SUGGESTED SPECIFICATIONS FOR VENTILATOR MODEL 96ST
Exhaust Ventilator to be SOUTHERN ENGINEERING SYSTEMS by Duke Mfg Co., model
96ST, Type I, UL Listed, exhaust only, Hood Assembly for commercial cooking appliances and in
compliance with NFPA Bulletin 96.
Canopy
gutterless. Weld extraction chamber, plenum, and external seams and joints to form a liquid tight
construction. Polish stainless steel to a #3 finish.
Exhaust plenum Filter Housing to be same material as canopy, full length of section at the back.
Furnish stainless steel UL Listed grease filters, installed a 45 degree angle, full length of housing. Filter
housing to terminate at bottom in a pitched drip tray to accept gravity flow residue and drain to a
covered stainless steel container.
Grease Container constructed of 18-gauge stainless steel. Fabricate container so as to be easily
removed for daily cleaning.
Furnish Duct Collar, fully welded, in top of canopy within exhaust plenum area. Duct collar size based
on an average 1800 FPM air velocity.
Optional automatic Fire Damper constructed of 12-gauge steel within exhaust duct collar. Damper
operated by an externally mounted spring load mechanism and controlled by a fusible link.
Integral Make-Up Air shall NOT be furnished.
, constructed of 18-gauge stainless steel (where exposed) with bottom perimeter edges
Furnish Rod Hanger Brackets at front and center (as required) to suspend canopy from
ceiling. Furnish angle frame members at rear for fastening to wall.
Canopy shall be UL Listed and NSF approved. All equipment built in an ISO 9001:2000
approved manufacturing facility.
2305 N. Broadway
St. Louis, MO 63012
Ph 314-231-1130
BY
"Your Solutions Partner"
Fax 314-231-5074
www.dukemfg.com
5/07
Exhaust Requirements
CFM ________________ SP (“w.g.) _____________
Duct Collar ________ “x ______________”
Fire Protection Lighting Fixtures
(Submit cooking equipment plan showing make (Not Available)
and model on equipment.)
Ansul Wet #R-102
Other ___________________________________
Internal Piping Only
Complete System
By Others
NOTE: Fuel shut-off devices by others (unless specified
otherwise). Enclosure paneling
(Finished ceiling higher than 9’0”)
Fan switch
Loose duct collars
UL Exhaust Fire Damper
Optional Accessories
Shipping Wt. 80 lbs./Linear Ft.
COMMENTS/NOTES __________________________________________________________________
.