This uninterruptible power supply (UPS) controller
UB10.241 is an addition to standard 24V power
supplies to bridge power failures or voltage
fluctuations. Expensive downtimes, long restart
cycles and loss of data can be avoided.
The DC-UPS includes a professional battery
managem
the battery to achieve the longest battery service life
as well as many diagnostic functions that ensure a
reliable operation of the entire system.
A unique feature of the UB10.241 is that only one
1
2V battery is required to buffer the 24V output.
This makes matching batteries unnecessary and
allows a precise battery charging and testing.
The UB10.241 requires one exte
which two preassembled battery modules are
available. A lightweight 7Ah battery which can be
mounted on the DIN-Rail and a 26Ah module that
can be panel mounted for longer buffer times.
In addition to the UB10.241, the UBC10.241 UPS
inc
ludes the same controller with an integrated 5Ah
battery.
ent system which charges and monitors
rnal 12V battery for
UB10.241
DC-UPSCONTROL UNIT
■ Requires Only One 12V Battery for a 24V Output
■ Stable Output Voltage in Buffer Mode
■ Superior Battery Management for Longest Battery Life
■ Comprehensive Diagnostic and Monitoring Functions
■ Replace Battery Signal Included
■ Electronically Overload and Short Circuit Protected
■ 50% Power Reserves
■ Selectable Buffer Time Limiter
■ 3 Year Warranty
2. SHORT-FORM DATA
Input voltage nom. 24Vdc
range 22.5-30Vdc
Output current min.15A Normal mode
min. 10A Buffer mode
Output voltage typ. 0.23V lower
s input voltage
a
22.25V Buffer mode, 10A
Allowed batteries 3.9Ah to 40Ah VRLA lead acid
Temperature range -25 to +70°C Operational
The unit shall only be installed and put into operation by qualified personnel.
This unit is designed for installation in an enc
office, communication, and instrumentation equipment. Do not use this device in aircraft, trains and nuclear
equipment, where malfunctioning of the power supply may cause severe personal injury or threaten human life.
losure and is intended for general use, such as in industrial control,
TERMINOLOGY AND ABREVIATIONS
DC-UPS Uninterruptible power supply with DC-Input.
Normal mode Describes a condition where the battery is charged, the input voltage is in range and the output is
loaded within the allowed limits.
Buffer mode Describes a condition where the input voltage is below the transfer threshold level, the unit is
running on battery (buffering) and the output is loaded within the allowed limits.
Charging mode Describes a condition where the battery is being charged, the input voltage is in range and the
output is loaded within the allowed limits.
Inhibit mode De
Buffer time Same a
T.b.d. To be defined, value or description will follow later.
scribes a condition where buffering is disabled on purpose by using the inhibit input of the DC-
UPS. (e.g. for service actions, or to save battery capacity)
s the term “hold-up time”.
DISCLAIMER
The information presented in this document is believed to be accurate and reliable and may change without notice.
Some parts of this unit are patent by PULS (US patent No 091662,063, Des. 424,529, …).
No part of this document may be reproduced or utilized in any form without permission in writing from the publisher.
2/23
Page 3
UB10.241
5. INPUT
Input voltage nom. DC 24V
Input voltage ranges nom. 22.5 to 30Vdc Continuous operation, see Fig. 5-1
30 to 35Vdc Temporarily allowed, no damage to the DC-UPS *)
Allowed input voltage ripple max. 1.5Vpp Bandwidth <400Hz
1Vpp Bandwidth 400Hz to 1kHz
Allowed voltage between input
and earth (ground)
Turn-on voltage
max. 23Vdc
Input current **) typ. 120mA Internal current consumption
typ. 1.1A Current consumption for battery charging in constant
External capacitors on the input
*) The DC-UPS shows “Check Wiring” with the red LED and buffering is not possible
**) The total input current is the sum of the output current, th
charging process and the current which is needed to supply the DC-UPS itself. See also Fig. 5-2. This calculation does not apply
in overloa
***) Please note: This is the input current and not the current which flows into the battery during charging. The battery current ca
be found in chapter
d situations where the DC-UPS limits the output current, therefore see
8.
Fig. 5-1 Input voltage range Fig. 5-2 Input current, definitions
V
OUT
D
AB
35Vdc Absolute maximum input voltage with no damage to the
DC-UPS
0 to 22.5Vdc The DC-UPS switches into buffer mode and delivers
output voltage from the battery if the input was above
the turn-on level before and all other buffer conditions
are fulfilled.
max. 60Vdc or
42.4Vac
typ. 22.8Vdc The output does not switch on if the input voltage does
not exceed this level.
current mode at 24V input See Fig. 8-2 ***)
No limitation
e current which is required to charge the battery during the
Fig. 5-3.
C
Input
Current
Output
Current
n
183035V22.50
A: Rated input voltage range
B: Temp. allowed, no harm to the unit
C: Absolute max. input voltage
D: Buffer mode
V
IN
Electronic output current limitation
The DC-UPS is equipped with an electronic output
current limitation. This current limitation works
in a switching mode which reduces the power
losses and heat generation to a minimum. As a
result, the output voltage drops since there is not
enough current to support the load. A positive
effect of the current limitation in switching mode
is that the input current goes down despite an
increase in the output current resulting in less
stress for the supplying source.
p
n
I
t
p
consumptio n
for battery
charging
r
u
C
t
u
t
u
C
u
Current
n
e
r
r
r
e
Internal
current
consumptio n
Fig. 5-3 Input current and output voltage vs.
output current, typ. (battery fully charged)
20V
10
20A
15
10
5
0
Output Voltage
O
u
481220A
0
Overload
t
t
n
15
3/23
Page 4
UB10.241
6. OUTPUT IN NORMAL MODE
Output voltage in normal mode
output
max. 0.45V At 15A output current, see Fig. 6-1 for typical values
Ripple and noise voltage max. 20mVpp 20Hz to 20MHz, 50Ohm *)
Output current nom. 15A Continuously allowed
Output power nom. 360W Continuously allowed
Short-circuit current min. 17.9A Load impedance 100mOhm, see Fig. 6-2 for typical values
max. 21A Load impedance 100mOhm, see Fig. 6-2 for typical values
Capacitive and inductive loads No limitation
*) This figure shows the ripple and noise voltage which is generated by the DC-UPS. The ripple and noise voltage
might be higher if the supplying source has a higher ripple and noise voltage.
Fig. 6-1
Input to Output
Voltage drop
0.4V
0.35
0.25
0.15
0.05
Input to output voltage drop, typ.
0.3
0.2
0.1
r
u
C
t
p
u
t
0
0210
Ou
4 6 812 14 16
nom. DC 24V The output voltage follows the input voltage reduced by
the input to output voltage drop.
max. 0.3V At 10A output current, see Fig. 6-1 for typical values Voltage drop between input and
Fig. 6-2 Output voltage vs. output current in
normal mode at 24V input, typ.
Output Voltage
28V
24
20
t
n
e
r
18A
16
12
8
4
0
05101520
Output Current
25A
4/23
Page 5
A
UB10.241
7. OUTPUT IN BUFFER MODE
If the input voltage falls below a certain value (transfer threshold level), the DC-UPS starts buffering without any
interruption or voltage dips. Buffering is possible even if the battery is not fully charged.
Output voltage in buffer mode
Ripple and noise voltage max. 20mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 10A Continuously allowed
15A < 5s with full output voltage *)
Short-circuit current min. 17.9A Load impedance 100mOhm **)
max. 21A Load impedance 100mOhm **)
*) If the output current is in the range between 10A and 15A for longer than 5s, a hardware controlled reduction of the
maximal output current to 10A occurs. If the 10A are not sufficient to maintain the 24V, buffering stops after another 5s. The
buffering is possible again as soon as the input voltage recovers.
**) If the nominal output voltage cannot be maintained in buffer mode,
capacity.
Fig. 7-1 Buffering transition, definitions Fig. 7-2 Transfer behavior, typ.
nom. DC 24V Output voltage is stabilized and independent from
battery voltage
22.45V ±1%, at no load,
22.25V ±1%, at 10A output current
typ. 80mV higher than the output voltage in buffer mode Transfer threshold for buffering
the DC-UPS switches off after 5s to save battery
O
t
p
u
t
Input
voltage
28V
24V
Transfer
threshold
2
4
V
2
2
.
2
5
V
a
t
1
0
A
u
V
t
l
o
a
g
e
2
4
V
t
Output
voltage
Buffer mode
t
I
0
V
V
I
m
s
/
D
0
0
5
e
g
t
l
a
o
t
u
V
p
n
Fig. 7-3
Available output current in buffer
Output
Current
mode
15A
10A
5A
0
05 Sec.
BonusPower
®
Time
Fig. 7-4 Output voltage vs. output current in
Output Voltage
25V
20
15
10
5
0
0
Continuously available
A
Available for 5s then auto switching to curve
B
Buffering will stop after 5s
C
Buffering will stop after 5s
D
buffer mode, typ.
AB
CD
Output
Current
5101520
25
D
5/23
Page 6
UB10.241
8. BATTERY INPUT
The DC-UPS requires one 12V VRLA battery to buffer the 24V output.
Battery voltage nom. DC 12V Use one maintenance-free 12V VRLA lead acid battery or
one
9.0 – 15.0V Continuously allowed, except deep discharge protection Battery voltage range
max. 35Vdc Absolute maximum voltage with no damage to the unit
typ. 7.4V Above this voltage level battery charging is possible
Allowed battery sizes min. 3.9Ah max. 40Ah
max. 100mOhm See individual battery datasheets for this value Internal battery resistance
Battery charging method CC-CV Constant current, constant voltage mode
Battery charging current (CC-mode) nom. 1.5A Independent from battery size,
max. 1.7A Corresponding 24V input current see Fig. 8-2
End-of-charge-voltage (CV-mode) 13.4-13.9V Adjustable, see chapter 14
Battery charging time typ. 5h *) For a 7Ah battery
typ. 17h *) For a 26Ah battery
Battery discharging current **) typ. 21A Buffer mode, 10A output current, 11.5V on the battery
typ. 0.3A Buffer mode, 0A output current
max. 50μA At no input, buffering had switched off, all LEDs are off
typ. 270mA At no input, buffering had switched off, yellow LED
typ. 10.5V At 0A output current Deep discharge protection ***)
typ. 9.0V At 10A output current
*) The charging time depends on the duration and load current of the last buffer event. The numbers in the table represent a
fully discharged battery. A typical figure for a buffer current of 10A is 3h 20Min. for a 7Ah battery.
**) The current between the battery and the DC-UPS is more than twice t
battery voltage to a 24V level.This high current requires large wire gauges and short cable length for the longest possible
buffer time. The higher the resistance of the connection between the battery and the DC-UPS, the lower the voltage on the
battery terminals which increases the discharging current. See also chapter
***) To ensure longest battery lifetime, the DC-UPS has a battery deep discharge protection feature included. The DC-UPS stops
bufferin
g when the voltage on the battery terminals of the DC-UPS falls below a certain value. The yellow LED will show
“buffer time expired” for a period of 15 minutes after the unit stopped buffering.
Fig. 8-1 Battery discharging current
vs. output current, typ.
Battery Current
30A
25
20
15
10
5
0
0
2.57.51015A12.55
O
u
t
p
u
C
t
r
r
u
e
n
A B C
Voltage on
battery terminal
of the DC-UPS:
A:
10.5V
B:
11V
C:
12V
t
battery module which is listed in the chapter
accessories.
terminal of the DC-UPS, see Fig. 8-1 for other parameters
shows “buffer time expired” (max. 15 minutes)
he output current. This is caused by boosting the 12V
25 for more installation instructions.
Fig. 8-2 Required input current vs. input
voltage for battery charging
Input Current
1.5A
1.25
1.0
0.75
0.5
0.25
m
a
x.
(
b
a
t
t
e
r
y
c
h
a
r
g
i
n
g
c
u
r
r
e
n
t
1
.
7
A
t
yp
.
(
b
a
t
t
e
r
y
c
h
a
r
g
i
n
g
c
u
r
p
n
I
t
u
o
V
t
l
a
g
0
23
24252628V
e
)
r
e
n
t
1
.
5
A
)
27
6/23
Page 7
UB10.241
9. BUFFER TIME
The buffer time depends on the capacity and performance of the battery as well as the load current. The diagram
below shows the typical buffer times of the standard battery modules.
Buffer time with battery module UZK12.071 min. 19’12’’ At 5A output current *)
min. 5’42’’ At 10A output current *)
typ. 21’30’’ At 5A output current, see Fig. 9-1 **)
typ. 6’45’’ At 10A output current, see Fig. 9-1 **)
Buffer time with battery module UZK12.261 min. 99’30’’ At 5A output current *)
min. 39’ At 10A output current *)
typ. 130’ At 5A output current, see Fig. 9-1 **)
typ. 55’ At 10A output current, see Fig. 9-1 **)
*) Minimum value includes 20% aging of the battery and a cable length of 1.5m with a cross section of 2.5mm2 between the
battery and the DC-UPS and requires a fully charged (min. 24h) battery.
**) Typical value includes 10% aging of the battery and a cable length of 0.3m with a cross section of 2.5mm
and the DC-UPS and requires a fully charged (min. 24h) battery.
Buffer Current
10A
Fig. 9-1
8
6
4
2
Buffer time vs. output current with the battery modules UZK12.071 and UZK12.261
U
Z
K
1
2
.
2
6
1
t
y
p.
6
A
h
b
a
t
t
e
r
y
7
1
t
y
p
.
b
a
t
t
er
y
90
120 150210 240
18027090
Buffer Time (Minutes)
515
201025 30 3545 504055 60 65 70 75 80 85
1
2
V
2
U
Z
K
1
2
.
0
1
2
V
7
A
h
U
U
The battery capacity is usually specified in amp-hours (Ah) for a 20h discharging event. The battery discharge is nonlinear (due to the battery chemistry). The higher the discharging current, the lower the appropriable battery capacity.
The magnitude of the reduction depends on the discharging current as well as on the type of battery. High current
battery types can have up to 50% longer buffer times compared to regular batteries when batteries will be
discharged in less than 1 hour.
High discharging currents do not necessarily mean high power losse
s as the appropriable battery capacity is reduced
with such currents. When the battery begins to recharge after a discharging event, the process is completed much
faster since only the energy which was taken out of the battery needs to be “refilled”.
For this reason, the buffer time cannot be calculated using the
Ah capacity value. The equation “I x t” = capacity in
Ah generally leads to incorrect results when the discharging current is higher than C20 (discharging current for 20h).
The battery datasheet needs to be studied and a determination of the expected buffer time can be made according
to the following example:
2
between the battery
Z
K
1
2
.
2
6
1
t
y
p
Z
K
1
2
.
0
7
1
t
y
p
Min.
.
.
300
7/23
Page 8
Example how to determine the expected buffer time for other battery types and battery sizes:
Step 1
Check the datasheet of the battery which is planned to be used and look for the discharging curve.
Sometimes, the individual discharging curves are marked with relative C-factors instead of current
values. This can easily be converted. The C-factor needs to be multiplied with the nominal battery
capacity to get the current value. E.g.: 0.6C on a 17Ah battery means 10.2A.
Fig. 9-2 Typical discharging curve of a typical 17Ah battery, curve taken from a
manufacturer’s datasheet
UB10.241
Step 2Determine the required battery current. Use Fig. 8-1 “Battery discharging current vs. output current” to
get the battery current. Fig. 8-1 requires the average voltage on the battery terminals. Since there is a
voltage drop between the battery terminals and the battery input of the DC-UPS, it is recommended to
use the curve A or B for output currents > 3A or when long battery cables are used. For all other
situations, use curve C.
Step 3 Use the de
(Discha
UPS stops buffering due to the under-voltage lockout.
Step 4 De
Example:
The buffer current: is 7.5A and a battery according Fig. 9-2 is used. The cable between the battery and the DC-UPS is
1
m and has a cross section of 2.5mm
Answer:
According to Fig. 8-1, the battery current is 18A. Curve A is used since the battery current is > 3A and the
According to Fig. 9-2, a buffer time (Discharging Time) of 30 Minutes can be determined. It is recommended
pending on Fig. 9-2, the buffer time needs to be reduced to take aging effects or guaranteed values
into ac
length of the cable is one meter.
duce this figure to approximately 24 minutes for a guaranteed value and to cover aging effects.
to re
termined current from Step 2 to find the appropriate curve in Fig. 9-2. The buffer time
rging Time) can be found where this curve meets the dotted line. This is the point where the DC-
count.
2
. How much is the maximum achievable buffer time.
8/23
Page 9
UB10.241
10. EFFICIENCY AND POWER LOSSES
Efficiency typ. 97.8% Normal mode, 10A output current, battery fully charged
Power losses typ. 2.9W Normal mode, 0A output current, battery fully charged
typ. 5.5W Normal mode, 10A output current, battery fully charged
typ. 5.0W During battery charging, 0A output current
typ. 18.5W Buffer mode, 10A output current
Fig. 10-1 Efficiency at 24V, typ. Fig. 10-2 Losses at 24V, typ.
Efficiency vs. output
current in normal mode
98%
97.5
97.0
96.5
96.0
95.5
95.0
94.5
39
t
n
e
r
r
u
C
t
u
p
t
u
O
571113
15A
Power losses versus output
current in normal mode
8W
7
6
5
4
3
2
1
0
07.5
O
2.5510 12.5
u
C
t
p
u
t
u
t
n
e
r
r
15A
11. FUNCTIONAL DIAGRAM
Fig. 11-1 Functional diagram
DC-UPS Control Unit
Input Fuse
24V
Power
Supply
12V Battery
+
-
+
Input
-
+
Battery
-
&
Reverse
Polarity
Protection
Battery
Tester
Cut-off
Relay
*
Battery
Charger
Step-up
Converter
(1)(2)
Ready
Contact
Controller
(3)(4)
Buffering
Contact
Electronic
Current
Limiter
(5)(6)
Replace
Battery
Contact
+
Output
Buffered
Load
-
Status LED (green)
Diagnosis LED (yellow)
Check Wiring LED (red)
Buffer-time Limiter
10s, 30s, 1m, 3m, 10m,
End-of-charge Voltage
(7)
Inhibit +
(8)
Inhibit -
*) Return current protection; This feature utilizes a Mosfet instead of a diode in order to minimize the voltage drop and power
losses.
9/23
Page 10
UB10.241
12. CHECK WIRING AND BATTERY QUALITY TESTS
The DC-UPS is equipped with an automatic “Check Wiring” and “Battery Quality” test.
“Check Wiring” test:
Under normal circumstances, an incorrect or bad connection from the battery to the DC-UPS or a missing (or blown)
battery fuse would not be recognized by the UPS when operating in normal mode. Only when back up is required
would the unit not be able to buffer. Therefore, a “check wiring” test is included in the DC-UPS. This connection is
tested every 10 seconds by loading the battery and analyzing the response from the battery. If the resistance is too
high, or the battery voltage is not in range, the unit displays “Check Wiring” with the red LED. At the same time the
green “Ready” LED will turn off.
“State of Health” (SoH) test:
The battery has a limited service life and needs to be replaced in a fixed interval which is defined by the specified
rvice life (acc. to the Eurobat guideline), based on the surrounding temperature and the number of
se
charging/discharging cycles. If the battery is used longer than the specified service life, the battery capacity will
degrade. Details can be found in chapter
However, it c
the DC-UPS.
The battery quality test consists of different types of tests:
During cha
During operation:
A battery problem is indicated with the yellow LED (replace batte
Please note that it can take up to 50 hours (with the largest size of battery) until a battery problem is reported. This
should avoid nuisance error messages as any urgent battery problems will be reported by the “Check Wiring” test
and create a warning signal. The battery tests require up to 50h uninterrupted operation. Any interruptions in the
normal operation of the DC-UPS may result in the “Replace Battery” test cycle to start over.
When “Replace battery” is indicated, it is recommended to replace battery as soon as possible.
an detect a battery failure within the specified service life of the battery. Therefore a SoH is included in
rging:
If the battery does not reach the ready status (see chapter 14) within 30h, it is considered
The reason could be a broken cell inside the battery.
Once the battery is fully charged, a voltage drop test and a load test is performed alternately every 8 hours.
Three of the tests must consecutively produce negative results to indicate a battery problem.
27.1. The battery SoH test can not determine a gradual loss in capacity.
to be defective.
ry pattern) and the relay contact “Replace Battery”.
10/23
Page 11
UB10.241
13. RELAY CONTACTS AND INHIBIT INPUT
The DC-UPS is equipped with relay contacts and signal inputs for remote monitoring and controlling of the unit.
Relay contacts:
Ready: Conta
Buffering: Contact is closed when unit is buffering.
Replace Battery: Contact is closed when the unit is powere
Relay contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load
min 1mA at 5Vdc min.
Isolation voltage max 500Vac, signal port to power port
Signal input:
Inhibit: The inhibit input disables buffering. In normal mode, a static signal is
Signal voltage max. 35Vdc
Signal current max. 6mA, current limited
Inhibit threshold min. 6Vdc, buffering is disabled above this threshold level
max. 10Vdc
Isolation nom. 500Vac, signal port to power port
Restriction apply when using the signal and relay contacts in a Haz-Loc environment:
The Buffering, Ready and Replace Battery contact is intended to be used for a separately investigated nonincendive field wiring
and/
or field wiring apparatus. The DC-UPS may be located in a Class I, Division 2 (Group A, B, C or D) hazardous (classified)
location. Associated apparatus must be installed in accordance with its manufacturer's control drawing and Article 504 of the
National Electrical Code (ANSI/NFPA 70) for installation in the United States, or Section 18 of the Canadian Electrical Code for
Installations in Canada.
Selected associated apparatus must be third part listed as providing nonincendive field circuits for the application, and have Voc
not excee
Non associated nonincendive field wiring apparatures shall not be connected in parallel unless this is permitted by the associated
noni
ding Vmax, Isc not exceeding Imax.
ncendive field wiring apparatures approval.
ct is closed when battery is charged more than 85%, no wiring failure are recognized, input
voltage is sufficient and inhibit signal is not active.
d from the input and the battery quality test (SOH test)
reports a negative result.
7 +
required. In buffer mode, a pulse with a minimum length of 250ms is
required to stop buffering. The inhibit is stored and can be reset by
cycling the input voltage. See also section
27.1 for application hints.
Inhibit
8 -
3mA
5,1V
11/23
Page 12
Fig. 13-1 Contact control drawing for use in Haz-Loc
+
+
-
InputOutput
Ready
DCUPS
Buffering
Replace
Battery
Battery
+
-
Hazardous
-
Location
1
2
3
4
5
6
environments
Isc
Voc
Isc
Voc
Isc
Voc
Non Hazardous
Location
Apparatus
UB10.241
Selected barriers must have entity parameters such that
V max, Isc < I max,
Voc <
Ci + Ccable, La > Li + Lcable.
Ca >
For Ccable and Lcable, if the capacitance per foot
or the inductance
following values shall be used: Ccable = 60pF/foot
and Lcable = 0.2µH/foot.
Contact current: I max = 50mA
Contact voltage: V max. = 35V (DC or AC)
Max. associated circuit capacitance Ci = 0
Max. associated circuit inductance Li = 0
No polarity requirement
per foot is not known, then the
12/23
Page 13
UB10.241
14. FRONT SIDE USER ELEMENTS
Power Port
A
Quick-connect spring-clamp terminals, connection for input voltage,
output voltage and battery
Signal Port
B
Plug connec
Connections for the Ready, Buffering, Replace Battery relay contacts and
for the Inhibit input. See details in chapter . 13
Green Status LED
C
Ready: Ba
voltage is sufficient and inhibit signal is not active.
Charging: Ba
Buffering: Unit is i
Flashing pattern of the green status LED:
D
Yellow Diagnosis LED
Overload: Output has switched off due to long overload in buffer mode
or due to high temperatures.
Replace battery: Indicates a battery which failed the battery quality test
(SoH test). Battery should be replaced soon.
Buffer-time expired: Output has switched off due to settings of Buffer-
timer Limiter. This signal will be displayed for 15 minutes.
Inhibit active: Indicates that buffering is disabled due to an active inhibit
signal.
Flashing pattern of the yellow diagnosis LED:
E
Red Check Wiring LED
This LED indicates a failure in the installation (e.g
F Buffer-time Limiter:
User accessible dial which limits the maximum buffer time in a buffer event to save battery energy. When the
battery begins to recharge after a discharging event, the process is completed much faster since only the energy
which was taken out of the battery needs to be “refilled”. The following times can be selected: 10 seconds, 30
seconds, 1 minute, 3 minutes, 10 minutes or infinity (until battery is flat) which allows buffering until the deep
discharge protection stops buffering.
G End-of-charge-voltage Selector:
The end-of-charge-voltage shall be set manually according to the expec
located. The dial on the front of the unit allows an continuously adjustment between +10 and +40°C. 10°C will set
the end-of-charge-voltage to 13.9V, 25°CÆ13.65V and 40°CÆ13.4V. If in doubt about the expected temperature,
set the unit to 35°C.
tor with screw terminals, inserted from the bottom.
ttery is charged > 85%, no wiring failure is recognized, input
ttery is charging and the battery capacity is below 85%.
n buffer mode.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
. too low input voltage), wiring, battery or battery fuse.
Charging
Buffering
Overload
Replace
Buffer time
ted temperature in which the battery is
Ready
Battery
expired
Inhibit
active
13/23
Page 14
UB10.241
15. TERMINALS AND WIRING
Type Bi-stable, quick-connect spring-
Solid wire 0.5-6mm
Stranded wire 0.5-4mm0.2-1.5mm
AWG 20-10AWG 22-14AWG
Ferrules Allowed, but not required Allowed, but not required
Fig. 15-1 Spring-clamp terminals, connecting a wire
1.
Insert the wire
To disconnect wire:
reverse the procedure
Power terminalsSignal terminals
Plug connector with screw te
clamp terminals. IP20 Fingertouch-proof. Suitable for fieldand factory installation. Shipped
in open position.
14AWG:50N, 16AWG:40N
according to UL486E
2.
Close the lever
22
22
construction with captive screws for 3.5mm slotted
screwdriver. Suitable for field- and factory installation.
Shipped in open position. To meet GL requirements,
unused terminal compartments should be closed.
0.2-1.5mm
Not applicable
Instructions:
a) Use
b) Follow
c) Ensure that all
d) Up to two stranded wires with the same c
appropriate copper cables, that are designed
for an operating temperature of 60°C
national installation codes and regulations!
terminal connection!
section are permitted in one connection point
rminal. Finger-touch-proof
strands of a stranded wire enter the
ross
16. RELIABILITY
Lifetime expectancy min. 137 400h At 10A output current, 40°C
min. > 15 years At 5A output current, 40°C
min. > 15 years At 10A output current, 25°C
MTBF SN 29500, IEC 61709 886 000h At 10A output current, 40°C
1 482 000h At 10A output current, 25°C
MTBF MIL HDBK 217F 397 900 At 10A output current , 40°C, ground benign GB40
545 000 At 10A output current , 25°C, ground benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours.
Lifetime expectancy is calculated according to the capacitor’s manufacturer specification. The prediction model allows
a calculation of up to 15 years from date of shipment.
MTBF st
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
ands for Mean Time Between Failure, which is calculated according to statistical device failures and indicates
14/23
Page 15
UB10.241
17. EMC
The unit is suitable for applications in industrial environment as well as in residential, commercial and light industry
environment without any restrictions. CE mark is in conformance with EMC guideline 89/336/EEC and 93/68/EEC and
the low-voltage directive (LVD) 73/23/EEC, 93/68/EEC.
A detailed EMC Report is available on request.
Generic standards
EMC Immunity
Electrostatic discharge EN 61000-4-2 Contact discharge
Electromagnetic RF field EN 61000-4-3 80MHz-1GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Out- and input lines 2kV Criterion A
Signal lines **) 2kV Criterion A
Surge voltage EN 61000-4-5 Output + Æ -
Conducted disturbance EN 61000-4-6 0,15-80MHz 10V Criterion A
*) DIN-Rail earthed
**) Tested with coupling clamp
EN 61000-6-3, EN 61000-6-4 Generic standards
EMC Emission
Conducted emission EN 55022 Input lines Class B *)
EN 55022 Output lines Class B *)
Radiated emission EN 55011, EN 55022 Class B
This device complies with FCC Part 15 rules.
Operation is subjected to the following two conditions: (1) this device may not cause harmful interference, and (2) this
de
vice must accept any interference received, including interference that may cause undesired operation.
*) Informative measurement with voltage probe
Switching frequencies
Switching frequency of boost converter 100kHz Constant frequency
Switching frequency of electronic output curre
Switching frequency of battery charger 19.5kHz Constant frequency
EN 61000-6-1, EN 61000-6-2
nt limitation 78kHz Constant frequency
8kV
Air discharge
Input + Æ + / - Æ housing
The DC-UPS has three convert
switching frequencies included.
15kV
500V
500V
500V
Criterion A*)
Criterion A *)
Criterion A
Criterion A
Criterion A
ers with three different
15/23
Page 16
C
C
UB10.241
18. ENVIRONMENT
Operational temperature -25°C to +70°C (-13° to +158°F) For the DC-UPS control unit.
Derating 0.43A/°C
0.25A/°C
Storage temperature -40 to +85°C (-40° to +185°F) Storage and transportation, except battery
Humidity 5 to 95% r.H. IEC 60068-2-30
Vibration sinusoidal 2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g IEC 60068-2-6
Shock 30g 6ms, 20g 11ms IEC 60068-2-27
Altitude 0 to 6000m Approvals apply only up to 2000m
Over-voltage category III EN 50178
II EN 50178 above 2000m altitude
Degree of pollution 2 EN 50178, not conductive
Fig. 18-1 Output current vs. ambient temperature Fig. 18-2 Output current vs. ambient temperature
Allowable Output
Current in Normal Mode
15A
12.5
10
7.5
5
2.5
0
-2502040
Ambient Temperature
c
o
n
t
i
n
u
o
u
s
70°
60
Allowable Output
Current in Buffer Mode
15A
12.5
10
7.5
2.5
The ambient temperature is defined 2cm below the unit.
Keep battery in a cooler environment!
+60°C to +70°C (+140°F to +158°F),
normal mode see Fig. 18-1
+60°C to +70°C (+140°F to +158°F),
Degree of protection IP20 EN/IEC 60529
Penetration protection > 3.5mm E.g. screws, small parts
Reverse battery polarity protection yes Max. –35Vdc;
Wrong battery voltage protection yes Max. +35Vdc (e.g. 24V battery instead of 12V battery)
Battery deep discharge protection yes The limit is battery current dependent
Over temperature protection yes Output shut-down with automatic restart
Input over-voltage protection yes Max. 35Vdc, no harm or defect of the unit
Internal input fuse 25A, blade type No user accessible part, no service part
protected against overload, no-load and short-circuits
In case of an internal defect, a redundant circuitry
limits the maximum output voltage. The output
automatically shuts-down and makes restart attempts.
16/23
Page 17
UB10.241
20. SAFETY
Output voltage SELV IEC/EN 60950-1
PELV EN 60204-1, EN 50178, IEC 60364-4-41
Class of protection III PE (Protective Earth) connection is not required
Isolation resistance > 5MOhm Power port to housing, 500Vdc
Dielectric strength 500Vac Power port to signal port
500Vac Power port / signal port to housing
Touch current (leakage current) The leakage current which is produced by the DC-UPS itself depends on the input
Max. allowed voltage between any input,
60Vdc or 42.4Vac
ge ripple and need to be investigated in the final application.
volta
For a smooth DC input voltage, the produced leakage current is less than 100μA.
output or signal pin and ground:
21. APPROVALS
UL 508
UL 60950-1
IEC 60950-1
UL 1604 RECOGNIZED E246877 recognized for use in U.S.A. (UL 1604) and
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations as well as for Class I
Marine
Z
one 2 Groups IIA, IIB and IIC locations. Substitution of components may impair suitability for
Class I Division 2 environment. Do not disconnect equipment unless power has been switched
off. Wiring must be in accordance with Class I, Division 2 wiring methods of the National
Electrical Code, NFPA 70, and in accordance with other local or national codes.
18WM
IND. CONT. EQ.
IECEE
CB SCHEME
GL
ABS
LISTED E198865 listed for use in U.S.A. (UL 508) and
C
anada (C22.2 No. 14-95)
Industrial Control Equipment
RECOGNIZED E137006 recognized for the use in
U.S.A. (UL 609
Information Technology Equipment, Level 5
CB Scheme,
Information Technology Equipment
Canada (C22.2 No. 213-M1987)
Hazardous Location Class I Div 2 T4 Groups A,B,C,D and
Class I Zone 2 Groups IIA, IIB and IIC
GL (Germanischer Lloyd) classified and ABS (Americ
Shipping) PDA for marine and offshore applications.
Environmental category: C, EMC2
50-1) and Canada (C22.2 No. 60950)
an Bureau for
22. FULFILLED STANDARDS
EN/IEC 60204-1 Safety of Electrical Equipment of Machines
EN/IEC 61131 Programmable Controllers
EN 50178, IEC 62103 Electronic Equipment in Power Installations
17/23
Page 18
UB10.241
23. USED SUBSTANCES
The unit does not release any silicone and is suita
The unit conforms to the RoHS directive 2002/96/EC.
Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems.
Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated.
The materials used in our production process do not include the following toxic chemicals:
P
Width 49mm / 1.93’’
Height 124mm / 4.88’’ Plus height of signal connector plug
Depth 117mm / 4.61’’ Plus depth of DIN-rail
Weight 530g / 1.17lb
DIN-Rail Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN-rail height must be added to the depth (117mm) to calculate the total required installation
depth.
Electronic files with mechanical data can be downloaded at www.pulspower.com
Fig. 24-1 Side viewFig. 24-2 Front view
18/23
Page 19
UB10.241
25. INSTALLATION NOTES
Mounting:
The power terminal shall be located on top of the unit. An appropriate electrical and fire end-product enclosure
should be considered in the end use application.
Cooling: Convec
Installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended
wh
en loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance are
recommended.
Risk of electrical shock, fire, personal injury or death!
Turn power off and disconnect battery fuse before working on the DC-UPS. Protect against inadvertent re-powering.
Make sure the wiring is correct by following all local and n
Use caution to prevent any foreign objects from entering into the housing.
Do not use in wet locations or in areas where
Service parts:
The unit does not contain any service parts. The tripping of an internal fuse is c
or malfunctioning should occur during operation, immediately turn power off and send unit to the factory for
inspection!
Wiring and installation instructions:
(1) Connect the power supply to the input terminals of the DC-UPS.
(2) Connect the battery to the battery terminals of the DC
cabinet or in a place where the battery will not be heated up by adjacent equipment. Do not install the battery
in airtight housings or cabinets. The battery should be installed according to EN50272-2, which includes sufficient
ventilation. Batteries store energy and need to be protected against energy hazards. Use a 30A battery fuse typ
ATO® 257 030 (Littelfuse) or similar in the battery path. The battery fuse protects the wires between the battery
and the DC-UPS. It also allows the disconnection of the battery from the DC-UPS which is recommended when
working on the battery or DC-UPS. Disconnect battery fuse before connecting the battery.
Please note: Too small or too long wires between the DC-UPS and the battery c
result in a malfunction of the DC-UPS. Do not use wires smaller than 2.5mm
2x1.5m (cord length 1.5m). Avoid voltage drops on this connection.
(3) Connect the buffered load to the output terminals
allowing load circuits to be easily split into buffered and non buffered sections. Noncritical loads can be
connected directly to the power supply and will not be buffered. The energy of the battery can then be used in
the circuits which requires buffering.
(4) Install the fuse when the wiring is finishe
Fig. 25-1 Typical wiring diagram
tion cooled, no forced air cooling required. Do not obstruct air flow!
ational codes. Do not open, modify or repair the unit.
moisture or condensation can be expected.
aused by an internal fault. If damage
-UPS. It is recommended to install the battery outside the
an shorten the buffer time or can
2
(or 12AWG) and not longer than
of the DC-UPS. The output is decoupled from the input
d.
24V
unbuffered
branch
24V
buffered
branch
+
-
24V
Power
supply
NLPE
+-+-+
24V
12V
IN
BAT
DC-UPS
UB10.241
24V
OUT
-
+
-
12V
Battery
+
-
Buffered
load
+
-
Unbuffered
load
19/23
Page 20
UB10.241
26. ACCESSORIES
Battery Modules
Two pre-assembled battery modules with a single 12V battery are available for different buffer times. As an option,
the mounting brackets are also available without batteries. This option offers more flexibility in selecting an
appropriate battery or can save shipping and logistic costs. See individual datasheets for detailed information.
UZK12.071 UZK12.261
Battery type Standard version
Service life 3 to 5years 10 to 12years According to EUROBAT guideline
Dimensions 155x124x112mm 214x179x158mm Width x height x depth
Weight 3.2kg 9.9kg
DIN-Rail mountable yes no
Order numbe
UZO12.07 UZO12.26 Mounting bra
UZB12.071 UZB12.261 Replacement b
Fig. 26-1 UZK12.071 Fig. 26-2 UZK12.261
r UZK12.071 UZK12.261 Battery module
12V, 7Ah
High current version
12V, 26Ah
VRLA lead-acid maintenance free
battery
cket without battery
attery only
ZM1.WALL Wall / Panel mounting bracket
This bracket is used to mount the DC-UPS units onto a fla
brackets and the black plastic slider of the DC-UPS have to be removed so that the two surface brackets can be
mounted.
t surface without utilizing a DIN-Rail. The two aluminum
20/23
Page 21
UB10.241
27. APPLICATION NOTES
27.1. BATTERY REPLACEMENT INTERVALS
Batteries have a limited life time. They degrade slowly beginning from the production and need to be replaced
periodically. The design life figures can be found in the individual datasheets of the batteries and usually is specified
according to the Eurobat guideline or according to the manufacturer’s specifications.
The design life is the estimated life based on laboratory cond
recommended float voltage condition. According to the Eurobat guideline, design lives have been structured into the
following different groups:
3 - 5 years:
6 - 9 years:
10 - 12 years:
A battery failure within the specified design life of the
function (broken cell, defect connection, …) and will be detected and reported by the periodical battery tests which
are included in the UB10.241 DC-UPS control unit.
If the operational parameters differ from those which are specified for the design life, an earlier change of the
battery might be necessary. The “real life” is called service life and is defined as the point at which the cell’s actual
capacity has reached 80% of its nominal capacity. At the end of the service life the capacity degrades much faster, so
that a further use of the battery is not recommended.
Temperature effect:
The temperature has the most impact in th
of the battery begins. The wear-out results in a degradation of battery capacity. See Fig. 27-1 for details.
Effect of discharging cycles
The number as well as the depth of discharging cycles is limited
earlier than the calculated service life if the battery exceeds the numbers and values of Fig. 27-2.
Other effects which shortens the service life
Guidelines for a long battery service life:
This group of batteries is very popular in standby applications and in small emergency equipment.
This represents a 4 years design life with a production tolerance of ±1 year.
This group of batteries is usually used when an improved life is required.
This represents a 7.5 years design life with a production tolerance of ±1.5 years.
This group of batteries is used when in applications where longest life and highest safety level are
required. This represents a 11 years design life with a production tolerance of ±1 year.
battery usually results in a complete loss of the battery
e service life. The hotter the temperature, the earlier the wear-out phase
Ove
Cha
Exc
Plac
Do not place the battery near heat generating devices.
Do not store discharged batteries.
Do not discharge the battery more than necessary. Set buffer time limiter to the required buffer time.
When c
rcharging and deep discharging shortens the service life and should be avoided. Thanks to the single
battery concept of the UB10.241, the end-of-charge-voltage can be set very precisely to the required value
an thereby avoiding unnecessary aging effects.
rge retention is important to get the longest battery life. Stored batteries which are not fully charged
age faster then charged batteries. Batteries which are not in use should be recharged at least once a year.
essive float charge ripple across the battery has an effect of reducing life and performance. The UB10.241
does not produce such a ripple voltage. This effect can be ignored when the battery is charged with the
UB10.241.
e the battery in a cool location: E.g. near the bottom of the control cabinet.
hoosing the battery capacity, always try to get the next higher capacity than required. The depth of
discharge reduces the service life of the battery and limits the number of cycles. See Fig. 27-2.
ition, and is quoted at 20°C using the manufacturer’s
. A replacement of the battery might be necessary
21/23
Page 22
UB10.241
Example for calculating the service life and the required replacement cycle:
Parameters for the example:
A 7Ah battery with a design life of 3-5 years is used (e.g. Yuasa battery from the battery module UZK12.071)
The average ambient temperature is 30°C
One buffer event consumes approx. 25% of the achievable buffer time.
One buffer event per day
Calculation:
Ambient temperature influence:
According to Fig. 27-1 curve A, a 2years s
ervice life can be expected for an ambient temperature of 30°C.
Number of discharging cycles: 2 years * 365 cycles = 730cycles in 2 years.
Ac
cording to Fig. 27-2, curve C has to be used (only 25% of battery capacity is required). 730 cycles have only a
gligible influence in a battery degradation and can be ignored.
ne
Result:
The battery shall be replaced after 2 years.
Please note that the battery degrading begins from the production date (check date code on the battery) which may
shorten the replacement intervals.
Fig. 27-1 Service life versus ambient
temperatures, typ *)
Service Life in Years
10
9
8
7
6
5
4
3
2
1
20°C
C
B
A
Ambient Temperature
30°C35°C
25°C
Design Life
of Battery
A:
3-5 Years
B:
6-9 Years
C:
10-12 Years
40°C
45°C
Fig. 27-2 Cell capacity degradation vs. discharging
Cell Capacity
120%
100%
80%
60%
40%
20%
0
UZK12.071
UZK12.261
A
200400600800 1000 1200
cycles *)
C
B
Depth of
discharge
A: 100%
B: 50%
C: 30%
Number of Discharging Cycles
80
160240320400480
*) datasheet figures from battery manufacturer
27.2. PARALLEL AND SERIAL USE
Do not use the DC-UPS in parallel to increase the output power. However, two units of the DC-UPS can be paralleled
for 1+1 redundancy to gain a higher system reliability.
Do not use batteries in parallel, since the battery quality test might create an error message.
Do not connect two or more units in series for higher output voltages.
Do not connect two or more units in a row to get longer hold-up times.
22/23
Page 23
UB10.241
27.3. USING THE INHIBIT INPUT
The inhibit input disables buffering. In normal mode, a static signal is required. In buffer mode, a pulse with a
minimum length of 250ms is required to stop buffering. The inhibit is stored and can be reset by cycling the input
voltage.
For service purposes, the inhibit input can also be used to c
be supplied from the output of the DC-UPS.
Fig. 27-3 Wiring example for inhibit input
+
-
12V
Battery
+ -+ -
Output
Power
Supply
Input
PE
NL
onnect a service switch. Therefore, the inhibit signal can
-
+ -+ -+ -
BAT
IN
24V
12V
DC-UPS
UB10.241
Signal Port
OUT
24V
+ -
Inhibit
+
Buffered
Load
Service
Switch
27.4. TROUBLESHOOTING
The LEDs on the front of the unit and relay contacts indicate about the actual or elapsed status of the DC-UPS. Please
see also chapter 14.
The following guidelines provide instructions for fixing the most common failures and problems. Always start with
the most likely and easiest-to-check condition. Some of the suggestions may require special safety precautions. See
notes in section
“Check wiring” LED is on
DC-UPS did not buffer
DC-UPS stopped buffering
Output has shut down Cycle the input power to reset the DC-UPS
DC-UPS constantly switches between normal mode and buffer mode
25 first.
Check correct wiring between the battery and the DC-UPS
Check battery fuse. Is the battery fuse inserted or blown?
Check battery voltage (must be typically between 7.4V and 15.1V)
Check input voltage (must be typically between 22.8V and 30V)
Check battery polarity
Inhibit input was set
Battery did not have enough time to be charged and is still below the deep discharge
protection limit.
Buffer time limiter stopped buffering Æ set buffer time limiter to a higher value
Deep discharge protection stopped buffering Æ use a larger battery, or allow
sufficient time for charging the battery
Output was overloaded or short circuit Æ reduce load
Le
t DC-UPS cool down, over temperature protection might have triggered.
The supplying source on the input is too small and can not deliver sufficient current
Æ Use a larger power supply or reduce the output load
23/23
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.