Series 3
JEHSCU0400CM3
JEHSCU0500CM3
JEHSCU0600CM3
JEHSCU0680CM3
Series 4
JEHSCU0800CM3
JEHSCU1000CM3
Scroll condensing unit
for low temperature application
Series 2
JEHSCU0200CL3
JEHSCU0300CL3
Series 3
JEHSCU0400CL3
JEHSCU0500CL3
JEHSCU0600CL3
Series 4
JEHSCU0750CL3
2
1.
Nomenclature
2
2.
Safety and Health
2
3.
Installation & commissioning
3
4.
Decommissioning & Disposal
6
5.
Checklist
6
6.
Service and Maintenance
7
7.
F gas Regulations
7
8.
Trouble Shooting
8
9.
Specifications
9
10.
Outline Drawings
11
11.
Electrical Data
14
12.
Appendix
20
Important Note
installed in accordance with all applicable codes,
mental capabilities, or lack of experience and
responsible for their safety. Children should be
J&E Hall
REFRIGIRATION
CONDENSING UNIT
TYPE OF COMPRESSOR
CCU: RECIPROCATING
SCU:
NOMINAL COOLING
CAPACITY IN
HP (DEVIDED BY 100)
POWER SUPPLY
1:
3: 400V/50Hz/3PH
APPLICATION
M: MEDIUM TEMPERATURE
L: LOW TEMPERATURE
GENERATION
B: 2ND
C: 3RD
Contents
1. Nomenclature
SCROLL
2. Safety and Health
General Information
Only a qualified refrigeration engineer who is familiar
with refrigeration systems and components, including all
controls should perform the installation and start-up of
the system. To avoid potential injury, use care when
working around coil surfaces or sharp edges of metal
cabinets. All piping and electrical wiring should be
ordinances and local by-laws.
This appliances is not intended for use by persons
(including children) with reduced physical, sensory or
knowledge, unless they have been given supervision or
instruction concerning use of the appliance by a person
supervised to ensure that they do not play with the
appliance.
O-CU06-DEC14-1
All specifications are subjected to change by the manufacturer without prior notice. The English text is the
original instruction. Other languages are the translations of the original instructions.
230V/50Hz/1PH
•Ensure the unit received is the correct model for the
intended application.
•Ensure refrigerant, voltage, are suitable for the
proposed application and environment.
•Installation and maintenance are to be performed only
by qualified personnel who are familiar with local codes
and regulations, and experienced with this type of
equipment.
•The condensing unit is delivered with a nitrogen holding
charge.
•The condensing unit contains moving machinery and
electrical power hazards. May cause severe injury or
death. Disconnect and shut off power before installation
or service of the equipment.
•Refrigerant release into the atmosphere is illegal.
Proper evacuation, handling and leak testing
procedures must be observed at all times.
•Condensing unit must be earthed.
Improper earthing may result in electric
shocks or fire.
•Be sure to switch off the unit before touching any
electrical parts. Touching a live part may result in
electric shocks or fire.
•The electrical covers and condenser fan guard must
remain fitted at all times.
•Use of the condensing unit outside of design conditions
and application for which units were intended may be
unsafe and be detrimental to the unit, regardless short
or long term operation.
•The condensing units are not designed to withstand
loads or stresses from other equipment or personnel.
Such extraneous loads or stress may cause
failure/leak/injury.
•In some circumstances, a suction accumulator (not
supplied) component may be required, it offers
protection against refrigerant flood back during
operation. It helps protect against off-cycle migration by
adding internal free volume to the low side of the
system.
•Test must be conducted to ensure the amount of off-
cycle migration to the compressor does not exceed the
compressor’s charge limit.
•Wherever possible the system should be installed to
utilize a pump down configuration. For unit Series 1
JEHCCU040CM1 and JEHCCU0050CM1, it is
advisable to connect with thermostat cut off
configuration using the reserved terminal in control box.
•After installation, the system should be allowed to run
for 3 – 4 hours. The oil level should be checked after 3
– 4 hours run time and topped up as necessary. The oil
level should not be lower than quarter of the
compressor oil sight glass.
3
Important Note
Wrong !
Correct !
Wrong !
Correct !
Air Discharge
Springs to
absorb vibrations
Otherwise, the compressor can fall from its 3 compressor
housing spring, which results in noisy vibrations during
operation and possible to breakdown.
3. Installation & Commissioning
3.1 Unit site location
•In order to achieve maximum cooling capacity, the
installation location for condensing unit should be
carefully selected.
•Install the condensing unit in such a way so that hot air
distributed by the condensing unit cannot be drawn in
again (as in the case of short circuit of hot discharge
air). Allow sufficient space for maintenance around the
unit.
•Ensure that there is no obstruction of air flow into or out
of the unit. Remove obstacles which block air intake or
discharge.
•The location must be well ventilated, so the unit can
draw in and distribute plenty of air thus lowering the
condensing temperature.
•To optimize the unit running conditions, the condenser
coil must be cleaned at regular intervals.
3.2 Installation Clearance
•The installation location should allow sufficient space
for air flow and maintenance around the unit.
Air inlet
•To allow sufficient space for doing service or
installation.
3.3 Compressor handling
To ensure compressor reliability, the condensing unit and
the compressor must not be tilt greater than an angle of 45°.
3.4 Field Piping
Line sizing should only be determined by qualified
personnel. All local codes of practice must be observed
in the installation of refrigerant piping
To ensure satisfactory operation and performance, the
following points should be noted for field piping
arrangements,
•Couples one indoor unit with one outdoor condensing
unit only.
•Release all the pre-charged nitrogen before pipework
connection.
•Connecting pipe size for suction and liquid line must
same as attaches to the condensing unit. Correct line
sizing will minimize the pressure drop and maintain
sufficient gas velocity for proper oil return.
•Pipework routes must be as simple and as short as
possible. Avoid low points on pipework where oil can
accumulate.
•Use only clean, dehydrated refrigeration grade copper
tube with large radius elbows. The piping shall be kept
with enough bending radius.
•Braze without over filling to ensure there is no excess
solder into the tube.
•To prevent oxidation, blow nitrogen through pipework
when brazing.
• Install insulation on all suction lines after pressure test.
• Adequately support all pipe work at a maximum of 2
meter intervals.
•For the condition where the outdoor condensing unit is
above the indoor unit, the height difference between
units shall be less than 25 m and install oil trap on
suction pipe every 4 m height. The suction pipe must
always be fitted with U-trap at the bottom.
•For the condition where the outdoor condensing unit is
below the indoor unit, the height difference between
units shall be less than 4 m. Pipe trap shall be installed
upward on outlet of indoor unit (suction pipe).
• The recommended piping length is 25 m or less.
• Additional oil might be required in case field piping is
long or with many oil traps. Check the oil level of the
O-CU06-DEC14-1
All specifications are subjected to change by the manufacturer without prior notice. The English text is the
original instruction. Other languages are the translations of the original instructions.
compressor to decide to add the oil after minimum 2
hours operation.
•It is recommended as well to install the MOP (Maximum
Operation Pressure), expansion valve for medium
evaporating temperature units, if the working suction
pressure during start procedure especially after defrost
cycle, is out of the limit, as refer to the table provided.
Recommend compressor working pressure range
Model
Pressure
Range High
Pressure
Range Low
AE/CAJ/TAJ
R407F
13.2 – 27.7
1.5 – 8.3
6.7 –
15.8
0.1 –
3.9
13.2 –
27.7
1.0 –
7.2
MTZ
R407F
7.9 –
12.5 –
22.6
0.6 –
4.7
29.4
1.4 –
6.6
7.14 – 27.6
1.98 – 7.14
ZB*KQE
Ensure that a good quality vacuum pump is used to pull
a minimum vacu um of -0.1 barg (250 microns) or less.
Ensure that no pressure increase during 1 hour or more
after stop vacuuming. If pressure increase, there is
moisture or leakage along the pipeline.
3.8 Safety pressure switch settings
The pressure switch fitted to condensing units with auto
reset for low pressure and manual reset for high pressure
6.6 –
22.6
0.6 –
3.8
are NOT
factory preset.
3.5 Pressure testing
•Make sure that both service valves are closed when
running a pressure test on field piping, always use an
inert, dry gas such as Nitrogen
•The pressure differential between the high and low side
shall not higher than below.
• Test pressures shall be as shown follows.
• If there is pressure drop, check the leakage portion.
3.6 Leak detection
• Make sure that all manual valves are open
• Perform a leak test of the system using nitrogen mixed
with the refrigerant to be used
•Do not use CFC for leak testing the condensing unit
which will be used with HFC refrigerants
•The use of leak testing fluids is not recommended as
this may interact with the lubricants own additives
3.7 Vacuum - moisture removal
Moisture prevents proper functioning of the compressor
and the refrigeration system
Air and moisture reduce service life and increase
condensing pressure causing abnormally high discharge
temperatures likely to destroy the oil’s lubricating properties.
The risk of acid formation is also increased by air and
moisture and copper plating can be generated in this way.
All these phenomena can cause mechanical and electrical
failure.
spindle
2. Differential setting spindle, LP
3. Main arm
5. High pressure (HP) setti ng
spindle
7. Main spring
8. Differential spring
9. Bellows
10. LP connection
13. Terminals
14. Earth terminal
15. Cable entry
16. Tumbler
18. Locking plate
19. Arm
20. Manual reset
button
11. HP connection
High pressure safety (Manual reset)
The high pressure safety switch is required to protect the
compressor from working out of its envelope. The high
pressure switch shall set equal or lower than bel ow values
depending on the type of refrigerant, application and the
ambient condition.
O-CU06-DEC14-1
All specifications are subjected to change by the manufacturer without prior notice. The English text is the
original instruction. Other languages are the translations of the original instructions.
5
O-CU06-DEC14-1
All specifications are subjected to change by the manufacturer without prior notice. The English text is the
original instruction. Other languages are the translations of the original instructions.
High Pressure side range
adjusting screw
Clockwise: Increase cut off
pressure setting
Anticlockwise: Decrease cut off
pressure setting
Clockwise: Increase pressure
set point
Anticlockwise: Decrease
pressure set point
360° = 1 turn
Approx. 1.5 barg
MEDIUM TEMP MODEL
REFRIG
FAN SPEED (RPM)
REFRIGERANT : R134a
FAN SPEED (RPM)
LOW TEMP MODEL
REFRIGERANT: R404A, R407A
FAN SPEED (RPM)
TEMPERATURE (C°)
TEMPERATURE (C°)
TEMPERATURE (C°)
Manual reset switch
Low pressure safety (Auto reset)
The low pressure safety switch is recommended to avoid
compressor operation at too lower suction pressure and
vacuum condition. The low pressure safety cut should never
be set below value as shown in the following table.
* M: Medium temperature; L: Low temperature
Cut off: Fan motor stops when the pressure decreases
below the value P
min
.
Note:
F.V.S. = Full Voltage Set Point (pressure setting for
maximum speed)
E.P.B. = Effective Proportional Band (6 bar)
P
= (F.V.S. – 6)
min
a
For Series 1 model: Recommended setting for Series 1
model which using pressure switch to on/off fan:
Refrigerant
R407A/
R134a
The low pressure cut off pressure is the setting of cut in
minus the differential.
There must be no more than 10 compressor starts per
hour. A higher number reduces the
compressor. If necessary, use an anti-short-cycle timer in
the control circuit.Minimum a 2m i nut e runtimeafter each
start of compressor and a 3
stop & start are
down cycle may the compressor
3.9 Fan speed controller setting
The fan speed controller regulates t he speed of the
condenser’s fan.
It keeps the condensing pressure at a steady level by
changing the speed of the fan according to the required
condensing pressure.
For model in Series 2 and 4 : Recommended setting for
range setting pointer/ range adjusting screw as table below:
Medium Temp
Setting (bar) 19
Low Temp
O-CU06-DEC14-1
All specifications are subjected to change by the manufacturer without prior notice. The English text is the
original instruction. Other languages are the translations of the original instructions.
service life of the
minute idle time after each
recommended. Onlyduring the pump
run for muchshorter
(bar)
(bar)
16 10
7 7
The low pressure cut off pressure is the setting of cut in
minus the differential.
For model in Series 3, the fan speed controller setting as
shown below.
ERANT: R404A, R407A, R407F
7
MAX
150°C
OPEN
position
Eart wire
(
Power supply wire
Clamp
Earth
terminal
3.10 Commissioning of the Condensing Unit
Please make sure that all manual service valves are fully
open when starting the system for the first time. This
includes external and internal shut off valves as well as
liquid receiver valve in the unit.
The ball valve open position is shown as below:
•Check compressor oil level via compressor sight glass,
the oil level should not be lower than quarter of sight
glass.
•Check the TXV capacity sizing based on indoor unit
capacity. Check TXV applicable refrigerant. Check
position and condition of the sensing bulb fixing
•Observed the system pressures during the charging
and initial operation process.
•Ensure that suction pressure will decrease, discharge
pressure will increase. No abnormal noise from the
compressor.
•Continue to charge the system until sight glass is clear.
Make sure that high pressure is > 14 barg for R404A
and > 8 barg for R134a when doing this charge
adjustment operation. Continuous flow of clear
refrigerant through the sight glass, with perhaps an
occasional bubble at very high temperature indicates
the refrigerant is at optimum.
•Check the compressor’s discharge and suction
3.11 Compressor electrical wiring
Verification of proper rotation direction is made by observing
that suction pressure drops and discharge pressure rises
when the compressor is energized. Reverse rotation of a
scroll compressor also results in substantially reduced
current draw. Suction temperature will be high, discharge
temperature will be low and the compressor may generate
abnormal noise.
3.12 Earthing of Condensing Unit
Installation of earth wire must be made to earthing screw
(labelled with earth label) before connecting the live wires.
The earth wire shall be slack as shown in below diagram.
pressure, to ensure it is within operating range.
Discharge temperature should be within 50 to 90 °C
and pressure should be around 15 to 26 barg (for
system charged with R404A) and 8 to 16 barg (for
system charged with R134a).
•Check the current of condensing unit and ensure it is
below the motor circuit breaker setting value.
•Check condenser fan, ensure warm air blowing off the
condenser coil.
•Check evaporator blower, ensure it’s discharging cool
air.
•Check suction superheat and adjust expansion valve to
prevent liquid flood back to the compressor.
Recommended 5 to 20 K of suction superheat.
•Do not leave the system unattended until the system
has reached its normal operating condition and the oil
charge has properly adjusted itself to maintain the
proper level in the sight glass.
•Check periodically the compressor performance and all
the moving components during the first day of
operation.
•Check the liquid line sight glass and expansion valve
operation. If there is an indication that the system is low
on refrigerant, thoroughly check the system for leaks
before adding refrigerant.
Slack)
4. Decommissioning &
Disposal
At the end of the unit’s useful life, a suitably qualified
engineer should decommission it. The refrigerant and
compressor oil are classed as hazardous waste and as such
must be reclaimed and disposed of in the correct manner,
including completion of waste transfer paperwork. The unit
components must be disposed of or recycled as appropriate
in the correct manner.
5. Checklist
•Ensure the high low pressure controls are configured
properly.
•Ensure crankcase heater is energized minimum 12
hours prior to start up and permanently energized.
• Check the refrigerant is correct for intended use.
• Check all electrical connections.
• Check all electrical termination and circuits are correct.
O-CU06-DEC14-1
All specifications are subjected to change by the manufacturer without prior notice. The English text is the
original instruction. Other languages are the translations of the original instructions.
Loading...
+ 15 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.