Desa EVDDVF36STN, EVDDVF36PN User Manual

®
DIRECT-VENT GAS FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
(Peninsula Shown)
EVDDVF36PN (PENINSULA) AND EVDDVF36STN (SEE THRU)
NATURAL GAS - ELECTRONIC IGNITION
WARNING: If the information in these instruc­tions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS :
• Do not try to light any appliance.
• Do not touch any electrical switch;
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a
qualified installer, service agency, or the gas supplier.
SAVE THIS BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appli­ance, it also contains information that will enable you to obtain replacement parts or optional accessory items when needed. Keep it with your other important papers.
WARNING: Improper installation, adjustment, alteration, service, or maintenance to this appliance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This Direct-Vent Gas Fireplace series is intended for use with Natural or Propane/LP gas only. Do not attempt to burn any solid fuels in these appliances.
CHECK LOCAL CODES PRIOR TO INSTALLATION
This appliance may be installed in an aftermarket* permanently located, manufactured (mobile) home, where not prohibited by state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
Save this manual for future reference.
®
DIRECT-VENT GAS FIREPLACE
EVDDVF36PN and EVDDVF36STN
Alternate Bottom Gas Supply Inlets
(Front)
ø1.5
(4cm)
1
10
/
2
(27cm)
Top Spacer
Back of Surround
(Back)
Right Side Surround
Left Side Surround
23 5/
8
(60cm)
15
11
/
(30cm)
1 1/4 (3cm)
(Left Side)
10
(27cm)
1
/
2
ø1.5
(4cm)
(Right Side)
16
RIGHT SIDE
Rating Plate Location
5
/
8
22
(57cm)
32 (81cm) (Opening) 1
1
/8 (104cm)
41
7
/8 (5cm)
Figure 1 - EVDDVF36PN (Peninsula) Dimensions
Left Side Surround
Back of Surround
(Back)
Right Side
23 5/
(60cm)
8
15
11 (30cm)
TOP VIEW
(Left Side)
10 1/
(27cm)
2
ø1.5
(4cm)
(Right Side)
/
16
Alternate Bottom Gas Supply Inlets
(Front)
ø1.5
(4cm)
1
/
8
11
(28cm)
Surround
39 3/
(101cm)
39 3/
(101cm)
4
(67cm)
3 (8cm)
4
26
(67cm)
3 (8cm)
BACK VIEWTOP VIEW
GLOSSARY OF TERMS
Chase - A box-like enclosure to protect
3
34
/
4
venting from the elements when the venting run is on the outside of a structure.
Mastic - A pliable sealant for use around the vent terminal.
Snorkel Termination - A box that raises the horizontal termination above ground level clearances.
Vent Terminal - Mounted on an outside wall or roof to separate the inlet and outlet of the vent system and protect it from weather.
Vinyl Siding Standoff - A metal box that separates the vent cap from vinyl siding.
Wall Thimble/Firestop - A metal plate used to secure the vent pipe when it passes through a wall or ceiling.
3
/
4
34
3
/
8
26
1 (3cm)
22
(57cm)
2 (5cm)
(88cm)
5
/
8
3 (8cm)
FRONT VIEW
30
(76cm)
(Opening)
7
/8 (50cm)
19
(Opening) 25 (64cm)
BACK VIEW
3
/
8
1 (3cm)
22
(57cm)
2 (5cm)
(88cm)
5
/
8
3 (8cm)
1
1
/4 (3cm)
RIGHT SIDE
Top Spacer
Rating Plate
22 5/
(57cm)
8
32 (81cm) (Opening)
1
43
/8 (110cm)
Location
7
/8 (5cm)
1
Figure 2 - EVDDVF36STN (See Thru) Dimensions
Note:
All dimensions in this manual are in inches unless otherwise specified.
FRONT VIEW
5
23
/8 (60cm)
25 (64cm)
2
30
(76cm)
(Opening)
106573
OWNER’S MANUAL
INTRODUCTION
Model EVDDVF36PN series is a three-sided direct-vent gas fireplace with a sealed com­bustion chamber. Model EVDDVF36STN series is a two-sided direct-vent gas fire­place with a sealed combustion chamber. These models are equipped with an elec­tronic direct spark ignition system and re­quire household electricity to operate. A fan kit is available for these models as an option (see Accessories on page 26).
NOTICE: Check local building codes for area requirements be­fore installing this appliance.
• Models EVDDVF36PN and EVDDVF36STN use NATURAL GAS ONLY.
If you have any doubts as to which gas your particular appliance is approved and tested for, please check the AGA/CGA rating plate located at the interior of the appliance open­ing or consult your local distributor (see Figures 1 and 2, page 2).
BEFORE YOU BEGIN
Before beginning the installation of your appliance, read these instructions through completely.
This DESA appliance and its approved com­ponents are safe when installed according to this installation manual and operated as recommended by DESA. Unless you use DESA approved components tested for this appliance, YOU MAY CAUSE A SAFETY
HAZARD!
The DESA warranty will be voided by, and DESA disclaims any responsibility for the following actions:
A) Modification of the appliance or any of
the components manufactured by DESA unless otherwise permitted in writing by DESA.
B) The use of any components part not ap-
proved by DESA in combination with this DESA appliance.
C) Installation and/or operation in a man-
ner other than instructed in this manual.
D) The burning of anything other than the
type of gas approved for use in this gas appliance.
This appliance, when installed, must be elec­trically grounded in accordance with local codes, or in the absence of local codes, with the National Electrical Code, ANS/NFPA 70 or the Canadian Electrical Code, CSA C22.1.
The installation must conform with local codes or, in the absence of local codes, with the
National Fuel Gas Code, ANS Z223.1 or the Canadian Installation Code, CAN/CGA B149.
This appliance complies with ANS Z21.50­1998/CSA 2.22-M48 as a VENTED GAS FIREPLACE. It is listed and tested by Inter­national Approval Services.
NOTICE: This appliance is in­tended to be used only for supple­mental heat.
WARNING: Installation and repair should be done by a quali­fied installer/service person. The appliance should be inspected before use, and at least annually thereafter by a qualified service person. More frequent cleaning may be required due to exces­sive lint from carpeting, bedding, pet hair, etc. It is imperative that the control compartments, burn­ers, and circulating air systems be kept clean.
SELECTING LOCATION
To determine the safest and most efficient location for your appliance, consider the following guidelines:
1. The location must allow for proper clearances (see Clearances, page 4).
2. Consider a location where heat output would not be affected by drafts, air con­ditioning ducts, windows, or doors.
3. A location that avoids the cutting of joists or roof rafters makes installation easier.
In selecting a location, the following pre­cautions must be observed:
1. A projection may be ideal for a new ad­dition on an existing finished wall. See Horizontal Termination Configuration, pages 10 and 11, or Vertical Termina- tion Configuration, pages 13 and 14.
2. Do not locate appliance close to where gasoline or other flammable liquids may be stored. The appliance must be kept clear and free from combustible materials.
3. Do not connect this appliance to a chimney system used for solid fuel burning fireplace.
4. Due to high temperatures, do not lo­cate this appliance in high traffic areas or near furniture and draperies.
5. This fireplace may be installed in bed­rooms or bathrooms in accordance with local codes.
6. Never obstruct the openings of the ap­pliance or flow of ventilation air. Keep the control compartments accessible.
7. Do not use this appliance if any part has been under water . Immediately con­tact a local service technician to exam­ine the appliance and to replace any part(s) of the control ignition system and other related components that have submerged under water.
Figure 3 - Possible Installation of Peninsula Fireplace
106573
3
®
DIRECT-VENT GAS FIREPLACE
EVDDVF36PN and EVDDVF36STN
PRE-INSTALLATION PREPARATION
CLEARANCES
Minimum clearances to combustibles are:
• Back and Sides
of Surround: .............................0" min.
• Vent Surfaces:
Vertical Runs:................ 1" (5cm) min.
Top of Horizontal Runs . 2" (5cm) min.
• Ceiling to Opening: ... 36" (91cm) min.
• Floor: ........................................0" min.
• Wall to Front of Glass:36" (91cm) min.
• Perpendicular Wall to
Opening of Unit: ........... 2" (5cm) min.
• Top Spacer: .............................. 0" min.
CEILING
36"
(914mm)
Min.
WALL
CAUTION: Do not block re­quired air spaces with insula­tion or any other material. Do not obstruct the effective opening of the appliance with any type of facing material.
Top Spacer
MANTEL CLEARANCES
Woodwork, such as wood trims, mantels, and other combustible materials projecting no more than 1 1/2 inches (3.8cm) shall not be placed within 7 inches (17.8cm) from the opening of the unit. Combustible material above and projecting more than 1 1/2 inches (3.8cm) from the appliance’s face must not be placed less than 15 inches (38.1cm) from the louver opening (see Figure 6).
Combustible Material May Be Used
21"
(533mm)
Top of Louver Opening
Min.
(381mm)
(102mm)
15"
Min.
7" (178mm) Min.
Drywall (Gypsum Board, Sheetrock, Etc.)
12"
(305mm)
Min.
4"
Min.
Safe Zone for Projection of Combustible Material
2 x 4 Spacer
1
/2" (38mm)
1 Min.
UNIT
36"
(914mm)
Min.
Figure 4 - Minimum Clearances (Peninsula Shown)
Left Side Surround (0" Min.)
*Combustible
Material
Right Side Surround (0" Min.)
Perpendicular Wall 2" (51mm) Min. From Opening
Figure 5 - Minimum Clearances (See Thru Shown)
TOP VIEW
2" (51mm)
Wall In Front Of Glass
36" (91cm) Min.
0" Floor
(914mm)
* May be attached with screws to the surround.
0"
Drywall
2 x 4 Stud
Minimum 1" Clearance from Side (Only for See Thru)
36"
Figure 6 - Mantel Clearances for Peninsula and See Thru Fireplaces (Peninsula Shown)
FRAMING
Once the final location has been determined, observing height clearances for vent termi­nation, you may construct framing using dimensions shown in Figures 7 through 9, page 5, depending on your installation.
If the appliance is to be installed directly on carpeting, tile (other than ceramic), or any combustible material other than wood floor­ing, the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance. There are three holes on each side of the bottom of the unit where screws can be used to secure the unit to the floor.
4
106573
OWNER’S MANUAL
PRE-INSTALLATION PREPARATION
Continued
"
8
/
5
23
(600mm)
40
1
(1029mm)
/
2
Figure 7 - Rough Opening for Installing Peninsula Fireplace
Platform Must Be Solid, Flat, and Fully Supported
(1010mm)
40
1
(1029mm)
/
2
"
Figure 8 - Rough Opening for Installing Peninsula Fireplace on Platform
* As required by design as long as ceiling clearance is maintained.
"
8
/
5
23
(600mm)
39 3/4"
(1010mm)
Min.
43
1
(1098mm)
/4"
Figure 9 - Rough Opening for Installing See Thru Fireplace
"
39 3/4"
Min.
39 3/4"
(1010mm)
Min.
23
(600mm)
*
"
8
/
5
1" (25mm)
Dia. Hole
1"
(25mm)
3"
2" (51mm)
Dia. Hole
2"
(51mm)
3" (76mm)
(76mm)
Figure 10 - Hole Locations For Gas Line and Electric Wires for Peninsula and See Thru Fireplaces
10"
(254mm)
Square Min.
Height
Depends On
Installation
Figure 11 - Rough Opening for Installing Exterior Vent Terminal
Refer to Pages 8 through 14 for Horizontal and Vertical Installation Details
Vertical Height
Depends on
Installation
o
90
Elbow
o
45
Elbow
3
26
/8"
(670mm)
Horizontal
Length Depends
on Installation
Figure 12 - Vent Opening Height
GENERAL VENTING
These models are approved for use with Simpson Dura-Vent 6 5/8" direct-vent pipe components and terminations as well as both flex and rigid Vanguard vent components.
Your fireplace is approved to be vented either through the side wall, or vertically using the following guidelines:
• Only use Vanguard or Simpson Dura­V ent GS venting components or kits spe­cifically approved for this fireplace.
• Minimum clearance between vent pipes and combustible materials is 1" (25 mm), except where stated otherwise.
• Combustible material may be flush with the top front of fireplace with a maxi­mum thickness of 3/4".
• Do not recess venting terminals into a wall or siding.
• If installing on vinyl siding a vinyl sid­ing standoff must be used (see Figure 19, page 9).
• Install horizontal venting with a 1/4" rise for every 12" of run tow ard the ter­mination.
• You may paint the vent terminal with 450°F (232°C) heat-resistant paint to co­ordinate with the exterior finish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks, or utility buildings within 24" from the front of the termination cap.
• Do not locate termination cap where ex­cessive snow or ice build up may occur. Be sure to clear vent termination area af­ter snow falls to prev ent accidental block­age of venting system. When using sno w blowers, do not direct snow to wards vent termination area.
LOCATION OF VENT TERMINATION
When locating vent termination, it is impor­tant to observe the minimum clearances shown in Figure 13, page 6. You will avoid extra framing by positioning your fireplace against an already existing framing mem­ber. The sides of the fireplace may be posi­tioned directly against combustible walls.
*Check with local codes or with the current
CAN/CGA B149[.1 or .2] Installation Codes
for Canada or the USA Installations follow the current National Fuel Gas Code, ANS
Z223.1, also known as NFPA 54.
Continued
106573
5
®
DIRECT-VENT GAS FIREPLACE
EVDDVF36PN and EVDDVF36STN
GENERAL VENTING
D
E
V
B
L
F
V
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (305mm) minimum]
B = clearance to window or door that may be opened
[12 inches (305mm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(305mm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (610mm) from the
center-line of the terminal [18 inches (457mm) minimum] E = clearance to unventilated soffit [12 inches (305mm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within
36 inches (914mm) horizontally from the center-line of the regulator
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow
the current Note: Local codes or regulations may require different clearances
C
V
B
TERMINATION CAP
National Fuel Gas Code, ANS Z223.1
Continued
Fixed
Closed
Openable
V
Openable
B
AIR SUPPLY INLET
X
B
Fixed
Closed
B
J
V
A
X
I = clearance to service regulator vent outlet [*72 inches (1829mm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12 inches (305mm) minimum]
K = clearance to a mechanical air supply inlet [*72 inches (1829mm)
minimum]
L = † clearance above paved side-walk or a paved driveway located on
public property [*84 inches (2133mm) minimum] M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡] N = clearance above a roof shall extend a minimum of 24 inches (610mm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (457mm)
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
Outside Corner Recessed Location
N
H
V
G
G
GAS METER RESTRICTED AREA
I
M
V
(TERMINATION PROHIBITED)
N
G
V
G
X
K
V
A
A
Balcony with No Side Wall
G = Combustible 24" (610mm)
Noncombustible 18" (457mm)
V
G
V
A = 6" (152mm)
V
Balcony with Perpendicular Side Wall
H
V
Combustible & Noncombustible H = 24" (610mm) J = 20" (508mm)
Figure 13 - Minimum Clearances for Vent Terminations
B
J
B = 6" (152mm)
6
D
C
V
C = Maximum depth of 48" (1219mm) for
recessed location
D = Minimum width for back wall of
recessed location ­Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in
recessed location­Combustible - 6" (152mm) Noncombustible - 2" (51mm)
C
E
106573
OWNER’S MANUAL
VENTING INSTALLATION
WARNING: Read all instruc­tions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life. Operation of im­properly installed and maintained venting system could result in serious injury, property damage or loss of life.
WARNING: Seal all of the outer pipe connections with high tem­perature silicone (600°F/316° C) every time a vent connection is made. Before joining elbows and pipes, apply a small bead of high temperature silicone sealant (GE RTV 106/Loctite RTV 81585) to the outer section of male end of the elbow or pipe. High tempera­ture silicone must also be used to re-seal any connections after maintenance to venting system.
NOTICE: Failure to follow these instructions will void the warranty.
INSTALLATION PRECAUTIONS
Consult local building codes before begin­ning the installation. The installer must make sure to select the proper vent system for installation. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified installer or service person should install venting system. The installer must follow these safety rules:
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the war­ranty on your venting system:
• Installation of any damaged venting component
• Unauthorized modification of the vent­ing system
• Installation of any component part not manufactured or approved by DESA International
• Installation other than as instructed by these instructions
WARNING: This gas fireplace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning ap­pliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING: Horizontal sec­tions of this vent system require a minimum clearance of 2" from the top of the vent pipe and 1" minimum to the sides and bot­tom. Vertical sections of this sys­tem require a minimum of 1" clear­ance to combustible materials on all sides of the vent pipe.
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination It is important to select the proper length of
vent pipe for the type of termination you choose. It is also important to note the wall thickness.
For Horizontal Termination: Select the amount of vertical rise desired. The horizon­tal run of venting must have 1/4" rise for every 12" of run towards the termination.
WARNING: Never run the vent downward as this may cause ex­cessive temperatures which could cause a fire.
You may use one or two 90° elbows in this vent configuration. See Horizontal Termina- tion Configurations on pages 10 and 11.
For Vertical Termination: Measure the distance from the fireplace flue outlet to the ceiling. Add the ceiling thickness, the verti­cal rise in an attic or second story, and allow for sufficient vent height above the roofline.
You may use one or two 90° elbows in this vent configuration. See Vertical Termination Configurations on pages 13 and 14.
Note:
You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows.
For two-story applications, firestops are re­quired at each floor level. If an offset is needed in the attic, additional pipe and el­bows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase, below.
Your Vanguard direct-vent fireplace has been tested for a minimum 3' rise with a maximum 10" wall thickness. The maxi­mum horizontal run is 20' with 8' vertical rise (see Installation for Horizontal Termi- nation, page 8). The maximum vertical run is 30' (see Installation for Vertical Termina- tion, page 12).
It is very important that the venting system maintain its balance between the combus­tion air intake and the flue gas exhaust. Certain limitations apply to vent configura­tions and must be strictly followed.
Installing Vent System in a Chase
A chase is a vertical box-like structure built to enclose venting that runs along the out­side of a building. A chase is not required for such venting.
NOTICE: Treatment of firestops and construction of the chase may vary from building type to build­ing type. These instructions are not substitutes for the require­ments of local building codes. You must follow all local building codes.
Note:
When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially im­portant in cold climates. Minimum clear­ance between vent pipes and combustible materials such as insulation is 1".
After framing the chase (see Framing on pages 4 and 5) install the vent system by following the installation instructions.
Continued
106573
7
®
DIRECT-VENT GAS FIREPLACE
EVDDVF36PN and EVDDVF36STN
VENTING INSTALLATION
Continued
INSTALLATION FOR HORIZONTAL TERMINATION
1. Determine the route your horizontal venting will take. of the horizontal vent termination on the exterior wall must meet all local and national building codes and must not be easily blocked or obstructed.
Note:
The location
1' Minimum
90°
12" Minimum
WARNING: Do not recess vent
terminal into a wall or siding.
Snorkel terminations are available for terminations requiring a vertical rise on the exterior of the building (see Figures 14 and 15). Snorkel kit SVK is also available (see page 15). Follow the same installation procedures used for standard horizontal terminations. If installing the snorkel termination below grade (base­ment applications), you must provide proper drainage to prevent water from entering the snorkel termination (see Figure 15). Do not back fill around the snorkel termination.
2. Rigid vent pipes and fittings have spe­cial twist-lock connections. Assemble the desired combination of pipe and el­bows to the appliance adaptor with pipe seams oriented towards the wall or floor .
Twist-lock Procedure: The female ends of the pipes and fittings have four locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes and fit­tings. (All connections must be sealed with high temperature silicone sealant as specified in the second warning state­ment on page 7.) Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. See Figure 16, page 9. must be supported every three feet. Use wall straps for this purpose.
Flexible vent pipe must be installed with spacer springs every 12". See Figure 16, page 9. All connections must be clamped tightly and sealed with high temperature silicone sealant as specified in the sec­ond warning statement on page 7.
Note:
Horizontal runs of vent
Snorkel
45°
Figure 14 - Snorkel Termination
90°
1' Minimum
45°
Figure 15 - Snorkel Termination with Drainage Pipe
Snorkel
12" Minimum
Adequate Drainage
8
106573
OWNER’S MANUAL
VENTING INSTALLATION
Continued
3. Attach vent pipe assembly to the fire­place. Set fireplace in front of it’ s per­manent location to insure minimum clearances. Mark the wall for a 10" square hole (for noncombustible ma­terial such as masonry block or con­crete, a 7 1/2" diameter hole is accept­able). See Figure 17. The center of the hole should line up with the center­line of the horizontal rigid vent pipe. Cut a 10"x10" (254mm x 254mm) square hole through combustible ex­terior wall (7 1/2" [190mm] diameter hole if noncombustible). Frame as nec­essary (see Figure 17).
4" Clamp
Female Locking Lugs
Male Slots
7" Clamp
Spacer Spring
4" Flex Pipe
7" Flex Pipe
4. Apply a bead of non-hardening mastic around the outside edge of the vent cap. Position the vent cap in the center of the 7 1/2" or 10" hole on the exterior wall with the arrow on the vent cap pointing up. Insure proper clearance of 1" to combustibles is maintained. At­tach the vent cap with four wood screws supplied (see Figure 18).
Note
: Re­place the wood screws with appropri­ate fasteners for stucco, brick, concrete, or other types of siding.
WARNING: Do not recess vent termination in to any wall. This will cause a fire hazard.
For vinyl siding use vinyl siding stand­offs between vent cap and exterior w all. The vinyl siding standoff prevents ex­cessive heat from melting the vinyl sid­ing material. Bolt the vent cap to the standoff. Apply non-hardening mastic around outside edge of the standoff in­stead of the vent cap assembly. Use wood screws provided to attach the standoff. See Figure 19.
5. Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap (see Figure 20).
6. Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should be a minimum of 1 1/4". Apply silicone to the connection. Fasten all vent connec­tions with screws provided. Refer to Framing on pages 4 and 5 for instruc­tions on securing unit to framing or floor.
7. Slide the wall thimble against the inte­rior wall surface and attach with screws provided (see Figure 20).
Cut Vinyl Siding Away to Fit Standoff
Vinyl Siding Standoff
Wood Screw
Standoff
UP
Nut
Apply Mastic to All Four Sides
Figure 19 - Installing Vinyl Siding Standoff
Vent Cap
Bolt
Rigid Vent Pipe Flexible Vent Pipe
Figure 16 - Vent Pipe Connections
Vent Opening
Combustible Wall
10"
(254mm)
10"
(254mm)
(Framing
Vent Opening
Non-Combustible Wall
7 1/2"
(190mm)
Figure 17 - Vent Opening Requirements
106573
Detail)
Apply Mastic to All Four Sides
UP
Wood Screw
Vent Cap
Figure 18 - Installing Horizontal Vent Cap
9
Interior Wall Surface
Wall Thimble
Vent Cap (Horizontal Termination)
Figure 20 - Connecting Vent Cap with Horizontal Vent Pipe
Screw
Horizontal Vent Pipe
Continued