Daikin JEHCCU-CL1, JEHCCU-CM1, JEHCCU-CM3, JEHSCU-CL3, JEHSCU-CM1 User manual

...
Reciprocating condensing unit
Scroll condensing unit
Series 1
Series 2
Installation Manual
Operation Manual
(Original Instruction)
JEHCCU0040CM1 JEHCCU0050CM1 JEHCCU0051CM1 JEHCCU0063CM1 JEHCCU0067CM1 JEHCCU0077CM1 JEHCCU0095CM1
Reciprocating condensing unit
for low temperature application
JEHCCU0100CM1 JEHCCU0113CM1
Series 2 JEHCCU0140CM1 JEHCCU0140CM3
Series 1
JEHCCU0115CL1
JEHSCU0200CM1 JEHSCU0200CM3 JEHSCU0250CM1 JEHSCU0250CM3 JEHSCU0300CM1 JEHSCU0300CM3 JEHSCU0350CM3
Series 3 JEHSCU0400CM3 JEHSCU0500CM3 JEHSCU0600CM3 JEHSCU0680CM3
Series 4 JEHSCU0800CM3 JEHSCU1000CM3
Scroll condensing unit
for low temperature application
Series 2
JEHSCU0200CL3 JEHSCU0300CL3
Series 3
JEHSCU0400CL3 JEHSCU0500CL3 JEHSCU0600CL3
Series 4
JEHSCU0750CL3
2
1.
Nomenclature
2
2.
Safety and Health
2
3.
Installation & commissioning
3
4.
Decommissioning & Disposal
6
5.
Checklist
6
6.
Service and Maintenance
7
7.
F gas Regulations
7
8.
Trouble Shooting
8
9.
Specifications
9
10.
Outline Drawings
11
11.
Electrical Data
14
12.
Appendix
20

Important Note

installed in accordance with all applicable codes,
mental capabilities, or lack of experience and
responsible for their safety. Children should be
J&E Hall REFRIGIRATION CONDENSING UNIT
TYPE OF COMPRESSOR CCU: RECIPROCATING SCU:
NOMINAL COOLING CAPACITY IN HP (DEVIDED BY 100)
POWER SUPPLY 1: 3: 400V/50Hz/3PH
APPLICATION M: MEDIUM TEMPERATURE L: LOW TEMPERATURE
GENERATION B: 2ND C: 3RD

Contents

1. Nomenclature

SCROLL

2. Safety and Health

General Information
Only a qualified refrigeration engineer who is familiar with refrigeration systems and components, including all controls should perform the installation and start-up of the system. To avoid potential injury, use care when working around coil surfaces or sharp edges of metal cabinets. All piping and electrical wiring should be
ordinances and local by-laws. This appliances is not intended for use by persons (including children) with reduced physical, sensory or
knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person
supervised to ensure that they do not play with the appliance.
O-CU06-DEC14-1 All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.
230V/50Hz/1PH
Ensure the unit received is the correct model for the intended application.
Ensure refrigerant, voltage, are suitable for the proposed application and environment.
Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment.
The condensing unit is delivered with a nitrogen holding charge.
The condensing unit contains moving machinery and electrical power hazards. May cause severe injury or death. Disconnect and shut off power before installation or service of the equipment.
Refrigerant release into the atmosphere is illegal. Proper evacuation, handling and leak testing procedures must be observed at all times.
Condensing unit must be earthed. Improper earthing may result in electric shocks or fire.
Be sure to switch off the unit before touching any electrical parts. Touching a live part may result in electric shocks or fire.
The electrical covers and condenser fan guard must remain fitted at all times.
Use of the condensing unit outside of design conditions and application for which units were intended may be unsafe and be detrimental to the unit, regardless short or long term operation.
The condensing units are not designed to withstand loads or stresses from other equipment or personnel. Such extraneous loads or stress may cause failure/leak/injury.
In some circumstances, a suction accumulator (not supplied) component may be required, it offers protection against refrigerant flood back during operation. It helps protect against off-cycle migration by adding internal free volume to the low side of the system.
Test must be conducted to ensure the amount of off- cycle migration to the compressor does not exceed the compressor’s charge limit.
Wherever possible the system should be installed to utilize a pump down configuration. For unit Series 1 JEHCCU040CM1 and JEHCCU0050CM1, it is advisable to connect with thermostat cut off configuration using the reserved terminal in control box.
After installation, the system should be allowed to run for 3 – 4 hours. The oil level should be checked after 3 – 4 hours run time and topped up as necessary. The oil level should not be lower than quarter of the compressor oil sight glass.
3
Important Note
Wrong !
Correct !
Wrong !
Correct !
Air Discharge
Springs to
absorb vibrations
Otherwise, the compressor can fall from its 3 compressor housing spring, which results in noisy vibrations during operation and possible to breakdown.

3. Installation & Commissioning

3.1 Unit site location
In order to achieve maximum cooling capacity, the installation location for condensing unit should be carefully selected.
Install the condensing unit in such a way so that hot air distributed by the condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.
Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or discharge.
The location must be well ventilated, so the unit can draw in and distribute plenty of air thus lowering the condensing temperature.
To optimize the unit running conditions, the condenser coil must be cleaned at regular intervals.
3.2 Installation Clearance
The installation location should allow sufficient space for air flow and maintenance around the unit.
Air inlet
To allow sufficient space for doing service or installation.
3.3 Compressor handling
To ensure compressor reliability, the condensing unit and the compressor must not be tilt greater than an angle of 45°.
3.4 Field Piping
Line sizing should only be determined by qualified personnel. All local codes of practice must be observed in the installation of refrigerant piping
To ensure satisfactory operation and performance, the following points should be noted for field piping arrangements,
Couples one indoor unit with one outdoor condensing unit only.
Release all the pre-charged nitrogen before pipework connection.
Connecting pipe size for suction and liquid line must same as attaches to the condensing unit. Correct line sizing will minimize the pressure drop and maintain sufficient gas velocity for proper oil return.
Pipework routes must be as simple and as short as possible. Avoid low points on pipework where oil can accumulate.
Use only clean, dehydrated refrigeration grade copper tube with large radius elbows. The piping shall be kept with enough bending radius.
Braze without over filling to ensure there is no excess solder into the tube.
To prevent oxidation, blow nitrogen through pipework when brazing.
Install insulation on all suction lines after pressure test.
Adequately support all pipe work at a maximum of 2
meter intervals.
For the condition where the outdoor condensing unit is above the indoor unit, the height difference between units shall be less than 25 m and install oil trap on suction pipe every 4 m height. The suction pipe must always be fitted with U-trap at the bottom.
For the condition where the outdoor condensing unit is below the indoor unit, the height difference between units shall be less than 4 m. Pipe trap shall be installed upward on outlet of indoor unit (suction pipe).
The recommended piping length is 25 m or less.
Additional oil might be required in case field piping is
long or with many oil traps. Check the oil level of the
O-CU06-DEC14-1 All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.
4
Compressor
Pressure differential
AE/AJ
19 barg
(275 psig)
MTZ/ZB*KQE
30 barg
(435 psig)
Test pressure
High side
Low side
28 barg
(405 psig)
19 barg
(275 psig)
1. Low pressure (LP) setting
12. Switch
Model
AE/CAJ/TAJ
MTZ/ZB
Refrigerant
R404A/
R134a
R404A/
R407F
R134a
Cut Out (barg)
27.7
18
27.7
18
Cut Out (psig)
402
261
402
261
Model
AE/CAJ/TAJ
MTZ
ZB*KQE
Cut out (psig)
21.8
7.3
14.5
8.7
20.3
29
8.7
Compressor Model
Refrigerant R404A R134a R404A R134a R407C R404A R134a
Work ing Pressure
Ran ge High Side,
(barg)
13.2 - 27.7 6.7 - 15.8 13.2 - 27.7 7.9 - 22.6 12.5 - 29.4 7.14 - 27.6 6.6 - 22.6
Work ing Pressure
Ran ge Low Side,
(barg)
1.5 - 8.3 0.1 - 3.9 1.0 -7.2 0.6 - 4.7 1.4 - 6.6 1.98 - 7.14 0.6 - 3.8
Med Temp
MTZ
Med Temp
ZB*KQE
Med Temp
AE/CAJ/TAJ
Important Note
Important Note
flare
Compressor
Med Temp
Med Temp
Med Temp
Refrigerant
R404A/R407A/
R134a
R404A
R134a
R407C
R404A/R407A/
R134a
Working
Side (barg)
Working
Side, (barg)
compressor to decide to add the oil after minimum 2 hours operation.
It is recommended as well to install the MOP (Maximum Operation Pressure), expansion valve for medium evaporating temperature units, if the working suction pressure during start procedure especially after defrost cycle, is out of the limit, as refer to the table provided.
Recommend compressor working pressure range
Model
Pressure
Range High
Pressure
Range Low
AE/CAJ/TAJ
R407F
13.2 – 27.7
1.5 – 8.3
6.7 –
15.8
0.1 –
3.9
13.2 –
27.7
1.0 –
7.2
MTZ
R407F
7.9 –
12.5 –
22.6
0.6 –
4.7
29.4
1.4 –
6.6
7.14 – 27.6
1.98 – 7.14
ZB*KQE
Ensure that a good quality vacuum pump is used to pull a minimum vacu um of -0.1 barg (250 microns) or less. Ensure that no pressure increase during 1 hour or more after stop vacuuming. If pressure increase, there is moisture or leakage along the pipeline.
3.8 Safety pressure switch settings The pressure switch fitted to condensing units with auto reset for low pressure and manual reset for high pressure
6.6 –
22.6
0.6 –
3.8
are NOT
factory preset.
3.5 Pressure testing
Make sure that both service valves are closed when running a pressure test on field piping, always use an inert, dry gas such as Nitrogen
The pressure differential between the high and low side shall not higher than below.
Test pressures shall be as shown follows.
If there is pressure drop, check the leakage portion.
3.6 Leak detection
Make sure that all manual valves are open
Perform a leak test of the system using nitrogen mixed
with the refrigerant to be used
Do not use CFC for leak testing the condensing unit which will be used with HFC refrigerants
The use of leak testing fluids is not recommended as this may interact with the lubricants own additives
3.7 Vacuum - moisture removal
Moisture prevents proper functioning of the compressor and the refrigeration system
Air and moisture reduce service life and increase condensing pressure causing abnormally high discharge temperatures likely to destroy the oil’s lubricating properties. The risk of acid formation is also increased by air and moisture and copper plating can be generated in this way. All these phenomena can cause mechanical and electrical failure.
spindle
2. Differential setting spindle, LP
3. Main arm
5. High pressure (HP) setti ng spindle
7. Main spring
8. Differential spring
9. Bellows
10. LP connection
13. Terminals
14. Earth terminal
15. Cable entry
16. Tumbler
18. Locking plate
19. Arm
20. Manual reset button
11. HP connection
High pressure safety (Manual reset) The high pressure safety switch is required to protect the compressor from working out of its envelope. The high pressure switch shall set equal or lower than bel ow values depending on the type of refrigerant, application and the ambient condition.
R407A/
R407A/
R407F
R404A/
Refrigerant
Application M* M* M* M* M* M* M* Cut out (barg) 1.5 0.5 1 0.6 1.4 2 0.6
R407A/
R134a R404A R134a R407C
R407F
R404A/ R407A/
R407F
R134a
O-CU06-DEC14-1 All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.
5
O-CU06-DEC14-1 All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.
6
Refrigerant
R404A/R407C/R407F/R407A
R134a
Series 2- 13 Series 4 -10
Refrigerant
R404A/R407A/R407C/R407F
Setting (bar)
JEHR model -19
JEHS model - 13
R404A/ R407F
Setting Cut in
Setting Differential
Important Note
intervals.
Low Pressure side range
djusting screw
Clockwise: Decrease cut in
pressure setting
Anticloc
kwise: Increase cut in
pressure setting
Differential adjusting screw Clockwise: Increase differential pressure setting Anticlockwise:Decrease differential pressure setting
Low pressure side connector
High pressure side connector
High Pressure side range adjusting screw Clockwise: Increase cut off pressure setting Anticlockwise: Decrease cut off pressure setting
Clockwise: Increase pressure set point Anticlockwise: Decrease pressure set point
360° = 1 turn Approx. 1.5 barg
MEDIUM TEMP MODEL REFRIG FAN SPEED (RPM)
REFRIGERANT : R134a FAN SPEED (RPM)
LOW TEMP MODEL REFRIGERANT: R404A, R407A FAN SPEED (RPM)
TEMPERATURE (C°)
TEMPERATURE (C°)
TEMPERATURE (C°)
Manual reset switch
Low pressure safety (Auto reset) The low pressure safety switch is recommended to avoid
compressor operation at too lower suction pressure and vacuum condition. The low pressure safety cut should never be set below value as shown in the following table.
* M: Medium temperature; L: Low temperature
Cut off: Fan motor stops when the pressure decreases below the value P
min
.
Note: F.V.S. = Full Voltage Set Point (pressure setting for maximum speed) E.P.B. = Effective Proportional Band (6 bar) P
= (F.V.S. – 6)
min
a
For Series 1 model: Recommended setting for Series 1 model which using pressure switch to on/off fan:
Refrigerant
R407A/
R134a
The low pressure cut off pressure is the setting of cut in minus the differential.
There must be no more than 10 compressor starts per hour. A higher number reduces the compressor. If necessary, use an anti-short-cycle timer in
the control circuit. Minimum a 2 m i nut e runtime after each
start of compressor and a 3 stop & start are down cycle may the compressor
3.9 Fan speed controller setting
The fan speed controller regulates t he speed of the condenser’s fan. It keeps the condensing pressure at a steady level by changing the speed of the fan according to the required condensing pressure.
For model in Series 2 and 4 : Recommended setting for range setting pointer/ range adjusting screw as table below:
Medium Temp
Setting (bar) 19
Low Temp
O-CU06-DEC14-1 All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.
service life of the
minute idle time after each
recommended. Only during the pump
run for much shorter
(bar)
(bar)
16 10
7 7
The low pressure cut off pressure is the setting of cut in minus the differential.
For model in Series 3, the fan speed controller setting as shown below.
ERANT: R404A, R407A, R407F
7
MAX 150°C
OPEN position
Eart wire (
Power supply wire
Clamp
Earth terminal
3.10 Commissioning of the Condensing Unit
Please make sure that all manual service valves are fully open when starting the system for the first time. This includes external and internal shut off valves as well as liquid receiver valve in the unit. The ball valve open position is shown as below:
Check compressor oil level via compressor sight glass, the oil level should not be lower than quarter of sight glass.
Check the TXV capacity sizing based on indoor unit capacity. Check TXV applicable refrigerant. Check position and condition of the sensing bulb fixing
Observed the system pressures during the charging and initial operation process.
Ensure that suction pressure will decrease, discharge pressure will increase. No abnormal noise from the compressor.
Continue to charge the system until sight glass is clear. Make sure that high pressure is > 14 barg for R404A and > 8 barg for R134a when doing this charge adjustment operation. Continuous flow of clear refrigerant through the sight glass, with perhaps an occasional bubble at very high temperature indicates the refrigerant is at optimum.
Check the compressor’s discharge and suction
3.11 Compressor electrical wiring
Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation of a scroll compressor also results in substantially reduced current draw. Suction temperature will be high, discharge temperature will be low and the compressor may generate abnormal noise.
3.12 Earthing of Condensing Unit
Installation of earth wire must be made to earthing screw (labelled with earth label) before connecting the live wires. The earth wire shall be slack as shown in below diagram.
pressure, to ensure it is within operating range. Discharge temperature should be within 50 to 90 °C and pressure should be around 15 to 26 barg (for system charged with R404A) and 8 to 16 barg (for system charged with R134a).
Check the current of condensing unit and ensure it is below the motor circuit breaker setting value.
Check condenser fan, ensure warm air blowing off the condenser coil.
Check evaporator blower, ensure it’s discharging cool air.
Check suction superheat and adjust expansion valve to prevent liquid flood back to the compressor. Recommended 5 to 20 K of suction superheat.
Do not leave the system unattended until the system has reached its normal operating condition and the oil charge has properly adjusted itself to maintain the proper level in the sight glass.
Check periodically the compressor performance and all the moving components during the first day of operation.
Check the liquid line sight glass and expansion valve operation. If there is an indication that the system is low on refrigerant, thoroughly check the system for leaks before adding refrigerant.
Slack)

4. Decommissioning & Disposal

At the end of the unit’s useful life, a suitably qualified engineer should decommission it. The refrigerant and compressor oil are classed as hazardous waste and as such must be reclaimed and disposed of in the correct manner, including completion of waste transfer paperwork. The unit components must be disposed of or recycled as appropriate in the correct manner.

5. Checklist

Ensure the high low pressure controls are configured properly.
Ensure crankcase heater is energized minimum 12 hours prior to start up and permanently energized.
Check the refrigerant is correct for intended use.
Check all electrical connections.
Check all electrical termination and circuits are correct.
O-CU06-DEC14-1 All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.
Loading...
+ 15 hidden pages