Daikin ERHQ006BBV3, ERHQ007BBV3, ERHQ008BBV3, ERLQ006BBV3, ERLQ007BBV3 Installation manuals

...
Page 1
INSTALLATION MANUAL
Outdoor unit for air to water heat pump
ERHQ006BBV3 ERHQ007BBV3 ERHQ008BBV3
ERLQ006BBV3 ERLQ007BBV3 ERLQ008BBV3
Page 2
CE - ATITIKTIES-DEKLARACIJA
CE - ATBILSTĪBAS-DEKLARĀCIJA
CE - VYHLÁSENIE-ZHODY
CE - UYUMLULUK-BİLDİRİSİ
CE - IZJAVA O SKLADNOSTI
CE - VASTAVUSDEKLARATSIOON
CE - ДЕКЛАРАЦИЯ-ЗА-СЪОТВЕТСТВИЕ
deklaruje na własną wyłączną odpowiedzialność, że urządzenia, których ta deklaracja dotyczy:
z vso odgovornostjo izjavlja, da je oprema naprav, na katero se izjava nanaša:
kinnitab oma täielikul vastutusel, et käesoleva deklaratsiooni alla kuuluv varustus:
declară pe proprie răspundere că echipamentele la care se referă această declaraţie:
m
o
x
r
18
20
17
19
CE - IZJAVA-O-USKLAĐENOSTI
CE - MEGFELELŐSÉGI-NYILATKOZAT
CE - DEKLARACJA-ZGODNOŚCI
CE - DECLARAŢIE-DE-CONFORMITATE
19 Direktive z vsemi spremembami.
10 Direktiver, med senere ændringer.
visiška savo atsakomybe skelbia, kad įranga, kuriai taikoma ši deklaracija:
ar pilnu atbildību apliecina, ka tālāk aprakstītās iekārtas, uz kurām attiecas šī deklarācija:
vyhlasuje na vlastnú zodpovednosť, že zariadenie, na ktoré sa vzťahuje toto vyhlásenie:
декларира на своя отговорност, че оборудването, за което се отнася тази декларация:
b
21
tamamen kendi sorumluluğunda olmak üzere bu bildirinin ilgili olduğu donanımının aşağıdaki gibi olduğunu beyan eder:
t
v
k
w
23
24
25
22
instrukcjami:
conformitate cu instrucţiunile noastre
инструкции:
16 megfelelnek az alábbi szabvány(ok)nak vagy egyéb irányadó dokumentum(ok)nak, ha azokat előírás szerint használják:
17 spełniają wymogi następujących norm i innych dokumentów normalizacyjnych, pod warunkiem że używane są zgodnie z naszymi
18 sunt în conformitate cu următorul (următoarele) standard(e) sau alt(e) document(e) normativ(e), cu condiţia ca acestea să fie utilizate în
19 skladni z naslednjimi standardi in drugimi normativi, pod pogojem, da se uporabljajo v skladu z našimi navodili:
20 on vastavuses järgmis(t)e standardi(te)ga või teiste normatiivsete dokumentidega, kui neid kasutatakse vastavalt meie juhenditele:
21 съответстват на следните стандарти или други нормативни документи, при условие, че се използват съгласно нашите
s našim návodom:
22 atitinka žemiau nurodytus standartus ir (arba) kitus norminius dokumentus su sąlyga, kad yra naudojami pagal mūsų nurodymus:
23 tad, ja lietoti atbilstoši ražotāja norādījumiem, atbilst sekojošiem standartiem un citiem normatīviem dokumentiem:
24 sú v zhode s nasledovnou(ými) normou(ami) alebo iným(i) normatívnym(i) dokumentom(ami), za predpokladu, že sa používajú v súlade
25 ürünün, talimatlarımıza göre kullanılması koşuluyla aşağıdaki standartlar ve norm belirten belgelerle uyumludur:
01 Directives, as amended.
20 Direktiivid koos muudatustega.
21 Директиви, с техните изменения.
22 Direktyvose su papildymais.
23 Direktīvās un to papildinājumos.
24 Smernice, v platnom znení.
25 Değiştirilmiş halleriyle Yönetmelikler.
Direktiivejä, sellaisina kuin ne ovat muutettuina.
irányelv(ek) és módosításaik rendelkezéseit.
14 v platném znění.
15 Smjernice, kako je izmijenjeno.
16
17 z późniejszymi poprawkami.
11 Direktiv, med företagna ändringar.
12 Direktiver, med foretatte endringer.
13
02 Direktiven, gemäß Änderung.
03 Directives, telles que modifiées.
04 Richtlijnen, zoals geamendeerd.
18 Directivelor, cu amendamentele respective.
05 Directivas, según lo enmendado.
06 Direttive, come da modifica.
07 √‰ËÁÈÒv, fiˆ˜ ¤¯Ô˘Ó ÙÚÔÔÔÈËı›.
08 Directivas, conforme alteração em.
09 Директив со всеми поправками.
<B>
Cертификата <C>.
pagal Sertifikatą <C>.
положително от <B> съгласно
21 Забележка * както е изложено в <A> и оценено
a(z) <C> tanúsítvány szerint.
vērtējumam saskaņā ar sertifikātu <C>.
* kā norādīts <A> un atbilstoši <B> pozitīvajam
22 Pastaba * kaip nustatyta <A> ir kaip teigiamai nuspręsta
23 Piezīmes
de <B> în conformitate cu Certificatul <C>.
<B> i Świadectwem <C>.
<A> DAIKIN.TCF.015N12/02-2011
<B> DEKRA (NB0344)
<C> 74736-KRQ/EMC97-4957
súlade s osvedčením <C>.
<A>‘da belirtildiği gibi ve <C> Sertifikasına
göre <B> tarafından olumlu olarak
değerlendirildiği gibi.
*
Not
24 Poznámka * ako bolo uvedené v <A> a pozitívne zistené <B> v
25
skladu s certifikatom <C>.
kiidetud <B> järgi vastavalt sertifikaadile <C>.
CE - ILMOITUS-YHDENMUKAISUUDESTA
CE - PROHLÁŠENÍ-O-SHODĚ
заявляет, исключительно под свою ответственность, что оборудование, к которому относится настоящее заявление:
erklærer som eneansvarlig, at udstyret, som er omfattet af denne erklæring:
u
q
09
10
CE - FÖRSÄKRAN-OM-ÖVERENSTÄMMELSE
CE - DECLARAÇÃO-DE-CONFORMIDADE
СЕ - ЗАЯВЛЕНИЕ-О-СООТВЕТСТВИИ
CE - OPFYLDELSESERKLÆRING
CE - DICHIARAZIONE-DI-CONFORMITA
CE - ¢H§ø™H ™YMMOPºø™H™
prohlašuje ve své plné odpovědnosti, že zařízení, k němuž se toto prohlášení vztahuje:
izjavljuje pod isključivo vlastitom odgovornošću da oprema na koju se ova izjava odnosi:
deklarerar i egenskap av huvudansvarig, att utrustningen som berörs av denna deklaration innebär att:
erklærer et fullstendig ansvar for at det utstyr som berøres av denne deklarasjon, innebærer at:
s
n
11
12
teljes felelőssége tudatában kijelenti, hogy a berendezések, melyekre e nyilatkozat vonatkozik:
ilmoittaa yksinomaan omalla vastuullaan, että tämän ilmoituksen tarkoittamat laitteet:
c
y
h
j
13
14
15
16
la declaración:
referencia
acordo com as nossas instruções:
инструкциям:
instrukser:
förutsättning att användning sker i överensstämmelse med våra instruktioner:
disse brukes i henhold til våre instrukser:
08 estão em conformidade com a(s) seguinte(s) norma(s) ou outro(s) documento(s) normativo(s), desde que estes sejam utilizados de
09 соответствуют следующим стандартам или другим нормативным документам, при условии их использования согласно нашим
10 overholder følgende standard(er) eller andet/andre retningsgivende dokument(er), forudsat at disse anvendes i henhold til vore
11 respektive utrustning är utförd i överensstämmelse med och följer följande standard(er) eller andra normgivande dokument, under
mukaisesti:
12 respektive utstyr er i overensstemmelse med følgende standard(er) eller andre normgivende dokument(er), under forutssetning av at
13 vastaavat seuraavien standardien ja muiden ohjeellisten dokumenttien vaatimuksia edellyttäen, että niitä käytetään ohjeidemme
14 za předpokladu, že jsou využívány v souladu s našimi pokyny, odpovídají následujícím normám nebo normativním dokumentům:
15 u skladu sa slijedećim standardom(ima) ili drugim normativnim dokumentom(ima), uz uvjet da se oni koriste u skladu s našim uputama:
Low Voltage 2006/95/EC
Electromagnetic Compatibility 2004/108/EC *
19 ob upoštevanju določb:
20 vastavalt nõuetele:
21 следвайки клаузите на:
22 laikantis nuostatų, pateikiamų:
23 ievērojot prasības, kas noteiktas:
24 održiavajúc ustanovenia:
25 bunun koşullarına uygun olarak:
16 Megjegyzés * a(z) <A> alapján, a(z) <B> igazolta a megfelelést,
och godkänts av <B> enligt
tifikatet <C>. Cer
11 Information * enligt <A>
da <B> secondo il Certificato <C>.
06 Nota * delineato nel <A> e giudicato positivamente
19 Opomba * kot je določeno v <A> in odobreno s strani <B> v
17 Uwaga * zgodnie z dokumentacją <A>, pozytywną opinią
18 Notă * aşa cum este stabilit în <A> şi apreciat pozitiv
bedømmelse av <B> ifølge Sertifikat <C>.
hyväksynyt Sertifikaatin <C> mukaisesti.
souladu s osvědčením <C>.
12 Merk * som det fremkommer i <A> og gjennom positiv
13 Huom * jotka on esitetty asiakirjassa <A> ja jotka <B> on
14 Poznámka * jak bylo uvedeno v <A> a pozitivně zjištěno <B> v
положительным решением <B> согласно
·fi ÙÔ <B> Û‡Ìʈӷ Ì ÙÔ ¶ИЫЩФФИЛЩИОfi <C>.
positivo de <B> de acordo com o Certificado <C>.
09 Примечание * как указано в <A> и в соответствии с
07 ™ËÌ›ˆÛË * fiˆ˜ ηıÔÚ›˙ÂÙ·È ÛÙÔ <A> Î·È ÎÚ›ÓÂÙ·È ıÂÙÈο
08 Nota * tal como estabelecido em <A> e com o parecer
20 Märkus * nagu on näidatud dokumendis <A> ja heaks
strane <B> prema Certifikatu <C>.
15 Napomena * kako je izloženo u <A> i pozitivno ocijenjeno od
Свидетельству <C>.
henhold til Certifikat <C>.
10 Bemærk * som anført i <A> og positivt vurderet af <B> i
Jean-Pierre Beuselinck
General Manager
Ostend, 1st of April 2011
declares under its sole responsibility that the equipment to which this declaration relates:
erklärt auf seine alleinige Verantwortung, dass die Ausrüstung für die diese Erklärung bestimmt ist:
déclare sous sa seule responsabilité que l’équipement visé par la présente déclaration:
verklaart hierbij op eigen exclusieve verantwoordelijkheid dat de apparatuur waarop deze verklaring betrekking heeft:
declara bajo su única responsabilidad que el equipo al que hace
dichiara sotto la propria responsabilità che gli apparecchi a cui è riferita questa dichiarazione:
a
d
f
l
e
CE - DECLARATION-OF-CONFORMITY
CE - KONFORMITÄTSERKLÄRUNG
CE - DECLARATION-DE-CONFORMITE
CE - CONFORMITEITSVERKLARING
Daikin Europe N.V.
01
02
i
03
05
04
06
10 under iagttagelse af bestemmelserne i:
11 enligt villkoren i:
12 gitt i henhold til bestemmelsene i:
13 noudattaen määräyksiä:
14 za dodržení ustanovení předpisu:
15 prema odredbama:
16 követi a(z):
17 zgodnie z postanowieniami Dyrektyw:
18 în urma prevederilor:
declara sob sua exclusiva responsabilidade que os equipamentos a que esta declaração se refere:
‰ЛПТУВИ МВ ·ФОПВИЫЩИО‹ ЩЛ˜ В˘ı‡УЛ fiЩИ Ф ВНФПИЫМfi˜ ЫЩФУ ФФ›Ф ·У·К¤ЪВЩ·И Л ·ЪФ‡Ы· ‰‹ПˆЫЛ:
p
g
07
08
ERHQ006BBV3, ERHQ007BBV3, ERHQ008BBV3,
ERLQ006BBV3, ERLQ007BBV3, ERLQ008BBV3,
instructions:
daß sie gemäß unseren Anweisungen eingesetzt werden:
onze instructies:
nuestras instrucciones:
nostre istruzioni:
01 are in conformity with the following standard(s) or other normative document(s), provided that these are used in accordance with our
02 der/den folgenden Norm(en) oder einem anderen Normdokument oder -dokumenten entspricht/entsprechen, unter der Voraussetzung,
03 sont conformes à la/aux norme(s) ou autre(s) document(s) normatif(s), pour autant qu'ils soient utilisés conformément à nos instructions:
04 conform de volgende norm(en) of één of meer andere bindende documenten zijn, op voorwaarde dat ze worden gebruikt overeenkomstig
05 están en conformidad con la(s) siguiente(s) norma(s) u otro(s) documento(s) normativo(s), siempre que sean utilizados de acuerdo con
Û‡Ìʈӷ Ì ÙȘ Ô‰ËÁ›Â˜ Ì·˜:
06 sono conformi al(i) seguente(i) standard(s) o altro(i) documento(i) a carattere normativo, a patto che vengano usati in conformità alle
07 В›У·И Ы‡МКˆУ· МВ ЩФ(·) ·ОfiПФ˘ıФ(·) ЪfiЩ˘Ф(·) ‹ ¿ППФ ¤ББЪ·КФ(·) О·УФУИЫМТУ, ˘fi ЩЛУ ЪФ¸fiıВЫЛ fiЩИ ¯ЪЛЫИМФФИФ‡УЩ·И
01 following the provisions of:
EN60335-2-40,
02 gemäß den Vorschriften der:
03 conformément aux stipulations des:
04 overeenkomstig de bepalingen van:
05 siguiendo las disposiciones de:
06 secondo le prescrizioni per:
07 Ì ًÚËÛË Ùˆv ‰È·Ù¿Íˆv Ùˆv:
08 de acordo com o previsto em:
09 в соответствии с положениями:
according to the Certificate <C>.
beurteilt gemäß Zertifikat <C>.
<B> conformément au Certificat <C>.
<B> overeenkomstig Certificaat <C>.
positivamente por <B> de acuerdo con el
Certificado <C>.
01 Note * as set out in <A> and judged positively by <B>
02 Hinweis * wie in der <A> aufgeführt und von <B> positiv
03 Remarque * tel que défini dans <A> et évalué positivement par
04 Bemerk * zoals vermeld in <A> en positief beoordeeld door
05 Nota * como se establece en <A> y es valorado
3PW68004-1
Page 3
ERHQ006BBV3 ERLQ006BBV3 ERHQ007BBV3 ERLQ007BBV3 ERHQ008BBV3 ERLQ008BBV3
Outdoor unit for air to water heat pump
Installation manual
CONTENTS Page
1. Definitions .................................................................................. 1
1.1. Meaning of warnings and symbols................................................. 1
1.2. Meaning of used terms................................................................... 2
2. General safety precautions........................................................ 2
Warning.......................................................................................... 3
Caution........................................................................................... 3
3. Before installation ......................................................................4
3.1. Scope of the manual ...................................................................... 4
3.2. Precautions for R410A ................................................................... 4
3.3. Installation ...................................................................................... 4
3.4. Model identification......................................................................... 4
3.5. Accessories.................................................................................... 4
3.6. Handling ......................................................................................... 5
4. Overview of unit ......................................................................... 5
4.1. Opening the unit .............................................................................5
4.2. Main components ...........................................................................5
4.3. Functional diagram ......................................................................... 5
5. Selecting installation site ........................................................... 6
5.1. General........................................................................................... 6
5.2. Selecting a location in cold climates .............................................. 7
6. Precautions on installation......................................................... 7
6.1. Foundation work ............................................................................. 7
6.2. Drain work ...................................................................................... 7
General........................................................................................... 7
7. Installation servicing space........................................................ 8
Wall facing one side (unit: mm) ...................................................... 8
Walls facing two sides (unit: mm) ...................................................8
Walls facing three sides (unit: mm)................................................. 8
7.1. Outdoor unit installation drawing ....................................................8
8. Refrigerant pipe size and allowable pipe length ........................9
8.1. Selection of piping material ............................................................ 9
8.2. Refrigerant pipe size ......................................................................9
8.3. Allowable pipe length and height difference ................................... 9
9. Precautions on refrigerant piping............................................... 9
10. Refrigerant piping .................................................................... 10
10.1. Flaring the pipe end .....................................................................10
10.2. Connecting the refrigerant piping to the outdoor unit................... 10
10.3. Refrigerant piping work ................................................................ 10
Pipe handling guidelines ..............................................................10
Selection of copper and heat insulation materials........................ 10
11. Leak test and vacuum drying................................................... 11
11.1. General guidelines ....................................................................... 11
12. Charging refrigerant................................................................. 12
12.1. Important information regarding the refrigerant used................... 12
12.2. Precautions and general guidelines............................................. 12
12.3. Calculating the additional refrigerant............................................ 12
12.4. Complete recharging.................................................................... 13
13. Pump down operation.............................................................. 13
13.1. Pump down procedure................................................................. 13
13.2. Forced cooling operation .............................................................. 13
14. Electrical wiring work ...............................................................13
14.1. Precautions on electrical wiring work........................................... 13
14.2. Internal wiring – Parts table.......................................................... 14
14.3. Connecting power supply and interunit wiring.............................. 14
Notes to observe .......................................................................... 15
14.4. Electrical characteristics............................................................... 15
15. Test operation .......................................................................... 15
15.1. Pre-run checks............................................................................. 15
15.2. Trial operation and testing ............................................................ 16
16. Maintenance and servicing ...................................................... 16
16.1. Service precautions...................................................................... 16
16.2. Service mode operation ............................................................... 16
17. Disposal requirements ............................................................. 16
18. Unit specifications.................................................................... 16
18.1. Technical specifications................................................................ 16
18.2. Electrical specifications................................................................ 16
Thank you for purchasing this product.
The original instructions are written in English. All other languages are translations of the original instructions.
CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION. THEY WILL TELL YOU HOW TO INSTALL AND HOW TO CONFIGURE THE UNIT PROPERLY. KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE.

1. DEFINITIONS

1.1. Meaning of warnings and symbols

Warnings in this manual are classified according to their severity and probability of occurrence.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
NOTICE
Indicates situations that may result in equipment or property-damage accidents only.
INFORMATION
This symbol identifies useful tips or additional information.
Some types of danger are represented by special symbols:
Electric current.
Danger of burning and scalding.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
1
Page 4

1.2. Meaning of used terms

Installation manual:
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual:
Instruction manual specified for a certain product or application, explaining how to operate it.
Maintenance instructions:
Instruction manual specified for a certain product or application, which explains (if relevant) how to install, configure, operate and/or maintain the product or application.
Dealer:
Sales distributor for products as per the subject of this manual.
Installer:
Technical skilled person who is qualified to install products as per the subject of this manual.
User:
Person who is owner of the product and/or operates the product.
Service company:
Qualified company which can perform or coordinate the required service to the unit.
Applicable legislation:
All international, European, national and local directives, laws, regulations and/or codes which are relevant and applicable for a certain product or domain.
Accessories:
Equipment which is delivered with the unit and which needs to be installed according to instructions in the documentation.
Optional equipment:
Equipment which can optionally be combined to the products as per the subject of this manual.
Field supply:
Equipment which needs to be installed according to instructions in this manual, but which are not supplied by Daikin.

2. GENERAL SAFETY PRECAUTIONS

The precautions here, all cover very important topics, so be sure to follow them carefully.
All activities described in this manual shall be carried out by an installer.
Be sure to wear adequate personal protection equipment (protection gloves, safety glasses, …) when performing installation, maintenance or service to the unit.
If not sure of installation procedures or operation of the unit, always contact your local dealer for advice and information.
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Be sure only to use accessories and optional equipment made by Daikin which are specially designed for use with the products as of subject in this manual and have them installed by an installer.
DANGER: ELECTRICAL SHOCK
Switch off all power supply before removing the switch box service panel or before making any connections or touching electrical parts.
To avoid electric shock, be sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main circuit capacitors or electrical parts and, before touching, be sure that those voltages are 50 V DC or less.
When service panels are removed, live parts can easily be touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
Do not touch the refrigerant piping, water piping or internal parts during and immediately after operation. The piping and internal parts may be hot or cold depending on the working condition of the unit.
Your hand may suffer burns or frostbite if you touch the piping or internal parts. To avoid injury, give the piping and internal parts time to return to normal temperature or, if you must touch them, be sure to wear protective gloves.
Installation manual
2
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 5
Warning
Ask your dealer or qualified personnel to carry out installation work. Do not install the machine by yourself. Improper installation may result in water leakage, electric shocks or fire.
Perform installation work in accordance with this installation manual. Improper installation may lead to water leakage, electric shocks or fire.
Consult your local dealer regarding what to do in case of refrigerant leakage. When the unit is to be installed in a small room, it is necessary to take proper measures so that the amount of any leaked refrigerant does not exceed the concentration limit in the event of a leakage. Otherwise, this may lead to an accident due to oxygen depletion.
Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in water leakage, electric shocks, fire, or the unit falling.
Install the unit on a foundation that can withstand its weight. Insufficient strength may result in the fall of equipment and causing injury.
Carry out the specified installation work in consideration of strong winds, typhoons, or earthquakes. Improper installation work may result in accidents due to fall of equipment.
Make certain that all electrical work is carried out by qualified personnel according to the applicable legislation and this installation manual, using a separate circuit. Insufficient capacity of the power supply circuit or improper electrical construction may lead to electric shocks or fire.
Make sure that all wiring is secure, using the specified wires and ensuring that external forces do not act on the terminal connections or wires. Incomplete connection or fixing may cause a fire.
When wiring between the indoor and outdoor units, and wiring the power supply, form the wires so that the frontside panel can be securely fastened. If the frontside panel is not in place, overheat of the terminals, electric shocks or a fire may be caused.
If refrigerant gas leaks during installation work, ventilate the area immediately. Toxic gas may be produced if refrigerant gas comes into contact with fire.
After completing the installation work, check to make sure that there is no leakage of refrigerant gas. Toxic gas may be produced if refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.
When planning to relocate former installed units, you must first recover the refrigerant after the pump down operation. Refer to chapter "13. Pump down operation" on page 13.
Never directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.
Be sure to install an earth leakage circuit breaker in accordance with applicable legislation. Failure to do so may cause electrical shock and fire.
Electrical work must be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice. Insufficient capacity or incomplete electrical work may cause electrical shock or fire.
Be sure to use a dedicated power circuit. Never use a power circuit shared by another appliance.
For wiring, use a cable long enough to cover the entire distance with no connection. Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit. Failure to do so may cause abnormal heat, electric shock, or fire.
During pump down operation, stop the compressor before removing the refrigerant piping. If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the freezer cycle which will lead to breakage and even to injury.
During installation, attach the refrigerant piping securely before running the compressor. If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is running, causing abnormal pressure in the freezer cycle which will lead to breakage and even to injury.
Caution
Earth the unit. Earthing resistance should be according to applicable legislation. Do not connect the earth wire to gas or water pipes, lightning conductor or telephone earth wire. Incomplete earthing may cause electric shocks.
Gas pipe.
Ignition or explosion may occur if the gas leaks.
Water pipe.
Hard vinyl tubes are not effective earths.
Lightning conductor or telephone earth wire.
Electric potential may rise abnormally if struck by a lightning bolt.
Install the indoor and outdoor units, power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise. (Depending on the radio waves, a distance of 1 meter may not be sufficient to eliminate the noise.)
Do not rinse the outdoor unit. This may cause electric shocks or fire.
Do not install the unit in places such as the following:
Where there is mist of mineral oil, oil spray or vapour for
example a kitchen. Plastic parts may deteriorate, and cause them to fall out or
water to leak.
Where corrosive gas, such as sulphurous acid gas, is
produced. Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.
Where there is machinery which emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.
Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile flammables, such as thinner or gasoline, are handled.
Such gases may cause a fire.
Where the air contains high levels of salt such as that near
the ocean.
Where voltage fluctuates a lot, such as in factories.
In vehicles or vessels.
Where acidic or alkaline vapour is present.
Do not allow a child to mount on the outdoor unit or avoid placing
any object on the unit. Falling or tumbling may result in injury.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
3
Page 6
For use of units in applications with temperature alarm settings it is advised to foresee a delay of 10 minutes for signalling the alarm in case the alarm temperature is exceeded. The unit may stop for several minutes during normal operation for "defrosting the unit", or when in "thermostat stop" operation.
Tighten the flare nut according to the specified method such as with a torque wrench. If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.

3. BEFORE INSTALLATION

WARNING
Since maximum working pressure for this outdoor unit is
4.17 MPa or 41.7 bar, pipes of larger wall thickness may be required. Refer to paragraph "8.1. Selection of piping
material" on page 9.
3.4. Model identification
ERLQ units include special equipment (insulation, bottom plate heater,...) to ensure good operation in areas where low ambient temperature can occur together with high humidity conditions. In such conditions the ERHQ models may experience problems with severe ice build up on the aircooled coil. In case such conditions are expected, the ERLQ must be installed instead. These models contain countermeasures (insulation, bottom plate heater,...) to prevent freeze up.
ER H Q 006 BB V3
V3=1~, 230 V, 50 Hz
Series
Capacity class (kW)
Outdoor unit on R410A
H=low water temperature – ambient zone (0~–10°C) L=low water temperature – ambient zone (–10°C~–20°C)
Split outdoor pair heat pump

3.1. Scope of the manual

This manual describes the procedures for handling, installing and connecting ERHQ and ERLQ units. This manual has been prepared to ensure adequate maintenance of the unit, and it will provide help if problems occur.

3.2. Precautions for R410A

The refrigerant requires strict cautions for keeping the system clean, dry and tight.
- Clean and dry Foreign materials (including mineral oils or moisture) should be prevented from getting mixed into the system.
- Tight Read "9. Precautions on refrigerant piping" on page 9 carefully and follow these procedures correctly.
Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state. (If the refrigerant is in state of gas, its composition changes and the system will not work properly).
The connected indoor unit must be the EKHBH/X008 unit designed exclusively for R410A.

3.3. Installation

For installation of the indoor unit, refer to the indoor unit installation manual.
Never operate the unit without the thermistors, burning of the compressor may result.
Be sure to confirm the model name and the serial no. of the outer (front) plates when attaching/detaching the plates to avoid mistakes.
When closing the service panels, take care that the tightening torque does not exceed 4.1 N•m.
INFORMATION
An ERLQ0*BA/BB outdoor unit can only be connected to an EKHBH/X008BA/BB indoor unit (bottom plate heater at outdoor unit has to be controlled by indoor unit).
An ERHQ0*BA/BB outdoor unit can be connected to an EKHBH/X008BA/BB indoor unit or to an EKHBH/ X008AA indoor unit (if a bottom plate heater kit is required, see "Possible options" on page 4).

3.5. Accessories

Check if the following accessories are included with the unit
Installation manual 1
Fluorinated greenhouse gases label
Multilingual fluorinated greenhouse gases label
Possible options
ERHQ Optional kit
ERLQ Standard
(a) Factory mounted.
Optional bottom plate heater
EKHBH/X008AA Possible Not allowed EKHBH/X008BA/BB Possible Possible
1
1
Bottom plate heater
(a)
EKBPHT08 EKBPHT08BA
Installation manual
4
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 7

3.6. Handling

A
B

4.2. Main components

As shown in the figure below, slowly move the unit by grabbing the left and right grips.
A
B
A B
CAUTION
To avoid injury, do not touch the air inlet or aluminium fins of the unit.

4. OVERVIEW OF UNIT

4.1. Opening the unit

2
1
1
2
1 Heat exchanger 2 Fan motor 3 Switch box with main pcb (inverter and control pcb) 4 Terminal communication and power supply 5 Service pcb 6 4-way valve 7 Electronic expansion valve (main) 8 Accumulator
9 Compressor 10 Liquid stop valve 11 Gas stop valve 12 Service port

4.3. Functional diagram

3
4 5
6
7 8
9 10
11 12
1x
3
DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
See "2. General safety precautions" on page 2.
2
1
3
M
4
5
6
5
12
7
8
1011
1 Thermistor (air)
2 Heat exchanger
3 Thermistor (heat exchanger)
4 Fan motor
5 Filter
6 Electronic expansion valve
7 Liquid stop valve
8 Gas stop valve with service port
9 Accumulator 10 Compressor 11 Thermistor (discharge) 12 4-way valve (ON=heating)
Cooling Heating
9
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
5
Page 8

5. SELECTING INSTALLATION SITE

5.1. General

WARNING
Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals.
Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.
The equipment is not intended for use in a potentially explosive atmosphere.
Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbours of the user.
Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
There must be sufficient space for carrying the unit into and out of the site.
There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
The site must be free from the possibility of flammable gas leakage in a nearby place.
Locate the unit so that the noise and the discharged hot air will not annoy the neighbours.
Install units, power cords and inter-unit cables at least 3 m away from television and radio sets. This is to prevent interference to images and sounds.
Depending on radio wave conditions, electromagnetic interference may still occur even if installed more than 3 m away.
In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the outdoor unit.
Since drain flows out of the outdoor unit, do not place anything under the unit which must be kept away from moisture.
Select an installation site where the following conditions are satisfied and that meets with your customer's approval.
- Places which are well-ventilated.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and
vibration and where the unit can be installed level.
- Places where there is no possibility of flammable gas or
product leak.
- The equipment is not intended for use in a potentially
explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the indoor and outdoor units' piping and wiring
lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
- Places where the rain can be avoided as much as possible.
- Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
- Do not place any objects or equipment on top of the unit (top
plate).
- Do not climb, sit or stand on top of the unit,
- Be sure that sufficient precautions are taken, in accordance
with applicable legislation, in case of refrigerant leakage.
When installing the unit in a place exposed to strong wind, pay special attention to the following. Strong winds of 5 m/sec or more blowing against the outdoor unit's air outlet causes short circuit (suction of discharge air), and this may have the following consequences:
- Deterioration of the operational capacity.
- Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks. Refer to the figures for installation of this unit in a place where the wind direction can be foreseen.
Install a baffle plate on the air suction side of the outdoor unit and set the outlet side at a right angle to the direction of the wind:
2
1
3
2
1 Baffle plate 2 Strong wind 3 Discharge air
Prepare a water drainage channel around the foundation, to drain waste water from around the unit.
If the water drainage of the unit is not easy, please build up the unit on a foundation of concrete blocks, etc. (the height of the foundation should be maximum 150 mm).
If you install the unit on a frame, please install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction.
When installing the unit in a place frequently exposed to snow, pay special attention to elevate the foundation as high as possible.
If you install the unit on a building frame, please install a waterproof plate (field supply)(within 150 mm of the underside of the unit) in order to avoid the drain water dripping. (See figure).
Make sure that the unit is installed level.
NOTICE
Units cannot be installed hanging from ceiling or stacked.
Installation manual
6
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 9

5.2. Selecting a location in cold climates

Refer to "3.4. Model identification" on page 4.
NOTICE
When operating the outdoor unit in a low outdoor ambient temperature, be sure to follow the instructions described below.
To prevent exposure to wind, install the outdoor unit with its suction side facing the wall.
Never install the outdoor unit at a site where the suction side may be exposed directly to wind.
To prevent exposure to wind, install a baffle plate on the air discharge side of the outdoor unit.
In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit and set the outlet side at a right angle to the direction of the wind:

6. PRECAUTIONS ON INSTALLATION

6.1. Foundation work

When installing the outdoor unit, please refer to "5. Selecting
installation site" on page 6 to select an appropriate location.
1 Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after installation.
2 Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers
each (field supply).
3 Fix the unit securely by means of the foundation bolts in
accordance with the foundation drawing. It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.
20

6.2. Drain work

3
4
3
1 Construct a large canopy. 2 Construct a pedestal.
Install the unit high enough off the ground to prevent burying in snow.
3 Strong wind 4 Discharge air
1
General
Assure that drain water coming from the outdoor unit during heating operation and defrost operation can be properly evacuated.
Install the unit on a base that can assure a proper drainage in order to avoid ice accumulation.
2
A drain channel can be foreseen under the unit. Be sure that drain water in this drain channel does not freeze causing blockage by ice accumulation.
Avoid drain water flowing over the footpath, so that in case of ambient freezing temperatures the footpath does not become slippery.
NOTICE
If drain holes of the outdoor unit are covered by a mounting base or by floor surface, raise the unit in order to provide a free space of more than 150 mm under the
150 mm
outdoor unit.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
7
Page 10

7. INSTALLATION SERVICING SPACE

330 mm
580 mm
120 mm
4
1
3
2
7
56
Where a wall or other obstacle is in the path of the outdoor unit air intake or exhaust airflow, follow the installation guidelines below.
For any of the installation patterns below, the wall height on the exhaust side should be 1200 mm or less.
Wall facing one side (unit: mm)
>100 >350
1200
Walls facing two sides (unit: mm)

7.1. Outdoor unit installation drawing

>100
>50
>350
Walls facing three sides (unit: mm)
>100
>50
>350
>50
1 Wrap the insulation pipe with finishing tape from bottom to
top.
2 Service cover 3 Stop valve cover 4 250 mm from wall. Allow space for piping and electrical
servicing.
5 If there is danger of the unit falling or overturning, fix the
unit with foundation bolts, or with wire or other means.
6 Distance from the outer side of the stop valve cover 7 If the location does not have good drainage, place the unit
on block bases. Adjust foot height until the unit is levelled. Failure to do so may result in water leakage or accumulation.
Installation manual
8
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 11
8. REFRIGERANT PIPE SIZE AND ALLOWABLE
PIPE LENGTH
DANGER
Piping and other pressure containing parts shall comply with the applicable legislation and shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant.
Installation shall be done by an installer, the choice of materials and installation shall comply with applicable legislation. In Europe the EN378 is the application standard that shall be used.
NOTICE To persons in charge of piping work:
Be sure to open the stop valve after piping installing and vacuming is complete. (Running the system with the valve closed may break the compressor.)
INFORMATION
It is forbidden to discharge refrigerant into the atmosphere. Collect the refrigerant in accordance with the freon collection and destruction law.

8.3. Allowable pipe length and height difference

See the figure and table below concerning allowable lengths and heights. Assume that the longest line in the figure corresponds with the actual longest pipe, and the highest unit in the figure corresponds with the actual highest unit.
L
H
Maximum total one-way piping length
L 30 m
Minimum one-way piping length
L3 m
Maximum height between indoor and outdoor
H 20 m
Chargeless length
L 10 m
H Height
L Length
Allowable pipe length

8.1. Selection of piping material

Construction material: phosphoric acid deoxidised seamless copper for refrigerant.
Temper grade: use piping with temper grade in function of the pipe diameter as listed in table below.
The pipe thickness of the refrigerant piping should comply with applicable legislation. The minimal pipe thickness for R410A piping must be in accordance with the table below.
Temper grade
Pipe Ø
6.4 O 0.80
15.9 O 1.00
O=Annealed
of piping material
Minimal thickness t (mm)

8.2. Refrigerant pipe size

The pipes between outdoor unit and indoor unit should have the same size as the outdoor connections.
Refrigerant pipe size (mm)
Gas pipe Ø15.9
Liquid pipe Ø6.4

9. PRECAUTIONS ON REFRIGERANT PIPING

Do not allow anything other than the designated refrigerant to get mixed into the freezing cycle, such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.
Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose, etc.) that are exclusively used for R410A installations to withstand the pressure and to prevent foreign materials (e.g. mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working. Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr, –755 mm Hg).
In order to prevent dirt, liquid or dust from entering the piping, cure the piping with a pinch or taping. Great caution is needed when passing copper tubes through walls.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Place Installation period Protection method
Outdoor unit
Indoor unit
More than a month Pinch the pipe
Less than a month
Regardless of the
period
Pinch or tape the pipe
Piping should be mounted so that the flare is not subjected to mechanical stress.
Installation manual
9
Page 12

10. REFRIGERANT PIPING

10.1. Flaring the pipe end

To flare each pipe end, follow the procedure below:
1 Cut the pipe end with a pipe cutter.
2 Remove burrs with the cut surface facing downward so that the
chips do not enter the pipe.
1 Cut exactly at right angles. 2 Remove burrs
2 When loosening a flare nut, always use two wrenches together.
When connecting the piping, always use a spanner and torque wrench together to tighten the flare nut to prevent nut cracking and leaks.
1 Torque wrench 2 Spanner 3 Piping union 4 Flare nut
12
4
3
12
3 Remove the flare nut from the stop valve and put the flare nut on
the pipe.
4 Flare the pipe. Set exactly at the position shown below.
A
Conventional flare tool
Flare tool for R410A
(clutch type)
A 0~0.5 mm 1.0~1.5 mm 1.5~2.0 mm
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
5 Check that the flaring is properly made.
1 Flare's inner surface must be flaw-
free.
2 The pipe end must be evenly flared in
a perfect circle.
3 Make sure that the flare nut is fitted.
1 2

10.2. Connecting the refrigerant piping to the outdoor unit

DANGER
Installation shall be done by an installer, the choice of materials and installation shall comply with applicable legislation. In Europe the EN378 is the application standard that shall be used.
CAUTION
Do not use mineral oil on flared part. Mineral oil getting into the system would reduce the lifetime of the units.
Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
Do never install a drier to this R410A unit in order to guarantee its lifetime. The drying material may dissolve and damage the system.
Incomplete flaring may cause refrigerant gas leakage.
1 When connecting the flare nut, coat the flare inner surface with
ether oil or with ester oil and initially tighten 3 or 4 turns by hand before tightening firmly.
Flare nut Flare nut tightening torque
Ø6.4 mm (1/4") 15~17 N•m
Ø15.9 mm (5/8") 63~75 N•m
Valve cap tightening torque
Valve cap Gas pipe
Ø6.4 mm (1/4") 21.6~27.4 N•m
Ø15.9 mm (5/8") 44.1~53.9 N•m
Service port cap tightening torque
10.8~14.7 N•m

10.3. Refrigerant piping work

Pipe handling guidelines
All pipe bends should be as gentle as possible. Use a pipe bender for bending.
3
Bending radius should be 30 to 40 mm or larger.
Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following:
Insulation material: polyethylene foam Heat transfer rate: 0.041 to 0.052 W/mK (0.035 to 0.045 kcal/ mh°C) Refrigerant gas pipe's surface temperature reaches 110°C max. Choose heat insulation materials that will withstand this temperature.
Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.
Pipe size Pipe insulation
Outer diameter Thickness Inner diameter Thickness
6.4 mm (1/4") 0.8 mm 8-10 mm 10 mm
15.9 mm (5/8") 1.0 mm 16-20 mm 13 mm
2
1 6 5
1 Gas pipe 2 Inter-unit wiring 3 Liquid pipe 4 Liquid pipe insulation 5 Finishing tape 6 Gas pipe insulation
Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
3 4
Installation manual
10
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 13

11. LEAK TEST AND VACUUM DRYING

When all piping work is complete and the outdoor unit is connected to the indoor unit, it is necessary to:
check for any leakages in the refrigerant piping
to perform vacuum drying to remove all moisture in the
refrigerant piping.
If there is a possibility of moisture being present in the refrigerant piping (for example, rainwater may have entered the piping), first carry out the vacuum drying procedure below until all moisture has been removed.
All refrigerant pipe joints should be tightened with a torque
wrench at the specified tightening torque. See "10.2. Connecting
the refrigerant piping to the outdoor unit" on page 10 for details.
14
8
2 3
10
5

11.1. General guidelines

All piping inside the unit has been factory tested for leaks.
Use a 2-stage vacuum pump with a non-return valve which can
evacuate to a gauge pressure of –100.7 kPa (5 Torr absolute, –755 mm Hg).
Connect the vacuum pump to the service port of the gas stop valve.
NOTICE
Make sure that the gas stop valve and liquid stop valve are firmly closed before performing the leak test or vacuum drying.
Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
WARNING
Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
INFORMATION
Do not purge the air with refrigerants. Use a vacuum pump to evacuate the installation.
If using additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump, then charge additional refrigerant.
Use a hexagonal wrench (4 mm) to operate the stop valve rod.
6
7 8 9
1 Pressure meter 2 Gauge manifold 3 Low-pressure valve (Lo) 4 High-pressure valve (Hi) 5 Charging hoses 6 Vacuum pump 7 Service port 8 Valve lids 9 Gas stop valve
10 Liquid stop valve
1 Connect the projection side (on which the worm pin is pressed)
of the charging hose coming from the gauge manifold to the gas stop valve's service port.
2 Fully open the gauge manifold's low-pressure valve (Lo) and
completely close its high-pressure valve (Hi). The high-pressure valve subsequently requires no operation.
3 Apply vacuum pumping. Check that the compound pressure
gauge reads –0.1 MPa (–760 mm Hg).
Pipe length
≤≤≤≤15 m >15 m
Run time 10 minutes 15 minutes
4 Close the gauge manifold's low-pressure valve (Lo) and stop the
vacuum pump. Leave as is for 4-5 minutes and make sure that the coupling
meter needle does not go back.
NOTICE
If the meter needle does go back, this may indicate presence of moisture or leaking from connecting parts. Repeat steps 2 through 4 after checking all connecting parts and slightly loosening and retightening the nuts.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
5 Remove the covers from the liquid stop valve and gas stop valve.
6 Turn the liquid stop valve's rod 90 degrees counterclockwise with
a hexagonal wrench to open the valve. Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit's flare and the outdoor unit's flare and the valve rods. After the check is complete, wipe all soapy water off.
7 Disconnect the charging hose from the gas stop valve's service
port, then fully open the liquid and gas stop valves. Do not attempt to turn the valve rod beyond its stop.
8 Tighten the valve lids and service port caps for the liquid and
gas stop valves with a torque wrench at the specified torques. See "10.2. Connecting the refrigerant piping to the outdoor unit"
on page 10 for details.
Installation manual
11
Page 14
INFORMATION
After opening the stop valve, it is possible that the pressure in the refrigerant piping does not rise. This might be caused by e.g. the closed state of the expansion valve in the outdoor unit circuit, but does not present any problem for correct operation of the unit.

12. CHARGING REFRIGERANT

This outdoor unit is factory charged.

12.2. Precautions and general guidelines

CAUTION
When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid hammer.
WARNING
Refrigerant cylinders shall be opened slowly.
Always use protective gloves and protect your eyes
when charging refrigerant.

12.1. Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A
(1)
GWP
value: 1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
■➀ the factory refrigerant charge of the product,
■➁ the additional refrigerant amount charged in the field and
■➀+➁ the total refrigerant charge
on the fluorinated greenhouse gases label supplied with the product.
The filled out label must be adhered on the inside of the product and in the proximity of the product charging port (e.g. on the inside of the service cover).
4
1
2
3
5
6
1 Factory refrigerant charge of the product:
see unit name plate
2 Additional refrigerant amount charged in the field 3 Total refrigerant charge 4 Contains fluorinated greenhouse gases covered by the
Kyoto Protocol
5 Outdoor unit 6 Refrigerant cylinder and manifold for charging
INFORMATION
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. Therefore, an additional multilingual fluorinated greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that label.
DANGER
When the power is on, please close the front panel when leaving the unit unattended.
Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant (R410A) is charged.
Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe. Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant composition to change, preventing normal operation.
Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or not (the cylinder should be marked with "liquid filling siphon attached" or something similar).
Charge the liquid refrigerant with the cylinder in upright position.
Charge the liquid refrigerant with the cylinder in up-side-down position.
Be sure to use tools exclusively for R410A to ensure required pressure resistance and to prevent foreign materials from mixing into the system.

12.3. Calculating the additional refrigerant

It is not necessary to charge additionally if the piping length is under 10 m.
If the piping length is over 10 m please determine the additional amount of refrigerant to be charged using the formula below.
R=(total length (m) of liquid piping – 10 m) x 0.02
R=additional charge (kg)(rounded in units of 0.01 kg)
Determine the weight of refrigerant to be charged additionally and fill in the amount in the service sticker on the rear side of the stop valve cover.
To avoid compressor breakdown. Do not charge the refrigerant more than the specified amount.
This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant.
Installation manual
12
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 15

12.4. Complete recharging

NOTICE
Before recharging, make sure to execute vacuum drying of the internal piping of the unit as well.
In case complete recharging is required, refer to the nameplate of the unit. The nameplate states the type of refrigerant and necessary amount.
Total charging amount <unit: kg>
Charge of refrigerant (kg) depends on total liquid piping length.
Total refrigerant charge=1.7 kg + (total length (m) of liquid piping–10 m) x 0.02
Remark: Factory refrigerant charge is 1.7 kg.

13. PUMP DOWN OPERATION

In order to protect the environment, be sure to pump down when relocating or disposing of the unit. The pump down operation will extract all refrigerant from the piping into the outdoor unit.

13.1. Pump down procedure

1 Remove the valve lid from liquid stop valve and gas stop valve.
2 Carry out the forced cooling operation.
3 After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<–10°C)), close the liquid stop valve with a hexagonal wrench.
NOTICE
Take care that while running forced cooling operation the water temperature remains higher than 5°C (see temperature read out of the indoor unit). You can achieve this, for example, by activating all fans of the fan coil units.

14. ELECTRICAL WIRING WORK

WARNING
All wiring must be performed by an authorized electrician.
Electrical connections shall be made to fixed wiring.
All components procured on the site and all electric
construction shall comply with the applicable legislation.
DANGER: HIGH VOLTAGE
To avoid electrical shock, make sure to disconnect the power supply 1 minute or more before servicing the electrical parts. Even after 1 minute, always measure the voltage at the terminals of main circuit capacitors or electrical parts and, before touching, make sure that those voltages are 50 V DC or less.
NOTICE To persons in charge of electrical wiring work:
Do not operate the unit until the refrigerant piping is complete. (Running it before the piping is ready will break the compressor.)
4 After 2-3 minutes, close the gas stop valve and stop forced
cooling operation.
1 Gas stop valve 2 Close 3 Hexagonal wrench 4 Valve lid 5 Liquid stop valve
1
5
2

13.2. Forced cooling operation

1 Press the forced operation switch SW1 to begin forced cooling.
2 Press the forced operation switch SW1 again to stop forced
cooling.
S102
S2
LED-A
ABCD
SW4
ON
SW1
1
1 Forced operation switch SW1

14.1. Precautions on electrical wiring work

DANGER
3
4
4
Use only copper wires.
A main switch or other means for disconnection, having a
Never squeeze bundled cables into a unit.
Fix cables so that cables do not make contact with the pipes
Secure the electrical wiring with cable ties as shown in the figure
When installing the earth leakage circuit breaker make sure that
The power supply cable and circuit breaker must be selected in
Do not use tapped wires, stranded conductor wires (see caution
Before obtaining access to terminal devices, all supply
circuits must be interrupted.
Be sure to install an earth leakage circuit breaker in accordance with applicable legislation. Failure to do so may cause electrical shock.
Do not turn on the main switch until all the wiring is completed.
contact separation in all poles, must be incorporated in the fixed wiring in accordance with applicable legislation.
(especially on high pressure side).
in chapter "14.3. Connecting power supply and interunit wiring"
on page 14 so that it does not come in contact with the piping,
particularly on the high-pressure side. Make sure no external pressure is applied to the terminal connectors.
it is compatible with the inverter (resistant to high frequency electrical noise) to avoid unnecessary opening of the earth leakage circuit breaker.
accordance with applicale legislation.
1 under "Notes to observe" on page 15), extension cords, or connections from a star system, as they may cause overheating, electrical shock or fire.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
13
Page 16
Do not use locally purchased electrical parts inside the product and do not branch the power for the heater tape, etc., from the terminal block. Doing this may cause electrical shock or fire.
As this unit is equipped with an inverter, installing a phase advancing capacitor not only will deteriorate power factor improvement effect, but also may cause capacitor abnormal heating accident due to high-frequency waves. Therefore, never install a phase advancing capacitor.
CAUTION
Be sure to install the required fuses or circuit breakers.
(1)
This equipment complies with EN/IEC 61000-3-11 that the system impedance Z
is less than or equal to Z
sys
provided
at
max
the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a system impedance Z
equal to Z
max
. Z
max
=0.42 Ω
Equipment complying with EN/IEC 61000-3-12
less than or
sys
(2)
14.2. Internal wiring – Parts table
AC1,AC2 ........................... Connector
E1,E2 ................................ Connector
E1H .............................* .... Bottom plate heater
FU1 ................................... Fuse 30 A
FU2,FU3............................ Fuse 3.15 A
FU4,FU5......................* .... Fuse 1 A 250 V
HR1,HR2........................... Connector
L ........................................ Live
L1R.................................... Reactor
LED A................................ Pilot lamp
M1C................................... Compressor motor
M1F................................... Fan motor
MRM10,MRM20,MRC/W .. Magnetic relay
N........................................ Neutral
PCB1,PCB2 ...................... Printed circuit board
PM1................................... Power module
Q1L ................................... Overload protector
R1T~R3T .......................... Thermistor
S2~S102 ...........................Connector
SA2 ................................... Surge arrester
Sheet metal....................... Terminal strip fixed plate
SW1 .................................. Forced operation ON/OFF switch
SW4 .................................. Local setting switch
U........................................ Connector
V........................................ Connector
V2,V3,V5,V9,V100 ............ Varistor
W....................................... Connector
X11A,X12A........................ Connector
X1M,X2M .......................... Terminal strip
Y1E.................................... Electronic expansion valve voil
Y1R ...................................Reversing solenoid valve coil
Z1C~Z7C........................... Ferrite core
* Only for ERLQ

14.3. Connecting power supply and interunit wiring

1 Strip the insulation from the wire (20 mm).
2 Connect the connection wires between the indoor and outdoor
units so that the terminal numbers match (see wiring diagram below). Tighten the terminal screws securely. We recommend a flathead screwdriver to tighten the screws. See also caution 2 under "Notes to observe" on page 15 for wiring guidelines.
123
123
LN
123
1 2 3
H05VV
1 4 53
1 Interconnection between indoor unit and outdoor unit:
when wire length exceeds 10 m, use Ø2.5 mm wires instead of Ø1.5 mm wires.
2 Power supply cable
(refer to the unit nameplate for maximum running current)
3 Earth 4 Safety breaker 5 Earth leakage circuit breaker
3 Earth terminal installation
WARNING
This unit must be earthed. For earthing, follow the applicable local standard for
electrical installations.
Use the following method when installing single core wires.
23
A'A
3
1
1 Single core wire 2 Screw 3 Flat washer
Use the following method when using round crimp-style terminals.
23
B
B
1
1 Round crimp-style terminal 2 Screw 3 Flat washer
1
AA'
2
50 Hz 230 V
321
(1) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current 75 A.
(2) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems with input current >16 A and 75 A per phase.
Installation manual
14
4 Pull the connected wire and make sure that it does not
disconnect. Then fix the wires in place in the wire clamp. See also "Notes to observe" on page 15.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 17
Notes to observe

14.4. Electrical characteristics

Observe the notes mentioned below when wiring to the power supply terminal board.
1 2
123
L N
4
4
C
B
A3
5
1 Interconnection
Only if bottom plate heater applicable (optional for ERHQ)
2 Power supply cable
3 Bottom plate heater power supply cable 4 Tie wrap 5 Bottom plate heater cable
Use the specified wire type and connect it securely (A).
Firmly secure the wire clamp so that wire terminations do not
receive external stress (B).
Shape wires so that the service cover and stop valve cover fit securely (C).
CAUTION
1. In case the use of stranded conductor wires is
unavoidable for one reason or another, make sure to install round crimp-style terminals on the tip. Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool.
21
1 Stranded conductor wire 2 Round crimp-style terminal
CAUTION
Select all cables and wire sizes in accordance with applicable legislation.
CAUTION
After finishing the electrical work, confirm that each electric part and terminal inside the electric part box is connected securely.
The wiring diagram can be found on the inside of the front plate of the unit.

15. TEST OPERATION

DANGER
Never leave the unit unattended during installation or servicing. When the service panel is removed live parts can be easily touched by accident..
INFORMATION
Note that during the first running period of the unit, required power input may be higher than stated on the nameplate of the unit. This phenomenon originates from the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption.

15.1. Pre-run checks

Check Symptom
Outdoor unit is installed properly
on solid base.
No refrigerant gas leaks. Incomplete cooling/heating
Refrigerant gas and liquid pipes
are thermally insulated.
System is properly earthed. Electrical leakage
The specified wires are used for
interconnecting wire connections.
Outdoor unit air intake and
exhaust is free of obstructions. Stop valves are opened.
Fall, vibration, noise
function
Water leakage
Inoperative or burn damage
Incomplete cooling/heating function
2. When connecting the connection wires to the terminal
board using a single core wire, be sure to perform curling.
Not executing the connections properly may cause heat and fire. Strip the wire at terminal block:
1 Strip wire end to this point 2 Excessive strip length may cause electrical
shock or leakage.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
15
Page 18

15.2. Trial operation and testing

1 Measure the voltage at the primary side of the safety breaker.
Check that it is 230 V.
2 Carry out the test operation in accordance with the indoor
installation manual and operation manual to ensure that all functions and parts are working properly.
INFORMATION
If the circuit breaker trips to shut off the power to the outdoor unit, the system will restore the original operation mode when the power supply is restored. See installation manual, chapter "Field settings" of the indoor unit for more details.
INFORMATION
Instruct the customer how to operate the unit correctly.
NOTICE
For applications with benefit kWh rate power supply
The outdoor unit power supply (L, N) interruption may not be longer than 2 hours to guarantee optimized startup condition for compressor. See installation manual of the indoor unit for more details.

16. MAINTENANCE AND SERVICING

16.1. Service precautions

In order to ensure optimal operation of the unit, a number of checks and inspections should be carried out on the unit at regular intervals, preferably yearly.
This maintenance shall be carried out by the installer or service agent.
DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
DANGER: DO NOT TOUCH PIPING AND INTERNAL PA RT S
See "2. General safety precautions" on page 2.
Do not touch live parts for 10 minutes after the power supply is turned off because of high voltage risk.
Make sure that the power supply is turned off before performing the maintenance work. The heater of the compressor may operate even in stop mode.
The outdoor fan may rotate due to strong backblow wind, causing the capacitor to charge. This may result in an electric shock.
After maintenance, make sure the outdoor fan connector is connected again. Otherwise, the unit may break down.

16.2. Service mode operation

Refer to the service manual to carry out any service mode operation.

17. DISPOSAL REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, of oil and of other parts must be done in accordance with applicable legislation.

18. UNIT SPECIFICATIONS

18.1. Technical specifications
Casing material Painted galvanised steel Dimensions hxwxd (mm) 735x825x300 Weight (kg) 57 Operation range
• cooling (min./max.) (°C) 10/43
• heating (min./max.) (°C) –15/25
• domestic hot water (min./max.)
Refrigerant oil Daphne FVC68D Piping connection
• liquid (mm) 6.4
• gas (mm) 15.9
18.2. Electrical specifications
Phase 1~ Frequency (Hz) 50 Voltage range
• minimum (V) 207
• maximum (V) 253
(°C) –15/35
CAUTION
Do not rinse the outdoor unit. This may cause electric shocks or fire.
NOTICE
Touch a metal part by hand (such as the stop valve) in order to eliminate static electricity and to protect the PCB before performing service.
Please note that some sections of the electric component box are extremely hot.
Make sure you do not touch a conductive section.
After measuring the residual voltage, pull out the outdoor fan
connector.
Installation manual
16
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 19
Page 20
4PW68002-1A 03.2011
Copyright 2011 Daikin
Loading...