INSTALLATION MANUAL
Master/Slave interface
Power interface
EPIMSA6
EPIA6
Installation manual
Master/Slave interface + Power interface
Installationsanleitung
Master/Slave Schnittstelle + Stromschnittstelle
Manuel d'installation
Interface maître/esclave + Interface d'alimentation
Manual de instalación
Interfaz Unidad principal/Unidad esclava + Interfaz de alimentación
Manuale d'installazione
Interfaccia "master/slave" + Interfaccia di alimentazione
English
Deutsch
Français
Español
Italiano
EPIMSA6
EPIA6
The
Master/Slave interface
installed to use microprocessor-based control panels on
the whole range of units for models with a current
consumption greater than 1.12 A.
The EPIMSA6
Master/Slave interface
or
Power interface
Master/Slave interface
Power interface
must be
is used for
connecting up to 4 units in parallel to 1 controller
(ECFWEB6 or ECFWER6). Up to 3 EPIMSA6 interfaces
can be connected in parallel to 1 controller. The capacity
of the EPIMSA6 contacts is 4 x 3 A.
The EPIA6
Power interface
permits to use the
electronic remote controller (ECFWEB6 or ECFWER6)
on the whole range of units with a current consumption
greater than 1.12 A. The capacity of the EPIA6 contacts
is 16 A.
Neglecting the absolute requirement to install
an additional interface (EPIA6 or EPIMSA6) to
units with a current consumption greater than
1.12 A may cause fire or other damage to the
equipment.
Ta ble below lists the maximum current of the whole
range of units.
FWL, FWM, FWV FWB FWD
01 0.16 A — —
02 0.21 A 0.56 A —
03 0.27 A 0.56 A —
04 0.39 A 0.56 A 0.95 A
05 —
06 0.38 A
07 —
08 0.80 A
09 —
10
1.12 A 1.40 A 1.97 A
12 — —
16 — —
18 — —
≤
>1.12 A
Master/Slave function is possible by installing the EPIMSA6
1.12 A
EPIMSA6 or EPIA6 must be installed
EPIA6 must be installed
>3 A
1.10 A —
1.10 A 1.58 A
1.10 A —
1.40 A 1.97 A
1.40 A —
3.21 A
5.37 A
5.37 A
Installation manual
ECHNICAL SPECIFICATIONS
T
EPIMSA6 EPIA6
Power supply
Contacts at output 4x 3A 250 V 1x 16A 250 V
Operating temperature 0~40°C
Humidity limits (RH)
Protection rating IP30
Container 105 x 90 x 70 mm
Weight 265 g
I
NSTALLATION
■
All field wiring and components must be
installed by a licensed electrician and must
comply with relevant local and national
regulations.
■
Before obtaining access to terminals, all
power supply circuits must be interrupted.
■
The EPIMSA6 or EPIA6 interfaces are to be installed
on a DIN guide, usually housed in the electric boards
cabinet.
■
The overall dimensions of the EPIMSA6 and EPIA6
interface are shown in figure 3.
■
Make the electrical connections with POWER OFF
as indicated in the diagrams of figure 1+2 that show
the following:
Figure 1: microprocessor-based controller + 2x
EPIMSA6 connected to 8 units.
Figure 2: connections of EPIA6
Each unit requires a switch (IL) on the power supply line
with a distance of at least 3 mm between the opening
contacts, and a suitable safety fuse (F).
NOTE
Connect only one unit per EPIMSA6 or
EPIA6 output.
230 V
–15% +10% 50 Hz
20~80%
non-condensing
EPIMSA6 + EPIA6
Master/Slave interface + Power interface
4PW17562-1A
Installation manual
1