Detcon X40-08-N4X, X40-32-N4X, X40-32-N1P, X40-32-N7 Operator's Installation And Instruction Manual

Model X40-08-N4X, Model X40-32-N4X
www.detcon.com
Model X40-32-N1P, Model X40-32-N7
Integrated Alarm and Control System
In t e g r a t e d Al a r m & C on t r o l S ys tem
Operator’s Installation and Instruction Manual
Covers all Model X40 Control Systems
DETCON, Inc.
The Woodlands, Texas 77381
Ph.713.559.9200 / Fax 281.298.2868
January 5, 2015• Document #3672 • Revision 3.4
Model X40
This page left intentionally blank
Shipping Address: 4055 Technology Forest Blvd., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 713.559.9200 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
Model X40 Instruction Manual Rev. 3.4 ii
Model X40
Table of Contents
1.0 Introduction........................................................................................................................................1
1.1 Features .......................................................................................................................................................... 1
1.2 LCD Main Display Function..........................................................................................................................2
1.3 ModbusCommunication ............................................................................................................................ 2
1.4 Secure Digital Card (SD Card)....................................................................................................................... 2
1.5 I/O Modules and Connections ........................................................................................................................ 2
1.6 Enclosure Types ............................................................................................................................................. 4
1.7 Alarms and Fault Condition ........................................................................................................................... 5
1.8 System Operation ........................................................................................................................................... 6
1.9 Operator Interface...........................................................................................................................................7
1.9.1 Magnetic Programming Tool...................................................................................................8
1.9.2 Front Panel User Interface......................................................................................................8
1.10 Main Display Functions ................................................................................................................................. 9
1.10.1 Sensor Group...........................................................................................................................9
1.10.2 Transceiver Group...................................................................................................................9
1.10.3 RL4/Alarm Stations Group....................................................................................................10
1.10.4 AO-4 Group...........................................................................................................................10
1.11 Menu Function ............................................................................................................................................. 10
1.12 Optional Remote Alarm Reset/Acknowledge Switch .................................................................................. 11
1.13 Wireless Option............................................................................................................................................ 12
2.0 Installation........................................................................................................................................13
2.1 Safety Guidelines ......................................................................................................................................... 13
2.2 N1P and N1R Enclosure Installation............................................................................................................ 13
2.3 N4X Enclosure Installation .......................................................................................................................... 16
2.4 N7 Enclosure Installation ............................................................................................................................. 21
2.4.1 NEMA7 units with RXT-320 Transceiver ..............................................................................24
3.0 I/O Connections ...............................................................................................................................28
3.1 I/O Module Installation ................................................................................................................................ 28
3.2 Analog 4-20mA Sensor Inputs (DA-4) ........................................................................................................ 29
3.3 Dry Contact Inputs (DI-4) ............................................................................................................................ 30
3.4 Analog 4-20mA Outputs (AO-4).................................................................................................................. 31
3.5 Alarm Relay Outputs (RL-4)........................................................................................................................ 33
3.6 RS-485 Serial Gas Sensors........................................................................................................................... 34
3.7 Wireless RXT-320 ModbusDevices and CXT-320 Sensors.................................................................... 35
3.8 RXT-320 Wireless transceiver Analog Inputs.............................................................................................. 35
3.9 SmartWireless® CXT Sentinel Slave Controller ......................................................................................... 36
3.10 SmartWireless® CX Sentinel Sensor Station............................................................................................... 38
3.11 General Installation Wiring Notes................................................................................................................ 39
3.12 Initial Start-Up.............................................................................................................................................. 39
4.0 Secure Digital Card .........................................................................................................................40
5.0 System Configuration......................................................................................................................41
5.1 X40 Controller Setup.................................................................................................................................... 41
5.2 Menu Functions............................................................................................................................................ 41
5.2.1 Auto Configure System...........................................................................................................41
5.2.2 Setup Channel Data...............................................................................................................42
5.2.3 Set Channel Alarms ...............................................................................................................43
5.2.4 Set Relay (Alarm) Functions..................................................................................................44
5.2.5 Inhibit and Alarm Test Mode.................................................................................................45
5.2.6 System Diagnostics................................................................................................................45
5.2.7 Time and Date........................................................................................................................46
5.2.8 View TWA and Peak ..............................................................................................................47
Model X40 Instruction Manual Rev. 3.4 iii
Model X40
6.0 ModbusSlave Communications Port.........................................................................................48
6.1 ModbusRegister Map...............................................................................................................................48
7.0 Remote Alarm Reset/Acknowledge Switch Installation...............................................................50
8.0 Troubleshooting Guide....................................................................................................................51
8.1 Replacement of the display PCA in NEM7 units .........................................................................................51
8.2 Replacement of the NEMA 4 Drop-In Display Assembly............................................................................52
9.0 Customer Support and Service Policy ...........................................................................................53
10.0 Warranty Notice ..............................................................................................................................54
11.0 Appendix...........................................................................................................................................55
11.1 Specifications................................................................................................................................................55
11.2 Hexadecimal Table.......................................................................................................................................56
11.3 Utilities .........................................................................................................................................................57
11.3.1 Set Channel Data...................................................................................................................57
11.3.2 Set RF Silence and RF Sleep (Wireless Function Only)........................................................59
11.3.3 Set Low Battery Alarms .........................................................................................................59
11.3.4 Set ModbusAddress...........................................................................................................60
11.3.5 CXT Low Battery Threshold..................................................................................................60
11.3.6 Module Update Interval.........................................................................................................60
11.3.7 Set COMM Baud Rates..........................................................................................................60
11.3.8 Set ModbusTimeouts.........................................................................................................61
11.3.9 Display Settings .....................................................................................................................61
11.4 Spare Parts and Wireless Accessories...........................................................................................................63
11.5 Revision Log.................................................................................................................................................64
Table of Figures
Figure 1 Model X40-N4X Controller..............................................................................................................1
Figure 2 Menu Flow Chart...............................................................................................................................7
Figure 3 Magnetic Programming Tool ............................................................................................................8
Figure 4 Front Panel User Interface.................................................................................................................8
Figure 5 Radio Module..................................................................................................................................12
Figure 6 N1P Controller Mounting and Dimensional View..........................................................................14
Figure 7 N1P RS-485 Port Connections........................................................................................................15
Figure 8 X40-08-N4X Controller Mounting and Dimensional View............................................................16
Figure 9 X40-32-N4X Controller Mounting and Dimensional View............................................................17
Figure 10 N4X Protective Earth Connector...................................................................................................18
Figure 11 Display Wiring..............................................................................................................................18
Figure 12 Cable Entry Points.........................................................................................................................18
Figure 13 N4X AC/DC Inputs.......................................................................................................................19
Figure 14 N4X RS-485 Master Port Connections.........................................................................................19
Figure 15 N4X RS-485 Slave Port Connections............................................................................................20
Figure 16 N4X Antenna Connector...............................................................................................................20
Figure 17 N7 Controller Mounting and Dimensional View ..........................................................................21
Figure 18 N7 Controller PCA........................................................................................................................22
Figure 19 N7 Controller Assembly w/Mounting Plate..................................................................................22
Figure 20 N7 AC/DC Converter Board Wiring.............................................................................................23
Figure 21 N7 DC Power Wiring....................................................................................................................24
Figure 22 Typical NEMA7 with Transceiver ................................................................................................25
Figure 23 Model 100 Terminal Board...........................................................................................................25
Model X40 Instruction Manual Rev. 3.4 iv
Model X40
Figure 24 Model 100 Terminal Board Rotary Switches................................................................................26
Figure 25 N7 AC/DC Converter Board Wiring with Transceiver.................................................................26
Figure 26 N7 DC Power Wiring with Transceiver........................................................................................27
Figure 27 I/O Module Installation.................................................................................................................28
Figure 28 Model DA-4 4-20mA Input Module and 4-20mA Gas Sensor Connections................................29
Figure 29 Model DA-4 4-20mA Input Module and 4-20mA Gas Sensors....................................................30
Figure 30 Model DI-4 Contact Input Module................................................................................................31
Figure 31 Model AO-4 4-20mA Output Module...........................................................................................32
Figure 32 Model RL-4 Relay Output Module...............................................................................................33
Figure 33 ModbusGas Sensor Connections..............................................................................................35
Figure 34 CXT Wireless Transceiver............................................................................................................37
Figure 35 CXT Relay Output PCA................................................................................................................37
Figure 36 CXT Analog Input PCA................................................................................................................37
Figure 34 N1P & N4X Remote Switch Input................................................................................................50
Figure 35 N7 Remote Switch Input...............................................................................................................50
Figure 36 Detcon C1D1 Switch Connections................................................................................................50
Figure 37 NEMA 7 Display Assembly PCA.................................................................................................51
Figure 38 NEMA 4 Drop-In Display Assembly............................................................................................52
List of Tables
Table 1 X40 Model 100 Terminal Board Connector Plugs...........................................................................25
Table 2 AO-4 ModbusAddresses..............................................................................................................32
Table 3 RL-4 Relay ModbusAddresses....................................................................................................34
Table 4 X40 Register Map.............................................................................................................................48
Model X40 Instruction Manual Rev. 3.4 v
Model X40
This page left intentionally blank
Shipping Address: 4055 Technology Forest Blvd., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 713.559.9200 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
Model X40 Instruction Manual Rev. 3.4 vi
Model X40
1.0 Introduction
1.1 Features
The Detcon X40 controller (Figure 1) is a multi-channel gas detection control system. The X40 serves as a host monitor/controller for a network of gas detection sensors and various other field devices. The controller offers a non-intrusive magnetic interface with backlit LCD display and Modbustechnology that supports either wireless or a hard wire sensor connection. The X40 is equipped with an auto configure feature to automatically search the Modbusaddresses for various Detcon equipment associated with the controller and adds the equipment to the controller without user intervention.
Remote mounted gas detection sensors include any analog 4-20mA or RS-485 (Modbus) serial devices such as;
toxic gas, combustible gas, or oxygen deficiency sensors.
Remote field devices include contact closure inputs such as:
liquid level, temperature, pressure, or smoke detection devices.
In t e g r a t e d Al a r m & Co n t r o l Sy s t e m
Figure 1 Model X40-N4X Controller
Model X40 Instruction Manual Rev. 3.4 Page 1 of 65
Model X40
1.2 LCD Main Display Function
The main display is an 11/4" x 6" backlit LCD that is four lines by forty characters and displays up to eight configured channels at one time. The four internal magnetic switches are located above the backlit LCD display and offer basic navigation for a complete configuration of the controller (Section 5.1).
Real time sensor status includes:
channel number gas concentration, device tag (gas type) alarm/fault status.
Each channel displays the current status of three alarm levels and a fault condition on the front panel LED indicators.
1.3 ModbusCommunication
The controller uses the RS-485 ModbusRTU protocol to communicate with RS-485 serial sensors and I/O modules. A secondary Modbusport is addressable by a PLC, PC/HMI, DCS or other Modbus RTU master-polling devices.
Primary ModbusInterface (COMM1 Master)
Uses two-wire half duplex RS-485, 9600 baud, 8 data bits, 1 stop bit, no parity. Communicates directly
with Modbus™ capable sensors and Detconꞌs independently addressable I/O modules that operate on 11.5-
30VDC.
Secondary ModbusInterface (COMM2 Slave)
The Modbusslave interface communicates with the remote display or an additional controller.
1.4 Secure Digital Card (SD Card)
The X40 controller allows data logging when an SD memory card is installed. The card must be installed on the back of the PCA (printed circuit assembly) before the controller is powered up. The controller will automatically format the card (Section 4.0) and create the necessary files for data logging.
Data logging does not occur during the first 10 minutes after power-up of the unit. This
NOTE
delay allows the sensors time to stabilize, so that inaccurate or faulty readings will not be logged during this stabilization period.
1.5 I/O Modules and Connections
A maximum of 32 sensor channels are configurable for the X40 models and are customizable using
Detconꞌs I/O modules. Accommodation for the I/O modules relies on the type of enclosure utilized.
Seamless system expansion is accomplished through DIN rail mounted and stackable modules. The modules communicate with the controller using Modbustechnology and are available in four types;
4-20mA inputs dry contact inputs 4-20mA outputs relay outputs.
Model X40 Instruction Manual Rev. 3.4 Page 2 of 65
Model X40
The analog sensors and analog field devices interfaced to the I/O modules communicate with the COMM1 Modbusmaster port on the X40 controller via the I/O Module. Serial sensors interface directly with the COMM1 port and do not require I/O modules. The types of sensors/field devices interfaced will dictate the I/O modules required for the X40 controller. Configuration inputs are completely field-configurable providing a distinctive combination of flexibility and expansion for the customer.
I/O modules are factory installed unless specifically instructed otherwise. The number of I/O modules that can be installed in the X40 enclosure is dictated by the enclosure due to physical space limitations. Additional I/O modules in excess of the maximum allowed for each enclosure must be mounted in a separate enclosure by the customer. The module limits for each enclosure varies dependent on the type of enclosure, and the set-up of the particular unit. The typical limitations are as follows:
X40-32-N1P enclosure - maximum of two I/O modules (Mounted on the back, outside)
X40-08-N4X enclosure - maximum of six I/O modules inside
X40-32-N4X enclosure - maximum of twelve I/O modules inside
X40-32-N7 enclosure - does not accommodate module installations
The X40 controller can be configured for various I/O module combinations at the Detcon factory. Customer application/site specific information must be provided on the Configuration Form. Information provided is verified for correct quantity and type of I/O modules to support application/site requirements. The customer should supply the following site specific information:
1. Number of gas/sensor channels.
2. Detcon sensor model number and I/O type (Modbusor 4-20mA) for each channel.
3. Range, units, and gas type for each channel.
4. Alarm level(s) for each gas channel.
5. Device Tag for each channel.
6. Assignment and set-up information for each relay contact.
7. Analog output requirements for each channel.
NOTE
The set-up configuration is executed by the user in the field (Section 5.0). Modifications to are expected to take place on site due to requirement changes and/or system expansions.
Detcon I/O Modules (Purchased Separately)
Analog 4-20mA Sensor Inputs (DA-4)
Provides power to any two or three wire field sensors
Receives standard 4-20mA signal outputs from the sensors
Four 4-20mA inputs to support up to four sensors
Uses RS-485 ModbusRTU protocol to communicate with the controller and must have a unique Modbusaddress set between 01 and 7Fh.
Dry Contact Inputs (DI-4)
Relay contact outputs from field devices can be connected
Four relay contact inputs
Can be installed on the DIN rail of the controller
Uses RS-485 ModbusRTU protocol to communicate the state of the contact outputs from field devices and must have a unique Modbusaddress set between 01 and 7Fh.
Analog 4-20mA Outputs (AO-4)
Provide a 4-20mA output equal to the current concentration reading reported to the controller for the associated channel.
Uses RS-485 ModbusRTU protocol to receive the 4-20mA output levels. AO-4 modules must have a unique Modbusaddress set between A0 and AFh.
Model X40 Instruction Manual Rev. 3.4 Page 3 of 65
Model X40
Alarm Relay Outputs (RL-4)
Alarms can be used to control (fire) annunciating devices or signal inputs to other control devices.
Four Form C, Single Pole Double Throw (SPDT), 5 Amp relay contacts each assigned specifically to one alarm.
Uses RS-485 ModbusRTU protocol to communicate the outputs and must have a unique Modbusaddress set between 80 and 8Fh.
The X40 controller is configured with a maximum of eight separate relay banks each holding up to two RL-4 modules.
Anytime a specific alarm (e.g. Alarm 3) is fired for a particular module in a bank (e.g. Bank2), all corresponding alarms (e.g. Alarm 3’s) for all modules in that particular bank (e.g. Bank2) are also triggered.
RS-485 Serial Gas Sensors (Modbus)
RS-485 Serial gas sensors can be interfaced directly with the X40 controller without the use of I/O modules by connecting the sensors in a series to the primary RS-485 Modbusinterface (RS-485 Master Port).
1.6 Enclosure Types
The X40 controller is available in three enclosure types to accommodate various customer needs and configurations. The number of I/O modules varies depending on the enclosure type and configuration.
N1P Enclosure
The Model X40-32-N1P controller is housed in a NEMA 1 panel mount enclosure for indoor use. The internal power supply of the N1P controller converts 100-120/220-240VAC to 24VDC and can power a maximum of 32 sensors and associated I/O modules. A maximum of two I/O modules can be installed on the outside of the controller. Additional modules must be mounted separately by the customer.
The power supply for the N1P is capable of handling AC inputs from 100-120/220-240VAC, 50-60Hz without degradation. The X40 controller can be powered by an external DC source that meets the input requirements (11.5-30VDC) of the unit if AC power is not preferred or available. DC power can be used for primary or back-up power in the event of an AC power failure. RS-485 and power out are provided for connection to sensors attached to the unit.
N4X Enclosure
The X40 controller is available in two different size models for the N4X enclosure type. Both the X40-08­N4X and X40-32-N4X controllers are housed in a NEMA 4X water/corrosion proof enclosure for indoor/outdoor use. The power supplies for both enclosure types are capable of handling AC inputs from 100-120/220-240VAC, 50-60Hz without degradation. The X40-N4X can be powered by an external DC source that meets the input requirements (11.5-30VDC) of the X40 if AC power is not preferred or available. This input can be used for primary power or back-up power in the event of an AC power failure. The DC output voltage is capable of delivering a maximum of 2 Amps of current to the sensors attached to the X40 controller.
RS-485 master port and power out are provided for connection to serial sensors attached to the unit.
The X40-08-N4X enclosure houses a maximum of six I/O modules inside of the controller and is capable of communicating with a maximum of 32 devices. The enclosure can incorporate integral alarms such as an 8" strobe mounted on the top of the enclosure, horn, or both.
The X40-32-N4X enclosure houses a maximum of twelve I/O modules inside of the controller and communicates with up to 32 devices.
Model X40 Instruction Manual Rev. 3.4 Page 4 of 65
Model X40
N7 Enclosure
The X40-32-N7 controller is housed in an explosion proof NEMA 7 enclosure for indoor/outdoor use. The N7 enclosure does not accommodate module installations. Modules must be mounted externally by the customer. Any sensors and associated I/O modules will need to be powered separately by the customer.
The X40 controller can be powered directly by an external DC source provided by the customer, which meets the input requirements (11.5-30VDC) of the unit. A plug-in male connector is provided for input wiring terminations. A plug-in male connector provides quick disconnect convenience during replacement or servicing.
An optional AC/DC converter board inside a condulet/J-Box is available from Detcon to only power the N7 controller with an AC voltage source. The converter uses AC inputs between 100-240VAC and provides a 24VDC (up to 167mA) output. Power to I/O modules or sensors must be provided by the customer.
Detcon offers an optional mounting plate for mounting the X40-32-N7 controller to a pole.
1.7 Alarms and Fault Condition
The alarms (Alarm 1, Alarm 2, Alarm 3, and Fault) can be used to control annunciating devices or as signal inputs to other control devices. The field configurable magnetic user interface permits alarm values and fault condition to cause an assigned relay or bank of relay outputs to fire, triggering external alarm devices. The assigned relay outputs will return to normal state when a gas alarm or a fault condition clears. Additionally, an external manual switch can be wired to the X40, acting as an acknowledge/reset switch (Section 1.12).
When the X40 is in alarm, the display will remain on the channel group with the alarm. When there is more than one alarm/fault, the controller will cycle through group pages with alarms/faults including the transceiver, RL-4/alarm station, and AO-4 group pages. The user can manually cycle to any group page that exists using the arrow switches. After a time out period, the X40 will resume page cycle protocols based upon the existence of alarms/faults. Four LED indicators on the front panel show alarm/fault alarm output status and are labeled respectively as ALM 1 (yellow), ALM 2 (yellow), ALM 3 (red), and FAULT (blue).
All alarms can be configured Energized/De-Energized, Latching/Non-Latching and Silenceable/Non­Silenceable for the relays.
Energized Mode
The normally open contact is closed if the alarm level has not been reached or if the sensor is not in fault. Energized mode provides for fail-safe operation since a loss of power or cable failure will cause the contact to be open.
De-Energized Mode
The normally open contact is open if the alarm level has not been reached or if the sensor is not in fault.
Silenceable
The corresponding alarm LED and relay can be deactivated by acknowledging the Alarm Silence function on the front panel of the X40 controller or by activating the external acknowledge switch if installed (Section 7.0).
Model X40 Instruction Manual Rev. 3.4 Page 5 of 65
Model X40
Non-Silenceable
The corresponding alarm LED and relay will remain activated until the cause of the alarm or fault is clear.
Latching Mode
The relay can be deactivated after the alarm condition has cleared by acknowledging the Alarm Reset function on the front panel of the X40 controller or by activating the external reset switch if installed (Section 7.0).
Non-Latching Mode
The relay is deactivated as soon as the sensor alarm or fault condition is clear.
1.8 System Operation
The setup of the controller is critical for proper operation. Modbusaddresses must be correct on all the devices connected to the controller before the controller will acknowledge the devices. Each wireless sensor must have a unique Modbus address (refer to sensor manual for details). The number of sensors is determined during auto configure if the addresses on the sensors and modules are set correctly.
The operator interface of the X40 utilizes four internal magnetic switches located above the controller’s backlit LCD display. The four switches provide a non-intrusive interface and allow for complete configuration of the controller and are labeled as follows:
PROG,
(Up Arrow),
(Down Arrow) and
ENTER.
The ENTER switch also doubles as a RESET/ACK switch from the Main Display only (not in Menu Mode).
Model X40 Instruction Manual Rev. 3.4 Page 6 of 65
Model X40
1.9 Operator Interface
Reference the Menu Flow Chart (Figure 2) to learn how to easily navigate the menus and make changes.
MAIN DISPLAY
NORMAL OPERATION
MAIN MENU
AUTO CONFIGURESYSTEM
MAIN MENU
SETUP CHANNELDATA MENU
MAIN MENU
SET CHANNEL ALARMS
MAIN MENU
SET RELAYFUNCTION
CHANNELS: ## AO4S: # RXT-320S:## RL4/ALM BANK 1: # RL4/ALM BANK 2: #
SLAVE ID: ## DEVICE TYPE:
ANALOG INPUT: # DECIMAL POINT: # RANGE: ###
TYPE: RL4 BANK CNT:#
ALM1 LEVEL: ##
ALM1 ASCENDING: Y/N
ALM2 LEVEL: ##
ALM2 ASCENDING: Y/N
ALM3 LEVEL: ##
ALM3 ASCENDING: Y/N
LATCHING (Bank1): Y/N
ENERGIZED (Bank1): Y/N
SILENCEABLE (Bank1): Y/N
LATCHING (Bank2): Y/N
ENERGIZED (Bank2): Y/N
SILENCEABLE (Bank2): Y/N
Multiple Channels
Multiple Channels
Multiple Relays
(Fault, Alm1,Alm2, Alm3)
UTILITY MENU
UTILITY MENU
SETUP CHANNELDATA
UTILITY MENU
SET RFSILENCE
AND RFSLEEP
UTILITY MENU
SET LOW BATTERY ALARMS
UTILITY MENU
SET MODBUSADDRESS
UTILITY MENU
SET CXT LOW BATTERY
THRESHOLD
UTILITY MENU
SET MODBUS UPDATEINTERVAL
Multiple Channels
SLAVE ID: ## inhex
DEVICE TYPE: XXXXXX
ANALOG INPUT: # DECIMAL POINT: # RANGE: #####
TYPE: XXXXXXXXX RL4 BANK: XXX
RF SILENCE: ON/OFF RF SLEEP: ##:## RF SLEEP: ON/OFF
TTE(DD:HH:MM): ##:##:## SOC(%): ###%
MODBUS ADDRESS: ###
THRESHOLD: 5-7 VDC
UPDATE INTERVAL: 0-5 mins
MAIN MENU
INHIBIT &ALARM TESTMODE
MAIN MENU
SYSTEM DIAGNOSTICS
MAIN MENU
TIME ANDDATE
MAIN MENU
VIEW TWA& PEAK
INHIBIT MODE: #:## INHIBIT MODE: START/STOP ALARM TEST MODE: ON/OFF
LCD DISPLAY TEST LED DRIVER TEST EXT RESET SWITCH TEST RELAY DRIVER TEST MODBUS DRIVER TEST
TIME: HH:MM:SS DATE: MM/DD/YY
DATE,TIME,CHANNEL, TWA:######,PEAK: ######
UTILITY MENU
SET COMM BAUDRATES
UTILITY MENU
SET MODBUS TIMEOUTS
UTILITY MENU
DISPLAY SETTINGS
COMM1 BAUD RATE: ####
COMM2 BAUD RATE: ####
RESPONSE TIMEOUT: #### INTERPOLL DELAY: ####
BRIGHTNESS: ### BACKLIGHT TIMEOUT: #:## CONTRAST: ###
Figure 2 Menu Flow Chart
Model X40 Instruction Manual Rev. 3.4 Page 7 of 65
Model X40
1.9.1 Magnetic Programming Tool
The magnetic programming tool (Figure 3) is used to operate the magnetic switches. For switch activation, the programming magnet is briefly held on the switch marker () and then removed. This action will be referred to as a "swipe" for the remainder of this manual.
Figure 3 Magnetic Programming Tool
1.9.2 Front Panel User Interface
The front panel user interface (Figure 4) contains four switches necessary to configure the X40 controller.
I n t e g r a t e d A l a r m & C o n t r o l S y s t e m
Figure 4 Front Panel User Interface
PROG Switch
From the Main Display, the PROG switch enters into the Main Menu. Once inside the Main Menu, the PROG switch acts as an "Escape" switch that moves backwards in the menu flow chart.
NOTE
While in Main Menu mode there are no updates to gas readings and hence no alarms will take place.
Up Arrow Switch
This switch moves the user up the Main Menu flow chart. It is also used to change selected entries in the menu selections in the upward direction.
Down Arrow Switch
This switch moves the user down the Main Menu flow chart. It is also used to change selected entries in the menu selections in the downward direction.
ENTER and RESET/ACK Switch
This switch has multi-purpose use:
Model X40 Instruction Manual Rev. 3.4 Page 8 of 65
Model X40
The ENTER function is used to accept selections in all menu screens and to execute the Reset
and Acknowledge functions.
The Reset function releases all latched relays once the alarm/fault condition has cleared.
The Acknowledge function will disengage any silenceable relays that are in an active state.
This is used to silence alarms once the end-user has assessed the alarm condition.
The RESET/ACKNOWLEDGE function of the switch is only applicable from the Main Display
and not while in Main Menu mode.
1.10 Main Display Functions
When the X40 is in alarm, the LCD display will stay on the channel group with the channel in alarm. If more than one alarm/fault exists, the X40 will cycle through group pages with alarms/faults including the transceiver, RL-4/alarm station, and AO-4 group pages. At any time the user can manually cycle to any group page using the arrow switches. After a time out period (15 seconds), the X40 will resume page cycle protocols based upon the existence of alarms/faults. Four LED indicators on the front panel show alarm and fault alarm output status. The LEDs represent ALM 1 (yellow), ALM 2 (yellow), ALM 3 (red) and FAULT (blue).
NOTE
The X40 only cycles through sensor group pages when no alarms/faults exist.
1.10.1 Sensor Group
XX> YYY "Device Tag" XX – represents the corresponding channel number YYY – the gas concentration value "Device Tag" – Either user enter tag or:
IN ALARM# = If any channel is in any gas alarm condition, # is the alarm level. IN FAULT = If any gas channel is in fault. COMM ERR = If any channel is not appropriately communicating with the device.
1.10.2 Transceiver Group
WTXX ‘Status’ YYY% XX – represents the transceiver Modbusslave address. ‘Status’ – Status message of the alarm station.
OFFLINE = Not communicating. DC POWER = Communicating; line powered. BATT ERR = Communicating; cannot read smart battery pack. LOW BATT = Communicating; battery life is below the set threshold. 45+ DAYS = Communicating; smart battery pack has more than 45 days before empty. 0-45 DAYS = Communicating; the number of days until smart battery pack is empty. x.xxV = Communicating; the voltage of the installed non-rechargeable battery
YYY% - represents the link quality of the transceiver.
Model X40 Instruction Manual Rev. 3.4 Page 9 of 65
1.10.3 RL4/Alarm Stations Group
Hardwired RL4 Module
RMXX> ‘Status’ XX – represents the RL4 Modbus slave address. ‘Status’ – Status message of the RL4 module.
COMM ERR = Not communicating with module. RL4 MODULE = Communicating with module.
Wireless Alarm Stations
ASXX ‘Status’ YYY% XX – represents the alarm station Modbus slave address. ‘Status’ – Status message of the alarm station.
OFFLINE = Not communicating. DC POWER = Communicating; line powered. BATT ERR = Communicating; cannot read smart battery pack. LOW BATT = Communicating; smart battery state of charge below the set threshold. 0 – 100% = Communicating; current state of charge of the smart battery pack.
YYY% - represents the link quality of the alarm station.
Model X40
1.10.4 AO-4 Group
AMXX> ‘Status’ XX – represents the AO-4 module Modbus slave address ‘Status’ – Status message of the AO - 4 module
COMM ERR = Not communicating with module AO-4 MODULE = Communicating with module
1.11 Menu Function
The X40 controller setup is accomplished through the Main Menu and consists of seven menu items:
1. Auto Configure System
2. Setup Channel Data
3. Set Channel Alarms
4. Set Relay Function
5. Inhibit & Alarm Test Mode
6. System Diagnostics
7. Time and Date
8. View TWA & Peak
Auto Configure System
The Auto Configure System automatically configures the X40 controller when other Detcon devices are installed as part of the control system. When activated, the controller searches for Detcon serial sensors, RL-4 modules/alarm stations, AO-4 modules and wireless radio modules.
Setup Channel Data
Setup Channel Data displays the Modbus ID, device type, range, and gas type for each channel. The assigned RL4 bank and number of analog inputs (for channels using an RXT-320) is also displayed. Only the gas type can be changed by the user. No other values on this screen can be changed.
Model X40 Instruction Manual Rev. 3.4 Page 10 of 65
Model X40
Set Channel Alarms
All sensors have three alarm settings ALM1 (Alarm 1), ALM2 (Alarm 2) and ALM3 (Alarm 3). The user establishes the alarm levels for each sensor depending on the range. The values represent the alarm level set points and entered in 5% increments of the full-scale range selected for that channel. In ascending mode the relay is activated when the concentration is above the alarm threshold. In descending mode, the alarm relay is activated when the concentration is below the alarm threshold. Alarms are usually ascending, with the exception of oxygen sensors. The alarm ascending level can be either Y (Yes) or N (No).
Set Relay (Alarm) Functions
The Set Relay Functions menu enables configuration (Latching, Energized and Silenceable) of the relays in Bank1-8. Each relay bank has three relay outputs for ALM1, ALM2 and ALM3 and a fourth relay output for the Fault condition. All relays in the bank must be configured for the following three settings:
Latching or Non-Latching Energized or De-Energized, Silenceable or Non-Silenceable
Inhibit and Alarm Test Mode
The Inhibit and Alarm Test Mode permits the user to inhibit functionality of alarms in the network, simulate alarm conditions and verify relay contacts. The Inhibit mode disables alarm outputs while sensor are being calibrated or tested. The Alarm Test Mode simulates alarm conditions by increasing the gas readings from zero for all active gas channels at increments of 5% full scale then decrease back to zero and exit the test mode.
System Diagnostics
The System Diagnostics menu performs complete functionality tests for:
LCD display Panel LEDs External reset switch Relays Modbusinterface
Time and Date
The Time and Date menu enables the user to effortlessly establish the time and date. The time will be displayed as military time (24hrs) in hours, minutes and seconds. The date will be displayed as the month, day and two digit year. If the time and/or date are not correct, they can be updated.
View TWA and Peak
The View TWA and Peak menu permits viewing the recorded time weighted average (TWA) and peak readings for each channel represented by its assigned gas sensor. The data is recorded on the SD card with the date, time, channel number, TWA and peak readings each time the controller polls a sensor. Data on the SD card is viewed by using the Detcon Log File Viewer application on a computer.
1.12 Optional Remote Alarm Reset/Acknowledge Switch
An optional remote Alarm Reset/Acknowledge switch enables the user to reset or acknowledge alarms without having to open the X40 enclosure. The switch is a normally open push button mounted on the bottom or side of the NEMA 4X enclosure. For the N1P and N7 enclosures, the switch must be mounted externally (e.g. bottom of the J-Box).
Model X40 Instruction Manual Rev. 3.4 Page 11 of 65
Model X40
1.13 Wireless Option
The Model X40 controller offers a wireless option that uses Modbustechnology to connect the controller and other devices to a wireless platform. The local Modbuscommunication uses a wireless grid of transceivers to broadcast information throughout the wireless network, creating a seamless network of Modbusdevices that are not physically connected. The transceiver operates at 2.4GHz and conforms to non-licensed radio frequency usage worldwide. Spread spectrum technology supports integrity and security for the wireless network.
Wireless applications can be a single field device communicating with a host controller or multiple field devices forming a network of subscribers. Each device in the network is assigned a Network ID and a Modbusaddress. If radio communication is impossible due to distance or obstruction, each slave device is capable of locating an alternate route using an additional radio to communicate with the designated device. This innovative technology is designed to create a robust network that automatically routes around congestion and line-of-sight obstacles while improving throughput as subscriber device density increases. Refer to the Wireless Radio Module instruction manual for detailed information.
Wireless Radio Module Mounting
Detcon’s wireless radio modules are factory installed. The radio module has a rotary dial for setting the RF channel. The radio module, wireless sensors, and wireless alarm stations must all be set to the same RF channel to operate correctly.
NOTE
The radio module, wireless sensors, and wireless alarm stations must all be set to the same RF channel to operate correctly.
Figure 5 Radio Module
For NEMA 1 or NEMA 12 units the antenna is typically mounted separately, using Detcon’s remote antenna mounting kit. On NEMA 4 units the antenna can be installed on the top of the enclosure or separated up to 50m using Detcon’s remote antenna mounting kit (Section 2.3). On N7 units the antenna is mounted on the Transceiver, and is part of the unit (Section 2.4). Detcon’s antennas are vertically polarized. This means that there is an RF ‘Dead-Zone’ directly above and below any transmitting antenna. Because of this, any device with an antenna that is located near an elevated antenna should be placed at least as far from the elevated antenna as the antenna is high. For example, if an antenna is 20ft. off the ground, the nearest antenna should be at least 20 ft. away.
Model X40 Instruction Manual Rev. 3.4 Page 12 of 65
Model X40
2.0 Installation
2.1 Safety Guidelines
If equipment is used in a manner not specified by Detcon, the protection provided by the equipment may be impaired.
CAUTION
DANGER
PROTECTIVE EARTH TERMINAL
FUNCTIONAL EARTH TERMINAL
The user must consult this manual for more information about any location marked with this symbol.
Danger of electrical shock. User must ensure that power has been disconnected prior to installation or servicing of the equipment.
This symbol identifies a terminal that is the connection point for a protective earth conductor. Only the protective earth conductor should be connected here.
This symbol identifies a terminal that provides an earth ground reference point. These terminals are not for safety earthing purposes.
2.2 N1P and N1R Enclosure Installation
The X40-32-N1P and X40-32-N1R units can power a maximum of 32 sensors. Damage to the power supply may result if the maximum number of sensors is
CAUTION
exceeded.
1. Provide a panel opening that is 9.25" wide by 7.5" high for the N1P controller. The N1R controller is meant to be mounted in a 19” Rack.
2. Securely mount the X40-32-N1P or X40-32-N1R controller at an indoor location using the mounting dimensions provided in Figure 6 and Figure 7. The N1R is made to fit a 19” Rack.
10.5"
9.75"
0.375" R0.109"
Slot Detail
0.218"
Model X40 Instruction Manual Rev. 3.4 Page 13 of 65
1.687" 11.825"
3.5" 8"
6.94"
7"
I/O Modules
(Qty. of 2 Max)
Figure 6 N1P Controller Mounting and Dimensional View
Model X40
NOTE
1.7" 12"
5.75" 8.7"
6.94"
7.5"
0.375"
0.218"
19"
18.25"
R0.109"
Slot Detail
Figure 7 N1R Controller Mounting and Dimensional View
If the AC and DC wiring are run in conduit, ensure that the AC wiring is not housed in the same conduit as the DC signal/wiring
NOTE
The power supply for the X40-32-N1P and X40-32-N1R is capable of handling AC inputs between 100-120/220-240VAC, 50-60Hz without degradation.
3. Install AC or DC power as follows: (Refer to Figure 8.) a. Install AC power by connecting the 100-120/220-240VAC input wiring to the terminals
labeled VAC (L1), NEU (L2), and GROUND.
b. Install DC power by connecting the 11.5-30VDC to the terminals of the DIN rail mounted
terminal block labeled 24VDC and DC Comm.
Equipment and equipment to be electrically connected shall use safety approved
CAUTION
wire/cable in conjunction with appropriate and compatible protective cable gland, all of which meet the requirements of the max equipment rating (250VAC, 5A) and any local electrical codes, regulations and standards. The cable used to connect to the terminals of the X40-32-N1P and X40-32-N1R must be rated for a minimum of 105ºC.
NOTE
NOTE
The DC input voltage should be capable of delivering at least 4.2 Amps of current to the load (100 Watts @ 24VDC).
The supply of power should be from an isolated source with over-current protection and an input voltage range between 11.5-30VDC.
4. Connect the external Modbussensors at the RS-485 connections labeled RS-485 Master: A’,
B’, and ‘Shld’ (Figure 8).
Model X40 Instruction Manual Rev. 3.4 Page 14 of 65
Model X40
Disconnect
Terminal Blocks
B
DC Comm
24VDC
A
RS-485 VDC
Out
+
A B
RS-485 SLAVE
RESET
Figure 8 N1P and N1R Connections
5. If 24VDC is required to power external sensors, connect the sensors to the power terminals labeled
VDC Out, ‘+’ and ‘–‘.
6. If linking the X40 enclosure to an RD-64X remote display unit, connect the unit to the terminals
labeled RS-485 Slave: A’, B’, and ‘Shld’.
Model X40 Instruction Manual Rev. 3.4 Page 15 of 65
2.3 N4X Enclosure Installation
The power supply for the X40-08-N4X controller can power a maximum of eight sensors even though the controller is capable of communicating with 32 devices. An additional power supply will be required if powering more than
CAUTION
CAUTION
CAUTION
1. Securely mount the enclosure in accordance with the dimensions provided in Figure 9 (X40-08-
N4X) or Figure 10 (X40-32-N4X).
eight sensors or an upgrade to Model X40-32-N4X is needed which can power a maximum of 32 sensors. Damage to the power supply may result if the maximum number of sensors is exceeded.
The wall attachments must be able to withstand a force four times the weight of the equipment.
The X40 must be mounted in a location that does not impair the operation of the external disconnection device. Internal Disconnect Terminal Blocks are provided for the removal of power at the unit when needed.
Model X40
11.85" 8"
12.75"
Ø0.31"
Mounting
Bracket
13.75"
6.79"
6.5"
Figure 9 X40-08-N4X Controller Mounting and Dimensional View
Model X40 Instruction Manual Rev. 3.4 Page 16 of 65
Loading...
+ 49 hidden pages