Delta Electronics DOP-A-AE-AS User Manual

4 (2)
Delta Electronics DOP-A-AE-AS User Manual

www.delta.com.tw/industrialautomation

ASIA

Delta Electronics, Inc.

Taoyuan1

31-1, Xingbang Road, Guishan Industrial Zone,

Taoyuan County 33370, Taiwan, R.O.C.

TEL: 886-3-362-6301 / FAX: 886-3-362-7267

Delta Electronics (Jiang Su) Ltd.

Wujiang Plant3

1688 Jiangxing East Road,

Wujiang Economy Development Zone, Wujiang City, Jiang Su Province,

People's Republic of China (Post code: 215200) TEL: 86-512-6340-3008 / FAX: 86-769-6340-7290

Delta Electronics (Japan), Inc.

Tokyo Office

Delta Shibadaimon Building, 2-1-14 Shibadaimon,

Minato-Ku, Tokyo, 105-0012, Japan

TEL: 81-3-5733-1111 / FAX: 81-3-5733-1211

Delta Electronics (Korea), Inc.

Donghwa B/D 3F, 235-6, Nonhyun-dong,

Kangnam-gu, Seoul 135-010, Korea

TEL: 82-2-515-5303/5 / FAX: 82-2-515-5302

Delta Electronics (Singapore) Pte. Ltd.

8 Kaki Bukit Road 2, #04-18 Ruby Warehouse Complex, Singapore 417841

TEL: 65-6747-5155 / FAX: 65-6744-9228

AMERICA

Delta Products Corporation (USA)

Raleigh Office

P.O. Box 12173,5101 Davis Drive,

Research Triangle Park, NC 27709, U.S.A.

TEL: 1-919-767-3813 / FAX: 1-919-767-3939

EUROPE

Deltronics (The Netherlands) B.V.

Eindhoven Office

De Witbogt 15, 5652 AG Eindhoven, The Netherlands

TEL: 31-40-2592850 / FAX: 31-40-2592851

*We reserve the right to change the information in this manual without prior notice

20080122

Series

HMI Connection Manual

Manual Connection HMI Series

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

1.1Pin Definition of Serial Communication

DOP-A Series

 

 

 

 

 

 

 

COM1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIN

Mode

 

 

 

 

 

 

 

RS-232

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

N.C

 

 

 

 

Pin1

 

2

RXD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

TXD

 

 

 

 

 

 

 

4

N.C

 

 

 

 

 

 

 

5

GND

 

 

 

 

 

 

 

6

N.C

 

 

 

 

 

 

 

7

RTS

 

 

 

 

 

 

 

8

CTS

 

 

 

 

 

 

 

9

N.C

 

COM2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIN

 

Mode 1

Mode 2

 

Mode 3

 

 

 

 

RS-232

RS-422

 

RS-485

 

 

 

 

 

 

 

 

 

1

 

N.C

RXD-

 

D-

 

 

Pin1

2

 

RXD

RXD+

 

D+

 

 

 

3

 

TXD

TXD+

 

D+

 

 

 

4

 

N.C

TXD-

 

D-

 

 

 

5

 

GND

GND

 

GND

 

 

 

6

 

N.C

RTS-

 

N.C

 

 

 

7

 

RTS

RTS+

 

N.C

 

 

 

8

 

CTS

CTS+

 

N.C

 

 

 

9

 

N.C

CTS-

 

N.C

 

 

 

 

 

 

 

 

 

 

NOTE

1)Mode 3 is for RS-485. Pin 2 & 3 are D+ and pin 1 & 4 are D-.

2)Grounding is highly recommended if RS-485 & RS-422 are used for long transmission.

3)DO NOT connect Frame Ground (FGND) to GND. Please connect FGND to the outer covering of connector.

4)Transmission speed is relevant to distance and baud rate.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-1

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

DOP-AE Series COM1

 

PIN

Mode

 

RS-232

 

 

 

1

N.C

Pin1

2

RXD

 

 

3

TXD

 

4

N.C

 

5

GND

 

6

N.C

 

7

RTS

 

8

CTS

 

9

N.C

 

 

 

COM2/COM3

 

 

 

 

 

 

 

 

PIN

Mode 1

Mode 2

Mode 3

Mode 4

Mode 5

Mode 6

 

RS-232

RS-422

RS-485

RS-232x2 RS-422x2

RS-485x2

 

 

 

1

N.C

RXD-

D-

N.C

RXD-

D-

Pin1

2

RXD

RXD+

D+

RXD

RXD+

D+

COM2

3

TXD

TXD+

D+

TXD

TXD+

D+

 

4

N.C

TXD-

D-

N.C

TXD-

D-

 

5

GND

GND

GND

GND

GND

GND

 

6

N.C

RTS-

N.C

N.C

TXD-

D-

COM3

7

RTS

RTS+

N.C

TXD

TXD+

D+

 

8

CTS

CTS+

N.C

RXD

RXD+

D+

 

9

N.C

CTS-

N.C

N.C

RXD-

D-

1-2

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

DOP AS Series COM1/COM3

 

 

PIN

Mode 1

Mode 2

 

 

RS-232

RS-232x2

 

 

 

 

 

1

N.C

N.C

Pin1

 

2

RXD

RXD

 

COM 1

3

TXD

TXD

 

 

4

N.C

N.C

 

 

5

GND

GND

 

 

 

 

 

 

 

 

 

6

N.C

N.C

 

COM 3

7

RTS

TXD

 

 

8

CTS

RXD

 

 

9

N.C

N.C

 

 

 

 

 

COM2

 

PIN

Mode 1

Mode 2

 

 

 

 

RS-422

RS-485

 

 

 

 

 

 

 

R-

RXD-

D-

 

 

 

 

 

R+

RXD+

D+

 

 

 

 

 

T-

TXD-

D-

 

 

 

 

 

T+

TXD+

D+

 

 

 

 

 

 

GND

GND

 

 

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-3

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

1.2 Cable for Download

Download via COM Port

RS-232

DOP series HMI

 

 

PC

9 pin D-SUB male (RS-232)

9 pin D-SUB female (RS-232)

 

 

 

 

 

RXD (2)

 

 

(3)

TXD

 

 

TXD (3)

 

 

(2)

RXD

 

 

GND (5)

 

 

(5) GND

 

 

RTS (7)

 

 

(8) CTS

 

 

CTS (8)

 

 

(7) RTS

 

 

 

 

 

 

 

Controller

Pin1

Download via USB Flash Drive

USB Connection

1-4

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

1.3Supported Controllers and Devices

Please refer to the following table for supported controllers and devices provided by DOP series HMI.

Brand

Controller Name / Series Name

 

 

 

Delta Controller

Delta

For Servo/AC drive/Temperature Controller/PLC

(984 RTU mode / ASCII mode)

 

 

 

Delta DVP PLC

 

 

Allen Bradley

MicroLogix PLC

 

SLC5 PLC

 

 

 

Cimon

Loader Protocol

 

 

Copley

Servo (Stepnet Protocol)

 

 

Danfoss

VLT 2800 (FC Protocol)

 

 

Emerson

EC20 Series PLC

 

 

Facon

FB Series PLC

 

 

Festo

Festo PLC

 

 

GE Fanuc

90 Series SNP PLC

 

 

Hitachi

EH Series

 

 

Hust

Hust CNC Controller

 

 

Jetter

Nano Series PLC

 

JC Series PLC

 

 

 

Keyence

KV/KZ Series

 

 

Koyo

SU/DL Series

 

K-Sequence

 

 

 

Lenze

LECOM-A/B Protocol

 

 

 

Master-K120S/200S

 

 

LG

Glofa GM6 CNET

 

Master-K CNET

 

 

 

 

XGT CNET

 

 

LI YAN

LYPLC EX

 

 

M2i

M2i Master

 

M2i Slave

 

 

 

Matsushita

FP Series

 

 

Mirle

FAMA SC

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-5

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Brand

Controller Name / Series Name

 

 

 

 

FX / FX2N

 

 

 

 

FX3U

 

 

 

 

A Series/J71UC24

 

 

 

Mitsubishi

Mitsubishi A2A/A2AS/A2USH A1SH/A3N/A2ASH CPU Port

 

 

Q Series CPU Port

 

 

 

 

 

Q Series Computer Link

 

 

 

 

FX Series Computer Link

 

 

 

 

J2s Series

 

 

 

 

BY125

MKS

 

 

CT150

 

 

 

 

MC700/720

 

 

 

 

Modbus (Master) --- 984 RTU / ASCII mode

 

 

 

Modbus

Hexadecimal Address (Master) --- RTU / ASCII mode

 

 

nW (Master) --- RTU / ASCII mode

 

 

 

 

 

Modbus (Slave) --- RTU / ASCII mode

 

 

 

 

TSX Micro

Uni-Telway

Modicon

 

Modbus RTU

 

 

 

 

 

TWIDO

 

 

Moeller

Moeller PLC

 

 

NIKKI DENSO

NCS-FI/FS Series

 

 

 

C Series

Omron

 

CJ1/CS1 Series

 

 

 

TPM1A

 

 

 

S7 200

 

 

Siemens

S7-300 (with PC Adaptor)

 

 

 

S7-300 (without PC Adaptor)

 

 

Taian

TP02 PLC

 

 

Vigor

M Series

 

 

VIPA

VIPA PLC

 

 

Yokogawa

ACE PLC

 

 

 

1-6

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Delta (Servo/AC Drive/PLC/Temperature) Controller

Back to Table

A. HMI factory setting

Baud rate: ASCII: 9600, 7, None, 2.

RTU: 9600, 8. None, 2.

Controller station number: 1.

Control area/status area: None.

NOTE

1)This driver can support all Delta products, i.e. AC drive, PLC, Servo, Temperature Controller and Modbus standard connection. The users can easily set and communicate with these devices via using this driver.

2)For people who are using Modbus standard connection:

Modbus / ASCII (Master), Modbus / 984 RTU (Master), Modbus / ASCII Hex Address (Master) and Modbus / RTU Hex Address (Master) can be compatible with the new Delta controller ASCII and Delta controller RTU. To change the driver settings, the user only needs to change the “Controller” Option which is used to set the controller, then the new driver can be used immediately.

B. Definition of controller Read/Write address

Registers

Register Type

Format

Read/Write Range

Data Length

Word No.

 

Bit No.

 

 

 

 

Servo communication

SERVO-n

n: 0 ~ 0700h

N/A

 

Word

address

 

 

 

 

 

 

 

 

 

 

 

 

AC drive communication

INVERTER-n

n: 0 ~ 2299h

N/A

 

Word

address

 

 

 

 

 

 

 

 

 

 

 

 

TCntrl communication

TEMP_CTRL-n

n: 0 ~ 6000h

N/A

 

Word

address

 

 

 

 

 

 

WORD_DEVICE_X

PLC_Xn

n: 0 ~ 360(octal)

N/A

 

Word

 

 

 

 

 

 

WORD_DEVICE_Y

PLC_Yn

n: 0 ~ 360(octal)

N/A

 

Word

 

 

 

 

 

 

WORD_DEVICE_M

PLC_Mn

n: 0 ~ 1520,

N/A

 

Word

 

 

1536 ~ 4080

N/A

 

Word

 

 

 

 

 

 

WORD_DEVICE_S

PLC_Sn

n: 0 ~ 1008

N/A

 

Word

 

 

 

 

 

 

WORD_DEVICE_T

PLC_Tn

n: 0 ~ 255

N/A

 

Word

 

 

 

 

 

 

WORD_DEVICE_C

PLC_Cn

n: 0 ~ 199

N/A

 

Word

 

 

 

 

 

 

WORD_DEVICE_D

PLC_Dn

n: 0 ~ 4095,

N/A

 

Word

 

 

4096 ~ 9999

N/A

 

Word

 

 

 

 

 

 

WORD_DEVICE_HC

PLC_HCn

n: 200 ~ 255

N/A

 

Double Word

 

 

 

 

 

 

PLC communication

PLC_Modulen

n: 4000 ~ 4499h

N/A

 

Word

address Module

 

 

 

 

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-7

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Register Type

 

Format

 

Read/Write Range

Data Length

 

Word No.

 

Bit No.

 

 

 

 

 

Output Registers

RW-n

 

n: 0 ~ FFFFh

N/A

 

Word

 

 

 

 

 

 

 

Input Registers

R-n

 

n: 0 ~ FFFFh

N/A

 

Word

 

 

 

 

 

 

 

 

Output Registers

Wn

 

n: 40001

~ 50000

N/A

 

Word

 

 

 

 

 

 

 

 

Input Registers

Wn

 

n: 30001

~ 40000

N/A

 

Word

 

 

 

 

 

 

 

 

NOTE

1)The above addresses of Servo, AC drive, Temperature controller and PLC Module are in hexadecimal format. PLC Word Device X and Y are in octal format. Other PLC Word Device M, S, T, C, D and HC are in decimal format.

2)WORD_DEVICE_ X / WORD_DEVICE_Y / WORD_DEVICE_M / WORD_DEVICE_S: Address must be 0 or the multiple of 16.

Contacts

Contact type

Format

Read/Write Range

Word No.

 

Bit No.

 

 

 

Servo communication address

SERVO-n.b

n: 0 ~ 0700h

 

b: 0 ~ f

 

 

 

 

 

AC drive communication address

INVERTER-n.b

n: 0 ~ 2299h

 

b: 0 ~ f

 

 

 

 

 

TCntrl communication address

TEMP_CTRL-n.b

n: 0 ~ 6000h

 

b: 0 ~ f

 

 

 

 

 

Servo Digital Input

SERVO_DI-n

N/A

 

n: 1 ~ 8

 

 

 

 

 

Servo Digital Output

SERVO_DO-n

N/A

 

n: 1 ~ 5

 

 

 

 

 

WORD_DEVICE_X

PLC_Xn

N/A

 

n: 0 ~ 377(octal)

 

 

 

 

 

WORD_DEVICE_Y

PLC_Yn

N/A

 

n: 0 ~ 377(octal)

 

 

 

 

 

WORD_DEVICE_M

PLC_Mn

N/A

 

n: 0 ~ 1535

 

 

 

 

1536 ~ 4095

 

 

 

 

 

WORD_DEVICE_S

PLC_Sn

N/A

 

n: 0 ~ 1023

 

 

 

 

 

WORD_DEVICE_T

PLC_Tn

N/A

 

n: 0 ~ 255

 

 

 

 

 

WORD_DEVICE_C

PLC_Cn

N/A

 

n: 0 ~ 255

 

 

 

 

 

TCntrl Bit communication address

TEMP_CTRLB-n

N/A

 

n: 800 ~ 8FFh

 

 

 

 

 

Discrete Outputs

RWB-n

N/A

 

n: 0 ~ FFFFh

 

 

 

 

 

Discrete Inputs

RB-n

N/A

 

n: 0 ~ FFFFh

 

 

 

 

 

Discrete Outputs

Bn

N/A

 

n: 1 ~ 10000

 

 

 

 

 

Discrete Inputs

Bn

N/A

 

n: 10001 ~ 20000

 

 

 

 

 

NOTE

1)The above addresses of Servo, AC drive, Temperature controller and PLC Module are in hexadecimal format.

1-8

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

2)PLC Word Device X and Y are in octal format. Other PLC Word Device M, S, T, C, D and HC are in decimal format.

3)Servo Digital Input and Servo Digital Output are only for Servo.

Pay close attention to the following important notes:

4)For Delta AC drive:

Communication address for HMI read/write address uses hexadecimal format. For detailed information about communication address of Delta AC drive, please refer to Delta AC drive “User Manual”.

Example 1: Parameter 9-01 of Delta VFD-S drive Transmission Speed needs to be set to INVERTER901 in HMI. (Decimal 9 is converted to 09 in hexadecimal and 01 is converted to 01 in hexadecimal. Therefore, setting INVERTER901 to HMI will discard the first 0)

Decimal value

Hexadecimal value

01

09

(Hexadecimal value)

(Hexadecimal value)

The communication address of parameter 9-01 is 0901H.

Example 2: if setting of parameter 8-17 (Lower Bound of DC Braking Start-up Frequency) of Delta VFD- S drive is desired, user needs to set INVERTER811 in HMI. (8 is converted to 08 in hexadecimal and 17 is converted to 11 in hexadecimal. Therefore, setting the INVERTER811 to HMI will discard the first 0)

Decimal value

Hexadecimal value

11

08

(Hexadecimal value)

(Hexadecimal value)

The communication address of parameter 8-17 is 0811H.

5) For Delta Servo drive:

yHMI Read/Write address setting needs to input the communication address listed in SERVO “User Manual”.

yServo Digital Input and Servo Digital Output are only for Servo.

6)For Delta Temperature Controller (DTA series):

HMI can be set up to connect to several Delta A series temperature controllers on standard Modbus networks by using RTU transmission mode. However, the communication delay time may need to increase. Therefore, 5ms or longer is highly recommended.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-9

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

C. Connections (Connector Pinouts)

Delta Servo

RS-232

 

DOP Series

Controller

 

Controller

 

 

 

CN3 cable connector

 

 

9 pin D-SUB male (RS-232)

CN3 cable connector (RS-232)

 

 

 

 

(RS-232)

 

 

 

 

 

 

RXD (2)

 

 

(2) TX

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

3

5

TXD (3)

 

 

 

(4) RX

 

 

 

 

 

 

 

 

 

 

 

 

2

4

6

 

 

 

 

 

GND (5)

 

(1) GND

Top View

 

RS-422

DOP Series

 

Controller

 

Controller

 

CN3 cable connector

9 pin D-SUB male (RS-422)

CN3 cable connector (RS-422)

 

 

(RS-422)

 

 

 

 

 

 

 

RXD+ (2)

 

 

(5) TX+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RXD- (1)

 

 

(6) TX-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

3

5

 

 

TXD+ (3)

 

 

(3) RX+

 

 

 

 

 

 

 

 

 

2

 

 

 

4

6

 

 

TXD- (4)

 

 

(4) RX-

Top View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS-485

DOP Series

 

 

Controller

 

Controller

 

 

CN3 cable connector

9 pin D-SUB male (RS-485)

CN3 cable connector (RS-485)

 

 

(RS-485)

 

 

 

 

 

 

 

 

RXD+ (2)

(3) 485+

 

 

 

 

 

 

 

 

TXD+ (3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(5) 485+

 

1

3

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

RXD- (1)

(4) 485-

 

4

6

TXD- (4)

 

 

 

 

(6) 485-

Top View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-10

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Delta AC drive

RS-485

DOP Series

 

 

Controller

 

 

 

 

 

Controller

9 pin D-SUB male (RS-485)

RJ-11 cable connector (RS-485)

RJ-11 cable connector (RS-485)

RXD+ (2)

 

 

(4) SG+

 

 

 

 

 

2: GND

 

 

 

 

 

 

 

 

 

 

 

TXD+ (3)

 

 

 

 

 

 

 

 

3: SG-

 

 

 

 

 

 

 

 

4: SG+

 

 

 

 

 

 

 

 

 

 

 

RXD - (1)

 

 

 

1

 

 

 

 

6

 

 

 

 

 

(3 ) SG-

Top View

TXD- (4)

 

 

 

 

DO NOT use Pin 1, 5 and 6 while

GND (5)

 

 

 

 

(2) GND

 

 

 

using RS-485 communication.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE

1)When connecting to a Delta VFD-M series AC drive, please connect Pin 5 (GND) of the Delta HMI and Pin 2 (GND) of the Delta VFD-M AC drive.

Temperature Controller

RS-485

DOP Series

 

 

Controller

9 pin D-SUB male (RS-485)

 

 

RS-485 cable connector

RXD+ (2)

 

 

D+

 

 

TXD+ (3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RXD- (1)

 

 

 

TXD- (4)

 

 

 

 

D-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-11

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Delta DVP PLC Back to Table A. HMI factory settings

Baud rate: 9600, 7, Even, 1.

Controller station number: 1.

Control area/status area: D0 / D10.

B. Definition of controller Read/Write address

Registers

Register Type

 

Format

 

 

Read/Write Range

 

 

 

Word No.

Bit No.

 

 

 

 

 

X_Data

Xn

 

n: 0 ~ 360(octal)

N/A

 

 

 

 

 

Y_Data

Yn

 

n: 0 ~ 360(octal)

N/A

 

 

 

 

 

M_Data

Mn

 

n: 0 ~ 1520, 1536 ~ 4080

N/A

 

 

 

 

 

 

S_Data

Sn

 

n: 0 ~

1008

N/A

 

 

 

 

 

 

 

T_Register

Tn

 

n: 0

~

255

N/A

 

 

 

 

 

 

 

C_Register

Cn

 

n: 0

~

199

N/A

 

 

 

 

 

 

D_Register

Dn

 

n: 0

~ 4095, 4096 ~ 9999

N/A

 

 

 

 

 

HC_Register

Cn

 

n: 200 ~ 255

N/A

 

 

 

 

 

 

 

NOTE

1)(W) is “Word”.

2)(DW) is “Double Word”.

3)X_Data / Y_Data / M_Data / S_Data: Address must be 0 or the multiple of 16.

Contacts

Contact type

 

Format

Read/Write Range

 

Word No.

 

Bit No.

 

 

 

 

X_Data

Xn

 

N/A

n: 0

~ 377(octal)

 

 

 

 

 

 

Y_Data

Yn

 

N/A

n: 0

~ 377(octal)

 

 

 

 

 

 

M_Data

Mn

 

N/A

n: 0

~ 1520, 1536 ~ 4080

 

 

 

 

 

 

S_Data

Sn

 

N/A

n: 0

~ 1023

 

 

 

 

 

T_Coil

Tn

 

N/A

n: 0 ~ 255

 

 

 

 

 

C_Coil

Cn

 

N/A

n: 0 ~ 255

 

 

 

 

 

 

1-12

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

C. Connections (Connector Pinouts)

RS-232 Connection

DOP Series

Controller

Controller

9 pin D-SUB male (RS-232)

8 pin Mini DIN male (RS-232)

8 pin Mini DIN male (RS-232)

 

 

 

RXD (2)

 

 

 

(5) TXD

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TXD (3)

 

 

 

(4) RXD

5 4

 

 

 

 

 

 

GND (5)

 

 

 

(8) GND

8

 

 

 

 

 

 

 

 

Top View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS-485 Connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOP Series

 

 

 

 

 

 

Controller

 

 

 

9 pin D-SUB male (RS-485)

 

 

 

RS-485 cable connector

 

 

 

 

 

 

RXD+ (2)

 

 

 

 

 

 

D+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TXD+ (3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RXD - (1 )

 

 

 

 

 

 

D -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TXD- (4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-13

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

AllenBradley MicroLogix PLC Back to Table A. HMI factory setting

Baud rate: 19200, 8, None, 1.

PLC station number: 1.

Control area/status area: B3:0/B3:10.

B. Definition of controller Read/Write address

Registers

 

 

 

Read/Write Range

Register Type

Format

Word No.

 

 

Bit No.

 

Low Byte

 

High Byte

 

 

 

 

 

 

 

 

 

File No.

 

 

 

 

 

 

Output File

O:n

n: 0 ~ 3

 

N/A

 

0

 

 

 

 

 

 

 

Input File

I:n

n: 0 ~ 3

 

N/A

 

1

 

 

 

 

 

 

 

Status File

S2:n

n: 0 ~ 65

 

N/A

 

2

 

 

 

 

 

 

 

Bit File

B3:n

n: 0 ~ 255

 

N/A

 

3

 

 

 

 

 

 

 

Timer Flag

T4:n

n: 0 ~ 255

 

N/A

 

4

 

 

 

 

 

 

 

Timer Preset Value

T4:n.PRE

n: 0 ~ 255

 

N/A

 

4

 

 

 

 

 

 

 

Timer Accumulator Value

T4:n.ACC

n: 0 ~ 255

 

N/A

 

4

 

 

 

 

 

 

 

Counter Flag

C5:n

n: 0 ~ 255

 

N/A

 

5

 

 

 

 

 

 

 

Counter Preset Value

C5:n.PRE

n: 0 ~ 255

 

N/A

 

5

 

 

 

 

 

 

 

Counter Accumulator Value

C5:n.ACC

n: 0 ~ 255

 

N/A

 

5

 

 

 

 

 

 

 

Control File

R6:n

n: 0 ~ 255

 

N/A

 

6

 

 

 

 

 

 

 

Control Size of Bit Array

R6:n.LEN

n: 0 ~ 255

 

N/A

 

6

 

 

 

 

 

 

 

Control Reserved File

R6:n.POS

n: 0 ~ 255

 

N/A

 

6

 

 

 

 

 

 

 

Integer File

N7:n

n: 0 ~ 255

 

N/A

 

7

 

 

 

 

 

 

 

¾Bit No : Low byte is not used, so the value is 0. High byte stores file number.

¾Data Size : Word.

¾T4, C5 and R6 only read 1 Word once.

¾If reading multiple Words once, the communication speed of PLC will be slow.

NOTE

1)After last communication data has been memorized by PLC (PLC will send 0x10 0x05 consecutively), communication may fail. At this time, power off and power up HMI or power off and power up PLC once.

1-14

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Contacts

 

 

 

Read/Write Range

Contact Type

Format

Word No.

 

 

Bit No.

 

Low Byte

 

High Byte

 

 

 

 

 

 

 

 

Bits

 

File No.

Output

O:n/b

n: 0 ~ 3

 

b: 0 ~ 15

 

0

 

 

 

 

 

 

 

Input

I:n/b

n: 0 ~ 3

 

b: 0 ~ 15

 

1

 

 

 

 

 

 

 

Status

S2:n/b

n: 0 ~ 65

 

b: 0 ~ 15

 

2

 

 

 

 

 

 

 

Bit

B3:n/b

n: 0 ~ 255

 

b: 0 ~ 15

 

3

 

 

 

 

 

 

 

Timer

T4:n/b

n: 0 ~ 255

 

b: 0 ~ 15

 

4

 

T4:n/EN

n: 0 ~ 255

 

15

 

 

 

T4:n/TT

n: 0 ~ 255

 

14

 

 

 

T4:n/DN

n: 0 ~ 255

 

13

 

 

 

 

 

 

 

 

 

Timer Preset Value

T4:n.PRE/b

n: 0 ~ 255

 

b: 0 ~ 15

 

4

 

 

 

 

 

 

 

Timer Accumulator Value

T4:n.ACC/b

n: 0 ~ 255

 

b: 0 ~ 15

 

4

 

 

 

 

 

 

 

Counter flag

C5:n/b

n: 0 ~ 255

 

b: 0 ~ 15

 

5

 

C5:n/CU

n: 0 ~ 255

 

15

 

 

 

C5:n/CD

n: 0 ~ 255

 

14

 

 

 

C5:n/DN

n: 0 ~ 255

 

13

 

 

 

C5:n/OV

n: 0 ~ 255

 

12

 

 

 

C5:n/UN

n: 0 ~ 255

 

11

 

 

 

C5:n/UA

n: 0 ~ 255

 

10

 

 

 

 

 

 

 

 

 

Counter Preset Value

C5:n.PRE/b

n: 0 ~ 255

 

b: 0 ~ 15

 

5

 

 

 

 

 

 

 

Counter Accumulator Value

C5:n.ACC/b

n: 0 ~ 255

 

b: 0 ~ 15

 

5

 

 

 

 

 

 

 

Control

R6:n/b

n: 0 ~ 255

 

b: 0 ~ 15

 

6

 

R6:n/EN

n: 0 ~ 255

 

15

 

 

 

R6:n/DN

n: 0 ~ 255

 

13

 

 

 

R6:n/ER

n: 0 ~ 255

 

11

 

 

 

R6:n/UL

n: 0 ~ 255

 

10

 

 

 

R6:n/IN

n: 0 ~ 255

 

9

 

 

 

R6:n/FD

n: 0 ~ 255

 

8

 

 

 

 

 

 

 

 

 

Control Size of Bit Array

R6:n.LEN/b

n: 0 ~ 255

 

b: 0 ~ 15

 

6

 

 

 

 

 

 

 

Control Reserved

R6:n.POS/b

n: 0 ~ 255

 

b: 0 ~ 15

 

6

 

 

 

 

 

 

 

Integer

N7:n/b

n: 0 ~ 255

 

b: 0 ~ 15

 

7

 

 

 

 

 

 

 

¾Bit No : Low byte stores Bit address. High byte stores file number.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-15

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

C. Connections (Connector Pinouts)

RS-232 Connection

 

DOP Series

Controller

 

Controller

 

 

 

8 pin Mini DIN male

 

 

9 pin D-SUB male (RS-232)

8 pin Mini DIN male (RS-232)

 

 

 

 

(RS-232)

 

 

 

 

 

 

RXD (2)

 

 

 

 

(7) TXD

2 1

 

 

 

 

 

TXD (3)

 

 

 

 

(4) RXD

3

 

 

 

 

GND (5)

 

 

 

(2) GND

4

 

 

 

7

6

 

 

 

 

 

 

 

 

 

(3) RTS

 

 

 

 

 

 

 

 

(6) CTS

Top View

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-16

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

AllenBradley SLC5 PLC

Back to Table

A. HMI factory setting

Baud rate: 19200, 8, None, 1.

PLC station number: 1.

Control area/status area: B3:0/B3:10.

NOTE

1) Error Check uses CRC (Cyclical Redundancy Check).

B. Definition of controller Read/Write address

Registers

 

 

 

Read/Write Range

Register Type

Format

Word No.

 

 

Bit No.

Element No.

Low Byte

 

High Byte

 

 

 

 

 

 

 

Slot or File No.

 

 

 

 

 

Output File

O:n

n: 0 ~ 30

N/A

 

Slot No. s = 0

 

O:s.n

 

 

 

s: 0 ~ 255

 

 

 

 

 

File No. = 0

 

 

 

 

 

 

Input File

I:n

n: 0 ~ 30

N/A

 

Slot No. s = 0

 

I:s.n

 

 

 

s: 0 ~ 255

 

 

 

 

 

File No. = 1

 

 

 

 

 

 

Status File

S2:n

n: 0 ~ 255

N/A

 

File No. = 2

 

 

 

 

 

 

Bit File

Bf:n

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 3.

 

 

 

 

 

 

Timer Flag

Tf:n

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 4.

 

 

 

 

 

 

Timer Preset Value

Tf:n.PRE

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 4.

Timer Accumulator Value

Tf:n.ACC

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 4.

 

 

 

 

 

 

Counter Flag

Cf:n

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 5.

 

 

 

 

 

 

Counter Preset Value

Cf:n.PRE

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 5.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-17

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

 

 

 

Read/Write Range

Register Type

Format

Word No.

 

 

Bit No.

Element No.

Low Byte

 

High Byte

 

 

 

 

 

 

 

Slot or File No.

 

 

 

 

 

Counter Accumulator Value

Cf:n.ACC

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 5.

 

 

 

 

 

 

Control File

Rf:n

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 6.

Control Size of Bit Array

Rf:n.LEN

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 6.

 

 

 

 

 

 

Control Reserved File

Rf:n.POS

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 6.

 

 

 

 

 

 

Integer File

Nf:n

n: 0 ~ 255

N/A

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 7.

¾Bit No : Low byte is not used, so the value is 0. High byte stores file number.

Contacts

 

 

 

Read/Write Range

Contact Type

Format

Word No.

 

 

Bit No.

Element No.

Low Byte

 

High Byte

 

 

 

 

 

Bits

 

Slot or File No.

 

 

 

 

Output

O:n/b

n: 0 ~ 30

b: 0 ~ 15

Slot No. s = 0

 

O:s.n/b

 

 

 

s: 0 ~ 255

 

 

 

 

 

File No. = 0

 

 

 

 

 

 

Input

I:n/b

n: 0 ~ 30

b: 0 ~ 15

 

Slot No.

 

I:s.n/b

 

 

 

s = 0

 

 

 

 

 

s: 0 ~ 255

 

 

 

 

 

File No. = 1

 

 

 

 

 

 

Status

S2:n/b

n: 0 ~ 31

b: 0 ~ 15

 

2

 

 

 

 

 

 

Bit

Bf:n/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 3.

 

 

 

 

 

 

Timer

Tf:n/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

Tf:n/EN

n: 0 ~ 255

15

 

If f is ignored, file no. will be

 

 

default setting 4.

 

Tf:n/TT

n: 0 ~ 255

14

 

 

 

 

 

Tf:n/DN

n: 0 ~ 255

13

 

 

 

 

 

 

 

 

Timer Preset Value

Tf:n.PRE/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 4.

 

 

 

 

 

 

1-18

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

 

 

 

Read/Write Range

Contact Type

Format

Word No.

 

 

Bit No.

Element No.

Low Byte

 

High Byte

 

 

 

 

 

Bits

 

Slot or File No.

 

 

 

 

Timer Accumulator Value

Tf:n.ACC/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 4.

 

 

 

 

 

 

Counter Flag

Cf:n/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

Cf:n/CU

n: 0 ~ 255

15

 

If f is ignored, file no. will be

 

 

default setting 5.

 

Cf:n/CD

n: 0 ~ 255

14

 

 

 

 

 

Cf:n/DN

n: 0 ~ 255

13

 

 

 

Cf:n/OV

n: 0 ~ 255

12

 

 

 

Cf:n/UN

n: 0 ~ 255

11

 

 

 

Cf:n/UA

n: 0 ~ 255

10

 

 

 

 

 

 

 

 

Counter Preset Value

Cf:n.PRE/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 5.

Counter Accumulator Value

Cf:n.ACC/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 5.

 

 

 

 

 

 

Control

Rf:n/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

Rf:n/EN

n: 0 ~ 255

15

 

If f is ignored, file no. will be

 

 

default setting 6.

 

Rf:n/DN

n: 0 ~ 255

13

 

 

 

 

 

Rf:n/ER

n: 0 ~ 255

11

 

 

 

Rf:n/UL

n: 0 ~ 255

10

 

 

 

Rf:n/IN

n: 0 ~ 255

9

 

 

 

Rf:n/FD

n: 0 ~ 255

8

 

 

 

 

 

 

 

 

Control Size of Bit Array

Rf:n.LEN/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 6.

 

 

 

 

 

 

Control Reserved

Rf:n.POS/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 6.

Integer

Nf:n/b

n: 0 ~ 255

b: 0 ~ 15

 

f: 10 ~ 255

 

 

 

 

 

If f is ignored, file no. will be

 

 

 

 

 

default setting 7.

 

 

 

 

 

 

¾Bit No : Low byte stores Bit address. High byte stores file number.

NOTE

1) Device O and I need to assign Slot No. (s). If not assign Slot No., it will use default setting 0.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-19

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

C. Connections (Connector Pinouts)

RS-232

 

DOP series

Controller

 

Controller

 

 

 

9 pin D-SUB female

 

 

9 pin D-SUB male (RS-232)

9 pin D-SUB female (RS-232)

 

 

 

 

(RS-232)

 

 

 

 

 

 

RXD (2)

 

 

 

(3) TXD

Pin1

 

 

TXD (3)

 

 

(2) RXD

 

 

 

 

GND (5)

 

 

(5) SG

 

 

 

 

 

 

 

 

(7) RTS

 

 

 

 

 

(8) CTS

Top View

 

 

 

 

 

1-20

Revision January, 2008, Doc. Name: 2007PDD23000007

 

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Cimon PLC (Loader Protocol)

Back to Table

A. HMI factory setting

 

Baud rate: 38400, 8, None, 1, RS-232.

PLC station number: 1.

Control area/status area: D00000 / D00010.

B. Definition of controller Read/Write address

Registers

Register Type

 

Format

Read/Write Range

 

Data Length

 

Word No.

Bit No.

 

 

 

 

 

 

 

Input

Xn

 

n: 000-512

N/A

 

Word

 

 

 

 

 

 

 

 

Output

Yn

 

n: 000-512

N/A

 

Word

 

 

 

 

 

 

 

 

General Purpose Relay

Mn

 

n: 000-999

N/A

 

Word

 

 

 

 

 

 

 

 

General Purpose Relay

Ln

 

n: 000-999

N/A

 

Word

 

 

 

 

 

 

 

 

Latch Relay

Kn

 

n: 000-999

N/A

 

Word

 

 

 

 

 

 

 

 

Flags

Fn

 

n: 000-127

N/A

 

Word

 

 

 

 

 

 

 

 

Timer (Set)

TSn

 

n: 0000-4095

N/A

 

Word

 

 

 

 

 

 

 

 

Timer (Current)

TCn

 

n: 0000-4095

N/A

 

Word

 

 

 

 

 

 

 

 

Counter (Set)

CSn

 

n: 0000-4095

N/A

 

Word

 

 

 

 

 

 

 

 

Counter (Current)

CCn

 

n: 0000-4095

N/A

 

Word

 

 

 

 

 

 

 

 

General Purpose Word Data

Dn

 

n:00000-31999

N/A

 

Word

 

 

 

 

 

 

 

 

Step Controller

Sn

 

n: 0-99

N/A

 

Byte

 

 

 

 

 

 

 

 

Contacts

 

 

 

 

 

 

 

 

 

 

 

 

 

Contact Type

 

Format

Read/Write Range

 

 

 

Word No.

Bit No.

 

 

 

 

 

 

 

Input

Xnb

 

n: 000-512

b: 0-F

 

 

 

 

 

 

 

 

 

Output

Ynb

 

n: 000-512

b: 0-F

 

 

 

 

 

 

 

 

 

General Purpose Relay

Mnb

 

n: 000-999

b: 0-F

 

 

 

 

 

 

 

 

 

General Purpose Relay

Lnb

 

n: 000-999

b: 0-F

 

 

 

 

 

 

 

 

 

Latch Relay

Knb

 

n: 000-999

b: 0-F

 

 

 

 

 

 

 

 

 

Flags

Fnb

 

n: 000-127

b: 0-F

 

 

 

 

 

 

 

 

 

Timer Status

Tb

 

N/A

b: 0-4095

 

 

 

 

 

 

 

 

 

Counter Status

Cb

 

N/A

b: 0-4095

 

 

 

 

 

 

 

 

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-21

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

C. Connections (Connector Pinouts)

RS-232

 

DOP series

Controller

 

Controller

 

 

 

9 pin D-SUB female

 

 

9 pin D-SUB male (RS-232)

6 pin RJ11

 

 

 

 

(RS-232)

 

 

 

 

 

 

RXD (2 )

2

 

TXD (3)

3

1 ~ 6

GND (5)

5

Top View

 

 

NOTE

1)Device S

The unit of PLC internal memory is byte and Device S is read by the unit of byte. Therefore, we recommend the user do not use two consecutive devices S as the read addresses or the interference will occur. For example, when choosing two numeric input device, please use S24 and S26, do not use S24 and S25.

1-22

Revision January, 2008, Doc. Name: 2007PDD23000007

 

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Copley Servo (Stepnet Protocol)

Back to Table

A. HMI factory setting

 

Baud rate: 9600, 8, None, 1.

PLC station number: 0.

Control area/status area: None.

B. Definition of controller Read/Write address

Registers

Register Type

Format

Read/Write Range

 

Data Length

Word No.

Bit No.

 

 

 

 

 

 

RAM memory

Rn

n: 00-FF (Hex)

N/A

 

DWord

 

 

 

 

 

 

 

Flash memory

Fn

n: 00-FF (Hex)

N/A

 

DWord

 

 

 

 

 

 

 

Internal Register

IRn

n: 0-31

N/A

 

Word

 

 

 

 

 

 

 

Contacts

 

 

 

 

 

 

 

 

 

 

 

Contact Type

Format

Read/Write Range

 

 

Word No.

Bit No.

 

 

 

 

 

 

BIT_DEVICE_RB

RBn.b

n: 00-FF (Hex)

b: 0-31

 

 

 

 

 

 

 

 

BIT_DEVICE_FB

FBn.b

n: 00-FF (Hex)

b: 0-31

 

 

 

 

 

 

 

 

BIT_DEVICE_T0

T0n

N/A

n: 0

 

 

 

 

 

 

 

 

BIT_DEVICE_T1

T1n

N/A

n: 0

 

 

 

 

 

 

 

 

BIT_DEVICE_T2

T2n

N/A

n: 0

 

 

 

 

 

 

 

 

BIT_DEVICE_RST

RSTn

N/A

n: 0

 

 

 

 

 

 

 

 

BIT_DEVICE_CPR

CPRn

n: 00-FF (Hex)

N/A

 

 

 

 

 

 

 

 

BIT_DEVICE_CPF

CPFn

n: 00-FF (Hex)

N/A

 

 

 

 

 

 

 

 

 

NOTE

1)RB and FB are the bit access of Ram/Flash memory. Therefore, RB0x21.14 indicates bit 14 of Ram memory 0x21.

2)T0, T1 and T2 is virtual device for simulating Trajectory Generator Command. The number of 0, 1 and 2 indicates the subcommand of that command, so only bit 0 is acceptable.

3)RST is for simulating Reset Command, so only bit 0 is acceptable.

4)CPR and CPF are for simulating Copy Command of Ram and Flash individually. The address (n) after CPR and CPF is just the copy address for Ram/Flash memory. For example, CPRCA indicates that the content of Ram memory 0xCA will be copied into Flash memory 0xCA and CPFA6 indicates that the content of Flash memory 0xA6 will be copied into Ram memory 0xA6.

5)T0, T1, T2, RST, CPR, CPF are all write-only and they can not be used on Reset button.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-23

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

C. Connections (Connector Pinouts)

RS-232

DOP series

 

Controller

9 pin D-SUB male (RS-232)

 

9 pin D-SUB female (RS-232)

RXD (2 )

 

 

RS-232 TxD

 

 

TXD (3 )

 

 

RS-232 RxD

 

 

GND (5)

 

 

Signal Gro und

 

 

 

 

 

 

1-24

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Danfoss VLT 2800 (FC Protocol)

Back to Table

A. HMI factory setting

Baud rate: 9600, 8, Even, 1, RS-485.

PLC station number: 1.

Control area/status area: None / None.

NOTE

1)Delta HMI can be connected to for VLT-2800, 5000, 6000, 7000 controllers.

2)Each data length format of Danfoss AC drive parameter is not fixed, therefore, “Multiple Duplicate” function is not provided.

3)Max. supported alarm number is 16. If the alarm number is over 16, a fault will occur.

4)Does not support “optimum read/write” characteristic.

5)If the selected element is a string, the minimum data length should be more than 2.

B. Definition of controller Read/Write address

Registers

 

 

 

Read/Write Range

Register Type

Format

Word No.

 

 

Bit No.

Low Byte

 

High Byte

 

 

 

 

 

 

 

 

Index No.

Parameter

Pn:I

n: 0 ~ 999

0

 

I: 0 ~ 31

 

 

 

 

 

 

Control Word

CTRWD

0

N/A

 

N/A

 

 

 

 

 

 

Status Word

STAWD

0

N/A

 

N/A

 

 

 

 

 

 

¾Index No : If the index No. is not used, its default setting will be 0. The default setting of index No. for parameter P606 ~ P617 is 1.

¾Please notice that it is necessary to input the index No. when using some parameters of Danfoss controllers. At this time, please pay close attention on the setting range of index number. If the setting range is not started from 0, the parameter read & write failure will occur. For example, the index No. setting range of the parameter P615 is from 1 to 20, if the users do not input the index No., the system will assume the index number is 0 (default setting) and the a fault will occur when the users read or write the parameter.

¾CTRWD: Write-only. (Can not be used on the devices which can display the value or input value. It is recommended to be used on the setting value/setting constant (button), or marco function.)

¾STAWD: Read-only.

¾Control & Status Word: Please refer to the explanation on the next page.

Revision January, 2008, Doc. Name: 2007PDD23000007

1-25

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Contacts

 

 

 

Read/Write Range

Contact Type

Format

Word No.

 

 

Bit No.

Element No.

Low Byte

 

High Byte

 

 

 

 

 

Bits

 

Index No.

 

 

 

 

Parameter

Pn:I.b

n: 0 ~ 999

b: 0 ~ 31

 

I: 0 ~ 31

 

 

 

 

 

 

¾Bit No : Low byte stores Bit address. High byte stores index number.

C. Connections (Connector Pinouts)

 

RS-485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOP Series

 

 

 

 

 

 

Controller

 

 

 

 

9 pin D-SUB male (RS-485)

 

 

 

RS-485 cable connector

 

 

 

 

RXD+ (2)

 

 

 

 

 

 

68 TXD/RXD+

 

 

 

 

 

 

 

 

 

 

 

 

 

TXD+ (3 )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RXD - (1 )

 

 

 

 

 

 

69 TXD/RXD -

 

 

 

 

 

 

 

 

 

 

 

 

 

TXD- (4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shell

 

Shell

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Explanation of Control Word & Status Word

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Word

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

Bit = 0

 

Bit = 1

 

 

 

15

 

No Function

 

Reversing

 

 

 

14

 

Choice of Setup 2 (msb)

 

 

 

 

 

 

 

 

 

13

 

Choice of Setup 1 (lsb)

 

 

 

 

 

 

 

 

 

12

 

No Function

 

Relay 04 activated

 

 

11

 

No Function

 

Relay 01 activated

 

 

10

 

Data Not Vaild

 

Vaild

 

 

 

9

 

Ramp 1

 

Ramp2

 

 

 

8

 

Jog 1 OFF

 

ON

 

 

 

7

 

No Function

 

Reset

 

 

 

6

 

Ramp Stop

 

Start

 

 

 

5

 

Hold

 

Ramp Enable

 

 

 

4

 

Quick-Stop

 

Ramp

 

 

 

3

 

Coasting

 

Enable

 

 

 

2

 

DC Brake

 

Ramp

 

 

 

1

 

Preset reference choice msb

 

 

 

 

 

 

 

 

 

0

 

Preset reference choice msb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

¾When Bit 10 = 1 (Data Valid), the Control Word is valid.

1-26

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Status Word

Bit

Bit = 0

Bit = 1

15

Timer OK

Above limit

14

Torque OK

Above limit

13

Voltage OK

Above limit

12

Temperature OK

Over-Temp, auto-start pending

11

Not Running

Running

10

Out of Range

Frequency OK

9

Local Control

Bus Control

8

Speed ≠ reference

Speed = reference

7

No Warning

Warning

6

Reserved

 

5

Reserved

 

4

Reserved

 

3

No Fault

Trip

2

Coasting

Enabled

1

VLT not ready

Ready

0

Control not ready

Ready

 

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-27

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

Emerson EC20 Series PLC Back to Table A. HMI factory setting

Baud rate: 19200, 8, Even, 1 (RS-232).

PLC station number: 0.

Control area/status area: D0 / D10.

B. Definition of controller Read/Write address

Registers

Register Type

Format

Read/Write Range

 

Data Length

Word No.

Bit No.

 

 

 

 

 

 

Data Word

Dn

n: 0-7999

N/A

 

Word

 

 

 

 

 

 

 

Special Data Word

SDn

n: 0-255

N/A

 

Word

 

 

 

 

 

 

 

Data Word

Zn

n: 0-15

N/A

 

Word

 

 

 

 

 

 

 

Timer

Tn

n: 0-255

N/A

 

Word

 

 

 

 

 

 

 

Counter

Cn

n: 0-199

N/A

 

Word

 

 

 

 

 

 

 

DoubleWord Counter

CDWn

n: 200-255

N/A

 

DWord

 

 

 

 

 

 

 

DoubleWord Data Word

DDWn

n: 0-7998

N/A

 

DWord

 

 

 

 

 

 

 

Contacts

 

 

 

 

 

 

 

 

 

 

 

Contact Type

Format

Read/Write Range

 

 

Word No.

Bit No.

 

 

 

 

 

 

External Output Relay

Yb

N/A

b: 0-377(Octal)

 

 

 

 

 

 

External Input Relay

Xb

N/A

b: 0-377(Octal)

 

 

 

 

 

 

 

Internal Relay

Mb

N/A

b: 0-1999

 

 

 

 

 

 

 

 

Special Internal Relay

SMb

N/A

b: 0-255

 

 

 

 

 

 

 

 

Status Relay

Sb

N/A

b: 0-991

 

 

 

 

 

 

 

 

Timer

Tb

N/A

b: 0-255

 

 

 

 

 

 

 

 

Counter

Cb

N/A

b: 0-255

 

 

 

 

 

 

 

 

 

NOTE

PLC Communication Settings:

1)Emerson EC20 series PLC has two communication ports, COM0 and COM1. They are provided for the communication protocol for connecting to PC, Modbus communication protocol and user-defined protocol. The default setting is COM0 to be enabled only, so the user needs to set the communication mode as Modbus RTU via PC software before using it.

2)COM1 supports RS-232 and RS-485.

1-28

Revision January, 2008, Doc. Name: 2007PDD23000007

Delta DOP Series HMI Connection Manual|DOP-A/AE/AS Series

3)Please note that not all of the addresses can be written when reading SM and SD device. We recommend the user not to set all of the addresses as write address except when setting parameters.

C. Connections (Connector Pinouts)

RS-232

 

 

DOP series

 

 

Controller

 

 

9 pin D-SUB male (RS-232)

 

 

COM1

 

 

RXD (2 )

 

 

 

TXD

 

 

 

 

 

 

TXD (3 )

 

 

 

RXD

 

 

 

 

 

 

GND (5)

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RS-485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOP series

 

 

Controller

 

 

9 pin D-SUB male (RS-232)

 

 

COM1

 

 

D- (1)

 

 

 

 

(3) RS485+

 

 

 

 

 

 

 

D- (4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D+ (2)

 

 

 

 

(4) RS485-

 

 

 

 

 

 

 

D+ (3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G ND (5)

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision January, 2008, Doc. Name: 2007PDD23000007

1-29

Loading...
+ 107 hidden pages