SUGGESTED SPECIFICATIONS FOR VENTILATOR MODEL
96EM
Exhaust Ventilator to be SOUTHERN ENGINEERING SYSTEMS by Duke Mfg Co., model
96EM, Type I, UL Listed, hood assembly for commercial cooking appliances and be in compliance
with NFPA Bulletin No. 96
Canopy, constructed of 18-gauge stainless steel (where exposed) with bottom perimeter edges
gutterless. Weld extraction chamber, plenum, and external seams and joints to form a liquid tight
construction. Polish stainless steel to a #3 finish.
Exhaust plenum Filter Housing to be same material as canopy, full length of section at the back.
Furnish stainless steel UL Classified grease filters, installed a 45 degree angle, full length of housing.
Filter housing to terminate at bottom in a pitched drip tray to accept gravity flow residue and drain to a
covered stainless steel container.
Grease Container constructed of 18-gauge stainless steel. Fabricate container so as to be easily
removable for daily cleaning.
Furnish Duct Collar, fully welded, in top of canopy within exhaust plenum area. Duct collar size based
on an average 1800 F.P.M. air velocity.
Optional automatic exhaust Fire Damper constructed of 12-gauge steel within exhaust duct collar.
Damper operated by an externally mounted spring-loaded mechanism and controlled by an fusible link.
Integral Make-Up Air shall NOT be furnished. Canopy shall be constructed with 18-gauge stainless
steel stationary panels on all exposed sides forming box type construction
Furnish Rod Hanger Brackets at front and rear to suspend canopy from ceiling.
Canopy shall be UL and NSF listed. All equipment built in an ISO 9001:2000 approved
manufacturing facility.
2305 N. Broadway
St. Louis, MO 63012
Ph 314-231-1130
BY
"Your Solutions Partner"
Fax 314-231-5074
www.dukemfg.com
5/07
Exhaust Requirements
CFM ________________ SP (“w.g.) _____________
Duct Collar ________ “x ______________”
Fire Protection Lighting Fixtures
(Submit cooking equipment plan showing make (Not Available)
and model on equipment.)
Ansul Wet #R-102
Other ___________________________________
Internal Piping Only
Complete System
By Others
NOTE: Fuel shut-off devices by others Optional Accessories
(Unless specified otherwise). Enclosure paneling
(Finished ceiling higher than 9’0”)
Fan switch
Loose duct collars
UL Exhaust Fire Damper
Shipping Wt. 70 lbs./Linear Ft.
COMMENTS/NOTES
__________________________________________________________________
3/8" DIA. G.I. ROD HANGERS
FURNISHED BY OTHERS
STATIONARY S.S. PANELING
FLUE EXTENSION
OVEN
U.L. LISTED FIRE DAMPER
(OPTIONAL)
2'-0"
SS CLASSIFIED
GREASE FILTERS
7'-0" A.F.F.
RECESSED REMOVABLE
SS GREASE CONTAINER
2'-3"
10"
1"
10"