Desa GCP10TGCN20T, GCP6 GCN10T, GCP20T, GCN6 User Manual

VENT-FREE BLUE FLAME GAS HEATER
SAFETY INFORMATION AND INSTALLATION MANUAL
For more information, visit www.desatech.com
For more information, visit www.desatech.com
CR94-001 UNVENTED
ROOM HEATER
GCN20T, GCP20T
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal in­jury, or loss of life.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed
by a qualified installer, service agency, or the gas supplier.
GCN6, GCP6
GCN10T, GCP10T
Unvented room heaters are for installa­tion in SINGLE FAMILY TYPE RESI­DENCES ONLY, and the installation is limited to ONE (1) unit per residence.
WARNING: Improper installation, adjust­ment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installa­tion and operational procedures. For as­sistance or additional information con­sult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for ad­equate combustion and ventilation air must be provided. Refer to
and Ventilation
on page 4 of this manual.
Air For Combustion
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
UNPACKING............................................................................... 3
PRODUCT IDENTIFICATION ..................................................... 3
PRODUCT FEATURES .............................................................. 3
LOCAL CODES........................................................................... 4
AIR FOR COMBUSTION AND VENTILATION ........................... 4
INSTALLATION ........................................................................... 6
OPERATING HEATER.............................................................. 14
INSPECTING BURNER ............................................................ 15
CLEANING AND MAINTENANCE ............................................ 16
TROUBLESHOOTING .............................................................. 17
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate, or ser­vice this heater. Improper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead
to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, persons with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are
fuel gases. Fuel gases are odorless. An odor-making agent is added to fuel gases. The odor helps you detect a fuel gas leak. However, the odor added to fuel gas can fade. Fuel gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
ILLUSTRATED PARTS BREAKDOWN AND PARTS LIST ....... 20
SPECIFICATIONS..................................................................... 26
SERVICE CENTER/P ARTS CENTRAL .................................... 26
OWNER’S REGISTRA TION FORM .......................................... 27
REPLACEMENT PARTS .......................................................... 29
SERVICE HINTS....................................................................... 29
TECHNICAL SERVICE ............................................................. 29
SERVICE PUBLICATIONS ....................................................... 29
ACCESSORIES ........................................................................ 29
WARRANTY INFORMATION...................................... Back Cover
WARNING: Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this heater.
Children and adults should be alerted to the hazard of high surface temperature and should stay away to avoid burns or clothing ignition.
Surface of heater becomes very hot when running heater. Heater will remain hot for a time after shut­down. Allow surface to cool before touching.
Any safety screen or guard removed for servicing the appliance must be replaced prior to operation the heater.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Carefully supervise young children when they are in the same room with heater.
WARNING: Any change to this heater or its
controls can be dangerous.
WARNING: Do not use any accessory not ap-
proved for use with this heater.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Make sure grill guard is in place before running heater.
Keep the appliance area clear and free from combus­tible materials, gasoline, and other flammable vapors and liquids.
112157-01A
SAFETY INFORMATION
Continued
SAFETY INFORMATION
UNPACKING
PRODUCT IDENTIFICATION
PRODUCT FEATURES
3
3
Installation and repair should be done by a qualified service person. The appliance should be inspected and serviced before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpeting, etc. It is imperative that control compartments, burn­ers and circulating air passageways of the appliance be kept clean.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors.
3. Do not install in a bedroom or a bathroom.
4. If you smell gas
• Shut off gas supply
• Do not try to light any appliance
• Do not touch any electrical switch; do not use any phone in
your building
• Immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• If you cannot reach your gas supplier, call the fire department
5. This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, pages 4 through 6.
6. Keep all air openings in the front and bottom of heater clear and free of debris. This will insure enough air for proper combustion.
7. If heater and pilot shuts off unexpectedly, do not relight the pilot until you provide fresh, outside air. If heater keeps shut­ting off, have it serviced.
8. Do not run heater
• where flammable liquids or vapors are used or stored
• under dusty conditions
9. Before using furniture polish, wax, carpet cleaner, or similar products, turn heater off. If heated, the vapors from these prod­ucts may create a white powder residue within burner box or on adjacent walls or furniture.
10. Do not use heater if any part has been under water. Immedi­ately call a qualified service technician to inspect the room heater and to replace any part of the control system and any gas control which has been under water.
11. Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
12. Operating heater above elevations of 4,500 feet (1 370 m) could cause pilot outage due to lower levels of oxygen in the air.
13. T o prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. (45 kg) capacity.
14. Provide adequate clearances around air openings.
15. Before using the heater, provide adequate ventilation. An area of 10 square inches (65 cm2) of opening of a window or roof vent is needed for adequate combustion and ventilation air.
UNPACKING
1. Remove heater from carton.
2. Remove all protective packaging applied to heater for shipment.
3. Check heater for any shipping damage. If heater is damaged, promptly inform dealer where you bought heater.
PRODUCT IDENTIFICATION
Piezo Ignitor Button
6,000/10,000 Btu/Hr
Figure 1 - Vent-Free Gas Heater
Control Knob
Grill Guard
Glass Panel
Front Panel
Heater Cabinet
Piezo Ignitor Button
Control Knob
20,000 Btu/Hr
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent­free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.
THERMOSTATIC HEAT CONTROL
Thermostat models have a thermostat sensing bulb and a control valve. This results in the greatest heater comfort. This can also result in lower gas bills.
112157-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
LOCAL CODES AIR FOR COMBUSTION AND VENTILATION
4
Providing Adequate Ventilation
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code*.
*Available from www.csa.ca or 1-800-463-6727 (call your local gas company for your local codes).
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction un­less provisions are provided for adequate combus­tion and ventilation air. Read the following instruc­tions to insure proper fresh air for this and other fuel­burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materi­als, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from CAN/CGA B149.1 Natural Gas Installation Code or CAN/CGA B149.2 Propane Installation Code.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the outside atmosphere
have a continuous water vapor retarder with a rating of one perm (6 x 10 ings gasketed or sealed
b. weather stripping has been added on openable windows
and doors
c. caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and floors, between wall-ceiling joints, between wall pan­els, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide additional fresh air. See
doors
, page 6
If your home does not meet all of the three criteria above, proceed to page 5.
Determining Fresh-Air Flow For Heater Location,
and
.
-11
kg per pa-sec-m2) or less with open-
and
Ventilation Air From Out-
Confined and Unconfined Space
The Canadian Gas Association Certification Requirement, CGA CR94-001 REV. 2 states that when combustion air supply is for the unvented room heater only, it shall be sized at the rate of one (1) square inch per 5000 BTU/HR (1.5 KW) from outdoors or the manufacturer’s specification (whichever is greater). However, com­bustion air is acceptable when available from the principal heat source and sized to the current CAN/CGA-B149.1 or .2 require­ments. Where unvented equipment is installed in an area separated from a combustion air supply by a door, then permanent openings, grills or louvers shall be provided. One shall be within 18 inches (46 cm) from the ceiling and one 18 inches (46 cm) from the floor, sized to one (1) square inch per 1000 BTU/HR (0.29 KW) to allow free movement of air with the source of combustion air supply.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
112157-01A
AIR FOR COMBUSTION AND VENTILATION
Continued
AIR FOR COMBUSTION AND VENTILATION
Determining Fresh-Air Flow For Heater Location
5
5
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height =___________ cu. ft. (m
space)
Example:
8 ft. (2.44 m) (ceiling height) = 2560 cu. ft. (72.6m3) (volume of space) If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr (kW) the space can support.
__________ (volume of space) x 20 = [Maximum Btu/Hr (kW) the
Example:
[maximum Btu/Hr (kW) the space can support]
3. Add the Btu/Hr of all fuel burning appliances in the space.
* Do not include direct-vent gas appliances. Direct-vent draws com­bustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
__________________ __________________ Btu/Hr (kW) (actual amount of Btu/Hr used)
Example:
Space size 20 ft. (6.1 m) (length) x 16 ft. (4.88 m) (width) x
space can support]
2560 cu. ft. (72.6m3) (volume of space) x 20 = 51,200
Vent-free heater _____________ Btu/Hr (kW) Gas water heater* _____________ Btu/Hr (kW) Gas furnace _____________ Btu/Hr (kW) Vented gas heater _____________ Btu/Hr (kW) Gas fireplace logs _____________ Btu/Hr (kW) Other gas appliances* + _____________ Btu/Hr (kW) Total = _____________ Btu/Hr (kW)
Example:
Gas water heater _____________ Btu/Hr (kW) Vent-free heater + _____________ Btu/Hr (kW) Total = _____________ Btu/Hr (kW)
51,200 Btu/Hr (15kW) (maximum the space can support) 60,000 Btu/Hr (17.6kW) [actual amount of Btu/Hr (kW)
used]
40,000 (11.7)
20,000 (5.9)
60,000 (17.6)
Btu/Hr (kW) (maximum the space can support)
3
) (volume of
The space in the above example is a confined space because the actual Btu/Hr (kW) used is more than the maximum Btu/Hr (kW) the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See V entilation Air Fr om Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 6.
C. Install a lower Btu/Hr (kW) heater, if lower Btu/Hr (kW) size makes
room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr (kW) the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construc­tion, provide adequate combustion and ventilation air by one of the methods described in
Natural Gas Installation Code Propane Installation Code
or applicable local code.
CAN/CGA B149.1
or
CAN/CGA B149.2
112157-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
6
Ventilation Air
INSTALLATION
Check Gas Type
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 18" (45 cm) of the ceiling and one within 18" (45 cm) of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow CAN/CGA B149.1 Natural Gas Installation Code or CAN/ CGA B149.2 Propane Installation Code for required size of venti­lation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 18" (45 cm) of the ceiling and one within 18" (45 cm) of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow CAN/CGA B149.1 Natural
Gas Installation Code or CAN/CGA B149.2 Propane Installation Code for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Ventilation
Grills
into Adjoining
Room,
Option 1
Do not provide openings for inlet or outlet air into
18"
12"
(45 cm)
Ventilation Grills
Into Adjoining Room,
Or
Remove Door into Adjoining
Room,
Option 3
Option 2
Ventilated Attic
Crawl Space
Ventilated
To Attic
To
Crawl
Space
Outlet Air
Inlet Air
Outlet Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
Installation must conform with local codes or, in the absence of local codes, with the current standard
CAN/CGA B149.1 Natural Gas Installation Code CAN/CGA B149.2 Propane Installation Code
NOTICE: This heater is intended for use as supple­mental heat. Use this heater along with your primary heating system. Do not install this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified service person must in-
stall heater. Follow all local codes.
CHECK GAS TYPE
or
18"
12"
(45 cm)
Figure 2 - Ventilation Air from Inside Building
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Use only the correct type of gas (natural or propane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater.
112157-01A
)
INSTALLATION
Continued
INSTALLATION
Installation Items
Locating Heater
7
7
INSTALLATION ITEMS
Before installing heater, make sure you have the items listed below.
• for propane/LP gas, external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• for natural gas, test gauge connection* * A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 29.
LOCATING HEATER
This heater is designed to be mounted on a wall.
WARNING: Maintain the minimum clearances shown in Figure 4. If you can, provide greater clear­ances from floor, ceiling, and joining wall.
Models GCN20T and GCP20T only: You can locate heater on
floor, away from a wall. An optional floor mounting stand is needed. Purchase the floor mounting stand from your dealer. See Accesso- ries, page 29.
CAUTION: This heater creates warm air currents. These currents move heat to wall surfaces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as but not limited to, tobacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT:
Vent-free heaters add moisture to the air. Although this is beneficial, installing heater in rooms without enough venti­lation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, pages 4 through 6. If high humidity is experienced, a dehumidifier may be used to help lower the water vapor content in the air.
CAUTION: If you install the heater in a home garage
heater pilot and burner must be at least 18 inches (46 cm) above floor
locate heater where moving vehicle will not hit it
For convenience and efficiency, install heater
• where there is easy access for operation, inspection, and service
• in coldest part of room For 20,000 Btu/hr (5.9 kW) models, an optional fan kit is available
from your dealer. See Accessories, page 29. If planning to use fan, locate heater near a grounded electrical outlet. Outlet must be grounded in accordance with local codes, with the current Canadian Electrical Code Part 1 CSA C22.1.
CEILING
WARNING: Never install the heater
in a bedroom or bathroom
in a recreational vehicle
where curtains, furniture, clothing, or other flam-
mable objects are less than 36 inches (92 cm) from the front, top, or sides of the heater
as a fireplace insert
in high traffic areas
in windy or drafty areas
For more information, visit www.desatech.com
For more information, visit www.desatech.com
112157-01A
6"
(15.3 cm)
Minimum From Sides Of Heater
Left Side
Figure 4 - Mounting Clearances As Viewed From Front of Heater
36" (91.5 cm Minimum
6,000 Btu/Hr
(1.8 kW)
Model Shown
Right Side
Minimum To Top Surface Of Carpeting, Tile Or Other Combustible Material
3" (7.7 cm)
INSTALLATION
8
Thermostat Sensing Bulb (Thermostat Models Only) Installing Heater To Wall 6,000 and 10,000 Btu/Hr Models (1.8 and 2.9 kW)
INSTALLATION
Continued
THERMOSTAT SENSING BULB (Thermostat Models Only)
The thermostat sensing bulb has been placed inside the heater for protection during shipping.
Locating Thermostat Sensing Bulb (for thermostat applications)
1. Remove front panel of heater [for 10,000 Btu/Hr (2.9 KW) heater, see Figure 11 page 9 or for 20,000 Btu/Hr (5.9 KW) heater see Figure 14, page 10].
2. Locate thermostat sensing bulb just under burner assembly.
IMPORTANT:
Attach thermostat sensing bulb to back of heater for
proper operation.
Attaching Thermostat Sensing Bulb
1. Remove thermostat sensing bulb from holders inside heater. Route through slot opening in bottom of heater.
2. Place clamp on thermostat sensing bulb as shown in Figure 5. Clamp is provided in hardware package.
3. Snap clamp into upper mounting hole as shown in Figure 5. Mounting hole is located on lower left edge on back of heater. Make sure the thermostat sensing bulb is pointing up.
Thermostat Sensing Bulb
Clamp
Figure 5 - Attaching Thermostat Sensing Bulb
INSTALLING HEATER TO WALL 6,000 AND 10,000 BTU/HR MODELS (1.8 AND 2.9 KW)
Marking Screw Locations
1. Determine where you will locate heater.
WARNING: Maintain minimum clearances shown in Figure 6. If you can, provide greater clearances from floor and joining wall.
7
/8"
8
(22.5 cm)
Blue Flame
Minimum To
Maintain 6"
Clearance From Wall
JOINING WALL
FLOOR
Figure 6 - Mounting Screw Locations
3
/4"
7
(19.7 cm)
Mounting
Screw
Locations
1
/4" (51.4 cm)
20
Minimum To
Maintain 3" (7.6
cm) Clearance
From Floor
Installing Two Mounting Screws
Note:
Wall anchors and mounting screws are in hardware package.
The hardware package is provided with heater.
Attaching to wall stud method
For attaching mounting screw to wall stud
1. Drill hole at marked location using 9/64" drill bit.
2. Insert mounting screw into wall stud.
3. Tighten screw until 1/16" (1.6 mm) space (thickness of penny) is between screwhead and wall.
Attaching to wall anchor method
Follow instructions below to attach mounting screws to hollow walls (wall areas between studs) or solid walls (concrete or masonry).
1. Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1 1/4" (3.2 cm) deep.
2. Fold wall anchor (see Figure 7).
3. Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
4.
For thin walls [1/2" (1.27 cm ) or less], insert red key into wall anchor. Push red key to “pop” open anchor wings (see Figure 8).
IMPORTANT:
(1.27 cm) thick] or solid walls, do not pop open wings.
Do not hammer key! For thick walls [over 1 /2"
Thin Walls (1/4" to 1/2" thick) (1.6 to 1.2 cm)
2. Mark two mounting screw locations on wall (see Figure 6).
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 7 - Folding Anchor
Figure 8 - Popping Open Anchor Wings For Thin Walls
112157-01A
INSTALLATION
Continued
Installing Heater To Wall 6,000 and 10,000 Btu/Hr Models (1.8 and 2.9 kW) (Cont.)
INSTALLATION
Installing Heater To Wall 20,000 Btu/Hr Models (5.9 kW)
9
9
5. Tighten two screws until 1/16" (1.6 mm) space (thickness of penny) is between screwheads and wall (see Figure 9).
Thin or Thick Wall (thick wall shown)
1/16" Space (1.6 mm)
Solid Wall
Figure 9 - Tightening Anchors
Placing Heater On Mounting Screws
1. Locate two keyhole slots on back panel of heater (see Figure 10).
2. Place large openings of slots over screwheads. Slide heater down until screws are in small portion of slots.
Keyhole Slots
Installing Bottom Mounting Screw
1. Locate bottom mounting hole. This hole is near bottom on back panel of heater (see Figure 12).
2. Mark screw location on wall.
3. Remove heater from wall.
4. If installing bottom mounting screw into hollow or solid wall, install wall anchor. Follow steps 1 through 5 under Attaching T o Wall Anchor Method, page 10. If installing bottom mounting screw into wall stud, drill hole at marked location using 9/64" drill bit.
5. Replace heater on wall.
6. Insert bottom anchor screw through back panel into bottom anchor or drilled hole (see Figure 12).
7. Tighten screw until heater is firmly secured to wall. Do not over tighten.
Note:
Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 11 and 12).
Figure 10 - Location Of Keyhole Slots On Back Panel Of Heater
Removing Front Panel Of Heater
1. Remove two screws near bottom corners of front panel.
2. Lift straight up on grill guard until it stops. Grill guard will slide up about 1/4" (6 mm).
3. Pull bottom of front panel forward, then down.
Figure 11 - Removing Front Panel Of Heater
Figure 12 - Installing Bottom Mounting Screw
INSTALLING HEATER TO WALL 20,000 BTU/HR MODELS (5.9 KW)
Mounting Bracket
Locate mounting bracket in heater carton. Remove mounting bracket from heater carton.
Figure 13 - Mounting Bracket
112157-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
INSTALLATION
10
Installing Heater To Wall 20,000 Btu/Hr Models (5.9 kW) (Cont.)
INSTALLATION
Continued
Removing Front Panel Of Heater (20,000 Btu/Hr Models Only) (5.9 kW)
1. Remove the four painted screws, two on each side of front panel.
2. Pull bottom of front panel forward, then out.
3. Remove any remaining packaging materials.
8"
(20.3 cm)
Min.
Only Insert Mounting Screws Through Last
Hole On Each End
Adjoining Wall
Figure 15 - Mounting Bracket Clearances
14"
(35.6 cm)
18 3/4"
(47.7 cm)
Min.
Floor
Attaching Mounting Bracket To Wall
Note:
Wall anchors, mounting screws, and spacers are in hardware
package. The hardware package is provided with heater.
Figure 14 - Removing Front Panel Of Heater
Methods For Attaching Mounting Bracket To Wall
Only use last hole on each end of mounting bracket to attach bracket to wall. These two holes are 14 inches (35.5 cm) apart from their centers. Attach mounting bracket to wall in one of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Stud: This method provides the strongest hold.
Insert mounting screws through mounting bracket and into wall studs.
Attaching to Wall Anchor: This method allows you to attach
mounting bracket to hollow walls (wall areas between studs) or to solid walls (concrete or masonry).
Decide which method better suits your needs. Either method will provide a secure hold for the mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where heater will be located. Make sure mounting bracket is level.
WARNING: Maintain minimum clearances shown in Figure 15. If you can, provide greater clearances from floor and joining wall.
2. Mark screw locations on wall (see Figure 15).
Note:
Only mark last hole on each end of mounting bracket.
Insert mounting screws through these holes only.
3. Remove tape and mounting bracket from wall.
Attaching To Wall Stud Method
For attaching mounting bracket to wall studs
1. Drill holes at marked locations using 9/64" drill bit.
2. Place mounting bracket onto wall. Line up last hole on each end of bracket with holes drilled in wall.
3. Insert mounting screws through bracket and into wall studs.
4. Tighten screws until mounting bracket is firmly fastened to wall studs.
Attaching To Wall Anchor Method
For attaching mounting bracket to hollow walls (wall areas be­tween studs) or solid walls (concrete or masonry)
1. Drill holes at marked locations using 5/16" drill bit. For solid walls (concrete or masonry), drill at least 1" (2.5 cm) deep.
2. Fold wall anchor as shown in Figure 16.
3. Insert wall anchor (wings first) into hole. Tap anchor flush to wall.
4. For thin walls [1/2" (1.27 cm) or less ], insert red key into wall anchor. Push red key to “pop” open anchor wings.
IMPORTANT:
Do not hammer key! For thick walls [over 1/2" (1.27 cm) thick] or solid walls, do not pop open wings.
5. Place mounting bracket onto wall. Line up last hole on each end of bracket with wall anchors.
6. Insert mounting screws through bracket and into wall anchors.
7. Tighten screws until mounting bracket is firmly fastened to wall.
Figure 16 - Folding Anchor
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 17- Popping Open Anchor Wings For Thin Walls
112157-01A
INSTALLATION
Continued
Installing Heater To Wall 20,000 Btu/Hr Models (5.9 kW) (Cont.)
INSTALLATION
Mounting Heater To Floor With Optional Floor Kit [20,000 Btu/Hr (5.9 kW) Only]
11
11
Placing Heater On Mounting Bracket
1. Locate two horizontal slots on back panel of heater.
2. Place heater onto mounting bracket. Slide horizontal slots onto stand-out tabs on mounting bracket.
Horizontal Slots
Stand-Out Tab
Figure 18 - Mounting Heater Onto Mounting Bracket
Mounting Bracket (attached to wall)
Installing Bottom Mounting Screws
1. Locate two bottom mounting holes. These holes are near bot­tom on back panel of heater (see Figure 19).
2. Mark screw locations on wall.
3. Remove heater from mounting bracket.
4. If installing bottom mounting screws into hollow or solid wall, install wall anchors. Follow steps 1 through 4 under Attaching T o W all Anc hor Method, page 10.
If installing bottom mounting screw into wall stud, drill holes at marked locations using 9/64" drill bit.
5. Replace heater onto mounting bracket.
6. Place spacers between bottom mounting holes and wall anchor or drilled hole.
7. Hold spacer in place with one hand. With other hand, insert mounting screw through bottom mounting hole and spacer. Place tip of screw in opening of wall anchor or drilled hole.
8. Tighten both screws until heater is firmly secured to wall. Do not over tighten.
Note:
Do not replace front panel at this time. Replace front panel after making gas connections and checking for leaks (see pages 11 and 12).
Heater
Wall
MOUNTING HEATER TO FLOOR WITH OPTIONAL FLOOR KIT [20,000 BTU/HR (5.9 KW) ONLY]
Mounting Base Feet to Heater
1. Lay heater cabinet on its back on a table with the heater bot­tom overhanging the table edge.
2. Align holes in base foot with mounting holes on bottom of cabinet (see Figure 20).
3. Secure base foot to heater using sheet metal screws.
4. Repeat for other side.
Mounting Base Feet to Floor (Where required by local code)
If heater is being installed directly on carpeting, tile or other combustible material (other than wood flooring), the heater shall be installed on a metal or wood panel extending the full width and depth of the appliance.
1. Remove front cover (see Removing Front Panel of Heater, page 10).
2. Position heater with base feet in desired location. Mark holes for drilling. Remove heater with base.
3. If mounting base to a wood floor, drill 1/8 inch diameter hole, 3/4 inch (2 cm) deep. (Do not use anchors in wood floors).
If mounting base to a concrete floor, drill with 1/4 inch diam­eter concrete drill bit, 13/8 inches (3.5 cm) into floor. Insert anchors completely into holes.
4. Reposition heater with base feet over holes. Secure base to floor with wood screws. See Figure 20.
Wood Screw
Front View
Figure 19 - Installing Bottom Mounting Screws
For more information, visit www.desatech.com
For more information, visit www.desatech.com
112157-01A
Side View
Spacer
Base Foot
Sheet Metal Screw
Figure 20 - Installing Base Feet (Heater may vary from illustration)
INSTALLATION
12
Connecting To Gas Supply
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pres­sure regulator.
WARNING: A qualified service person must con­nect heater to gas supply. Follow all local codes.
WARNING: For natural gas, never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
IMPORTANT
connecting heater to gas line. Gas line pressure must be no greater than
10.5 inches (26.6 cm) of water. If gas line pressure is higher, heater regulator damage could occur.
CAUTION: For propane/LP gas, never connect heater directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the heater and pro­pane/LP supply.
For propane/LP gas, the installer must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches (28 and 35.5 cm) of water. If you do not reduce incoming gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 21. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe. Internally-tinned copper tubing may be used in cer­tain areas. Check your local codes. Use pipe of large enough diameter to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Typical inlet pipe diameter for 20,000 btu/hr (5.9 kW) models - 3/8" or greater.
: For natural gas, check gas line pressure before
Propane/LP Supply Tank
External Regulator
Installation must include equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 22).
IMPORTANT:
Install an equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install sediment trap in supply line as shown in Figure 22. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.
IMPORTANT:
Hold pressure regulator with wrench when con­necting it to gas piping and/or fittings. Do not over tighten pipe connection to regulator. The regulator body could be damaged.
3/8" NPT Pipe Nipple
Ground Joint Union
Equipment Shutoff Valve*
Natural Gas
From Gas Meter [
6/10,000 Btu/Hr (1.8/2.9 kW)
4" (10 cm) W.C. to
10.5" (26.7 cm) W.C. Pressure]
20,000 Btu/Hr (5.9 kW)
5" (12.7 cm) W.C. to 10.5" (26.7 cm) W.C. Pressure]
Propane/LP
From External Regulator (11" (27.9 cm) W.C. to 14" (35.6 cm) W.C. Pressure)
3"
7.7 cm) Minimum
Tee Joint Reducer
Bushing to 1/8" NPT
1/8" NPT Plug Tap
Tee Joint
Pipe Nipple
Cap
Pressure Regulator
Heater Cabinet
Test Gauge Connection*
Sediment Trap
Vent Pointing Down
Figure 21 - External Regulator With Vent Pointing Down (Propane/LP Systems Only)
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 22 - Gas Connection
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 29.
112157-01A
ON
POSITIO
OF
POSI
INSTALLATION
Continued
Checking Gas Connections
INSTALLATION
13
13
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections for leaks after installing or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: For propane/LP gas, make sure exter­nal regulator has been installed between propane/LP supply and heater. See guidelines under
to Gas Supply
, page 12.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (con­trol valve) and equipment shutoff valve from gas supply pip­ing system. Pressures in excess of 1/2 psig (3.5 kPa) will dam­age heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using com­pressed air.
4. Check all joints of gas supply piping system. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 23).
2. Pressurize supply piping system by either opening propane/ LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas, or using compressed air.
3. Check all joints from gas meter for natural gas (see Figure 24) or propane/LP supply tank for propane/LP gas, to equipment shutoff valve (see Figure 25). Apply a noncorrosive leak de­tection fluid to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Connecting
2. Open main gas valve located on or near gas meter for natural gas or open propane/LP supply tank valve.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from equipment shutoff valve to control valve (see Fig ures 24 and 25 ). Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater pages 14 and 15). Check the rest of the internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appliance, page 15).
8. Replace front panel.
Equipment Shutoff Valve
Figure 23 - Equipment Shutoff Valve
Control Valve Location
Gas Meter
Figure 24 - Checking Gas Joints for Natural Gas [6, 000 Btu/Hr Model (1.8 kW) Shown]
Propane/LP Supply Tank
Open
Closed
Equipment Shutoff Valve
Control Valve Location
Equipment Shutoff Valve
Pressure Testing Heater Gas Connections
1. Open equipment shutoff valve (see Figure 23).
112157-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 25 - Checking Gas Joints for Propane/LP Gas [6,000 Btu/Hr Model (1.8 kW) Shown]
OPERATING HEATER
14
For Your Safety Read Before Lighting Lighting Instructions
OPERATING HEATER
FOR YOUR SAFETY READ
BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing prop­erty damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire de­partment.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service techni­cian or gas supplier. Force or attempted r epair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
1. STOP! Read the safety information above.
2. Make sure equipment shutoff valve is fully open.
3. Turn control knob clockwise (see Figure 26 or 27).
4. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Fol­low “B” in the safety information, abov e. If you don’t smell gas, go to the next step.
5. Press in control knob and turn counterclockwise to the PILOT position. Keep control knob pressed in for five (5) seconds (see Figure 26 or 27).
Note:
You may be running this heater for the first time after hooking up to gas supply . If so, the control knob may need to be pressed in for 30 seconds or more. This will al­low air to bleed from the gas system.
• If control knob does not pop up when released, contact a
qualified service person or gas supplier for repairs.
to the OFF position
Clockwise
C-clockwise
6. With control knob pressed in, push down and release igni­tor button. This will light pilot. The pilot is attached to the front of burner. The pilot can be seen through the glass panel. If needed, keep pressing ignitor button until pilot lights.
Note:
If pilot does not stay lit, refer to Troubleshooting,
pages 18 through 20. Also contact a qualified service per­son or gas supplier for repairs. Until r epairs are made, light pilot with a match. To light pilot with amatch, see Manual Lighting Procedure, page 15.
7. Keep control knob pressed in for 30 seconds after lighting pilot. After 30 seconds, release control knob.
• If control knob does not pop up when released, contact a
qualified service person or gas supplier for repairs.
Note:
If pilot goes out, repeat steps 3 through 7. Thermo­stat model heaters have a safety interlock system. W ait one (1) minute before lighting pilot again.
8. Manual Controlled Models Only T urn control knob coun- terclockwise
C-clockwise
to the HI position. The main burner should light. Set control knob to HI or LO. To turn control knob from HI to LO, press in the control knob and turn coun­terclockwise
Note:
Both HI and LO are locked positions. Y ou must pr ess
C-clockwise
.
in control knob before turning it from these positions.
9. Thermostat Controlled Models Only T urn control knob counterclockwise
C-clockwise
to desired heating level. The main burner should light. Set control knob to any heat le vel between 1 and 5.
CAUTION: Do not try to adjust heating levels by
using the equipment shutoff valve.
Ignitor Button
Control Knob
Figure 26 - Control Knob In The OFF Position (Manual Controlled Models)
Ignitor Button
Control Knob
T
O
L
I
P
F
F
O
Figure 27 - Control Knob In The OFF Position (Thermostat Controlled Models)
Thermocouple
Ignitor Electrode
Pilot Burner
Figure 28 - Pilot
For more information, visit www.desatech.com
For more information, visit www.desatech.com
112157-01A
To Turn Off Gas To Appliance
OPERATING HEATER
Thermostat Control Operation (Thermostat Models Only)
Manual Lighting Procedure
INSPECTING BURNER
Pilot Flame Pattern
Burner Flame Pattern
15
15
OPERATING HEATER
Continued
TO TURN OFF GAS
TO APPLIANCE
Shutting Off Heater
1. Press in and turn control knob clockwise position.
2. Turn off all electric power to the appliance if service is to be performed.
Shutting Off Burner Only (pilot stays lit)
Turn control knob clockwise
to the PILOT position.
Clockwise
THERMOSTAT CONTROL
OPERATION (THERMOSTAT
MODELS ONLY)
The thermostatic control used on these models differs from standard thermostats. Standard thermostats simply turn on and off the burner. The thermostat used on this heater senses the room temperature. The thermostat adjusts the amount of gas flow to the burner. This increases or decreases the burner flame height. At times the room may exceed the set temperature. If so, the burner will shut off. The burner will cycle back on when room temperature drops below the set temperature. The control knob can be set to any heat level between 1 and 5.
Note:
The thermostat sensing bulb measures the temperature of air near the heater cabinet. This may not always agree with room temperature (depending on housing construction, installation location, room size, open air temperatures, etc.). Frequent use of your heater will let you determine your own comfort levels.
MANUAL LIGHTING
PROCEDURE
1. Remove front panel [for 6,000 (1.8 kW) and 10,000 (2.9 kW)
Btu/Hr heater see Figure 11, page 9, for 20,000 Btu/Hr (5.9 kW) heater, see Figure 14 page 10].
2. Follow steps 1 through 5 under Lighting Instructions,
page 14.
3. With control knob pressed in, strik e match. Hold match to
pilot until pilot lights.
4. Keep control knob pressed in for 30 seconds after pilot is
lit. After 30 seconds, release control knob. Follow step 8 under Lighting Instructions, page 14.
5. Replace front panel.
Clockwise
to the OFF
INSPECTING BURNER
Check pilot flame pattern and burner flame pattern often.
PILOT FLAME PATTERN
Figure 29 shows a correct pilot flame pattern. Figure 30 shows an incorrect pilot flame pattern. The incorrect pilot flame is not touching the thermocouple. This will cause the thermocouple to cool. When the thermocouple cools, the heater will shut down.
If pilot flame pattern is incorrect, as shown in Figure 30
• turn heater off (see To Turn Off Gas to Appliance, column 1)
• see Troubleshooting, pages 18 through 20
Note:
The pilot flame on natural gas units will have a slight curve,
but flame should be blue and have no yellow or orange color.
Thermocouple
Blue Flame
Pilot Burner
Figure 29 - Correct Pilot Flame Pattern
BURNER FLAME PATTERN
WARNING: If yellow tipping occurs, your heater
could produce increased levels of carbon monoxide.
NOTICE: Do not mistake orange flames with yellow tipping. Dust or other fine particles enter the heater and burn causing brief patches of orange flame.
Figure 31 shows a correct burner flame pattern. Figure 32 shows an incorrect burner flame pattern. The incorrect burner flame pattern shows yellow tipping of the flame. It also shows the flame higher than 1/2 the glass panel height.
If burner flame pattern is incorrect, as shown in Figure 32
• turn heater off (see To Turn Off Gas to Appliance, column 1)
• see Troubleshooting, pages 18 through 20
Thermocouple
Figure 30 - Incorrect Pilot Flame Pattern
Yellow Tipping
1/2 GLASS HEIGHT
Yellow Flame
Pilot Burner
112157-01A
(Models GCN6 and GCP6 will be
lower due to lower input rating)
Figure 31 - Correct Burner Flame Pattern
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 32 - Incorrect Burner Flame Pattern
CLEANING AND MAINTENANCE
16
ODS/Pilot and Burner Orifice Burner Pilot Air Inlet Hole Cabinet
CLEANING AND MAINTENANCE
WARNING: Turn off heater and let cool before
cleaning.
CAUTION: You must keep control areas, burner, and circulating air passageways of heater clean. In­spect these areas of heater before each use. Have heater inspected yearly by a qualified service person. Heater may need more frequent cleaning due to exces­sive lint from carpeting, bedding material, pet hair, etc.
WARNING: Failure to keep the primary air opening(s) of the burner(s) clean may result in soot­ing and property damage.
ODS/PILOT AND BURNER ORIFICE
• Use a vacuum cleaner, pressurized air, or small, soft bristled brush to clean.
BURNER PILOT AIR INLET HOLE
The primary air inlet holes allow the proper amount of air to mix with the gas. This provides a clean burning flame. Keep these holes clear of dust, dirt, lint, and pet hair. Clean these air inlet holes prior to each heating season. Blocked air holes will create soot. We recommend that you clean the unit every three months during operation and have fireplace inspected yearly by a qualified service person.
We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt. To clean these parts we recommend using compressed air no greater than 30 PSI (207 kPa). Your local computer store, hardware store, or home center may carry compressed air in a can. You can use a vacuum cleaner in the blow position. If using compressed air in a can, please follow the directions on the can. If you don't follow directions on the can, you could damage the pilot assembly.
1. Shut off the unit, including the pilot. Allow the unit to cool for
at least thirty minutes.
2. Inspect burner, pilot for dust and dirt.
3. Blow air through the ports/slots and holes in the burner.
4. Never insert objects into the pilot tube.
Clean the pilot assembly also. A yellow tip on the pilot flame indicates dust and dirt in the pilot assembly. There is a small pilot air inlet hole about two inches from where the pilot flame comes out of the pilot assembly (see Figure 33). With the unit off, lightly blow air through the air inlet hole. You may blow through a drinking straw if compressed air is not available.
Pilot Assembly
Pilot Air Inlet
Figure 33 - Pilot Inlet Air Hole
CABINET
Air Passageways
• Use a vacuum cleaner or pressurized air to clean.
Exterior
• Use a soft cloth dampened with a mild soap and water mixture. Wipe the cabinet to remove dust.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
112157-01A
TROUBLESHOOTING
Note:
For additional help, visit DESA’s
technical service web site at www.desatech.com.
Note:
All troubleshooting items are listed in
order of operation.
WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service and repair heater.
TROUBLESHOOTING
CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.
17
17
OBSERVED PROBLEM
When ignitor button is pressed, there is no spark at ODS/pilot
When ignitor button is pressed, there is spark at ODS/pilot but no ignition
ODS/pilot lights but flame goes out when control knob is released
POSSIBLE CAUSE
1. Ignitor electrode positioned wrong
2. Ignitor electrode broken
3. Ignitor electrode not connected to igni­tor cable
4. Ignitor cable pinched or wet
5. Broken ignitor cable
6. Bad piezo ignitor
1. Gas supply turned off or equipment shutoff valve closed
2. Control knob not in PILOT position
3. Control knob not pressed in while in PILOT position
4. Air in gas lines when installed
5. Depleted gas supply (propane/LP only)
6. ODS/pilot is clogged
7. Gas regulator setting is not correct
1. Control knob not fully pressed in
2. Control knob not pressed in long enough
3. Safety interlock system has been triggered
4. Equipment shutoff valve not fully open
5. Thermocouple connection loose at con­trol valve
6. Pilot flame not touching thermocouple, which allows thermocouple to cool, causing pilot flame to go out. This prob­lem could be caused by one or both of the following: A) Low gas pressure B) Dirty or partially clogged ODS/pilot
7. Thermocouple damaged
8. Control valve damaged
REMEDY
1. Replace pilot assembly
2. Replace pilot assembly
3. Reconnect ignitor cable
4. Free ignitor cable if pinched by any metal or tubing. Keep ignitor cable dry
5. Replace ignitor cable
6. Replace piezo ignitor
1. Turn on gas supply or open equipment shutoff valve
2. Turn control knob to PILOT position
3. Press in control knob while in PILOT position
4. Continue holding down control knob. Repeat igniting operation until air is re­moved
5. Contact local propane/LP gas company
6. Clean ODS/pilot (see Cleaning and Maintenance, page 16) or replace ODS/ pilot assembly
7. Replace gas regulator
1. Press in control knob fully
2. After ODS/pilot lights, keep control knob pressed in 30 seconds
3. Wait one minute for safety interlock sys­tem to reset. Repeat ignition operation
4. Fully open equipment shutoff valve
5. Hand tighten until snug, then tighten 1/4 turn more
6. A) Contact local natural or propane/LP gas company B) Clean ODS/pilot (see Cleaning and Maintenance, page 16) or replace ODS/ pilot assembly
7. Replace pilot assembly
8. Replace control valve
112157-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
TROUBLESHOOTING
18
TROUBLESHOOTING
Continued
OBSERVED PROBLEM
Burner does not light after ODS/pilot is lit
Delayed ignition of burner
Burner backfiring during combustion
Yellow flame during burner combustion
POSSIBLE CAUSE
1. Burner orifice is clogged
2. Inlet gas pressure is too low
1. Manifold pressure is too low
2. Burner orifice is clogged
1. Burner orifice is clogged or damaged
2. Burner damaged
3. Gas regulator defective
1. Not enough air
2. Gas regulator defective
3. Clogged or dirty burner
REMEDY
1. Clean burner orifice (see Cleaning and Maintenance, page 16) or replace burner
orifice
2. Contact local natural or propane/LP gas company
1. Contact local natural or propane/LP gas company
2. Clean burner orifice (see Cleaning and Maintenance, page 16) or replace burner orifice
1. Clean burner orifice (see Cleaning and Maintenance, page 16) or replace burner orifice
2. Replace burner
3. Replace gas regulator
1. Check burner for dirt and debris. If found, clean burner (see Cleaning and Maintenance, page 16)
2. Replace gas regulator
3. Clean burner (see Cleaning and Main- tenance, page 16)
Slight smoke or odor during initial operation
Heater produces a whistling noise when burner is lit
Heater produces a clicking/ticking noise just after burner is lit or shut off
1. Residues from manufacturing processes
1. Turning control knob to HI position when burner is cold
2. Air in gas line
3. Air passageways on heater blocked
4. Dirty or partially clogged burner orifice
1. Metal expanding while heating or con­tracting while cooling
1. Problem will stop after a few hours of operation
1. Turn control knob to LO position and let warm up for a minute
2. Operate burner until air is removed from line. Have gas checked by local natural or propane/LP gas company
3. Observe minimum installation clear­ances (see Figure 4, page 7)
4. Clean burner (see Cleaning and Mainte- nance, page 16) or replace burner orifice
1. This is common with most heaters. If noise is excessive, contact qualified ser­vice person
For more information, visit www.desatech.com
For more information, visit www.desatech.com
112157-01A
Loading...
+ 42 hidden pages