Det-Tronics EA2100CG User Manual

DET -TR O NICS
®
INSTRUCTIONS
Eagle 2000™
Hazard Event Monitoring System
7/99 Form 95-8424-02
INSTRUCTIONS
EAGLE 2000
Hazard Event Monitoring System
Section I
System Overview
NOTE
This manual covers the basic operation of the communication module, digital communication unit, gateway, network extender and relay module. It will not cover any specific detector, host device or Operator Interface Station. Refer to the appropri­ate instruction manual for complete information relating to these devices. While this manual cov­ers general practices and procedures for installa­tion and wiring of the Eagle 2000 system, always refer to the instruction manual provided with each device for specific instructions.
APPLICATION
Det-Tronics’ Eagle 2000 is a state-of-the-art hazard detection monitoring system consisting of any combina­tion of addressable flame, gas or environmental detec­tors. The system communicates through an RS422 or RS232 serial port utilizing Modbus®protocol to make the system’s data available to a variety of host devices.
FEATURES
• Field addressable
• Utilizes industry standard Modbus protocol
• Comprehensive data acquisition
• Up to 250 devices per loop on a single twisted pair of wires
• Accommodates a variety of devices with 4 to 20 ma or relay contact inputs
• Non-volatile memory for alarm and calibration data
• Fault tolerant communication loop
• Built in diagnostics
• Compatible with Det-Tronics flame, gas or environ­mental sensors
• Sensor sensitivity trending.
SYSTEM DESCRIPTION
The Eagle system can consist of the following components:
Detector Communication Gateway (EA2100CG) Digital Communication Unit (EA2200DCU) Communication Module (EA2300CM) Network Extender (EA2400NE) Relay Module (EA2500RM) A host device
Shielded twisted pair cable (22 AWG, Level 4) is used to wire all nodes in a serial communication loop starting and ending at the gateway. Refer to Figure 1.
DETECTOR
The Eagle system is compatible with a variety of detec­tors including flame, combustible gas, toxic gas, oxy­gen, and environmental monitoring devices. The output of the detector can be a 4 to 20 ma signal, or a digital contact signal such as a switch closure or relay contact.
DET -TR O NICS
®
©Detector Electronics Corporation 1999 7/99 95-8424-02
Modbus is a registered trademark of Modicon Inc.
422/232
OR
60 SENSORS AND / OR 2000 METER LOOP
EAGLEVISION
OIS
POWER SUPPLY
PLC
DCS
COMMUNICATION
GATEWAY
(EA2100CG)
PORT (2)
NODE 2
NODE 3
NODE 4
NODE 5
OR
PORT (1)
NODE 1
DIGITAL
COMMUNICATION UNIT
(EA2200DCU)
DET-TRONICS
FLAME
DETECTION
DET-TRONICS
GAS
DETECTION
DET-TRONICS
ENVIRONMENTAL
MONITORING
COMMUNICATION MODULES (EA2300CM)
NETWORK
EXTENDER
(EA2400NE)
A1551
A1644
NODE 1 NODE 8
NODE 3 NODE 6
NODE 2 NODE 7
NODE 4 NODE 5
MAIN
GATEWAY
A1645
MAIN
GATEWAY
NODE 1 NODE 8
NODE 3 NODE 6
NODE 2 NODE 7
NODE 4 NODE 5
PATH A PATH B
WIRING FAULT
A1646
MAIN
GATEWAY
NODE 1 NODE 8
NODE 3 NODE 6
NODE 2 NODE 7
NODE 4 NODE 5
PATH A PATH B
WIRING FAULT
A1647
MAIN
GATEWAY
NODE 1
NODE 6
NODE 2
RELAY
MODULE
NODE 5
NODE 3 NODE 4
PATH A PATH B
AUXILIARY
GATEWAY
WIRING FAULT
3.7
(9.4)
3.3
(8.4)
4.1
(10.4)
B1482
4.5
(11.4)
4.1
(10.4)
0.3 DIA. (0.8)
3/4" NPT (2)
RELAY
RELAY
ALARM
RELAY
GND
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
DO NOT RUN WIRES IN THIS AREA.  KEEP CLEAR FOR RIBBON CABLE CONNECTOR.
A1556
MAGNETIC SWITCH * EARTH GROUND TERMINAL
6.5
(16.5)
3.38 (8.4)
4.1 (10.4)
B1520
4.5 (11.4)
4.1
(10.4)
3/4" NPT (2)
0.3 DIA. (0.8)
Section IV
EA2100CG
Communication Gateway
APPLICATION
The gateway provides the communication link between a Det-Tronics addressable detector and the host device. Registers in the gateway are used for passing information between the host and communication modules. The gate­way communicates with the host device through a serial interface port (RS232 or RS422) using Modbus protocol.
Local annunciation capability is provided utilizing a three digit display, LEDs and a twenty segment bar graph dis­play. When a detector is in alar m or when a calibration or fault event occurs, the detector’s address and detec­tor type are identified on the digital display, and the per­centage of full scale is indicated on the bar graph.
FEATURES
• Utilizes industry standard Modbus protocol
• Bar graph and digital displays
• Alarm, calibrate and fault LEDs
• Transformer isolation of network ports
• Programmable relay outputs
• Mounts in standard Q4004 rack
• Multiple gateways to enhance reliability or support additional host devices
• EMI/RFI hardened.
SPECIFICATIONS
INPUT VOLTAGE—
18 to 32 vdc.
POWER CONSUMPTION—
Operating: 325 ma at 24 vdc maximum. Startup: 1.0 ampere at 24 vdc, momentary.
I/O PORTS—
Host Port: The gateway is a “Modbus slave” device and communicates with a host device through a serial port using Modbus protocol. The serial port provided for the host can be configured as either RS232 or RS422.
Network Port: Two 78.5 kbps communication ports pro­vide the start and end of the loop upon which the sen­sors and their communication modules reside. The loop wiring is level 4, 22 AWG shielded twisted pair. The wiring is transformer coupled to protect the transceivers.
TEMPERATURE RANGE—
+32°F to +140°F (0°C to +60°C).
HUMIDITY RANGE—
0 to 90% RH, non-condensing.
SHIPPING WEIGHT (Approximate)—
2.6 lb (1.2 kg).
DIMENSIONS—
See Figure 9.
DESCRIPTION
The Eagle gateway transmits information from the com­munication modules to any device that can act as a Modbus Master. This interface between the gateway and host device conforms to the Modbus RTU standard.
For systems requiring a higher throughput than the Modbus 19.2 kbaud standard, the EagleVision Operator Interface Station can connect to the gateway at 57.6 kbaud.
The Eagle system is designed to operate with up to 4 gate­ways (one main and three auxiliary) on a single communi­cation loop. Each gateway is configured by DIP switches to function either as a “main” or an “auxiliary” gateway. Both gateways contain identical software and hardware and differ only in respect to their function within the system.
MAIN GATEWAY
The main gateway is used by the host device to perform device configuration. It also generates a periodic time and date broadcast as well as a heartbeat signal on the communication loop for use by the devices on the loop in their fault isolation schemes. As long as wiring integrity is maintained, all “normal” gateway initiated communication on the loop originates from the primary communication port (Com. 1). If a fault occurs, commu­nication takes place from both the primary and the sec­ondary communication port (Com. 2).
A relay in the gateway terminates the communication wiring during normal operation. In the event of a power loss, a communication pass-through circuit is created.
9 95-8424
9.3 (23.6)
2.0
(5.0)
7.0
(17.8)
A1496
Figure 9—Gateway Dimensions in Inches (Centimeters)
RELAY 1
100
90
80
70
60
50
40
30
20
10
RELAY 2
RELAY 3
RELAY 4
FAULT
RESET
RELAY 1 LED
RELAY 2 LED
RELAY 3 LED
RESET PUSHBUTTON
DIGITAL DISPLAY
BAR GRAPH DISPLAY
RELAY 4 LED
FAULT LED
A1542
A1543
GATEWAY GATEWAYGATEWAY
MULTIPLEXER
HOST
NODE NODENODENODE NODE
HOST
GATEWAY
A1596
TOTAL LOOP CAPACITY: 60 NODES, 2000 METERS
NODE NODENODENODE NODE
HOST
TOTAL LOOP CAPACITY: 180 NODES, 6000 METERS
A1597
NODE NODE NODENODE
NODE
GATEWAY
NODENODENODE
NODENODE NODE
NETWORK
EXTENDER
NODE
NODENODE
NODE NODENODE
NODE
NETWORK
EXTENDER
NODE NODE
NODE NODENODENODE NODE
HOST
A1598
TOTAL LOOP CAPACITY: 60 NODES, 2000 METERS
HOST
MAIN
GATEWAY
AUXILIARY GATEWAY
NOTE: SHIELDS GROUNDED AT GATEWAY ONLY.  SHIELDS CONNECTED TO EACH OTHER (NOT TO GROUND) AT EACH NODE BUT OPEN AT ONE NODE NEAR MIDDLE OF LOOP.
B1611
NODE NODE
NODE
NODE NODE
GATEWAY
GROUND SHIELD
AT ONE END ONLY
A1599
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
A
A
B
B
22 AWG LEVEL 4
SHIELDED TWISTED PAIR
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
+
+
C NO NC COM IN 1 COM IN 2 4 TO 20 MA
– +
DIGITAL INPUT 1
DIGITAL INPUT 2
RELAY
DETECTOR POWER
(24 VDC)
1 2 3 4 5 6 7 8
1 2 3 4
1 2 4 8 16 32 64 128
OPEN OPEN
}
LEAVE IN
OPEN POSITION
NODE ADDRESS EQUALS THE ADDED VALUE OF ALL CLOSED ROCKER SWITCHES
A1557
BINARY VALUE
1 2 3 4 5 6 7 8 9
18 17 16 15 14 13 12 11 10
CHASSIS GROUND
ALARM ALARM CALIBRATE CALIBRATE FAULT FAULT
4 TO 20 MA RESET
+ –
EAGLE U8800
SENSOR
A1650
1 2 3 4 5 6 7 8 9
18 17 16 15 14 13 12 11 10
CHASSIS GROUND
COMMUNICATION MODULE
22 AWG SHIELDED TWISTED PAIR
NOTES
1. WIRING TYPE
2.SHIELD CONNECTED AT ONE END ONLY.
GATEWAY/
COM MOD
– +
POWER
SUPPLY
GATEWAY/
COM MOD
ALARM ALARM CALIBRATE CALIBRATE FAULT FAULT
+ –
RESET
– +
EAGLE U8700
(JUMPERED FOR NON-ISOLATED CURRENT OUTPUT)
SENSOR
POWER
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
A B A B
+ + – –
RELAY COMMON
+ –
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
A B A B
+ + – –
RELAY COMMON
+ –
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
COMMUNICATION MODULE
4 TO 20 MA
POWER
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
COMMUNICATION MODULE/DCU
18 17 16 15 14 13 12 11 10
RED BLACK GREEN
SENSOR
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
422 TXD
+ 
422 TXD – CHASSIS GND
+ –
422 RXD +  422 RXD – EXT RESET COM 232 TXD
232 RXD COM A  B A  B
C NO NC
C NO NC
C NO NC
C NO NC
C NO NC
CHASSIS GND
GATEWAY
K1
K2
K3
K4
FAULT
+
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
A B A B
+ + – –
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
COMMUNICATION MODULE/DCU
18 17 16 15 14 13 12 11 10
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
24 VDC
NET 0
NET 1
24 VDC
A1588
22 AWG SHIELDED TWISTED PAIR
WIRING TYPE
RED BLACK GREEN
SENSOR
DETECTOR POWER
(24 VDC)
CHASSIS
CHASSIS A B A B
+ + – –
RELAY COMMON
1 2 3 4 5 6 7 8 9
18 17 16 15 14 13 12 11 10
A1549
1 2 3 4 5 6 7 8 9
POWER SUPPLY
18 17 16 15 14 13 12 11 10
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 2 3 4 5 6 7 8 9
18 17 16 15 14 13 12 11 10
RED
WHITE
NC
BLACK
SENSOR
GAS TRANSMITTER
+
RED
WHITE
NC
BLACK
SENSOR
GAS TRANSMITTER
RED
WHITE
NC
BLACK
SENSOR
GAS TRANSMITTER
22 AWG SHIELDED TWISTED PAIR
NOTES
1. WIRING TYPE
2.THREE MODULES SHOWN, 250 MODULES MAXIMUM.
3.SHIELD CONNECTED AT ONE END ONLY.
COMMUNICATION MODULE/DCU
GATEWAY
COMMUNICATION MODULE/DCU
COMMUNICATION MODULE/DCU
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
A B A B
+ + – –
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
422 TXD
+ 
422 TXD – CHASSIS GND
+ –
422 RXD +  422 RXD – EXT RESET COM 232 TXD
232 RXD COM A  B A  B
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
CHASSIS GND
K1
K2
K3
K4
FAULT
NET 0
NET 1
24 VDC
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
A B A B
+ + – –
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
A B A B
+ + – –
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
POWER
4 TO 20
+ –
POWER
4 TO 20
+ –
POWER
4 TO 20
+ –
18
17
16
15
14
13
12
11
10
123456789
A1652
123456789
GATEWAY
123456789
COMMUNICATION MODULE
18
17
16
15
14
13
12
11
10
18
17
16
15
14
13
12
11
10
U7698E
U7652C4
FAULT FIRE
oi
+
U7602
C 
NO
FAULT
NC
4 TO 20CNO
 FIRE
NC
END OF LINE RESISTOR
FIRE PANEL
GROUND
FAULT 
MONITOR
22 AWG SHIELDED TWISTED PAIR
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
ABA
B
++–
–
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
ABA
B
++–
–
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
ABA
B
++–
–
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
COMMUNICATION MODULE
COMMUNICATION MODULE
4 TO 20
123456789
10
+–+
11
12
13
14
15
16
17
18
19
20
+ 
– +–
o
i
FIRE
FAULT
123456789
123456789
+
CON 2 CON 1
FIRE
FAULT
4 TO 20
+
o
i
24
VDC
+ 
(A)
(B)
(C)
1.48 (37.59)
(D)
A1475
ALL CONTROLLER CAGES REQUIRE A MINIMUM OF 10.12 INCHES (257.1 MM) DEPTH CLEARANCE
(E)
1
A1476
FIRE CONTROLLERS ARE APPROX. TWO INCHES WIDE AND REQUIRE TWO GUIDE RAILS FOR INSERTION. PLACE THE RETAINING CLIP BETWEEN RAILS TO FORM SETS, LEAVE A GAP BETWEEN SETS.
SET
SETGAP
1
2 3 2
THE Q4004 CONTROLLER CAGE HAS BEEN MODIFIED
TO ACCOMMODATE EITHER FIRE OR GAS CONTROLLERS
OR ANY COMBINATION OF THE TWO.
BY FOLLOWING THE INSTRUCTIONS BELOW, THE CAGE
CAN BE SET UP TO ANY CONFIGURATION.
2
TO INSERT A BLANK PANEL, PLACE A CLIP IN THE TOP BRACKET IN LINE WITH THE CLIP IN THE BOTTOM BRACKET.
3
GAS CONTROLLERS ARE APPROX. ONE INCH WIDE AND REQUIRE ONE RAIL FOR INSERTION. PLACE CLIPS IN LINE WITH GUIDE RAILS, CAGES WILL ACCEPT AS MANY GAS CONTROLLERS AS RAILS PROVIDED.
RACK PART NUMBER CONTROLLER TYPE 005269-XXX POSITIONS FOR: HT: DIM. (A) DIM. (B) DIM. (C) DIM. (D) DIM. (E) WEIGHT
FIRE GAS INCH MM INCH MM INCH MM INCH MM INCH MM LB KG
4U –001 8 16 4U 19.00 482.6 18.30 464.8 17.36 440.9 4.00 101.6 6.97 177.1 9.3 4.2 4U –002 6 12 4U 15.06 382.6 14.36 364.7 13.42 340.9 7.6 3.5 4U –003 4 8 4U 11.13 282.6 10.43 264.9 9.49 241.1 5.9 2.7 4U –004 3 6 4U 9.16 232.7 8.46 214.9 7.52 191.0 5.1 2.3 4U –005 2 4 4U 7.19 182.7 6.49 164.9 5.55 141.0 4.2 1.9 4U –006 1 2 4U 5.22 132.6 4.52 114.8 3.58 90.9 3.1 1.4 3U –007 16 3U 19.00 482.6 18.30 464.8 17.36 440.9 2.25 57.15 5.22 132.6 9.3 4.2 3U –008 12 3U 15.06 382.6 14.36 364.7 13.42 340.9 7.6 3.5 3U –008 8 3U 11.13 282.6 10.43 264.9 9.49 241.1 5.9 2.7 3U –010 6 3U 9.16 232.7 8.46 214.9 7.52 191.0 5.1 2.3 3U –011 4 3U 7.19 182.7 6.49 164.9 5.55 141.0 4.2 1.9 3U –012 2 3U 5.22 132.6 4.52 114.8 3.58 90.9 3.1 1.4
123456789
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
422 TXD
+ 
422 TXD –
CHASSIS GND
+
422 RXD + 
422 RXD –
EXT RESET
COM
232 TXD 232 RXD
COM
A BA 
B
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
CHASSIS GND
K1
K2
K3
K4
FAULT
NET 0
NET 1
24 VDC
A1648
18
17
16
15
14
13
12
11
10
ALARM
ALARM
CALIBRATE
CALIBRATE
FAULT
FAULT
4 TO 20
RESET
+
EAGLE U8700/U8800
SENSOR
123456789
18
17
16
15
14
13
12
11
10
A1545
123456789
COMMUNICATION MODULE/DCU
OIS
123456789
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
GATEWAY
COMMUNICATION MODULE/DCU
123456789
COMMUNICATION MODULE/DCU
18
17
16
15
14
13
12
11
10
22 AWG SHIELDED TWISTED PAIR
NOTES
1. WIRING TYPE
2.SHIELD CONNECTED AT ONE END ONLY
3. OIS: OPERATOR INTERFACE SYSTEM
GREEN
RED
BLACK
POWER
SUPPLY
+ –
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
ABA
B
++–
–
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
422 TXD
+ 
422 TXD –
CHASSIS GND
+
422 RXD + 
422 RXD –
EXT RESET
COM
232 TXD 232 RXD
COM
A BA 
B
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
CHASSIS GND
K1
K2
K3
K4
FAULT
NET 0
NET 1
24 VDC
CHASSIS
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
ABA
B
++–
–
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
ABA
B
++–
–
RELAY COMMON
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
POWER
NOTE 3
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
COMMUNICATION MODULE/DCU
18 17 16 15 14 13 12 11 10
RED BLACK GREEN
SENSOR
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
422 TXD
+ 
422 TXD – CHASSIS GND
+ –
422 RXD +  422 RXD – EXT RESET COM 232 TXD
232 RXD COM A  B A  B
C NO NC
C NO NC
C NO NC
C NO NC
C NO NC
CHASSIS GND
GATEWAY
K1
K2
K3
K4
FAULT
+
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
+
–
4 TO 20 MA IN
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
DETECTOR POWER
(24 VDC)
RELAY MODULE
18 17 16 15 14 13 12 11 10
24 VDC POWER INPUT
NETWORK IN
NETWORK OUT
IN 2
COM
IN 1
COM
NC
NO
DIGITAL INPUT 2
DIGITAL INPUT 1
RELAY
24 VDC
NET 0
NET 1
24 VDC
A1649
CHASSIS A  B A  B 
+ + – –
RELAY COMMON
CHASSIS A B A B
+ + – –
RELAY COMMON
SHIELD
2 1
+ + – –
SHIELD
2 1
NETWORK EXTENDER
COM A
24 VDC
COM B
NOTE:
22 AWG SHIELDED TWISTED PAIR
1. WIRING TYPE
2. SEE TEXT FOR SHIELD GROUNDING INSTRUCTIONS
PARITY ENABLE (OFF = NO PARITY, ON = PARITY ENABLED) BAUD RATE BIT 2 (MSB) BAUD RATE BIT 1 BAUD RATE BIT 0 (LSB)
PARITY TYPE (OFF = ODD, ON = EVEN)
NUMBER OF STOP BITS (OFF = 1, ON = 2)
RS-422/RS-485 (OFF = RS-422, ON = RS-485) NUMBER OF DATA BITS (OFF = 7, ON = 8)
1 2 3 4 5 6 7 8
S6 SOFTWARE SERIAL PORT CONFIGURATIONS (CHANNEL 1 ONLY)
0 = 1200 1 = 2400 2 = 9600
3 = 19200 4 = 57600 5 = 38400
6 = 300 7 = 4800
A1554
CHANNEL 1 RS-422 RECEIVER ENABLE CHANNEL 1 RS-232 RECEIVER ENABLE CHANNEL 0 RS-422 RECEIVER ENABLE CHANNEL 0 RS-232 RECEIVER ENABLE
CHANNEL 0 RS-422 TRANSMITTER TERMINATION
CHANNEL 0 RS-422 RECEIVER TERMINATION
CHANNEL 1 RS-422 RECEIVER TERMINATION CHANNEL 1 RS-422 TRANSMITTER TERMINATION
1 2 3 4 5 6 7 8
S5 HARDWARE SERIAL PORT CONFIGURATIONS
MODBUS ADDRESS BIT 3 MODBUS ADDRESS BIT 2 MODBUS ADDRESS BIT 1 MODBUS ADDRESS BIT 0 (LSB)
MODBUS ADDRESS BIT 4
MODBUS ADDRESS BIT 5
MODBUS ADDRESS BIT 7 (MSB) MODBUS ADDRESS BIT 6
1 2 3 4 5 6 7 8
S7 MODBUS ADDRESS
UNDEFINED UNDEFINED GATEWAY ADDRESS BIT 1 (MSB) GATEWAY ADDRESS BIT 0 (LSB)
UNDEFINED
NON-LATCHING GATEWAY RELAYS
MAIN/AUXILIARY GATEWAY (OFF = AUX, ON = MAIN) BACKUP GATEWAY
1 2 3 4 5 6 7 8
S8 LON CONFIGURATION
S8S7S6S5
A1546
3 SEC 3 SEC 3 SEC 3 SEC
ACCEPT ZERO ACCEPT SPAN
REED SWITCH
ANALOG IN
LED
1
UNCONTROLLED ANALOG SIGNAL
A1555
3 SEC 3 SEC 3 SEC 3 SEC
ACCEPT ZERO ACCEPT SPAN
3O SEC MIN
3O SEC MIN
3O SEC MIN
RECORD SPAN
TRENDING SPAN
REED SWITCH
ANALOG IN
LED
U8800 INPUT
ANALOG IN LED
IN ONE
ACCEPT ZERO ACCEPT SPAN
3 SEC
3 SEC
OLD SPAN
CALIBRATED SPAN
1
SEC
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
A1555
A1555
3 SEC 3 SEC 3 SEC 3 SEC
3 SEC 3 SEC
ACCEPT ZERO ACCEPT SPAN
ACCEPT ZERO ACCEPT SPAN
REMOVE GAS
SPAN GAS
ZERO GAS
3O SEC MIN
3O SEC MIN
3O SEC MIN
RECORD SPAN
TRENDING SPAN
REED SWITCH
ANALOG IN
LED
REED SWITCH
ANALOG IN
LED
U8800 INPUT
ANALOG IN LED
IN ONE
ACCEPT ZERO ACCEPT SPAN
3 SEC
3 SEC
OLD SPAN
CALIBRATED SPAN
1
SEC
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
A1555
A1555
A1555
3O SEC MIN
3 SEC 3 SEC 3 SEC 3 SEC
3 SEC 3 SEC
3 SEC 3 SEC 3 SEC
ACCEPT ZERO ACCEPT SPAN
ACCEPT ZERO
ACCEPT ZERO ACCEPT SPAN
FRESH AIR
REMOVE GAS
SPAN GAS
ZERO GAS
3O SEC MIN
3O SEC MIN
3O SEC MIN
RECORD SPAN
TRENDING SPAN
REED SWITCH
ANALOG IN
LED
REED SWITCH ANALOG IN
LED
REED SWITCH
ANALOG IN
LED
U8800 INPUT
ANALOG IN LED
IN ONE
A1555
ACCEPT ZERO ACCEPT SPAN
3 SEC
3 SEC
OLD SPAN
CALIBRATED SPAN
1
SEC
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
A1555
A1555
A1555
3O SEC MIN
3 SEC 3 SEC 3 SEC
ACCEPT ZERO
ZERO
IN ONE ANALOG IN
LED
A1555
UNCONTROLLED ANALOG SIGNAL
3 SEC 3 SEC 3 SEC 3 SEC
3 SEC 3 SEC
3 SEC 3 SEC 3 SEC
ACCEPT ZERO ACCEPT SPAN
ACCEPT ZERO
ACCEPT ZERO ACCEPT SPAN
FRESH AIR
REMOVE GAS
SPAN GAS
ZERO GAS
3O SEC MIN
3O SEC MIN
3O SEC MIN
RECORD SPAN
TRENDING SPAN
REED SWITCH
ANALOG IN
LED
REED SWITCH
ANALOG IN
LED
REED SWITCH
ANALOG IN
LED
U8800 INPUT
ANALOG IN LED
IN ONE
A1555
ACCEPT ZERO ACCEPT SPAN
3 SEC
3 SEC
OLD SPAN
CALIBRATED SPAN
1
SEC
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
UNCONTROLLED ANALOG SIGNAL
A1555
A1555
A1555
3O SEC MIN