The original instructions are written in English. All other languages
are translations of the original instructions.
CAREFULLY READ THESE INSTRUCTIONS BEFORE
INSTALLATION. THEY WILL TELL YOU HOW TO INSTALL
AND HOW TO CONFIGURE THE UNIT PROPERLY.
KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE
REFERENCE.
1. DEFINITIONS
1.1. Meaning of warnings and symbols
Warnings in this manual are classified according to their severity and
probability of occurrence.
DANGER
Indicates an imminently hazardous situation which, if not
avoided, will result in death or serious injury.
WARNING
Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also
be used to alert against unsafe practices.
NOTICE
Indicates situations that may result in equipment or
property-damage accidents only.
INFORMATION
This symbol identifies useful tips or additional information.
Some types of danger are represented by special symbols:
Electric current.
Danger of burning and scalding.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
1
Page 4
1.2. Meaning of used terms
Installation manual:
Instruction manual specified for a certain product or application,
explaining how to install, configure and maintain it.
Operation manual:
Instruction manual specified for a certain product or application,
explaining how to operate it.
Maintenance instructions:
Instruction manual specified for a certain product or application,
which explains (if relevant) how to install, configure, operate and/or
maintain the product or application.
Dealer:
Sales distributor for products as per the subject of this manual.
Installer:
Technical skilled person who is qualified to install products as per the
subject of this manual.
User:
Person who is owner of the product and/or operates the product.
Service company:
Qualified company which can perform or coordinate the required
service to the unit.
Applicable legislation:
All international, European, national and local directives, laws,
regulations and/or codes which are relevant and applicable for a
certain product or domain.
Accessories:
Equipment which is delivered with the unit and which needs to be
installed according to instructions in the documentation.
Optional equipment:
Equipment which can optionally be combined to the products as per
the subject of this manual.
Field supply:
Equipment which needs to be installed according to instructions in
this manual, but which are not supplied by Daikin.
2.GENERALSAFETYPRECAUTIONS
The precautions here, all cover very important topics, so be sure to
follow them carefully.
All activities described in this manual shall be carried out by an
installer.
Be sure to wear adequate personal protection equipment (protection
gloves, safety glasses, …) when performing installation, maintenance
or service to the unit.
If not sure of installation procedures or operation of the unit, always
contact your local dealer for advice and information.
Improper installation or attachment of equipment or accessories
could result in electric shock, short-circuit, leaks, fire or other damage
to the equipment. Be sure only to use accessories and optional
equipment made by Daikin which are specially designed for use with
the products as of subject in this manual and have them installed by
an installer.
DANGER: ELECTRICAL SHOCK
Switch off all power supply before removing the switch box
service panel or before making any connections or
touching electrical parts.
To avoid electric shock, be sure to disconnect the power
supply 1 minute or more before servicing the electrical
parts. Even after 1 minute, always measure the voltage at
the terminals of main circuit capacitors or electrical parts
and, before touching, be sure that those voltages are
50 V DC or less.
When service panels are removed, live parts can easily be
touched by accident. Never leave the unit unattended
during installation or servicing when the service panel is
removed.
DANGER: DO NOT TOUCH PIPING AND INTERNAL
PA RT S
Do not touch the refrigerant piping, water piping or internal
parts during and immediately after operation. The piping
and internal parts may be hot or cold depending on the
working condition of the unit.
Your hand may suffer burns or frostbite if you touch the
piping or internal parts. To avoid injury, give the piping and
internal parts time to return to normal temperature or, if
you must touch them, be sure to wear protective gloves.
Installation manual
2
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 5
Warning
■Ask your dealer or qualified personnel to carry out installation
work. Do not install the machine by yourself.
Improper installation may result in water leakage, electric shocks
or fire.
■Perform installation work in accordance with this installation
manual.
Improper installation may lead to water leakage, electric shocks
or fire.
■Consult your local dealer regarding what to do in case of
refrigerant leakage. When the unit is to be installed in a small
room, it is necessary to take proper measures so that the
amount of any leaked refrigerant does not exceed the
concentration limit in the event of a leakage. Otherwise, this may
lead to an accident due to oxygen depletion.
■Be sure to use only the specified accessories and parts for
installation work.
Failure to use the specified parts may result in water leakage,
electric shocks, fire, or the unit falling.
■Install the unit on a foundation that can withstand its weight.
Insufficient strength may result in the fall of equipment and
causing injury.
■Carry out the specified installation work in consideration of
strong winds, typhoons, or earthquakes.
Improper installation work may result in accidents due to fall of
equipment.
■Make certain that all electrical work is carried out by qualified
personnel according to the applicable legislation and this
installation manual, using a separate circuit.
Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or fire.
■Make sure that all wiring is secure, using the specified wires and
ensuring that external forces do not act on the terminal
connections or wires.
Incomplete connection or fixing may cause a fire.
■When wiring between the indoor and outdoor units, and wiring
the power supply, form the wires so that the frontside panel can
be securely fastened.
If the frontside panel is not in place, overheat of the terminals,
electric shocks or a fire may be caused.
■If refrigerant gas leaks during installation work, ventilate the area
immediately.
Toxic gas may be produced if refrigerant gas comes into contact
with fire.
■After completing the installation work, check to make sure that
there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the room
and comes into contact with a source of fire, such as a fan
heater, stove or cooker.
■When planning to relocate former installed units, you must first
recover the refrigerant after the pump down operation. Refer to
chapter "13. Pump down operation" on page 13.
■Never directly touch any accidental leaking refrigerant. This
could result in severe wounds caused by frostbite.
■Be sure to install an earth leakage circuit breaker in accordance
with applicable legislation. Failure to do so may cause electrical
shock and fire.
■Electrical work must be carried out in accordance with the
installation manual and the national electrical wiring rules or
code of practice.
Insufficient capacity or incomplete electrical work may cause
electrical shock or fire.
■Be sure to use a dedicated power circuit. Never use a power
circuit shared by another appliance.
■For wiring, use a cable long enough to cover the entire distance
with no connection. Do not use an extension cord. Do not put
other loads on the power supply, use a dedicated power circuit.
Failure to do so may cause abnormal heat, electric shock, or fire.
■During pump down operation, stop the compressor before
removing the refrigerant piping.
If the compressor is still running and the stop valve is open
during pump-down, air will be sucked in when the refrigerant
piping is removed, causing abnormal pressure in the freezer
cycle which will lead to breakage and even to injury.
■During installation, attach the refrigerant piping securely before
running the compressor.
If the compressor is not attached and the stop valve is open
during pump-down, air will be sucked in when the compressor is
running, causing abnormal pressure in the freezer cycle which
will lead to breakage and even to injury.
Caution
■Earth the unit.
Earthing resistance should be according to applicable
legislation.
Do not connect the earth wire to gas or water pipes,
lightning conductor or telephone earth wire.
Incomplete earthing may cause electric shocks.
■ Gas pipe.
Ignition or explosion may occur if the gas leaks.
■ Water pipe.
Hard vinyl tubes are not effective earths.
■ Lightning conductor or telephone earth wire.
Electric potential may rise abnormally if struck by a lightning
bolt.
■Install the indoor and outdoor units, power wire and connecting
wire at least 1 meter away from televisions or radios to prevent
image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not
be sufficient to eliminate the noise.)
■Do not rinse the outdoor unit. This may cause electric shocks or
fire.
■Do not install the unit in places such as the following:
■ Where there is mist of mineral oil, oil spray or vapour for
example a kitchen.
Plastic parts may deteriorate, and cause them to fall out or
water to leak.
■ Where corrosive gas, such as sulphurous acid gas, is
produced.
Corrosion of copper pipes or soldered parts may cause the
refrigerant to leak.
■ Where there is machinery which emits electromagnetic
waves.
Electromagnetic waves may disturb the control system, and
cause malfunction of the equipment.
■ Where flammable gases may leak, where carbon fiber or
ignitable dust is suspended in the air or where volatile
flammables, such as thinner or gasoline, are handled.
Such gases may cause a fire.
■ Where the air contains high levels of salt such as that near
the ocean.
■ Where voltage fluctuates a lot, such as in factories.
■ In vehicles or vessels.
■ Where acidic or alkaline vapour is present.
■Do not allow a child to mount on the outdoor unit or avoid placing
any object on the unit. Falling or tumbling may result in injury.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
3
Page 6
■For use of units in applications with temperature alarm settings it
is advised to foresee a delay of 10 minutes for signalling the
alarm in case the alarm temperature is exceeded. The unit may
stop for several minutes during normal operation for "defrosting
the unit", or when in "thermostat stop" operation.
■Tighten the flare nut according to the specified method such as
with a torque wrench.
If the flare nut is tightened too hard, the flare nut may crack after
a long time and cause refrigerant leakage.
3.BEFOREINSTALLATION
WARNING
Since maximum working pressure for this outdoor unit is
4.17 MPa or 41.7 bar, pipes of larger wall thickness may be
required. Refer to paragraph "8.1. Selection of piping
material" on page 9.
3.4. Model identification
ERLQ units include special equipment (insulation, bottom plate
heater,...) to ensure good operation in areas where low ambient
temperature can occur together with high humidity conditions. In such
conditions the ERHQ models may experience problems with severe
ice build up on the aircooled coil. In case such conditions are
expected, the ERLQ must be installed instead. These models contain
countermeasures (insulation, bottom plate heater,...) to prevent
freeze up.
ERHQ006BBV3
V3=1~, 230 V, 50 Hz
Series
Capacity class (kW)
Outdoor unit on R410A
H=low water temperature – ambient zone (0~–10°C)
L=low water temperature – ambient zone (–10°C~–20°C)
Split outdoor pair heat pump
3.1. Scope of the manual
This manual describes the procedures for handling, installing and
connecting ERHQ and ERLQ units. This manual has been prepared
to ensure adequate maintenance of the unit, and it will provide help if
problems occur.
3.2. Precautions for R410A
■The refrigerant requires strict cautions for keeping the system
clean, dry and tight.
- Clean and dry
Foreign materials (including mineral oils or moisture) should be
prevented from getting mixed into the system.
- Tight
Read "9. Precautions on refrigerant piping" on page 9 carefully
and follow these procedures correctly.
■Since R410A is a mixed refrigerant, the required additional
refrigerant must be charged in its liquid state. (If the refrigerant is
in state of gas, its composition changes and the system will not
work properly).
■The connected indoor unit must be the EKHBH/X008 unit
designed exclusively for R410A.
3.3. Installation
■For installation of the indoor unit, refer to the indoor unit
installation manual.
■Never operate the unit without the thermistors, burning of the
compressor may result.
■Be sure to confirm the model name and the serial no. of the
outer (front) plates when attaching/detaching the plates to avoid
mistakes.
■When closing the service panels, take care that the tightening
torque does not exceed 4.1 N•m.
INFORMATION
■An ERLQ0*BA/BB outdoor unit can only be
connected to an EKHBH/X008BA/BB indoor unit
(bottom plate heater at outdoor unit has to be
controlled by indoor unit).
■An ERHQ0*BA/BB outdoor unit can be connected to
an EKHBH/X008BA/BB indoor unit or to an EKHBH/
X008AA indoor unit (if a bottom plate heater kit is
required, see "Possible options" on page 4).
3.5. Accessories
■Check if the following accessories are included with the unit
As shown in the figure below, slowly move the unit by grabbing the
left and right grips.
A
B
AB
CAUTION
To avoid injury, do not touch the air inlet or aluminium fins
of the unit.
4.OVERVIEWOFUNIT
4.1. Opening the unit
2
1
1
2
1 Heat exchanger
2 Fan motor
3 Switch box with main pcb (inverter and control pcb)
4 Terminal communication and power supply
5 Service pcb
6 4-way valve
7 Electronic expansion valve (main)
8 Accumulator
9 Compressor
10 Liquid stop valve
11 Gas stop valve
12 Service port
■Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.
■Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.
■The equipment is not intended for use in a potentially explosive
atmosphere.
■Choose a place solid enough to bear the weight and vibration of
the unit, where the operation noise will not be amplified.
■Choose a location where the hot air discharged from the unit or
the operation noise will not cause a nuisance to the neighbours
of the user.
■Avoid places near a bedroom and the like, so that the operation
noise will cause no trouble.
■There must be sufficient space for carrying the unit into and out
of the site.
■There must be sufficient space for air passage and no
obstructions around the air inlet and the air outlet.
■The site must be free from the possibility of flammable gas
leakage in a nearby place.
■Locate the unit so that the noise and the discharged hot air will
not annoy the neighbours.
■Install units, power cords and inter-unit cables at least 3 m away
from television and radio sets. This is to prevent interference to
images and sounds.
■Depending on radio wave conditions, electromagnetic
interference may still occur even if installed more than 3 m away.
■In coastal areas or other places with salty atmosphere of sulfate
gas, corrosion may shorten the life of the outdoor unit.
■Since drain flows out of the outdoor unit, do not place anything
under the unit which must be kept away from moisture.
■Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.
- Places which are well-ventilated.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and
vibration and where the unit can be installed level.
- Places where there is no possibility of flammable gas or
product leak.
- The equipment is not intended for use in a potentially
explosive atmosphere.
- Places where servicing space can be well ensured.
- Places where the indoor and outdoor units' piping and wiring
lengths come within the allowable ranges.
- Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
- Places where the rain can be avoided as much as possible.
- Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a
lot of dust is created, the unit must be covered.
- Do not place any objects or equipment on top of the unit (top
plate).
- Do not climb, sit or stand on top of the unit,
- Be sure that sufficient precautions are taken, in accordance
with applicable legislation, in case of refrigerant leakage.
■When installing the unit in a place exposed to strong wind, pay
special attention to the following.
Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
- Deterioration of the operational capacity.
- Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.
■Install a baffle plate on the air suction side of the outdoor unit
and set the outlet side at a right angle to the direction of the
wind:
2
1
3
2
1 Baffle plate
2 Strong wind
3 Discharge air
■Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.
■If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the
foundation should be maximum 150 mm).
■If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the
invasion of water from the lower direction.
■When installing the unit in a place frequently exposed to snow,
pay special attention to elevate the foundation as high as
possible.
■If you install the unit on a building frame,
please install a waterproof plate (field
supply)(within 150 mm of the underside of
the unit) in order to avoid the drain water
dripping. (See figure).
■Make sure that the unit is installed level.
NOTICE
Units cannot be installed hanging from ceiling or stacked.
Installation manual
6
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 9
5.2. Selecting a location in cold climates
Refer to "3.4. Model identification" on page 4.
NOTICE
When operating the outdoor unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below.
■To prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.
■Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.
■To prevent exposure to wind, install a baffle plate on the air
discharge side of the outdoor unit.
■In heavy snowfall areas it is very important to select an
installation site where the snow will not affect the unit and set the
outlet side at a right angle to the direction of the wind:
6.PRECAUTIONSONINSTALLATION
6.1. Foundation work
When installing the outdoor unit, please refer to "5. Selecting
installation site" on page 6 to select an appropriate location.
1Check the strength and level of the installation ground so that
the unit will not cause any operating vibration or noise after
installation.
2Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers
each (field supply).
3Fix the unit securely by means of the foundation bolts in
accordance with the foundation drawing.
It is best to screw in the foundation bolts until their length are
20 mm from the foundation surface.
20
6.2. Drain work
3
4
3
1 Construct a large canopy.
2 Construct a pedestal.
Install the unit high enough off the ground to prevent
burying in snow.
3 Strong wind
4 Discharge air
1
General
Assure that drain water coming from the outdoor unit during heating
operation and defrost operation can be properly evacuated.
■Install the unit on a base that can assure a proper drainage in
order to avoid ice accumulation.
2
■A drain channel can be foreseen under the unit. Be sure that
drain water in this drain channel does not freeze causing
blockage by ice accumulation.
■Avoid drain water flowing over the footpath, so that in case of
ambient freezing temperatures the footpath does not become
slippery.
NOTICE
If drain holes of the outdoor unit
are covered by a mounting base or
by floor surface, raise the unit in
order to provide a free space of
more than 150 mm under the
150 mm≥
outdoor unit.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
7
Page 10
7.INSTALLATIONSERVICINGSPACE
330 mm
580 mm
120 mm
4
1
3
2
7
56
■Where a wall or other obstacle is in the path of the outdoor unit
air intake or exhaust airflow, follow the installation guidelines
below.
■For any of the installation patterns below, the wall height on the
exhaust side should be 1200 mm or less.
Wall facing one side (unit: mm)
>100>350
≤1200
Walls facing two sides (unit: mm)
7.1. Outdoor unit installation drawing
>100
>50
>350
Walls facing three sides (unit: mm)
>100
>50
>350
>50
1 Wrap the insulation pipe with finishing tape from bottom to
top.
2 Service cover
3 Stop valve cover
4 250 mm from wall. Allow space for piping and electrical
servicing.
5 If there is danger of the unit falling or overturning, fix the
unit with foundation bolts, or with wire or other means.
6 Distance from the outer side of the stop valve cover
7 If the location does not have good drainage, place the unit
on block bases. Adjust foot height until the unit is levelled.
Failure to do so may result in water leakage or
accumulation.
Installation manual
8
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 11
8.REFRIGERANTPIPESIZEANDALLOWABLE
PIPELENGTH
DANGER
■Piping and other pressure containing parts shall
comply with the applicable legislation and shall be
suitable for refrigerant. Use phosphoric acid
deoxidised seamless copper for refrigerant.
■Installation shall be done by an installer, the choice of
materials and installation shall comply with applicable
legislation. In Europe the EN378 is the application
standard that shall be used.
NOTICE
To persons in charge of piping work:
Be sure to open the stop valve after piping installing and
vacuming is complete. (Running the system with the valve
closed may break the compressor.)
INFORMATION
It is forbidden to discharge refrigerant into the atmosphere.
Collect the refrigerant in accordance with the freon
collection and destruction law.
8.3. Allowable pipe length and height difference
See the figure and table below concerning allowable lengths and
heights. Assume that the longest line in the figure corresponds with
the actual longest pipe, and the highest unit in the figure corresponds
with the actual highest unit.
L
H
Maximum total one-way piping length
L30 m
Minimum one-way piping length
L3 m
Maximum height between indoor and outdoor
H20 m
Chargeless length
L≤10 m
H Height
L Length
Allowable pipe length
8.1. Selection of piping material
■Construction material: phosphoric acid deoxidised seamless
copper for refrigerant.
■Temper grade: use piping with temper grade in function of the
pipe diameter as listed in table below.
■The pipe thickness of the refrigerant piping should comply with
applicable legislation. The minimal pipe thickness for R410A
piping must be in accordance with the table below.
Temper grade
Pipe Ø
6.4O0.80
15.9O1.00
O=Annealed
of piping material
Minimal thickness t (mm)
8.2. Refrigerant pipe size
The pipes between outdoor unit and indoor unit should have the
same size as the outdoor connections.
Refrigerant pipe size (mm)
Gas pipeØ15.9
Liquid pipeØ6.4
9.PRECAUTIONSONREFRIGERANTPIPING
■Do not allow anything other than the designated refrigerant to
get mixed into the freezing cycle, such as air, etc. If any
refrigerant gas leaks while working on the unit, ventilate the
room thoroughly right away.
■Use R410A only when adding refrigerant
Installation tools:
Make sure to use installation tools (gauge manifold charge hose,
etc.) that are exclusively used for R410A installations to
withstand the pressure and to prevent foreign materials (e.g.
mineral oils and moisture) from mixing into the system.
Vacuum pump:
Use a 2-stage vacuum pump with a non-return valve
Make sure the pump oil does not flow oppositely into the system
while the pump is not working.
Use a vacuum pump which can evacuate to –100.7 kPa (5 Torr,
–755 mm Hg).
■In order to prevent dirt, liquid or dust from entering the piping,
cure the piping with a pinch or taping.
Great caution is needed when passing copper tubes through
walls.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
PlaceInstallation periodProtection method
Outdoor unit
Indoor unit
More than a monthPinch the pipe
Less than a month
Regardless of the
period
Pinch or tape the pipe
■Piping should be mounted so that the flare is not subjected to
mechanical stress.
Installation manual
9
Page 12
10. REFRIGERANTPIPING
10.1. Flaring the pipe end
To flare each pipe end, follow the procedure below:
1Cut the pipe end with a pipe cutter.
2Remove burrs with the cut surface facing downward so that the
chips do not enter the pipe.
1 Cut exactly at right angles.
2 Remove burrs
2When loosening a flare nut, always use two wrenches together.
When connecting the piping, always use a spanner and torque
wrench together to tighten the flare nut to prevent nut cracking
and leaks.
3Remove the flare nut from the stop valve and put the flare nut on
the pipe.
4Flare the pipe. Set exactly at the position shown below.
A
Conventional flare tool
Flare tool for R410A
(clutch type)
A0~0.5 mm1.0~1.5 mm1.5~2.0 mm
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
5Check that the flaring is properly made.
1 Flare's inner surface must be flaw-
free.
2 The pipe end must be evenly flared in
a perfect circle.
3 Make sure that the flare nut is fitted.
12
10.2. Connecting the refrigerant piping to the outdoor
unit
DANGER
Installation shall be done by an installer, the choice of
materials and installation shall comply with applicable
legislation. In Europe the EN378 is the application
standard that shall be used.
CAUTION
■Do not use mineral oil on flared part.
Mineral oil getting into the system would reduce the
lifetime of the units.
■Never use piping which has been used for previous
installations. Only use parts which are delivered with
the unit.
■Do never install a drier to this R410A unit in order to
guarantee its lifetime. The drying material may
dissolve and damage the system.
■Incomplete flaring may cause refrigerant gas leakage.
1When connecting the flare nut, coat the flare inner surface with
ether oil or with ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.
Flare nutFlare nut tightening torque
Ø6.4 mm (1/4")15~17 N•m
Ø15.9 mm (5/8")63~75 N•m
Valve cap tightening torque
Valve capGas pipe
Ø6.4 mm (1/4")21.6~27.4 N•m
Ø15.9 mm (5/8")44.1~53.9 N•m
Service port cap tightening torque
10.8~14.7 N•m
10.3. Refrigerant piping work
Pipe handling guidelines
All pipe bends should be as gentle as possible. Use a pipe bender for
bending.
3
Bending radius should be 30 to 40 mm or larger.
Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the
following:
■Insulation material: polyethylene foam
Heat transfer rate: 0.041 to 0.052 W/mK (0.035 to 0.045 kcal/
mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this
temperature.
■Be sure to insulate both the gas and liquid piping and to provide
insulation dimensions as below.
Pipe sizePipe insulation
Outer diameterThicknessInner diameterThickness
6.4 mm (1/4")0.8 mm8-10 mm≥10 mm
15.9 mm (5/8")1.0 mm16-20 mm≥13 mm
2
1
6
5
1 Gas pipe
2 Inter-unit wiring
3 Liquid pipe
4 Liquid pipe insulation
5 Finishing tape
6 Gas pipe insulation
■Use separate thermal insulation pipes for gas and liquid
refrigerant pipes.
3
4
Installation manual
10
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 13
11. LEAKTESTANDVACUUMDRYING
When all piping work is complete and the outdoor unit is connected to
the indoor unit, it is necessary to:
■check for any leakages in the refrigerant piping
■to perform vacuum drying to remove all moisture in the
refrigerant piping.
If there is a possibility of moisture being present in the refrigerant
piping (for example, rainwater may have entered the piping), first
carry out the vacuum drying procedure below until all moisture has
been removed.
■All refrigerant pipe joints should be tightened with a torque
wrench at the specified tightening torque. See "10.2. Connecting
the refrigerant piping to the outdoor unit" on page 10 for details.
14
8
2
3
10
5
11.1. General guidelines
■All piping inside the unit has been factory tested for leaks.
■Use a 2-stage vacuum pump with a non-return valve which can
evacuate to a gauge pressure of –100.7 kPa (5 Torr absolute,
–755 mm Hg).
■Connect the vacuum pump to the service port of the gas stop
valve.
NOTICE
■Make sure that the gas stop valve and liquid stop
valve are firmly closed before performing the leak test
or vacuum drying.
■Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may
damage the vacuum pump or the unit.
WARNING
■Do not mix any substance other than the specified
refrigerant (R410A) into the refrigeration cycle.
■When refrigerant gas leaks occur, ventilate the room
as soon and as much as possible.
■R410A, as well as other refrigerants, should always
be recovered and never be released directly into the
environment.
INFORMATION
Do not purge the air with refrigerants. Use a vacuum pump
to evacuate the installation.
■If using additional refrigerant, perform air purging from the
refrigerant pipes and indoor unit using a vacuum pump, then
charge additional refrigerant.
■Use a hexagonal wrench (4 mm) to operate the stop valve rod.
6
7 8 9
1 Pressure meter
2 Gauge manifold
3 Low-pressure valve (Lo)
4 High-pressure valve (Hi)
5 Charging hoses
6 Vacuum pump
7 Service port
8 Valve lids
9 Gas stop valve
10 Liquid stop valve
1Connect the projection side (on which the worm pin is pressed)
of the charging hose coming from the gauge manifold to the gas
stop valve's service port.
2Fully open the gauge manifold's low-pressure valve (Lo) and
completely close its high-pressure valve (Hi).
The high-pressure valve subsequently requires no operation.
3Apply vacuum pumping. Check that the compound pressure
gauge reads –0.1 MPa (–760 mm Hg).
Pipe length
≤≤≤≤15 m>15 m
Run time≥10 minutes≥15 minutes
4Close the gauge manifold's low-pressure valve (Lo) and stop the
vacuum pump.
Leave as is for 4-5 minutes and make sure that the coupling
meter needle does not go back.
NOTICE
If the meter needle does go back, this may indicate
presence of moisture or leaking from connecting
parts. Repeat steps 2 through 4 after checking all
connecting parts and slightly loosening and
retightening the nuts.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
5Remove the covers from the liquid stop valve and gas stop valve.
6Turn the liquid stop valve's rod 90 degrees counterclockwise with
a hexagonal wrench to open the valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit's
flare and the outdoor unit's flare and the valve rods.
After the check is complete, wipe all soapy water off.
7Disconnect the charging hose from the gas stop valve's service
port, then fully open the liquid and gas stop valves.
Do not attempt to turn the valve rod beyond its stop.
8Tighten the valve lids and service port caps for the liquid and
gas stop valves with a torque wrench at the specified torques.
See "10.2. Connecting the refrigerant piping to the outdoor unit"
on page 10 for details.
Installation manual
11
Page 14
INFORMATION
After opening the stop valve, it is possible that the pressure
in the refrigerant piping does not rise. This might be
caused by e.g. the closed state of the expansion valve in
the outdoor unit circuit, but does not present any problem
for correct operation of the unit.
12. CHARGINGREFRIGERANT
This outdoor unit is factory charged.
12.2. Precautions and general guidelines
CAUTION
When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in view of
the danger of liquid hammer.
WARNING
■Refrigerant cylinders shall be opened slowly.
■Always use protective gloves and protect your eyes
when charging refrigerant.
12.1. Important information regarding the refrigerant
used
This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type:R410A
(1)
GWP
value:1975
(1)
GWP = global warming potential
Please fill in with indelible ink,
■➀ the factory refrigerant charge of the product,
■➁ the additional refrigerant amount charged in the field and
■➀+➁ the total refrigerant charge
on the fluorinated greenhouse gases label supplied with the product.
The filled out label must be adhered on the inside of the product and
in the proximity of the product charging port (e.g. on the inside of the
service cover).
4
1
2
3
5
6
1 Factory refrigerant charge of the product:
see unit name plate
2 Additional refrigerant amount charged in the field
3 Total refrigerant charge
4 Contains fluorinated greenhouse gases covered by the
Kyoto Protocol
5 Outdoor unit
6 Refrigerant cylinder and manifold for charging
INFORMATION
National implementation of EU regulation on certain
fluorinated greenhouse gases may require to provide the
appropriate official national language on the unit.
Therefore, an additional multilingual fluorinated
greenhouse gases label is supplied with the unit.
Sticking instructions are illustrated on the backside of that
label.
DANGER
■When the power is on, please close the front panel
when leaving the unit unattended.
■Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant (R410A) is charged.
■Be sure to charge the specified amount of refrigerant in liquid
state to the liquid pipe.
Since this refrigerant is a mixed refrigerant, adding it in gas form
may cause the refrigerant composition to change, preventing
normal operation.
■Before charging, check whether the refrigerant cylinder is
equipped with a siphon tube or not (the cylinder should be
marked with "liquid filling siphon attached" or something similar).
Charge the liquid
refrigerant with the
cylinder in upright
position.
Charge the liquid
refrigerant with the
cylinder in up-side-down
position.
■Be sure to use tools exclusively for R410A to ensure required
pressure resistance and to prevent foreign materials from mixing
into the system.
12.3. Calculating the additional refrigerant
It is not necessary to charge additionally if the piping length is under
10 m.
If the piping length is over 10 m please determine the additional
amount of refrigerant to be charged using the formula below.
R=(total length (m) of liquid piping – 10 m) x 0.02
R=additional charge (kg)(rounded in units of 0.01 kg)
Determine the weight of refrigerant to be charged additionally and fill
in the amount in the service sticker on the rear side of the stop valve
cover.
To avoid compressor breakdown. Do not charge the refrigerant
more than the specified amount.
This outdoor unit is factory charged with refrigerant and depending
on pipe sizes and pipe lengths some systems require additional
charging of refrigerant.
Installation manual
12
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 15
12.4. Complete recharging
NOTICE
Before recharging, make sure to execute vacuum drying of
the internal piping of the unit as well.
In case complete recharging is required, refer to the nameplate of the
unit. The nameplate states the type of refrigerant and necessary
amount.
Total charging amount <unit: kg>
Charge of refrigerant (kg) depends on total liquid piping length.
Total refrigerant charge=1.7 kg + (total length (m) of liquid
piping–10 m) x 0.02
Remark: Factory refrigerant charge is 1.7 kg.
13. PUMPDOWNOPERATION
In order to protect the environment, be sure to pump down when
relocating or disposing of the unit. The pump down operation will
extract all refrigerant from the piping into the outdoor unit.
13.1. Pump down procedure
1Remove the valve lid from liquid stop valve and gas stop valve.
2Carry out the forced cooling operation.
3After 5 to 10 minutes (after only 1 or 2 minutes in case of very
low ambient temperatures (<–10°C)), close the liquid stop valve
with a hexagonal wrench.
NOTICE
Take care that while running forced cooling operation the
water temperature remains higher than 5°C (see
temperature read out of the indoor unit). You can achieve
this, for example, by activating all fans of the fan coil units.
14. ELECTRICALWIRINGWORK
WARNING
■All wiring must be performed by an authorized
electrician.
■Electrical connections shall be made to fixed wiring.
■All components procured on the site and all electric
construction shall comply with the applicable
legislation.
DANGER: HIGH VOLTAGE
To avoid electrical shock, make sure to disconnect the
power supply 1 minute or more before servicing the
electrical parts. Even after 1 minute, always measure the
voltage at the terminals of main circuit capacitors or
electrical parts and, before touching, make sure that those
voltages are 50 V DC or less.
NOTICE
To persons in charge of electrical wiring work:
Do not operate the unit until the refrigerant piping is
complete. (Running it before the piping is ready will break
the compressor.)
4After 2-3 minutes, close the gas stop valve and stop forced
cooling operation.
1 Gas stop valve
2 Close
3 Hexagonal wrench
4 Valve lid
5 Liquid stop valve
1
5
2
13.2. Forced cooling operation
1Press the forced operation switch SW1 to begin forced cooling.
2Press the forced operation switch SW1 again to stop forced
cooling.
S102
S2
LED-A
ABCD
SW4
ON
SW1
1
1 Forced operation switch SW1
14.1. Precautions on electrical wiring work
DANGER
3
4
4
■Use only copper wires.
■A main switch or other means for disconnection, having a
■Never squeeze bundled cables into a unit.
■Fix cables so that cables do not make contact with the pipes
■Secure the electrical wiring with cable ties as shown in the figure
■When installing the earth leakage circuit breaker make sure that
■The power supply cable and circuit breaker must be selected in
■Do not use tapped wires, stranded conductor wires (see caution
■Before obtaining access to terminal devices, all supply
circuits must be interrupted.
■Be sure to install an earth leakage circuit breaker in
accordance with applicable legislation. Failure to do
so may cause electrical shock.
■Do not turn on the main switch until all the wiring is
completed.
contact separation in all poles, must be incorporated in the fixed
wiring in accordance with applicable legislation.
(especially on high pressure side).
in chapter "14.3. Connecting power supply and interunit wiring"
on page 14 so that it does not come in contact with the piping,
particularly on the high-pressure side.
Make sure no external pressure is applied to the terminal
connectors.
it is compatible with the inverter (resistant to high frequency
electrical noise) to avoid unnecessary opening of the earth
leakage circuit breaker.
accordance with applicale legislation.
1 under "Notes to observe" on page 15), extension cords, or
connections from a star system, as they may cause overheating,
electrical shock or fire.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
13
Page 16
■Do not use locally purchased electrical parts inside the product
and do not branch the power for the heater tape, etc., from the
terminal block. Doing this may cause electrical shock or fire.
■As this unit is equipped with an inverter, installing a phase
advancing capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal
heating accident due to high-frequency waves. Therefore, never
install a phase advancing capacitor.
CAUTION
Be sure to install the required fuses or circuit breakers.
(1)
■This equipment complies with EN/IEC 61000-3-11
that the system impedance Z
is less than or equal to Z
sys
provided
at
max
the interface point between the user's supply and the public
system. It is the responsibility of the installer or user of the
equipment to ensure, by consultation with the distribution
network operator if necessary, that the equipment is connected
only to a supply with a system impedance Z
14.3. Connecting power supply and interunit wiring
1Strip the insulation from the wire (20 mm).
2Connect the connection wires between the indoor and outdoor
units so that the terminal numbers match (see wiring diagram
below). Tighten the terminal screws securely. We recommend a
flathead screwdriver to tighten the screws.
See also caution 2 under "Notes to observe" on page 15 for
wiring guidelines.
123
123
LN
123
1
2
3
H05VV
1453
1 Interconnection between indoor unit and outdoor unit:
when wire length exceeds 10 m, use Ø2.5 mm wires
instead of Ø1.5 mm wires.
2 Power supply cable
(refer to the unit nameplate for maximum running current)
(1) European/International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage supply
systems for equipment with rated current ≤75 A.
(2) European/International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage systems
with input current >16 A and ≤75 A per phase.
Installation manual
14
4Pull the connected wire and make sure that it does not
disconnect. Then fix the wires in place in the wire clamp. See
also "Notes to observe" on page 15.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 17
Notes to observe
14.4. Electrical characteristics
Observe the notes mentioned below when wiring to the power supply
terminal board.
1
2
123
LN
4
4
C
B
A3
5
1 Interconnection
Only if bottom plate heater applicable (optional for ERHQ)
2 Power supply cable
3 Bottom plate heater power supply cable
4 Tie wrap
5 Bottom plate heater cable
■Use the specified wire type and connect it securely (A).
■Firmly secure the wire clamp so that wire terminations do not
receive external stress (B).
■Shape wires so that the service cover and stop valve cover fit
securely (C).
CAUTION
1.In case the use of stranded conductor wires is
unavoidable for one reason or another, make sure to
install round crimp-style terminals on the tip.
Place the round crimp-style terminal on the wire up to
the covered part and fasten the terminal with the
appropriate tool.
Select all cables and wire sizes in accordance with
applicable legislation.
CAUTION
After finishing the electrical work, confirm that each electric
part and terminal inside the electric part box is connected
securely.
The wiring diagram can be found on the inside of the front plate of the
unit.
15. TESTOPERATION
DANGER
Never leave the unit unattended during installation or
servicing. When the service panel is removed live parts
can be easily touched by accident..
INFORMATION
Note that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates from
the compressor that needs elapse of a 50 hours run in
period before reaching smooth operation and stable power
consumption.
15.1. Pre-run checks
CheckSymptom
Outdoor unit is installed properly
■
on solid base.
No refrigerant gas leaks.Incomplete cooling/heating
■
Refrigerant gas and liquid pipes
■
are thermally insulated.
System is properly earthed.Electrical leakage
■
The specified wires are used for
■
interconnecting wire connections.
Outdoor unit air intake and
■
exhaust is free of obstructions.
Stop valves are opened.
Fall, vibration, noise
function
Water leakage
Inoperative or burn damage
Incomplete cooling/heating
function
2.When connecting the connection wires to the terminal
board using a single core wire, be sure to perform
curling.
Not executing the connections properly may cause
heat and fire.
Strip the wire at terminal block:
1 Strip wire end to this point
2 Excessive strip length may cause electrical
shock or leakage.
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Installation manual
15
Page 18
15.2. Trial operation and testing
1Measure the voltage at the primary side of the safety breaker.
Check that it is 230 V.
2Carry out the test operation in accordance with the indoor
installation manual and operation manual to ensure that all
functions and parts are working properly.
INFORMATION
If the circuit breaker trips to shut off the power to the
outdoor unit, the system will restore the original
operation mode when the power supply is restored.
See installation manual, chapter "Field settings" of the
indoor unit for more details.
INFORMATION
Instruct the customer how to operate the unit correctly.
NOTICE
For applications with benefit kWh rate power supply
The outdoor unit power supply (L, N) interruption may not
be longer than 2 hours to guarantee optimized startup
condition for compressor. See installation manual of the
indoor unit for more details.
16. MAINTENANCEANDSERVICING
16.1. Service precautions
In order to ensure optimal operation of the unit, a number of checks
and inspections should be carried out on the unit at regular intervals,
preferably yearly.
This maintenance shall be carried out by the installer or service
agent.
DANGER: ELECTRICAL SHOCK
See "2. General safety precautions" on page 2.
DANGER: DO NOT TOUCH PIPING AND INTERNAL
PA RT S
See "2. General safety precautions" on page 2.
■Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.
■Make sure that the power supply is turned off before
performing the maintenance work. The heater of the
compressor may operate even in stop mode.
■The outdoor fan may rotate due to strong backblow wind,
causing the capacitor to charge. This may result in an electric
shock.
After maintenance, make sure the outdoor fan connector is
connected again. Otherwise, the unit may break down.
16.2. Service mode operation
Refer to the service manual to carry out any service mode operation.
17. DISPOSALREQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with applicable legislation.
18. UNITSPECIFICATIONS
18.1. Technical specifications
Casing materialPainted galvanised steel
Dimensions hxwxd(mm)735x825x300
Weight (kg)57
Operation range
• cooling (min./max.) (°C)10/43
• heating (min./max.) (°C)–15/25
• domestic hot water
(min./max.)
Refrigerant oilDaphne FVC68D
Piping connection
• liquid(mm)6.4
• gas(mm)15.9
18.2. Electrical specifications
Phase1~
Frequency(Hz)50
Voltage range
• minimum(V)207
• maximum(V)253
(°C)–15/35
CAUTION
Do not rinse the outdoor unit. This may cause electric
shocks or fire.
NOTICE
Touch a metal part by hand (such as the stop valve) in
order to eliminate static electricity and to protect the PCB
before performing service.
■Please note that some sections of the electric component box
are extremely hot.
■Make sure you do not touch a conductive section.
■After measuring the residual voltage, pull out the outdoor fan
connector.
Installation manual
16
ERHQ006~008BBV3 + ERLQ006~008BBV3
Outdoor unit for air to water heat pump
4PW68002-1A – 03.2011
Page 19
Page 20
4PW68002-1A 03.2011
Copyright 2011 Daikin
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.