Desa EFS26NRA, VMH26NRB, VMH26PRB, EFS26PRA User Manual

UNVENTED (VENT-FREE) GAS
COMPACT CLASSIC HEARTH
OWNER’S OPERATION AND INSTALLATION MANUAL
Shown with optional cabinet mantel/hearth base accessory.
REMOTE-READY MODELS:
VMH26PRB, VMH26NRB, EFS26NRA, EFS26PRA
®
FIREPLACE
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, altera­tion, service, or maintenance can cause injury or prop­erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi­tional information consult a qualified installer, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation section on page 6 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
TABLE OF CONTENTS
Safety Information ............................................... 3
Product Identification .......................................... 4
Optional Remote Control Accessories ................5
Local Codes ........................................................ 5
Product Features ................................................ 5
Unpacking ........................................................... 5
Assembly ............................................................ 5
Air For Combustion and Ventilation ....................6
Installation ........................................................... 9
Operating Fireplace .......................................... 22
Inspecting Burners ............................................ 25
2
www.desatech.com 113110-01A
Cleaning and Maintenance ...............................26
Wiring Diagram .................................................27
Troubleshooting ................................................28
Specifications .................................................... 32
Replacement Parts ........................................... 33
Service Hints ..................................................... 33
T echnical Service.............................................. 33
Illustrated Parts Breakdown and Parts List ....... 34
Accessories.......................................................36
Warranty Information.......................... Back Cover
SAFETY INFORMATION
WARNING: This product con­tains and/or generates chemi­cals known to the State of Cali­fornia to cause cancer or birth defects, or other reproductive harm.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this fireplace. Im­proper use of this fireplace can cause serious injury or death from burns, fire, explosion, elec­trical shock, and carbon mon­oxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of car-
bon monoxide poisoning resemble the flu, with head­aches, dizziness, or nausea. If you have these signs, the fireplace may not be working properly. Get fr esh air at once! Have fireplace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/
LP gases are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warn­ings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Any change to this fireplace or its controls can be dangerous.
WARNING: Do not use a blower insert, heat exchanger in­sert, or other accessory not ap­proved for use with this fireplace.
Due to high temperatures, the appliance should be located out of traffic and away from furni­ture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Fireplace front and screen be­come very hot when running heater. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fire­place will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young chil­dren when they are in the room with fireplace. When using the hand-held remote accessory keep selector switch in the OFF position to prevent children from turning on burners with remote.
You must operate this fireplace with the fireplace screen in place. Make sure fireplace screen is closed before running fireplace.
Keep the appliance area clear and free from combustible ma­terials, gasoline, and other flam­mable vapors and liquids.
113110-01A
www.desatech.com
3
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appli­ance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) in­side any structure. Locate propane/LP supply tank(s) outdoors.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call
the fire department
4. This fireplace shall not be installed in a bath­room or bedroom.
5. Do not use this fireplace as a wood-burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. This fireplace is designed to be smokeless. If logs ever appear to smoke, turn off fireplace and call a qualified service person. ing initial operation, slight smoking could oc­cur due to log curing and fireplace burning manufacturing residues.
8. To prevent the creation of soot, follow the instructions in Cleaning and Maintenance, page 26.
9. Before using furniture polish, wax, carpet cleaner, or similar products, turn fireplace off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
10. This fireplace needs fresh air ventilation to run properly. This fireplace has an Oxygen Depletion Sensing (ODS) safety shutoff sys­tem. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Com- bustion and Ventilation, pages 6 through 8. If fireplace keeps shutting off, see Troubleshoot- ing, pages 28 through 31.
Note:
Dur-
11. Do not run fireplace
• where flammable liquids or vapors are used or stored.
• under dusty conditions.
12. Do not use this fireplace to cook food or burn paper or other objects.
13. Never place any objects in the fireplace or on logs.
14. Do not use fireplace if any part has been under water. Immediately call a qualified service tech­nician to inspect the room fireplace and to re­place any part of the control system and any gas control which has been under water.
15. Turn off and unplug fireplace and let cool be­fore servicing. Only a qualified service per­son should service and repair fireplace.
16. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
17. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
18. To prevent performance problems, do not use pro­pane/LP fuel tank of less than 100 lbs. capacity .
19. Provide adequate clearances around air openings.
PRODUCT
IDENTIFICATION
Fireplace Cabinet
N O
F
E
F
T
O
O M E R
Selector Switch (Optional)
Ignitor Button
Control Knob
Figure 1 - Vent-Free Compact Classic
Hearth® Fireplace
Screen
Logs
Remote Control (Optional)
4
www.desatech.com 113110-01A
OPTIONAL REMOTE
CONTROL ACCESSORIES
There are four optional remote controls that can be purchased separately:
• wall switch
• hand-held ON/OFF remote
• wall thermostat
• hand-held thermostat remote See Accessories, pages 36 and 37.
LOCAL CODES
Install and use fireplace with care. Follow all lo­cal codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI
Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
SAFETY PILOT
This fireplace has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room fireplaces. The ODS/pilot shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system re­quires no matches, batteries, or other sources to light fireplace.
UNPACKING
1. Remove fireplace and hood from carton. Log is wrapped and inside fireplace. Do not re­move at this time.
2. Remove all protective packaging applied to fireplace for shipment.
3. Make sure your fireplace includes one hard­ware packet.
4. Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
ASSEMBLY
WARNING: Always have branch support and screen in place before operating fireplace. This prevents excessive tem­peratures on fireplace surfaces.
WARNING: Failure to posi­tion the parts in accordance with these diagrams or failure to use only parts specifically approved with this fireplace may result in property damage or personal injury.
ASSEMBLING FIREPLACE
Tools Required:
• Phillips screwdriver
• 5/16" hex wrench
• slotted screwdriver
• scissors
1. Remove two screws that hold fireplace screen in place for shipping. These screws are located near top of screen. Discard screws. Lift fireplace screen up and pull out to remove. Set screen aside until installation has been completed.
2. Cut two plastic straps to remove the log from the firebox cavity.
3. An optional blower is available. See Acces- sories, pages 36 and 37. Install optional blower now. Follow installation instructions provided with blower or (see page 14).
Shoulder Screw
Burner Support With Log Locator Tabs
Screen
Branch Support
113110-01A
www.desatech.com
Figure 2 - Removing Screen
5
ASSEMBLY
Continued
4. Locate four black phillips sheet metal screws from the hardware packet.
5. Rotate hood as shown in Figure 3. Make sure hood tabs point toward fireplace.
6. Insert hood tabs between baffle and louvers (see Figure 3).
7. Gently rotate hood to upright position. Make sure hood tabs are behind louvers and hood is resting on firebox top (see Figure 3).
8. Align screw holes on hood with screw holes on firebox top.
9. Insert screws as shown in Figure 3. Tighten screws firmly.
Hood Tabs
Hood
Louver
Sheet Metal Screws
Figure 3 - Assembling Hood
Hood Tab
Firebox Top
Baffle
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This fireplace shall not be installed in a con­fined space or unusually tight construction unless provisions are provided for adequate com­bustion and ventilation air. Read the following instructions to in­sure proper fresh air for this and other fuel-burning appliances in your home.
Today’ s homes are built more ener gy efficient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy effi­cient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFP A 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three fol­lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 6 through 8 will help you
classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion and ven­tilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
6
www.desatech.com 113110-01A
AIR FOR COMBUSTION
AND VENTILATION
Continued
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 or less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors
c. caulking or sealants are applied to ar-
eas such as joints around window and door frames, between sole plates and floors, between wall-ceiling joints, be­tween wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of these three crite­ria, you must provide additional fresh air. See
Ventilation Air From Outdoor s
If your home does not meet all of the three criteria above, proceed to
Air Flow For Fireplace Location,
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined space as a space whose vol-
ume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space and an un­confined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all ap­pliances installed in that space. Rooms communi­cating directly with the space in which the appli­ances are installed*, through openings not fur­nished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills be­tween them.
-11
kg per pa-sec-m2)
and
, page 8
Determining Fresh-
below.
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will in-
stall fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft. (volume of space)
Example:
(width) x 8 ft. (ceiling height) = 1792 cu. ft. (vol­ume of space)
If additional ventilation to adjoining room is sup­plied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
.
Example:
35,840 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace _________ Btu/Hr Gas water heater* _________ Btu/Hr Gas furnace _________ Btu/Hr Vented gas heater _________ Btu/Hr Gas fireplace logs _________ Btu/Hr Other gas appliances* + ________ Btu/Hr Total = ________ Btu/Hr * Do not include direct-vent gas appliances. Di-
rect-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater _____________ Btu/Hr Vent-free fireplace _____________ Btu/Hr Total _____________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
________ ________
Example:
Space size 16 ft. (length) x 14 ft.
1792 cu. ft. (volume of space) x 20 =
30,000 10,000 40,000
Btu/Hr (maximum the space can support) Btu/Hr (actual amount of Btu/Hr used) 35,840 Btu/Hr (maximum the space
can support) 40,000 Btu/Hr (actual amount of
Btu/Hr used)
113110-01A
www.desatech.com
7
AIR FOR COMBUSTION
AND VENTILATION
Continued
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. Y ou must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an ad-
joining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.
B. V ent room directly to the outdoors. See Venti-
lation Air From Outdoors.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr
size makes room unconfined.
If the actual Btu/Hr used is less than the maxi­mum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
WARNING: If the area in which the fireplace may be op­erated is smaller than that de­fined as an unconfined space or if the building is of unusually tight construction, provide ad­equate combustion and ventila­tion air by one of the methods described in the
Gas Code, ANSI Z223.1/NFPA 54 Section 5.3
cal codes
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un­confined space. When ventilating to an adjoining unconfined space, you must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). Y ou can also remove door into adjoining room (see option 3, Figure 4). Follow the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of
ventilation grills or ducts.
.
National Fuel
or applicable lo-
12"
Ventilation Grills
Ventilation
Grills
into Adjoining
Room,
Option 1
Or Remove Door into Adjoining
Room,
Option 3
Into Adjoining Room,
12"
Option 2
Figure 4 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent open­ings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
Do not provide openings for inlet or outlet air into attic if attic has a thermostat-con­trolled power vent. Heated air entering the attic will activate the power vent.
Ventilated Attic
Crawl Space
Ventilated
To Attic
To
Crawl
Space
Outlet Air
Inlet Air
Outlet Air
Inlet Air
Figure 5 - Ventilation Air from Outdoors
8
www.desatech.com 113110-01A
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified ser­vice person must install fire­place. Follow all local codes.
WARNING: Never install the fireplace
• in a bathroom or bedroom
• in a recreational vehicle
• where curtains, furniture,
clothing, or other flammable objects are less than 36 inches from the front, top, or sides of the fireplace
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: This fireplace cre­ates warm air currents. These currents move heat to wall sur­faces next to fireplace. Install­ing fireplace next to vinyl or cloth wall coverings or operating fire­place where impurities (such as, but not limited to, tobacco smoke, aromatic candles, clean­ing fluids, oil or kerosene lamps, etc.) in the air exist, may dis­color walls or cause odors.
IMPORTANT:
the air. Although this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventilation, pages 6 through 8.
Note:
clearance installations. W all or framing material can be placed directly against any exterior surface on the rear, sides, or top of your fireplace, except where stand­off spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Note:
peting, tile or other combustible material, other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth of the fireplace.
Use the dimensions shown for rough openings to create the easiest installation (see Built-In Fire- place Installation, page 10).
Vent-free fireplaces add moisture to
Your fireplace is designed to be used in zero
When installing fireplace directly on car-
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If your gas supply is not correct, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
WARNING: This appliance is equipped for (natural or pro­pane/LP) gas. Field conversion is not permitted.
INSTALLATION ITEMS
Before installing fireplace, make sure you have the items listed below.
• external regulator (supplied by installer, for propane/LP units only)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection*
• ground joint union
• sediment trap
• tee joint
• pipe wrench
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, pages 36 and 37.
Note:
If desired, purchase a four-sided trim kit for built-in installations. See Accessories, pages 36 and 37.
113110-01A
www.desatech.com
9
INSTALLATION
Continued
FIREPLACE CLEARANCES
WARNING: Maintain the minimum clearances shown in Figure 6. If you can, provide greater clearances from floor, ceiling, and joining wall.
If your fireplace is to be used with an optional mantel, the installation instructions included with your mantel shows an CSA approved method of attaching the fireplace/mantel system to a wall.
IMPORTANT:
ner mantels specified in this manual. Purchase the optional mantel from your dealer (see Accesso- ries, pages 36 and 37).
If your fireplace is to be recessed into the wall, see Built-In Fireplace Installation to secure your fireplace into the wall.
fireplace in a home garage
• fireplace pilot and burner must
be at least 18 inches above floor.
• locate fireplace where moving
vehicle will not hit it.
For convenience and efficiency, install fireplace
• where there is easy access for operation, inspec­tion, and service
• in coldest part of room
An optional blower kit is available from your dealer. See Accessories, pages 36 and 37. If plan­ning to use blower, follow instructions provided with blower for power source.
Only use optional cabinet or cor-
CAUTION: If you install the
Example
Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabi-
net to any combustible material and wall should follow diagram in Figure 6.
Example: The face of a mantel, bookshelf, etc. is made of combustible material and pro­trudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fire­place opening (see Figure 6).
B. Clearances from the top of the fireplace
opening to the ceiling should not be less than 36 inches.
C. For mantel clearances, see Figure 10 on
page 12.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
Top Left and Bottom
Right Sides and Rear
36" 6" 0"
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves in­stalling fireplace into a framed-in enclosure. This makes the front of fireplace flush with wall. An optional trim kit accessory is available (see Ac- cessories, pages 36 and 37). Trim will extend past sides of fireplace approximately 1/2 inch. This will cover the rough edges of the wall opening. If in­stalling a built-in mantel above the fireplace, you must follow the clearances shown in Figure 10, page 12. Follow the instructions below to install the fireplace in this manner.
Actual Framing Height 26" 26 7/8" Front Width 26 3/4" 26 7/8" Depth 9 1/2" 10 1/2" Bottom 3/4" 3/4"
*Minimum 16 inches from Side Wall
Figure 6 - Minimum Clearance for
Combustible to Wall
10
1. Frame in rough opening. Use dimensions shown in Figure 7, page 11 for the rough opening. If installing in a corner, use dimensions shown in
*
www.desatech.com 113110-01A
Figure 8 for the rough opening. The height is 26 7/8" which is the same as the wall opening above.
INSTALLATION
Continued
2. If installing GA3450T blower accessory, do so at this time. Follow instructions included with blower accessory.
Note:
If not installing blower accessory, you may wish to run electrical wiring to your fire­place for future blower installation (see Ac- cessories, pages 36 and 37). Use only ap­proved three-wire electrical wiring.
Note:
A qualified installer should make all electrical connections.
WARNING: If pre-wiring, do not connect wiring to any elec­trical source at this time.
Install fireplace electrical outlet and connect wiring to outlet be­fore connecting to electrical source. The fireplace electrical outlet is included with the GA3450T blower accessory.
Only use the fireplace electrical outlet supplied with the GA3450T blower accessory.
3. Install gas piping to fireplace location. This installation includes an approved flexible gas line (if allowed by local codes) after the equip­ment shutoff valve. The flexible gas line must be the last item installed on the gas piping.
4. If you have not assembled firebox, follow in­structions beginning on page 5.
5. Carefully set fireplace in front of rough open­ing with back of fireplace inside wall opening.
6. Attach flexible gas line to fireplace gas regu­lator. See Connecting Fireplace to Gas Sup- ply, pages 17 and 18.
7. Bend four nailing flanges on outer casing with pliers (see Figure 9).
8. Attach fireplace to wall studs using nails or wood screws through holes in nailing flange.
9. Check all gas connections for leaks. See Checking Gas Connections, page 18.
10. If using optional trim kit, install the trim after final finishing and/or painting of wall. See instructions included with trim accessory for attaching trim.
IMPORTANT:
When finishing your firebox, com­bustible materials such as wall board, gypsum board, sheet rock, drywall, plywood, etc. may be butted up next to the sides and top edge of the firebox. Combustible materials should never over­lap the firebox front facing.
WARNING: Do not allow any combustible materials to over­lap the firebox front facing.
IMPORTANT:
brick, tile, etc. may overlap the front facing, but should never cover any necessary openings like louvered slots.
Noncombustible materials such as
Wall Studs
1
10
/
2
"
7
/
8
"
26
3/4" Off
7
26
/
8
"
The Floor Minimum
Figure 7 - Rough Opening for Installing
in Wall
5
36
/
8
"
7
/
8
"
26
3
/
4
"
51
7
/
8
"
25
Figure 8 - Rough Opening for Installing
in Corner
113110-01A
www.desatech.com
Nails or Wood Screws
Nailing Flanges
Figure 9 - Attaching Fireplace to Wall
Studs
11
INSTALLATION
Continued
WARNING: Do not allow non­combustible materials to cover any necessary openings like louvered slots.
WARNING: Never modify or cover the louvered slots on the front of the firebox.
WARNING: Use only noncom­bustible mortar or adhesives when overlapping the front facing with noncombustible facing material.
Mantel Clearances for Built-In Installation
If placing mantel above built-in fireplace, you must meet minimum clearance between mantel shelf and top of fireplace opening.
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the fire­box may become hot to the touch. If installed properly, these tem­peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
13"
16"
Mantel Shelf
21"
19"
Note:
All vertical measurements are from top of fireplace opening to bottom of mantel shelf. All measurements are in inches.
10" 8" 6" 2 1/2"
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one of the following:
• raise the mantel to an accept­able height
• remove the mantel
OPTIONAL MANTEL INSTALLATION
Note:
Refer to instructions provided with the man­tel for assembly instructions. Refer to the follow­ing instructions for system installation. Refer to instructions on page 5 for fireplace assembly. Blower accessory should be installed if it is being used (see Installing Optional Blower Accessory GA3450T, pages 13 through 15).
1. Unscrew four screws that attach top louver to
fireplace. Remove louver from fireplace and set aside (see Figure 11).
2. Place base assembly next to wall at installa-
tion location.
3. Place fireplace on wood base (see Figure 12,
page 13).
4. Place mantel around fireplace on base (see
Figure 12, page 13).
5. Assemble perimeter trim kit. See Assembling
Perimeter Trim, page 13.
6. Firmly snap perimeter trim kit on shoulder
screws. Shoulder screws are located on fire­place cabinet (see Figure 12, page 13).
7. Align perimeter trim kit for flush fit around
opening.
8. Center mantel left to right on base making sure
mantel is flush against wall.
9. Use two 3" wood screws provided and attach
base of fireplace to wooden mantel base (see Figure 12, page 13).
10. Remove perimeter trim kit and mantel. Be
careful not to damage wall or mantel.
Side of Firebox
Figure 10 - Minimum Mantel Clearances
12
for Built-In Installation
www.desatech.com 113110-01A
Upper Louver Assembly
Figure 11 - Removing Top Louver