Daikin JEHCCU-CL1, JEHCCU-CM1, JEHCCU-CM3, JEHSCU-CL3, JEHSCU-CM1 User manual

...
0 (0)

Installation Manual

Operation Manual

(Original Instruction)

Reciprocating condensing unit

Scroll condensing unit

for medium temperature application

for medium temperature application

Series 1

Series 2

JEHCCU0040CM1

JEHSCU0200CM1

JEHCCU0050CM1

JEHSCU0200CM3

JEHCCU0051CM1

JEHSCU0250CM1

JEHCCU0063CM1

JEHSCU0250CM3

JEHCCU0067CM1

JEHSCU0300CM1

JEHCCU0077CM1

JEHSCU0300CM3

JEHCCU0095CM1

JEHSCU0350CM3

JEHCCU0100CM1

 

JEHCCU0113CM1

Series 3

 

JEHSCU0400CM3

Series 2

JEHSCU0500CM3

JEHCCU0140CM1

JEHSCU0600CM3

JEHCCU0140CM3

JEHSCU0680CM3

Reciprocating condensing unit

Series 4

for low temperature application

JEHSCU0800CM3

Series 1

JEHSCU1000CM3

Scroll condensing unit

JEHCCU0115CL1

 

for low temperature application

 

Series 2

 

JEHSCU0200CL3

 

JEHSCU0300CL3

 

Series 3

 

JEHSCU0400CL3

 

JEHSCU0500CL3

 

JEHSCU0600CL3

 

Series 4

 

JEHSCU0750CL3

 

Contents

 

 

 

 

 

 

 

Ensure the unit received is the correct model for the

 

 

 

 

 

 

 

 

 

intended application.

 

 

 

 

 

 

 

 

 

 

 

 

Ensure refrigerant, voltage, are suitable for the

 

 

 

 

 

 

 

 

 

 

 

 

 

proposed application and environment.

1.

Nomenclature

 

 

 

2

 

 

 

Installation and maintenance are to be performed only

 

 

 

 

 

 

 

by qualified personnel who are familiar with local codes

2.

Safety and Health

 

 

 

2

 

 

 

 

and regulations, and experienced with this type of

 

 

 

 

 

 

 

equipment.

3.

Installation & commissioning

3

 

 

 

The condensing unit is delivered with a nitrogen holding

4.

Decommissioning & Disposal

6

 

 

 

 

charge.

 

 

 

The condensing unit contains moving machinery and

5.

Checklist

 

 

 

6

 

 

 

 

electrical power hazards. May cause severe injury or

 

 

 

 

 

 

 

death. Disconnect and shut off power before installation

 

 

 

 

 

 

 

 

 

 

 

 

 

6.

Service and Maintenance

7

 

 

 

or service of the equipment.

7.

F gas Regulations

 

 

 

7

 

 

 

Refrigerant release into the atmosphere is illegal.

 

 

 

 

 

 

 

Proper evacuation, handling and leak testing

8.

Trouble Shooting

 

 

 

8

 

 

 

 

procedures must be observed at all times.

 

 

 

 

 

 

Condensing unit must be earthed.

9.

Specifications

 

 

 

9

 

 

 

 

Improper earthing may result in electric

10.

Outline Drawings

 

 

 

11

 

 

 

 

shocks or fire.

 

 

 

 

 

 

Be sure to switch off the unit before touching any

11.

Electrical Data

 

 

 

14

 

 

 

 

electrical parts. Touching a live part may result in

 

 

 

 

 

 

 

electric shocks or fire.

12.

Appendix

 

 

 

20

 

 

 

The electrical covers and condenser fan guard must

 

 

 

 

 

 

 

 

 

 

 

 

 

remain fitted at all times.

1.

Nomenclature

 

 

 

 

 

 

 

Use of the condensing unit outside of design conditions

 

 

 

 

 

 

 

 

and application for which units were intended may be

 

 

 

 

 

 

 

 

 

 

 

 

 

unsafe and be detrimental to the unit, regardless short

 

 

 

 

 

 

 

 

 

 

 

 

 

or long term operation.

 

 

 

 

 

 

 

 

 

 

 

 

The condensing units are not designed to withstand

 

 

 

 

 

 

 

 

 

 

 

 

 

loads or stresses from other equipment or personnel.

 

 

 

 

 

 

 

 

 

 

 

Such extraneous loads or stress may cause

 

 

 

 

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

1: 230V/50Hz/1PH

 

 

failure/leak/injury.

J&E Hall

 

 

 

 

REFRIGIRATION

 

 

 

 

3: 400V/50Hz/3PH

 

In some circumstances, a suction accumulator (not

CONDENSING UNIT

 

 

 

 

 

 

 

 

 

 

supplied) component may be required, it offers

 

 

 

 

 

 

 

 

 

 

 

 

 

protection against refrigerant flood back during

 

 

 

 

 

 

 

 

 

 

 

 

 

TYPE OF COMPRESSOR

 

 

 

 

 

 

operation. It helps protect against off-cycle migration by

 

APPLICATION

 

CCU: RECIPROCATING

 

 

M: MEDIUM TEMPERATURE

 

adding internal free volume to the low side of the

SCU: SCROLL

 

 

L: LOW TEMPERATURE

 

system.

 

 

 

 

 

 

 

 

 

 

 

 

Test must be conducted to ensure the amount of off-

 

NOMINAL COOLING

 

GENERATION

 

 

cycle migration to the compressor does not exceed the

 

CAPACITY IN

 

B: 2ND

 

 

 

 

 

compressor’s charge limit.

 

HP (DEVIDED BY 100)

 

C: 3RD

 

 

 

 

Wherever possible the system should be installed to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

utilize a pump down configuration. For unit Series 1

 

 

 

 

 

 

 

 

 

 

 

 

 

JEHCCU040CM1 and JEHCCU0050CM1, it is

2.

Safety and Health

 

 

 

 

 

advisable to connect with thermostat cut off

 

 

 

 

 

configuration using the reserved terminal in control box.

 

 

 

 

 

 

 

 

 

 

 

 

After installation, the system should be allowed to run

 

General Information

 

 

 

 

 

 

 

 

for 3 – 4 hours. The oil level should be checked after 3

 

 

 

 

 

 

 

 

 

– 4 hours run time and topped up as necessary. The oil

 

 

 

 

 

 

 

 

 

 

 

 

 

level should not be lower than quarter of the

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor oil sight glass.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Important Note

 

 

 

 

 

 

 

 

 

 

Only a qualified refrigeration engineer who is familiar

 

 

 

with refrigeration systems and components, including all

 

 

 

controls should perform the installation and start-up of

 

 

 

the system. To avoid potential injury, use care when

 

 

 

working around coil surfaces or sharp edges of metal

 

 

 

cabinets. All piping and electrical wiring should be

 

 

 

installed in accordance with all applicable codes,

 

 

 

ordinances and local by-laws.

 

 

 

 

 

 

 

 

 

 

This appliances is not intended for use by persons

 

 

 

(including children) with reduced physical, sensory or

 

 

 

mental capabilities, or lack of experience and

 

 

 

knowledge, unless they have been given supervision or

 

 

 

instruction concerning use of the appliance by a person

 

 

 

responsible for their safety. Children should be

 

 

 

supervised to ensure that they do

not play

with the

 

2

 

O-CU06-DEC14-1

 

 

 

 

 

 

 

 

 

appliance.

 

 

 

 

 

 

 

 

 

All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.

Daikin JEHCCU-CL1, JEHCCU-CM1, JEHCCU-CM3, JEHSCU-CL3, JEHSCU-CM1 User manual

3.Installation & Commissioning

3.1Unit site location

In order to achieve maximum cooling capacity, the installation location for condensing unit should be carefully selected.

Install the condensing unit in such a way so that hot air distributed by the condensing unit cannot be drawn in again (as in the case of short circuit of hot discharge air). Allow sufficient space for maintenance around the unit.

Wrong ! Correct !

Ensure that there is no obstruction of air flow into or out of the unit. Remove obstacles which block air intake or discharge.

Correct !

Wrong !

The location must be well ventilated, so the unit can draw in and distribute plenty of air thus lowering the condensing temperature.

To optimize the unit running conditions, the condenser coil must be cleaned at regular intervals.

3.2 Installation Clearance

The installation location should allow sufficient space for air flow and maintenance around the unit.

Air inlet

 

 

 

Air Discharge

To allow sufficient space for doing service or installation.

3.3 Compressor handling

To ensure compressor reliability, the condensing unit and the compressor must not be tilt greater than an angle of 45°.

Otherwise, the compressor can fall from its 3 compressor housing spring, which results in noisy vibrations during operation and possible to breakdown.

Springs to absorb vibrations

3.4 Field Piping

Important Note

Line sizing should only be determined by qualified personnel. All local codes of practice must be observed in the installation of refrigerant piping

To ensure satisfactory operation and performance, the following points should be noted for field piping arrangements,

Couples one indoor unit with one outdoor condensing unit only.

Release all the pre-charged nitrogen before pipework connection.

Connecting pipe size for suction and liquid line must same as attaches to the condensing unit. Correct line sizing will minimize the pressure drop and maintain sufficient gas velocity for proper oil return.

Pipework routes must be as simple and as short as possible. Avoid low points on pipework where oil can accumulate.

Use only clean, dehydrated refrigeration grade copper tube with large radius elbows. The piping shall be kept with enough bending radius.

Braze without over filling to ensure there is no excess solder into the tube.

To prevent oxidation, blow nitrogen through pipework when brazing.

Install insulation on all suction lines after pressure test.

Adequately support all pipe work at a maximum of 2 meter intervals.

For the condition where the outdoor condensing unit is above the indoor unit, the height difference between units shall be less than 25 m and install oil trap on suction pipe every 4 m height. The suction pipe must always be fitted with U-trap at the bottom.

For the condition where the outdoor condensing unit is below the indoor unit, the height difference between units shall be less than 4 m. Pipe trap shall be installed upward on outlet of indoor unit (suction pipe).

The recommended piping length is 25 m or less.

Additional oil might be required in case field piping is long or with many oil traps. Check the oil level of the

O-CU06-DEC14-1

3

All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.

compressor to decide to add the oil after minimum 2 hours operation.

It is recommended as well to install the MOP (Maximum Operation Pressure), expansion valve for medium evaporating temperature units, if the working suction pressure during start procedure especially after defrost cycle, is out of the limit, as refer to the table provided.

Important Note

Ensure that a good quality vacuum pump is used to pull a minimum vacuum of -0.1 barg (250 microns) or less. Ensure that no pressure increase during 1 hour or more after stop vacuuming. If pressure increase, there is moisture or leakage along the pipeline.

 

Recommend compressor working pressure range

 

3.8 Safety pressure switch settings

 

Compressor

 

 

Med Temp

 

 

Me Temp

 

Med Temp

 

 

 

 

 

 

 

 

 

 

ModelCompressor

 

 

Med Temp

 

Med Temp

 

Med Temp

 

The pressure switch fitted to condensing units with auto

 

ModelAE/CAJ/TAJ

 

 

MTZ

 

ZB*KQE

 

 

Refrigerant

 

 

AE/CAJ/TAJ

R404A

MTZ

R407C

ZB*KQE

R134a

reset for low pressure and manual reset for high pressure

 

R404A/R407A/

R134a

R134a

R404A/R407A/

 

Refrigerant R407FR404A

R134a

R404A

R134a

R407C

R404AR407F R134a

 

are NOT factory preset.

 

 

 

 

 

 

 

 

 

 

 

 

WorkingWorking Pressure

 

6.7 –

.2 –

7.9 –

12.5 –

 

6.6 –

 

 

 

Pressure

 

 

13.2 - 27.7

7.14 - 27.6 6.6 - 22.6

 

 

 

Range High Side,

6.7 - 15.8

13.2 - 27.7

7.9 - 22.6

12.5 - 29.4

22.6

 

 

 

Range High

 

13.2 – 27.7

15.8

27.7

22.6

29.4

7.14 – 27.6

 

 

 

Side (barg)(barg)

 

 

 

 

 

 

 

 

 

 

 

Working Pressure

 

 

 

 

 

 

 

 

 

 

Working

 

 

1.5 - 8.3

0.1 - 3.9

1.0 -7.2

0.6 - 4.7

1.4 - 6.6

1.98 - 7.14 0.6 - 3.8

 

 

 

 

Range Low Side,

0.6 –

 

 

 

Pressure

 

1.5 – 8.3

0.1 –

1.0 –

0.6 –

1.4 –

1.98 – 7.14

 

 

 

Range Low(barg)

3.9

7.2

4.7

6.6

3.8

 

 

 

Side, (barg)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5 Pressure testing

Make sure that both service valves are closed when running a pressure test on field piping, always use an inert, dry gas such as Nitrogen

The pressure differential between the high and low side

 

 

flare

 

 

 

shall not higher than below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

Pressure differential

 

 

 

 

 

 

 

AE/AJ

19 barg

 

 

 

 

 

 

 

 

 

(275 psig)

 

1.

Low pressure (LP) setting

12.

Switch

 

 

MTZ/ZB*KQE

30 barg

 

 

 

 

spindle

13.

Terminals

 

 

 

(435 psig)

 

2.

Differential setting spindle, LP

14.

Earth terminal

Test pressures shall be as shown follows.

3.

Main arm

15.

Cable entry

5.

High pressure (HP) setting

16.

Tumbler

 

 

Test pressure

 

spindle

18.

Locking plate

 

 

High side

Low side

 

7.

Main spring

19.

Arm

 

 

28 barg

19 barg

 

8.

Differential spring

20.

Manual reset

 

 

(405 psig)

(275 psig)

 

9.

Bellows

button

If there is pressure drop, check the leakage portion.

10. LP connection

 

 

 

 

 

 

 

 

11. HP connection

 

 

 

3.6 Leak detection

Make sure that all manual valves are open

Perform a leak test of the system using nitrogen mixed with the refrigerant to be used

Do not use CFC for leak testing the condensing unit which will be used with HFC refrigerants

The use of leak testing fluids is not recommended as this may interact with the lubricants own additives

3.7Vacuum - moisture removal

Important Note

Moisture prevents proper functioning of the compressor and the refrigeration system

Air and moisture reduce service life and increase condensing pressure causing abnormally high discharge temperatures likely to destroy the oil’s lubricating properties. The risk of acid formation is also increased by air and moisture and copper plating can be generated in this way. All these phenomena can cause mechanical and electrical failure.

High pressure safety (Manual reset)

The high pressure safety switch is required to protect the compressor from working out of its envelope. The high pressure switch shall set equal or lower than below values depending on the type of refrigerant, application and the ambient condition.

Model

 

 

 

AE/CAJ/TAJ

 

 

MTZ/ZB

 

 

Refrigerant

 

 

R404A/

R134a

 

R404A/

 

R134a

 

 

 

 

 

R407A/

 

 

 

R407A/

 

 

 

 

 

 

 

 

 

R407F

 

 

 

R407F

 

 

 

 

 

Cut Out (barg)

 

27.7

 

18

 

 

27.7

 

18

 

 

Cut Out (psig)

 

402

 

261

 

 

402

 

261

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

AE/CAJ/TAJ

 

 

 

 

MTZ

 

 

 

ZB*KQE

Refrigerant

R404A/

 

R134a

 

R404A

 

R134a

R407C

 

R404A/

 

R134a

R407A/

 

 

 

 

R407A/

 

 

R407F

 

 

 

 

 

 

 

 

 

 

R407F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Application

M*

 

M*

 

M*

 

 

M*

M*

 

M*

 

M*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cut out (barg)

1.5

 

 

0.5

 

1

 

0.6

1.4

 

 

2

 

0.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cut out (psig)

21.8

 

 

7.3

 

14.5

 

8.7

20.3

 

29

 

8.7

O-CU06-DEC14-1

4

All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.

O-CU06-DEC14-1

5

All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.

Low pressure safety (Auto reset)

The low pressure safety switch is recommended to avoid compressor operation at too lower suction pressure and vacuum condition. The low pressure safety cut should never be set below value as shown in the following table.

* M: Medium temperature; L: Low temperature

Low Pressure side range adjusting screw Clockwise: Decrease cut in pressure setting

Anticlockwise: Increase cut in pressure setting

Differential adjusting screw Clockwise: Increase differential pressure setting Anticlockwise:Decrease differential pressure setting

High Pressure side range adjusting screw

Clockwise: Increase cut off Manual reset switch pressure setting

Anticlockwise: Decrease cut off pressure setting

Low pressure

High pressure

side connector

side connector

 

 

The low pressure cut off pressure is the setting of cut in minus the differential.

Important Note

There must be no more than 10 compressor starts per hour. A higher number reduces the service life of the compressor. If necessary, use an anti-short-cycle timer in the control circuit. Minimum a 2 minute runtime after each start of compressor and a 3 minute idle time after each stop & start are recommended. Only during the pump down cycle may the compressor run for much shorter intervals.

3.9 Fan speed controller setting

The fan speed controller regulates the speed of the condenser’s fan.

It keeps the condensing pressure at a steady level by changing the speed of the fan according to the required condensing pressure.

For model in Series 2 and 4 : Recommended setting for range setting pointer/ range adjusting screw as table below:

Medium Temp

Refrigerant

 

R404A/R407C/R407F/R407A

 

R134a

Setting (bar)

 

19

 

Series 2- 13

 

 

Series 4 -10

 

 

 

 

 

 

Low Temp

 

 

 

 

Refrigerant

R404A/R407A/R407C/R407F

 

 

Setting

JEHR model -19

 

 

(bar)

JEHS model - 13

 

Clockwise: Increase pressure set point

Anticlockwise: Decrease pressure set point

360° = 1 turn Approx. 1.5 barg

Cut off: Fan motor stops when the pressure decreases below the value Pmin.

Note:

F.V.S. = Full Voltage Set Point (pressure setting for maximum speed)

E.P.B. = Effective Proportional Band (6 bar) Pmin = (F.V.S. – 6)

For Series 1 model: Recommended setting for Series 1 model which using pressure switch to on/off fan:

Refrigerant

R404A/

 

R407A/

R134a

 

R407F

 

Setting

 

 

(bar)

16

10

Cut in

 

 

Setting

 

 

(bar)

7

7

Differential

 

 

The low pressure cut off pressure is the setting of cut in minus the differential.

For model in Series 3, the fan speed controller setting as shown below.

MEDIUM TEMP MODEL

 

 

REFRIGERANT: R404A, R407A, R407F

 

 

 

REFRIGERANT : R134a

FAN SPEED (RPM)

 

 

FAN SPEED (RPM)

 

 

 

 

 

TEMPERATURE (C°)

 

TEMPERATURE (C°)

 

 

 

LOW TEMP MODEL

REFRIGERANT: R404A, R407A

FAN SPEED (RPM)

TEMPERATURE (C°)

O-CU06-DEC14-1

6

All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.

3.10 Commissioning of the Condensing Unit

Please make sure that all manual service valves are fully open when starting the system for the first time. This includes external and internal shut off valves as well as liquid receiver valve in the unit.

The ball valve open position is shown as below:

MAX 150°C

OPEN position

3.11 Compressor electrical wiring

Verification of proper rotation direction is made by observing that suction pressure drops and discharge pressure rises when the compressor is energized. Reverse rotation of a scroll compressor also results in substantially reduced current draw. Suction temperature will be high, discharge temperature will be low and the compressor may generate abnormal noise.

3.12 Earthing of Condensing Unit

Installation of earth wire must be made to earthing screw (labelled with earth label) before connecting the live wires. The earth wire shall be slack as shown in below diagram.

Earth

 

 

 

 

 

 

Power supply wire

terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Eart wire

Clamp

(Slack)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.Decommissioning & Disposal

At the end of the unit’s useful life, a suitably qualified engineer should decommission it. The refrigerant and compressor oil are classed as hazardous waste and as such must be reclaimed and disposed of in the correct manner, including completion of waste transfer paperwork. The unit components must be disposed of or recycled as appropriate in the correct manner.

Check compressor oil level via compressor sight glass, the oil level should not be lower than quarter of sight glass.

Check the TXV capacity sizing based on indoor unit capacity. Check TXV applicable refrigerant. Check position and condition of the sensing bulb fixing

Observed the system pressures during the charging and initial operation process.

Ensure that suction pressure will decrease, discharge pressure will increase. No abnormal noise from the compressor.

Continue to charge the system until sight glass is clear. Make sure that high pressure is > 14 barg for R404A and > 8 barg for R134a when doing this charge adjustment operation. Continuous flow of clear refrigerant through the sight glass, with perhaps an occasional bubble at very high temperature indicates the refrigerant is at optimum.

Check the compressor’s discharge and suction pressure, to ensure it is within operating range. Discharge temperature should be within 50 to 90 °C and pressure should be around 15 to 26 barg (for system charged with R404A) and 8 to 16 barg (for system charged with R134a).

Check the current of condensing unit and ensure it is below the motor circuit breaker setting value.

Check condenser fan, ensure warm air blowing off the condenser coil.

Check evaporator blower, ensure it’s discharging cool air.

Check suction superheat and adjust expansion valve to prevent liquid flood back to the compressor. Recommended 5 to 20 K of suction superheat.

Do not leave the system unattended until the system has reached its normal operating condition and the oil charge has properly adjusted itself to maintain the proper level in the sight glass.

Check periodically the compressor performance and all the moving components during the first day of operation.

Check the liquid line sight glass and expansion valve operation. If there is an indication that the system is low on refrigerant, thoroughly check the system for leaks before adding refrigerant.

 

5.

Checklist

Ensure the high low pressure controls are configured

 

properly.

 

Ensure crankcase heater is energized minimum 12

 

hours prior to start up and permanently energized.

Check the refrigerant is correct for intended use.

Check all electrical connections.

Check all electrical termination and circuits are correct.

O-CU06-DEC14-1

7

All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction. Other languages are the translations of the original instructions.

Loading...
+ 15 hidden pages