Det-Tronics C7052J UV-IR User Manual

NOTE
Not compliant to FM 3260 (2000).
APPLICATION
The R7495B/C7052J UV/IR Flame Detection System is designed to provide continuous and automated fire pro­tection in applications where the use of ultraviolet (UV) or infrared (IR) detectors alone can result in unwanted (false) alarms. The R7495B/C7052J system features a flame detector that uses both a UV and a single fre­quency IR sensing device mounted side-by-side on a junction box assembly.
When used alone, a UV detector can respond to sources of radiation besides fire, such as lightning, x­rays or arc welding. A UV detector does not respond to the radiation emitted by flickering hot objects. Likewise, an IR detector can respond to infrared radiation sources besides hydrocarbon fires, such as flickering hot objects. An IR detector does not respond to radiation from lightning, x-rays or arc welding. Since both UV and IR sensors respond to hydrocarbon fires but have virtually no false alarm sources in common, the R7495B/C7052J UV/IR system provides reliable flame detection while being virtually immune to false alarms.
The detector junction box contains a power supply and signal processing circuitry for the sensors. A fire signal is generated in the detector junction box and sent to the controller only when a fire is simultaneously detected by both the UV and IR sensors. Since the two detecting elements independently monitor different portions of the radiation spectrum and have virtually no sources of out­put actuation in common besides fire, a high degree of false alarm immunity is achieved. The controller contin-
uously monitors up to eight UV/IR detectors and ener­gizes the appropriate relay outputs in response to a fire signal from the detectors. Fire relays are provided in the controller: two instant (alarm) relays, two delayed (fire) relays, and a system fault relay.
Typical applications include:
— Transport loading terminals — Offshore drilling and production platforms — Tank farms — Refineries — Butane and propane loading and storage — Pipeline compressor stations — Turbine enclosures — Aircraft Hangars — Paint Spray Booths — Chemical and petrochemical production
DET-TRONICS
®
©Detector Electronics Corporation 2003 4/03 95-8302-02
INSTRUCTIONS
UV/IR Flame Detection System
R7495B Controller
C7052J Detector
*o
i
is Detector Electronics' Trademark for its patented Optical Integrity Systems, U.S. Patent 3,952,196, United Kingdom Patent 1,534,969, Canada Patent 1,059,598.
2
FEATURES
• Controller continuously monitors up to eight detec­tors.
• Detectors can be divided into either two groups of up to four detectors, each with its own alarm and fire zone output, or one group of up to eight detec­tors with two alarm and two fire zone outputs.
• Two fire zone relays, two alarm relays and a fault relay provided.
• Ignores false alarm sources such as arc welding, x­rays, gamma radiation and radiation from flickering hot objects.
• Fast response - typically 1 to 5 seconds for an intense hydrocarbon fire.
• Field adjustable sensitivity and time delay.
• Front panel LEDs indicate fire response and fault conditions.
• Microprocessor control provides continuous diag­nostics and automatic fault indication.
• Automatic Optical Integrity (o
i
) for both UV and IR
sensors.
• Explosion-proof (flame-proof) detector housing
•FM approved, CSA and BASEEFA/CENELEC certi­fied.
• Voting circuitry for improved false alarm rejection.
SYSTEM DESCRIPTION
Detector
The C7052J UV/IR Flame Detector is an explosion-proof device that consists of a UV sensor and an IR sensor mounted side-by-side on a junction box. This mounting arrangement allows both sensors to monitor the same hazardous location with a 80 degree cone of vision. Up to eight C7052J Detectors can be connected to one R7495B Controller.
The UV sensor responds to high energy radiation with wavelengths from .185 to .245 microns (1850 to 2450 angstroms). See Figure 1. It detects radiation from sources such as fire, arc welding, lightning, x-rays and
gamma rays. However, it is not sensitive to radiation from the sun or radiation from flickering hot objects (blackbodies).
The IR sensor is sensitive to IR radiation over the range of 4.2 to 4.7 microns. See Figure 1. It is not sensitive to radiation from the sun, lightning, x-rays, gamma rays, or arc welding. However, it will respond to fire and flicker­ing blackbody (heat) radiation sources. IR radiation that is generated by a hydrocarbon flame which reaches the detector in pulsations or “flicker.” These pulsations are present in all flames and are created by turbulent mix­ing of fuel with air. For this reason, electronic circuitry in the detector monitors the output of the IR sensing ele­ment for the appropriate amplitude and a flicker fre­quency between 1 and 16 cycles per second. If both the radiation and flicker requirements are met, a fire sig­nal is generated. This dual criteria for the IR detector results in increased reliability. However, since the IR detector responds only to hydrocarbon fires, the UV/IR detector cannot respond to non-hydrocarbon fires such as burning hydrogen, ammonia or metal.
The detector junction box contains a +290 vdc power supply for the UV sensor as well as circuitry to process signals from both sensors. When both sensors detect a fire, the IR sensor activates the circuitry in the junction box to allow the signal from the UV sensor to be sent to the controller. By using both a UV and an IR sensor, the C7052J is able to discriminate virtually all false alarm sources from a true hydrocarbon fire.
o
i
Feature
Both sensors are equipped with the automatic Optical Integrity (
o
i
) test feature. This patented system assures proper operation of the detector by checking the clean­liness of the optical surfaces, sensitivity of the sensors, and proper functioning of the electronic components of the detector once every minute. If a problem should occur, it is quickly detected. The
o
i
test is accom­plished without the use of an external UV or IR source. To minimize the possibility of nuisance fault signals, the detector must fail the automatic
o
i
test three consecu-
tive times for an
o
i
fault signal to be generated.
The
o
i
test is initiated by a signal from the controller
which causes actuation of the
o
i
test lamps. A calibrat-
ed low level test beam is generated by the
o
i
test
Figure 1—Detector Sensitivity Range
100
ATMOSPHERIC
TRANSMISSION
ULTRAVIOLET SENSOR RESPONSE
75
50
25
0
ULTRAVIOLET
SOLAR RADIATION REACHING THE EARTH
VISIBLE INFRARED
WAVELENGTH (MICRONS)
INFRARED SENSOR RESPONSE
5.04.03.02.01.51.00.90.80.70.60.50.40.30.20.1
A1516
lamps, as shown in Figure 2. Although the test lamps are mounted in the same enclosure with the sensor, an optical shield prevents the test beam from reaching the sensor directly. The test beam travels out through the viewing window, where it encounters the reflective
o
i
ring and is directed back through the window to the sensor. Electronic circuitry in the detector then evalu­ates the return signal from the sensor and generates the appropriate output response. Since the test beam must pass through the same portion of the viewing window as radiation produced by a fire, this test of the ability of the detector to “see” a flame has a high degree of reliability.
Detector Enclosure
The C7052J features an explosion-proof, dust-tight, and water-tight (NEMA 4/IP66) housing that is designed for installation in hazardous locations in both indoor and outdoor environments. The enclosure is FM approved, CSA certified, and BASEEFA/CENELEC approved.
Controller
The R7495B is designed for use with 24 volt dc power supplies, but will operate from any direct current supply between 18 and 32 volts. The unit will tolerate tran­sients such as those that can occur when fully dis­charged batteries are placed on charge. When power is present at the R7495B Controller, it is indicated by a continuously energized green LED. All other lights and displays on the R7495B front panel are normally off, but may be periodically checked for operation by pressing the RESET/LAMP TEST button located directly below the POWER light as illustrated in Figure 3. It is not neces­sary for the controller to be in the TEST mode when this check is performed.
With power applied and the TEST/NORM toggle switch in the normal mode, the R7495B Controller continuously cycles through the Automatic Optical Integrity test (see the “
o
i
Feature” section), checking each detector and its wiring. At the same time, it monitors the system for any status changes, such as a fault, a “fire” signal from one of the detectors or zones, or a change in the setting of the TEST/NORM toggle switch. If a status change occurs, the controller will respond accordingly by indi­cating the change on the front panel LEDs and generat­ing the appropriate output.
Front Panel
The front panel of the R7495B provides switches for selecting mode of operation and resetting the controller. It also provides LEDs for indicating system status infor­mation. Figure 3 illustrates the front panel of the con­troller.
3 95-8302
Figure 2—o
i
Function within th e Detector
Figure 3—R7495B Controller Front Panel
UV TEST LAMP
OPTICAL SHIELD
UV DETECTOR
SNAP-IN oi RING
o
SNAP-IN
3
5
POWER LED
RING
i
ALARM LED
A1703
VIEWING WINDOW
IR TEST LAMP (2)
IR SENSING ELEMENT
IR DETECTOR
OPTICAL FILTER
VIEWING WINDOW
UV SENSOR
DETECTOR LEDS
FIRE ZONE LEDS
FAULT LED
RESET/LAMP TEST
MODE SWITCH
4
PUSHBUTTON
B1048
1
2
6
7
1. A DETECTOR LED for each channel provides an immediate visual indication that a fire has been detected. The LED blinks slowly (once per second) if the fire intensity does not exceed the fire thresh­old and blinks rapidly if a fire output is generated. Steady illumination indicates that the fire intensity has returned below the alarm threshold (i.e., fire has been extinguished).
2. The FIRE ZONE LEDs signal actuation of the corre­sponding Fire (timed) relay outputs.
3. Illumination of the ALARM LED indicates actuation of an Alarm (instant) relay output.
4. Illumination of the FAULT LED indicates a system malfunction (in Normal mode).
5. The POWER LED is illuminated when power is applied to the system.
6. The RESET/LAMP TEST button illuminates all LEDs for testing and also resets the system. While the button is depressed, the outputs are disabled. This will cause a fault condition until the controller restarts (approximately two seconds).
11. The TEST/NORM toggle switch selects NORMAL or TEST mode.
Normal Mode
In the Normal operating mode, the R7495B Controller monitors the outputs of all detectors connected to it and compares the detector output signals to field adjusted settings (refer to the “STAR Logic Programming” proce­dure in the “Programming the Controller” section) to determine whether a fire condition exists. Diagnostic circuitry continuously checks the system for wiring con­tinuity as well as faults that could prevent proper response to a fire through the Automatic
o
i
feature. The Fire Zone (timed) and Alarm (instant) relays are normally de-energized. The Fault relay is normally energized, as long as no system malfunctions are detected. Only the POWER LED is illuminated.
Resetting the Controller
Any existing system status indications and the controller outputs are returned to normal operating condition with all LEDs except the POWER LED off, and all relays except the Fault relay de-energize (after the radiation source is removed or the fault is corrected) in one of the following ways:
1. Depress the RESET/LAMP TEST button.
2. Place the mode switch in the TEST position, then return it to NORMAL.
3. Close the optional remote reset switch connected between terminals 31 and 32.
Programming Switches
Rocker switches that are located on the side of the con­troller are used for selecting various options available with the R7495B. These programming options are listed below and must be set prior to system operation. Refer to the “Programming the Controller” section of this man­ual for detailed instructions.
1. Number of detectors connected to the controller (up to eight)
2. Gate Length, Consecutive Gate Selection, Count Selection (system sensitivity and time delay).
3. Detector Grouping/Voting Logic
4. Latching/non-latching outputs.
Detector Grouping
The microprocessor-based circuitry in the controller requires that the detectors be “grouped” into detection zones. Two options are possible:
Separate - Two independent groups consisting of up to four detectors each (channels 1 to 4 and channels 5 to
8) can energize an Alarm and a Fire Zone output.
Combined - All eight channels make up a single detec­tion zone, with both Alarm outputs and/or both Fire Zone outputs being actuated simultaneously.
Alarm Outputs
Two Alarm relays are provided for controlling external fire response devices. If any of the detectors in the group detects a fire that exceeds the gate length, con­secutive gates, and count selection requirements.
1. One or both of the Alarm relays is energized.
2. Actuation of an Alarm relay is indicated by illumina­tion of the ALARM LED on the front panel of the controller.
3. The detector(s) responding to fire is identified by illumination of its corresponding DETECTOR LED.
Fire Zone Outputs -
If the combination of detectors
responding to fire satisfies the pre-programmed voting
4
requirements, actuation of one or both of two Fire Zone outputs will also occur. If the controller is programmed for two separate zones, an output is generated if the selected number of detectors in the group (one or two) responds to fire. If an eight detector group is pro­grammed, the controller energizes both Fire Zone out­puts if fire is detected by the selected minimum number (one to four) of detectors.
This voting feature allows different combinations of detectors to fulfill the logic requirements, and provides the best balance between dependable fire detection and freedom from false alarms. Actuation of a Fire Zone output is signaled by illumination of the appropriate FIRE ZONE LED on the controller.
Ext Reset/Inhibit
Connecting a switch between terminals 31 and 32 allows the controller to be reset or inhibited from a remote location (close switch to inhibit/reset).
Fault Detection
The R7495B/C7052J system uses the Automatic oi fea­ture to continuously check the cleanliness of the detec­tor viewing windows and sensitivity of the sensors. In addition, automatic diagnostic circuitry in the controller monitors the system for wiring continuity faults as well as other malfunctions that could prevent the system from responding in the event of a fire. If a fault is detected:
1. The normally energized Fault relay is de-energized. This relay is typically used for controlling an exter­nal fault annunciation device or removing power from a hazardous process.
2. The FAULT LED on the front panel of the controller is illuminated to provide a visual indication that a system fault has occurred.
Field Wiring Connector
The R7495B Controller is furnished with a field wiring connector backplate that incorporates pressure type screw terminals for connecting the external wiring. The use of a Q4004 Mounting Cage is recommended for mounting the controller. The controller is designed for installation in a non-hazardous area.
SPECIFICATIONS
SPECTRAL SENSITIVITY RANGE—
UV: The UV sensor responds to radiation over the range
of 0.185 to 0.245 microns (1850 to 2450 angstroms).
IR: The single frequency infrared sensor responds to
radiation between 4.2 and 4.7 microns. Figure 1 illustrates the spectral response range of the UV and IR sensors.
CONE OF VISION—
The C7052J has a 80 degree cone of vision with the highest sensitivity lying along its central axis. See Figure 4.
FLAME SENSITIVITY—
The C7052J5 with a part number DE5500 IR Sensor Module (the sensor part number is printed on its side) detects a 1 foot by 1 foot gasoline fire at 50 feet, a 2 foot by 2 foot JP4 fire at 100 feet, and a 10 foot by 10 foot JP4 fire at 150 feet.
The C7052J with a part number DE3895 IR Sensor Module (the sensor part number is printed on its side) detects a 1 foot by 1 foot gasoline fire at 35 to 45 feet, a 2 foot by 2 foot JP4 fire at 100 feet, and a 10 foot by 10 foot JP4 fire at 150 feet.
RESPONSE TIME—
The response time of the detector is a function of fuel, fire size, distance, orientation of the fire source and the field programmable controller settings. With typical controller settings of 0.25 second gate length, 4 counts per gate, and 4 consecutive gates, the system will respond to an intense fire signal in less than 2 seconds.
Response times of less than 1 second to an intense fire signal can be achieved by setting the controller for a
0.125 second gate length, 2 counts per gate, and 3 consecutive gates.
INPUT VOLTAGE—
Controller and Detector 24 vdc nominal (18 vdc minimum, 32 vdc maximum) with less than 1 volt of ripple.
5 95-8302
Figure 4—Cone of Vision
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
30°
45°
A1461
INCIDENCE DECREASES.
15°
DETECTION
DISTANCE
(PERCENT)
100
90
80
70
60
50
40
30
20
10
15°
30°
45°
POWER CONSUMPTION—
Controller: 1.5 watts typical, 3.5 watts maximum. Detector: 1.0 watt typical, 3.5 watts maximum.
RELAY CONTACT RATINGS—
3 amperes at up to 30 vdc or up to 240 vac
CONTROLLER TEMPERATURE RANGE—
Operating: +32°F to +140°F (0°C to +60°C) Storage: –40°F to +140°F (–40°C to +60°C)
DETECTOR TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C). Storage: –67°F to +185°F (–55°C to +85°C)
DETECTOR HUMIDITY RANGE—
0 to 95% relative humidity.
DETECTOR ENCLOSURE MATERIAL—
Copper-free aluminum (red) or 316 stainless steel, with optional stainless steel mounting bracket.
DETECTOR ENCLOSURE RATINGS—
FM approved and CSA certified for Class I, Groups C and D, and Class II, Groups E, F, and G hazardous locations. NEMA 4 enclosure. BASEEFA/CENELEC certified flame-proof for EExd IIB T6; IP66 enclosure rating.
RFI/EMI HARDENED—
Detector designed to meet RFI and EMI immunity requirements of MIL STD 461, 462, and 463.
DIMENSIONS—
See Figures 5, 6, 7 and 8.
SHIPPING WEIGHT—
R7495B Controller:
4.4 pounds (2.0 kilograms)
C7052J Detector:
Aluminum: 6.0 pounds (2.7 kilograms) Stainless Steel: 14.0 pounds (6.4 kilograms)
6
Figure 5—Detector Dimensions in Inches (MM)
Figure 6—R7495 Controller Dimensions in Inches (MM)
Figure 7—Mounting Base Dimensions
3.38 (85.8 MM) 7.11 (181 MM)
2.5 DIA. (64 MM)
7.81
(198 MM)
5.25
(133 MM)
C1047
10.0 (254 MM)
B0906
CONDUIT ENTRY 3/4 NPT OR 25 MM
2.0
(50 MM)
7.0
(177 MM)
A1305
2–1/2 (64 MM) DIA.
° ± 2° (2)
120
0.25 (6.4 MM) DIA. (3)
2.00 (50.8 MM) DIA.
OPTIONS
Power supplies are available for operating the R7495B and C7052J from line (mains) voltage.
Q4004 Mounting Cage is designed for holding up to eight micro-module devices and is recommended for ease of installation and servicing. Mounting cages that hold fewer modules are also available. Optional filler panels (part number 002188-001) can be used to cover unused sections of the mounting cage.
Locking devices must be used on detector housings to comply with applicable regulations in some areas (BASEEFA/CENELEC).
Q1113 Air Shields for areas where there is an abnormal­ly high level of airborne contaminants. Two Q1113 Air Shields are required for each detector.
Q9001G Swivel Assembly (part number 004404-001) for easy mounting and sighting of detector assemblies.
RESPONSE CHARACTERISTICS
The response time of the detector is a function of fuel, fire size, distance, orientation of the fire source and the field programmable controller settings. As with all fire tests, results must be interpreted according to the indi­vidual application, taking into account all possible vari­ables (see the Application Guidelines” section for a dis­cussion of of these factors).
Typical response distances of the C7052J Detector to various fuels are listed in Table 1. Each liquid fuel fire (acetone, diesel, gasoline, methanol, and toluene) con­sisted of approximately one pint of fuel burned in a 1 foot by 1 foot steel pan unless otherwise noted. The
excelsior (wood shaving) fire consisted of one pound of wood shavings. The wood fire consisted of a 10-inch by 10-inch crib (wood stack). The methane fire was per­formed to FM standard, with the flame approximately 30 inches high and 6 to 8 inches in diameter. The detec­tors were sited to observe the fire at center axis ±10 degrees. The controller sensitivity and time delay set­tings were 4 counts per gate, 4 consecutive gates, and
0.25 second gate lengths.
APPLICATION GUIDELINES
Certain guidelines must be followed when using any type of sensing device as a fire detector. This involves not only recognizing the strengths and advantages of a particular device, but also understanding its limitations.
It is also important to note that in any system that uses two or more sensors to produce a fire signal, the detec­tor will be disabled should one of its sensors fail. The Automatic Oi feature will warn of such failure. Routine manual testing and checking of the system is recom­mended for increased system reliability.
Potential radiation sources in the environment must also be carefully considered. A UV sensor will respond to sources of UV besides fire, such as electric arc welding, lightning, x-rays and gamma radiation. The C7052J has been designed to ignore steady state infrared sources that do not have a flicker frequency characteristic of a fire, however, it should be noted that if these steady state infrared sources are hot enough to emit adequate amounts of infrared radiation in the response range of the IR sensor and if this radiation becomes interrupted from the view of the detector in a pattern characteristic of a flickering flame, the IR sensor can respond. Any object having a temperature greater than 0° Kelvin (–273°C) emits infrared radiation. The hotter the object, the greater the intensity of the emitted radiation. See Figure 9. The closer the infrared source is to the detec­tor, the greater the potential for the IR sensor to produce
7 95-8302
JUNCTION BOX MOUNTING
Figure 8—Q9001G Swivel Mounting Bracket Dimensions
Table 1—C7052J Typical Response Distances
Fuel Distance from U7652 Acetone 45 feet (13.7 meters) Diesel 40 feet (12.2 meters) Gasoline 50 feet (15 meters) Methane 35 feet (10.7 meters) Methanol 35 feet (10.7 meters) Toluene 50 feet (15 meters) Wood Shavings (Excelsior) 50 feet (15 meters) Wood Stack (Crib) 50 feet (12.2 meters) JP4 (surface area)
2 ft
2
100 feet (30 meters)
4 ft
2
150 feet (45 meters)
10 ft
2
150 feet (45 meters)
BRACKET (ATTACHES WITH TWO ENCLOSED FLATHEAD SCREWS)
3/4 INCH NUT USED TO SECURE DETECTOR BRACKET TO SWIVEL MOUNT
1/2 INCH NUT USED TO ADJUST ELBOW TO DESIRED ANGLE
5-1/4 INCHES
(133 MM)
1-3/8 INCH NUT USED TO ROTATE SWIVEL/DETECTOR ASSEMBLY TO DESIRED POSITION
MOUNTING BASE
2-1/2 INCHES
(64 MM)
B1303
an alarm. The IR sensor can respond to IR radiation sources that can meet the amplitude and flicker require­ments of the detector such as vibrating hot objects. Although the C7052J Detector is designed to reduce false actuations, certain combinations of ambient radia­tion must be avoided. For example, if IR radiation with an intensity that exceeds the fire threshold of the IR sen­sor should reach the detector as a flickering signal, and if at the same time an electric arc welding signal also reaches the sensors, an alarm output will be generated.
The C7052J ignores arc welding beyond 15 feet from the detector. However, the UV sensor will respond to the intense UV radiation generated by the arc welding, and at distances closer than 15 feet the heated metal from the welding can become a false alarm source for the IR sensor.
Another important fact regarding a radiation detector of any type is that radiation must reach the detector in order for it to respond. Care must be taken to keep physical obstructions out of the line of view of the detec­tor. In addition, UV or IR absorbing gases or vapors must not be allowed to accumulate between the detec­tor and the protected hazard. See Table 2 for a listing of these substances. Smoke will also absorb radiation, therefore, the detector should not be mounted close to the ceiling or other areas where smoke can accumulate.
It is important to keep the detector viewing windows as free of contaminants as possible in order to maintain maximum sensitivity and to assure proper operation of the flame detection system. Commonly encountered substances that can significantly attenuate UV and/or IR radiation include, but are certainly not limited to, the fol­lowing:
Silicones Oils and greases Ice buildup Dust and dirt buildup Paint overspray
The
o
i
test feature is designed to register an
o
i
fault when the detector sensitivity is reduced to approximate­ly 50% of its maximum detection range. For maximum system reliability, it is recommended that the detector viewing windows be cleaned on a regularly scheduled basis. (Refer to the “Maintenance” section of this manu­al for additional information regarding detector mainte­nance.) The use of model Q1113 Air Shields can help extend the time period between required maintenance.
The C7052J is designed to be resistant to interference from EMI and RFI. It will not respond to a 5 watt walkie­talkie at a distance of greater than 1 foot.
8
Figure 9—Blackbody Spectral Emittance
The following is a partial list of compounds that exhibit significant UV absorption characteristics. These are also usually hazardous vapors. While generally of little conse­quence in small amounts, these gases can restrict UV detection if they are in the atmosphere in heavy concen­trations. It should also be determined whether or not large amounts of these gases may be released as a result of a fire-causing occurrence.
Acetaldehyde Methyl Methacrylate Acetone Alpha-Methylstyrene Acrylonitrile Naphthalene Ethyl Acrylate Nitroethane Methyl Acrylate Nitrobenzene Ethanol Nitromethane Ammonia 1-Nitropropane Aniline 2-Nitropropane Benzene 2-Pentanone 1,3 Butadiene Phenol 2—Butanone Phenyl Clycide Ether Butylamine Pyridine Chlorobenzene Hydrogen Sulfide 1-Chloro-1-Nitropropane Styrene Chloroprene Tetrachloroethylene Cumene Toluene Cyclopentadiene Trichloroethylene O-Dichlorobenzene Vinyl Toluene P-Dichlorobenzene Xylene
If UV-absorbing gases may be a factor in a given applica­tion, precautionary measures should be taken. Detectors can be placed closer to the potential hazard area, and/or the sensitivity of the detection system can be increased. Contact the factory for further details.
Substances such as methane, propane, butane, hexane, camphor and octane are not UV absorbing.
Absorption of infrared radiation in the range of 4.2 to 4.7 microns is not a significant problem with most organic vapors, with the exception of those compounds that have triple bonds such as acetylene, nitriles, silane, or iso­cyanates. Carbon dioxide concentrations higher than nor­mally present in the atmosphere can also cause substan­tial loss of fire detection sensitivity.
Table 2—Radiation Absorbing Gases and Vapors
4
10
4000°K
3
10
2
10
WATTS
2
1
10
(CM ) (MICRON)
1
–1
10
–2
10
–3
RADIANT EMITTANCE
10
–4
10
A0576
0.6 0.8 1 2 4 6 8 10 20 30
0.4
6000°K
2000°K
1000°K
500°K
WAVELENGTH (MICRONS)
300°K
250°K
The C7052J uses a single frequency IR sensing device with detection limited to the hot CO2 emission peak, therefore, it cannot be used to detect fires that do not contain carbon, such as hydrogen, sulfur, burning met­als, or other non-hydrocarbons without thorough testing.
INSTALLATION
Detector Positioning
When determining the proper number and positioning of detectors needed for adequately protecting any given installation, it is essential to consider the cone of vision of the detector. The C7052J Detector has a nominal 80 degree cone of vision with the highest sensitivity along its central axis. Refer to Figure 4. Careful observation of this graph reveals that at 50 percent of the maximum detection distance, the cone of vision is still 80 degrees. As the detection distance increases beyond 50 percent, the cone of vision gradually decreases. For example, the C7052J will detect a 1 foot by 1 foot gasoline fire at 50 feet. Therefore, we can assume that at 25 feet (50% maximum distance) the cone of vision will be 80 degrees. If the fire increases in size, both the maximum detection distance and the cone of vision at longer dis­tances will be increased.
It is also important to note that as the distance increases between the detector and the fire source, the time need­ed for the detector to respond to a fire of a given size also increases (fastest response requires maximum fire signal). The intensity of the radiation reaching the detector decreases with distance. For fastest response time, locate the detector as close as possible to the anticipated fire source.
The following recommendations should be observed in designing or installing any fire detection system:
— Use enough detectors to adequately cover the pro-
tected area with overlapping cones of vision.
— For fastest response time, position the detectors as
close as possible to the anticipated fire source.
— Aim the detector as directly as possible at the antic-
ipated fire source.
— If possible, conduct actual flame tests to verify cor-
rect detector positioning and proper system opera­tion.
Whenever possible, the detector should be positioned in a manner that will minimize the buildup of contami­nants on the viewing window and
o
i
ring. Substances such as snow, ice, dirt, oil, paint overspray, and numer­ous other commonly encountered materials are capable of attenuating UV or IR radiation and adversely affecting detector response.
For outdoor applications, the detector should be aimed downward to minimize the buildup of water or ice on the detector viewing window and to prevent it from scanning the horizon. This minimizes the response to distant radiation sources outside the protected area.
The detector should not be placed where smoke can obscure its view of the hazardous area. For indoor applications, if dense smoke is expected to accumulate at the onset of a fire, mounting the detector on a side wall a few feet (1 meter) down from the ceiling will nor­mally allow enough time for the unit to respond before it is affected by rising smoke. The detector should be located where it can be easily accessed for periodic maintenance, testing and cleaning.
Wiring Requirements
The system should be wired using four conductor shielded cable, at least 18 gauge (1.024 mm diameter). The length of cable should be considered when wiring the system to ensure that a minimum input voltage of 18 vdc is present at the detector. The cable length should not exceed 2000 feet. In applications where the wiring cable is installed in conduit, the conduit should not be used for wiring to other electrical equipment. Foil type shielded cable is recommended to protect from electro­magnetic and radio frequency interference. When using cables with shields, the shield should be insulated at the detector and grounded only at the control cabi­net.
NOTE It is important to use cable that is suitable for the installation environment. In applications involving high humidity or salt water, use a cable that is made specifically for harsh, salt water environ­ments. In all cases, typical cable insulation resis­tance should be at least 100 megohms. If the resistance drops below 10 megohms, the cable could be deteriorating and should be replaced to avoid shorting. When testing the insulation resis­tance, disconnect the leads from the detector/con­troller before connecting the megohmmeter (insula­tion tester) to the cable.
Since moisture can be detrimental to electronic devices, it is important that moisture not be allowed to come in contact with the electrical connections of the system. Moisture in the air can become trapped within sections of conduit, therefore the use of conduit seals is required to prevent damage to electrical connections caused by condensation within the conduit. These seals must be water-tight and explosion-proof and are to be installed even if they are not required by local wiring codes. A seal must be located as close to the C7052J as possi­ble. In no case should this seal be located more than 18 inches (46 cm) from the unit. If a conduit swivel is
9 95-8302
used, the seal must be located between the swivel and the detector. When an explosion-proof installation is required, an additional seal must also be installed at any point where the conduit enters a non-hazardous area. When pouring a seal, the use of a fiberdam is required to assure proper formation of the seal. The seals should never be poured in temperatures that are below freezing, since the water in the sealing com­pound will freeze and the compound will not dry proper­ly. Contamination problems can then result when tem­peratures rise above the freezing point and the com­pound thaws. The shielding of the cable should be stripped back to permit the seal to form around the indi­vidual leads, rather than around the outside of the shield. This will prevent any siphoning action that might occur through the inside of the shield. The electrical continuity of the shield must be maintained through the seal via the shield drain wire.
Moisture in the air can be trapped within sections of conduit and can condense and accumulate at the base of vertical conduit runs. To eliminate this condition, explosion-proof drains and breathers should be installed to automatically bleed off accumulated water.
It is recommended that the detector be oriented with the conduit opening at the bottom or at either side of the device. This will reduce the possibility of moisture entering the junction box through the conduit entry and also ensure that the
o
i
test lamps are not in a position
that would make the detector overly susceptible to
o
i
Oi
faults. Whenever possible, slope the conduit run down­ward from the detector. Do not use conduit runs that enter the device from the top. See Figure 10 for identifi­cation of the detector parts of interest when mounting, and Figure 11 for an example of vertical detector mount­ing.
Detector Mounting and Wiring Procedure
The following procedure should be used for mounting and wiring the C7052J.
1. Detectors should be located in positions best suited for covering the area to be protected. Whenever practical, they should be placed where they will be easily accessible for cleaning and other periodic servicing. Particular attention should also be paid to potential false alarm sources within the cone of vision of the detector, such as distant arc welding, rotating fan blades, surface vibration of an IR source, and movement of people or machines between the detector and an IR source, all of which could allow a flickering IR signal to reach the detec­tor. Rain or ice can absorb radiation, which can reduce the capability of the detector. For outdoor applications, aim the detector downward to mini­mize the buildup of water or ice on the detector viewing windows and to prevent the cone of vision from scanning the horizon. This minimizes response to distant radiation sources outside the protected area.
10
Figure 10—Front View of the C7052J Detector
IR SENSOR HOUSING
A1327
*o
TEST LAMP (2)
i
LED (2)
CONDUIT SEAL REQUIRED WITHIN 18 INCHES OF DETECTOR. DETECTOR MUST BE ORIENTED WITH CONDUIT ENTRY AT BOTTOM OR SIDE TO ELIMINATE DRAINAGE INTO JUNCTION BOX.
UV SENSOR HOUSING
oi RING OPENING DOWN
*
o
TEST LAMPS AT TOP OR SIDE
i
LED (2)
o
TEST LAMP
i
NOTE The wiring procedures in this manual are intended to ensure proper functioning of the device under normal conditions. However, because of the many variations in wiring codes and regulations, total compliance to these ordinances cannot be guaran­teed. Be certain that all wiring complies with appli­cable regulations that relate to the installation of electrical equipment in a hazardous area. If in doubt, consult a qualified electrician before wiring the system.
2. Remove the junction box cover assembly from the base by loosening the six screws on the cover (see Figure 12).
3. Mount the detector junction box base and mounting bracket assembly on the wall or ceiling. See Figures 7 and 8 for dimensions of the mounting bracket. The mounting surface should be free of excessive heat and vibration.
NOTE Do not wire the system, or plug in or remove the sensor modules with power applied.
4. Figure 13 shows the detector terminal block. Letter designations correspond to connections as indicat­ed below.
A = +24 vdc B = detector output signal C = circuit ground D = Oi control signal
Minimum requirements for wiring the detector are for the B-lead (signal) to be shielded. It is preferred that the A-lead, C-lead, and D-lead also be shield­ed to provide maximum immunity to EMI/RFI. The wiring procedure below is the preferred method of detector to controller wiring. Refer to Figure 14 for an example of a typical application showing detec­tor to controller wiring.
a. Connect the B-lead shields to the chassis
(earth) ground connection (terminal 5) of the controller.
b. Be certain that the shield is NOT connected
to the detector at terminal “C” (circuit ground) or any other points.
c. Connect the C-leads of the detectors to termi-
nal 2 (circuit ground) of the controller.
d. Connect a non-polarized 0.47 microfarad 250
vdc capacitor from terminal 5 to terminal 2. This places the earth ground and the circuit ground at the same ac potential, minimizing induction of noise into the system through the detector cable.
5. Check to make sure that all wiring is correct. If con­duit is used, pour the conduit seals and allow them to dry.
6. If the UV and/or IR sensor modules are already installed in the detector housing, proceed to step
12. If the sensors are not installed, remove the applicable sensor housings from the junction box cover (see Figure 12). If the detectors are equipped with a cover locking device (see Figure
15), loosen the clamp and disengage the “catch” from the blind hole. The tool required is a 5/32-inch hexagonal (Allen) wrench.
7. If the UV sensor module is already installed, proceed to step 9. If the UV module is not installed, remove the UV sensor module from its shipping package.
8. Determine the proper orientation for the UV module by lining up the long index pin on the terminal block with the hole in the printed circuit board of the mod­ule. See Figure 12. Firmly press the module into place on the terminal block, taking care not to touch the glass envelope of the sensor module, since fin­gerprints can absorb UV radiation and reduce the sensitivity of the sensor.
11 95-8302
PROVIDE ENOUGH CABLE
Figure 11—Vertical Mountign Detector
FOR ADJUSTMENT OF SWIVEL
CONDUIT SEAL
A1478
12
Figure 13—Detectro Terminal Block
Figure 12—C7052J Detector Part Identification
UV TERMINAL BLOCK
INDEX PIN
JUNCTION BOX
JUNCTION BOX COVER
MOUNTING PIN
IR SENSOR MODULE
IR TEST LAMPS (2)
UV SENSOR MODULE
UV TEST LAMP OPENING
O-RING
UV SENSOR HOUSING
UV oi RING
+24 VDC (A)
OUTPUT SIGNAL (B)
O-RING
IR SENSOR HOUSING
IR oi RING
F0946
D0947
CIRCUIT GND (C)
oi SIGNAL (D)
EARTH GND
13 95-8302
HOT
IMPORTANT
If the UV sensor module is supplied with a jumper plug “J” as shown in Figure 16, remove the jumper plug from the detector tube module and discard it. Jumper plug “J” is supplied for installations in which the tube module is used with other detector models.
NOTE The C7052J contains semiconductor devices that are susceptible to damage by electrostatic dis­charge. An electrostatic charge can build up on the skin and discharge when an object is touched. Therefore, use caution when handling the detector,
taking care not to touch the terminals or electronic components. For more information on proper han­dling, refer to Service Memo form 75-1005 at the front of this manual.
9. If the IR sensor is already installed, proceed to step
12. If the IR sensor is not installed, remove the IR module from its shipping package (avoid touching the IR sensing element at the top of the module). Two IR sensor designs exist; the DE5500 is electri­cally connected via a wire harness on the junction box that must be threaded through the sensor mod­ule to a connector at the top of the module (see Figure 17), the DE3895 plugs directly onto a termi­nal block in the base of the IR housing via connec­tors on the bottom of the IR sensor module (see Figure 12).
10. If the IR sensors are the DE3895 type that electri­cally connects directly onto the terminal block, install them by lining up the connection pins using the index pin to properly orient the module. Press the sensor firmly into place.
11. If the IR sensor is the DE5500 type that connects via a wire harness (Figure 17), thread the wire leads and keyed connector plug through the slotted opening on the side of the IR module. Plug the IR module into the two banana plugs inside the junc­tion box cover. If repositioning is necessary to properly align the
o
i
lamps (as described in the “NOTE” below), this module can be rotated 180° and remounted on the banana plugs.
Figure 14—Typical Application Wiring
Figure 15—Cover Locking Assembly (Optional)
NEUTRAL
A0976
24 VDC
+
PROCESS CONTROL
LOAD
LOAD
FAULT
ALARM
0.47µf
1
+
DC INPUT
2 3 4
CHASSIS (EARTH) GROUND
5
NC
6
NO
7
COM
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
FIRE ZONE 1
NC NO COM NC NO COM
FIRE ZONE 2
NC NO COM NC
ALARM 1
NO COM NC
ALARM 2
NO COM NC
FAULT*
NO COM
THE FAULT RELAY, SHOWN DE-ENERGIZED,
*
IS ENERGIZED UNDER NORMAL OPERATING CONDITIONS.
UP TO EIGHT DETECTORS CAN BE CONNECTED*
R7495
EXTERNAL RESET
CIRCUIT GROUND CIRCUIT GROUND
31 32 33 34 35
D1
36
D2
37
D3
38
D4
39
D5
40
D6
41
D7
42
D8
43
B1
44
B2
45
B3
46
B4
47
B5
48
B6
49
B7
50
B8
EXTERNAL
RESET SWITCH
A B C D
A B C D
A B C D
C7052J
C7052J
C7052J
BLIND HOLE
CATCH
COVER
LOCKING
ASSEMBLY
A1078
CLAMP
SCREW
STRAP
BARREL
LENS CAP
NOTE
The two
o
i
lamps on the DE5500 IR sensor should be at the top or side of the detector (when viewed from the front) and the opening on the
o
i
ring should be at the bottom. See Figure 10. This will ensure proper operation of the
o
i
system and also minimize the accumulation of moisture and con­taminants between the
o
i
ring and the viewing win-
dow. (The
o
i
lamps on the IR sensor are identified
as oblong in shape and clear in color.)
12. Connect the keyed connector plug to the 4-pin con­nector on the DE5500 IR module. Tuck the lead­wires inside the module to prevent binding or wire damage when installing or removing the sensor housing.
13. Check the O-rings on both sensor housings to be sure that they are in good condition and are fitted properly, then re-install the sensor housings on the junction box cover. (See the “Maintenance” section of this manual for information regarding care of O­rings.) The sensor housing with the large viewing window is for the UV detector and the sensor hous­ing with the small window is for the IR detector. Hand tighten the sensor housings into the base until the O-rings are fully seated to maintain the explo­sion-proof and watertight integrity of the housing. If the unit is equipped with cover locking clamps, loosen the clamps sufficiently so that the clamp catches can be seated in the blind holes on the junction box cover. Fasten the clamps securely using a 5/32 inch hexagonal (Allen) wrench. (See Figure 15.)
14. Re-install the junction box cover, making sure that the center nine-pin connector on the cover is prop­erly aligned with the connector in the junction box.
The six screws must be tight to ensure a metal to metal fit to maintain explosion-proof and watertight integrity of the junction box.
15. Inspect and clean (if necessary) the detector view­ing windows and
o
i
rings by following the instruc-
tions in the “Maintenance” section of this manual.
16. The opening of the
o
i
rings should be pointed down to minimize the accumulation of moisture or con­taminants behind the ring (see Figure 10). Verify that the
o
i
test lamp is at the top or side of each sensor. Note that Figure 10 shows the DE5500 IR module with the test lamps located together on one side of the edge. The DE3895 IR module has test lamps located directly opposite one another. In both cases, ensure that no test lamp is positioned at the bottom when the detector is installed.
17. If the detector is so equipped, install the air shields on each sensor housing, then connect the air sup­ply line to the air shields.
NOTE Be sure that the detector is correctly aimed at the potential hazard and that no obstructions interfere with its line of vision. In addition, UV and/or IR absorbing gases (see Table 2) should not exist between the detector and the potential hazard.
CONTROLLER INSTALLATION AND WIRING
The R7495B Controller must be mounted in a non-haz­ardous area. The optional Q4004 Mounting Cage is designed to hold up to eight modules in a 19 inch instrument rack. Other mounting cages are available to accommodate 1, 2, 3, 4 or 6 units. These mounting
14
IR MODULE
Figure 17—IR Module with Four-Wire Connector
Figure 16—Jumper Plug
4–WIRE CONNECTOR PLUG
A1702
JUMPER "J"
A1331
cages can also house voltage converters and other micro-module equipment that is used in conjunction with the R7495B Controller as part of the total protection system. See Figure 18 for illustration and dimensions.
Electrical Connections
All electrical connections are made to the field wiring connector that is furnished with the controller. Figure 19 shows the terminal configuration for the controller. Power to the R7495B Controller and C7052J Detectors may be furnished by external 24 volt batteries, a regulated dc power supply, or optional Det-Tronics voltage converters.
Terminal 1 — Connect to the positive (+)
side of an external 24 vdc power source.
Terminal 2 — Connect to the negative (–)
side of the dc power source (circuit ground). The C termi­nals on the detectors must also be connected to circuit ground.
Terminal 3 — Do not use.
Terminal 4 — Do not use.
Terminal 5 — Chassis (earth) ground termi-
nal is connected to the con­troller chassis and should be connected to the nearest earth ground connection.
Terminals 6 to 11 — Relay Contacts, Fire Zone 1.
Terminals 12 to 17 — Relay Contacts, Fire Zone 2.
Terminals 18 to 20 — Relay Contacts, Alarm 1.
Terminals 21 to 23 — Relay Contacts, Alarm 2.
Terminals 24 to 26 — Fault relay contacts- the fault
relay is normally energized in the Normal mode with no sys­tem faults present.
Terminals 31 and 32 — External Reset - a normally
open switch connected between terminals 31 and 32 (circuit ground) allows the con­troller to be reset from a remote location.
Terminal 33 — Circuit ground - connect to all
detector wiring shields.
15 95-8302
Figure 18—Q4004 Mounting Cage Dimensions in Inches (MM)
RACK PART NUMBER CONTROLLER TYPE 005269-XXX POSITIONS FOR: HT: DIM. (A) DIM. (B) DIM. (C) DIM. (D) DIM. (E) WEIGHT
4U –001 8 16 4U 19.00 482.6 18.30 464.8 17.36 440.9 4.00 101.6 6.97 177.1 9.3 4.2
4U –002 6 12 4U 15.06 382.6 14.36 364.7 13.42 340.9 7.6 3.5
4U –003 4 8 4U 11.13 282.6 10.43 264.9 9.49 241.1 5.9 2.7
4U –004 3 6 4U 9.16 232.7 8.46 214.9 7.52 191.0 5.1 2.3
4U –005 2 4 4U 7.19 182.7 6.49 164.9 5.55 141.0 4.2 1.9
4U –006 1 2 4U 5.22 132.6 4.52 114.8 3.58 90.9 3.1 1.4
FIRE GAS INCH MM INCH MM INCH MM INCH MM INCH MM LB KG
(A)
(B)
(C)
1.48 (37.59)
A1475
(D)
ALL CONTROLLER CAGES REQUIRE A MINIMUM OF 10.12 INCHES (257.1 MM) DEPTH CLEARANCE
(E)
Terminal 34 — Do not use.
Terminals 35 to 42 — Connect to the D-leads (oi
control signal) of the corre­sponding detectors.
Terminals 43 to 50 — Connect to the B-leads (detec-
tor output) of the correspond­ing detectors.
PROGRAMMING THE CONTROLLER
The R7495B Controller is field programmable in order to meet the requirements of the individual installation. This is accomplished by setting rocker switches that are located on the left side of the controller (see Figure 20) to either “open” or “closed.” The programming options are listed below. A more detailed description follows.
1. Number of detectors connected to the controller (up to eight)
2. Gate Length, Consecutive Gate Selection, and Count Selection (system sensitivity and time delay).
3. Detector Grouping/Voting Logic
4. Latching/non-latching outputs.
The individual rocker switches are identified by num­bers 1-1, 1-2, 1-3, etc. in this manual. The number pre­ceding the dash indicates the number of the switch assembly. The number following the dash identifies the specific rocker on the switch assembly. See Figure 20.
Each rocker switch assembly contains eight separate rocker switches. The rockers are identified by the num­bers one through eight on one side of the assembly. The word “open” can be seen on the opposite side. The switch is open when depressed in the direction of the word “open” and closed when depressed in the direction of the numbers.
16
Figure 20—Rocker Switch Setting
Figure 19—Terminal Configuration
J1
1
NOT USED NOT USED
COMMON
COMMON
COMMON
COMMON
COMMON
COMMON
COMMON
+ –
2 3 4
J2 31
5
EXTERNAL RESET
32
6
CIRCUIT GROUND
33
7
CIRCUIT GROUND
34
8
NOT USED
35
9
D1
36
10
D2
37
11
D3
38
12
D4
39
13
D5
40
14
D6
41
15
D7
42
16
D8
43
17
B1
44
18
B2
45
19
B3
46
20
B4
47
21
B5
48
22
B6
49
23
B7
50
24
B8 25 26
FIRE ZONE 1
FIRE ZONE 2
ALARM 1
ALARM 2
FAULT*
A0972
+24 VDC INPUT
CHASSIS GROUND
NORMALLY CLOSED
NORMALLY OPEN
NORMALLY CLOSED
NORMALLY OPEN
NORMALLY CLOSED
NORMALLY OPEN
NORMALLY CLOSED
NORMALLY OPEN
NORMALLY CLOSED
NORMALLY OPEN
NORMALLY CLOSED
NORMALLY OPEN
NORMALLY CLOSED
NORMALLY OPEN
THE FAULT RELAY, SHOWN DE-ENERGIZED
*
IS NORMALLY ENERGIZED IN THE NORMAL OPERATING MODE WITH NO FAULTS OCCURING
SWITCH ASSEMBLY 1
DETECTOR SELECTION SWITCH
THIS SWITCH PROGRAMS THE MICROPROCESSOR
SWITCH ASSEMBLY 3
CONSECUTIVE GATE SELECTION
ROCKER 1 – 1 COUNT ROCKER 2 – 2 COUNTS ROCKER 3 – 4 COUNTS ROCKER 4 – 8 COUNTS
ADD VALUE OF CLOSED ROCKERS
2 GATES MINIMUM
COUNT SELECTION
ROCKER 5 – 1 GATE ROCKER 6 – 2 GATES ROCKER 7 – 4 GATES ROCKER 8 – 8 GATES
VALUES OF CLOSED ROCKERS
ARE ADDED – 2 COUNTS MINIMUM
IF GATE IS GREATER THAN OR EQUAL
TO 0.5 SECOND, A MULTIPLICATION FACTOR
ROCKER SWITCH NUMBERS ARE DESIGNATED 1-1, 1-2, 1-3, ETC. THE NUMBER PRECEDING THE DASH INDICATES THE SWITCH ASSEMBLY. THE NUMBER FOLLOWING THE DASH INDICATES THE ROCKER NUMBER OF THE SWITCH INDICATED.
DEPRESS ROCKER TOWARD "OPEN" ON SWITCH ASSEMBLY TO SET IN THE OPEN POSITION. DEPRESS ROCKER TOWARD NUMBER DESIGNATIONS ON SWITCH ASSEMBLY TO SET IN CLOSED POSITION.
A0973
MUST BE USED.
NOTE 1:
NOTE 2:
FOR EACH DETECTOR CONNECTED
PLACE ROCKER IN OPEN POSITION
FOR EACH CHANNEL WITH A DETECTOR CONNECTED
SWITCH ASSEMBLY 2
GATE LENGTH
CLOSE ROCKERS TO ACTIVATE
ROCKER 1 – 31.25 MILLISECONDS
ROCKER 2 – 62.5 MILLISECONDS
ROCKER 3 – 0.125 SECOND
ROCKER 4 – 0.25 SECOND
ROCKER 5 – 0.5 SECOND
ROCKER 6 – 1 SECOND ROCKER 7 – 2 SECONDS ROCKER 8 – 4 SECONDS
VALUES OF ROCKERS CLOSED
ARE ADDED TOGETHER
SWITCH ASSEMBLY 4
DETECTOR GROUPING/VOTING LOGIC
ROCKER POSITION
4-1 CL CL CL CL OP OP OP OP
ROCKER 5 – LATCHING OUTPUTS WHEN ROCKER IS OPEN
4-3
4-2
DC
DC
DC
DC
OP
DC
CL
DC
ALL OPEN 1 CLOSED 2 CLOSED 3 CLOSED
OP = OPEN, CL = CLOSED, DC = DON'T CARE
FIRE
DETECTOR RESPONSE
ZONE
4-4
OUTPUTS
OP
1
CL
1
DC
2
DC
2
1 OF 8 DETECTORS
1•2
2 OF 8 DETECTORS
1•2
3 OF 8 DETECTORS
1•2
4 OF 8 DETECTORS
1•2
1•2 = 1 AND 2
ROCKERS 6, 7, 8 NOT USED
1 DETECTOR
2 DETECTORS
1 DETECTOR
2 DETECTORS
The rocker switches must be set before power is applied to the system. Do not plug the controller in or remove it from the mounting rack while power is turned on.
CAUTION
Use care when setting the rocker switches on the controller. An incorrectly set rocker switch can result in an obvious controller malfunction, or the controller could appear to be functioning normally, but not produce the desired output in response to the input conditions. (Some of the rocker switches on the R7495B are not used. These rockers should be left open.)
Detector Selection - Rocker Switches 1-1 to 1-8
The number after the dash corresponds to the number of each zone. Open the rocker for each zone that has a detector connected to it. Care must be taken when set­ting these rockers. If a rocker is set open, but no detec­tor is connected in that location, the controller will indi­cate a fault. If a rocker is set closed when a detector is connected, the controller will appear to be operating correctly and will produce an alarm condition if the cor­responding detectors sense a fire. However, that detector will be eliminated from the Automatic
o
i
test sequence, and any faults occurring in its circuitry or wiring will not be indicated.
STAR Logic Programming (System Sensitivity and Time Delay) - Rocker Switches 2-1 to 2-8 (Gate Length), Rocker Switches 3-1 to 3-4 (Count Selection Per Gate), and Rocker Switches 3-5 to 3­8 (Consecutive Gates Selection).
The STAR Logic switch settings determine system sen­sitivity and time delay. The most important factor in determining the appropriate sensitivity setting for a par­ticular application is the intensity of radiation expected to reach the detector in the event of a fire. This depends on several factors, including the distance of the detector from the potential fire, the fuel type, the flame size, and whether any radiation absorbing vapors are present (these are listed in Table 2).
The most effective way to set system sensitivity is to install the system, program the STAR Logic according to the typical settings shown in Figure 21, program all other aspects of controller operation according to this section (“Programming the Controller”), then perform the “Initial and Periodic Checkout Procedure” using a UV/IR test lamp and the “STAR Programming Checkout Procedure.”. If the system fails to respond appropriate­ly during these tests and all system wiring is correct, then system sensitivity (gate length, counts per gate, and consecutive gates) needs to be adjusted. It is important that all wiring and programmed settings be checked to ensure that they are correct before adjusting these settings.
17 95-8302
Figure 21—Graphic Representation of STAR Logic (Typical Setting Shown)
R7495 STAR Logic Program
4 Counts per Gate
0.25 Second Gate Length
4 Consecutive Gates
R7495 Switch Settings
Rockers Closed Rockers Open
3-3 3-1, 3-2, 3-4
2-4 2-1, 2-2, 2-3, 2-5, 2-6, 2-7, 2-8
3-7 3-5, 3-6, 3-8
A1584
FLAME
C7052
4 COUNTS PER GATE
UV SIGNAL
IR SIGNAL
4 CONSECUTIVE GATES
0.25 SECOND GATE LENGTH
COUNT (SIGNAL)
UV
AND
IR
UV/IR
FIRE
ALARM
CONDITION
Rocker switch assemblies 2 and 3 control three vari­ables; gate length, counts per gate and consecutive gates required for a fire output. Refer to Figure 21 for a visual representation of how these variables function together with typical controller settings. Keep in mind that when the UV and IR sensors of the detector respond to a fire, the IR sensor activates the circuitry in the UV/IR detector junction box. This allows the electri­cal pulses (signal) from the UV sensor to be sent to the controller. The frequency of this signal is proportional to the intensity of the fire. The controller looks at this sig­nal in comparison to the sensitivity settings in order to determine whether a fire exists. A brief description of each variable follows:
1. Gate Length is adjustable from 31.25 milliseconds to 8 seconds. The gate length is the increment of time that the controller looks at the detector signal to determine if the “Counts per Gate” requirement is fulfilled. In Figure 21, the gate length is 0.25 sec­onds (Rocker Switch 2-4 closed, Rocker Switches 2-1, 2-2, 2-3, 2-5, 2-6, 2-7, and 2-8 open).
2. Counts per Gate is adjustable from 2 to 15 counts. These counts make up the signal from the detector and are a direct response to a flame or other UV/IR source. In Figure 21, the counts per gate setting is 4 counts (Rocker Switch 3-3 closed, Rocker Switches 3-1, 3-2, and 3-4 open).
3. Consecutive Gates required for a fire output are adjustable from 2 to 15 gates. This is the number of consecutive gates in which the “Counts per Gate” requirement is fulfilled that the controller must see before going into a fire alarm condition. In Figure 21, the consecutive gates setting is 4 gates (Rocker Switch 3-7 closed, Rocker Switches 3-5, 3-6, and 3­8 open).
If changes in the sensitivity and/or time delay settings are required, read the detailed discussions of each of the three STAR Logic variables that follows before mak­ing changes. When changing the settings, keep in mind the following guidelines:
1. Increasing Gate Length while the other variables remain unchanged results in higher sensitivity and a longer time delay.
2. Increasing Consecutive Gates while the other vari­ables remain unchanged results in a longer time delay and greater noise immunity.
3. Increasing Counts per Gate while the other vari­ables remain unchanged results in lower sensitivity and greater false alarm rejection.
Gate Length - Rocker Switches 2-1 to 2-8
The gate length can be adjusted in 31.25 millisecond increments from 31.25 milliseconds to 8 seconds. Each rocker selects a particular time value. The gate length is the value of all rockers closed, added together. If no rocker is closed, the controller will select the minimum length (31.25 milliseconds). The typical gate length set­tings used in most applications are between 0.125 and
0.5 second.
Rocker 2-1 - 31.25 milliseconds Rocker 2-2 - 62.5 milliseconds Rocker 2-3 - 0.125 second Rocker 2-4 - 0.25 second Rocker 2-5 - 0.5 seconds Rocker 2-6 - 1 seconds Rocker 2-7 - 2 seconds Rocker 2-8 - 4 seconds
The value of the closed switches are added together to obtain the total time delay.
Count Selection - Rocker Switches 3-1 to 3-4
When a gate length of less than 0.5 second, the rockers select counts needed per gate for a fire signal. The val­ues of all rockers closed are added together. If no counts or less than 2 counts are selected (only rocker 1 closed), the microprocessor will select 2. Counts per gate are selectable in 1 count increments from 2 to 15 counts. The typical counts per gate setting used in most applications are between 2 and 8 counts.
Rocker 3-1 - 1 count Rocker 3-2 - 2 counts Rocker 3-3 - 4 counts Rocker 3-4 - 8 counts
When a gate length of 0.5 second or greater is used, the programmed counts per gate value is multiplied by a fac­tor that is determined by the gate length that has been programmed using rocker switches 2-5 to 2-8. Refer to Figure 22 to determine the proper multiplication factor. Note that the multiplication factor is determined by the highest numbered rocker switch in the closed position.
The STAR logic program uses this multiplication tech­nique to prevent accidental programming of a very low count value combined with a long gate length, since this combination would result in an extremely high sensitivity level that would increase susceptibility to false alarms.
For example, suppose that a gate length of 1.5 seconds and a sensitivity of 4 counts per gate is selected. Since the gate length exceeds 0.5 second, the counts per gate value must be multiplied by the factor determined
18
from Figure 22. In this case, 4 counts per gate is multi­plied by a factor of 4, to obtain a total programmed value of 16 counts per gate. Without this feature, it would be possible to program the system to interpret 4 counts in 1.5 seconds as a fire signal, which would make the system susceptible to frequent false alarms.
Consecutive Gate Selection - Rocker Switches 3-5 to 3-8
These rockers select the number of consecutive gates required for a fire signal. Consecutive gates are selectable in 1-gate increments from 2 to 15 gates. If fewer than 2 gates are selected (only rocker 5 closed), the microprocessor will select 2. The values of the rock­ers closed are added together. The typical consecutive gate settings used in most applications are between 3 and 8 gates.
Rocker 3-5 - 1 Gate Rocker 3-6 - 2 Gates Rocker 3-7 - 4 Gates Rocker 3-8 - 8 Gates
Detector Grouping/Voting Logic Selection 4-1 to 4-4
Rocker switches 4-1 to 4-4 are used to program the controller for the particular voting arrangement to be used. (Refer to the “System Description” section of this manual for a description of the options available with the Detector Grouping/Voting Logic feature.) Refer to Figure 20 (Switch Assembly 4) to determine the correct positions for rocker switches 4-1 to 4-4.
NOTE When in the Normal mode and the outputs are set for non-latching operation, the voting process will actuate the Fire Logic output(s) only if the pre­selected number of detectors “see” fire at the same time. When the outputs are set for latching opera­tion, the voting process will actuate the Fire Logic output(s) when voting criteria have been met, even if a fire is not being seen by each detector at the same time.
Detector Grouping - Rocker 4-1
Separate - closed Combined - open
When rocker switch 4-1 is closed, detectors 1 to 4 acti­vate the Alarm 1 and Fire Zone 1 outputs, and detectors 5 to 8 activate the Alarm 2 and Fire Zone 2 outputs.
When rocker switch 4-1 is open, a fire at any of eight detectors causes actuation of both Alarm outputs. Fulfillment of the programmed voting requirements results in actuation of both Fire Zone outputs.
Voting Selection - Rockers 4-2 to 4-4
Rocker switches 4-2 to 4-4 are used to program the controller for the particular voting logic arrangement to be used. Refer to the “Description” section of this man­ual for a description of the options available with the vot­ing logic feature. Then refer to the Voting Selection Table (Table 3) to determine the correct switch posi­tions.
Separate — For two separate voting groups: 4-1 is closed 4-2 is not used in this voting arrangement 4-3 programs Fire Zone output 2 (channels 5, 6, 7, 8)
- open, any one detector
- closed, any two detectors
4-4 programs Fire Zone output 1 (channels 1, 2, 3, 4)
- open, any one detector
- closed, any two detectors
19 95-8302
START
Figure 22—Multiplication Factors
Table 3—Voting Selection Table
ROCKER 2–8
CLOSED?
NO
ROCKER 2–7
CLOSED?
YES
YES
MULTIPLY BY 16
MULTIPLY BY 8
NO
NO
YES
YES
MULTIPLY BY 4
MULTIPLY BY 2
A974
ROCKER 2–6
CLOSED?
ROCKER 2–5
CLOSED?
SWITCH ASSEMBLY 4
VOTING LOGIC
ROCKER POSITION
4-1 CL CL CL CL OP OP OP OP
4-3
4-2
DC
DC
DC
DC
OP
DC
CL
DC
ALL OPEN 1 CLOSED 2 CLOSED 3 CLOSED
OP = OPEN, CL = CLOSED, DC = DON'T CARE
4-4 OP
CL DC DC
FIRE
ZONE
OUTPUTS
1 1 2
2 1•2 1•2 1•2 1•2
1•2 = 1 AND 2
DETECTOR RESPONSE
1 DETECTOR
2 DETECTORS
1 DETECTOR
2 DETECTORS 1 OF 8 DETECTORS 2 OF 8 DETECTORS 3 OF 8 DETECTORS 4 OF 8 DETECTORS
Common— For up to eight channels voting, and Fire Zone outputs 1 and 2 energized simultaneously: 4-1 is open 4-2, 4-3, 4-4 - All open = any one detector
Any one closed = any two detectors Any two closed = any three detectors All three closed = any four detectors
Outputs Latching/Non-latching - Rocker Switch 4-5
Once energized, an output will remain on (latching) until the controller is reset if rocker 4-5 is set open.
Rockers 4-6, 4-7 and 4-8 are not used.
When the proper position for each of the rocker switch­es has been determined, record this information careful­ly on the system layout chart in Figure 23. This provides a means of double checking switch positions before power is applied to the controller, and to provide a record of switch positions for future reference.
TYPICAL SYSTEM APPLICATION
The following application is an example only. For assis­tance in adapting a system to your individual require­ments, contact the Field Support Group at Detector Electronics.
Power is supplied to the system by a 24 volt dc power supply. A four conductor shielded cable is used to con­nect the detectors to the controller as shown in Figure
14. Terminals A and C (power connections) are com­mon to all the detectors in the system. The B- and D­leads of each detector are connected to their corre­sponding “B” and “D” terminals on the controller. The shields are tied together and grounded at terminal 33. A 0.47 microfarad, 250 volt capacitor is placed between terminal 5 and terminal 2. A remote reset switch is pro­vided for resetting the controller or inhibiting the outputs from a remote location. The connections are made to terminals 31 and 32.
Figure 23—System Layout Chart
20
SWITCH 1
DETECTOR SELECT
ROCKER OPEN CLOSED
1
2
3
4
5
6
7
8
OPEN SWITCH FOR EACH
DETECTOR CONNECTED
SWITCH 3
CONSECUTIVE GATE
SELECTION
ROCKER OPEN CLOSED
1
2
3
4
5 – 1 GATE
6 – 2 GATES
7 – 4 GATES
8 – 8 GATES
ADD VALUE OF CLOSED
ROCKERS – 2 GATES MINIMUM
SWITCH 3
COUNT SELECTION
ROCKER OPEN CLOSED
1 (1 COUNT)
2 (2 COUNTS)
3 (4 COUNTS)
4 (8 COUNTS)
ROCKERS – 2 COUNTS MINIMUM – USE MULTIPLICATION FACTOR
IF GATE IS 0.5 SECOND OR GREATER
A0975
5
6
7
8
ADD VALUE OF CLOSED
OPEN
OPEN
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
SWITCH 2
GATE LENGTH (SECONDS)
ROCKER OPEN CLOSED
8 – 4.0
7 – 2.0
6 – 1.0
5 – 0.5
4 – 0.25
3 – 0.125
2 – 0.062
1 – 0.031
ADD VALUE OF
CLOSED ROCKERS
SWITCH 4
OUTPUTS LATCHING
ROCKER OPEN CLOSED
1
2
3
4
5
6
7
8
OPEN = LATCHING
VOTING LOGIC
ROCKER OPEN CLOSED
1
2
3
4
5
6
7
8
SEE VOTING TABLE IN FIGURE 20
OPEN
SWITCH 4
OPEN
A0975
OPEN
OPEN
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
Power is connected to a load circuit through the normal­ly closed contacts of the Alarm relay. Detection of a fire causes the contacts to open and remove power from the load. If the pre-programmed voting requirements are met, power is applied to an extinguishing load through the Fire Zone relay. Power is connected to a process control circuit through the normally energized Fault relay. In the event of a system fault or when the controller is in the Test mode, the contacts open and remove power from the process. An annunciation device is connected to the power source through the Fault relay to provide a visual or audible warning of a system failure.
STARTUP PROCEDURE
The startup procedure should be performed after instal­lation of the equipment is complete.
1. After making the electrical connections and setting the switches, plug the controller into the wiring con­nector.
2. Disable any extinguishing system connected to the system.
3. Turn on the input power to the system and perform the “Initial and Periodic Checkout Procedure.”
4. If the controller is operating normally and is pro­grammed correctly, remove any mechanical block­ing devices and restore power to the extinguishing loads.
INITIAL AND PERIODIC CHECKOUT PROCEDURE
The entire system should be periodically checked with a UV/IR test lamp to be sure that the detectors are not obstructed, that the area “seen” by the detector has not changed, and that there is no fault in the oi circuit.
1. Place the Mode switch in the TEST position. The FAULT LED will be illuminated.
CAUTION
Placing the controller in the Test mode inhibits the outputs, rendering the system incapable of actuating any extinguishing or alarm circuits that are connect­ed to it. However, for maximum safety, secure the output loads that would normally be actuated by the system before performing the checkout procedure.
2. Shine the UV/IR test lamp into the viewing window of the detector under test. The ALARM LED is illu­minated and the corresponding DETECTOR LED blinks.
3. If the voting requirements are met, the appropriate FIRE ZONE LED(s) is also illuminated.
4. Turn off the UV/IR source. The FIRE ZONE LED remains on if it was previously illuminated. The DETECTOR LED remains on, but stops blinking.
5. Repeat steps 2 through 4 for each detector in the system.
6. After all detectors have been checked, reset the system by placing the Mode switch in the NORMAL position. All LEDs except the POWER LED are off.
7. Restore power to the output loads and remove any mechanical blocking devices.
Star Programming Checkout Procedure
1. Secure output loads (remove power from valves, relays or other devices that might otherwise be actuated by the UV/IR system) before testing.
2. Apply power to the UV/IR detection system.
3. Ensure that the area being monitored is operating under normal conditions (equipment that would nor­mally be on is on).
4. Place the UV/IR controller toggle switch in the NOR­MAL position and monitor for one hour.
— If the rockers have been set correctly, transient
radiation in the area should not activate the system. The upper and lower LED displays should remain dark. If this is the case, lower (more sensitive) set­tings can be attempted.
— If the system sensitivity is set too high, one of the
eight DETECTOR LEDs will turn on and the appro­priate FIRE ZONE LEDs will turn on if voting require­ments are met. If this happens, set the rocker switches for more counts per gate, for more con­secutive gates required for actuation, or for a short­er gate length and repeat the test. Altering detector placement may also decrease the susceptibility of the system to transient radiation.
For further assistance, contact the Field Support Group at Detector Electronics.
MAINTENANCE
The C7052J Detector requires no periodic calibration. However, to maintain maximum sensitivity, the detector viewing windows must be kept clean at all times. Even a small amount of certain UV or IR absorbing materials
21 95-8302
(sometimes barely detectable to the human eye) can significantly reduce the sensitivity of the detector. The windows and
o
i
rings should be thoroughly cleaned on a regular basis. The length of time between periodic cleanings will be determined by the nature and amount of contaminants present in the environment.
Remove the
o
i
rings by squeezing the tabs together and pulling away from the detector. Clean the viewing windows thoroughly, all the way to the edge. Also clean the reflective surface of the
o
i
rings (the surface of the ring that faces the detector viewing window). When re­installing an
o
i
ring, hold it by its tabs to avoid leaving fingerprints on the reflective surface. Re-install the ring so that the opening is pointed down to prevent a buildup of contaminants. If corrosive contaminants in the atmosphere cause the reflective rings to deteriorate to the extent that it is no longer possible to restore them to their original condition, they must be replaced.
Det-Tronics window cleaning solution (part number 001680-001) is designed specifically for cleaning the optical surfaces of the detector. DO NOT use commer­cial cleaners. These products can leave a residue on the surface that is intended to give it a “sparkling” look, however, this residue can substantially attenuate the radiation reaching the sensor.
Use a clean cloth or tissue to clean the window. DO NOT use commercial glass cleaning tissues, since many of these contain a silicone substance that remains on the window after cleaning. Silicone readily absorbs radiation and can effectively “blind” the detector, even though the window appears to be clean.
NOTE When cleaning the detector windows, remove input power or place the system in the “Bypass” or “Reset/Inhibit” mode. Rubbing motion on the sur­face of the windows during cleaning can create an unwanted output activation.
Viton O-rings on each of the detector housings are used to ensure the watertight integrity of the detector. Periodically, the housing should be opened and the O­rings inspected for breaks, cracks, and dryness. To test them, remove the rings from the detector housing and stretch them slightly. If cracks are visible, the ring should be replaced. If they feel dry to the touch, a thin coating of lubricant should be applied. When re-installing the rings, be sure that they are properly seated in the groove on the housing. It is imperative that these O-rings be properly installed and in good condition. Failure to maintain these rings can allow water to enter the detector and cause premature failure. The life expectancy of Viton O-rings can vary considerably, depending on the amount and
nature of contaminants that are present in the environ­ment. The individual responsible for maintenance of the system must rely on experience and common sense to determine how frequently the rings should be inspected.
The recommended material for lubricating the O-rings is a silicone free polyalphaolefin grease, part number 005003-001, available from Detector Electronics. A coating of lubricant should also be applied to the threads on the sensor housings before reassembling the detector. This will both lubricate the threads and help to prevent moisture from entering the detector housing.
Refer to “Recommended Spare Parts” in the “Ordering Information” section of this manual for a list of products available from Detector Electronics for maintenance of the detector.
Sensor Module Replacement Procedure
To replace a defective module:
CAUTION
Do not open the detector housing in a hazardous location without first removing power.
a. Remove power from the detector.
b. Remove the sensor housing (see Figure 12).
c. Remove the sensor module.
d. Determine the proper orientation for the new
sensor module (with the o
i
test lamps posi­tioned at the top or side of the detector), then install the module. Attach the connector plug (DE5500 models of the IR sensor only).
e. Ensure that the O-rings at the base of the sen-
sor housing are positioned correctly and in good condition. (Refer to the “Maintenance” section of this manual for complete informa­tion regarding care of O-rings.)
f. Re-install the sensor housing. Hand tighten
the sensor housing into the base until the O­ring is fully seated to ensure explosion-proof and watertight integrity of the housing.
g. Inspect the viewing windows and o
i
rings and
clean if necessary. Also check the position of
the o
i
rings.
h. Perform the “Startup Procedure” before return-
ing the system to normal operation.
22
TROUBLESHOOTING
Table 4 is intended to serve as an aid in locating the source of a system malfunction. The R7495B Controller is not designed to be repaired by the customer in the field, but should be returned to the factory in the event of a mal­function. Refer to the “Maintenance” section of this man­ual for information regarding servicing of the detector.
DEVICE REPAIR AND RETURN
Prior to returning devices or components, contact the nearest local Detector Electronics office so that an RMI (Return Material Identification) number can be assigned. A written statement describing the malfunc­tion must accompany the returned device or component to expedite finding the cause of the failure, thereby reducing the time and cost of the repair to the customer. Return all equipment transportation prepaid to the facto­ry in Minneapolis.
Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Operator: (952) 941-5665 or (800) 765-FIRE Customer Service: (952) 946-6491 Fax: (952) 829-8750 Web site: www.detronics.com E-mail: detronics@detronics.com
ENGINEERING SPECIFICATIONS
The UV/IR flame detection system shall have a micro­processor-based controller that can operate up to 8 detectors and provide relay outputs through the use of a relay output module. The controller shall be field pro­grammable for selecting time delay length, sensitivity, voting output configuration, and latching or non-latching operation. The system shall operate on 24 vdc. The UV/IR flame detection system shall be capable of responding to a 1 foot by 1 foot gasoline fire at a dis­tance of 50 feet. The detector shall be capable of 1.0 second response time to an intense fire signal. It shall not respond to radiation generated by arc welding, x rays, or hot surfaces, but shall be capable of respond­ing to a fire in their presence. The UV/IR flame detector shall be in a red, copper-free aluminum enclosure1. The detector shall be the Det-Tronics model C7052J, no equal. The controller shall be the Det-Tronics model R7495B Controller and the that fits in the Det-Tronics model Q4004 Mounting Rack which is designed to fit standard 19” racks, no equal.
The UV/IR flame detector shall have one 3/4” NPT2 entry for field wiring.
The controller shall have visual annunciation of fire and fault conditions. The controller shall have eight red LEDs for individual detector alarm indications, one green LED for power indication, one yellow LED for fault indication, one red LED to indicate an alarm, and two red LEDs for fire zone (voting) output indication.
The signal processing shall require the UV radiation and the flickering IR radiation to exceed field adjust thresh­old levels and time delay before signalling an alarm condition. The detector shall have a 80 degree cone of vision and be of a modular plug-in design that allows the UV and IR sensor modules to be easily field replaced without the use of special tools. All optical surfaces shall be easy to access for cleaning. No metal rods shall be allowed in front of the sensor windows.
The UV/IR flame detector shall have optical testing capabilities on both the UV and IR sensor. Films that blind the UV sensor or the IR sensor shall cause a fail­ure of the optical test.
The UV/IR flame detector shall be rated for an operating temperature range of -40°F to +167°F (–40°C to +75°C) and a storage temperature of -40°F to +185°F (–40°C to +85°C). The detector shall operate over a humidity range of 0 to 95% RH and be able to withstand 100% condensing humidity for short periods of time. All print­ed circuit boards shall be coated to provide protection from the environmental conditions. The UV/IR flame detector shall meet MIL-STD 810C for vibration and
23 95-8302
Table 4—Troubleshooting Guide
Problem Possible Cause
No POWER LED 1. Input power failure.
2. Wiring to external power source
3. Controller power supply failure.
FAULT LED on 1. Mode switch in TEST position.
2. Low input voltage.
FAULT LED and a 1. o
i
fault - dirty window and/or the
DETECTOR LED on o
i
ring
2. Detector module has lost sensitivity
3. Detector wiring problem
FAULT LED off, 1. Detector responding to UV/IR DETECTOR LED source not large enough to exceed blinking slowly the fire threshold programmed into
the controller
ALARM LED on, no 1. Mode switch in TEST position. actuation of outputs 2. Output circuit failure.
have a swivel mounting bracket to provide a means to easily mount and aim the detector.
The UV/IR flame detector shall be explosion-proof for Class I, Division 1, Groups B, C and D; Class II, Division 1, Groups E, F and G. The device shall be rated NEMA 4 (dust-tight, watertight). The detector shall be FM approved3.
An explosion-proof UV/IR test lamp shall be provided to allow field testing of the UV/IR flame detection system. The test lamp shall be FM approved for use in Class I, Division 1, Groups C and D hazardous areas. The explosion-proof UV/IR test lamp shall be the Det-Tronics model W867, no equal.
The following options can be substituted for the item in bold:
1
or: “in a 316 stainless steel enclosure.”
2
or “25 mm”
3
or: “flame-proof for EEx d IIB. The device shall
be rated IP66 (dust-tight/water-tight). The detector shall be BASEEFA/CENELEC certi­fied.”
or: “explosion-proof for Class I, Division 1,
Groups C and D; Class II, Division 1, Groups E, F and G. The device shall be rated NEMA 4 (dust-tight, watertight). The detector shall be CSA certified.
ORDERING INFORMATION
When ordering, specify: — R7495B Controller — C7052J Detector — Number detectors needed — Detector housing materials
— Anodized copper-free aluminum — 316 stainless steel
— Approvals required
—FM — CSA — BASEEFA/CENELEC
ACCESSORIES
— Q4004 Mounting Cage accommodates eight mod-
ules (Controllers) and fits standard 19-inch instru­ment rack. Smaller sizes are available.
— Filler panels for empty spaces in the Q4004
Mounting Cage — 000507-XXX power supplies — Cover locking assembly — Q1113 Air Shields — W867 UV/IR Test Lamp — Q9001G Swivel Assembly
RECOMMENDED SPARE PARTS
Description Part Number Quantity UV
o
i
rings 002519-001 2 per 10 detectors
IR
o
i
rings 003525-001 2 per 10 detectors UV Sensor Module DE1888 1 per 10 detectors IR Sensor Module 003895-001 1 per 10 detectors
(plug-in type)
003895-002 1 per 10 detectors IR Sensor Module 005500-001 1 per 10 detectors (wire harness type)
Junction box circuit board004432-001 1 per 10 detec­tors O-rings 107427-004 4 per 10 detectors Grease 005003-001 1 per 10 detectors
(silicone-free)
Window Cleaner Kit 001680-001
(six bottles)
APPLICATION ASSISTANCE
For assistance in ordering a system to fit your applica­tion, please contact:
Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Operator: (952) 941-5665 or (800) 765-FIRE Customer Service: (952) 946-6491 Fax: (952) 829-8750 Web site: www.detronics.com E-mail: detronics@detronics.com
24
Loading...