Detcon 880S-N1R User Manual

Model 880A-N1R
Model 880S-N1R
PLC Graphic Control System
FAULT
NO COMM
POWER
ON / OFF
ALARM 3
Operator’s Installation and Instruction Manual
3200 Research Forest Dr., A-1
The Woodlands, Texas 77381
Ph.281.367.4100 / Fax 281.298.2868
DETCON, Inc.
www.detcon.com
May 30, 2009 • Document # 3299 • Revision 0.0
880-N1R
Page intentionally blank
880-N1R Instruction Manual ii
880-N1R
Table of Contents
Introduction.............................................................................................................................................1
1.0
1.1 Serial Systems (RS-485) ...................................................................................................................... 1
1.2 Analog Systems (4-20mA sensors) ...................................................................................................... 2
2.0 System Configuration .............................................................................................................................3
2.1 Configuration........................................................................................................................................ 3
2.2 Touch Panel Graphic Display............................................................................................................... 3
2.3 Programmable Logic Controller........................................................................................................... 4
2.4 Isolated Network Adapter .................................................................................................................... 4
2.5 Specifications ....................................................................................................................................... 6
3.0 Installation...............................................................................................................................................7
3.1 Installing I/O Modules.......................................................................................................................... 7
3.2 Unit Connections.................................................................................................................................. 8
3.3 Battery Backup - Auxiliary 24VDC Input.......................................................................................... 11
3.4 Initial Power Checks .......................................................................................................................... 11
3.5 880 Remote Display Installation (Optional)....................................................................................... 12
4.0 Setup.......................................................................................................................................................15
4.1 User interface ..................................................................................................................................... 15
4.2 Clock and Screen Adjustments........................................................................................................... 16
4.3 880 Setup............................................................................................................................................ 18
4.4 Remote Display Set-up....................................................................................................................... 23
5.0 System Operation..................................................................................................................................25
5.1 Alarm Indicators................................................................................................................................. 25
5.2 Main Screen........................................................................................................................................ 25
5.3 Channel X Details Screen ................................................................................................................... 26
5.4 Alarm History Screen......................................................................................................................... 27
6.0 Trouble-shooting ...................................................................................................................................28
6.1 Sensor Faults ...................................................................................................................................... 28
6.2 Troubleshooting RS485 Networks ..................................................................................................... 28
7.0 Spare Parts.............................................................................................................................................30
8.0 Warranty................................................................................................................................................30
Appendix A........................................................................................................................................................31
RS-485 System Integration Wiring ................................................................................................................ 31
Appendix B ........................................................................................................................................................37
Hexadecimal Table......................................................................................................................................... 37
Appendix C........................................................................................................................................................38
Drawings and Diagrams ................................................................................................................................. 38
Table of Figures
Figure 1 RS-485 Network Configuration............................................................................................................. 1
Figure 2 DA4 4-20mA Configuration .................................................................................................................. 2
Figure 3 Back of Touch Panel Display................................................................................................................. 3
Figure 4 Basic PLC .............................................................................................................................................. 4
880-N1R Instruction Manual iii
880-N1R
Figure 5 Isolated Network Adapter ...................................................................................................................... 5
Figure 6 Unit overview......................................................................................................................................... 5
Figure 7 Dimensional Overview .......................................................................................................................... 7
Figure 8 installing Din-Rail mounted modules .................................................................................................... 8
Figure 9 Setting Device Addresses....................................................................................................................... 8
Figure 10 Typical RS-485 connections ................................................................................................................ 9
Figure 11 Typical Analog Sensor Wiring ............................................................................................................ 9
Figure 12 Typical RL4 Module.......................................................................................................................... 10
Figure 13 Main 880 terminal blocks and connections........................................................................................ 10
Figure 14 Typical Input Power connections....................................................................................................... 10
Figure 15 Typical 24VDC Input Connections.................................................................................................... 11
Figure 16 Dimensional Overview ...................................................................................................................... 12
Figure 17 Main 880 terminal blocks and connections........................................................................................ 13
Figure 18 Remote RS-422 connections.............................................................................................................. 13
Figure 19 Remote Interconnect Wiring.............................................................................................................. 13
Figure 20 Typical Input Power connections....................................................................................................... 14
Figure 21 Input Keyboard .................................................................................................................................. 15
Figure 22 Input Keypad...................................................................................................................................... 15
Figure 23 Warning Screen.................................................................................................................................. 16
Figure 24 Main Menu......................................................................................................................................... 16
Figure 25 Screen Settings................................................................................................................................... 17
Figure 26 Clock Adjust Screen........................................................................................................................... 17
Figure 27 Adjust Display Screen........................................................................................................................ 17
Figure 28 Main Screen ....................................................................................................................................... 18
Figure 29 Analog Configuration Screen............................................................................................................. 18
Figure 30 Serial Configuration Screen............................................................................................................... 19
Figure 31 Inputting the Facility Name ............................................................................................................... 19
Figure 32 Inputting numbers .............................................................................................................................. 20
Figure 33 Channel Detail Screen........................................................................................................................ 21
Figure 34 The Main Screen ................................................................................................................................26
Figure 35 Channel Details Screen ...................................................................................................................... 27
Figure 36 Alarm History Screen......................................................................................................................... 27
Figure 37 RS-485 Bus with 4 transceiver chips ................................................................................................. 31
Figure 38 Correct and incorrect wiring schemes................................................................................................ 32
Figure 39 Recommended RS-485 communications set-up ................................................................................ 33
Figure 40 Unbalanced Data Bus......................................................................................................................... 34
Figure 41 Data Bus using two repeaters............................................................................................................. 34
Figure 42 Repeater wiring diagram.................................................................................................................... 34
Figure 43 Daisy Chain wiring diagram .............................................................................................................. 35
Figure 44 Unbalanced Data Bus......................................................................................................................... 35
Figure 45 Four repeater Data Bus ...................................................................................................................... 36
Figure 46 wire length vs. data speed .................................................................................................................. 36
Shipping Address: 3200 A-1 Research Forest Dr., The Woodlands Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Phone: 888.367.4286, 281.367.4100 • Fax: 281.292.2860 •
880-N1R Instruction Manual iv
www.detcon.comsales@detcon.com
880-N1R

1.0 Introduction

The standard Detcon Model 880 is a PLC based graphic control system specifically designed to serve as a host monitoring and control system for networks of gas detection sensors as well as a wide range of other field devices. The main unit is programmed as a Modbus master and is available in two versions: Serial (Model 880S-N1R) and Analog (Model 880A-N1R). Both are fully Field configurable and are made to be mounted in a 19” indoor rack mount cabinet or enclosure.
The Serial unit (Model 880S-N1R) is designed to monitor up to 32 serial field devices, while the Analog version (880A-N1R) can monitor up to 72 analog devices via Detcon’s DA4 Modules. The unit features a color touch screen that graphically displays the status of each device, provides three fully programmable “Banks” of alarm outputs, and provides the ability to log alarm events to a USB Drive. The use of standard industrial components makes the Detcon Model 880 an easy and practical choice when configuring point-to­point monitoring and data acquisition. The system can also be used for remote monitoring simply by adding the 880 Remote Display Unit.

1.1 Serial Systems (RS-485)

Another method of integration commonly used in industrial applications is the RS-485 serial communications network, or Modbus™ (Figure 1). RS-485 serial communication is used for multipoint communications and is a popular choice due to ease of wiring installation.
Advantages of using RS-485 serial communication:
¾ Inexpensive method allowing multiple devices to communicate over a single twisted pair of wires. ¾ More data/information can be sent beyond the simple 4-20mA signal. ¾ Transceiver communication up to 4,000 feet without using repeaters. ¾ Highly resistant to induced noise when proper cable and terminations are used. ¾ Two-way (bi-directional), half-duplex, data bus communication consisting of multiple transmitter and
receiver combinations.
Most systems use the RS-485 master/slave architecture for multiple device communication. Each slave unit has a unique address and responds to data packets generated by the master. The master periodically polls all connected slave units.
1 2
ALARM 3
FAULT
NO COMM
POWER ON / OFF
ALARM 2
ALARM 1
Typical Sensors
31 32
Figure 1 RS-485 Network Configuration
The protocol used by Detcon for the RS-485 communications is the Modbus RTU, which is compatible with most PLC’s, MMI’s, and distributed control systems. The Modbus RTU protocol is standard and allows for a maximum of 32 sensors and/or field devices to be used in this configuration.
880-N1R Instruction Manual Rev. 0.0 Page 1 of 38
880-N1R

1.2 Analog Systems (4-20mA sensors)

The signal outputs from multiple sensors provide the user with various options for integrating the Model 880 Graphic Control System. One method of integration is accomplished by using 4-20mA signal output gas sensors with Detcon DA4 Modules (Figure 2). The DA4 Module receives an analog 4-20mA signal corresponding to the range of detection then changes it to Modbus™ before relaying the information to the 880A. The Sensor’s output signal is calibrated so that a 4mA input represents a reading of “0” and a 20mA input represents a reading of full scale. The scale used for each sensor is user programmable and can be set in the field. Readings outside the range of 4-20mA will cause a Fault.
Sensor 4
COMM
M S D
L S D
4-20mA
INPUT
Sensor 3
Typical Sensors
Sensor 2
Sensor 1
Figure 2 DA4 4-20mA Configuration
Analog 4-20mA networks are typically recognized as the most fail-safe approach. When using DA4 Module(s), the 880A can communicate with up to 72 analog input channels.
880-N1R Instruction Manual Rev. 0.0 Page 2 of 38
880-N1R

2.0 System Configuration

The Model 880 is designed to monitor and display the status of field sensor devices, provide programmable alarm outputs, and log alarm incidents via a USB drive. The system is equipped with a color graphic touch screen display. Control electronics are industry standard PLC modules pre-selected to fit the application. Three programmable “Banks” of Alarms are designed to give the user the ability to set up three “Zones” of Alarm 1, Alarm 2, Alarm 3 and Fault conditions. Through the use of the Detcon RL4 Modules, each alarm can provide multiple sets of contacts: Common, Normally Open, and Normally Closed for customer annunciator connections.

2.1 Configuration

A Model 880 is equipped with:
8.31" x 6.24" (211.2 x 158.4 mm) Color Graphical Touch Screen display panel
Four slot Programmable Logic Controller (PLC)
o Two communication port CPU Module o Eight channel Relay Output Module o Communications Module (2ea.)
Isolated Network Adapter
24VDC 5Amp Power Supply
Fault, Alarm, Communications, and Power Panel Indicator LED’s

2.2 Touch Panel Graphic Display

The Model 880 is equipped with a graphic display panel (Figure 3) that is prompted to display information such as the operational status of each monitoring device, alarm output readings, and record alarm incidents to a USB Drive.
DC Input
NOT Used
+
24V . . . .
Dedicated power supply recommended
PWR CPU TxD RxD
PLC Serial Port
BACK VIEW
USB Type A Port USB Type B Port
Audio Line Out
BOTTOM VIEW
Ethernet 10/100 Base T Connector
Figure 3 Back of Touch Panel Display
880-N1R Instruction Manual Rev. 0.0 Page 3 of 38
880-N1R
The touch panel acts as a master interface to the internally located PLC. As such, the touch panel polls the PLC, which, in turn, polls the field devices for information. A wand is used on the screen to operate system controls and/or move to additional screens.
A USB port (Figure 3) is located on the back of the unit. When a USB Drive (USB Memory Stick) is installed, the display will automatically log to the drive where any alarms and/or faults have been recorded by
the PLC. The information is logged into a folder named ‘Log’ and named ‘Alarm_yymmdd.txt’ where yy is the year, mm is the month, and dd is the day. The files are written in text format.

2.3 Programmable Logic Controller

At the core of the Model 880 is the modular Programmable Logic Controller (PLC), which is designed to offer maximum flexibility in system configuration (Figure 4). The PLC and all other electronic components are mounted within the enclosure.
CPU
PWR
Direct
LOGIC
+
205
G
BATT
RELAY
RUN CPU
RUN TERM STOP
OUT RELAY
4
0
5
1
6
2
7
3
D2-08TR
5-240VAC 1A 50/60Hz
C
C
0
L
4
L
1
5
2
6
3
7
5-30VDC 5mA-1A
D2-DCM
DATA
COM
D2-DCM
DATA
COM
Figure 4 Basic PLC
Installed in the PLC is the programmable Central Processing Unit (CPU), which processes all instructions, data, and polls all field devices. The CPU utilizes flash memory to store the running program. All units are shipped with firmware loaded and a lithium battery installed. The CPU has two communication ports. The top RS232 port (Port 1) is the programming and interface for the touch display panel. The 15-pin bottom port (Port 2) supports RS232 or RS422 and serves as I/O master for the RS-485 Modbus™ network. The PLC contains an 8-channel Relay Output Module that controls the LED’s on the front panel of the unit. The PLC also utilizes two Data Communication Modules (DCM’s) that are used to communicate with the Remote Display (if connected), and Auxiliary units such as printers or other external compatible devices.

2.4 Isolated Network Adapter

The Model 880 PLC uses an Isolated Network Adapter to interface with devices on the RS-485 Modbus™ network. The Isolated Network Adapter (Figure 5) converts RS-422/485 signals from sensors and other digital devices, to an RS-232 signal that the main CPU can utilize.
The Isolated Network Adapter performs well in noisy environments where data corruption is possible due to induced noise. The Isolated Network Adapter can also be used to verify whether or not the unit is communicating and polling. To simplify troubleshooting, the Isolated Network Adapter has transmit and receive LED’s.
880-N1R Instruction Manual Rev. 0.0 Page 4 of 38
880-N1R
A
Switch Settings: S21 - ON (1)
5V BIAS - ON (1) 0V BIAS - ON (1) 1/2 DPX - ON (1) 1/2 DPX - ON (1) All other switces should be set to OFF (0).
Figure 5 Isolated Network Adapter
Touch Screen Display
TOP VIEW
TB2
(Top Removed)
Power
Supply
B
RXD
TXD
TXD EN
CTS
C-A+VC-A
TX+
TX-
RX-
RX+
C-B
RXD
TXD
1
C3
WMS1C03 240V- 10000
I ON
GROUND
23
C3
WMS1C03 240V- 10000
NEU (L2)
6 7 8 1112 13 14 15 16 17 18 1920910
5A
I
I ON
O
B
B
A
A
+
0V
TXD-
RXD-
TXD+
RXD+
RS-485
RS-485 VDC
REMOTE
Primary
Primary Out
24V -
24V +
24VDC
VAC (L1)
INPUT
OUTPUT
AC Power and Communication
Terminal Blocks
Power Distribution Terminal Blocks
A
Network Adapter
Room for Customer Supplied
USB
PORT
USB Port
TB1
TXD+ RS-422
0V
TXD-
RXD-
RXD+
SLAVE
Room for Customer
Supplied Modules
BACK VIEW
PLC
Modules
Figure 6 Unit overview
880-N1R Instruction Manual Rev. 0.0 Page 5 of 38
880-N1R

2.5 Specifications

Capacity
User Configurable Serial Units: Up to 32 serial devices Analog Units: Up to 72 analog inputs using the Detcon DA-4 Modules
Inputs
RS-485 Modbus™ RTU
Outputs
Primary: RS-485 Slave: RS-485 Remote Output: RS-422 User Configurable Relays via the use of Detcon RL4 Modules
Power Input
100-240VAC 50~60Hz 18-30VDC
Power Consumption
Base Unit <40W – Not to include I/O Modules and sensors. Total Power is dependent on number of I/O modules, number of sensors, and the type of sensors attached. Total power of unit with I/O modules and gas sensors not to exceed 120 Watts.
Display
8” inch diagonal Graphic Backlit LCD Touch screen display
Electrical Classification
19” Rack Mount Enclosure
Dimensions
19''W x 10.5''H x 15''D
Operating Temperature Range
0°C to +45°C
Warranty
One year
880-N1R Instruction Manual Rev. 0.0 Page 6 of 38
880-N1R

3.0 Installation

The Detcon Model 880-N1R PLC is a 19” Rack Mount enclosure. The 880-N1R is a 19” Rack Mount Unit and should be securely mounted in a 19” Rack Mount Cabinet or other suitable 19” Rack Mount Enclosure. Figure 7 provides a dimensional overview of the unit. The unit is 15 inches deep. Several more inches in depth will be needed if Din-Rail Modules are added.
Care should be given to prevent sharp objects from colliding with the touch screen display as damage to the display may cause the unit to become inoperative. The screen can be cleaned with a mild detergent and a lint free cloth. Never use an abrasive cleaner on the display.
19.0"
18.3"
FAULT
NO COMM
ALARM 3
ALARM 2
7.5"
10.5"
15.0"
12.0"
ALARM 1
POWER
ON / OFF
R0.109"
SLOT DETAIL
0.218"
0.375"
Figure 7 Dimensional Overview

3.1 Installing I/O Modules

The 880-N1R provides extra Din-Rail space on the back of the unit for the addition of Din-Rail mounted I/O Modules. There is enough room for the addition of up to 8 modules, but the number of modules that can be mounted should be determined more by the current load imposed on the unit than by the physical space provided. The maximum current load is to be restricted to 3Amps. An RS-485 connector is provided for Modbus™ and power connections to the unit for these Din-Rail mounted modules.
WARNING
devices is be restricted to no more than 3Amps maximum (75 Watts). This equates to 5 DA4 Modules (with 20 sensors and/or field devices attached) and 1 or 2 RL4 Modules. Care should be taken to insure that the total current load of installed modules and other devices utilizing this power does not exceed this 3Amp rating, as this may cause detrimental damage to the unit and will void the warranty. An External Power Source should be used to power any and all modules or devices that exceed this rating. A 3Amp fuse is installed in the unit to limit the current load of this 24VDC Output.
Modules should be mounted on the Din-Rail starting from the right and plugging additional modules in to the left. An RS-485 cable with the appropriate I/O connector is provided on the right side of the Din-Rail and should be plugged into the first module.
: The use of the 880’s 24VDC to power unit mounted Din-Rail modules and external
880-N1R Instruction Manual Rev. 0.0 Page 7 of 38
880-N1R
RS-485 I/O Connector
+
COMM
M S D
L S D
RELAY
COMM
M S D
L S D
RELAY
COMM
M S D
L S D
RELAY
COMM
M S D
L S D
RELAY
COMM
M S D
L S D
4-20mA
INPUT
COMM
M S D
L S D
4-20mA
INPUT
COMM
M
S D
L S D
4-20mA
INPUT
COMM
M S D
L S D
4-20mA
INPUT
SBA-+
-
S
B
A
RS-485 and Power
(Beldon Cable P/N 1502P)
Figure 8 installing Din-Rail mounted modules
I/O Module Addressing
I/O modules must be serially addressed to establish correct communications. All Modules are addressed in Hexadecimal. Typically, the modules will be addressed from 01 to FF Hex starting from the module on the right hand side of the stack. The I/O module’s address is established by setting the two rotary switches to the correspondingly correct position. The top rotary switch sets the Most Significant Bit (MSB). The bottom rotary switch sets the Least Significant Bit (LSB). For an address of 01, set the top switch (MSB) to 0 and the bottom switch (LSB) to 1. See Appendix B for Decimal to Hexadecimal conversion.
NOTE: All addresses must be unique. There can be no duplication of addresses or a Communication
Error (NO COMM) will occur.
COMM
COMM
COMM
COMM
COMM
M S D
L S D
RELAY
COMM
M S D
L S D
RELAY
COMM
M S D
L S D
RELAY
M S D
L S D
RELAY
M
S B
L S B
D
C
D
C
F
E
B
A
F
E
B
A
M S D
L S D
4-20mA
INPUT
0
1
2
3
6
7
8
9
0
1
2
3
6
7
9
8
M S D
L S D
4-20mA
INPUT
4
5
4
5
M S D
L S D
4-20mA
INPUT
COMM
M S D
L S D
4-20mA
INPUT
Figure 9 Setting Device Addresses

3.2 Unit Connections

Connections to the 880 are made via terminals on TB1, located on the back of the unit, refer to Figure 6.
Serial Connections
1. For Serial Units (880S), connect the RS-485 Modbus™ network to the terminal blocks labeled
“Primary RS-485,” “A,” “B,” and “Shld” (Figure 10). Ensure that the network is properly laid out. Proper layout of the RS-485 network is important for correct operation. Refer to Appendix A (RS-485 Integration and Wiring) for proper network layouts. The unit provides no power for external serial devices connected to the unit.
880-N1R Instruction Manual Rev. 0.0 Page 8 of 38
880-N1R
WARNING
: The use of the 880’s 24VDC to power external devices and unit mounted Din-Rail
modules are to be restricted to no more than 3Amps maximum (75 Watts). This equates to about 32 sensors, maximum. Care should be taken to insure that the total current load of devices and Din-Rail mounted modules utilizing this power does not exceed this 3Amp rating, as this may cause detrimental damage to the unit and will void the warranty. An External Power Source should be used to power any and all modules or devices that exceed this rating. A 3Amp fuse is installed in the unit to limit the current load of this 24VDC Output.
678 910
Part of
TB1
B
B
A
A
+
RS-485
RS-485 VDC Primary
Primary Out
Figure 10 Typical RS-485 connections
Analog Sensor Connections
2. For Analog Units (880A), Sensor communication is accomplished by using Detcon DA4 modules and
the RS-485 Modbus™. The 4-20mA sensors are directly connected to the DA4 modules, while the DA4 modules are connected via the RS-485 Modbus™ to the 880 PLC (Figure 11). The unit provides power and Din-Rail space on the back of the unit for a maximum of 5 DA4 modules. Additional DA4 modules should be remotely mounted, require an external power source, and should be connected to the unit via the RS-485 Modbus™. The correct setup of the DA4’s is covered in Section 4.3 880 Setup.
Sensor 4
RS-485 to 880
COMM
M S D
L S D
4-20mA
INPUT
Sensor 3
Typical Sensors
Sensor 1
Sensor 2
Figure 11 Typical Analog Sensor Wiring
3. External annunciators should be connected to Detcon RL4 Modules. The Detcon RL4 Modules
communicate via Modbus™, and should be connected along with other serial devices directly to the RS-485 Modbus™. The correct setup of the RL4’s is covered in Section 4.3 880 Setup. Connections
880-N1R Instruction Manual Rev. 0.0 Page 9 of 38
880-N1R
are provided on each RL4 module for associated annunciators. These connections consist of a set of terminals (Common, Normally Open, Normally Closed) for the associated relay.
FAULT
A
ALARM 3
RS-485 from 880
COMM
M
M S
S D
D L
L S
S D
D
RELAY
A
A
ALARM 2
ALARM 1
A
Figure 12 Typical RL4 Module
4. Terminal blocks are provided for connection to other external devices such as a remote display, a
printer, or other device capable of communication with the 880. The Remote display should be connected to the “REMOTE OUTPUT” terminal blocks, and other devices should be connected to the “RS-422 SLAVE” terminal blocks.
11 12 13 14 15 16 17 18 19 20
Part of
TB1
TXD-
TXD+
RXD+
REMOTE
OUTPUT
0V
RXD-
TXD-
TXD+
RS-422 SLAVE
0V
RXD-
RXD+
Figure 13 Main 880 terminal blocks and connections
5. Connect 110-220VAC input to the Fuse Block labeled “VAC (L1)” in the lower left of the enclosure.
Connect Neutral (or L2) to terminal labeled “NEU (L2)” and Ground to the Green/Yellow terminal labeled “GROUND” (Figure 14). The power supply is able to accept AC input voltages from 100 to 240 volts at 50 or 60Hz.
23
1
C3
C3
WMS1C03
WMS1C03
240V-
240V-
10000
10000
Part of
TB1
Figure 14 Typical Input Power connections
I ON
Ground
I ON
VAC (L1)
NEU (L2)
880-N1R Instruction Manual Rev. 0.0 Page 10 of 38
Loading...
+ 31 hidden pages