Detcon SW-AV2-DV2 User Manual

Page 1
DETCON MODEL SW-AV2-DV2
Hazardous Duty Class I. Div 2, Multi-tone Alarm Station
Operator’s Installation and Instruction Manual
DETCON, Inc.
4055 Technology Forest Dr. Suite 100
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
www.detcon.com
Page 2
SW-AV2-DV2
This page left intentionally blank
SW-AV2-DV2 Instruction Manual ii
Page 3
SW-AV2-DV2
Table of Contents
1.0 Description................................................................................................................................................ 1
1.1 Strobe ................................................................................................................................................... 2
1.2 Horn...................................................................................................................................................... 2
1.3 Smart Battery Pack...............................................................................................................................3
1.4 Quad Battery Charger (Optional)......................................................................................................... 3
1.5 RXT Series Wireless Transceivers....................................................................................................... 4
2.0 Installation................................................................................................................................................ 5
3.0 Operation.................................................................................................................................................. 7
4.0 Parts List................................................................................................................................................... 8
5.0 Specifications............................................................................................................................................ 8
6.0 Warranty.................................................................................................................................................. 8
7.0 Revision Log............................................................................................................................................. 8
Table of Figures
Figure 1 Basic C1D2 Wireless Alarm Stations.................................................................................................... 1
Figure 2 Wireless Interconnect PCA.................................................................................................................... 1
Figure 3 Strobe.....................................................................................................................................................2
Figure 4 Horn ....................................................................................................................................................... 2
Figure 5 Smart Battery Pack ............................................................................................................................... 3
Figure 6 Quad Battery Charger ............................................................................................................................ 4
Figure 7 Dimensional...........................................................................................................................................5
Figure 8 Unit Wiring........................................................................................................................................... 6
SW-AV2-DV2 Instruction Manual iii
Page 4
SW-AV2-DV2
This page left intentionally blank
Shipping Address: 4055 TechnologyForest Dr. Suite 100, The Woodlands Texas 77381
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
SW-AV2-DV2 Instruction Manual iv
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Page 5
SW-AV2-DV2
1.0 Description
The Detcon AV2-DV2 Alarm Stations are wireless, battery powered alarm stations with a two 5 Joule Strobes and an 110Db @ 1mtr Horn that can provide one of 16 possible alarm tones. The unit is designed for installation and use in Hazardous duty, corrosive work environments rated at Class 1, Division 2, Groups E, F, and G.
Figure 1 Basic C1D2 Wireless Alarm Stations
The alarm station can be positioned almost anywhere, since the wireless ability of the unit means that there is no need for running conduit or outside connections. The alarm station is powered by two internal 12V battery packs. Communication is performed via the Detcon RXT-300 or RXT-320 series of transceivers. Access to the unit is only necessary for battery maintenance or exchange. With the addition of a solar panel, access can be kept to periodic functional tests and checks.
Internal wiring between components runs through the Wireless Alarm Interconnect PCA(s). This PCA controls the state of the alarms via communication with the Wireless Transceiver. When an alarm is triggered, the wireless transceiver will provide the interconnect PCA with the signal(s) necessary to activate the proper alarm(s).
wiring to/from
Transciever
wiring to/from Transciever
External
24VDC
connections
0
1
2
F
3
E
4
D
5
C
6
B
7
A
9
Rotary Switch
for Modbus
Address
8
Alarm 2
wiring
Alarm 1 wiring
Figure 2 Wireless Interconnect PCA
SW-AV2-DV2 Instruction Manual Rev. 0.3 Page 1 of 8
Page 6
SW-AV2-DV2
If the unit utilizes the RXT-320 Transceiver, the rotary switch on each of the Wireless Alarm Interconnect PCA’s is used to set the Modbus Address of the alarm unit. Each Wireless Alarm Interconnect PCA must have a unique Modbusaddress to be recognized on the network. This switch is not used with the RXT-300 Transceivers.
1.1 Strobe
The alarm station warning light is configured with choice of dome colors such as amber, blue, clear, green, magenta, or red. Dome guard is included. The rugged warning light is specifically designed for hazardous locations or corrosive environments where a very bright visual signal is required.
Figure 3 Strobe
1.2 Horn
The alarm station vibrating horn produces a noise level of a 100dB of sound by the electromechanical vibration of a stainless steel diaphragm. The horn mechanism has an effective broadcast range of 200 feet. The horn is enclosed in heavy-duty copper-free cast aluminum housing tapped for 3/4 - inch conduit.
The horn is capable of producing coded blasts or sustained tones, and is excellent for general alarm, start/dismissal, coded paging, and process control signaling in areas where their sound output exceeds ambient noise levels. The horn in the Strobe/Horn alarm stations has 32 possible combinations of sounds that are selectable by switch settings inside the alarm.
Figure 4 Horn
SW-AV2-DV2 Instruction Manual Rev.0.3 Page 2 of 8
Page 7
1.3 Smart Battery Pack
NOTE:
SW-AV2-DV2
Figure 5 Smart Battery Pack
The Wireless Alarm Station assembly also comes with a battery pack that allows the assembly to be remotely mounted without the need for any cables because of its wireless operation. Detcon has several options for battery packs. The battery packs provided are Detcon’s plug-in Smart Battery Packs which provides an output of 12VDC (See Figure 5). The battery packs consist of rechargeable Lithium-Ion batteries and are equipped with integrated safety electronics that include fuel gauge, voltage, current and temperature monitoring circuits. This “smart” circuitry continuously monitors the battery’s condition and reports critical status information to the wireless transceiver. The battery packs are designed to plug onto an 8-pin Beau connector on the terminal board and should not be exposed to outside elements without being housed and protected.
Only Detcon products specifically designed to utilize these battery packs should be used. Operating periods before recharge for the Wireless DM-100 assembly can be as long as 2-3 months and battery life can be up to 5 years before battery pack replacement is required. Improper use of the battery pack may be hazardous to personnel or the environment and will void the warranty.
The Wireless Alarm Station can also be powered by a customer provided external DC
power source. Refer to Section 2 for more details.
1.4 Quad Battery Charger (Optional)
Detcon’s Smart Battery Pack can be charged as needed using Detcon’s optional Quad Battery Charger which can charge up to four battery packs at one time. The Quad Battery Charger comes with a plug-in AC/DC adapter that plugs into a standard 120VAC outlet for power. The DC end of the adapter plugs into the DC power jack of the charger providing 24VDC. The Quad Battery Charger has four charging ports, each with 8­pin Beau connectors for battery pack connection. The ports and connectors are keyed to prevent incorrect positioning and connection. Each port has its own “FAULT” LED indicator and “CHARGE” LED indicator and will display either a red light or green light depending on the status of each battery being charged. Charging times will vary depending on the charge state of each battery pack, but a full charge of a depleted battery pack can take up to 24 hours.
SW-AV2-DV2 Instruction Manual Rev. 0.3 Page 3 of 8
Page 8
SW-AV2-DV2
Figure 6 Quad Battery Charger
When first powered on and with no battery packs connected to the charger, all the LED indicators on the Quad Charger should be green. When a battery pack is seated into a charging port, the “CHARGE” LED will go from green to red indicating the battery pack is not sufficiently charged. Once fully charged, the LED will go from red to green and the battery pack is ready to be used.
The “Fault” LED should remain green indicating that there are no problems with the battery pack or charging port. If the “Fault” LED turns red with the battery pack connected, then there is a problem or issue with the battery pack and it should not be used and be removed immediately. If the “Fault” LED turns red without a battery pack connected to the charge port, then there is a problem or issue with the port and that port should no longer be used.
Battery packs can remain connected to the charger even after a full charge indication (Green “Charge” LED) is shown due to the protection circuitry of the batter pack which prevents any overcharging issues.
1.5 RXT Series Wireless Transceivers
The wireless function of the alarm station is made possible by Detcon’s RXT series wireless transceivers. These transceivers transmit signal data such as analog 4-20mA DC or serial Modbusand can support up to 32 devices. They operate at 2.4GHz and conform to non-licensed radio frequency appliance usage around the world. Wireless network integrity and security is accomplished using direct sequence spread spectrum wireless mesh technology. Wireless applications can be as simple as a single field device communicating with a host controller or any number of field devices forming a network of subscribers. Every device in the network is capable of functioning as a router and repeater for all other devices in the network. This means that subscribers can “hop” through neighboring devices to communicate with each other thereby widening network access points. This unique and innovative technology is designed to create a robust network that automatically routes around congestion and line-of-sight obstacles while improving throughput as subscriber device density increases.
Detcon offers two models of the wireless transceiver, Model RXT-300 and Model RXT-320. Both models are functionally similar with one major difference: the RXT-300 provides a network wide control processing capability, whereas the RXT-320 does not. Refer to each models instruction manual for more detailed information.
SW-AV2-DV2 Instruction Manual Rev.0.3 Page 4 of 8
Page 9
SW-AV2-DV2
2.0 Installation
NOTE: The wireless alarm station is a precision instrument and care should be taken when handling it.
The Wireless AV2-DV2 Alarm Station is made to be mounted on a 2” or 3” diameter pipe. Two 3” U-bolts with hardware are provided for mounting. The location for mounting the wireless alarm station should be carefully selected. Occasional access to the unit will be necessary for battery replacement and maintenance.
No wiring is necessary for these units, once the unit has been mounted, install the battery pack and the unit will begin normal operation.
3.5
18.35 Typ
2each U-Bolts and
hardware for
mounting
0n 2"~3" Pole.
8
33
Typ.
12.25 Typ
Figure 7 Dimensional
If the unit is equipped with the RXT-320 Transceiver, the Address Switch on the Wireless Interconnect PCA should be set to the correct address for the alarm station. This switch is normally set at the factory. If there is more than one alarm station, each station should have a unique address for proper operation. For more information refer to the RXT-320 manual. Units equipped with RXT-300 Transceiver do not use this switch
The AV2 utilizes two batteries. Both batteries must be the same type. To install the battery packs, insure that the area is de-classified. Remove the cover from the junction boxes. Remove the Battery Cap, and install a battery in each junction box. The batteries can only be installed one way, and orientation is mandated by the battery supports and the connector. Insure that the batteries are completely seated, and close the retaining lever over the battery until it latches. The unit will power up, and begin normal operation. Replace the cover on the junction Boxes, and insure that the covers are completely screwed down and secured by the cap-head screw.
Battery operation can be supplemented by the addition of an external 24VDC power source. The unit should not need the addition of an external 24VDC power source, but if an external 24VDC is to be added, J6 is
SW-AV2-DV2 Instruction Manual Rev. 0.3 Page 5 of 8
Page 10
SW-AV2-DV2
provided for connection to the 24Volt input (refer to Figure 8 Unit Wiring). This voltage will be used to charge the battery pack as well as aid in operation of the alarm station.
Brown
Orange White/Violet White/Green
Wireless
Transceiver
Turck Power
receptical
White/Blue Red Black Purple
White/Brown
White/Black
3 - White
2 - Brown
1 - Blue
Gnd
DB3 PCA
Red
Green/Yellow
Black
Green/Yellow
Green/Yellow
Green/Yellow
Gnd
Green/Yellow
Green/Yellow
Alarm Term Bd.
Red
Black
Alarm Term Bd.
Red
Black
Red
Black
Black
Green/Yellow
Red
Green/Yellow
Black
Gnd
Strobe Enclosure
Red
Gnd
Strobe Enclosure
Figure 8 Unit Wiring
SW-AV2-DV2 Instruction Manual Rev.0.3 Page 6 of 8
Page 11
SW-AV2-DV2
3.0 Operation
The AV2-DV2 Wireless Alarm Stations provide two strobes and a dual alarm horn. The wireless alarm station is set to respond to alarms from the controlling unit. The controller/wireless network has independent control over the strobes and the Horns, and they will be activated when the appropriate alarm is activated.
All strobes have a flash rate of 1 Hz (one flash per second). This is preset by the manufacture and cannot be modified.
The horn has up to 32 possible settings, for use in different configurations. The default settings of the horn are factory set. To change the setting of the horn, remove the rear end of the horn, and set dip switches according to the Sound Signals Table.
Table 1 Sound Signals
TONE FREQ/DESCRIPTION
1 Alt Tones 800/970 Hz at 1/4 sec 11111 2 Sweeping 800/970 Hz at 7Hz 11110 Fast Sweep(LF)
3
Sweeping 800/1000 Hz at 1 Hz 4 Continuous at 2850 Hz 11100 5
Sweeping 2400-2850 Hz at 7 Hz
6
Sweeping 2400-2850 Hz at 1 Hz
7 8 9 Alt. Tones 2400/2850 Hz at 2 Hz 10111
10 Int. Tone of 970 Hz at 1 Hz 10110 11 Alt. Tones 800/970 Hz at 7/8 Hz 10101 12 Int. Tone at 2850 Hz at 1Hz 10100 13 970Hz at 1/4 sec on 1 sec off 10011 14 Continuous at 970 Hz 10010 15 554Hz for 100ms / 440 Hz for 400ms 10001 French Fire Sound 16 Int. 660 Hz 150 ms on 150 ms off 10000 Swedish Fire Alarm 17 Int. 660 Hz 1.8 sec on 1.8 sec off 01111 Swedish Fire Alarm 18 Int. 660 Hz 6.5 sec on 13 sec off 01110 Swedish Fire Alarm 19 Continuous 660 Hz 01101 Swedish Fire Alarm 20 Alt 554/440 Hz at 1 Hz 01100 Swedish Fire Alarm 21 Int. 660 Hz at 7/8 Hz 01011 Swedish Fire Alarm 22 Int. 2850 Hz 150 ms on 100 ms off 01010 23 24 25 26 27 Int. 3100 Hz 0.32s on / 0.68s off 00101 28 29 30 31 32
Sweep 1200-500 Hz at 1 Hz
Sweep 800-970 Hz at 50 Hz
Sweep 2400-2850 Hz at 50 Hz
3 970Hz pulses 0.5on/0.5off, 1.5 off
3 2850Hz pulses 0.5on/0.5off, 1.5 off
Slow Whoop
Spare/Customer Tone Spare/Customer Tone Spare/Customer Tone Spare/Customer Tone Spare/Customer Tone
SWITCH TONE
11101
11011 11010 11001 11000 Din Tone
01001 01000 00111 00110
00100 00011 00010 00001 00000
Med Sweep(LF)
Fast Sweep
Slow Whoop
Back-Up Alarm(LF)
Back Up Alarm(HF)
Pelican Crossing
Low Freq. Buzz
High Freq. Buzz
SW-AV2-DV2 Instruction Manual Rev. 0.3 Page 7 of 8
Page 12
4.0 Parts List
Detcon Part # Description
354-1916x6-024 24VDC Strobe, Ext Ground (x represents color of lamp)
Strobe colors: Red (2), Amber (4), Green (5), Blue (6), Magenta (7), and Clear (9) 356-DB3007-024 Model DB3 Horn 500-005146-000 24V Wireless Alarm Interconnect PCA 976-000300-316 Smart Wireless Transceiver 976-000320-316 Transparent wireless Transceiver 976-000303-012 12VDC. 2200mAh Battery Pack 976-0BP303-290 12VDC, 2900mAh Battery Pack
5.0 Specifications
Strobe
Dome Colors Amber / Blue / Clear / Green / Magenta / Red Flash Rate/Minute 60 Lamp Source LED
Horn
Db Output 115db @ 1meter (tone dependent) Duty Cycle Not rated for continuous duty (5 minute duty cycle)
Alarm Unit
Operating Current 2.8A Max (both Horn and Strobe operational) Operating Temperature -20ºC to 60ºC Voltage 12VDC Dimensions 31.25”H X 17”W X 11.75”D
SW-AV2-DV2
6.0 Warranty
Detcon Inc., as manufacturer, warrants under intended normal use each new SW-AV1-DV2, SW-A1-DV2, and SW-V1-DV2 Alarm station to be free from defects in material and workmanship for a period of one year. The warranty period begins from the date of shipment to the original purchaser and ends one year thereafter. All warranties and service policies are FOB the Detcon Inc. facility located in The Woodlands, Texas.
7.0 Revision Log
Revision Date Changes made Approval
0.0 04/25/11 Initial Release LU
0.1 11/30/11 Updated Mounting Plate LU
0.2 08/08/13 Update for new battery pack, new unit build, new PCA LU
0.3 12/30/13 Corrections to Horn and other information LU
Shipping Address: 4055 TechnologyForest Dr. Suite 100, The Woodlands Texas 77381
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
SW-AV2-DV2 Instruction Manual Rev.0.3 Page 8 of 8