SUGGESTED SPECIFICATIONS FOR VENTILATOR MODEL
96WDM
Exhaust Ventilator to be SOUTHERN ENGINEERING SYSTEMS by Duke Mfg Co., model 96WDM, Type I, UL Listed hood assembly for commercial cooking appliances and be in compliance with NFPA Bulletin No. 96.
Canopy constructed of 18-gauge stainless steel (where exposed) with bottom perimeter edges gutterless. Weld extraction chamber, plenum, and external seams and joints to form a liquid tight construction. Polish stainless steel to a #3 nish.
Exhaust plenum Filter Housing to be same material as canopy, full length of section at the back. Furnish stainless steel UL Classified grease lters, installed on a 45˚ angle, full length of housing. Filter housing to terminate at bottom in a pitched drip tray to accept gravity ow residue and drain to a covered stainless steel container.
Grease Container constructed of 18-gauge stainless steel. Fabricate container so as to be easily removable for daily cleaning.
Furnish Duct Collar, fully welded, in top of canopy within exhaust plenum area. Duct collar size based on an average 1800 F.P.M. air velocity.
Optional automatic Fire Damper constructed of 12-gauge steel within exhaust duct collar. Damper operated by an externally mounted spring-loaded mechanism and controlled by a fusible link.
Integral Make-Up Air furnished at front of ventilator shall be proprietary “Air Curtain” design. Outside shell constructed of 18-gauge stainless steel integrated with canopy. Lower front wall to be constructed of perforated 18-gauge stainless steel. Panels to be designed to distribute make-up air outward at medium velocity. Front panels shall be hinged at top to allow easy access to interior of make up chamber. Make-up air chamber tted with an interior diffuser baffle designed to provide even air distribution across the perforated surface. Top of chamber to be fitted with a properly sized rectangular duct collar. Make-up air duct collar sized to permit up to 80% supply air.
Furnish UL listed, NSF approved, vapor proof incandescent Light Fixtures (optional) installed on 3’ to 4’ centers. Fixtures to be completely inter wired to a junction box and left ready for nal connection to power source. Field connections and light switch by applicable trades.
Furnish Rod Hanger Brackets at front and center to suspend canopy from ceiling. Furnish angle frame members at rear for fastening to wall.
Canopy shall be UL Listed and NSF approved. All equipment built in an ISO 9001:2000 approved manufacturing facility.
SOUTHERN ENGINEERING
2305 N. Broadway St. Louis, MO 63012 Ph 314-231-1130 Fax 314-231-5074
www.dukemfg.com
BY
"Your Solutions Partner"
5/07
Exhaust Requirements Make-up Air Requirements
CFM ________________ SP (“w.g.) _____________ CFM ________________ SP (“w.g.) ________
Duct Collar ________ “x ______________” Duct Collar ________ “x __________”
Fire Protection Lighting Fixture (UL listed)
(Submit cooking equipment plan showing make Globe incandescent (100W)
and model on equipment.) Recessed incandescent (150W)
 Ansul Wet #R-102  Recessed fluorescent  Other ___________________________________  Light switch  Internal Piping Only NOTE: Incandescent lights are located Complete System on approx. 4’ centers. Fluorescent  By Others xtures are 3’ (50W) and 4’ (64W)
NOTE: Fuel shut-off devices by others (unless specified otherwise). Enclosure paneling
(Finished ceiling higher than 9’0”)  Fan switch Loose duct collars UL Exhaust Fire Damper
Optional Accessories
Shipping Wt. 90 lbs./Linear ft.
COMMENTS/NOTES ____________________________________________________________________
G.I. ANGLE AT REAR
FOR WALL MOUNTING
(OPTIONAL) U.L. LISTED FIRE DAMPER
'- "
"
2"
"
6"
2'-0"
UL SS GREASE FILTERS
'- "
(36" MIN. ST D .)
SS GREASE CONTAINER
45°
3/8" DIA. G.I. ROD HANGERS
FURNISHED BY OTHERS
FINISHED S.S. PANELING
DIFFUSER BAFFLES
18 GA. S.S. PERF. PANELING
HINGED AT TOP FOR ACCESS
INCANDESCENT LIGHTS
(FLOURESCENT LIGHTS OPTIONAL)
BULBS NOT INCL.
10"
2'-6"
10"
6'-6" A.F.F.
4"
"
INTEGRAL 3" AIRSPACE AT REAR