Detcon Four Channel Relay Card User Manual

Page 1
Four Channel Relay Card
Operator’s Instruction Manual
DETCON, Inc.
4055 Technology Forest Blvd. Suite 100,
The Woodlands, Texas 77381
Ph.281.367.4100 / Fax 281.298.2868
www.detcon.com
March 19, 2014 • Document #5155 • Revision 1.2
Page 2
This page left intentionally blank
Four Channel Relay Card Instruction Manual ii
Page 3
Table ofC ontents
1.0 Introduction.............................................................................................................................................. 1
1.1 Description........................................................................................................................................... 1
1.2 I/O Connections.................................................................................................................................... 1
1.2.1 Power Input.................................................................................................................................. 1
1.2.2 Sensor Inputs................................................................................................................................ 1
1.2.3 Relay Outputs............................................................................................................................... 1
1.2.4 Reset Switch Input........................................................................................................................ 2
2.0 Installation................................................................................................................................................ 2
3.0 Relay Card Configuration....................................................................................................................... 3
3.1 Sensor/Channel Configuration ............................................................................................................. 3
3.2 Alarm Configurations........................................................................................................................... 4
3.2.1 Silencable or Non Silenceable...................................................................................................... 5
3.2.2 Latching or non-Latching Relays................................................................................................. 5
3.2.3 Energized or Non-Energized........................................................................................................ 5
3.2.4 Fault............................................................................................................................................. 5
3.3 Reset..................................................................................................................................................... 5
4.0 Troubleshooting Guide............................................................................................................................ 6
5.0 Specifications............................................................................................................................................ 6
5.1 Parts List............................................................................................................................................... 6
6.0 Warranty.................................................................................................................................................. 7
7.0 Revision Log............................................................................................................................................. 8
Table ofFigu res
Figure 1 Relay Card Layout..............................................................................................................................2
Figure 2 Sensor/Channel configuration DIP Switches...................................................................................... 3
Figure 3 Alarm Configuration DIP Switches....................................................................................................4
Four Channel Relay Card Instruction Manual iii
Page 4
This page left intentionally blank
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas77381
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
Four Channel Relay Card Instruction Manual iv
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Page 5
1.0 Introduction
1.1 Description
The Detcon Four Channel Relay Card provides a low cost means of adding gas detection alarms to a fire alarm panel. The Relay Card is designed to interface up to four analog 4-20mA gas detection sensors and supports three programmable alarm levels for each channel. Any 4-20mA gas sensor can be used with this card.
The sensor inputs are continuously monitored by an A/D converter and microcontroller. Whenever one or more of the sensor inputs exceeds a preset configurable alarm level, the appropriate alarm relay is activated. The relays and alarm levels are configured using DIP switches mounted on the Relay Card. The Relay Card provides three configurable alarms (Alarm 1, Alarm 2, and Alarm 3) and a Fault alarm.
Each alarm provides a set of dry relay contacts. These relay contacts consist of “Normally Open” (NO), ‘Normally Closed’ (NC), and ‘Common’ (C).
The four relay outputs are associated with:
Three alarm levels
o Alarm Level 1 o Alarm Level 2 o Alarm Level 3
Sensor fault
An enclosure is not included with The Four Channel Relay Card. The Relay Card must be
NOTE
mounted in a user-supplied enclosure appropriate for the environment in which it will be used. Typically, the card is mounted inside a fire alarm controller enclosure.
1.2 I/O Connections
1.2.1 Power Input
The Relay Card operates using a supply voltage from 12 to 28VDC. Power connections are made via a 2 pin connector in the lower left corner of the Relay Card (Figure 1). This is a 2 pin connector (Detcon p/n 306­175701-900).
1.2.2 Sensor Inputs
The Relay Card uses 3-pin connectors (Detcon p/n 306-177984-800) for the sensor connections. The pin out for these connectors is: GND, sensor power (12-28VDC) and 4-20mA input (Figure 1). The sensor power pin is connected directly to the supply power connector. The sensor power pin is intended to power a single sensor (up to 100mA). Any voltage applied to the supply power pin will be present at the sensor power pin on the sensor connector. If 3-wire sensors are being used, all three pins in the sensor connector are used; if a two­wire sensor is being used, only power and mA connections are used.
1.2.3 Relay Outputs
Each relay also uses a 3-pin connector (Detcon p/n 306-175701-900) to provide dry relay contacts. The pin out is for the relay connectors are: Normally Open (NO), Common (C), and Normally Closed (NC) (Figure 1). The relays are rated at 5A 30VDC or 250VAC.
Four Channel Relay Card Instruction Manual Rev. 1.2 Page 1 of 8
Page 6
1.2.4 Reset Switch Input
The reset/silence switch uses a 2-pin connector (Detcon p/n 306-175701-900). The reset connector allows for the use of an external, normally-open, momentary push-button switch to reset and/or silence alarms (Figure 1). When the switch is closed, it will reset any latched alarms or silence any Silenceable alarms.
NO C NC
Alarm x
Alarm Relay
Dry Contacts
ON OFF
Silencable
Latching
Energized
ALARM 1
Latching
Not Used
FAULT
+ -
Power IN
12-28VDC
ON OFF
ALARM 2
ON OFF
ALARM 3
External
Reset
Silencable Latching Energized
Silencable Latching Energized
Power Input and Reset
Alarm Relay Settings
GND
PWR
mA
ON OFF
60% 55% 50% 45% 40% 35% 30% 25% 20% 15% 10%
CHx
Enable
CHx
Channel Input
and Alarm Levels
Figure 1 Relay Card Layout
2.0 Installation
1. Mount the Relay Card on standoffs so that there is no probability of shorting out any components on the back side of the Relay Card. The standoffs should be at least 3/8” tall. The screw size is set for 6-
32.
An enclosure is not included with The Four Channel Relay Card. The Relay Card must be
NOTE:
mounted in a user-supplied enclosure appropriate for the environment in which it will be used. Typically, the card is mounted inside a fire alarm controller enclosure.
Four Channel Relay Card Instruction Manual Rev.1.2 Page 2 of 8
Page 7
2. Connect the sensors to the Relay Card via the three pin connectors labeled CH1, CH2, CH3, and CH4. The connectors provide Power, Power Return, and mA connections for the sensors and are labeled as ‘GND’, ‘PWR’, and ‘mA’. Refer to Figure 1.
3. Connect incoming power to the two pin power connector. (located on the lower left corner of the RELAY CARD.) The input voltage has to be 12 to 28VDC for the Relay Card and the sensors to operate correctly. Refer to Figure 1 for proper connections.
4. Each alarm relay is provided with a 3-pin connector for connection to an exterior controller, or alarm. These connectors are labeled ‘Alarm 1’, ‘Alarm 2’, ‘Alarm 3’, and ‘Fault’. The contacts are Common, Normally Open, and Normally Closed, labeled ‘C’, ‘NO’, and ‘NC’ respectively (Figure 1).
5. If an external ‘Reset Switch’ is to be wired to the control Relay Card, the switch is to be a normally open momentary closed switch wired to the External Reset Connector (Figure 1).
3.0 Relay Card Configuration
3.1 Sensor/Channel Configuration
Each Sensor/channel has a DIP switch bank with 12 switches. Switch 1 is used to enable or disable the channel. Switches 2-12 are used to set the alarm levels for the channel. These eleven switches represent levels from 10% - 60% of full range in 5% increments. A maximum of three switches per channel can be activated (excluding the enable/disable switch) to configure the three alarm levels for a specific channel. Refer to the Table 1 for examples of alarm configurations.
ON OFF
60% 55% 50% 45% 40% 35%
GND PWR mA
CHx
Sensor
Connections
30% 25% 20% 15% 10% Enable
CHx
Alarm
Level Switch
Figure 2 Sensor/Channel configuration DIP Switches
If the mA input from the sensor rises above the configured level of the switch setting for that particular sensor the corresponding alarm relay is activated. I.E.: If the sensor connected to ‘CH1’ has the DIP switches set for 20%, 40% and 60%, and the sensor mA rises above 20% full scale, alarm 1 will be activated. If the mA input rises above 40% full scale, alarm 2 will activate, and if the mA rises above 60% full scale, alarm 3 will activate.
When an alarm level switch is set to “ON”, the alarm level corresponding to that switch is active for that particular channel. When only one level is active the switch is associated
NOTE:
with Alarm 1 (A1). If two switches are active, the lowest is A1 and the highest is A2. When three switches are active, the lowest level is Alarm 1, the middle level is Alarm 2 and the highest level is Alarm 3 (A1, A2, A3).
Four Channel Relay Card Instruction Manual Rev. 1.2 Page 3 of 8
Page 8
Table 1 Examples of Alarm Configuration
S W 12
S W 11
S W 10
S W 9
S W 8
S W 7
S W 6
S W 5
S W 4
S W 3
S W 2
S W 1
60% 55%
50% 45%
40% 35%
30% 25%
20% 15%
10% EN
M eaning
OFF OFF X OFF OFF OFF OFF OFF OFF X OFF OFF OFF OFF
ON
OFF OFF X OFF OFF OFF OFF OFF OFF X OFF OFF OFF OFF OFF OFF OFF X OFF OFF OFF OFF OFF OFF OFF X
ON ON ON
ON ON
Enabled, ALM1=10%, ALM2=15%,
ALM3=50%
OFF X
ON
ON
OFF X OFF OFF OFF
Enabled, ALM1=15%, ALM2=25%,
ALM3=35%
X OFF
X OFF OFF OFF
X OFF OFF OFF
OFF
Disabled,
input
ignored
ON
ON
ON ON O N ON
Enabled, ALM1=20%, ALM2=50%,
ALM3 not used
OFF OFF OFF
ON
OFF OFF OFF
Enabled,
ALM1=35%, ALM2 not used ALM3 not used
OFF
Enabled,
no alarms
enabled,
fault relay is
activated
ON
ON
ON ON
Enabled, too many
levels
enabled,
fault relay is
activated
The 4-20mA input from ‘Enabled’ channels is monitored by the controller. If the input on a channel is less than 2.2mA, the fault relay is activated. The fault relay is also activated if a channel is enabled, but no alarm levels or too many alarm levels have been enabled. If a channel is disabled, its 4-20mA input is not monitored.
3.2 Alarm Configurations
The alarm relays for alarms 1, 2, and 3 each have a DIP switch bank with three switches that are used to configure the relays. The Fault relay has a DIP switch with one active switch that controls the fault configuration. Alarms 1, 2, and 3 can be configured as Silencable, Non-Silencable, Latching, Non-Latching, Energized, or Non-Energized. The Fault relay can only be configured as Latching or Non-Latching. Each relay provides the customer with a set of dry contacts. The contacts are Common, Normally Open, and Normally Closed, labeled ‘C’, ‘NO’, and ‘NC’ respectively.
Silencable
ON OFF
Latching
Energized
ALARM 1
Latching
Not Used
FAULT
Figure 3 Alarm Configuration DIP Switches
ON OFF
Silencable Latching Energized
ALARM 2
Silencable Latching Energized
ALARM 3
Four Channel Relay Card Instruction Manual Rev.1.2 Page 4 of 8
Page 9
3.2.1 Silencable or Non Silenceable
Alarms 1, 2, and 3 can be configured as Silencable or Non-Silenceable. In order for an alarm to be Silenceable, the corresponding DIP switch must be set to Silenceable, and an external ‘Normally Open, Momentary Closed Switch’ must be connected to the ‘Reset’ connector on the Relay Card. If an alarm relay is configured as Silenceable and it is in an alarm state, it can be returned to its normal state (silenced) by activating the external reset switch. If a relay is configured as Non-Silenceable and is in an alarm state, the activation of the external reset switch has no effect. The ‘Fault’ alarm cannot be silenced.
If a relay has been silenced and the sensor input drops below the alarm level the alarm will
NOTE:
reset. If the sensor input again rises above the alarm level the relay will again enter an alarm state. If another sensor (one that did not cause the original alarm) goes into alarm, then the relay will be reactivated.
3.2.2 Latching or non-Latching Relays
Alarms 1, 2, and 3 can be configured as Latching or Non-Latching. If a relay is configured as Non-Latching, the relay returns to its normal state once the alarm has cleared or passed. If the alarm is set as Latching the relay remains in the alarm state even after the alarm has cleared. An alarm that is set as ‘Latching’ can only be returned to its normal state by activation of an external reset switch.
3.2.3 Energized or Non-Energized
Alarms 1, 2, and 3 can be configured as Energized or Non-Energized. The standard is Non-Energized. However, a relay can be configured as energized to provide application specific features. A normally energized relay will de-energize when in alarm. A typical application of the energized configuration is to have the alarm relay normally energized so that in the event of a power failure to the control module card, the alarm relay will de-energize causing its relay contacts to change state, thereby creating an alarm output.
3.2.4 Fault
The only configuration option for the fault relay is latching or non-latching. If the Fault alarm is configured as ‘Latching’ the fault relay will energize whenever a fault occurs, and will remain latched (energized) until the fault has cleared, and the ‘Reset Switch’ has been pushed. The ‘Fault’ alarm cannot be silenced.
The fault circuitry monitors the sensors attached to the controller. If a sensors mA input falls below
2.2mA the fault circuitry will generate a ‘Fault’.
If a sensor is attached to the Relay Card, with no alarm levels or more than three alarm levels
configured, the card will generate a ‘Fault’
3.3 Reset
The reset connector provides connections for an external ‘Normally Open, Momentary Closed Switch’. This switch is used to reset and/or silence alarms if the alarms are set as latching, and/or Silenceable.
Four Channel Relay Card Instruction Manual Rev. 1.2 Page 5 of 8
Page 10
4.0Troubleshooting Guide
Problem Potential Cause(s)
More than 3 alarm levels are set on an active channel
Fault active
Sensors not receiving power
Alarm Relay Active when sensor(s) is not in alarm
For further troubleshooting assistance, contact Detcon Service Department at Service@detcon.com, or contact Detcon customer service.
No alarm levels are set on an active channel 4-20mA input is not connected to the Channel 4-20mA input is below 2.2mA – fix/replace sensor Sensor not connected correctly Input voltage to Relay Card is not correct level (12-28 VDC) Connector wired incorrectly Relay is set for energized Relay connector wired incorrectly
5.0Specifications
Capacity
Up to 4 4-20mA input devices
Indicators:
Power Indicator LED 3 Alarm Status LED’s 1 Fault Status LED Channel Indicator LED’s
Detection Accuracy
+/2 2% of full scale value between 10% and 60%
Input Options:
Analog 4-20 mA DC
Output Options
Programmable Relay Contacts
Relays rated 5A @ 30VDC/250VAC
Warranty
One Year
Mechanical Specifications
Dimensions 4.5” x 5”
Electrical Specifications
Power Consumption
12-28VDC @ 800 mA max (Including Sensors)
5.1 Parts List
Part Number Description
306-177984-800 3-Pin Connector 306-175701-900 2-Pin Connector 440-005155-000 Four Channel Relay Card
Four Channel Relay Card Instruction Manual Rev.1.2 Page 6 of 8
Page 11
6.0 Warranty
Detcon, Inc., as the manufacturer, warrants under intended normal use each new Four Channel Relay Card to be free from defects in material and workmanship for a period of one year from the date of shipment to the original purchaser. Should the Relay Card fail to perform in accordance with published specifications within the warranty period, return to Detcon, Inc., for necessary repairs or replacement. All warranties and service policies are FOB the Detcon facility located in The Woodlands, Texas.
Four Channel Relay Card Instruction Manual Rev. 1.2 Page 7 of 8
Page 12
7.0Revision Log
Revision Date Changes made Approval
1.1 04/18/12 Updated with corrections LU
1.2 03/19/14 Updated, & reformatted with various corrections and clarifications LU
Shipping Address 4055 Technology Forest Blvd. Suite 100,., The Woodlands Texas77381
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 • www.detcon.com sales@detcon.com
Four Channel Relay Card Instruction Manual Rev.1.2 Page 8 of 8
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Loading...