Time Range: Programmable 0.001 to 9.999, or 00.01 to 99.99 seconds
Specifications
The small size and adjustable mounting bracket allow for positioning of the ValveMate close to the point of valve operation and provide convenient access to setup and dispensing adjustment controls.
Digital readout is shown for both dispensing time and air pressure.
“On the fly” time adjustment allows adjustment of valve output while the equipment is running. This feature eliminates the need to shut down parent machinery to change or adjust dispense time settings.
Other features and explanations of controls are detailed in the diagrams on pages 4 and 5.
3 / Specifications
Slow
14 cm (5.5")
14.2 cm (5.6")
6.4 cm (2.5")
8.6 cm (3.4")
RUN
POWER
Run
Setup
Steady
Test
Purge Fast
FastClear
Slow
Program Time Set
Time Set
STOP
SETUP
CYCLE
Pressure
Time
®
A NORDSON COMPANY
VALVEMATE 7000
Meets CSA and CE standards.
1. Digital time and air pressure LED display
Programmable floating decimal provides time range readout from 0.001 to 99.99 seconds.
Pressure readout can be programmed to read either in psi or bar. (Details on page 10.)
2. RUN / SETUP
Press to change the mode of operation between RUN and SETUP.
The SETUP mode provides access to the MEMORY, CLEAR, TEST and TIME SET functions. While in the SETUP mode, time values can be changed.
The RUN mode locks in the time displayed and locks out access to the CLEAR and TIME
SET functions.
3. STEADY / TEST
In the RUN mode, press this button to place
the ValveMate into the STEADY mode (no timer) and display will show dashes (---). Press again to return the ValveMate to the timed mode.
In the SETUP mode, this button initiates the ValveMate through one complete cycle. Use to test dispensing before going into the RUN mode.
4. CLEAR
In the RUN mode, the function is inoperative.
In the SETUP mode, press to clear time and
display to zero.
5. TIME SET (down)
Use to scroll time display down. Left button scrolls fast. Right button scrolls slowly.
6. STOP
This button, when pressed, stops the 7000 immediately. Also, holding this button in while turning the power switch on will deactivate or reactivate the low air pressure alarm.
7. PRESSURE / TIME
In the RUN mode, press to change the display
from time to pressure. Press a second time to change pressure back to time.
In the SETUP mode, press and hold for 3.0 seconds to toggle pressure display from psi to bar. Press a second time for 3.0 seconds to toggle pressure display back to psi.
8. TIME SET (up)
Use to scroll time display up. Left button scrolls fast. Right button scrolls slowly.
9. PURGE / PROGRAM
The RUN mode opens the valve for as long as
the button is held in. Use for priming or purging air from the system.
The SETUP mode opens the valve and sets time for as long as the button is held in. Use for setting deposit amount when a specific time value is not known.
Features and Controls
4 / Features and Controls
POWER
RUN
SETUP
CYCLE
STOP
Clear
Purge
Run
Setup Program
Fast Slow
Time Set
Steady
Test
Pressure
Time
Fast Slow
Time Set
34 5
7
6
89
1
2
®
A NORDSON COMPANY
VALVEMATE 7000
5 / Features and Controls
1. Power cord receptacle with voltage selection and fuse cartridge
Three input voltages can be used. 100 VAC, 120 VAC and 220 VAC. To change input volt­age, remove fuse cartridge and position the selected voltage marked on the cartridge so that it shows through the window. (Details on page 8.)
2. Foot pedal receptacle
For optional foot pedal, order part #2015A.
3. Air input push-in style fitting
Main air input supply is installed here. Set air pressure at 70 psi (4.8 bar). Lower than 60 psi (4.1 bar) will trigger insufficient air pres­sure alarm and shut down all functions.
4. Air output quick-connect
Install male connector from EFD valve air input hose here. Push in and turn clockwise to lock.
5. Input / Output terminal strip
For detail connection schematic and instruc­tions for input or output features, see diagram on page 15.
• The 7000 features a low pressure alarm system. An output signal, in the form of a solid-state switch, closes when pressure drops below 60 psi (4.1 bar). This closure can be used to operate an audible alarm, shut-off switch or other device. Maximum load is 250mA from 5 to 24 VDC. In addition, when the air pressure is low, the display will flash between “air” and “pressure” indicating that pressure has dropped below minimum. (See page 4 for instructions on deactivating or reacti­vating the alarm.)
• An End-of-Cycle signal, also in the form of a solid-state switch, closes upon comple­tion of the dispense cycle. Maximum load is 250mA from 5 to 24 VDC source (not included).
• The 7000 can be initiated using a 5 to 24 VDC signal.
• The 7000 can also be initiated with a contact closure such as a mechanical relay or optional foot pedal (order sepa­rately #2015A).
220
Air Output
Fuse T 125mA 250V 100/120/ 220VAC 50/60Hz 10/9VA
1. Initiate +
2. Initiate -
3. Output +
4. Output
1 2 4 3 5 6 7
8
7. Contact Closure
8. Contact Closure
250mA
5-24 VDC
5. Alarm +
5-24 VDC
5-24 VDC
250mA
6. Alarm -
Foot Pedal
Input
Exhaust
Air
1
2
5
34
6 / Indicator Lamps
Indicator Lamps
In the upper right corner of the front panel are four indica­tor lamps. These lamps indicate the mode of operation.
POWER
--
Indicates that there is power to the ValveMate.
RUN--Indicates that the ValveMate is in the RUN mode
ready to be initiated through a dispense cycle.
SETUP--Indicates that the 7000 is in the SETUP mode.
Time settings can only be changed in this mode.
CYCLE
--
This lamp is on whenever the control solenoid is
open, causing the dispense valve to be open.
POWER
RUN
SETUP
CYCLE
STOP
Clear
Purge
Program
Run
Setup
Fast Slow
Time Set
Steady
Test
Pressure
Time
Time Set
Fast Slow
Typical Setup
7 / Typical Setup
Five micron filter regulator
Shut-off valve
Voltage value
Cartridge window (check voltage indicated)
Spare fuse
Mounting
Included with the 7000 is a univer­sal mounting bracket. Mounting hardware is installed into the four 10-32 mounting holes on the sides of the cabinet. The bracket can be mounted either over or under the cabinet and will allow the 7000 to pivot up or down 30 degrees from a horizontal position. The bracket may be permanently mounted, or attach the rubber feet included and use the bracket as a bench-top tilt stand. Four rubber feet on the console are provided if the bracket is not used.
For panel mounting, a panel mount bracket kit is available (order #7000PMK).
Input Power
Check the input power cord recep­tacle fuse cartridge to ensure that the voltage is set properly. The cartridge may be set for input volt­ages of 100, 120, or 220 VAC.
To change voltage, remove the fuse cartridge. Remove the fuse holder from the cartridge, rotate the holder and position the correct voltage to show through the car­tridge window. Replace the car­tridge into the power cord recep­tacle and ensure that both sides snap securely into position.
Install the power cord.
Setup
8 / Setup
2
2
0
120
1
0
0
9 / Setup
Initiate Connection
The 7000 can be initiated through a time cycle by the application of 5 to 24 VDC to terminals 1 and 2, by closure of mechanical contacts across terminals 7 and 8, or by using an optional EFD foot pedal (order #2015A), plugged into the foot pedal receptacle. A connec­tion schematic is detailed on page
15. Select one of these methods and install now.
Air Input Connection
Connect the ValveMate 7000 to plant air by first installing the EFD five-micron filter regulator (#2000F755) to your air supply.
Install the air tee with barb fitting (#1116) in the output of the filter regulator.
10 feet of 1/4” OD air line is supplied. Using the barb fitting supplied,
connect one end to the #1116 air tee. Connect the other end of the air line by pushing it firmly into the air input connector on the ValveMate 7000 until it bottoms out. Be sure that the line is inserted all the way into the fitting.
Set the pressure at the #2000F755 filter regulator to 70 psi (4.8 bar).
The quick-connect on the air tee is used to provide air pressure to the air pressure regulator on EFD fluid reservoirs. This connection will be made at a later step in the setup.
Control Air Output
The dispense valve is connected to this output quick-connect. All EFD dispense valves are equipped with the matching male connector. Insert and twist to lock. At this point, however, do not attach the dispense valve.
Please continue to next page.
220
Air Output
Fuse T 125mA 250V 100/120/220VAC 50/60Hz 10/9VA
1. Initiate +
2. Initiate -
3. Output +
4. Output
1 2 4 3 5 6 7
8
7. Contact Closure
8. Contact Closure
250mA
5-24 VDC
5. Alarm +
5-24 VDC
5-24 VDC
250mA
6. Alarm -
Foot Pedal
Input
Exhaust
Air
10 / Setup
Turn the Power Switch On.
Setting the Decimal
The 7000 is shipped with the deci­mal set at the 99.99 second range.
If the 9.999 second range is desired, change as follows:
To place the display into the time position, press the
PRESSURE / TIME
button. This will toggle the display from pressure to time readout.
To move the decimal, press the
STOP
button and hold it for 3.0 seconds. The decimal point will switch to
0.000. To change back to 00.00, press and hold
STOP
again.
Setting the Pressure Readout
The 7000 is shipped with pressure display programmed in psi.
If bar is desired, change as follows:
Press
RUN / SETUP
and place the
7000 into the
SETUP
mode. Press
and hold the
PRESSURE / TIME
but­ton for 3.0 seconds. The display will change from psi to bar. To change back to psi, press and hold
PRESSURE / TIME
for approximately
3.0 seconds.
POWER
RUN
SETUP
CYCLE
STOP
Test
Clear
Purge
Run
Setup Program
Fast Slow
Time Set
Steady
Pressure
Time
Fast Slow
Time Set
®
A NORDSON COMPANY
VALVEMATE 7000
Note:
Changing the decimal place will change the current time setting by a factor of 10X. (Example - time setting of 5.350 becomes 53.50.)
11 / Installing the Valve
Installing the Valve
All EFD dispense valves are sup­plied with a complete instruction manual. If you have not yet read the manual, do this now. The man­ual will explain the operation of the valve and also how to set up the valve with the fluid reservoir.
FINAL SETUP CHECKLIST
• Fuse cartridge voltage has been checked or adjusted.
• Either voltage or mechanical contact initiate is connected.
• Air pressure of 70 psi (4.8 bar) is connected to the air input fit­ting.
• Power on.
• Decimal place is set.
• Pressure value is set for psi or bar.
Once you have read the operating manual for the valve that you are using, connected the valve to the fluid reservoir and have the reservoir prop­erly pressurized, you may begin the following steps to install the valve:
1. Install the quick-connect from the air line on the valve to the air output on the back of the 7000. Simply push in and twist to the right to lock.
2. Pressure to the 7000 should be set at 70 psi (4.8 bar). Remember, pressure may be checked by pressing the
PRES-
SURE / TIME
button.
3. Place a container under the out­let of the dispense valve.
4. Select and install a dispensing tip on the valve output tip adapter.
5. Place the 7000 into the
RUN
mode and press
PURGE / PRO-
GRAM
. Hold the button until liq­uid fills the lines and begins to flow from the valve.
6. Continue to purge until the liquid feed lines and valve are free of air.
7. Set up the deposit size using the
TIME SET
buttons illustrated on
page 4. Pressing the
TEST
button
in the
SETUP
mode will initiate one
dispense cycle.
12 / Schematic and Replacement Parts List
Replacement Parts List
1. 7104A Display board
2. 7105A Power supply board
3. 7106D Fuse drawer
4. 7107A Air input hose fitting, push-in style
5. 7108
* Exhaust muffler
6. 7109 Power switch
7. 7111 Fuse .125A
8. 7123 Transformer
9. 7131 Pressure sensor
10. 7143-01 Output circuit fuses
11. 2004B Female quick-connect, black
12. 2009-A24 Power cord*
13. 2024-160 1/4” OD x .160” ID tubing
14. 2085 1/8 NPT x 1/4 barb elbow, low profile
15. 2086 1/8 NPT x 1/4 barb 90°, brass
16. 2087 1/8 NPT x 1/4 barb elbow, brass
17. 2-7125-7000 Solenoid
18. 2-2017-1500 Foot pedal receptacle assembly
19. 20000F755
* Five micron filter regulator
20. 2015A* Foot pedal assembly (optional)
* Not Shown
55
11
3
7
18
4
4
99
18
10
131313
13
17
14
16
6
2
8
15
1
Timer is inoperative.
Troubleshooting Guide
Unit changes from
RUN
to
SETUP, SETUP
light is flashing,
and unit has to be reset.
13 / Troubleshooting
There is an “AIR”message.
No power.
If trouble cannot be corrected, or if you need further assistance,
please call
us
. In the US, call 800-556-3484. In the UK, phone 0800 585733.
In Asia, +86 (21) 5854 2345.
Trouble Possible cause and correction
The low level air alarm is active. Raise the input pressure to 70 psi (4.8 bar) on the display. Press
RUN / SETUP
button to reset.
Air pressure has momentarily dropped below 60 psi (4.1 bar). Increase input air pressure to 70 psi (4.8 bar). If already at 70 psi (4.8 bar), check to make sure that other devices such as air cylinders are not causing a pressure drop in the ValveMate 7000 input air line.
Check the input power fuse. If the fuse has failed, check the voltage value in the fuse cartridge window. Be sure that it matches the input voltage.
Ensure that the external voltage to the circuit is between 5 and 24 VDC and that the load does not exceed 250mA.
If the circuit has been overloaded, the fuse may be open. See internal diagram on page 15 and replace fuse if necessary.
Response delay in pneumatic circuit does not allow the valve to open when time is set at or below 0.010 seconds. Increase time.
Check to make sure unit is not in
STEADY
mode. The timer is very reliable. Any failure is total, so no inconsistency is possible.
End-of-Cycle Feedback
Circuit or low pressure alarm
is not functioning.
Does not dispense below
0.010 second time setting.
1. Voltage Initiate Circuit
The ValveMate 7000 may be initiated with a 5 to 24 VDC signal. The signal can be momentary (no less than 0.008 seconds) or maintained. A new cycle will begin once power is removed and then applied again. Refer to the schematic for proper installation.
2. End-of-Cycle Feedback Circuit
Upon completion of a dispense cycle, an open collector circuit closes and remains closed until the next dispense cycle. This circuit can be utilized to signal back to a host computer, start another device in sequence or other operations that need to be tied into the completion of the dispense cycle.
Upon closure, power from an external source is allowed to pass through the circuit to operate a 5 to 24 VDC load. The load illustrated is a relay, but this could be any device that will operate within the 5 to 24 volt range. Power consumption of the load must not exceed 250mA.
3. Low Pressure Alarm Circuit
The ValveMate features a low pressure alarm output that activates whenever pressure drops below the minimum valve operating pressure of 60 psi (4.1 bar).
Function and circuitry is identical to the feedback circuit described in #2.
See page 4 for deactivate/reactivate procedure.
4. Mechanical Contact Circuit
The ValveMate can be initiated via the closure of mechanical contacts such as a relay or switch. Closure of the contacts can be momentary (no less than 0.008 seconds) or maintained. A new cycle will begin once the contacts are opened and then closed again. Refer to the schematic for proper installation.
Note: For applications using more than one 7000, see pages 16 and 17 for connection instructions.
Input/Output Connections
14 / Input/Output Connections
15 / Input/Output Connections
100/120/ 220 VAC 50/60 Hz 10/9VA
Programmable
Display
Nonvolatile
Memory
Pressure
Sensor
Power Supply
+5 VDC
+12 VDC
Micro-
controller
Solenoid
Valve
Opto
Coupler
Opto
Coupler
Opto
Coupler
Protector
Fuse
Fuse
1. Voltage Initiate Circuit
+
5 to 24 VDC Power Source
_
Power Consumption
1
2
3
4
5
6
Lamp
7
8
2.2mA at 5 VDC
15.0mA at 24 VDC
2. End-of-Cycle Feedback Circuit
+
5 to 24 VDC
_
Power Source Maximum Load 250mA
3. Low Pressure
+
Alarm Circuit
5 to 24 VDC
_
Power Source Maximum Load 250mA
4. Mechanical
A relay and a lamp are illustrated as examples for utilizing the feedback and alarm circuits.
Contact Initiate
Mechanical Contact Power Consumption Contact Load =
5.5 VDC / 100uA
NOTE: DO NOT APPLY VOLTAGE
1. Parallel circuit diagram for Voltage Initiate. The same diagram should be
used when connecting Low Pressure Alarm terminals 5 & 6 or Mechanical Contact Initiate terminals 7 & 8.
16 / Connecting More than One 7000
Connecting More than One 7000
Follow these instructions and diagrams when the Voltage Initiate or End-of­Cycle Feedback features are used in a multiple 7000 installation.
1. Voltage Initiate Circuit
To start the dispense cycle for multi­ple 7000’s at the same time, connect the Voltage Initiate Circuit, the Contact Closure Initiate and the Low Pressure Alarm Circuits in parallel as illustrated.
Note:
The amperage consumption for the Voltage Initiate Circuit will increase with each ValveMate 7000 that is connected. The initi­ate power supply should be sized accordingly.
Example: First 7000 consumes
15.0mA at 24 volts. Second one will consume another 15.0mA; now total is 30.0mA. Third one will consume another 15.0 making the total 45.0mA and so on.
17 / Connecting More than One 7000
2. End-of-cycle Feedback Circuit
This circuit will ensure that the End­of-Cycle will come from the last 7000 to complete a dispense cycle. Connect in series as illustrated.
Note:
There will be a maximum voltage drop of 2.0 VDC through the Feedback Circuit with each 7000 that is added to the series. The input power should be adjusted for this drop to ensure that the required voltage is available to operate the load. Maximum input voltage to terminals 3 & 4 must not exceed 30.0 VDC.
Example: The load to be operated through the Feedback Circuit is 12 VDC. Four 7000’s are to be used. 4 X 2.0 = 8.0 VDC drop. Power supply should provide (12.0 + 8.0) or 20.0 VDC to ensure that 12.0 VDC is available to run the load.
Stack mounting two or more ValveMate 7000’s. Use the dimensions in the illustration to make up mounting bracket from flat stock.
2. Series circuit for End-of-Cycle Feedback feature. A relay is illus-
trated as one example for utilizing the Feedback Circuit.
REMEMBER: Maximum current through the Feedback Circuit must not exceed 250mA.
28.7 mm (1.13”)
25.9 mm (1.02”)
69.9 mm (2.75”)
5.2 mm (13/64”) hole size
For EFD sales and service in over 30 countries, contact EFD or go to www.efd-inc.com/contact
EFD, Inc.
East Providence, RI USA 800-556-3484; +1-401-434-1680 (outside the USA) info@efd-inc.com www.efd-inc.com
EFD International Inc.
Dunstable, Bedfordshire, UK 0800 585733 or +44 (0) 1582 666334 Ireland 00800 8272 9444 europe@efd-inc.com www.efd-inc.com
EFD, Inc., Asia
China: +86 (21) 5854 2345 china@efd-inc.com www.efd-inc.com/cn Singapore: +65 6896 9630 sin-mal@efd-inc.com
©2006 Nordson Corporation 7000-MAN-01 v062606
®
A NORDSON COMPANY
This equipment is regulated by the European Union under WEEE Directive (2002/96/EC). See www.efd-inc.com for information about how to properly dispose of this equipment.
Loading...