1.1About the documentation .............................................................................................................................................. 6
1.1.1Meaning of warnings and symbols ................................................................................................................6
1.2For the installer............................................................................................................................................................... 7
1.2.2Installation site ............................................................................................................................................... 8
2.1About this document ...................................................................................................................................................... 13
2.2Installer reference guide at a glance .............................................................................................................................. 14
3 About the box16
3.1Overview: About the box ................................................................................................................................................ 16
3.2Outdoor unit ................................................................................................................................................................... 16
3.2.1To handle the outdoor unit ............................................................................................................................ 16
3.2.2To unpack the outdoor unit ........................................................................................................................... 18
3.2.3To remove the accessories from the outdoor unit........................................................................................ 19
3.3Indoor unit ...................................................................................................................................................................... 20
3.3.1To unpack the indoor unit .............................................................................................................................. 20
3.3.2To remove the accessories from the indoor unit .......................................................................................... 20
3.3.3To handle the indoor unit............................................................................................................................... 20
4 About the units and options21
4.1Overview: About the units and options.......................................................................................................................... 21
4.2.1Identification label: Outdoor unit .................................................................................................................. 21
4.2.2Identification label: Indoor unit ..................................................................................................................... 22
4.3Combining units and options.......................................................................................................................................... 22
4.3.1Possible combinations of indoor unit and outdoor unit................................................................................ 22
4.3.2Possible options for the outdoor unit ............................................................................................................ 22
4.3.3Possible options for the indoor unit............................................................................................................... 23
5.2Setting up the space heating/cooling system ................................................................................................................ 26
5.3Setting up the domestic hot water tank......................................................................................................................... 30
5.3.2Selecting the volume and desired temperature for the DHW tank .............................................................. 30
5.3.3Setup and configuration – DHW tank ............................................................................................................ 31
5.3.4DHW pump for instant hot water .................................................................................................................. 32
5.3.5DHW pump for disinfection ........................................................................................................................... 32
5.4Setting up the energy metering...................................................................................................................................... 33
5.4.3Normal kWh rate power supply ..................................................................................................................... 34
5.4.4Preferential kWh rate power supply .............................................................................................................. 36
5.5Setting up the power consumption control ................................................................................................................... 37
5.5.1Permanent power limitation .......................................................................................................................... 37
5.5.2Power limitation activated by digital inputs .................................................................................................. 38
5.5.4BBR16 power limitation.................................................................................................................................. 39
5.6Setting up an external temperature sensor ................................................................................................................... 40
Installer reference guide
2
6 Unit installation42
6.1Preparing the installation site......................................................................................................................................... 42
6.1.1Installation site requirements of the outdoor unit........................................................................................ 42
6.1.2Additional installation site requirements of the outdoor unit in cold climates............................................ 45
6.1.3Installation site requirements of the indoor unit .......................................................................................... 45
6.2Opening and closing the units ........................................................................................................................................ 46
6.2.1About opening the units................................................................................................................................. 46
6.2.2To open the outdoor unit ............................................................................................................................... 47
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Table of contents
6.2.3To remove the transportation stay ................................................................................................................ 47
6.2.4To close the outdoor unit ............................................................................................................................... 48
6.2.5To open the indoor unit ................................................................................................................................. 48
6.2.6To lower the switch box on the indoor unit .................................................................................................. 50
6.2.7To close the indoor unit ................................................................................................................................. 51
6.3Mounting the outdoor unit............................................................................................................................................. 51
6.3.1About mounting the outdoor unit ................................................................................................................. 51
6.3.2Precautions when mounting the outdoor unit .............................................................................................. 51
6.3.3To provide the installation structure ............................................................................................................. 51
6.3.4To install the outdoor unit ............................................................................................................................. 52
6.3.5To provide drainage........................................................................................................................................ 53
6.3.6To install the discharge grille.......................................................................................................................... 55
6.3.7To remove the discharge grille, and put the grille in safety position............................................................ 56
6.4Mounting the indoor unit ............................................................................................................................................... 58
6.4.1About mounting the indoor unit .................................................................................................................... 58
6.4.2Precautions when mounting the indoor unit................................................................................................. 58
6.4.3To install the indoor unit ................................................................................................................................ 58
6.4.4To connect the drain hose to the drain ......................................................................................................... 59
7 Piping installation61
7.1Preparing water piping ................................................................................................................................................... 61
7.1.2Formula to calculate the expansion vessel pre-pressure .............................................................................. 63
7.1.3To check the water volume and flow rate ..................................................................................................... 63
7.1.4Changing the pre-pressure of the expansion vessel...................................................................................... 66
7.1.5To check the water volume: Examples .......................................................................................................... 66
7.2Connecting water piping................................................................................................................................................. 67
7.2.1About connecting the water piping ............................................................................................................... 67
7.2.2Precautions when connecting the water piping ............................................................................................ 67
7.2.3To connect the water piping .......................................................................................................................... 67
7.2.4To connect the recirculation piping ............................................................................................................... 69
7.2.5To fill the water circuit ................................................................................................................................... 70
7.2.6To protect the water circuit against freezing ................................................................................................ 70
7.2.7To fill the domestic hot water tank ................................................................................................................ 73
7.2.8To insulate the water piping .......................................................................................................................... 73
8 Electrical installation75
8.1About connecting the electrical wiring .......................................................................................................................... 75
8.1.1Precautions when connecting the electrical wiring....................................................................................... 75
8.1.2Guidelines when connecting the electrical wiring......................................................................................... 76
8.1.4About preferential kWh rate power supply ................................................................................................... 77
8.1.5Overview of electrical connections except external actuators ..................................................................... 78
8.2Connections to the outdoor unit.................................................................................................................................... 79
8.2.1To connect the electrical wiring on the outdoor unit ................................................................................... 79
8.2.2To reposition the air thermistor on the outdoor unit ................................................................................... 85
8.3Connections to the indoor unit ...................................................................................................................................... 86
8.3.1To connect the main power supply................................................................................................................ 88
8.3.2To connect the backup heater power supply ................................................................................................ 91
8.3.3To connect the shut-off valve (Heating/Cooling) .......................................................................................... 93
8.3.4To connect the electricity meters .................................................................................................................. 94
8.3.5To connect the domestic hot water pump .................................................................................................... 95
8.3.6To connect the alarm output ......................................................................................................................... 96
8.3.7To connect the space cooling/heating ON/OFF output................................................................................. 97
8.3.8To connect the changeover to external heat source..................................................................................... 98
8.3.9To connect the power consumption digital inputs........................................................................................ 99
8.3.10To connect the safety thermostat (normally closed contact)....................................................................... 100
8.4After connecting the electrical wiring to the indoor unit .............................................................................................. 102
9.1.1To access the most used commands ............................................................................................................. 105
9.3.3Main menu screen.......................................................................................................................................... 112
9.4.1What is a weather-dependent curve? ........................................................................................................... 118
9.5Settings menu ................................................................................................................................................................. 123
9.5.3Main zone ....................................................................................................................................................... 128
9.5.4Additional zone ............................................................................................................................................... 138
10.4.3Operation test run.......................................................................................................................................... 191
10.4.4Actuator test run ............................................................................................................................................ 191
12.1 Overview: Maintenance and service .............................................................................................................................. 197
12.4 To drain the domestic hot water tank............................................................................................................................ 201
12.5 About cleaning the water filter in case of trouble ......................................................................................................... 202
12.5.1To remove the water filter ............................................................................................................................. 202
12.5.2To clean the water filter in case of trouble.................................................................................................... 202
12.5.3To install the water filter ................................................................................................................................ 204
13.2 Precautions when troubleshooting ................................................................................................................................ 205
13.3 Solving problems based on symptoms ........................................................................................................................... 206
13.3.1Symptom: The unit is NOT heating or cooling as expected........................................................................... 206
13.3.2Symptom: Hot water does NOT reach the desired temperature.................................................................. 207
13.3.3Symptom: The compressor does NOT start (space heating or domestic water heating) ............................ 207
13.3.4Symptom: The system is making gurgling noises after commissioning ........................................................ 207
13.3.5Symptom: The pump is blocked..................................................................................................................... 208
13.3.6Symptom: The pump is making noise (cavitation)......................................................................................... 208
13.3.7Symptom: The pressure relief valve opens.................................................................................................... 209
13.3.8Symptom: The water pressure relief valve leaks........................................................................................... 209
13.3.9Symptom: The space is NOT sufficiently heated at low outdoor temperatures........................................... 210
13.3.10 Symptom: The pressure at the tapping point is temporarily unusually high................................................ 211
13.3.11 Symptom: Tank disinfection function is NOT completed correctly (AH-error) ............................................. 211
13.4 Solving problems based on error codes ......................................................................................................................... 211
13.4.1To display the help text in case of a malfunction .......................................................................................... 211
14.1 To recover refrigerant..................................................................................................................................................... 216
15 Technical data218
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Table of contents
15.1 Service space: Outdoor unit ........................................................................................................................................... 219
15.2 Piping diagram: Outdoor unit ......................................................................................................................................... 220
15.3 Piping diagram: Indoor unit ............................................................................................................................................ 222
15.4 Wiring diagram: Outdoor unit ........................................................................................................................................ 224
15.5 Wiring diagram: Indoor unit ........................................................................................................................................... 229
16 Glossary235
17 Field settings table237
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Installer reference guide
5
1 | General safety precautions
1 General safety precautions
In this chapter
1.1About the documentation......................................................................................................................................................6
1.2For the installer.......................................................................................................................................................................7
1.1 About the documentation
▪ The original documentation is written in English. All other languages are
translations.
▪ The precautions described in this document cover very important topics, follow
them carefully.
1.1.1Meaning of warnings and symbols ........................................................................................................................6
1.2.2Installation site .......................................................................................................................................................8
▪ The installation of the system, and all activities described in the installation
manual and in the installer reference guide MUST be performed by an authorised
installer.
1.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold
temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
Installer reference guide
6
WARNING
Indicates a situation that could result in death or serious injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate injury.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
1.2 For the installer
1 | General safety precautions
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.
SymbolExplanation
Before installation, read the installation and operation
manual, and the wiring instruction sheet.
Before performing maintenance and service tasks, read the
service manual.
For more information, see the installer and user reference
guide.
1.2.1 General
If you are NOT sure how to install or operate the unit, contact your dealer.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or internal parts during and
immediately after operation. It could be too hot or too cold. Give it time to return
to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Improper installation or attachment of equipment or accessories could result in
electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable
legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…)
when installing, maintaining or servicing the system.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially
children, can play with them. Possible risk: suffocation.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small
animals. Small animals that make contact with electrical parts can cause
malfunctions, smoke or fire.
Installer reference guide
7
1 | General safety precautions
In accordance with the applicable legislation, it might be necessary to provide a
logbook with the product containing at least: information on maintenance, repair
work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an accessible place at the
product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
CAUTION
▪ Do NOT place any objects or equipment on top of the unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under dry weather conditions to
avoid water ingress.
1.2.2 Installation site
▪ Name, address and day and night telephone numbers for obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
▪ Provide sufficient space around the unit for servicing and air circulation.
▪ Make sure the installation site withstands the weight and vibration of the unit.
▪ Make sure the area is well ventilated. Do NOT block any ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic waves.
Electromagnetic waves may disturb the control system, and cause malfunction of
the equipment.
▪ In places where there is a risk of fire due to the leakage of flammable gases
(example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is produced.
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
1.2.3 Refrigerant
Installer reference guide
8
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
1 | General safety precautions
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
▪ Toxic gas may be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Selfcombustion and explosion of the compressor because of air going into the
operating compressor.
▪ Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen
to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
▪ When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after
performing the leak test and the vacuum drying.
Possible consequence: Self-combustion and explosion of the compressor because of
oxygen going into the operating compressor.
▪ In case recharge is required, see the nameplate of the unit. It states the type of
refrigerant and necessary amount.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
▪ The unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant.
Installer reference guide
9
1 | General safety precautions
▪ Only use tools exclusively for the refrigerant type used in the system, this to
ensure pressure resistance and prevent foreign materials from entering into the
system.
▪ Charge the liquid refrigerant as follows:
IfThen
A siphon tube is present
Charge with the cylinder upright.
(i.e., the cylinder is marked with "Liquid
filling siphon attached")
A siphon tube is NOT presentCharge with the cylinder upside down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may prevent normal
operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of
the refrigerant tank immediately. If the valve is NOT closed immediately, remaining
pressure might charge additional refrigerant. Possible consequence: Incorrect
refrigerant amount.
1.2.4 Brine
If applicable. See the installation manual or installer reference guide of your
application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area
immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room,
e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous
situation.
WARNING
The use and installation of the application MUST comply with the safety and
environmental precautions specified in the applicable legislation.
1.2.5 Water
Installer reference guide
10
If applicable. See the installation manual or installer reference guide of your
application for more information.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
1.2.6 Electrical
1 | General safety precautions
NOTICE
Make sure water quality complies with EU directive 98/83EC.
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the switch box cover, connecting
electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1minute, and measure the voltage at
the terminals of main circuit capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you can touch electrical
components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a
contact separation in all poles providing full disconnection under overvoltage
categoryIII condition, MUST be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable legislation.
▪ All field wiring MUST be performed in accordance with the wiring diagram
supplied with the product.
▪ NEVER squeeze bundled cables and make sure they do NOT come in contact with
the piping and sharp edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge
absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER use a power supply shared by
another appliance.
▪ Make sure to install the required fuses or circuit breakers.
▪ Make sure to install an earth leakage protector. Failure to do so may cause
electric shock or fire.
▪ When installing the earth leakage protector, make sure it is compatible with the
inverter (resistant to high frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
CAUTION
When connecting the power supply, the earth connection must be made before the
current-carrying connections are established. When disconnecting the power supply,
the current-carrying connections must be separated before the earth connection is.
The length of the conductors between the power supply stress relief and the
terminal block itself must be as such that the current-carrying wires are tautened
before the earth wire is in case the power supply is pulled loose from the stress
relief.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Installer reference guide
11
1 | General safety precautions
Install power cables at least 1 m away from televisions or radios to prevent
interference. Depending on the radio waves, a distance of 1 m may not be
sufficient.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the power terminal block (slack
in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness, do as shown in the figure
above.
▪ For wiring, use the designated power wire and connect firmly, then secure to
prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the terminal screws. A screwdriver
with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
WARNING
▪ After finishing the electrical work, confirm that each electrical component and
terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/
OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the
power goes on and off while the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed phase can break the
compressor and other parts.
Installer reference guide
12
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
2 About the documentation
In this chapter
2.1About this document.............................................................................................................................................................. 13
2.2Installer reference guide at a glance...................................................................................................................................... 14
2.1 About this document
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
▪ General safety precautions:
- Safety instructions that you must read before installing
- Format: Paper (in the box of the indoor unit)
▪ Operation manual:
2 | About the documentation
- Quick guide for basic usage
- Format: Paper (in the box of the indoor unit)
▪ User reference guide:
- Detailed step-by-step instructions and background information for basic and
advanced usage
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
▪ Installation manual – Outdoor unit:
- Installation instructions
- Format: Paper (in the box of the outdoor unit)
▪ Installation manual – Indoor unit:
- Installation instructions
- Format: Paper (in the box of the indoor unit)
▪ Installer reference guide:
- Preparation of the installation, good practices, reference data,…
- Format: Digital files on http://www.daikineurope.com/support-and-manuals/
product-information/
▪ Addendum book for optional equipment:
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
- Additional info about how to install optional equipment
- Format: Paper (in the box of the unit) + Digital files on http://
Latest revisions of the supplied documentation may be available on the regional
Daikin website or via your dealer.
The original documentation is written in English. All other languages are
translations.
Installer reference guide
13
2 | About the documentation
Technical engineering data
▪ A subset of the latest technical data is available on the regional Daikin website
(publicly accessible).
▪ The full set of latest technical data is available on the Daikin Business Portal
(authentication required).
Online tools
In addition to the documentation set, some online tools are available for installers:
▪ Daikin Technical Data Hub
- Central hub for technical specifications of the unit, useful tools, digital
- Publicly accessible via https://daikintechnicaldatahub.eu.
▪ Heating Solutions Navigator
- Digital toolbox that offers a variety of tools to facilitate the installation and
- To access Heating Solutions Navigator, registration to the Stand By Me
resources, and more.
configuration of heating systems.
platform is required. For more information, see https://
professional.standbyme.daikin.eu.
▪ Daikin e-Care
- Mobile app for installers and service technicians that allows you to register,
configure and troubleshoot heating systems.
- The mobile app can be downloaded for iOS and Android devices using the QR
codes below. Registration to the Stand By Me platform is required to access
the app.
App StoreGoogle Play
2.2 Installer reference guide at a glance
ChapterDescription
General safety precautionsSafety instructions that you must read before
installing
About the documentationWhat documentation exists for the installer
About the boxHow to unpack the units and remove their
accessories
Installer reference guide
14
About the units and options▪ How to identify the units
▪ Possible combinations of units and options
Application guidelinesVarious installation setups of the system
Unit installationWhat to do and know to install the system,
including information on how to prepare for an
installation
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
2 | About the documentation
ChapterDescription
Piping installationWhat to do and know to install the piping of the
system, including information on how to
prepare for an installation
Electrical installationWhat to do and know to install the electrical
components of the system, including
information on how to prepare for an
installation
ConfigurationWhat to do and know to configure the system
after it is installed
CommissioningWhat to do and know to commission the system
after it is configured
Hand‑over to the userWhat to give and explain to the user
Maintenance and serviceHow to maintain and service the units
TroubleshootingWhat to do in case of problems
DisposalHow to dispose of the system
Technical dataSpecifications of the system
GlossaryDefinition of terms
Field settings tableTable to be filled in by the installer, and kept for
future reference
Note: There is also an installer settings table in
the user reference guide. This table has to be
filled in by the installer and handed over to the
user.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Installer reference guide
15
3 | About the box
3 About the box
In this chapter
3.1 Overview: About the box
3.1Overview: About the box........................................................................................................................................................ 16
3.2Outdoor unit ........................................................................................................................................................................... 16
3.2.1To handle the outdoor unit.................................................................................................................................... 16
3.2.2To unpack the outdoor unit ................................................................................................................................... 18
3.2.3To remove the accessories from the outdoor unit ............................................................................................... 19
3.3Indoor unit .............................................................................................................................................................................. 20
3.3.1To unpack the indoor unit...................................................................................................................................... 20
3.3.2To remove the accessories from the indoor unit .................................................................................................. 20
3.3.3To handle the indoor unit ...................................................................................................................................... 20
This chapter describes what you have to do after the boxes with the outdoor and
indoor unit are delivered on-site.
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage MUST be
reported immediately to the claims agent of the carrier.
▪ Bring the packed unit as close as possible to its final installation position to
prevent damage during transport.
▪ Prepare the path along which you want to bring the unit inside in advance.
3.2 Outdoor unit
3.2.1 To handle the outdoor unit
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium fins of the unit.
Crane
Keep the slings within the marked area to not damage the unit.
Installer reference guide
16
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
3 | About the box
±150
kg
4×
Forklift or pallet truck
Enter the pallet from the heavy side.
3 persons
After unpacking, carry the unit using the slings attached to the unit.
See also:
▪ "3.2.2To unpack the outdoor unit"[418]
▪ "6.3.4To install the outdoor unit"[452]
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Installer reference guide
17
3 | About the box
12
35
4
a
b
3.2.2 To unpack the outdoor unit
Installer reference guide
18
a, b Accessories
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
3.2.3 To remove the accessories from the outdoor unit
b
c
d
e
f
a
g
ENERG
IJAY
IAIE
ENERG
IJAY
IAIE
h
i
3 | About the box
a Shut-off valve (with integrated filter)
b O-ring for drain socket
c Drain socket
d Thermistor fixture (for installations in areas with low ambient temperatures)
e Installation manual – Outdoor unit
f Disposal manual – Recovering refrigerant
g Energy label
h Discharge grille (upper + lower part)
i Installation manual – Discharge grille
NOTICE
Unpacking – Front corners. When you remove the front packaging corners, hold the
box containing the discharge grille to prevent it from falling.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Installer reference guide
19
3 | About the box
12
8×
6×
12×1×4×1×
1×1×1×1×
ab
ghicdef
b
aa
b
3.3 Indoor unit
3.3.1 To unpack the indoor unit
3.3.2 To remove the accessories from the indoor unit
a Shut-off valves for water circuit
b Overpressure bypass valve
c General safety precautions
d Addendum book for optional equipment
e Indoor unit installation manual
f Operation manual
g Sealing rings for shut-off valves (space heating water circuit)
h Sealing rings for field-supplied shut-off valves (domestic hot water circuit)
i Sealing tape for low voltage wiring intake
3.3.3 To handle the indoor unit
Use the handles at the back and at the bottom to carry the unit.
Installer reference guide
20
a Handles at the back of the unit
b Handles at the bottom of the unit. Carefully tilt the unit to the back so that the
handles become visible.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
4 About the units and options
In this chapter
4.1Overview: About the units and options ................................................................................................................................. 21
4.2.1Identification label: Outdoor unit .......................................................................................................................... 21
4.2.2Identification label: Indoor unit ............................................................................................................................. 22
4.3Combining units and options.................................................................................................................................................. 22
4.3.1Possible combinations of indoor unit and outdoor unit ....................................................................................... 22
4.3.2Possible options for the outdoor unit.................................................................................................................... 22
4.3.3Possible options for the indoor unit ...................................................................................................................... 23
4.1 Overview: About the units and options
This chapter contains information about:
▪ Identifying the outdoor unit
▪ Identifying the indoor unit
▪ Combining the outdoor unit with options
4 | About the units and options
▪ Combining the indoor unit with options
4.2 Identification
NOTICE
When installing or servicing several units at the same time, make sure NOT to switch
the service panels between different models.
4.2.1 Identification label: Outdoor unit
Location
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Model identification
Example: EPRA14DAV3
CodeExplanation
EPEuropean hydro-split outdoor pair heat pump
RHigh water temperature – ambient zone 2 (see operation
range)
ARefrigerant R32
Installer reference guide
21
4 | About the units and options
14Capacity class
DAModel series
V3Power supply
4.2.2 Identification label: Indoor unit
Location
Model identification
Example: ETVZ16S18DA6V
EEuropean model
CodeExplanation
CodeDescription
TVFloor-standing hydro-split unit with integrated tank
ZDual-zone model
16Capacity class
SIntegrated tank material: Stainless steel
18Integrated tank volume
DAModel series
6VBackup heater model
4.3 Combining units and options
4.3.1 Possible combinations of indoor unit and outdoor unit
Indoor unitOutdoor unit
EPRA14EPRA16EPRA18
ETVZ16OOO
4.3.2 Possible options for the outdoor unit
Installer reference guide
22
Mounting stand (EKMST1, EKMST2)
In colder regions where heavy snowfall can occur, it is recommended to install the
outdoor unit on a mounting frame. Use one of the following models:
▪ EKMST1 with flange feet: to install the outdoor unit on a concrete foundation
where drilling is allowed.
▪ EKMST2 with rubber feet: to install the outdoor unit on foundations where
drilling is not allowed or possible, such as flat roofs or pavements.
For installation instructions, see the installation manual of the mounting stand.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
4.3.3 Possible options for the indoor unit
Multi-zoning wired controls
You can connect the following multi-zoning wired controls:
▪ Multi-zoning base unit 230V (EKWUFHTA1V3)
▪ Digital thermostat 230V (EKWCTRDI1V3)
▪ Analogue thermostat 230V (EKWCTRAN1V3)
▪ Actuator 230V (EKWCVATR1V3)
For installation instructions, see the installation manual of the control, and the
addendum book for optional equipment.
Wireless room thermostat (EKRTR1)
You can connect an optional wireless room thermostat to the indoor unit.
For installation instructions, see the installation manual of the room thermostat
and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination
with the wireless thermostat (EKRTR1).
4 | About the units and options
For installation instructions, see the installation manual of the room thermostat
and addendum book for optional equipment.
Digital I/O PCB (EKRP1HBAA)
The digital I/O PCB is required to provide following signals:
▪ Alarm output
▪ Space heating/cooling On/OFF output
▪ Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and
addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install
the demand PCB.
For installation instructions, see the installation manual of the demand PCB and
addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal sensor of the dedicated Human Comfort Interface
(BRC1HHDA used as room thermostat) will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room
temperature on another location.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
For installation instructions, see the installation manual of the remote indoor
sensor and addendum book for optional equipment.
INFORMATION
▪ The remote indoor sensor can only be used in case the user interface is
configured with room thermostat functionality.
▪ You can only connect either the remote indoor sensor or the remote outdoor
sensor.
Installer reference guide
23
4 | About the units and options
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure the outdoor
temperature.
As an option the remote outdoor sensor can be installed to measure the outdoor
temperature on another location (e.g. to avoid direct sunlight) to have an
improved system behaviour.
For installation instructions, see the installation manual of the remote outdoor
sensor and the addendum book for optional equipment.
PC cable (EKPCCAB4)
The PC cable makes a connection between the switch box of the indoor unit and a
PC. It gives the possibility to update the software of the indoor unit.
For installation instructions, see the installation manual of the PC cable.
Heat pump convector (FWXV, FWXT, FWXM)
INFORMATION
You can only connect either the remote indoor sensor or the remote outdoor sensor.
For providing space heating/cooling, it is possible to use the following heat pump
convectors:
▪ FWXV: floor-standing model
▪ FWXT: wall-mounted model
▪ FWXM: concealed model
For installation instructions, see:
▪ The installation manual of the heat pump convectors
▪ The installation manual of the heat pump convector options
▪ The addendum book for optional equipment
LAN adapter for smartphone control + Smart Grid applications (BRP069A61)
You can install this LAN adapter to:
▪ Control the system via a smartphone app.
▪ Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN adapter and the
addendum book for optional equipment.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a smartphone app.
Installer reference guide
24
For installation instructions, see the installation manual of the LAN adapter and the
addendum book for optional equipment.
Universal centralised controller (EKCC8-W)
Controller for cascade control.
Conversion kit (EKHVCONV2)
Use the connection kit to convert a heating only model to a reversible model.
For installation instructions, see the installation manual of the conversion kit.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
4 | About the units and options
Human Comfort Interface (BRC1HHDA) used as room thermostat
▪ The Human Comfort Interface (HCI) used as room thermostat can only be used in
combination with the user interface connected to the indoor unit.
▪ The Human Comfort Interface (HCI) used as room thermostat needs to be
installed in the room that you want to control.
For installation instructions, see the installation and operation manual of the
Human Comfort Interface (HCI) as room thermostat.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Installer reference guide
25
5 | Application guidelines
5 Application guidelines
In this chapter
INFORMATION
Cooling is only applicable in case a conversion kit (EKHVCONV2) is installed.
5.2Setting up the space heating/cooling system ........................................................................................................................ 26
5.2.1Multiple rooms – TwoLWT zones ......................................................................................................................... 27
5.3Setting up the domestic hot water tank ................................................................................................................................ 30
5.3.1System layout – Integrated DHW tank .................................................................................................................. 30
5.3.2Selecting the volume and desired temperature for the DHW tank ...................................................................... 30
5.3.3Setup and configuration – DHW tank .................................................................................................................... 31
5.3.4DHW pump for instant hot water .......................................................................................................................... 32
5.3.5DHW pump for disinfection ................................................................................................................................... 32
5.4Setting up the energy metering ............................................................................................................................................. 33
5.4.2Consumed energy .................................................................................................................................................. 34
5.4.3Normal kWh rate power supply............................................................................................................................. 34
5.4.4Preferential kWh rate power supply...................................................................................................................... 36
5.5Setting up the power consumption control........................................................................................................................... 37
5.5.1Permanent power limitation.................................................................................................................................. 37
5.5.2Power limitation activated by digital inputs .......................................................................................................... 38
5.5.3Power limitation process ....................................................................................................................................... 39
5.5.4BBR16 power limitation ......................................................................................................................................... 39
5.6Setting up an external temperature sensor........................................................................................................................... 40
5.1 Overview: Application guidelines
The purpose of the application guidelines is to give a glance of the possibilities of
the heatpump system.
NOTICE
▪ The illustrations in the application guidelines are meant for reference only, and
are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic
dimensioning and balancing are NOT shown, and are the responsibility of the
installer.
▪ For more information about the configuration settings to optimize heat pump
operation, see "9Configuration"[4104].
This chapter contains application guidelines for:
▪ Setting up the space heating/cooling system
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up the power consumption control
▪ Setting up an external temperature sensor
5.2 Setting up the space heating/cooling system
Installer reference guide
26
The heat pump system supplies leaving water to heat emitters in one or more
rooms.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
5 | Application guidelines
a
Because the system offers a wide flexibility to control the temperature in each
room, you need to answer the following questions first:
▪ How many rooms are heated or cooled by the heatpump system?
▪ Which heat emitter types are used in each room and what is their design leaving
water temperature?
Once the space heating/cooling requirements are clear, we recommend to follow
the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the
room frost protection. However, the room frost protection is only possible if [C.2]
Space heating/cooling=On.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be
guaranteed in all conditions, then you have to set Emergency [9.5] to Automatic.
NOTICE
An overpressure bypass valve can be integrated in the system. Keep in mind that this
valve might not be shown on the illustrations.
NOTICE
If you install this unit as a single-zone application, then:
Setup. Install a bypass between the space heating water inlet and outlet of the
additional zone (=direct zone). Do NOT interrupt the water flow by closing the shutoff valves.
a Bypass
Configuration. Set field setting [7-02]=0 (Number of zones = Single zone).
5.2.1 Multiple rooms – TwoLWT zones
This unit is designed to deliver water at 2 different temperatures. A typical
installation consists of underfloor heating at a lower temperature and radiators at
a higher water temperature.
In this document:
▪ Main zone = Zone with the lowest design temperature in heating, and the highest
design temperature in cooling
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
▪ Additional zone = Zone with the highest design temperature in heating, and the
lowest design temperature in cooling
Typical example:
Installer reference guide
27
5 | Application guidelines
B
A
D
E
C
a
b
a
Room (zone)Heat emitters: Design temperature
Living room (main zone)Underfloor heating:
▪ In heating: 35°C
▪ In cooling: 20°C (only refreshment, no
real cooling allowed)
Bed rooms (additional zone)Heatpump convectors:
▪ In heating: 45°C
▪ In cooling: 12°C
Setup
A Additional leaving water temperature zone
B Room 1
C Room 2
D Main leaving water temperature zone
E Room 3
a Heatpump convectors (+ controllers)
b Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
▪ For the main zone: the room temperature is controlled by the dedicated Human
Comfort Interface (BRC1HHDA used as room thermostat).
▪ For the additional zone:
- The external thermostat is directly connected to the indoor unit.
- The desired room temperature is set via the external thermostat and the
thermostatic valves of the radiators in each room.
- The heating demand signal from the external thermostat is connected to the
digital input on the indoor unit (X2M/35a and X2M/30). The indoor unit will
only supply the desired additional leaving water temperature when there is an
actual demand.
Installer reference guide
28
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Configuration
5 | Application guidelines
SettingValue
Unit temperature control:
▪ #: [2.9]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the dedicated Human
▪ Code: [C-07]
Comfort Interface.
Note:
▪ Main room = dedicated Human
Comfort Interface used as room
thermostat functionality
▪ Other rooms = external room
thermostat functionality
Number of water temperature zones:
1 (Dual zone): Main + additional
▪ #: [4.4]
▪ Code: [7-02]
In case of heatpump convectors:
External room thermostat for the
additional zone:
1 (1 contact): When the used
external room thermostat or heatpump
convector can only send a thermo ON/
OFF condition. No separation between
▪ #: [3.A]
heating or cooling demand.
▪ Code: [C-06]
Shut-off valve outputSet to follow the thermo demand of the
main zone.
Benefits
▪ Comfort.
- The smart room thermostat functionality can decrease or increase the desired
leaving water temperature based on the actual room temperature
(modulation).
- The combination of the two heat emitter systems provides the excellent
heating comfort of the underfloor heating, and the excellent cooling comfort of
the heatpump convectors.
▪ Efficiency.
- Depending on the demand, the indoor unit supplies different leaving water
temperature matching the design temperature of the different heat emitters.
- Underfloor heating has the best performance with the heat pump system.
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Installer reference guide
29
5 | Application guidelines
A
a
b
5.3 Setting up the domestic hot water tank
5.3.1 System layout – Integrated DHW tank
5.3.2 Selecting the volume and desired temperature for the DHW tank
A Domestic hot water
a Cold water IN
b Hot water OUT
People experience water as hot when its temperature is 40°C. Therefore, the DHW
consumption is always expressed as equivalent hot water volume at 40°C.
However, you can set the DHW tank temperature at a higher temperature
(example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the volume and desired temperature for the DHW tank consists of:
1Determining the DHW consumption (equivalent hot water volume at 40°C).
2Determining the volume and desired temperature for the DHW tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent
hot water volume at 40°C) using typical water volumes:
QuestionTypical water volume
How many showers are needed per
1shower = 10min×10l/min = 100l
day?
How many baths are needed per day?1bath = 150l
How much water is needed at the
1sink = 2min×5l/min = 10l
kitchen sink per day?
Are there any other domestic hot water
—
needs?
Installer reference guide
30
Example: If the DHW consumption of a family (4 persons) per day is as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
Then the DHW consumption = (3×100l)+(1×150l)+(3×10l)=480l
EPRA14~18DAV3+W1 + ETVZ16S18+23DA6V+9W
Daikin Altherma 3 H HT F
4P587503-1 – 2019.07
Loading...
+ 218 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.