DeLonghi CF-CP AR, CF-CP 30 ARE 290, CF-CP 40 ARE 290 User Manual

Page 1
CONTENTS
General recommendations 20
Basic safety rules 20
Recommendations 21
Range and accessories 21
Size and weight 22
Receiving the product 22
Quick connector 23
Connection of the units 23
Description of the air-conditioner 26
Technical data 28
Operating limits 28
Refrigerant circuits 29
Indoor unit multifilar wiring diagram
29
Outdoor unit multifilar wiring diagram
30
Indoor/outdoor unit wiring diagrams
30
Installation 31
Indoor unit installation 31
Outdoor unit installation 32
Condensate drainage 34
Routine maintenance 35
Extraordinary maintenance 35
User diagnostics 36
U I A
U I A
U I A
70°C
A
I
U
The following symbols have been used in some parts of this booklet and inside the appliance:
User
Installer
After-sales service
Attention
Forbidden
Danger: moving blades
Danger: high temperature
Danger: live parts
U I A
A
I A
I A
I A
U I A
I
I
I
I
I
A
A
I A
I A
I
I
I
I
AIU
COMPLIANCE
DECLARATION OF COMPLIANCE
The company:
DeLonghi S.p.A.
Via L. Seitz,47
31100 TREVISO ITALY
DECLARES
under its own responsibility that:
the AIR-CONDITIONERS
Range : CF-CP AR Models: CP 20 ARE 290
CF-CP 30 ARE 290 CF-CP 40 ARE 290
are in conformity with
• Low voltage Directive 73/23EEC,93/68 EEC,
• Electromagnetic compatibility Directive 89/336 EEC and 92/31EEC
AIU
Fire hazard
U I A
I A
U I A
I A
I A
Page 2
English
GENERAL RECOMMENDATIONS
BASIC SAFETY RULES
After having removed the packing, check that the con­tents are intact and complete.In the event of non-com-
pliance, contact the Agency which sold you the appliance.
appliances should be installed by a qualified company in accordance with the laws and regulations in force in the country of installation. Upon completion of work this company should issue the owner the declar
ation
of compliance of installation with current
regulations and standards and with the instructions given by in this booklet.
These appliances have been designed to heat or cool the air of rooms and should only be used for this pur­pose in compatibility with their performance characte­ristics.
Under no circumstances can be held liable for damage caused to property or injury to persons or animals due to incorrect installation, regulation and maintenance or to improper use.
Too low a temperature is harmful to health as well as being a useless waste of energy. Avoid prolonged direct contact with the flow of air. Avoid the room being closed for a long time. Periodically open the windows to ensure a correct change of air. During storms put the installation on/off switch to "off".
This instruction booklet is an integral part of the appliance and should therefore be carefully preserved and ALWAYS accompany the appliance, also in the event of transfer to another owner or user or into another installation. Should the booklet be damaged or lost, request a
copy from the Area Service Centre. Repair or maintenance work must be carried out by
the Service Centre or by qualified personnel in accordance with instructions given in this booklet. Do not alter or tamper with the appliance, since hazar­dous situations could be created and the manufacturer
of the appliance will not be liable for any damage or injury caused.
The unit should be installed in compliance with local installation and safety regulations.
For any repairs, contact only customer service centres authorised by the manufacturer. Repairs made by unauthorised personnel may be dangerous.
The CP20 ARE 290 air conditioner must be used and stored in rooms with a volume of over 31 cubic metres.
The CP30-CF30 ARE 290 air conditioner must be used and stored in rooms with a volume of over 53 cubic metres.
The CF40 ARE 290 air conditioner must be used and stored in rooms with a volume of over 53 cubic metres.
Non-ventilated environments where an appliance con­taining flammable refrigerant is used must be compati­ble, to avoid the possibility of a gas leak reaching a level of concentration such as to cause a fire or explo­sion resulting from the presence of other heat sources (electric heaters, stoves or similar units).
The R 290 refrigerant charge is highly flammable, and could cause an explosion in the event of leaks occur­ring in closed or poorly-ventilated areas. This gas is heavier than air and invisible, but it generates a mist if there is humidity in the air. Avoid contact of the liquefied gas with eyes or skin as it could cause injuries.
Transportation, charging, cleaning, recovery and dispo­sal of the refrigerant should be carried out only by customer service centres authorised by the manufactu­rer. Disposal of the appliance should be carried out only by specialised personnel authorised by the manufacturer.
Using electrically-operated products implies the observance of certain basic safety rules, such as those given below:
Children and unassisted handicapped persons are not allowed to use the air-conditioner. Do not touch the air-conditioner when barefoot or parts of the body are wet or damp. Do not carry out any cleaning operation until the air­conditioner has been disconnected from the mains electricity supply by putting the installation on/off swit­ch to "off". Do not alter the safety or regulating devices without the permission and instructions of the manufacturer of the air-conditioner. Do not pull, detach or twist the electric cables connec-
ted to the air-conditioner, even if disconnected from the mains electricity supply. Do not sit or stand on the appliance or rest anything at all on top of it. Do not spray or throw water directly onto the air-condi­tioner. Do not introduce sharp, pointed objects through the air intake or outlet grilles Do not access internal parts of the air-conditioner without having first put the on/off switch to "off". Do not leave the packing material (cardboard, staples, plastic bags, etc.) within reach of children, but dispose of properly since it is a potential source of danger.
AIU
AIU
Page 3
English
RECOMMENDATIONS
Extraordinary maintenance
Programmed maintenance always represents a saving in the running of the installation as well as preventing possible faults. To ensure trouble-free operation of the air-conditioner, it is recommended that it be inspected at least once a year, carrying out the following checks:
- cleanliness of the heat exchange coils of both units
Exposure control/personal protection
Use protective clothes and suitable gloves; protect eyes and face.
Handling
Avoid inhaling high concentrations of vapors. The atmospheric concentrations should be reduced to a minimum and kept below the professional exposure limit. The vapors are heavier than air and high concentrations may therefore form near to the ground, where general venti­lation is poor. Under such circumstances, ensure there is adequate ventilation. Avoid contact with naked flames and hot surfaces, otherwise irritating and toxic decomposition products could form. Avoid the liquid from coming into contact with eyes or skin.
Precautions to take in the event of accidental spillage
Ensure adequate personal protection (using protective breathing equipment) during elimination of spillage. If condi­tions are sufficiently safe, isolate the source of the leak.With small leaks or spills and provided there is adequate ventila­tion, let the material evaporate.With copious leaks or spills, adequately ventilate the area; keep the material from expan­ding using sand, earth or other suitable absorbent material. Prevent the liquid from entering into drains, sewers, cellars or work holes, since the vapors could create a suffocating atmosphere.
First aid measures Inhalation
- Remove the casualty from the area of exposure and keep him/her warm and still. Ask for immediate medical aid.
Contact with the skin
- Thaw the involved parts with water. Remove contamina­ted clothes, which could stick to the skin in the event of cold burns. In the event of contact with the skin, imme­diately rinse with abundant lukewarm water. Should there be symptoms of irritation or blisters, ask for medi­cal aid.
Contact with the eyes
- Bathe immediately with an eyewash solution or clean water, keeping the eyelids wide apart for at least ten minutes.Ask for medical aid.
Swallowing
- Do not provoke vomiting. If the casualty is conscious, make him/her rinse out his/her mouth with water and drink 200-300 ml of water. Ask for immediate medical aid.
Other medical care
- Symptomatic and back-up treatment as required. Do not administer adrenaline or similar sympathomimetic medi­cines following exposure, due to the risk of cardiac arrhythmia.
ATTENTION
For further information on the characteristics of the refrige­rant fluid, refer to the safety data sheets available c/o the refrigerant manufacturers.
spa cannot be held liable for any errors in this booklet and reserves the right to alter the specifications of its products without notice.
AIU
RANGE AND ACCESSORIES
AIU
Model Code
552626 20÷30 552929 20÷30 552632 20÷30 5572002700
552627 M
ACCESSORY
Condensate drainage pipe ø 16 - 50 m. Activated carbon filters (1 pc.) Wall bracket Gold Wall bracket Silver Condensate drain pump
Page 4
English
RECEIVING THE PRODUCT
SIZE AND WEIGHT
I
HANDLING
I
I
L
H
P
L
H
A
B
P
The air-conditioner comes in two packs protected by card­board packaging and is accompanied by:
- Instruction booklets for the user and the installer.
- Warranty certificate.
- Bar code labels.
- Supplied accessories, which are contained in a plastic bag to be found inside the indoor unit pack.
The instruction booklets are an integral part of the air­conditioner and should therefore be carefully read and preserved.
It is advisable to remove the packing only when the air­conditioner has been located in the point of installation.
Carefully remove the adhesive strips positioned on the air-conditioner
Packaging components must be disposed of correctly
and not left within reach of children since they are a potential source of danger.
The air-conditioner should be handled by suitably equipped personnel using equipment that is suitable for the weight of the appliance.
During transportation the outdoor unit must be kept in an UPRIGHT position.
INDOOR UNIT
OUTDOOR UNIT
Model 20 30 40
L 660 660 800 H 500 500 640 P 230 230 280 Weight 34 35 52 A 420 420 550 B 264 264 310
Model 20 30 40
L 810 810 967 H 300 300 300 P 195 195 195 Weight 9 9 11
Page 5
English
Components description
A. Liquid line (high pressure) B. Vapor (low pressure) C. Cover D. Electrical
Fig. 1Female Male
CONNECTION OF THE UNIT
I
QUICK CONNECTOR
I
BASIC OPERATION
The fast connector coupling uses a retractable sleeve and stem valve on the female half and a spring loaded poppet on the male side to create a safe, clean and quick
separation of split air condotioning system with minimal fluid loss and air inclusion (see Figure 1).
Page 6
CONNECTION OF THE UNIT
English
I
Fig. 2
Fig. 3 Fig. 4
TO CONNECT
- With the coupling handle in the full backposition (Figure
5), retract the release sleeve on the female and insert
the male half into the coupling. Make sure the inser tion tab on the male half lines up with the slot on the female
body (see
Figure 5).
- Realease the retractable sleeve to lock the halves together and tug gently on the halves to ensure locking has taken place (Figure 3).
- Rotate the coupling handle towards the male half to open the coupling. Make sure the handle bottoms on the
coupling body and the locking pin (on models equipped with spring loaded locking pins) popsinto the handle hole properly (see Figure 4).
- Connect the auxiliary electrical and condensate lines, if applicable.
- Connect the male and female caps together, if provided, to keep them clean while the unit is in operation and
they
are disconnected from their appropriate halves.
- Connect unit to power outlet and start the unit.
Fig. 5
No tools are required to connect the coupling: a retractable sleeve and four latch pins hold the male and female halves together. The coupling valves open when the handle is
pushed forward and locked into place, and shut when the handle is in the full backposition (see figures 3-4).
Page 7
English
TO DISCONNECT
- Shut off the air conditioning unit and unplug the unit from the power outlet.
- Wait five minutes for line pressures to equalize.
- Disconnect the auxiliar y electrical and condensate lines, if applicable.
- On couplings equipped with spring loaded locking pins, depress the pin until it clears the coupling handle is pulled up. When the handle clears the locking pin, pull coupling handle to its full backposition (see Figure 3).
- Retract the spring loaded release sleeve on the female and remove the male half (see Figure 5).
- Install the caps on both halves, if provided. Close the handle on female half after installing the cap.
DOS AND DON’T’S
- Thoroughly check the coupling for proper position of seal (see Figure 1), missing seals, leaking valves, debris, proper mounting, or other damage prior to reinstalling and restarting the air conditioner. Dont use a damaged coupling.
- Always keep the couplings connected even when the system is not in use in order to minimize refrigerant effusion, coupling damage and the entry of dirt or other foreign material. If it is not possible to keep the couplings connected, then both halves should be capped
immediatly upon disconnection with the optional caps as shows in Figures 6 & 7
.
- Dont tamper with the valves while disconnected or allow children access to disconnected couplings.
- Dont drop coupling half on any hard surfaces. The male half is made of brass and if allowed to drop may become d
amaged beyond the point where it can be reconnected. Installing caps immediatly after disconnection will minimize the possibility of damage if dropped.
- Do not open the coupling handle while the air conditioning unit is operating.After shutting off the air conditioning
unit, wait five minutes before opening the coupling in order to equalize line pressures. Opening the coupling during airconditioner operation may damage the compressor
.
Fig. 6
Fig. 7
CONNECTION OF THE UNIT
I
The length of the pipe connecting the internal unit to the external one is 4 m.
Page 8
English
DESCRIPTION OF THE AIR-CONDITIONER
AIU
The air-conditioner is an appliance designed for small user systems. It consists of an indoor unit for wall mounting and an outdoor unit.
REMOTE CONTROL
The infrared remote control is used for function control, re­gulation and programming; its operating modes and use are described in the user booklet.
INDOOR UNIT
The indoor unit housing is plastic. The electric fan unit consists of a tangential fan powered by
alternating current; it ensures high performance, efficiency and low noise operation. The speed may be changed according to needs. The heat exchanger has a large surface area and consists of scored copper pipes and swirl-type aluminium fins. Regulation, control of functions, data interchange with the outdoor unit and diagnostics are governed by a micropro­cessor card.
1 Wall-mounting plate 2 Indoor unit base 3 Indoor fan motor 4 Sensor unit 5 Room sensor support 6 Card support box 7 Noise filter 8 Fan capacitor + transformer 9 Electronic card 10 Cover 11 Mode push button 12 Cover 13 Sticker 14 Air filter
15 Air filter 16 Flaps motor l.h. shell 17 Flaps motor r.h.shell 18 Flap gear 19 Flap gear 20 Flap gear 21 Flap motor 22 Receiver-led card 23 Tamperproof grille 24 Fan support 25 Fixing angle bracket 26 Fan rubber grommet 27 Plastic fan bushing 28 Fan
29 Drain pipe 30 Finned coil 31 Flaps connecting rod/intermedia-
te control 32 Vertical flaps 33 Condensate collecting tray 34 Remote control 35 White cowl 36 Logo tab 37 Bushing 38 Bushing 39 Lower louver 40 Upper louver 41 Front grille
42 Strip 43 Bushing 44 Louver 45 Pipe fixing bracket 46 Quick male coupling 47 Connection tube
1
2
3
8
7
9
35
22
12
11
28
22
23
29
34
33
15
14
36
26
10
31
32
4
25
24
30
41
44
6
5
13
42
27
45
46
47
CF 20 ARE 290 / CF-CP 30 ARE 290 CF-CP 40 ARE 290
Page 9
English
115
116
130
128
126
122
121
101
127
125
106
118
104
117
107
108
102
113
134
114
129
112
103
105
131
124
123
111
100
120
119
109
110
111
132 133
OUTDOOR UNIT
The high efficiency sliding-vane compressor is on double vi­bration-isolation flexible mountings and is activated by an electric motor powered by alternating current and fitted with an overload cutout.
The electric fan unit consists of an axial flow fan in plastic and an electric motor powered by alternating current.
The large surface area exchange coil consists of scored copper pipes and aluminium fins. The air-conditioner is commanded and controlled by an electronic microprocessor system.
100 Right handle 101 Left handle 102 Filter 103 Fan breakaway starting capaci-
tor 104 Compressor 105 Compressor cap. 106 Compr.protection 107 Compr.gasket 108 Compr.cap 109 4-way valve coil 110 4-way valve 111 Pipe closing panel 111 Pipe closing panel + r.h.handle
112 Cable clamp 113 Compressor insulated cover 114 Compressor insulated cowl 115 Quick female coupling 116 Lower rubber plug 117 Upper rubber plug 118 Fan support 119 Fan flow nozzle 120 Back 121 Base 122 Metal foot 123 Vibration isolation foot 124 Finned coil 125 Plug
126 Condensate drainage union 127 Fan 128 Fan shock-absorber 129 Front 130 Front grille 131 Spring 132 Vibration-damping grommet 133 Insulating cowl
DESCRIPTION OF THE AIR-CONDITIONER
AIU
Page 10
Power supply
V/f/Hz
Cooling capacity Btu/h
W
Kcal/h Consumption W Current requirement A E.E.R. Dehumidifying l/h Heat output Btu/h
W
Kcal/h Consumption W Current requirement A C.O.P . Quantity of R290 refrigerant g
INDOOR UNIT
Air flow m
3
/h Sound level dB(A) Size: length mm
height mm depth mm
Indoor unit weight kg
OUTDOOR UNIT
Air flow m
3
/h Sound leve dB(A) Size: length mm
height mm depth mm
Outdoor unit weight kg
SPECIFICATIONS
Thermostat Timer Electronic defroster LCD remote control Microcomputer Electronic diagnostics Automatic night function Fan speed
English
OPERATING LIMITS
TECHNICAL DATA
AIU
Operating cycle Room air temperature External air temperature
MIN MAX MIN MAX
Cooling 21°C
d.b..16°C w.b. 32°C d.b./23°C w.b. -10°C d.b. 43° C d.b.
Heating
15°C d.b. 27°C d.b. -10°C w.b. 18°C w.b.
Performance is referred to the following conditions::
- Cooling indoor unit inlet air temperature 27°C d.b., 19°C w.b. external air temperature 35°C d.b., 24°C w.b.
- Heating indoor unit inlet air temperature 20 d.b., 15°C w.b. external air temperature 7°C d.b., 6°C w.b.
A
I
3 + silent
8013 12000 12000 17000 16320 2350 3520 3500 5000 4800 2025 3035 3020 4310 4137
740 1090 1050 1650 1570
3.9 5.7 5,7 7.6 7.6
3.18 3.23 3.20 3.03 3.0
1.3 1.5 1.5 2.2 1.9 8422 - 12000 - 19720 2470 - 3530 - 5800 2130 - 3030 - 5000
690 - 1055 - 1860
3.5 - 6 - 8.1
3.57 - 3.34 - 3.11 200 420 420 600 600
450 550 580 650 650
35 36 36 37 37
810 967 300 300 195 195
8991111
1350 1400 1600 2100 2500
445464647
660 800 500 640 230 280
35 35 35 51 52
CP 20
ARE 290
CF 30
ARE 290
CP 30
ARE 290
CF 40
ARE 290
CP 40
ARE 290
230/1/50
Page 11
English
REFRIGERANT CIRCUITS
Cooling
Heating/Cooling
HEATING
COOLING
Legend
Condenser
coil
Throttling part (capillary)
Quick coupling
General filter
Compressor
Reversing
valve
Check valve
Cooler coil
INDOOR UNIT MULTIFILAR WIRING DIAGRAM
LEGEND A1 = Unit power card A2 = Infrared receiver and leds card A3 = EMC noise filter BT1 = Room temperature sensor BT2 = Exchanger temperature sensor KA1 = Compressor relay M1 = Indoor fan motor M2 = Stepping motor for flap SB1 = Manual operation key TC1 = Transformer for card power supply XP1-XS1 = Transformer power supply connector XS2-XP2 = Motor M1 power supply connector XS3 = Quick connector XT1 = Power supply terminal board
A
I
A
I
FLAPSID1ID2
12VACSW IR
HALL
ST2 ST1
BLACK WHITE RED
BLUE PINK YELLOW ORANGE RED
123456
RED
GREEN
YELLOW
BLUE
VIOLET
VIOLET
VIOLET
VIOLET
VIOLET
BLUE
VIOLET
VIOLET
VIOLET
VIOLET
VIOLET
BLACK BLACK
BLUE
WHITE WHITE
3
2
1
1
2
3
1
2
3
4
5
6
7
8
9
BLUE
VIOLET
BLUE
VIOLET
BLUE
BLACK
BLACK
M2
TC1
A2
SB1
A1
BT2
BT1
WHITE
WHITE
M1
KA1
AUX 1
4 WAY
IN F
OUT F
L
L
L
L-FUS
PUMP
XT1
N32 1
3
2
1
1
2
3
BLUE
BLACK
BROWN
XP2
XS2
XS1
XP1
(1) BLUE
(3) BROWN
(2) BLACK
LINE
C
PT
+5V
OUT
SENSOR
RED
WHITE
BLACK
HALL
FAN MOTOR
POWER SUPPLY
1
3
2
4
A3
YE-GR
BROWN
BLUE
YE-GR
RED
BROWN
ORANGE
BLACK
BROWN
BLACK
BROWN
BROWN
BLUE BLUE
BLUE
YE-GR
XS3
Page 12
English
(1) Cooling only model
(2) Heat pump model
1 = Compressor power supply 2 = Fan motor power supply 3 = (1) N.C.(free) 3 = (2) Command line reversing valve N = Neutral
= Earth 6 = N.C. (free) 7 = N.C. (free)
XS1 = Female connector FR1 = Overload cutout (compressor)) Z1 = Compressor C1 = Compressor start and run capacitor M1 = Fan motor C2 = M1 capacitor start and run XT2 = Terminal board for earth YB1 = Reversing valve
INDOOR/OUTDOOR UNIT WIRING DIAGRAMS
OUTDOOR UNIT MULTIFILAR WIRING DIAGRAM
A
I
A
I
XS1
XT2
YB1
M1
C1
C
FR1
Z1
RS
C2
M
4
2
1
3
5
6
XS1
XT2
M1
C1
C
FR1
Z1
RS
C2
M
4
2
1
3
5
6
YB1
M1
XT2
C1C2
FR1
RS
C
BROWN
BLACK
BLACK
BLACK
BLACK
BLUE
BLACK
BROWN
YELLOW/GREEN
YELLOW/GREEN YELLOW/GREEN
BROWN
RED
Z1
XS1
M1
XT2
C1C2
FR1
RS
C
Z1
BROWN
YELLOW/GREEN
YELLOW/GREEN YELLOW/GREEN
BLUE
BLUE
BLACK
BLACK
RED
BLACK
BROWN
BROWN
4
2
1
3
5
6
XS1
4
2
1
3
6
5
1
3
6
4
2
5
N32
Unit interna
Unit esterna
1
Cooling/Heating
6-way female connector
(front view)
Indoor unit
Outdoor unit
Page 13
English
INSTALLATION
I
INSTALLATION OF THE INDOOR UNIT
I
;;
;;;;
;;;;;;
;;;
;
;
;
;;
;;;;;;;
;
;
;;;;;;;;
yy
yyyy
yyyyyy
yyy
y
y
y
yy
yyyyyyy
y
y
yyyyyyyy
;;
;;;;
;;
;;
;;
;;;;;;;
;
;;;;;;
;;;
;;;;;
;;
;
;
yy
yyyy
yy
yy
yy
yyyyyyy
y
yyyyyy
yyy
yyyyy
yy
y
y
;
;;;
;;
;
;;
;;;;;
;
;
;;;;;;;
;
;
;;;;;;;;;;;
;;;;
;;
y
yyy
yy
y
yy
yyyyy
y
y
yyyyyyy
y
y
yyyyyyyyyyy
yyyy
yy
50 mm
50 mm
50 mm
YES
NO
Recommended installation height is between 1.80 and 2.40 m from the ground.
The place of installation should be established by the instal­lation designer or by a technically competent person and should take into account technical requirements as well as relevant current laws and regulations, which envisage the obtaining of specific permits (e.g. town-planning, architectu­ral, fire, environmental pollution regulations, etc.); it is the­refore advisable to apply for and obtain the necessary per­mits prior to installing the air-conditioner.
The air-conditioner should be installed by a qualified com­pany in accordance with relevant laws and regulations in force in the country of installation.
Before commencing installation, establish the position of the indoor and the outdoor unit, taking into consideration the minimum technical spaces, maximum length of the refrige­rant lines and the difference in level between the applian­ces.
The indoor unit should be wall-mounted. It should be positioned so that the treated air may circulate freely throughout the whole room, while observing the mini-
mum spaces necessary for technical and maintenance ope­rations.
2
1
3
4
5
Water connections
Prior to installing the air-conditioner, decide the direction of the outlet pipes; they may be arranged in any of the five directions indicated in Fig.(8):
1. to rear right
2. to right
3. downwards
4. to left
5. to rear left
Positioning the fixing plate
- Remove the steel fixing plate on the unit back
- Rest the cardboard reference template, supplied in the kit, against the wall
- Position the steel fixing plate in the area outlined by the cardboard reference template
- Make sure the steel fixing plate is level, using a spirit level or a plumb line
- Secure the steel fixing plate using the 5 screw anchors and relative screws provided in the kit
- Should the refrigerant, electrical and condensate drainage lines exit from the rear in direction “1” or “5”, make the hole in the wall using a ø 68 mm bit, complying with the distances indicated in the figure to the side Fig. (9).
L
80 mm
86 mm
21 mm
H
102 mm
102 mm
A
B B
Steel plate
Overall dimensions
Cardboard template
Fig. 8
Fig. 9
Page 14
English
- The hole in the wall should be made sloping downwards in order to aid the natural flow of the condensate water, ob­serving the indications given in Fig.(11).
- Having completed all the operations for installing the steel fixing plate, remove the reference cardboard template.
- Position the pipes according to the direction required, ben­ding them properly in order not to cause kinks in the actual pipes.
- To position the pipes for directions “1” and “2” Fig.(10), they must be rotated to the required direction.
- Avoid bending the copper pipes several times in the same point, otherwise they could be damaged.
- Remove the unions and the rubber plugs from the indoor unit refrigerant circuit fittings only at the moment of con­necting to the outdoor unit.
- If the outlet direction is “2”, “3” or “4”, use a pair of pliers to remove the relative plastic knock-out on the unit.
Positioning the indoor unit on the steel fixing plate
After having connected the indoor unit to the outdoor unit connecting pipes, proceed as follows:
- Attach the indoor unit to the steel fixing plate by means of the relative slots on the back of the air-conditioner Fig.(12).
- Then press the indoor unit fir mly onto the fixing plate, en­suring that it is secured by the spring catch designed for the purpose.
For further safety, after having attached the indoor unit to the previously fixed steel plate, it is advisable to make another two holes in the wall and secure the unit using the spacers and the screws provided in the kit.To facilitate dril­ling operations, it is advisable to fix the unit onto the fixing plate, lift the front part and mark the drilling points on the wall through the relative holes.Fig.(13).
Attach here
Attach here
2 ~ 5 mm
Spacer
ø 6 mm screw anchors
Screw
The outdoor unit should be put in a position that guarantees the minimum space for sufficient air circulation and to allow maintenance work and the connections of electrical and re­frigerant circuit lines. It may be installed on a floor or flat roof or wall-mounted, provided its weight is properly supported and there is no transmission of vibration to the adjacent rooms.
It is advisable to avoid:
- installation in cavities or air vents;
- installation where obstacles or barriers could cause recir­culation of the expelled air;
- installation in places with an aggressive atmosphere;
- installation in confined places in which the sound level of
the outdoor unit could be increased by reverberation or re­sonance;
- installation in corners where dust, leaves or anything else usually collects, which could reduce the efficiency of the air-conditioner by obstructing the passage of air;
- installation in places where the air expelled by the outdoor unit could enter the inhabited rooms through windows or doors, thereby causing discomfort to those inside;
- installation in a place where the air expelled from the out­door unit is against a prevailing wind;
- installation in a place that is in direct sunlight.
2
1
3
4
5
INSTALLATION OF THE OUTDOOR UNIT
I
Fig. 10
Fig. 11
Fig. 12
Fig. 13
INSTALLATION OF THE INDOOR UNIT
I
Model 20 30 40
L 810 810 967 H 300 300 300 A524040 B 85 138 138
Page 15
English
Installation of the outdoor unit drain line (if available)
During operation in the heating mode, the condensate water may be drained from the outdoor unit through three drain holes.
Insert the drain male fitting into the hole where drainage of the condensate water is required and plug the remaining two holes using the plugs B supplied in the kit, as shown in Fig.(14).
FLOOR INSTALLATION
Installation on a floor or flat roof does not necessitate fixing the feet to the floor. The feet should instead be placed on supports (~70÷80 mm) to allow application of the conden­sate drain line (for units with heat pump only).
The minimum distances shown in the figure should be observed. Fig.(15).
SUSPENDED INSTALLATION
The minimum spaces indicated should be observed for suspended installation, which requires a support kit that must be ordered separately.
Carefully check the structure and the capacity load of the supporting wall. Fig.(16).
Fig. 14
Fig. 15
Fig. 16
100 mm
200 mm
100 mm
100 mm
A
B
C
D
INSTALLATION OF THE OUTOOR UNIT
I
Page 16
English
Installation place
Power supply cable
Pipework
Drain pipe
CONDENSATE DRAINAGE
I
The indoor unit is fitted with a condensate drain pipe, to which a drainage hose (ø inside 16 mm) should be connec­ted leading to a suitable drainage outlet.
- Fasten the condensate drain pipe to the refrigerant pipes with adhesive tape whenever the lines cross through a wall; this is to prevent the condensate drain pipes from being flattened. Fig.(17) - Fig.(18).
- In the summer mode of operation, check that the conden­sate is flowing out regularly.
The drainage pipe should have a 2° slope down towards the drain;it should never slope upwards.
Check all the joints for leaks.
Apply thermal insulating material to the joints. Fig.(19).
- The condensate drain pipe should be inserted onto the
coupling located on the bottom left part of the indoor unit.
;
;;
Drain pipe
Protection
Drain pipe extension
;
;;
y
yy
;
;
;;
;
;
;
;
;
;
y
y
yy
y
y
y
y
y
y
;
;
;
;
y
y
y
y
;
;
;
y
y
y
;
;
;
;;;;
;;;
;
;
;
y
y
y
yyyy
yyy
y
y
y
;
;;
y
yy
;
;
;
;
;;
;
y
y
y
y
yy
y
Insulating tape
Fig. 17
Fig. 18
Fig. 19
Page 17
English
ON
OFF
Periodic maintenance is essential for the safety, efficiency, reliability and long-life of the air-conditioner.
This may be periodically carried out by the Service Centre, which is technically prepared and also has original spare parts when necessary.
ROUTINE MAINTENANCE
AIU
EXTRAORDINARY MAINTENANCE
AI
;;
;;
yy
yy
Fig. 20
Do not carry out any cleaning operations until you have disconnected the air conditioner from the power supply by setting the systems main switch to OFF”.
CLEANING THE INDOOR UNIT
The appliance should be cleaned using a slightly damp cloth. Dry it with a dry cloth.
For safety reasons, do not use water to clean the air conditioner.
Caution Do not use gasoline, alcohol or solvents for cleaning. Do not spray insecticide or similar products on the unit.
CLEANING THE AIR FILTERS
To ensure the long life and efficiency of your air conditioner follow these instructions:
1. Clean the dust filter once a week.
2. Replace the purifying filter (if any) at the end of each
season, or when it is exhausted (follow the instructions
posted on the appliance next to the filter seat). The air purifying filters are located under the front intake grille. To clean the filters you need to:
1. Lift the front grille as shown in fig. 20.
2. Remove the purifying filter (black).
Remove the dust from the dust filter using a vacuum clea­ner. If there is a considerable amount of dust, wash with lukewarm water and rinse thoroughly. The water temperatu­re must not exceed 40°C.After washing, let the filter dry. To reinstall the filters, replace them in the filter holder, then reposition the latter in the machine.
SEASON CHECKS
- Before starting the appliance, make sure that the power
cord and outlet are in perfect condition and that the earthing/grounding system is efficient.
- Follow the installation instructions carefully.
Page 18
In the event of problems or failure, go through the following table. Should the problem persist, disconnect the air-condi­tioner from the mains electricity supply and contact the nea­rest Service Centre.
If the problem is not indicated in the table, please contact your installer.
Check the power supply
Power failure
Clean the filter
Clogged mesh filter
Remove obstruction
Air flow obstructed
Check
Contact between metal parts
Tighten screws
Loose screws
Check fan motor
Faulty fan
Check
Remote control regulation
Check
Faulty remote control or discharged batte­ries
Check the fuse on the electronic card
On/off switch on "off"
Put to "on”
Check
Faulty electronic card
PROBLEM CAUSE REMEDY
Insufficient output
Check (see user booklet)
General failure
Simultaneous blinking of indi­cator lights
Just wait 3' and the air-conditioner will start working again
Form of protection of the mechanism
The appliance does not work for about 3' upon starting
The fan does not operate
Noise and vibration
Room temp. sensor fault
Coil temp. sensor fault
Appliance empty
Condensate drain pump fault
High pressure switch fault
Fan fault
ON
OFF
ON ON
OFF
ON
OFF
ON ON
OFF
ON ON
OFF OFF OFF
ON ON ON
If there is an alarm, keep the MODE key on the indoor unit keyboard pressed down for about 4 sec. and wait for the acoustic signal, which is followed by the blinking of the leds
indicating the nature of the problem connected with the alarm.
USER DIAGNOSTICS
AIU
TROUBLESHOOTING
AIU