Duke 96IDB User Manual

SUGGESTED SPECIFICATIONS FOR VENTILATOR MODEL 96IDB
Exhaust Ventilator to be SOUTHERN ENGINEERING SYSTEMS by Duke Mfg Co., model 96IDB, Type I, UL Listed hood assembly for commercial cooking appliances and be in compliance with NFPA Bulletin No. 96.
Canopy constructed of 18-gauge stainless steel (where exposed) with bottom perimeter edges gutterless. Weld extraction chamber, plenum, and external seams and joints to form a liquid tight construction. Polish stainless steel to a #3 nish.
Grease Container constructed of 18-gauge stainless steel. Fabricate container so as to be easily removable for daily cleaning.
Furnish Duct Collar, fully welded, in top of canopy within exhaust plenum area. Duct collar size based on an average 1800 F.P.M. air velocity.
Optional automatic exhaust Fire Damper constructed of 12-gauge steel within exhaust duct collar. Damper operated by an externally mounted spring-loaded mechanism and controlled by a fusible link.
Integral Make-Up Air shall NOT be furnished. Bottom edge of canopy anged inward forming channel type edge tted with 18-gauge stainless steel stationary panels. Extend panels to nished ceiling (9’0” max.) on all exposed sides forming box type construction.
Furnish UL and NSF listed vapor proof incandescent Light Fixtures (optional) installed on 3’ to 4’ centers. Fixtures to be completely inter-wired to a junction box and left ready for nal connection to power source. Field connections and light switch by applicable trades.
Furnish Rod Hanger Brackets at front and center to suspend canopy from ceiling.
Canopy shall be UL Listed and NSF approved. All equipment built in an ISO 9001:2000 approved manufacturing facility.
2305 N. Broadway St. Louis, MO 63012 Ph 314-231-1130
BY
"Your Solutions Partner"
fax 314-231-5074
www.dukemfg.com
6/07
Exhaust Requirements
CFM ________________ SP (“w.g.) _____________
Duct Collar ________ “x ______________”
Fire Protection Lighting Fixture (UL listed)
(Submit cooking equipment plan showing make
and model on equipment.) Globe incandescent (100W) Recessed incandescent (150W)
 Ansul Wet #R-102  Recessed fluorescent  Other ___________________________________  Light switch  Internal Piping Only NOTE: Incandescent lights are located Complete System on approx. 4’ centers. Fluorescent  By Others xtures are 3’ (50W) and 4’ (64W)
NOTE: Fuel shut-off devices by others (unless specied
Optional Accessories
otherwise). Enclosure paneling (Finished ceiling higher than 9’0”)
 Fan switch Loose duct collars UL Exhaust Fire Damper
Shipping Wt. 180 lbs./Linear Ft.
COMMENTS/NOTE_______________________________________________________
FIELD JOINT
3/8" DIA. G.I. ROD HANGERS
FURNISHED BY OTHERS
FINISHED S.S. PANELING
INCANDESCENT LIGHTS
(FLOURESCENT LIGHTS OPTIONAL)
BULBS NOT INCL.
2'-6"
6'-6" A.F.F.
UL FIRE DAMPER
(OPT IONAL)
2'-0"
UL SS GREASE FILTERS
REMOVABLE S.S.
GREASE CONTAINERS
(72" MIN STD)