Druck RTX1000A Operating Manual

Page 1
RTX 1000A Series
Analog Pressure Transmitter
User manual
Druck Incorporated, 4 Dunham Drive, New Fairfield, Connecticut 06812, U.S.A.
Telephone: +1 203 746 0400 Facsimile: +1 203 746 2494
KA332
Page 2
USA
Druck Incorporated, 4 Dunham Drive, New Fairfield, Connecticut 06812, USA.
Tel: +1 203 746 0400 Fax : +1 203 746 2494
BRAZIL
Druck Brasil Ltda. Rua 9 de Julho, 25 - Térreo, São Bernardo do Campo - SP CEP 09606-010, Brazil.
Tel: +55 (0)11 4367 3477 Fax: +55 (0)11 4368 9686
FRANCE
Druck SA, 19 rue Maurice Pellerin, 92600 Asnières, France.
Tel: +33 (0)1 41 32 34 64 Fax: +33 (0)1 47 93 00 48
HOLLAND
Druck Nederland bv, Zuideinde 37, 2991 LJ Barendrecht, The Netherlands.
Tel: +31 (0)1806 11555 Fax : +31 (0)1806 18131
ITALY
Druck Italia Srl., Via Magenta 77, edificio 5, 20017 Rho (Milano), Italy.
Tel: +39 (0)2 93 20 61 Fax : +39 (0)2 93 20 62 99
JAPAN
Druck Japan KK, Medie Corp Building 8, 2-4-14 Kichijoji-Honcho, Musashino, Tokyo 180-0004, Japan.
Tel: +81 (0)422 20 7123 Fax: +81 (0)422 20 7155
Trademarks
All product names are trademarks of their respective companies.
GERMANY
Druck Messtechnik GmbH, Auf dem Hohenstein 7, 61231 Bad Nauheim, Germany.
Tel: +49 (0)6032 93300 Fax: +49 (0)6032 933080
UK
Druck Ltd., Fir Tree Lane, Groby, Leicester, LE6 0FH, England.
Tel: +44 (0)116 231 7100 Fax: +44 (0)116 231 7103
Page 3
RTX 1000A Series User Manual
Safety
To use this equipment safely, you must use the data and procedures in these publications:
The "Calibration data and instructions" for the equipment
The applicable CSA or FM Approvals 'Control Drawing'
(Hazardous or Classified areas only)
This user manual
These publications contain instructions to operate the equipment and maintain it in a safe condition. To prevent damage or injury:
Obey all warnings and cautions
Use the equipment only for the specified applications
Operate the equipment only in the specified limits.
To install and use the equipment, use only approved engineers who have the necessary skills and qualifications.
Hazardous (Classified) areas
Some versions of this equipment are certified for use in hazardous (classified) areas. For these versions, GE Druck supplies 'Control Drawings' with additional installation data. The 'Control Drawings' are:
CSA 'Control Drawing' - KA337
FM Approvals 'Control Drawing' - KA253
i KA332 Issue No. 1
Page 4
RTX 1000A Series User Manual
ABBREVIATIONS
The abbreviations in this publication are as follows:
Note: Abbreviations are the same in the singular and plural.
a absolute pressure
A/D analog to digital
AWG American wire gauge
CSA Canadian Standards Association D/A digital to analog
DAC digital to analog convertor
DC direct current
DIN Deutsche Industrie Norm
DIP dual inline package
DPM digital pressure module
°C degrees Celsius
°F degrees Fahrenheit EEPROM electrically erasable programmable read-only memory
EMC electromagnetic compatibility
FM Factory Mutual Approvals
FS full-scale
g gauge pressure
in inch (")
inH2O inches of water
IS intrinsically safe kg kilogram
lb pound
lbf.ft pound-force feet
LCD liquid crystal display
LDV lower display value
LRV lower range value
KA332 Issue No. 1 ii
Page 5
RTX 1000A Series User Manual
ABBREVIATIONS (continued)
m meter
mA milliampere
max maximum
mbar millibar
µF microfarads
mH millihenry
min minimum/minute mm millimeter
MSDS materials specification data sheet
MWP maximum working pressure
PCB printed circuit board
psi pound-force per square inch
PTFE polytetrafluoroethylene
PV primary variable RFI radio frequency interference
RH relative humidity
RTX rangeable transmitter
s seconds
sg specific gravity
UDV upper display value
URL upper range limit
URV upper range value V volt
ohm
W watt
iii KA332 Issue No. 1
Page 6
RTX 1000A Series User Manual
CONTENTS
Section title page
Safety ..................................................................... i
ABBREVIATIONS ................................................... ii
CONTENTS ........................................................... iv
1 DESCRIPTION ....................................................... 1-1
1.1 Introduction ............................................................ 1-1
1.2 About the Electronics Housing ............................... 1-1
1.3 Identification Codes ................................................ 1-3
2 TECHNICAL DATA ................................................ 2-1
2.1 Pressure Ranges ................................................... 2-1
2.2 Environment Data................................................... 2-1
2.3 Performance Data .................................................. 2-1
2.4 Physical Data ......................................................... 2-4
3 INSTALLATION ..................................................... 3-1
3.1 Introduction ............................................................ 3-1
3.2 Special Tools and Equipment ................................. 3-1
3.3 Location and Mounting ........................................... 3-2
3.4 To Rotate the Display Thru 90° ............................... 3-2
3.5 To Rotate the Housing ............................................ 3-3
3.6 Impulse Piping ........................................................ 3-3
3.7 The Transmitter Pressure Connections................... 3-4
3.8 Liquid Level Measurement ...................................... 3-6
3.9 Electrical Data ........................................................ 3-7
3.10 System Checks ...................................................... 3-10
KA332 Issue No. 1 iv
Page 7
RTX 1000A Series User Manual
CONTENTS (continued)
4 OPERATION .......................................................... 4-1
4.1 General .................................................................. 4-1
4.2 Manual Configuration Facilities ............................... 4-2
4.3 Manual Configuration - LCD Operation ................... 4-3
4.4 Manual Configuration - Calibration ......................... 4-4
5 Maintenance ......................................................... 5-1
5.1 General .................................................................. 5-1
5.2 Fault Finding........................................................... 5-2
5.3 Returned Goods Procedure ................................... 5-3
Safety Precautions ................................................. 5-3
Important Notice ..................................................... 5-3
Approved Service Agents ...................................... Back cover
v KA332 Issue No. 1
Page 8
RTX 1000A Series User Manual
ILLUSTRATIONS
Figure title page
1-1 General view .......................................................... 1-1
1-2 Transmitter schematic diagram............................... 1-2
2-1 Range limits ........................................................... 2-1
2-2 Dimensions (Transmitter) ....................................... 2-4
2-3 Dimensions (Optional mounting bracket) ................ 2-5
3-1 Display - Turn thru 90° ............................................ 3-2
3-2 Housing locking screws .......................................... 3-3
3-3 Piping arrangements .............................................. 3-5
3-4 Open tank level measurement ................................ 3-6
3-5 Power and load requirements ................................. 3-7
3-6 Electrical conduit configuration ............................... 3-9
3-7 Transmitter connections ......................................... 3-9
4-1 Location of DIP switches and push buttons ............ 4-2
4-4 Calibration set-up for safe areas ............................. 4-4
5-1 Fault finding from the output signal ......................... 5-2
TABLES
Table title page
1-1 Identification codes................................................. 1-4
3-1 Wire resistance ...................................................... 3-8
4-1 DIP switch operation ............................................... 4-2
4-2 Steps to change the LCD configuration .................. 4-3
5-1 LCD alarm codes and error messages ................... 5-2
KA332 Issue No. 1 vi
Page 9
RTX 1000A Series User Manual
1 DESCRIPTION
1.1 Introduction
The GE Druck RTX 1000A series is a process pressure transmitter that measures the pressure of liquid, gas or vapor and gives an analog output proportional to the applied pressure. The transmitter is available in a compact and lightweight metal housing with facilities for direct mounting to pipeline installations. The type of housing is specified in the order.
To adjust the transmitter operation, there are push-buttons and switches on the electronics module
1.2 About the Electronics Housing (Figure 1-1)
The electronics housing contains a digital pressure module (DPM), electronics module, connecting cables and the terminal block.
end-cap (with access to the terminal block)
electronics housing
certification label (If fitted)
electrical conduit entry
process pressure connection
name plate
Figure 1-1 General view
end-cap (with access to the electronics module)
housing locking screw
1-1 KA332 Issue No. 1
Page 10
RTX 1000A Series User Manual
KA332 Issue No. 1 1-2
Figure 1-2 Transmitter schematic diagram
Page 11
RTX 1000A Series User Manual
Digital Pressure Module (DPM) - (Figure 1-2)
The sensing element in the DPM is constructed from a micro-machined silicon diaphragm assembly bonded to a stainless steel or Hastelloy body. A Hastelloy isolation diaphragm and silicone fluid isolates the sensing element from the process media.
The sensor piezo-resistors, diffused into the surface of the silicon diaphragm, produce a signal in response to applied pressure. The accuracy of the sensor element is enhanced by measuring the residual errors over its operating temperature and pressure range and applying digital compensation in the transmitter electronics.
Electronics Module (Figure 1-2)
The electronics module uses microprocessor technology to give a compact circuit with the minimum of components. The module produces an extremely stable signal unaffected by changes in ambient temperature.
An optional LCD shows a value proportional to the measured pressure. Unless an alternative configuration is specified in the order, the factory configuration shows the pressure value as a percentage of the calibrated span. To change the configuration, refer to section 4.
1.3 Identification Codes (Table 1-1)
Table 1-1 shows the identification codes for the transmitter. Before you install the transmitter, use this table to make sure that the data on the transmitter is correct.
1-3 KA332 Issue No. 1
Page 12
RTX 1000A Series User Manual
Table 1-1 Identification codes
RTX 10 Base Model Number
Code Diaphragm Process Wetted Body Fill Fluid
00 Hastelloy C * 316 stainle ss steel * Sili cone oil
10 Hastelloy C Hastelloy C Silicone oil
20 I nconel 625* Inconel 625* Silico ne oil
Code Output
A 4 - 20 mA
Code Max Span Min Span Notes
04 0 - 10 psi 0 - 1.0 psi Gauge or abs olute
07 0 - 30 psi 0 - 3.0 psi Gauge or abs olute
10 0 - 1 00 psi 0 - 10 psi Gauge or abs olute
13 0 - 3 00 psi 0 - 30 psi Gauge or abs olute
16 0 - 1 ,000 ps i 0 - 100 p si Gauge or absolute
18 0 - 3 ,000 ps i 0 - 300 p si Seal ed gaug e or a bsolut e
22 0 - 10,00 0 psi 0 - 1000 psi Sealed gauge or abso lute
24 0 - 20,00 0 psi* * 0 - 20 00 psi Sealed gauge or abso lute
Code Type
A Absolut e
GGauge (seale d gauge for ra nges above 1,000 psi)
Code Process Connec tion
1G½ female
2 ½-14 NPT female
3G½ male to BS EN 837-1 (DIN 16288)
4 ½ NPT male
5 9/16" t ube Auto clave Enginee rs medi um pres sure, SF 562CX20 female* **
Code Elec trical Entry
N ½-14 NPT fema le (via adapt or)
Example identification code
Code Electronics Housing
0 Alumin um alloy
S Stainless steel
Code A pprovals
0 Safe area
F FM & CSA IS / Expl osionp ro of / Di vision 2
Code Options
0None
LA Di gital indicat or
B Bracket mounting
T DI N 3.1B materi al certi ficat e
End-caps
Aluminum alloy
Nickel plated aluminum bronz e
RTX1 0 00 A 07 G 2 N 0 0 0
-- - - - - ---
* Only available with range code 24, process connection code 5. Not available with CSA or FM
approval.
** Range code 24 (0-20,000 psi) only applies to RTX 1020 models.
*** Process connection code 5 (autoclave fitting) only applies to range code 24.
KA332 Issue No. 1 1-4
Page 13
RTX 1000A Series User Manual
2 TECHNICAL DATA
2.1 Pressure Ranges
The transmitter is supplied in one of the standard (zero based) ranges or it can be calibrated to any acceptable intermediate span. Refer to table 1-1.
The transmitter label shows the factory calibrated range and the maximum working pressure (MWP). The upper range limit (URL) = MWP.
2.2 Environment Data
Service ........................................................................... Liquid, gas or vapor
Pollution Degree ........................................................................................... 2
Installation (over-voltage) Category ........................................................... II
Temperature
ambient (Not CSA or FM approved) ........ -40°F to +185°F (- 40°C to +85°C)
(LCD Option) .....................................-4°F to +158°F (- 20°C to +70°C )
ambient (CSA or FM approved) .............................. minimum: -40°F (- 40°C)
.............................................. maximum: Refer to the product approval label.
process .................................................. -40°F to +248°F (- 40°C to +120°C)
compensated ............................................ -40°F to +185°F (- 40°C to +85°C)
Humidity limit
................................................................................................... 0 - 100% RH
2.3 Performance Data
Range adjustment
0
(psi a)
LRV (or URV) URV (or LRV)
-15 (psi g)
Figure 2-1 shows the limits for range adjustment. For example:
Span: The minimum span available for a 30 psi device is 3 psi (10:1 down-ranging).
Minimum span
(URV - LRV): 10% URL
Lower range value (LRV) = 4 mA pressure value Upper range value (URV) = 20 mA pressure value
Figure 2-1 Range limits
URL
2-1 KA332 Issue No. 1
Page 14
RTX 1000A Series User Manual
Zero offset: A 30 psi (MWP) gauge device can give 4 to 20 mA in the range
-15 psi to 30 psi. For example: If the span is 3 psi, 4 to 20 mA is available anywhere in the range up to a maximum zero offset of 27 psi (calibrated range = 27 to 30 psi).
Accuracy
0.15% of calibrated span. This includes non-linearity, hysteresis and repeatability.
Long term stability
At standard reference conditions, the maximum change in calibration is not more than 0.2% URL in a five year period.
Time response
Update rate (Compensated pressure reading) ................................... 100 ms
Damping (DIP switch selection) ............ 0.1 or 1 s to reach 63% of final value
Temperature effects
-40°F to -4°F (-40°C to -20°C): ..................................... 0.5% URL +1% span
-4°F to +122°F (-20°C to +50°C): ........................... 0.25% URL +0.75% span
+122°F to +185°F (+50°C to +85°C): ............................ 0.5% URL +1% span
Mounting position effect
Negligible effect. For ranges below 10 psi, you can adjust the `g' offset effect with the zero offset control.
Error conditions (NAMUR NE 43 compliant)
Failure mode (< 3.6 or > 21 mA) .......................... DIP Switch selected mode
(This function is always in operation)
Under range (DIP switch 2 off) ................................... 3.8 mA minimum
Over range (DIP switch 2 on) ................................... 20.5 mA maximum
An optional LCD shows the applicable alarm data. If the pressure is not in the upper or lower range limits, the pressure value on the display will flash.
Turn-on time
...................................................................................................... 2 seconds
Electronics housing
Material .................................. Aluminum alloy with polyester powder coating
or ................... Stainless steel with nickel plated aluminum bronze end-caps
Environmental protection ............................................................... NEMA 4X
KA332 Issue No. 1 2-2
Page 15
RTX 1000A Series User Manual
Overpressure
These pressure values will not degrade performance:
................................................................................ 6 x URL for 10 psi range
................................ 4 x URL (2,000 psi max) for ranges: 30 psi to 1,000 psi
....................... 2 x URL (13,000 psi max) for ranges: 3,000 psi to 10,000 psi
..................................................................... 30,000 psi for 20,000 psi range
Pressure containment
These pressures may damage the sensor but there is no leakage of the process media.
.............................................................................. 10 x URL for 10 psi range
..................... 6 x URL (3,000 psi max) for ranges: 30 psi to 1,000 psi gauge
................................................. 3,000 psi for ranges up to 1,000 psi absolute
... 20,000 psi for ranges: 3,000 psi to 10,000 psi sealed gauge and absolute
..................................................................... 30,500 psi for 20,000 psi range
Process media
A liquid, gas or vapor compatible with a fully welded assembly that includes:
A Hastelloy C276 diaphragm, and a body that is made of either
316 stainless steel or Hastelloy C276. Complies with NACE MR-01-75.
Inconel 625 (20,000 psi range, range code 24 only).
Sensor fill fluid
...................................................................................................... Silicone oil
Output current
(two wire configuration) .................................................................. 4 - 20 mA
The output is proportional to the calibrated pressure range.
Supply voltage (at the terminals)
Safe area ................................................................................ 12 to 35 V DC
Hazardous area ............................ Refer to the applicable "Control Drawing".
2-3 KA332 Issue No. 1
Page 16
RTX 1000A Series User Manual
2.4 Physical Data
Electrical/Process connections
............................................................................................ Refer to table 1-1
Dimensions
.................................................................................... Refer to figure 2-2, 2-3
Weight (without options)
Aluminum housing ............................................................. 2.51 lb (1.14 kg)
Stainless steel housing ........................................................ 5.95 lb (2.7 kg)
Options
Digital indicator: polarity sign + 5 digits
Aluminum option ........................................... Add 0.35 lb (0.16 kg)
Stainless steel option ...................................... Add 0.66 lb (0.3 kg)
Mounting bracket/bolts (stainless steel)
Material traceability for pressure containment parts to EN10204 3.1B
≈≈
4.61"
≈≈
(117* mm)
3.19"
(81 mm)
≈≈
4.21"
≈≈
(107 mm)
Dimensions in inches (millimeters) - illustration not to scale
Figure 2-2 Dimensions (Transmitter)
KA332 Issue No. 1 2-4
≈≈
3.62"
≈≈
(92 mm)
*LCD indicator option: 5.43" (138 mm)
Page 17
(a) Example -
Panel mounting
6.5"
(165 mm)
2.8"
(70 mm)
(b) Examples -
Horizontal pipe mounting
RTX 1000A Series User Manual
4.4"
(113 mm)
3.2"
(82 mm)
(c) Example -
Vertical pipe mounting
Dimensions in inches (millimeters) - illustration not to scale
Figure 2-3 Dimensions (Optional mounting bracket)
4.4"
(113 mm)
0.8" (20 mm)
2.8"
(70 mm)
2-5 KA332 Issue No. 1
Page 18
RTX 1000A Series User Manual
KA332 Issue No. 1 2-6
Page 19
RTX 1000A Series User Manual
3 INSTALLATION
Note: If the equipment is certified for use in a hazardous (classified)
area, refer to the applicable "Control Drawing" for additional data.
3.1 Introduction
The following procedures detail the correct installation of the unit.
Use qualified plant installation personnel and follow good engineering practice at all times.
WARNINGS:
1. OBSERVE APPROPRIATE LOCAL SAFETY INSTRUCTIONS.
2. BEFORE INSTALLATION, EXAMINE ALL FITTINGS AND EQUIPMENT FOR DAMAGE AND MAKE SURE THAT ALL EQUIPMENT IS TO THE CORRECT PRESSURE RATING.
3. USE THE IDENTIFICATION CODE ON THE TRANSMITTER TO MAKE SURE THAT IT HAS THE CORRECT SPECIFICATION FOR THE INSTALLATION (REFER TO TABLE 1-1).
3.2 Special Tools and Equipment
The following special tools and equipment are required.
Note: Equivalent substitutes can be used.
Special tools
Applicable torque wrench
GE Druck UPS-II [to measure current output]
Multimeter [to measure loop resistance]
Materials
Piping - the necessary length and rating depends on the distances.
Fittings to connect the above items including (but not limited to):
- Pipe tee (steam or high temperature liquid)
- Pipe fittings
Pipe compound or Teflon tape (where local piping codes allow)
Loctite PST sealant
3-1 KA332 Issue No. 1
Page 20
RTX 1000A Series User Manual
3.3 Location and Mounting (Figure 3-3)
Although designed to withstand harsh industrial environments, the transmitter should be located to minimize the following:
Vibration
Ambient temperature fluctuations
Physical impact or shock
3.4 To Rotate the Display Thru 90° (Figure 3-1)
If applicable, use the following procedure to turn the optional display in the electronics housing.
spacer (x4)
power cables
DPM cables
screw/washer (x4)
PCB
display bezel
end-cap
Figure 3-1 Display - Turn thru 90°
1. Isolate the power supply to the transmitter.
2. Remove the end-cap.
3. Loosen each screw/washer (x4).
4. Turn the PCB and the display bezel thru 90° until the screws align with the spacers again.
5. Tighten each screw/washer (x4) back in position, but make sure that there is not too much force on the cables, and that they are not caught.
6. Attach the end-cap.
KA332 Issue No. 1 3-2
Page 21
RTX 1000A Series User Manual
3.5 To Rotate the Housing (Figure 3-2)
CAUTION: Do not rotate the electronics housing on the transmitter more than 180 degrees relative to the pressure connection.
Two locking screws (hexagon socket screws) lock the electronics housing to the sensor body. To rotate the housing, loosen both of the screws and rotate the housing. When the angle is correct, tighten the screws.
Note: Do not remove the locking screws.
locking screws (hexagon socket screws)
Figure 3-2 Housing locking screws
3.6 Impulse Piping (Figure 3-3)
The purpose of arranging impulse piping for the specific application is to maintain a single phase of fluid in the piping and transmitter. Liquid applications should maintain a liquid state and allow any air or gas formation to travel up and away from the transmitter. Gas applications should allow the formation of liquids to drain down and away from the transmitter.
The pipe or tubing used for connection must be rated for continuous operation at the pipeline designed pressure and temperature. Threaded pipe fittings create voids (where air can be trapped) and increase the possibility of leaks. When installing the connecting tubing or impulse piping, the following apply:
Horizontally installed impulse piping must slope at least 1" per foot (approximately 75 mm per meter). For liquid and steam applications the piping must slope down towards the transmitter. For gas applications the piping must slope down away from the transmitter.
Impulse piping should be kept as short as possible and maintained at ambient temperature avoiding fluctuations and gradients.
3-3 KA332 Issue No. 1
Page 22
RTX 1000A Series User Manual
Installations outdoors for liquid or saturated gas service may require
insulation and heat tracing to prevent freezing.
For installations where the transmitter is more than 6 feet (1.8 m) from the tapping, the impulse piping must be supported to prevent sagging and vibration.
Impulse piping must be located in protected areas or against walls or ceilings. If routed across a floor, protective coverings or kick plates must be used. High temperature piping or equipment should be avoided.
Appropriate pipe sealing compound rated at the design piping temperature must be used on all threaded connections. When making threaded connections between stainless steel fittings, Loctite PST Sealant is recommended.
3.7 The Transmitter Pressure Connections
The recommended connection uses a two-valve manifold connected between the transmitter and the process pressure. Before connecting the transmitter remove the protection caps and carefully inspect the sealing face and threaded bore of the connection for damage.
Liquid service connections (Figure 3-3a)
Liquid measurement connections should be made to the side of the process line to avoid deposits of sediment. The transmitter should be mounted beside or below the connection so that gases vent into the process line.
Gas service connections (Figure 3-3b)
Gas measurement connections should be made to the top or side of the process line. The transmitter should be mounted beside or above the connection allowing any liquid to drain into the process line.
Steam service connections (Figure 3-3c)
Steam measurement connections should be made to the side of the process line. The transmitter should be mounted below the connection so that the piping remains filled with condensate. Live steam must not come into contact with the transmitter; to prevent this the lines should be filled with water or condensate.
KA332 Issue No. 1 3-4
Page 23
two-valve manifold
RTX 1000A Series User Manual
two-valve manifold
(b) Gas service(a) Liquid service
two-valve manifold
set length for cooling
plugged tee-piece for sealing fluid (water, condensate)
(c) Steam service
Figure 3-3 Piping arrangements
3-5 KA332 Issue No. 1
Page 24
RTX 1000A Series User Manual
3.8 Liquid Level Measurement (Figure 3-4)
Gauge pressure transmitters can be used to measure liquid level in an open or vented tank by measuring the hydrostatic pressure head. The head pressure can be calculated by multiplying the liquid height above the transmitter diaphragm by the specific gravity of the liquid.
The tank's volume and shape does not affect the head pressure. If the transmitter is mounted below the zero point (minimum level) of the measured range, zero suppression will be required.
maximum level
zero suppression
minimum level
Figure 3-4 Open tank level measurement
Calculations
Min. level = (40" x 1.1) inH2O
= 44" inH2O
Max level = ([40 + 200] x 1.1) inH2O
= (240 x 1.1) inH2O
= 264 inH2O
Range = 44 to 264 inH2O
(Span = 220 inH
2
O)
KA332 Issue No. 1 3-6
Page 25
RTX 1000A Series User Manual
3.9 Electrical Data
Note: If the equipment is certified for use in a hazardous (classified)
area, refer to the applicable "Control Drawing" for additional data.
WARNING: SWITCH OFF AND ISOLATE THE POWER SUPPLY BEFORE CONNECTING OR DISCONNECTING THE TRANSMITTER.
CAUTIONS:
1. The transmitter uses DC power in a 2-wire system to control current through a resistive load.
2. Do not apply more than 35 Volts to the loop circuit. The transmitter may be damaged.
General
The electrical installation must comply with local wiring codes and standards. To get the full performance from the transmitter, carefully choose the wiring scheme to be used and take care connecting the transmitter.
Power and maximum load (Figure 3-5)
The total loop resistance must include the connection wire resistance.
operating
maximum resistance
region
Resistive Loop Load - Ohms
Loop DC Power - Volts
Figure 3-5 Power and load requirements
3-7 KA332 Issue No. 1
Page 26
RTX 1000A Series User Manual
Wire selection (Table 3-1)
To get the best EMC performance, use shielded twisted pair cable for the field wiring.
Select a wire gauge for the required total length so the transmitter operates within the load requirements.
When using external power supplies, make sure the connection polarity allows current to flow into the +ve terminal and out of the -ve terminal. Refer to figure 3-7.
Table 3-1 Wire resistance
AWG Wire Diameter Loop Resistance
Inches mm Ohms/Foot Ohms/Meter
16 0.0508 (1.291) 0.0082 0.0264
18 0.0403 (1.024) 0.0128 0.0418
20 0.0320 (0.812) 0.0204 0.0666
22 0.0254 (0.644) 0.0322 0.1060
24 0.0201 (0.511) 0.0514 0.1680
Note: The typical values for resistance per length are doubled as
the circuit is a direct current loop.
Electrical conduit (Figure 3-6)
Use electrical conduit in accordance with local wiring codes. The electronics housing has two threaded holes for electrical conduit connections. The configuration in figure 3-6 prevents moisture getting into the housing. If conduit is not used, use the correct cable gland/plugs to seal the housing.
KA332 Issue No. 1 3-8
Page 27
RTX 1000A Series User Manual
plug
min: 2"
(50 mm)
flex Conduit
conduit tee
to drain
Figure 3-6 Electrical conduit configuration
Electrical connections (Figure 3-7)
The transmitter is a 2-wire loop powered device. The marks +ve and -ve identify the polarity of the connection terminals.
A label in the transmitter shows how to use the third terminal to measure the output current from the transmitter. In hazardous (classified) areas, do not use this third terminal.
power supply
Figure 3-7 Transmitter connections
Because the transmitter circuit is isolated from the housing, one of the signal wires (+ve or -ve) can be earthed (grounded) if necessary.
3-9 KA332 Issue No. 1
Page 28
RTX 1000A Series User Manual
3.10 System Checks
Leak test
Before the system is filled and/or commissioned, do a leak test with compressed air (or other inert compressed gas) or water. The minimum test pressure must be equal to the normal operating pressure. The maximum pressure is the MWP.
Apply pressure at a convenient point on the system.
Apply an applicable leak test solution to the impulse piping, valves,
transmitter connections and joints.
Look for a continuous stream of bubbles.
Bleed the system.
Do all the necessary repairs, and test the system again.
Return the system to the original configuration.
Transmitter test
Connect the necessary instruments to monitor the pressure signal . If necessary, connect a milliammeter to measure the output from the transmitter.
Apply power to the transmitter.
Apply the applicable pressure.
Monitor the pressure signal.
Refer to the 'Operation' section for the procedures to set up and operate the transmitter.
KA332 Issue No. 1 3-10
Page 29
RTX 1000A Series User Manual
4 OPERATION
Note: If the equipment is certified for use in a hazardous (classified)
area, refer to the applicable "Control Drawing" for additional data.
4.1 General
CAUTION: DO NOT over-pressurize the system.
Pressure ranges
The transmitter label shows the factory calibrated range and the maximum working pressure (MWP).
Start up procedure
When power is supplied to the transmitter, the output is set to the applicable alarm level (Refer to table 4-1). When the start up sequence is complete, the output changes to give the applicable process value.
During start up, the display (if applicable) shows these items:
1. the LCD test: -8.8.8.8.8
2. the software version (example: 1.00.00) When the start up sequence is complete, the display shows a value proportional
to the measured pressure.
Alarm/Error conditions
Refer to the 'Maintenance' section.
4-1 KA332 Issue No. 1
Page 30
RTX 1000A Series User Manual
4.2 Manual Configuration Facilities (Figure 4-1)
The manual configuration facilities (DIP switches and push buttons) are in the electronics module. To get access to the electronics module, remove the end-cap (with access to the electronics module).
DIP switches 1 to 4
push buttons:
- span (S)
- zero (Z)
optional display
Figure 4-1 Location of DIP switches and push buttons
Table 4-1 DIP switch operation
DIP Switch Function Set ON Set OFF
1 Write Protection To prevent accidental
2 Alarm level To use the high NAMUR
3 Damping To use the ON_Damping
4 Push button
operation
changes to the EEPROM values.
alarm (> 21 mA) when there is a transmitter failure.
factor. Default = 1 s
To change the range values (zero and/or span).
1) To change the range values (zero and/or span).
2) To set up the display - if applicable.
To use the low NAMUR alarm (< 3.6 mA) when there is a transmitter failure.
To use the OFF_Damping factor. Default = 0.1 s
To set up the display - if applicable.
KA332 Issue No. 1 4-2
Page 31
RTX 1000A Series User Manual
4.3 Manual Configuration - LCD (Table 4-2)
An optional LCD shows a value proportional to the measured pressure. Unless an alternative configuration is specified in the order, the factory configuration shows the pressure value as a percentage of the calibrated span (0% = 4 mA, 100% = 20 mA). To change the configuration, refer to table 4-2 ( 0 , 1 , and . show that the character flashes on the display).
Table 4-2 Steps to change the LCD configuration
Step Operation Result and/or example
1. Set DIP switches 1 and 4 to OFF.
2. Press S and Z together.
Set the decimal point position:
3. Press Z
Go to the next step (ZERO):
4. Wait 5 seconds or press S and Z together. 2ErO, then 0 . 0 0 0 0
Set the lower display value (LDV) to show an applicable 4 mA value:
5. a. To increase the value of a digit (0 ... 9, 0 ... ), press Z.
b. To select the next digit, press S
Go to the next step:
6. Wait 5 seconds or press S and Z together. 1 . 0 0 0 0
Set the value to positive or negative:
7. Press Z.
Go to the next step (SPAN):
8. Wait 5 seconds or press S and Z together. SPAn, then 0 . 0 0 0 0
Set the upper display value (UDV) to show an applicable 20 mA value:
9. Repeat steps 5 to 7. 1 . 0 0 0 0
Return to normal operation:
10. Wait 5 seconds or press S and Z together. 0 . 0 0 0 0
11. Set DIP switch 1 to ON. Refer to table 4-1
(Example device: - 1 to 1 psi)
Refer to table 4-1
_ _ _
_ _
.
_ _
_ _ _
.
0 . 0 0 0 0 1 . 0 0 0 0
1 . 0 0 0 0 1 . 0 0 0 0
1 . 0 0 0 0 - 1 . 0 0 0 0
_
_ _ _ _
.
4-3 KA332 Issue No. 1
Page 32
RTX 1000A Series User Manual
4.4 Manual Configuration - Calibration (Figure 4-2)
To get accurate results, do the calibration in conditions where the pressure and temperature are stable.
Equipment
A precision pressure calibrator such as the GE Druck DPI 605 or
DPI 610/615. The accuracy of the supplied pressure must be better than ±0.075%.
In safe areas, a 12 to 35 Volt DC power supply (separate or part of another system)
Fittings and tubing as required
excitation voltage and 4 mA to 20 mA signal
transmitter
precision pressure calibrator
Figure 4-2 Calibration set-up for safe areas
Calibration ranges
Set any span value from 10 to 100% of the URL. Refer to the 'Technical Data' section.
KA332 Issue No. 1 4-4
Page 33
RTX 1000A Series User Manual
Calibration adjustment - Lower range value (LRV)
1. Set DIP switch 1 to OFF and DIP switch 4 to ON (Refer to table 4-1).
2. Supply the necessary pressure and let the pressure become stable.
3. Press the S and Z buttons together. The optional display shows CAL, then a pressure value that flashes.
4.
Option - Return to normal operation without change:
Wait 25 seconds or press S and Z together.
Option - Save the new LRV:
Press the Z button. The signal output is set to 4 mA and the optional display shows a pressure value that does not flash.
Note: If the value is not in the applicable range, the value is ignored
and the optional display shows 'Error'.
5. Set DIP switch 1 to ON (Refer to table 4-1).
Calibration adjustment - Upper range value (URV)
To minimize measurement errors, do the LRV before the URV, then follow these steps:
1 - 3 As above.
4.
Option - Return to normal operation without change:
Wait 25 seconds or press S and Z together.
Option - Save the new URV:
Press the S button. The signal output is set to 20 mA and the optional display shows a pressure value that does not flash.
Note: If the value is not in the applicable range, the value is ignored
and the optional display shows 'Error'.
5. Set DIP switch 1 to ON (Refer to table 4-1).
4-5 KA332 Issue No. 1
Page 34
RTX 1000A Series User Manual
KA332 Issue No. 1 4-6
Page 35
RTX 1000A Series User Manual
5 MAINTENANCE
Note: If the equipment is certified for use in a hazardous (classified)
area, refer to the applicable "Control Drawing" for additional data.
5.1 General
The transmitter contains no moving parts and requires a minimum of maintenance.
Visual inspection
Inspect the transmitter for damage and corrosion. Any damage to the
transmitter must be assessed. If the housing is no longer sealed against water and/or dust, the transmitter must be replaced.
Cleaning
Clean the transmitter case with a damp lint-free cloth and mild
detergent.
Corrosion must be removed and the area of corrosion cleaned and, if necessary, neutralized.
If the product has been in contact with hazardous or toxic materials, obey all the applicable MSDS references and precautions when handling.
5-1
KA332 Issue No. 1
Page 36
RTX 1000A Series User Manual
5.2 Fault Finding (Figure 5-1)
If the measured pressure goes above URV or goes below LRV, the output signal will saturate at the following values:
Figure 5-1 Fault finding from the output signal
Failure alarm indications (Table 5-1)
If there is a specified fault condition, the transmitter output changes to the specified NAMUR alarm level. The alarm level is set by the position of DIP switch 2 (refer to table 4-1).
If applicable, the optional display shows an alarm code to help identify the fault (AL xx). Table 5-1 shows some of the codes. If there are several fault conditions, the alarm code is the hexadecimal sum of all the applicable codes.
Table 5-1 LCD alarm codes and error messages
Code Possible cause To correct the error
AL 02 Too much positive or negative pressure.
DPM error Power off, wait 25 seconds, then
AL 04 DPM data not received Power off, wait 25 seconds, then
LCD adjustment has loosened the DPM cable connection on the PCB.
AL 08 Examine the DPM cable
Error Refer to section 2 for the specified
Prot Set DIP switch 1 to OFF, then
LCD adjustment has loosened the DPM cable connection on the PCB.
Configuration error. The range is not in the specified limits for the device.
Configuration error. DIP switch 1 set to ON (Write protect).
Supply pressure in the specified limits for the device.
power on again.
power on again.
Examine the DPM cable connection (Figure 3-1).
connection (Figure 3-1).
range limits.
follow the procedures in Section 4.
If you cannot identify the code or the fault condition does not change, contact an approved service agent.
KA332 Issue No. 1
5-2
Page 37
RTX 1000A Series User Manual
Over/under range
If the measured pressure goes above or below the set range of the transmitter, the electronics module causes the transmitter output to change.
When the measured pressure is under range, the transmitter output continues below the 4.0 mA level until it reaches 3.8 mA (figure 5-1). When the measured pressure is over range, the transmitter output continues above the 20.0 mA level until it reaches 20.5 mA (figure 5-1).
If applicable, the optional display will also show a flashing pressure value.
5.3 Returned Goods Procedure
If the transmitter becomes unserviceable or requires calibration, it can be returned to the GE Druck Service Department.
Please contact our Service Department, either by 'phone or fax, to obtain a Returned Material Authorization (RMA) number. You will need to give the following information:
Product (i.e. RTX 1000A)
Pressure range
Serial number
Details of defect/work to be undertaken
Calibration traceability requirements
Operating conditions
Safety Precautions
You must also tell us if the product has been in contact with hazardous or toxic materials. Please supply the applicable MSDS references and precautions to be taken when handling.
Important Notice
Service or calibration by unauthorized sources will affect the warranty and may not guarantee further performance. If the equipment has "Hazardous (Classified) area" approval, the approval will also be invalid.
5-3
KA332 Issue No. 1
Page 38
RTX 1000A Series User Manual
KA332 Issue No. 1
5-4
Loading...