Duke 96WB User Manual

SUGGESTED SPECIFICATIONS FOR VENTILATOR MODEL 96WB
Exhaust Ventilator to be SOUTHERN ENGINEERING SYSTEMS by Duke Mfg Co., model 96WB, Type I, UL Listed assembly for commercial cooking appliances and be in compliance with NFPA Bulletin No. 96.
Canopy constructed of 18-gauge stainless steel (where exposed) with bottom perimeter edges gutterless. Weld extraction chamber, plenum, and external seams and joints to form a liquid tight construction. Polish stainless steel to a #3 nish.
Exhaust plenum Filter Housing to be same material as canopy, full length of section at the back. Furnish stainless steel UL Classified grease lters, installed on a 45˚ angle, full length of housing. Filter housing to terminate at bottom in a pitched drip tray to accept gravity ow residue and drain to a covered stainless steel container.
Grease Container constructed of 18-gauge stainless steel. Fabricate container so as to be easily removable for daily cleaning.
Furnish Duct Collar, fully welded, in top of canopy within exhaust plenum area. Duct collar size based on an average 1800 F.P.M. air velocity.
Optional automatic Fire Damper constructed of 12-gauge steel within exhaust duct collar. Damper operated by an externally mounted spring-loaded mechanism and controlled by an fusible link.
Integral Make-Up Air shall NOT be furnished. Bottom edge of canopy anged inward forming channel type edge, and tted with 18-gauge stainless steel stationary panels. Extend panels to nished ceiling (9’0” max.) on all exposed sides forming box type construction.
Furnish UL listed, NSF listed, vapor proof incandescent Light Fixtures (optional) installed on 3’ to 4’ centers. Fixtures to be completely inter-wired to a junction box and left ready for nal connection to power source. Field connections and light switch by applicable trades.
Furnish Rod Hanger Brackets at front and rear to suspend canopy from ceiling. Furnish angle frame members at rear for fastening to wall
Canopy shall be UL Listed and NSF approved. All equipment built in an ISO 9001:2000 approved manufacturing facility.
2305 N. Broadway St. Louis, MO 63012 Ph 314-231-1130
BY
"Your Solutions Partner"
Fax 314-231-5074 www.dukemfg.com
5/07
Exhaust Requirements
CFM ________________ SP (“w.g.) _____________
Duct Collar ________ “x ______________”
Fire Protection Lighting Fixture (UL listed)
(Submit cooking equipment plan showing make
and model on equipment.) Globe incandescent (100W) Recessed incandescent (150W)
 Ansul Wet #R-102  Recessed flourescent  Other ___________________________________  Light switch  Internal Piping Only NOTE: Incandescent lights are located Complete System on approx. 4’ centers. Fluorescent  By Others xtures are 3’ (50W) and 4’ (64W)
NOTE: Fuel shut-off devices by others (unless specified otherwise). Enclosure paneling
(Finished ceiling higher than 9’0”)  Fan switch Loose duct collars UL Exhaust Fire Damper
Optional Accessories
Shipping Wt. 80 lbs./Linear Ft.
COMMENTS/NOTES __________________________________________________________________
G.I. ANGLE AT REAR
FOR WALL MOUNTING
U.L. LISTED FIRE DAMPER
3/8" DIA. G.I. ROD HANGERS
FURNISHED BY OTHERS
FINISHED S.S. PANELING
INCANDESCENT LIGHTS
(FLUORESCENT LIGHTS OPTIONAL)
BULBS NOT INCLUDED
2'-6"
2 1/4"
6'-6" A.F.F.
UL SS GREASE FILTERS
INTEGRAL 3" AIR SPACE
(OPTIONAL)
"
2'-0"
(36" MIN. STD.)
SS GREASE CUP
AT REAR