This document describes the requirements and wiring instructions for a –48 VDC power cable and safety
ground wire for systems equipped with a –48 VDC power supply.
CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit
to the earthing conductor at the equipment. See installation instructions.
This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the
earthing conductor at the equipment. If this connection is made, all of the following conditions must be met:
–This equipment shall be connected directly to the DC supply system earthing electrode conductor or to a
bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode
conductor is connected.
–This equipment shall be located in the same immediate area (such as, adjacent cabinets) as any other
equipment that has a connection between the earthed conductor of the same DC supply circuit and the
earthing conductor, and also the point of earthing of the DC system. The DC system shall not be earthed
elsewhere.
–The DC supply source shall be located within the same premises as this equipment.
–Switching or disconnecting devices shall not be in the earthed circuit conductor between the DC source and
the point of connection of the earthing electrode conductor.
CAUTION: A qualified electrician must perform all connections to DC power and safety grounds. The system
must be safety grounded at the cabinet frame. All electrical wiring must comply with applicable local or national
codes and practices.
CAUTION: The system chassis must be positively grounded to the rack cabinet frame.
power to the system until grounding cables are connected.
CAUTION: An energy hazard will exist if the safety ground cable is omitted or disconnected.
Do not attempt to connect
Precaution Statements
This product is intended for restricted access locations (dedicated equipment rooms, equipment closet,
or the like) in accordance with the National Electrical Code, American National Standards Institute
(ANSI)/National Fire Protection Association (NFPA) 70.
Wire the unit with copper only, unless otherwise specified, 10 American Wire Gauge (AWG) wire rated
minimum 90ºC in parallel for source and return. Protect the
overcurrent protection rated 30-A rated for DC with a high interrupt current rating.
Connect the equipment to a
grounded 48 VDC SELV source). Ensure that the
–48 VDC supply source that is electrically isolated from the AC source (reliably
–48 VDC source is efficiently secured to earth (ground).
A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the
field wiring.
CAUTION: When stranded wiring is required, use approved wiring termination, such as closed-loop or
spade-type with upturned lugs. These terminations should be the appropriate size for the wires and must be
double crimped, one on the conductor and one on the insulation.
CAUTION: When installing the unit, the ground connection must always be made first and disconnected last to
prevent an energy hazard.
Cabling Instructions for the –48 VDC Power Supply3
–48 V (1 wire) with a branch circuit
Page 6
CAUTION: Never defeat the ground conductor or operate the equipment in the absence of a suitably installed
ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain
that suitable grounding is available.
Input Requirements
Supply voltage: –(48–60) VDC
Current consumption:20 A maximum
Kit Contents
•Tyco 556879-3 connector housing (1) or equivalent
•Tyco 556880-2 connector contacts (3) or equivalent
•AMP 2-320568-2 ring-tongue terminal (1) or equivalent
•#8-32 nut equipped with lock washer (1)
Required Tools
•Wire-stripper pliers capable of removing insulation from size 10 AWG solid or stranded, insulated
copper wire
NOTE: Use alpha wire part #3080 or equivalent (65/30 stranding)
•One UL 1015 10 AWG, 2 m maximum (stranded) black wire (–48 VDC)
•One UL 1015 10 AWG, 2 m maximum (stranded) red wire (48 VDC return)
•One UL 1015 10 AWG, 2 m maximum green, stranded wire (optional connector ground)
•One UL 1015 10 AWG, 2 m maximum green/yellow, green with a yellow stripe, stranded wire
(safety ground)
•AMP 90871-1 hand-crimping tool or equivalent
4Cabling Instructions for the –48 VDC Power Supply
Page 7
Assembling the DC Input Power Cable
CAUTION: Before connecting safety ground or power cables to the connector, ensure that the power is removed
from the DC circuit. To ensure that the power is off, locate the circuit breaker on the DC source circuit. Switch the
circuit breaker to the off position and, if available, install an approved safety locking device to the circuit breaker
or switch, to prevent against another person energizing the circuit.
To construct the DC input power cable, perform the following steps:
Strip the insulation from the ends of the DC power wires, exposing approximately 4.5 mm
1
(0.175 inches) of copper wire.
2
Using a hand-crimping tool, crimp a connector contact to each DC power wire.
3
To connect the optional connector ground, insert the green 48 VDC ground into connector housing
position 1 (see Figure 1-1 and Table 1-1).
NOTICE: Figure 1-1 shows the connector housing and pin locations as viewed from the back of the connector.
4
Insert the black –48 VDC wire into connector housing position 2 (see Figure 1-1 and Table 1-1).
5
Insert the red 48 VDC return wire into connector housing position 3 (see Figure 1-1 and Table 1-1).
Figure 1-1. Tyco Connector 556879-3 Housing Positions (Viewed from Back of Connector)
1
Table 1-1. Connector Housing Pin Assignments
PinDescriptionWire Color and Size
148 VDC ground (optional)Green 10 AWG
2–48 VDC Black 10 AWG
348 VDC returnRed 10 AWG
2
3
Cabling Instructions for the –48 VDC Power Supply5
Page 8
Assembling and Connecting the Safety Ground Wire
1
Strip the insulation from the end of the green/yellow wire, exposing approximately 4.5 mm
(0.175 inches) of copper wire.
2
Using a hand-crimping tool, crimp the ring-tongue terminal to the green/yellow wire.
3
Connect the safety ground to the grounding post on the back of the system using a #8-32 nut
equipped with a locking washer (see Figure 1-2).