DeDietrich DIEMATIC 3, DIEMATIC 3 CH Installation Instructions Manual

Page 1
Installation instructions
M000666
300003765-02
DIEMATIC 3 - FM129 DIEMATIC 3 CH - FM133
Control panel
en
M000665
Page 2
2
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
Contents
1 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3 Installing the outside sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3.1 Positions to be avoided . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
3.2 Installing the outside sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4 Fitting the flow sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
5 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.1 Important recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.2 Type of connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.3 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
5.4 Terminal block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
5.5 Basic connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
5.6 Connecting circuit B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.7 Connecting the options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
5.8 Connection of a second domestic hot water tank. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
5.9 Pool connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.10 Connecting a pool and preparation for solar heated domestic hot water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
5.11 Connecting one or two circuits with mixer valve. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
5.12 Hot water storage tank connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5.13 Basic connections if the installation is in cascade and when connecting to a regulation DIEMATIC VM. . . . . . . . . . . . . . . . . . . . .17
6 Skeleton Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Page 3
3
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
1. Symbols used
1 Symbols used
Caution danger Risk of injury and damage to equipment. Attention must be paid to the warnings on safety of persons and equipment
Specific information Information must be kept in mind to maintain comfort
Z
Reference Refer to another manual or other pages in this instruction manual
DHW: Domestic hot water
2 General
Control panel assembly
Z
See: Boiler installation instructions.
Fitting the boiler sensor
Z
See: Boiler installation instructions.
Connection of the water circuit for domestic use
Z
See: Calorifier instructions.
Installing options
Z
See: Option instructions.
Parameter settings and installation configuration
Z
See: Control panel technical instructions.
Page 4
4
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
3 Installing the outside sensor
Choose a location:
- on one face of the area to be heated, on the north if possible
- under the influence of meteorological variations
- protected from direct sunlight
- easy to access
Z: Inhabited area controlled by the sensor
H: Inhabited height controlled by the sensor
A: recommended position on a corner
B: Possible position
3.1 Positions to be avoided
3.2 Installing the outside sensor
CB Ø 4 wood screw + Inserts (provided)
A
Page 5
5
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
4. Fitting the flow sensor
4 Fitting the flow sensor
Heating circuit with mixing valve
The flow sensor with connecting cable (length 2.5 m) and connector plug should be fitted to the outlet circuit pipe concerned and must be connected to the point provided in the control panel as shown hereafter.
The flow sensor after the valve must be positioned around 0.5 m after the 3 way valve or after the heating pump if this is fitted to the outlet.
- Cut the pipe insulation by 50 mm.
- At the point where the sensor is fitted, thoroughly clean the pipes (there must be no trace of paint) and coat them with the ready-to­use contact paste provided in the syringe.
- Secure the sensor with the collar provided for this purpose.
The flow sensor must not be covered by the insulation around the pipe.
Page 6
6
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
5 Electrical connections
5.1 Important recommendations
The power supply must be cut prior to any intervention on the heating installation (for example, via the appropriate fuse or a general switch)and any restart must be prevented.
Connections must be made by a qualified technician
Do not modify the connections inside the control panel.
All connections are made to the terminals on the control panel.
Separate the sensor cables from the 230 V cables. In the boiler: Use the boiler's 2 grommets: Use 2 cableways at least 10 cm apart.
Attach the cables to the cable clamps provided for this purpose.
GT 120
GT 220
5.2 Type of connection
For the 230 V electrical connections, use 3-wire cables with a cross­section of 1,5 mm².
Keep to the polarity shown on the terminals: phase (L), neutral (N) and earth (
4
).
5.3 General
Make the electrical connections of the appliance according to:
- The instructions of the prevailing standards,
- The instructions on the circuit diagrams provided with the appliance,
- The manufacturer's instructions.
Power the appliance via a circuit which includes a remote omnipolar switch with a gap of more than 3 mm. Earthing shall comply with standard NFC 15100 (France) or RGBT (Belgium).
The available output per outlet is 450 W (2 A, with cos ϕ = 0,7) and the inrush current must be lower than 16 A. If the charge exceeds one of these values, relay the command using a contactor (fitted outside the control panel).
230 V main supply For Switzerland: Power supply cable Supplied
Sensors
Cable clamps
Page 7
7
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
5. Electrical connections
5.4 Terminal block
State on delivery
6
-B
2 x
0,75 mm
2
mini.
1(A) All countries except Switzerland:
To connect the mixing valve PCB + sensor options - See: Instructions for option FM48, AD217
1(B) For Switzerland:
To connect the mixing valve PCB + sensor options - See: Instructions for option FM48, AD217
2 Boiler sensor
3 Boiler remote control input
4 Alarm output
5 Connecting the TELCOM vocal telesurveillance module
See chapter: Connecting the options
6 Flue gas thermostat
Page 8
8
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
5.5 Basic connections
For Switzerland: circuit B
Z
See next page
8575N576
Alim
230 V - 50 H z
N L
VA + CS
NL N L N L N L
AU AX
o o ooo ooo oo oo o
2 134
ooo
EU QIN
O H PELET SIALER
SIA LERNOHPEL
ET
YALER ENOH
PELE
T
ERIALOS
RALOS
RALOS
SEEMUF
H CUA
R
SA G EULF
ERIAILIXUA
ZTASUZ
Y RA
IL I X UA
C TI UC
RIC ECN
AIB
MA
C SIE
R K
M UA R
C T
IUCR
IC MOOR
B
TI UC RI
C EC
NAI
BM A
B
SIERK
M UAR
B TI UCR
IC MOOR
C TI U CRI
C TRAPED
C
S I
E R K F
UAL
RO V
C
TI UCR
IC WO
LF R
ETAW
ERI
A
IL I X UA EP
M OP
G N A GSUA
SF LIH
T U P TUO
Y RA
ILI XUA
EGR
AH C ED
E PMOP
EPM
UPED
ALRE
HCIEPS
PM UP D
AOL
R UETA
RELEC
CA
E PMU
P SGN
UZI E
H
P MUP
GNI TA E
H
ETI RUCE
S ED
TC
AT N
O C
T KAT
NOKS
TI E HREH
CIS
TC AT NOC Y
T E FAS
E MRA
LA T
NAY
OV
E T HCUE
L MRAL
A
ROT
ACI
DN I M
R A LA
zH05 V
0 32
N O
IT ATNEM
IL A
z H0
5 V
03
2 R
HUF
UZMOR
T S
zH05 V 032
YLPP
US N
IAM
A
T IUC
R
IC E
CNA
IBM
A
A
SIER
K M
UAR
B A TI
UC RIC MOOR
E RI
ATIN
AS E
DUA
HC UAE
RESSAWM
RA
W
RE TA
W T
O H C
ITSEMOD
E R ÈI
D UAHC
L ESSEK
R E LI
OB
RUEI
R E T X E
N E SSUA
LAN
R E TX
E
B T
I U C RI
C T RAPE
D
B SI
ERK
F UAL
R OV
B TIUC
R
IC
W O LF RETAW
oo
36 3538 37
oo
40 39
oo
S FS SOL S AUX S EXTS CHS ECS
S AMB
(C)
S DEP
(C)
S AMB
(B)
S DEP
(B)
S AMB
(A)
o o
OPTION - ZUBEHÖR
SONDE - FÜHLER - SENSOR
OPTION ­ZUBEHÖR
BUS DIEMATIC DIEMATIC BUS
12345VA67
(A)
8910111213141516
AUX
46 45 44 4348 4750 4952 5154 5356 5558 57 142495061626
3 x
0,75 mm
2
mini.
2 x
0,75 mm
2
mini.
2 x 0,75 mm
2
mini.
2 x
0,75 mm
2
mini.
3 x
0,75 mm
2
mini.
3 x 1,5 mm
2
mini.
ÉSOP
MI TNA
RUO
C A
EDON
A
E DONA
MOR
TSD
ME R
F
EDON
A T NERR
U C
D ESSERP
MI
TA
-A
1
2
34
5
6
7
8
9
10
11
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 Pump circuit A
5 D.H.W. load pump
6 DHW sensor
7 Titanium anode
8 Outside sensor
9 Boiler sensor
10 Boiler with or without accumulator
11 Boiler with accumulator
Page 9
9
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
5. Electrical connections
5.6 Connecting circuit B
Originally for Switzerland, FM48 option for other countries.
(1) If using a two-way motor
Connect open to terminal 23
2
, close to terminal 223 and neutral to
terminal 24 (N).
If using a thermal motor
Connect between terminal 23
2
(open) and terminal 2 (N).
(2) Safety thermostat
If using underfloor heating, it is imperative that a temperature limit of 50°C is installed and a safety thermostat set to 65°C (cf. NF P 52­303-1) is fitted, which interrupts the operation of the circulating pump in the circuit concerned should overheating occur.
Connect the safety thermostat wires to the 5 pin connector at the point marked TS(B) terminals 17-18 after removing the jumper from terminals 17-18.
If the safety thermostat is fitted with an earth wire, connect the thermostat to the earth terminal on pump 21.
mini.
2 x
MODE
+
-
1234567
024
6 8 10 12 141618 20 22
24
8575N394B
1
2
3
4
5
6
1 Remote control (circuit B) (package FM51 or FM52)
2 Flow sensor (circuit B)
3 3-way valve (circuit B)
4 Pump (circuit B)
5 Safety thermostat
6 Remove bridge
Page 10
10
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
5.7 Connecting the options
For example: Solar collector, TELCOM vocal telesurveillance module, remote controls for circuits A and B, flue gas sensor.
-A
1
2
3
4
5
6
7
8
9
10
10
11
12
13
14
15
16
17
18
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 Pump circuit A
5 DHW sensor (Package AD212)
6 Titan Active System® simulation connector
(package AD212)
7 Outside sensor
8 Boiler sensor
9 Outlet sensor
10 Interactive remote control (package FM51 or FM52)
11 Flue gas sensor
12 TELCOM voice remote monitoring module (depending on its
availability in your country)
13 Solar sensor probe
14 Boiler with or without accumulator
15 Boiler with accumulator
16 DHW sensor (Package AD160)
For connection of solar collectors: adjust the S.AUX parameter (# FITTER PARAM.) to SOLAR.
17 D.H.W. load pump
18 Solar load pump
Page 11
11
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
5. Electrical connections
5.8 Connection of a second domestic hot water tank
This connection is possible if circuit A is not used
If connecting a second DHW tank, use circuit A:
- set the CIRC.A parameter (#. INSTAL PARAM.) to DHW.
- Fit the sensor (package AD 212) into the second DHW tank.
- Connect the sensor to the S.AUX input.
- Adjust the TEMP.DHW A set temperature using the key
2%
40-
80°C range to obtain a domestic hot water calorifier type operation.
-A
1
2
3
4
5
6
7
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 DHW sensor (Package AD212)
5 D.H.W. load pump
6 Outside sensor
7 Boiler sensor
8 Boiler with or without accumulator
9 Boiler with accumulator
Page 12
12
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
5.9 Pool connection
This connection is possible if circuit A is not used
-A
1
2
3
4
5
6
7
8
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 Swimming pool sensor (Package AD212)
5 Pool secondary pump
6 Primary pump pool
7 Outside sensor
8 Boiler sensor
Page 13
13
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
5. Electrical connections
Controlling the pool circuit
The DIEMATIC 3 regulation can be used to control a pool circuit in
two different cases:
Case 1
The regulation DIEMATIC 3 regulates the primary circuit (boiler / exchanger) and the secondary circuit (exchanger / pool).
- Set the value of TPC D to the temperature which corresponds to the needs of the exchanger.
- Set the parameter S.AUX (#FITTER PARAM.) to SWIM.P.
- Set the parameter CIRC. A: (#FITTER PARAM.) to SWIM.P.
- Connect the primary circuit pump (boiler/exchanger) to the pump A outlet. The TPC J temperature is then maintained during programme A comfort periods in summer and in winter.
- Connect the pool sensor (package AD212) to the S.AUX: input.
- Set the value of the pool sensor using key
2%
in the range 0.5-
39°C or to FF (Frost Free).
- With an FF setting, the primary pump starts up and the secondary pump stays off if the installation's antifreeze function is activated.
Case 2
The pool has already a regulation system that is to be kept. The DIEMATIC 3 control unit only regulates the primary circuit (boiler/ exchanger).
- Set the value of TPC D to the temperature which corresponds to the needs of the exchanger.
- Set the CIRC.A parameter in #INSTAL PARAM. to POOL
- Connect the primary circuit pump (boiler/exchanger) to the pump A outlet. The TPC J temperature is then maintained during programme A comfort periods in summer and in winter.
Hourly programming of the secondary circuit pump
The secondary pump operates during programme A comfort periods in summer and winter alike.
Stopping
To prepare your pool for winter, consult your pool specialist.
Page 14
14
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
5.10 Connecting a pool and preparation for solar heated domestic hot water
This connection is possible if circuit A and either circuit B or C are not used.
-A
1
2
3
4
56
7
8
10
9
111213
14
Page 15
15
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
5. Electrical connections
Parameter settings
- Fit the mixing valve PCB + sensor option (Package FM 48)
- adjust the S. AUX parameter to SWIM. P.
- adjust the CIRC.A parameter to SWIM. P.
- adjust the CIRC.B parameter to SOLAR
5.11 Connecting one or two circuits with mixer valve
Z
To connect the mixing valve PCB + sensor options - See: Instructions for option FM48
For Switzerland:
1 PCB + sensor for a mixing valve is already prefitted to the control panel.
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 Primary pump pool
5 Pool secondary pump
6 Swimming pool sensor (Package AD212)
7 DHW sensor
8 DHW sensor (Package AD212)
9 D.H.W. load pump
10 Solar load pump
11 Outside sensor
12 Boiler sensor
13 Titan Active System® simulation connector
(package AD 212)
14 Solar sensor probe
Page 16
16
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
5.12 Hot water storage tank connection
The storage tank handles heating and DHW production.
Package AD160 contains 2 sensors:
- The sensor for the solar panel is used as a storage tank sensor
- The sensor for the storage tank is used as a DHW sensor
Parameter settings
Set the parameter STOR.T.SENS (#CONFIGURATION) to ON.
Operation
In DHW production:
Operation is the same as the normal operation. The boiler setting only is equal to the DHW setting +10 K. The heating load pump is off.
In heating mode:
The burner and the heating load pump:
-are off if the temperature of the storage tank is higher than the boiler setting.
-start up if the temperature of the storage tank falls below the boiler setting -6 K.
-A
1
2
3
4
5
6
7
8
9
10
11
12
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 Pump circuit A
5 Outside sensor
6 Boiler sensor
7 Titan Active System® simulation connector
(package AD212)
8 DHW sensor (Package AD212)
9 Hot water storage tank sensor (Package AD160)
10 Buffer tank
11 D.H.W. load pump
12 Heating load pump
Page 17
17
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
5. Electrical connections
5.13 Basic connections if the installation is in cascade and when connecting to a regulation
DIEMATIC VM
(Without option AD217)
5.13.1 Master boiler 1
(1)
The boiler can be connected to a boiler in cascade or to a
DIEMATIC VM using a BUS cable (package AD134 or DB119).
-A
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 Primary injection pump
5 D.H.W. load pump
6 Titan Active System® simulation connector
(package AD 212)
7 DHW sensor
8 D.H.W. loop back pump
9 Outside sensor
10 Boiler sensor
11 Boiler with or without accumulator
12 Boiler with accumulator
13
To the Diematic VM
(1)
regulation
14
To 2 secondary boiler
(1)
Page 18
18
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
5.13.2 Secondary boiler
-B
1
2
34
5
6
7
8
9
1 230 V main supply
2 Flue gas thermostat
3 Burner fault alarm light
4 Primary injection pump
5 Boiler sensor (Follower boiler)
6 Boiler with or without accumulator
7 From the previous cascade boiler
8 Not used
9 Boiler sensor on common output
Page 19
19
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
5. Electrical connections
5.13.3 Cascade
To construct the cascade, set the parameter CASCADE (#CONFIGURATION) on each boiler to 1 and 2 respectively.
Set the parameter CIRC. A: to PRIM.P. on boiler
.
The boilers switch over every 7 days.
If necessary, the startup of the secondary boiler is timed at 4 minutes.
1 Master boiler
2 Secondary boiler
3 Primary injection pump
4 Common outlet sensor to be connected to the S ECS input on boiler
5 Mixing valve and circulating pump
To connect the mixing valve PCB + sensor options, See: Instructions for option FM48
Page 20
20
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
6. Skeleton Diagrams
6 Skeleton Diagrams
Plan n° : 300008992-001-A
N
S3 T2 T1 L1B4
Ë
ËË
Ë
J1
1
J1
5
J1
2
J1
6
J1
3
J1
4
J3
1
J3
2
J3
3
J3
4
J3
5
J3
8
J3
7
J3
6
J3
9
J2
2
J2
1
J2
3
J2
4
J2
5
J3
10
CSÄ AUX
L
LL
LN
NN
N
VA
L
LL
LN
NN
N
Ä A
L
LL
LN
NN
N
Ä Ã
L
LL
LN
NN
N N
NN
NL
LL
L
RL PA
RL ECS
RL AUX
RL BR
S EXT
θ°
C
1
11
12
22
2
S CH
θ°
C
1
11
12
22
2
S ECS
θ°
C
1
11
12
22
2
S AMB A S DEP B
θ°
C
1
11
12
22
21
11
12
22
2
S AMB B
1
11
12
22
2
Ì Ì
1
11
12
22
23
33
34
44
4
Ì
S DEP C
θ°
C
1
11
12
22
2
S AMB C
1
11
12
22
2
S AUX
θ°
C
1
11
12
22
2
S SOL
θ°
C
1
11
12
22
2
S
FUMEE
θ°
C
1
11
12
22
2
0 2 4 6 8 1012141618202224
AUTO
ËÃ
ÀÈÁ Ä
A B C
A B CA B C
A B C
+-
T A
2a
2b
VA
3
2
1
θ
θθ
θ
TS
1a1
2a
2b
2
1a1b
1
ZM
ZG
2a
2
1a
1
TEST
STB
TEST
STB
2a 2b
2
1a 1b
1
ZT
ZT
å
åå
å å
åå
å
AUTO
AUTOAUTO
AUTO AUTO
AUTOAUTO
AUTO
Alim
230 V-50Hz
FA
24 V (RL)
+
-
+
-
Schéma de principe - Stromlaufplan - Principle diagram - Principeschema "DIEMATIC III"
Schéma de principe - Stromlaufplan - Principle diagram - Principeschema "DIEMATIC III"Schéma de principe - Stromlaufplan - Principle diagram - Principeschema "DIEMATIC III"
Schéma de principe - Stromlaufplan - Principle diagram - Principeschema "DIEMATIC III"
DJ 6A
TEST SCHAKELAARTEST SWITCHZT
MANUEL SCHAKELAARMANUAL MODE SWI TCHZM
ALGEMENE SCHAKELAARMAIN SWITCHZG
ALARM LAMPJEALARM INDICATORVA
VEILIGHEIDSTHERMOSTAATSAFETY THERMOSTATTS
KETELTHERMOSTAATBOILER THERMOSTATTCH
CORROSIEBESCHERMINGSANODEELECTRIC ANODET A
SOLAR VOELERSSOLAR SENSORS SOL
ROOKGASSEN VOELERSSMOKE SENSORS FUMEE
BUITEN VOELERSOUTSIDE SENSORS EXT
SANITAIR WARM WATER VOELERSDOMESTIC HOT WATER SENSORS ECS
VERTREVOELERFLOW SENSORS DEP
KETEL VOELERSBO ILER SENSORS CH
VACUUM VOELERSAUXILIARY SENSORS AUX
RUIMTEVOELERROOM SENSORS AMB
VERWARMINGSPOMPE RELAISHEATING PUMP CONT ROL RELAYRL PA
RELAIS STURING LAADPOMPLOAD PUMP CONTROL RE LAYRL ECS
BRANDER RELAISBURNER CONTROL RELAYRL BR
AFZONDERINGSKLEP RE LAISAUXILIARY PUMP CONTROL RELAYRL AUX
NULLEIDERNEUTRALN
FASEPHASEL
AANSLUITKLEMPRINTED CIRCUIT B OARD PLUGJ.
TELEFONISCH RELA ISTELEPHONE RELAYÌ
ONSTORINGS-FILTEREMI SUPPRESSORFA
BRANDERBURNERË
THERMISCHE BEVEILIGINGCIRCUIT BREAKERDJ6A
VEILIGHEIDSCONTACT SAFETY CONTACTCS
HULPUITGANGPOMPAUXILIARY PUMPÄ AUX
LAADPOMPLOAD PUMPÄ Ã
VERWARMINGSPOMP KRING AHEATING PUMP CIRCUIT AÄ A
TESTSCHALTERINTERRUPTEUR TESTZT
UMSCHALTER FÜR HANDBETRIEBINTERRUPTEUR MANUELZM
HAUPTSCHALTERINTERR UPTEUR GENERALZG
ALARMLEUCHTEVOYANT ALARME
VA
SICHERHEITSTEMPERATURBEGRENZERTHERMOSTAT DE SE CURITETS
KESSEL TEMPERATURREGLERTHERMOSTAT DE CHAUDIERETCH
FREMDSTROMANODEANODE A COURANT IMPOSET A
SOLAR FÜHLERSONDE SO LAIRES SOL
ABGASFÜHLERSONDE FUMEES FUMEE
AUSSENFÜHLERSONDE EXTERIEURES EXT
WARMWASSERFÜHLERSONDE EAU CHAUDE SANI TAIRES ECS
VORLAUFFÜHLERSONDE DE DEPARTS DEP
KESSELFÜHLERSONDE CHAUDIERES CH
FÜHLER ZUSATZSONDE AUXILLIAIRES AUX
RAUMFÜHLERSONDE D' AMBIANCES AMB
HEIZUNGSPUMPE STEUERRELAISRELAIS DE COMMANDE ACCEL ERATEURRL PA
SPEICHERLADEPUMPE STEUERRELAISRELAIS DE COMMANDE POMPE DE
CHARGE
RL ECS
BRENNER STEUERRELAISRELAIS DE COMMANDE BR ULEURRL BR
ZUSATZPUMPE STEUERRELAISRELAIS DE COMMANDE POMPE
AUXILIAIRE
RL AUX
NULLEITERNEUTREN
PHASEPHASEL
LEITERPLATTE STECKERCONNECTEUR CIRCUIT IMPRIMEJ.
FERNSPRECHRELAISRELAIS TELEPHONIQUEÌ
FUNKENENSTÖRUNGSFI LTERFILTRE ANTIPARASITEFA
BRENNERBRULEURË
LEISTUNGSSCHALT ERDISJO NCTEURDJ6A
SICHERHEITSKONTAKTCONTACT DE SECURITECS
ZUSATZPUMPEPOMPE AUXILIAIREÄ AUX
SPEICHERLADEPUMPEPOMPE DE CHARGEÄ Ã
KESSELKREISPUMPE KREIS AACCELERATEUR CIRCUIT AÄ A
TCH
Page 21
21
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
6. Skeleton Diagrams
Page 22
22
DIEMATIC 3 - GT 120 / 220 27/11/2015 - 300003765-02
6. Skeleton Diagrams
Page 23
23
27/11/2015 - 300003765-02 DIEMATIC 3 - GT 120 / 220
6. Skeleton Diagrams
Page 24
© Copyright
All technical and technological information contained in these technical instructions, as well as any drawings and technical descriptions supplied, remain our property and shall not be multiplied without our prior consent in writing.
Subject to alterations.
27/11/2015
DE DIETRICH THERMIQUE 57, rue de la Gare F- 67580 MERTZWILLER - BP 30
DUEDI S.r.l.
DE DIETRICH SERVICE
BDR Thermea (Czech republic) s.r.o
www.duediclima.it
www.dedietrich.cz
Distributore Ufficiale Esclusivo
De Dietrich-Thermique Italia
www.dedietrich-heiztechnik.com
Freecall 0800 / 201608
Jeseniova 2770/56
130 00 Praha 3
+49 (0)25 72 / 9161-0
+49 (0)25 72 / 9161-102
info@remeha.de
Via Passatore, 12 - 12010 San Defendente di Cervasca CUNEO
+39 0171 857170 +39 0171 687875 info@duediclima.it
+420 271 001 627 dedietrich@bdrthermea.cz
IT
DE DIETRICH THERMIQUE S.A.S
DE DIETRICH THERMIQUE Iberia S.L.U.
www.dedietrich-calefaccion.es
C/Salvador Espriu, 11
08908 L’HOSPITALET de LLOBREGAT
+34 935 475 850 info@dedietrich-calefaccion.es
ES
129164, Ɋɨɫɫɢɹɝ. Ɇɨɫɤɜɚ
Ɂɭɛɚɪɟɜɩɟɪɟɭɥɨɤɞ
Ȼɢɡɧɟɫɰɟɧɬɪ©ɑɚɣɤɚɉɥɚɡɚª
ɨɮɢɫ
+7 (495) 221-31-51
CZ
info@dedietrich.ru
AD001-AM
300003765- 001- 02
Loading...