Daikin EGSQH10S18AA9W Installer reference guide

Page 1
Installer reference guide
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
Installer reference guide
Daikin Altherma ground source heat pump
English
Page 2

Table of contents

Table of contents
6.4.3 Overview of electrical connections except external
actuators ...................................................................... 22
6.4.4 Overview of electrical connections for external and
internal actuators ......................................................... 22
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 3
1.2 For the installer.......................................................................... 3
1.2.1 General ....................................................................... 3
1.2.2 Installation site ............................................................ 4
1.2.3 Refrigerant .................................................................. 4
1.2.4 Brine............................................................................ 5
1.2.5 Water .......................................................................... 5
1.2.6 Electrical ..................................................................... 5
2 About the documentation 6
2.1 About this document.................................................................. 6
2.2 Installer reference guide at a glance ......................................... 6
3 About the box 6
3.1 Overview: About the box ........................................................... 6
3.2 Indoor unit ................................................................................. 7
3.2.1 To unpack the indoor unit ........................................... 7
3.2.2 To remove the accessories from the indoor unit......... 7
4 About the units and options 7
4.1 Overview: About the units and options...................................... 7
4.2 Identification .............................................................................. 7
4.2.1 Identification label: Indoor unit .................................... 7
4.3 Possible options for the indoor unit ........................................... 7
5 Application guidelines 8
5.1 Overview: Application guidelines............................................... 8
5.2 Setting up the space heating system ........................................ 9
5.2.1 Single room................................................................. 9
5.2.2 Multiple rooms – OneLWT zone ................................ 10
5.2.3 Multiple rooms – TwoLWT zones............................... 12
5.3 Setting up an auxiliary heat source for space heating............... 13
5.4 Setting up the domestic hot water tank ..................................... 14
5.4.1 System layout – Integrated DHW tank........................ 14
5.4.2 Selecting the desired temperature for the DHW tank . 14
5.4.3 Setup and configuration – DHW tank.......................... 15
5.4.4 DHW pump for instant hot water................................. 15
5.4.5 DHW pump for disinfection ......................................... 15
5.5 Setting up the energy metering ................................................. 16
5.5.1 Produced heat............................................................. 16
5.5.2 Consumed energy....................................................... 16
5.5.3 Normal kWh rate power supply................................... 16
5.5.4 Preferential kWh rate power supply............................ 16
5.6 Setting up the power consumption control ................................ 16
5.6.1 Permanent power limitation ........................................ 17
5.6.2 Power limitation activated by digital inputs ................. 17
5.6.3 Power limitation process ............................................. 17
5.7 Setting up an external temperature sensor ............................... 18
6 Preparation 18
6.1 Overview: Preparation............................................................... 18
6.2 Preparing installation site .......................................................... 18
6.2.1 Installation site requirements of the indoor unit .......... 18
6.3 Preparing piping ........................................................................ 18
6.3.1 Circuit requirements.................................................... 18
6.3.2 Formula to calculate the expansion vessel pre-
pressure ...................................................................... 20
6.3.3 To check the water volume and flow rate of the
space heating circuit and brine circuit......................... 20
6.3.4 Changing the pre-pressure of the expansion vessel... 21
6.3.5 To check the water volume: Examples ....................... 21
6.4 Preparing electrical wiring ......................................................... 22
6.4.1 About preparing electrical wiring................................. 22
6.4.2 About preferential kWh rate power supply.................. 22
7 Installation 23
7.1 Overview: Installation ................................................................. 23
7.2 Opening the units ....................................................................... 23
7.2.1 About opening the units ............................................... 23
7.2.2 To open the indoor unit ................................................ 23
7.2.3 To open the switch box cover of the indoor unit .......... 24
7.3 Mounting the indoor unit............................................................. 24
7.3.1 About mounting the indoor unit.................................... 24
7.3.2 Precautions when mounting the indoor unit................. 24
7.3.3 To install the indoor unit............................................... 24
7.4 Connecting the brine piping........................................................ 25
7.4.1 About connecting the brine piping................................ 25
7.4.2 Precautions when connecting the brine piping ............ 25
7.4.3 To connect the brine piping.......................................... 26
7.4.4 To fill the brine circuit ................................................... 26
7.4.5 To connect the pressure relief valve to the drain on
the brine side ............................................................... 26
7.4.6 To insulate the brine piping.......................................... 26
7.5 Connecting the water piping....................................................... 27
7.5.1 About connecting the water piping............................... 27
7.5.2 Precautions when connecting the water piping............ 27
7.5.3 To connect the water piping......................................... 27
7.5.4 To connect the recirculation piping .............................. 27
7.5.5 To connect the pressure relief valve to the drain......... 27
7.5.6 To connect the drain hose ........................................... 28
7.5.7 To fill the space heating circuit..................................... 28
7.5.8 To fill the domestic hot water tank ............................... 28
7.5.9 To insulate the water piping ......................................... 28
7.6 Connecting the electrical wiring.................................................. 28
7.6.1 About connecting the electrical wiring.......................... 28
7.6.2 About electrical compliance ......................................... 29
7.6.3 Precautions when connecting the electrical wiring ...... 29
7.6.4 Guidelines when connecting the electrical wiring ........ 29
7.6.5 To connect the electrical wiring on the indoor unit....... 29
7.6.6 To connect the main power supply .............................. 30
7.6.7 To connect the remote outdoor sensor........................ 31
7.6.8 To connect the user interface ...................................... 31
7.6.9 To connect the shut-off valve....................................... 32
7.6.10 To connect the electrical meters .................................. 32
7.6.11 To connect the domestic hot water pump .................... 32
7.6.12 To connect the alarm output ........................................ 33
7.6.13 To connect the space heating ON/OFF output ............ 33
7.6.14 To connect the changeover to external heat source .... 33
7.6.15 To connect the power consumption digital inputs ........ 33
7.7 Finishing the indoor unit installation ........................................... 33
7.7.1 To fix the user interface cover to the indoor unit.......... 33
7.7.2 To close the indoor unit................................................ 34
8 Configuration 34
8.1 Overview: Configuration ............................................................. 34
8.1.1 To connect the PC cable to the switch box.................. 34
8.1.2 To access the most used commands .......................... 34
8.1.3 To copy the system settings from the first to the
second user interface................................................... 35
8.1.4 To copy the language set from the first to the second
user interface ............................................................... 36
8.1.5 Quick wizard: Set the system layout after first power
ON................................................................................ 36
8.2 Basic configuration ..................................................................... 36
8.2.1 Quick wizard: Language / time and date...................... 36
8.2.2 Quick wizard: Standard................................................ 36
8.2.3 Quick wizard: Options .................................................. 38
8.2.4 Quick wizard: Capacities (energy metering) ................ 40
8.2.5 Space heating control .................................................. 40
8.2.6 Domestic hot water control .......................................... 43
8.2.7 Contact/helpdesk number ............................................ 43
Installer reference guide
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 3

1 General safety precautions

8.3 Advanced configuration/optimization......................................... 43
8.3.1 Space heating operation: advanced ........................... 43
8.3.2 Domestic hot water control: advanced........................ 46
8.3.3 Heat source settings ................................................... 49
8.3.4 System settings........................................................... 50
8.4 Menu structure: Overview user settings .................................... 53
8.5 Menu structure: Overview installer settings............................... 54
9 Commissioning 55
9.1 Overview: Commissioning......................................................... 55
9.2 Precautions when commissioning ............................................. 55
9.3 Checklist before commissioning................................................ 55
9.4 Checklist during commissioning ................................................ 55
9.4.1 To check the minimum flow rate ................................. 55
9.4.2 Air purge function on the space heating circuit........... 55
9.4.3 Air purge function on the brine circuit ......................... 56
9.4.4 To perform a test run .................................................. 57
9.4.5 To perform an actuator test run .................................. 58
9.4.6 Underfloor heating screed dryout................................ 58
10 Hand-over to the user 59
10.1 To fix the applicable language on the unit name plate .............. 59
11 Maintenance and service 60
11.1 Overview: Maintenance and service ......................................... 60
11.2 Maintenance safety precautions................................................ 60
11.3 Checklist for yearly maintenance of the indoor unit................... 60
11.4 To drain the domestic hot water tank ........................................ 61
12 Troubleshooting 61
12.1 Overview: Troubleshooting........................................................ 61
12.2 Precautions when troubleshooting ............................................ 61
12.3 Solving problems based on symptoms...................................... 62
12.3.1 Symptom: The unit is NOT heating as expected ........ 62
12.3.2 Symptom: The compressor does NOT start (space
heating or domestic water heating)............................. 62
12.3.3 Symptom: The pump is making noise (cavitation) ...... 62
12.3.4 Symptom: The pressure relief valve opens................. 62
12.3.5 Symptom: The pressure relief valve leaks .................. 63
12.3.6 Symptom: The space is NOT sufficiently heated at
low outdoor temperatures ........................................... 63
12.3.7 Symptom: The pressure at the tapping point is
temporarily unusual high............................................. 63
12.3.8 Symptom: Decoration panels are pushed away due
to a swollen tank ......................................................... 63
12.3.9 Symptom: Tank disinfection function is NOT
completed correctly (AH-error).................................... 63
12.4 Solving problems based on error codes .................................... 63
12.4.1 Error codes: Overview ................................................ 64
13 Disposal 65
14 Technical data 66
14.1 Overview: Technical data .......................................................... 66
14.2 Dimensions and service space.................................................. 66
14.2.1 Dimensions and service space: Indoor unit ................ 66
14.3 Components .............................................................................. 69
14.3.1 Components: Switch box (indoor unit) ........................ 69
14.4 Piping diagram .......................................................................... 70
14.4.1 Piping diagram: Indoor unit ......................................... 70
14.5 Wiring diagram .......................................................................... 71
14.5.1 Wiring diagram: Indoor unit ......................................... 71
14.6 Technical specifications ............................................................ 79
14.6.1 Technical specifications: Indoor unit ........................... 79
14.7 Operation range ........................................................................ 82
14.7.1 Operation range: Indoor unit ....................................... 82
14.8 ESP curve ................................................................................. 84
14.8.1 ESP curve: Indoor unit ................................................ 84
15 Glossary 85
1 General safety precautions

1.1 About the documentation

▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide must be performed by an authorized installer.

1.1.1 Meaning of warnings and symbols

DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of extreme hot or cold temperatures.
WARNING
Indicates a situation that could result in death or serious injury.
CAUTION
Indicates a situation that could result in minor or moderate injury.
NOTICE
Indicates a situation that could result in equipment or property damage.
INFORMATION
Indicates useful tips or additional information.

1.2 For the installer

1.2.1 General

If you are not sure how to install or operate the unit, contact your dealer.
NOTICE
Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin.
WARNING
Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.
16 Field settings table 86
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
Page 4
1 General safety precautions
WARNING
Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information must be provided at an accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.

1.2.2 Installation site

▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are not subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.
WARNING
Always recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant must be treated according to the applicable legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with "Liquid filling siphon attached")
Charge with the cylinder upright.

1.2.3 Refrigerant

If applicable. See the installation manual or installer reference guide of your application for more information.
Installer reference guide
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 5
1 General safety precautions
If Then
A siphon tube is NOT present Charge with the cylinder upside
down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is not closed immediately, remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.

1.2.4 Brine

If applicable. See the installation manual or installer reference guide of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.
WARNING
The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.
WARNING
The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.

1.2.5 Water

If applicable. See the installation manual or installer reference guide of your application for more information.

1.2.6 Electrical

DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or touching electrical parts.
▪ Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, shall be installed in the fixed wiring.
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring must be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.
NOTICE
Make sure water quality complies with EU directive 98/83EC.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
Page 6

2 About the documentation

NOTICE
Precautions when laying power wiring:
▪ Do not connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure below.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1 metre away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.
2 About the documentation

2.1 About this document

Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set consists of:
General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the indoor unit)
Indoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the indoor unit)
Installer reference guide:
▪ Preparation of the installation, technical specifications, good
practices, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the indoor unit) + Digital files on
http://www.daikineurope.com/support-and-manuals/product­information/
Latest revisions of the supplied documentation may be available on the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages are translations.

2.2 Installer reference guide at a glance

Chapter Description
General safety precautions
About the documentation What documentation exists for the
About the box How to unpack the units and remove
About the units and options
Application guidelines Various installation setups of the system
Preparation What to do and know before going
Installation What to do and know to install the
Configuration What to do and know to configure the
Commissioning What to do and know to commission the
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and
Safety instructions that you must read before installing
installer
their accessories
▪ How to identify the units
▪ Possible combinations of units and
options
on‑site
system
system after it is installed
system after it is configured
kept for future reference
Note: There is also an installer settings table in the user reference guide. This table has to be filled in by the installer and handed over to the user.

3 About the box

3.1 Overview: About the box

This chapter describes what you have to do after the box with the indoor unit is delivered on-site.
It contains information about:
▪ Unpacking and handling the units
▪ Removing the accessories from the units
Keep the following in mind:
▪ At delivery, the unit must be checked for damage. Any damage
must be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
Installer reference guide
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 7

4 About the units and options

a
b
c
d
f
e
g

3.2 Indoor unit

3.2.1 To unpack the indoor unit

3.2.2 To remove the accessories from the indoor unit

1 Remove the screws at the top of the unit.
2 Remove the top panel.
4 About the units and options

4.1 Overview: About the units and options

This chapter contains information about:
▪ Identifying the indoor unit
▪ Combining the indoor unit with options

4.2 Identification

NOTICE
When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

4.2.1 Identification label: Indoor unit

Location
Model identification
Example: EGSQH10S18AA9W
Code Description
E European model
GS Ground source heat pump
3 Remove the accessories.
Q Refrigerant R410A
H Heating only
10 Capacity class
S Integrated tank material: Stainless steel
18 Integrated tank volume
AA Model series
9W Backup heater model

4.3 Possible options for the indoor unit

a General safety precautions
b Addendum book for optional equipment
c Installation manual
d Operation manual
e Remote outdoor sensor
f User interface kit cover
g Multilingual fluorinated greenhouse gases label
4 Reinstall the top panel.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
User interface (EKRUCBL*)
The user interface and a possible additional user interface are available as an option.
The additional user interface can be connected:
▪ To have both:
▪ control close to the indoor unit,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.
Following user interfaces are available:
Installer reference guide
7
Page 8

5 Application guidelines

▪ EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
▪ EKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ EKRUCBL7 contains following languages: English, German,
Russian, Danish.
Languages on the user interface can be uploaded by PC software or copied from an user interface to the other.
For installation instructions, see "7.6.8 To connect the user
interface"on page31.
Simplified user interface (EKRUCBS)
▪ The simplified user interface can only be used in combination with
the main user interface.
▪ The simplified user interface acts as room thermostat and needs
to be installed in the room that you want it to control.
For installation instructions, see the installation and operation manual of the simplified user interface.
Room thermostat (EKRTWA, EKRTR1)
You can connect an optional room thermostat to the indoor unit. This thermostat can either be wired (EKRTWA) or wireless (EKRTR1).
For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (EKRTR1).
For installation intructions, see the installation manual of the room thermostat and addendum book for optional equipment.
Digital I/O PCB (EKRP1HB)
The digital I/O PCB is required to provide following signals:
▪ Alarm output
▪ Space heating On/OFF output
▪ Changeover to external heat source
For installation instructions, see the installation manual of the digital I/O PCB and addendum book for optional equipment.
Demand PCB (EKRP1AHTA)
To enable the power saving consumption control by digital inputs you must install the demand PCB.
For installation instructions, see the installation manual of the demand PCB and addendum book for optional equipment.
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room temperature sensor.
As an option the remote indoor sensor can be installed to measure the room temperature on another location.
For installation instructions, see the installation manual of the remote indoor sensor and addendum book for optional equipment.
INFORMATION
The remote indoor sensor can only be used in case the user interface is configured with room thermostat functionality.
PC configurator (EKPCCAB)
The PC cable makes a connection between the switch box of the indoor unit and a PC. It gives the possibility to upload different language files to the user interface and indoor parameters to the indoor unit. For the available language files, contact your local dealer.
The software and corresponding operating instructions are available on http://www.daikineurope.com/support-and-manuals/software-
downloads/.
For installation instructions, see the installation manual of the PC cable and "8Configuration"on page34.
Heat pump convector (FWXV)
For providing space heating/cooling, it is possible to use heat pump convectors (FWXV).
For installation instructions, refer to the installation manual of the heat pump convectors, and the addendum book for optional equipment.
Cable for brine pressure switch connection (EKGSCONBP1)
Depending on the applicable legislation, you might have to install a brine pressure switch (field supply). To connect the brine pressure switch to the unit, you can use the cable for brine pressure switch connection.
For installation instructions, see the installation manual of the cable for brine pressure switch connection.
NOTICE
Daikin recommends to use a mechanical brine pressure switch. If an electrical brine pressure switch is used, capacitive currents might disturb the flow switch operation causing an error on the unit.
Brine filling kit (KGSFILL)
Brine filling valve kit for flushing, filling, and draining the brine circuit.
5 Application guidelines

5.1 Overview: Application guidelines

The purpose of the application guidelines is to give a glance of the possibilities of the Daikin heatpump system.
NOTICE
▪ The illustrations in the application guidelines are meant
for reference only, and are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.
▪ For more information about the configuration settings to
optimize heatpump operation, see "8Configuration"on
page34.
INFORMATION
Energy metering functionality is NOT applicable and/or NOT valid for this unit if it is calculated by the unit. If optional external meters are used, energy metering display is valid.
This chapter contains application guidelines for:
▪ Setting up the space heating system
Installer reference guide
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 9
5 Application guidelines
B
A
a
B
A
b
a
▪ Setting up an auxiliary heat source for space heating
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up the power consumption
▪ Setting up an external temperature sensor

5.2 Setting up the space heating system

The Daikin heat pump system supplies leaving water to heat emitters in one or more rooms.
Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:
▪ How many rooms are heated by the Daikin heatpump system?
▪ Which heat emitter types are used in each room and what is their
design leaving water temperature?
Once the space heating requirements are clear, Daikin recommends to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on the unit's user interface is turned ON.
INFORMATION
In case an external room thermostat is used and room frost protection needs to be guaranteed in all conditions, then you have to set auto emergency [A.5.1.2] to 1.

5.2.1 Single room

Underfloor heating or radiators – Wired room thermostat
Setup
▪ The room temperature is controlled by the user interface, which is
used as room thermostat. Possible installations:
▪ User interface (standard equipment) installed in the room and
used as room thermostat
▪ User interface (standard equipment) installed at the indoor unit
and used for control close to the indoor unit + user interface (optional equipment EKRUCBL*) installed in the room and used as room thermostat
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
Benefits
Cost effective. You do NOT need an additional external room
thermostat.
Highest comfort and efficiency. The smart room thermostat
functionality can decrease or increase the desired leaving water temperature based on the actual room temperature (modulation). This results in:
▪ Stable room temperature matching the desired temperature
(higher comfort)
▪ Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
▪ Lowest possible leaving water temperature (higher efficiency)
Easy. You can easily set the desired room temperature via the
user interface:
▪ For your daily needs, you can use preset values and schedules.
▪ To deviate from your daily needs, you can temporarily overrule
the preset values and schedules, use the holiday mode…
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
0 (1 LWT zone): Main
Underfloor heating or radiators – Wireless room thermostat
A Main leaving water temperature zone B One single room
a User interface used as room thermostat
▪ The underfloor heating or radiators are directly connected to the
indoor unit.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Setup
A Main leaving water temperature zone B One single room
a Receiver for wireless external room thermostat b Wireless external room thermostat
Installer reference guide
9
Page 10
5 Application guidelines
B
A
a
T
B C
A
a
▪ The underfloor heating or radiators are directly connected to the
indoor unit.
▪ The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
External room thermostat for the main zone:
▪ #: [A.2.2.4]
▪ Code: [C-05]
Benefits
Wireless. The Daikin external room thermostat is available in a
wireless version.
Efficiency. Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heatpump system.
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
1 (Thermo ON/OFF): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition.
Heatpump convectors
Setup
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
External room thermostat for the main zone:
▪ #: [A.2.2.4]
▪ Code: [C-05]
Benefits
Efficiency. Optimal energy efficiency because of the interlink
function.
Stylish.
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
1 (Thermo ON/OFF): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition.
5.2.2 Multiple rooms – OneLWT zone
If only one leaving water temperature zone is needed because the design leaving water temperature of all heat emitters is the same, you do NOT need a mixing valve station (cost effective).
Example: If the heat pump system is used to heat up one floor where all the rooms have the same heat emitters.
Underfloor heating or radiators – Thermostatic valves
If you are heating up rooms with under floor heating or radiators, a very common way is to control the temperature of the main room by using a thermostat (this can either be the user interface or an external room thermostat), while the other rooms are controlled by so-called thermostatic valves, which open or close depending on the room temperature.
Setup
A Main leaving water temperature zone B One single room
a Remote controller of the heatpump convectors
▪ The underfloor heating or radiators are directly connected to the
indoor unit.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The space heating demand signal is sent to one digital input on
the indoor unit (X2M/1 and X2M/4).
INFORMATION
When using multiple heat pump convectors, make sure each one receives the infrared signal from the remote controller of the heatpump convectors.
Installer reference guide
10
A Main leaving water temperature zone B Room 1 C Room 2
a User interface
▪ The underfloor heating of the main room is directly connected to
the indoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as thermostat.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 11
5 Application guidelines
M2M1
B C
A
a a
b
B
A
a a
C
▪ A thermostatic valve is installed before the underfloor heating in
each of the other rooms.
INFORMATION
Mind situations where the main room can be heated by another heating source. Example: Fireplaces.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
Benefits
Cost effective.
Easy. Same installation as for one room, but with thermostatic
valves.
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
0 (1 LWT zone): Main
Underfloor heating or radiators – Multiple external room thermostats
Setup
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
Benefits
Compared with underfloor heating or radiators for one room:
Comfort. You can set the desired room temperature, including
schedules, for each room via the room thermostats.
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
Heatpump convectors
Setup
A Main leaving water temperature zone B Room 1 C Room 2
a External room thermostat
b Bypass valve
▪ For each room, a shut-off valve (field supplied) is installed to avoid
leaving water supply when there is no heating demand.
▪ A bypass valve must be installed to make water recirculation
possible when all shut-off valves are closed.To guarantee reliable operation, provide a minimum water flow rate as described in
"6.3.3 To check the water volume and flow rate of the space heating circuit and brine circuit"on page20.
▪ The room thermostats are connected to the shut-off valves, but do
NOT have to be connected to the indoor unit. The indoor unit will supply leaving water all the time, with the possibility to program a leaving water schedule.
A Main leaving water temperature zone B Room 1 C Room 2
a Remote controller of the heatpump convectors
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The heating demand signals of each heat pump convector are
connected in parallel to the digital input on the indoor unit (X2M/1 and X2M/4). The indoor unit will only supply leaving water temperature when there is an actual demand.
INFORMATION
To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heatpump convector.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
1 (Ext RT control): Unit operation is decided by the external thermostat.
0 (1 LWT zone): Main
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
11
Page 12
5 Application guidelines
b
B C
A
a
M1
B
A
a a
C
E
D
b
c
d
Benefits
Compared with heatpump convectors for one room:
Comfort. You can set the desired room temperature, including
schedules, for each room via the remote controller of the heatpump convectors.
Combination: Underfloor heating + Heatpump convectors
Setup
In this document:
▪ Main zone = Zone with the lowest design temperature
▪ Additional zone = The other zone
CAUTION
When there is more than one leaving water zone, you must ALWAYS install a mixing valve station in the main zone to decrease (in heating) the leaving water temperature when the additional zone has demand.
Typical example:
Room (zone) Heat emitters: Design
temperature
Living room (main zone) Underfloor heating: 35°C
Bed rooms (additional zone) Heatpump convectors: 45°C
Setup
A Main leaving water temperature zone B Room 1 C Room 2
a External room thermostat b Remote controller of the heatpump convectors
▪ For each room with heat pump convectors: The heat pump
convectors are directly connected to the indoor unit.
▪ For each room with under floor heating: A shut-off valve (field
supply) is installed before the underfloor heating. It prevents hot water supply when the room has no heating demand.
▪ For each room with heat pump convectors: The desired room
temperature is set via the remote controller of the heat pump convectors.
▪ For each room with under floor heating: The desired room
temperature is set via the external room thermostat (wired or wireless).
INFORMATION
To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heatpump convector.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
Number of water temperature
0 (LWT control): Unit operation is decided based on the leaving water temperature.
0 (1 LWT zone): Main
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
5.2.3 Multiple rooms – TwoLWT zones
If the heat emitters selected for each room are designed for different leaving water temperatures, you can use different leaving water temperature zones (maximum 2).
Installer reference guide
12
A Additional leaving water temperature zone B Room 1 C Room 2 D Main leaving water temperature zone E Room 3
a Remote controller of the heatpump convectors b User interface c Mixing valve station d Pressure regulating valve
INFORMATION
A pressure regulating valve should be implemented before the mixing valve station. This is to guarantee the correct water flow balance between the main leaving water temperature zone and the additional leaving water temperature zone in relation to the required capacity of both water temperature zones.
▪ For the main zone:
▪ A mixing valve station is installed before the underfloor heating.
▪ The pump of the mixing valve station is controlled by the ON/
OFF signal on the indoor unit (X2M/5 and X2M/7; normal closed shut-off valve output).
▪ The room temperature is controlled by the user interface, which
is used as room thermostat.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 13
5 Application guidelines
a
b b
d
c
f
h
e
FHL1
FHL2
FHL3
f g
g
j
i
▪ For the additional zone:
▪ The heatpump convectors are directly connected to the indoor
unit.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors for each room.
▪ The heating demand signals of each heatpump convector are
connected in parallel to the digital input on the indoor unit (X2M/1 and X2M/4). The indoor unit will only supply the desired additional leaving water temperature when there is an actual demand.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is decided based on the ambient temperature of the user interface.
Note:
▪ Main room = user interface
used as room thermostat functionality
▪ Other rooms = external room
thermostat functionality
Number of water temperature zones:
1 (2 LWT zones): Main + additional
▪ #: [A.2.1.8]
▪ Code: [7-02]
In case of heatpump convectors:
External room thermostat for the additional zone:
▪ #: [A.2.2.5]
1 (Thermo ON/OFF): When the used external room thermostat or heatpump convector can only send a thermo ON/OFF condition.
▪ Code: [C-06]
Shut-off valve output Set to follow the thermo demand
of the main zone.
At the mixing valve station Set the desired main leaving
water temperature.
▪ When the room thermostat requests heating, the indoor unit or the
auxiliary boiler starts operating depending on the outdoor temperature (status of the changeover to external heat source). When the permission is given to the auxiliary boiler, the space heating by the indoor unit is turned OFF.
▪ Bivalent operation is only possible for space heating, NOT for
domestic hot water production. Domestic hot water is always produced by the DHW tank connected to the indoor unit.
INFORMATION
▪ During heating operation of the heat pump, the
heat pump operates to achieve the desired temperature set via the user interface. When weather­dependent operation is active, the water temperature is determined automatically depending on the outdoor temperature.
▪ During heating operation of the auxiliary boiler, the
auxiliary boiler operates to achieve the desired water temperature set via the auxiliary boiler controller.
Setup
▪ Integrate the auxiliary boiler as follows:
Benefits
Comfort.
▪ The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on the actual room temperature (modulation).
▪ The combination of the two heat emitter systems provides the
excellent heating comfort of the under floor heating, and the rapid air heat up of the heat pump convectors (e.g., living room=under floor heating and the bedroom=convector (no continuous heating)).
Efficiency.
▪ Depending on the demand, the indoor unit supplies different
leaving water temperature matching the design temperature of the different heat emitters.
▪ Underfloor heating has the best performance with Altherma LT.

5.3 Setting up an auxiliary heat source for space heating

▪ Space heating can be done by:
▪ The indoor unit
▪ An auxiliary boiler (field supply) connected to the system
a Indoor unit b Heat exchanger c Backup heater d Pump e Shut-off valve (field supply)
f Non-return valve (field supply) g Shut-off valve (field supply) h Collector (field supply)
i Auxiliary boiler (field supply)
j Aquastat valve (field supply)
FHL1...3 Underfloor heating
NOTICE
▪ Make sure the auxiliary boiler and its integration in the
system complies with applicable legislation.
▪ Daikin is NOT responsible for incorrect or unsafe
situations in the auxiliary boiler system.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
13
Page 14
5 Application guidelines
L
N
H
Com
A
K2AK1A
X2M
B
TI
K2AK1A
Indoor/Auto/Boiler
1 2 3 4 X Y
Indoor
FHL1
FHL2
FHL3
UI
a e
b
c
hgg
M
f
d
▪ Make sure the return water to the heatpump does NOT exceed
55°C. To do so:
▪ Set the desired water temperature via the auxiliary boiler
controller to maximum 55°C.
▪ Install an aquastat valve in the return water flow of the
heatpump.
▪ Set the aquastat valve to close above 55°C and to open below
55°C.
▪ Install non-return valves.
▪ Make sure to only have one expansion vessel in the water circuit.
An expansion vessel is already premounted in the indoor unit.
▪ Install the digital I/O PCB (option EKRP1HB).
▪ Connect X1 and X2 (changeover to external heat source) on the
PCB to the auxiliary boiler thermostat.
▪ To setup the heat emitters, see "5.2Setting up the space heating
system"on page9.
Configuration
Via the user interface (quick wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
NOTICE
▪ Make sure the bivalent hysteresis has enough
differential to prevent frequent changeover between indoor unit and auxiliary boiler.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.
NOTICE
▪ Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between indoor unit and auxiliary boiler.
▪ If the auxiliary contact is an outdoor temperature
thermostat, install the thermostat in the shadow so that it is NOT influenced or turned ON/OFF by direct sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.

5.4 Setting up the domestic hot water tank

5.4.1 System layout – Integrated DHW tank

Changeover to external heat source decided by an auxiliary contact
▪ Only possible in external room thermostat control AND one
leaving water temperature zone (see "5.2 Setting up the space
heating system"on page9).
▪ The auxiliary contact can be:
▪ An outdoor temperature thermostat
▪ An electricity tariff contact
▪ A manually operated contact
▪ …
▪ Setup: Connect the following field wiring:
Installer reference guide
14
BTIBoiler thermostat input
A Auxiliary contact (normal closed)
H Heating demand room thermostat (optional) K1A Auxiliary relay for activation of indoor unit (field supply) K2A Auxiliary relay for activation of boiler (field supply)
Indoor Indoor unit
Auto Automatic
Boiler Boiler
a Indoor unit b Heat exchanger c Backup heater d Pump e Motorised 3‑way valve
f DHW tank g Shut-off valve (field supply) h Collector (field supply)
FHL1...3 Underfloor heating
UI User interface

5.4.2 Selecting the desired temperature for the DHW tank

People experience water as hot when its temperature is 40°C. Therefore, the DHW consumption is always expressed as equivalent hot water volume at 40°C. However, you can set the DHW tank temperature at a higher temperature (example: 53°C), which is then mixed with cold water (example: 15°C).
Selecting the volume and desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the volume and desired temperature for the DHW
tank.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 15
5 Application guidelines
b c
a
d
e
f
b
a
c e
d
f
g
h
Possible DHW tank volumes
Type Possible volumes
Integrated DHW tank ▪ 180l
Energy saving tips
▪ If the DHW consumption differs from day to day, you can program
a weekly schedule with different desired DHW tank temperatures for each day.
▪ The lower the desired DHW tank temperature, the more cost
effective.
▪ The heatpump itself can produce domestic hot water of maximum
55°C. The electrical resistance integrated in the heat pump can higher this temperature. However, this consumes more energy. Daikin recommends to set the desired DHW tank temperature below 55°C to avoid using the electrical resistance.
▪ When the heatpump produces domestic hot water, it cannot heat
up a space. When you need domestic hot water and space heating at the same, Daikin recommends to produce the domestic hot water during the night when there is lower space heating demand.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption (equivalent hot water volume at 40°C) using the typical water volumes:
Question Typical water volume
How many showers are needed
1shower=10min×10l/min=100l
per day?
How many baths are needed per
1bath=150l
day?
How much water is needed at the
1sink=2min×5l/min=10l
kitchen sink per day?
Are there any other domestic hot
water needs?
Example: If the DHW consumption of a family (4 persons) per day is as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
Then the DHW consumption = (3×100l)+(1×150l)+(3×10l)=480l
Determining the volume and desired temperature for the DHW tank
Formula Example
V1=V2+V2×(T2−40)/(40−T1) If:
▪ V2=180l
▪ T2=54°C
▪ T1=15°C
Then V1=280l
V2=V1×(40−T1)/(T2−T1) If:
▪ V1=480l
▪ T2=54°C
▪ T1=15°C
Then V2=307l
V1DHW consumption (equivalent hot water volume at 40°C) V2Required DHW tank volume if only heated once T2DHW tank temperature T1Cold water temperature

5.4.3 Setup and configuration – DHW tank

▪ For large DHW consumptions, you can heat up the DHW tank
several times during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
▪ Thermodynamic cycle of the heatpump
▪ Electrical backup heater
▪ For more information about optimizing the energy consumption for
producing domestic hot water, see "8Configuration"on page34.

5.4.4 DHW pump for instant hot water

Setup
a DHW tank b DHW pump (field supply) c Shower (field supply) d Cold water e Domestic hot water OUT
f Recirculation connection
▪ By connecting a DHW pump, instant hot water can be available at
the tap.
▪ The DHW pump and the installation are field supply and the
responsibility of the installer.
▪ For more information about connecting the recirculation
connection: see "7Installation"on page23.
Configuration
▪ For more information, see "8Configuration"on page34.
▪ You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference guide.

5.4.5 DHW pump for disinfection

Setup
a DHW tank b DHW pump (field supply) c Heater element (field supply) d Non‑return valve (field supply) e Shower (field supply)
f Cold water g Domestic hot water OUT h Recirculation connection
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ The temperature of the DHW tank can be set to maximum 60°C. If
applicable legislation requires higher temperature for disinfection, you can connect a DHW pump and heater element as shown above.
▪ If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater element (if needed) as shown above.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
15
Page 16
5 Application guidelines
b
5
8
0 1
5
0
0
0
de
A
c
a
450896.005
Configuration
The indoor unit can control DHW pump operation. For more information, see "8Configuration"on page34.

5.5 Setting up the energy metering

▪ Via the user interface, you can read out the following energy data:
▪ Produced heat
▪ Consumed energy
▪ You can read out the energy data:
▪ For space heating
▪ For domestic hot water production
▪ You can read out the energy data:
▪ Per month
▪ Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy cannot be guaranteed.

5.5.1 Produced heat

INFORMATION
The sensors used to calculate the produced heat are calibrated automatically.
▪ The produced heat is calculated internally based on:
▪ The leaving and entering water temperature
▪ The flow rate
▪ Setup and configuration: No additional equipment needed.

5.5.2 Consumed energy

Measuring the consumed energy
▪ Requires external power meters.
▪ Setup and configuration:
▪ For the specifications of each type of meter, see "14Technical
data"on page66.
▪ When using electrical power meters, set the number of pulses/
kWh for each power meter via the user interface. Consumed energy data will only be available if this setting is configured.
INFORMATION
When measuring the electrical power consumption, make sure ALL power input of the system is covered by the electrical power meters.

5.5.3 Normal kWh rate power supply

General rule
One power meter that covers the entire system is sufficient.
Setup
Connect the power meter to X5M/7 and X5M/8.
Power meter type
Use a three-phase power meter.
Example
A Indoor unit
a Electrical cabinet (L1/L2/L3/N) b Power meter (L1/L2/L3/N) c Fuse (L1/L2/L3/N) d Backup heater (L1/L2/L3/N) e Indoor unit (L1/L2/L3/N)
Exception
▪ You can use a second power meter if:
▪ The power range of one meter is insufficient.
▪ The electrical meter cannot easily be installed in the electrical
cabinet.
▪ Connection and setup:
▪ Connect the second power meter to X5M/9 and X5M/10.
▪ In the software the power consumption data of both meters is
added so you do NOT have to set which meter covers which power consumption. You only need to set the number of pulses of each power meter.
▪ See "5.5.4 Preferential kWh rate power supply" on page16 for
an example with two power meters.

5.5.4 Preferential kWh rate power supply

Setup
▪ Connect power meter1 to X5M/7 and X5M/8.
▪ Connect power meter2 to X5M/9 and X5M/10.
Refer to "6.4.3 Overview of electrical connections except external
actuators"on page22.

5.6 Setting up the power consumption control

▪ The power consumption control:
▪ Allows you to limit the power consumption of the entire system
(sum of indoor unit and backup heater).
▪ Configuration: Set the power limitation level and how it has to
be achieved via the user interface.
▪ The power limitation level can be expressed as:
▪ Maximum running current (inA)
▪ Maximum power input (inkW)
▪ The power limitation level can be activated:
▪ Permanently
▪ By digital inputs
Installer reference guide
16
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 17
INFORMATION
P
i
t
DI
a
b
a
b
A
B
1
2
3
4
5
A8P
P
i
t
DI4
DI3
DI1
a
b
▪ During emergency operation, the power consumption
control will NOT be used. This is because the backup heater has a higher capacity then during normal operation (9 kW instead of 6 kW) and therefore the power calculated by the unit will be lower then the actual power.
▪ If power limitation is enabled, water temperature set
points above 60°C in space heating are NOT guaranteed.

5.6.1 Permanent power limitation

Permanent power limitation is useful to assure a maximum power or current input of the system. In some countries, legislation limits the maximum power consumption for space heating and DHW production.
PiPower input
t Time
DI Digital input (power limitation level)
a Power limitation active
b Actual power input
Setup and configuration
▪ No additional equipment needed.
▪ Set the power consumption control settings as described in "To
modify an overview setting"on page35 via the user interface (for
the description of all settings, see "8Configuration"on page34):
▪ Select full time limitation mode
▪ Select the type of limitation (power in kW or current in A)
▪ Set the desired power limitation level
NOTICE
Set a minimum power consumption of ±3kW to guarantee space heating and DHW production by allowing at least backup heater step1.

5.6.2 Power limitation activated by digital inputs

Power limitation is also useful in combination with an energy management system.
The power or current of the entire Daikin system is limited dynamically by digital inputs. Power limitation level is set via the user interface by limiting one of the following:
▪ Current (in A)
▪ Power input (in kW)
The energy management system (field supply) decides the activation of a certain power limitation level. Example: To limit the maximum power of the entire house (lighting, domestic appliances, space heating…).
5 Application guidelines
A Indoor unit B Energy management system
a Power limitation activation (4 digital inputs) b Backup heater
PiPower input
t Time
DI Digital inputs (power limitation levels)
a Power limitation active b Actual power input
Setup
▪ Demand PCB (option EKRP1AHTA) needed.
▪ Maximum four digital inputs are used to activate the
corresponding power limitation level:
▪ DI1 = weakest limitation (highest energy consumption)
▪ DI4 = strongest limitation (lowest energy consumption)
▪ For the specification and the connection of the digital inputs, see
"14.5Wiring diagram"on page71.
Configuration
Set the power consumption control settings as described in "To
modify an overview setting" on page 35 via the user interface (for
the description of all settings, see "8Configuration"on page34):
▪ Select activation by digital inputs.
▪ Select the type of limitation (power in kW or current in A).
▪ Set the desired power limitation level corresponding to each digital
input.
INFORMATION
In case more than 1 digital input is closed (at the same time), the digital input priority is fixed: DI4 priority>…>DI1.

5.6.3 Power limitation process

The compressor has better efficiency than the electrical heater. Therefore, the electrical heater is limited and turned OFF first. The system limits power consumption in the following order:
1 Limits electrical heater.
2 Turn OFF the electrical heater.
3 Limits the compressor.
4 Turns OFF the compressor.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
17
Page 18

6 Preparation

P
h
C
e
a
b
c
d
A B
>500
≥50≥50
(mm)
Example
PhProduced heat CeConsumed energy
A Compressor B Backup heater
a Limited compressor operation b Full compressor operation c Backup heater step1 turned ON d Backup heater step2 turned ON

5.7 Setting up an external temperature sensor

Indoor ambient temperature
You can connect one external temperature sensor. It can measure the indoor ambient temperature. Daikin recommends to use an external temperature sensor in the following cases:
▪ In room thermostat control, the user interface is used as room
thermostat and it measures the indoor ambient temperature. Therefore, the user interface must be installed on a location:
▪ Where the average temperature in the room can be detected
▪ That is NOT exposed to direct sunlight
▪ That is NOT near a heat source
▪ That is NOT affected by outside air or air draught because of,
for example, door opening/closing
▪ If this is NOT possible, Daikin recommends to connect a remote
indoor sensor (option KRCS01-1).
▪ Setup: For installation instructions, see the installation manual of
the remote indoor sensor.
▪ Configuration: Select room sensor [A.2.2.B].
Outdoor ambient temperature
The remote outdoor sensor (delivered as accessory) measures the outdoor ambient temperature.
▪ Setup:
▪ To install the remote outdoor sensor outside, see the
installation manual of the sensor (delivered as accessory).
▪ To connect the remote outdoor sensor to the indoor unit, see
"7.6.7To connect the remote outdoor sensor"on page31.
▪ Configuration: None.

6.2 Preparing installation site

Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
Choose the installation location with sufficient place for carrying the unit in and out of the site.

6.2.1 Installation site requirements of the indoor unit

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
▪ Mind the following spacing installation guidelines:
Do NOT install the unit in places such as:
▪ In places where a mineral oil mist, spray or vapour may be
present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.
▪ Sound sensitive areas (e.g. near a bedroom and the like), so that
the operation noise will cause no trouble.
▪ The foundation must be strong enough to bear the weight of the
unit. Take the weight of the unit with a domestic hot water tank full of water into account. Make sure, in the event of a water leak, water cannot cause any damage to the installation space and surroundings.
▪ In places with high humidity (max. RH=85%), for example a
bathroom.
▪ In places where frost is possible. Ambient temperature around the
indoor unit should be >5°C.
▪ The indoor unit is designed for indoor installation only and for
ambient temperatures ranging from 5~30°C.

6.3 Preparing piping

6 Preparation

6.1 Overview: Preparation

This chapter describes what you have to do and know before going on-site.
It contains information about:
▪ Preparing the installation site
▪ Preparing the piping
▪ Preparing the electrical wiring
Installer reference guide
18

6.3.1 Circuit requirements

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
Circuit types. Except for the refrigerant circuit, inside the unit 2 other circuits are included. For future references: the circuit connected to the bore hole is referred to as the brine circuit, the other circuit connected to the heating emitters is referred to as the space heating circuit.
Connecting piping – Legislation. Make all piping connections in
accordance with the applicable legislation and the instructions in the "Installation" chapter, respecting the water inlet and outlet.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 19
Connecting piping – Force. Do NOT use excessive force when
M
FCU1
FCU2
FCU3
FHL1
FHL2
FHL3
70°C
65°C
M
a
e
e
b b d
c
g
h
h
h
h
f
ji
connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
Connecting piping – Tools. Only use appropriate tooling to
handle brass, which is a soft material. If NOT, pipes will get damaged.
Connecting piping – Air, moisture, dust. If air, moisture or dust
gets into the circuit, problems may occur. To prevent this:
▪ Only use clean pipes
▪ Hold the pipe end downwards when removing burrs.
▪ Cover the pipe end when inserting it through a wall, to prevent
dust and/or particles entering the pipe.
▪ Use a decent thread sealant to seal connections.
Closed circuit. Use the indoor unit ONLY in a closed water
system for brine circuit and space heating circuit. Using the system in an open water system will lead to excessive corrosion.
WARNING
When connecting to an open groundwater system, an intermediate heat exchanger is required to prevent damage (dirt, freeze ups) to the unit.
Glycol. For safety reasons, it is NOT allowed to add any kind of
glycol to the space heating circuit.
Piping length. It is recommended to avoid long runs of piping
between the domestic hot water tank and the hot water end point (shower, bath,…) and to avoid dead ends.
Piping diameter. Select the piping diameter in relation to the
required flow and the available external static pressure of the pump. See "14Technical data"on page66 for the external static pressure curves of the indoor unit.
Fluid flow. You can find the minimum required water for the
indoor unit operation in the following table. When the flow is lower, flow error 7H will be displayed and the indoor unit will be stopped.
Model Minimum flow during backup heater
operation
10 ▪ Space heating circuit: 12l/min
▪ Brine circuit: 25l/min
Field supply components – Fluid. Only use materials that are
compatible with fluid used in the system and with the materials used in the indoor unit.
Field supply components – Fluid pressure and temperature.
Check that all components in the field piping can withstand the fluid pressure and fluid temperature.
Fluid pressure – Space heating and brine circuit. The
maximum fluid pressure of the space heating and brine circuit is 4bar. Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.
Fluid pressure – Domestic hot water tank. The maximum fluid
pressure of the domestic hot water tank is 10 bar. Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.
Fluid temperature. All installed piping and piping accessories
(valve, connections,…) MUST withstand the following temperatures:
INFORMATION
The following illustration is an example and might NOT match your system layout.
6 Preparation
a Indoor unit b Heat exchanger c Backup heater d Pump e Stop valve
f Motorised 3-way valve g Motorised 2-way valve (field supply) h Collector
i Domestic hot water tank
j Heat exchanger coil
FCU1...3 Fan coil unit (optional)
FHL1...3 Floor heating loop
Drainage – Low points. Provide drain taps at all low points of the
system in order to allow complete drainage of the circuit.
Drainage – Pressure relief valve. Provide a proper drain for the
pressure relief valve to avoid fluid dripping out of the unit. See
"7.5.5 To connect the pressure relief valve to the drain" on page27.
WARNING
▪ All pipe work connected to the brine pressure relief
valve MUST have a continuous fall.
▪ The discharge pipe from the brine pressure relief valve
MUST terminate in a safe, visible position without forming any risk to persons in the vicinity.
Air vents. Provide air vents at all high points of the system, which
must also be easily accessible for servicing. At the space heating side, an automatic air purge is provided in the indoor unit. Check that the air purge is NOT tightened too much, so that automatic release of air in the water circuit is possible.
Zn-coated parts. NEVER use Zn-coated parts in the fluid circuit.
Because the unit's internal circuit uses copper piping, excessive corrosion may occur. Zn coated parts used in the brine circuit may lead to the precipitation of certain components in the anti-freeze fluids corrosion inhibitor.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
19
Page 20
6 Preparation
c d
a b
FHL1
FHL2
FHL3
M1
T1
M2T2M3
T3
a
d d
e
c
b
b
e
e
f
f
g
WARNING
Due to presence of glycol, corrosion of the system is possible. Uninhibited glycol will turn acidic under the influence of oxygen. This process is accelerated by the presence of copper and high temperatures. The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system. Therefore it is important that:
▪ the water treatment is correctly executed by a qualified
water specialist,
▪ a glycol with corrosion inhibitors is selected to
counteract acids formed by the oxidation of glycols,
▪ no automotive glycol is used because their corrosion
inhibitors have a limited lifetime and contain silicates which can foul or plug the system,
▪ galvanized pipes are NOT used in glycol systems since
the presence may lead to the precipitation of certain components in the glycol's corrosion inhibitor.
INFORMATION
Be aware of the hygroscopic property of anti-freeze fluids: it absorbs moisture from its environment. Leaving the cap off the anti-freeze fluid container causes the concentration of water to increase. The anti-freeze fluid concentration is then lower than assumed. And in consequence, freezing can happen after all.
Preventive actions MUST be taken to ensure minimal exposure of the anti-freeze fluid to air.
Non-brass metallic piping. When using non-brass metallic
piping, insulate the brass and non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.
Valve – Change‑over time. When using a 2-way valve in the
space heating circuit, the maximum change-over time of the valve MUST be 60seconds.
Domestic hot water tank – Capacity. To avoid stagnation of
water, it is important that the storage capacity of the domestic hot water tank meets the daily consumption of domestic hot water.
Domestic hot water tank – After installation. Immediately after
installation, the domestic hot water tank must be flushed with fresh water. This procedure must be repeated at least once a day the first 5 consecutive days after installation.
Domestic hot water tank – Standstills. In cases where during
longer periods of time there is no consumption of hot water, the equipment MUST be flushed with fresh water before usage.
Domestic hot water tank – Disinfection. For the disinfection
function of the domestic hot water tank, see "8.3.2Domestic hot
water control: advanced"on page46.
Thermostatic mixing valves. In accordance with the applicable
legislation, it may be necessary to install thermostatic mixing valves.
Hygienic measures. The installation must be in compliance with
the applicable legislation and may require additional hygienic installation measures.
Recirculation pump. In accordance with the applicable
legislation, it may be required to connect a recirculation pump in between the hot water end point and the recirculation connection of the domestic hot water tank.
a Recirculation connection b Hot water connection c Shower d Recirculation pump

6.3.2 Formula to calculate the expansion vessel pre-pressure

The pre-pressure (Pg) of the vessel depends on the installation height difference (H):
Pg=0.3+(H/10) (bar)

6.3.3 To check the water volume and flow rate of the space heating circuit and brine circuit

The indoor unit has 2 expansion vessels of 10 litre, one for the space heating circuit and one for the brine circuit.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
▪ You must check the total space heating water volume unit.
▪ You must check the total brine water volume in the unit.
Minimum water volume
Check that the total water volume per circuit in the installation is minimum 20litre, the internal water volume of the indoor unit NOT included.
INFORMATION
If a minimum heating load of 1kW can be guaranteed and setting [9‑04] is changed by the installer from 1 to 4°C, the minimum water volume can be lowered to 10litre.
INFORMATION
In critical processes, or in rooms with a high heat load, extra water might be required.
NOTICE
When circulation in each space heating loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.
a Indoor unit b Heat exchanger c Backup heater d Pump e Shut-off valve (field supply)
f Collector (field supply)
g By-pass valve (field supply)
Installer reference guide
20
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 21
6 Preparation
2.5
2
1.5
0
1
0.5
0.3
a
b
0 400200 600 800 1000
20
2.5
2
1.5
0
1
0.5
a
b
0 500 1000 1500 1750
20
a
a
FHL1...3 Floor heating loop (field supply)
T1...3 Individual room thermostat (optional)
M1...3 Individual motorised valve to control loop FHL1...3 (field
supply)
Maximum water volume
Use the following graphs to determine the maximum water volume for the calculated pre-pressure. For brine, this is dependent on the variation of brine temperature in the system. Example: throughout the year, the temperature of the brine can fluctuate between –7°C and 10°C, as in graph1, or between 0°C and 10°C as in graph2.
Graph1: Brine temperature fluctuation is 17°C
NOTICE
When circulation in each or certain space heating loops is controlled by remotely controlled valves, it is important that the minimum flow rate is guaranteed, even if all valves are closed. In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating/operation).
Minimum required flow rate during backup heater operation
12l/min
See the recommended procedure as described in "9.4 Checklist
during commissioning"on page55.

6.3.4 Changing the pre-pressure of the expansion vessel

NOTICE
Only a licensed installer may adjust the pre-pressure of the expansion vessel.
When changing the default pre-pressure of the expansion vessel (1bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the schräder valve of the expansion vessel.
a Pre-pressure (bar)
b Maximum water volume (l)
Space heating vessel 40% propylene glycol (brine expansion vessel) 29% ethanol (brine expansion vessel)
Graph2: Brine temperature fluctuation is 10°C
a Pre-pressure (bar)
b Maximum water volume (l)
Space heating vessel 40% propylene glycol (brine expansion vessel) 29% ethanol (brine expansion vessel)
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup heater operation) in the installation is guaranteed in all conditions.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
a Schräder valve

6.3.5 To check the water volume: Examples

Example 1
The indoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100l.
No actions or adjustments are required.
Example 2
The indoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 300l.
Actions:
▪ Because the total water volume (300 l) is more than the default
water volume (280l), the pre-pressure must be decreased.
▪ The required pre-pressure is:
Pg = (0.3+(H/10))bar = (0.3+(0/10))bar=0.3bar.
▪ The corresponding maximum water volume at 0.3 bar is 350 l.
(See the graph in the chapter above).
▪ Because 300 l is lower than 350 l, the expansion vessel is
appropriate for the installation.
Installer reference guide
21
Page 22
6 Preparation
5
8
0
1
5
0
0
0
a
1+2
5
8
0
1
5
0
0
0
b
1+2 3
2
a
b
13
5
8
0
1
5
0
0
0
5
8
0
1
5
0
0
0

6.4 Preparing electrical wiring

6.4.1 About preparing electrical wiring

INFORMATION
Also read the precautions and requirements in the "General safety precautions" chapter.
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system. They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.
WARNING
▪ All wiring must be performed by an authorized
electrician and must comply with the applicable legislation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on the site and all electrical
construction must comply with the applicable legislation.
WARNING
ALWAYS use multicore cable for power supply cables.

6.4.2 About preferential kWh rate power supply

Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and Austria, ...
This equipment allows for connection to such preferential kWh rate power supply delivery systems.
Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the preferential kWh rate power supply delivery systems available, if any.
When the equipment is connected to such preferential kWh rate power supply, the electricity company is allowed to:
▪ interrupt power supply to the equipment for certain periods of time;
▪ demand that the equipment only consumes a limited amount of
electricity during certain periods of time.
The indoor unit is designed to receive an input signal by which the unit switches into forced off mode. At that moment, the unit compressor will not operate.
Whether the power supply is interrupted or not, the wiring to the unit is different.

6.4.3 Overview of electrical connections except external actuators

General remark about abbreviations in this and the following chapters:
▪ E1 = Refrigerant cycle components (e.g. compressor) and brine
piping parts (e.g. brine pump)
▪ E2 = All other components except backup heater
▪ E3 = Backup heater
Normal power
supply
Preferential kWh rate power supply
Power supply is NOT interrupted
Power supply is
interrupted
During preferential
kWh rate power During preferential kWh rate power supply activation, power supply is NOT interrupted. E1 is turned off by the control.
Remark: The electricity company MUST always allow the power
supply activation,
power supply is
interrupted
immediately or after
some time by the
electricity company.
In this case, the
hydro PCB MUST be
powered by a
separate normal
power supply.
consumption of E2 and E3.
a Normal power supply b Preferential kWh rate power supply 1 Power supply for E1 and E3 2 Power supply for E2 3 Preferential kWh rate power supply (voltage free contact)
NOTICE
The setting brine freezing temperature can be modified and the read out is correct in [A.6.9] Brine freezeup temp ONLY after having accessed menu [A.8] Overview settings.
This setting can ONLY be modified and/or saved and the read out is ONLY correct if the communication between hydro module and compressor module is present. The communication between hydro module and compressor module is NOT guaranteed and/or applicable if:
▪ error "U4" appears on the user interface,
▪ the heat pump module is connected to preferential kWh
rate power supply where power supply is interrupted and preferential kWh rate power supply is activated.

6.4.4 Overview of electrical connections for external and internal actuators

The following illustration shows the required field wiring.
Installer reference guide
22
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 23

7 Installation

M
a
16 14 19
15
20
12
6
13 14 17 18
INFORMATION
The following illustration is an example and might NOT match your system layout.
a Indoor unit
Item Description Wires Maximum
running
current
Indoor unit power supply
1 Power supply for E1
3+N + GND
(a)
and E3
2 Power supply for E2 2
4 Preferential kWh rate
2
(c)
(d)
power supply (voltage free contact)
5 Normal kWh rate power
2 6.3A
supply
User interface
6 User interface 2
(e)
Optional equipment
12 Room thermostat 3 or 4 100mA
13 Outdoor ambient
2
(b)
temperature sensor
14 Indoor ambient
2
(b)
temperature sensor
15 Heat pump convector 4 100mA
Field supplied components
16 Shut-off valve 2 100mA
17 Electricity meter 2 (per meter)
18 Domestic hot water
2
(b)
(b)
pump
19 Alarm output 2
20 Changeover to external
2
(b)
(b)
heat source control
22 Power consumption
digital inputs
2 (per input signal)
(b)
7 Installation

7.1 Overview: Installation

This chapter describes what you have to do and know on-site to install the system.
Typical workflow
Installation typically consists of the following stages:
1 Mounting the indoor unit.
2 Connecting the brine piping.
3 Connecting the water piping.
4 Connecting the electrical wiring.
5 Finishing the indoor installation.

7.2 Opening the units

7.2.1 About opening the units

At certain times, you have to open the unit. Example:
▪ When connecting the electrical wiring
▪ When maintaining or servicing the unit
DANGER: RISK OF ELECTROCUTION
Do NOT leave the unit unattended when the service cover is removed.

7.2.2 To open the indoor unit

1 Loosen and remove the screws at the bottom of the unit.
(b)
(b)
(b)
2 Push on the button at the bottom of the front plate.
WARNING: Sharp edges
Take the front plate on the upper part instead of the lower part. Watch your fingers, there are sharp edges on the lower part of the front plate.
3 Slide the front panel of the unit downwards and remove it.
CAUTION
The front panel is heavy. Be careful NOT to jam your fingers when opening or closing the unit.
4 Loosen and remove the 4 screws that fix the top panel.
5 Remove the top panel from the unit.
(a) Refer to name plate on unit. (b) Minimum cable section 0.75mm². (c) Cable section 2.5mm². (d) Cable section 0.75mm² till 1.25mm²; maximum length:
50m. Voltage-free contact shall ensure the minimum applicable load of 15VDC, 10mA.
(e) Cable section 0.75mm² till 1.25mm²; maximum length:
500m. Applicable for both single user interface and dual use interface connection.
NOTICE
More technical specifications of the different connections are indicated on the inside of the indoor unit.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
23
Page 24
7 Installation
3
2
4
5
1
2
210kg
1
2

7.3.2 Precautions when mounting the indoor unit

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

7.3.3 To install the indoor unit

1 Bring the unit on the pallet as close as possible to its installation
place.
2 Lift the indoor unit from the pallet and place it on the floor.

7.2.3 To open the switch box cover of the indoor unit

3 Slide the indoor unit into position. Make sure that the side
support bolts are present when handling the unit.
4 Unlink the heat pump module from the outer frame. ONLY
remove the side support bolts!

7.3 Mounting the indoor unit

7.3.1 About mounting the indoor unit

When
You have to mount the indoor unit before you can connect the brine and water piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1 Installing the indoor unit.
Installer reference guide
24
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 25
7 Installation
≤1°
a
b
c
NOTICE
Do NOT throw away any bolts. They need to be re-inserted when transport or heavy manipulation is required.
5 Open the front plate of the unit. If needed, the nylon bands for
lifting can be used.
NOTICE
Check if the front support bolts remain levelled and are NOT stressed. The support feet from outer (b) and inner frame (c) MUST be adjusted so that those front bolts remain level. Do NOT adjust support foot (a)!
Bottom view:
Side view:
6 Adjust the height of the 4 leveling feet of the outer frame to
compensate for floor irregularities. The maximum allowed deviation is 1°.
NOTICE
To avoid structural damage on unit, ONLY move the unit when levelling feet are at their lowest position.
NOTICE
For optimum sound reduction, carefully check if there is no gap between the bottom frame and the floor.
7 Adjust the height of the 2 front leveling feet of the inner frame to
compensate for irregularities.
CAUTION
Check that the heat pump module does NOT touch the outer casing.
INFORMATION
To check if the front support bolts are not stressed, loosen them partly and fix them again afterwards.

7.4 Connecting the brine piping

7.4.1 About connecting the brine piping

Before connecting the brine piping
Make sure the indoor unit is mounted.
Typical workflow
Connecting the brine piping typically consists of the following stages:
1 Connecting the brine piping.
2 Filling the brine circuit.
3 Connecting the pressure relief valve to the drain on the brine
side.
4 Insulating the brine piping.

7.4.2 Precautions when connecting the brine piping

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
25
Page 26
7 Installation
a b
a

7.4.3 To connect the brine piping

a Brine out b Brine in
NOTICE
To facilitate service and maintenance, it is recommended to install shut-off valves as close as possible to the inlet and outlet of the unit.

7.4.4 To fill the brine circuit

WARNING
Before, during and after filling carefully check the brine circuit for leakage.
WARNING
Temperature of the fluid running through the evaporator can become negative. It MUST be protected against freezing. Refer to setting [A‑04] in "8.2.2 Quick wizard:
Standard"on page36.
INFORMATION
The materials used in the units brine circuit are chemically resistant to the following anti-freeze fluids:
▪ 40 mass% propylene glycol
▪ 29 mass% ethanol
1 Connect the unit to the field supplied brine filling system.
2 Position the 3‑way valve correctly.
4 Purge as much air as possible from the brine circuit. For
instructions, see "9Commissioning"on page55.
5 Return the 3‑way valve to its original position.

7.4.5 To connect the pressure relief valve to the drain on the brine side

The blow out of the pressure relief valve is coming out of the backside of the unit.
3 Fill the circuit with brine until the manometer indicates a
pressure of ±2.0bar.
a Brine manometer
Installer reference guide
26
WARNING
▪ All pipe work connected to the brine pressure relief
valve MUST have a continuous fall.
▪ The discharge pipe from the brine pressure relief valve
MUST terminate in a safe, visible position without forming any risk to persons in the vicinity.

7.4.6 To insulate the brine piping

The piping in the complete brine circuit MUST be insulated to prevent reduction of the heating capacity.
Consider that the brine circuit piping inside the house can/will condensate. Foresee adequate insulation for these pipes.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 27
7 Installation
a c bd
a
b

7.5 Connecting the water piping

7.5.1 About connecting the water piping

Before connecting the water piping
Make sure the indoor unit is mounted.
Typical workflow
Connecting the water piping typically consists of the following stages:
1 Connecting the water piping of the indoor unit.
2 Connecting the pressure relief valve to the drain.
3 Filling the space heating circuit.
4 Filling the domestic hot water tank.
5 Insulating the water piping.
6 Connecting the recirculation piping.
7 Connecting the drain hose.

7.5.2 Precautions when connecting the water piping

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation

7.5.3 To connect the water piping

NOTICE
Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit.
1 Connect the domestic hot water in and out pipes to the indoor
unit.
NOTICE
▪ A drain device and pressure relief device should be
installed on the cold water inlet connection of the domestic hot water cylinder.
▪ To avoid back siphonage, it is recommended to install a
non-return valve on the water inlet of the domestic hot water tank in accordance with the applicable legislation.
▪ It is recommended to install a pressure reducing valve
on the cold water inlet in accordance with the applicable legislation.
▪ An expansion vessel should be installed on the cold
water inlet in accordance with the applicable legislation.
▪ It is recommended to install the pressure relief valve on
a higher position than the top of the domestic hot water tank. Heating of the domestic hot water tank causes water to expand and without pressure relief valve the water pressure inside the tank can rise above the tank design pressure. Also the field installation (piping, tapping points, etc.) connected to the tank is subjected to this high pressure. To prevent this, a pressure relieve valve needs to be installed. The overpressure prevention depends on the correct operation of the field installed pressure relief valve. If this is NOT working correctly, overpressure will deform the tank and water leakage may occur. To confirm good operation, regular maintenance is required.

7.5.4 To connect the recirculation piping

Prerequisite: Only required if you need recirculation in your system.
1 Loosen and remove the screws at the bottom of the unit.
2 Slide the front panel of the unit downwards and remove it.
3 Loosen and remove the 4 screws that fix the top panel.
4 Remove the top panel from the unit.
b Space heating water in
d Domestic cold water in (cold water supply)
NOTICE
It is recommended to install shut-off valves to cold water in and hot water out connections. Shut-off valves are field supplied.
NOTICE
To avoid damage to the surroundings in case of domestic water leakage, it is recommended to close the cold water inlet stop valves during periods of absence.
2 Connect the space heating in and out pipes to the indoor unit.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
a Space heating water out
c Domestic hot water out
a Knock-out hole b Connection for recirculation piping
5 Remove the knock-out hole at the backside of the unit.
6 Connect the recirculation piping to the recirculation connection
and route the piping through the knock-out hole at the backside of the unit.
7 Re-attach the insulation and casing.

7.5.5 To connect the pressure relief valve to the drain

The blow out of the pressure relief valve is coming out of the backside of the unit.
Installer reference guide
27
Page 28
7 Installation
a
a
a Pressure relief blow-out
The blow out should be connected to an appropriate drain according to the applicable legislation. It is recommended to use a tundish.
WARNING
The discharge pipes from the pressure relief valves MUST terminate in a safe and visible position without forming any risk to persons in the vicinity.

7.5.6 To connect the drain hose

Condensate can form on the brine components inside the compressor department of the unit. The unit contains a drain pan. Depending on room ambient temperature, room humidity and operation condition, the drain pan can overflow. A drain hose is supplied with the unit.
The drain hose is routed to the backside on the left, close to the bottom of the unit. A field supplied drain pump might be needed to pump the water away to the field drain.

7.5.7 To fill the space heating circuit

1 Connect the water supply hose to the fill valve (field supply).
NOTICE
▪ Air in the water circuit can cause malfunctioning of the
backup heater. During filling, it may not be possible to remove all the air from the circuit. Remaining air will be removed through the automatic air purge valves during the initial operating hours of the system. Additional filling with water afterwards may be required.
▪ To purge the system, use the special function as
described in the chapter "9 Commissioning" on
page 55. This function should be used to purge the
heat exchanger coil of the domestic hot water tank.
6 Close the fill valve.
7 Disconnect the water supply hose from the fill valve.
NOTICE
The water pressure indicated on the manometer will vary depending on the water temperature (higher pressure at higher water temperature).
However, at all times water pressure shall remain above 1bar to avoid air entering the circuit.

7.5.8 To fill the domestic hot water tank

1 Open every hot water tap in turn to purge air from the system
pipe work.
2 Open the cold water supply valve.
3 Close all water taps after all air is purged.
4 Check for water leaks.
5 Manually operate the field-installed pressure relief valve to
ensure a free water flow through the discharge pipe.

7.5.9 To insulate the water piping

The piping in the complete water circuit MUST be insulated to prevent reduction of the heating capacity.
2 Open the fill valve.
3 Make sure that the automatic air purge valve is open (at least 2
turns).
INFORMATION
For location of the air purge valve, see "Dimensions and service space: Indoor unit" in chapter "14 Technical
data"on page66.
4 Fill the circuit with water until the manometer indicates a
pressure of ±2.0bar.
a Water manometer
5 Purge as much air as possible from the water circuit.

7.6 Connecting the electrical wiring

7.6.1 About connecting the electrical wiring

Before connecting the electrical wiring
Make sure the brine and water piping are connected.
Typical workflow
Connecting the electrical wiring typically consists of the following stages:
1 Making sure the power supply system complies with the
electrical specifications of the heat pump.
2 Connecting the electrical wiring to the indoor unit.
3 Connecting the main power supply.
4 Connecting the remote outdoor sensor.
5 Connecting the user interface.
6 Connecting the shut–off valves.
7 Connecting the electrical meters.
8 Connecting the domestic hot water pump.
9 Connecting the alarm output.
10 Connecting the space heating ON/OFF output.
11 Connecting the changeover to an external heat source.
12 Connecting the power consumption digital inputs.
Installer reference guide
28
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 29
7 Installation
b a
cb
c
aa
A
AA´
c b ba c
a
B
B
a c b
a c b

7.6.2 About electrical compliance

Equipment complying with EN/IEC 61000‑3‑12 (European/ International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and ≤75A per phase.).

7.6.3 Precautions when connecting the electrical wiring

INFORMATION
Also read the precautions and requirements in the following chapters:
▪ General safety precautions
▪ Preparation
DANGER: RISK OF ELECTROCUTION
INFORMATION
More information about the legend and the location of the wiring diagram of the unit can be found in the "Technical data" chapter.
WARNING
ALWAYS use multicore cable for power supply cables.

7.6.4 Guidelines when connecting the electrical wiring

Keep the following in mind:
▪ If stranded conductor wires are being used, install a round crimp-
style terminal on the tip. Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool.
Tightening torques
Item Tightening torque (N•m)
X1M 2.2~2.7
X2M 0.8~0.9
X5M

7.6.5 To connect the electrical wiring on the indoor unit

INFORMATION
Foresee additional cable length of 35cm for all wires which should be connected to X2M and X5M on sheet metal support above the hydro PCB. Additional wire length should be tie wrapped at the back side of the unit. Reason is to guarantee serviceability of, for example, the hydro PCB.
1 To open the indoor unit, see "7.2.2To open the indoor unit"on
page23 and "7.2.3To open the switch box cover of the indoor unit"on page24.
2 Wiring should enter the unit from the top:
3 Routing of the wiring inside the unit should be as follows:
a Stranded conductor wire
b Round crimp-style terminal
▪ Use the following methods for installing wires:
Wire type Installation method
Single core wire
a Curled single core wire
b Screw
c Flat washer
Stranded conductor wire with round crimp-style terminal
a Terminal
b Screw
c Flat washer
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
29
Page 30
7 Installation
a c
≥50 mm
≥50 mm
c
a
≥50 mm
X5M
X2M
X1 X2 X3 X4
YC Y1 Y2 Y3 Y4
11 12
a c
NOTICE
▪ Make sure that 50mm is guaranteed between the low
voltage (a) and high voltage (c) cables.
▪ Make sure that the cables (a) and (c) are routed
between the wire guide and the backside of the switch box to prevent water ingress.
4 Fix the cable with cable ties to the cable tie mountings to
ensure strain relief and to make sure that it does NOT come in contact with the piping and sharp edges.
Routing Possible cables (depending on unit type and installed options)
a
Low voltage
b
High voltage power supply
c
High voltage control signal

7.6.6 To connect the main power supply

1 Connect the main power supply.
In case of normal kWh rate power supply
Installer reference guide
30
▪ Preferential power supply contact
▪ User interface
▪ Power consumption digital inputs (field supply)
▪ Outdoor ambient temperature sensor
▪ Indoor ambient temperature sensor (option)
▪ Electrical meters (field supply)
▪ Normal kWh rate power supply (power supply for unit)
▪ Preferential kWh rate power supply
▪ Heat pump convector (option)
▪ Room thermostat (option)
▪ Shut-off valve (field supply)
▪ Domestic hot water pump (field supply)
▪ Alarm output
▪ Changeover to external heat source control
CAUTION
Do NOT push or place redundant cable length in the unit.
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 31
X1M
N L3
L2 L1
X2M
30
X6YB
X6Y X6YA
31
X5M
a
X19AX1A
Legend: see illustration below.
X1M
N L3 L2 L1
X2M
29 34
X6YB
X6YA
X6Y
X5M
a
X19AX1A
S1S
L
N
b
c
3 4
30 31
X2M
X5M
11
10
12
X2M
X5M
a b
1
2
In case of preferential kWh rate power supply
Connect X6Y to X6YB.
7 Installation
INFORMATION
If the desired leaving water temperature is weather dependent, the full time outdoor temperature measurement is important.
1 Connect the external temperature sensor cable to the indoor
unit.
2 Fix the cable with cable ties to the cable tie mountings.
3 Install the remote outdoor sensor outside as described in the
installation manual of the sensor (delivered as accessory).
a Main power supply
b Normal kWh rate power supply
c Preferential power supply contact
2 Fix the cable with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect X6Y to X6YB. The necessity of separate normal kWh rate power supply to indoor unit (b) X2M30/31 depends on the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪ if preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.

7.6.8 To connect the user interface

▪ If you use 1 user interface, you can install it at the indoor unit (for
control close to the indoor unit), or in the room (when used as room thermostat).
▪ If you use 2 user interfaces, you can install 1 user interface at the
indoor unit (for control close to the indoor unit) + 1 user interface in the room (used as room thermostat).
The procedure differs slightly depending on where you install the user interface.
# At the indoor unit In the room
1 Connect the user interface cable to the indoor unit.
Fix the cable with cable ties to the cable tie mountings.
a Main user interface
b Optional user interface
(a)

7.6.7 To connect the remote outdoor sensor

The remote outdoor sensor (delivered as accessory) measures the outdoor ambient temperature.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
31
Page 32
7 Installation
b
a
PCB
a
PCB
b
a
b
PCB
b
a
PCB
b
b
NO
NC
X2M
X5M
5
67
5
6
7
X2M
X5M
M2SM2S
X2M
X5M
6
89107
S2S S3S
# At the indoor unit In the room
2 Insert a screwdriver into the slots underneath the user
interface and carefully separate the faceplate from the wallplate.
The PCB is mounted in the faceplate of the user interface. Be careful NOT to damage it.
3 Fix the wallplate of the user interface
to the sheet metal of the unit.
Be careful NOT to distort the shape
Fix the wallplate of the user interface to the wall.
of the backside of the user interface by overtightening the mounting screws.
4 Connect as shown in 4A. Connect as shown
in 4A, 4B, 4C or 4D.
5 Reinstall the faceplate onto the wallplate.
Be careful NOT to pinch the wiring when attaching the frontplate to the unit.
(a) The main user interface is required for operation, but has to
be ordered separately (mandatory option).
4A From the rear
4B From the left
NOTICE
Wiring is different for a NC (normal closed) valve and a NO (normal open) valve.
2 Fix the cable with cable ties to the cable tie mountings.

7.6.10 To connect the electrical meters

INFORMATION
In case of an electrical meter with transistor output, check the polarity. The positive polarity MUST be connected to X5M/7 and X5M/9; the negative polarity to X5M/8 and X5M/10.
1 Connect the electrical meters cable to the appropriate terminals
as shown in the illustration below.
4C From the top
4D From the top centre
2 Fix the cable with cable ties to the cable tie mountings.

7.6.11 To connect the domestic hot water pump

1 Connect the domestic hot water pump cable to the appropriate
terminals as shown in the illustration below.
a Notch this part for the wiring to pass through with nippers
etc.
b Secure the wiring to the front part of the casing using the
wiring retainer and clamp.

7.6.9 To connect the shut-off valve

1 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
Installer reference guide
32
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 33
X2M
X5M
3534
1~
M
M2P
2 Fix the cable with cable ties to the cable tie mountings.
X2M
X5M
A4P
29
a
X2M
X5M
A4P
29
a
X2M
X5M
A4P
LN
a
X2M
X5M
A8P
S6S
S7S
S8S
S9S
1 2 3 4 5
a

7.6.12 To connect the alarm output

1 Connect the alarm output cable to the appropriate terminals as
shown in the illustration below.
7 Installation

7.6.14 To connect the changeover to external heat source

1 Connect the changeover to external heat source cable to the
appropriate terminals as shown in the illustration below.
a Installation of EKRP1HB is required.
2 Fix the cable with cable ties to the cable tie mountings.
a Installation of EKRP1HB is required.
2 Fix the cable with cable ties to the cable tie mountings.

7.6.13 To connect the space heating ON/OFF output

1 Connect the space heating ON/OFF output cable to the
appropriate terminals as shown in the illustration below.

7.6.15 To connect the power consumption digital inputs

1 Connect the power consumption digital inputs cable to the
appropriate terminals as shown in the illustration below.
a Installation of EKRP1AHTA is required.
2 Fix the cable with cable ties to the cable tie mountings.

7.7 Finishing the indoor unit installation

2 Fix the cable with cable ties to the cable tie mountings.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
a Installation of EKRP1HB is required.

7.7.1 To fix the user interface cover to the indoor unit

1 Make sure that the front panel is removed from the indoor unit.
See "7.2.2To open the indoor unit"on page23.
2 Plug the user interface cover into the hinges.
Installer reference guide
33
Page 34

8 Configuration

X2M
X10A
X5M
A1P
2
345
H JS T
3 Mount the front panel to the indoor unit.

7.7.2 To close the indoor unit

1 Close the switch box cover.
2 Reinstall the top plate.
3 Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the tightening torque does NOT exceed 4.1N•m.
Accessing settings – Legend for tables
You can access the installer settings using two different methods. However, NOT all settings are accessible via both methods. If so, the corresponding table columns in this chapter are set to N/A (not applicable).
Method Column in tables
Accessing settings via the breadcrumb in the menu structure.
Accessing settings via the code in the overview settings.
See also:
"To access the installer settings"on page34
"8.5Menu structure: Overview installer settings"on page54
#
Code

8.1.1 To connect the PC cable to the switch box

Prerequisite: The EKPCCAB kit is required.
1 Connect the cable with USB connection to your PC.
2 Connect the plug of the cable to X10A on A1P of the switch box
of the indoor unit.
8 Configuration

8.1 Overview: Configuration

This chapter describes what you have to do and know to configure the system after it is installed.
Why
If you do NOT configure the system correctly, it might NOT work as expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system using two different methods.
Method Description
Configuring via the user interface
Configuring via the PC configurator
INFORMATION
When the installer settings are changed, the user interface will request to confirm. When confirmed, the screen will shortly turn OFF and "busy" will be displayed for several seconds.
First time – Quick wizard. When you turn ON the user interface for the first time (via the indoor unit), a quick wizard starts to help you configure the system.
Afterwards. If necessary, you can make changes to the configuration afterwards.
You can prepare the configuration off-site on PC and afterwards upload the configuration to the system with the PC configurator.
See also: "8.1.1To connect the PC cable to
the switch box"on page34.
3 Pay special attention to the position of the plug!

8.1.2 To access the most used commands

To access the installer settings
1 Set the user permission level to Installer.
2 Go to [A]:
To access the overview settings
1 Set the user permission level to Installer.
2 Go to [A.8]:
To set the user permission level to Installer
1 Set the user permission level to Adv. end user.
2 Go to [6.4]:
> Installer settings.
> Installer settings > Overview settings.
> Information > User permission level.
Installer reference guide
34
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 35
3 Press for more than 4seconds.
01
02 06 0a 0e
00 03
07 0b 0f
0000
04 08 0c
00 01
05 09 0d
15
Overview settings
Confirm Adjust Scroll
01
02 06 0a 0e
00 03
07 0b 0f
0000
04 08 0c
00 01
05 09 0d
15
Overview settings
Confirm
Adjust
Scroll
01
02 06 0a 0e
00 03
07 0b 0f
0000
04 08 0c
00 01
05 09 0d
20
Overview settings
Confirm
Adjust
Scroll
Installer settings
The system will restart.
Confirm Adjust
Cancel
OK
15:10
Tue
U5:Auto address
Push 4 sec. to continue
Synchronization
Data difference detected. Please select action:
Send data
Confirm
Adjust
Start copy
Are you sure you want to start the copy operation?
Cancel
OK
Confirm Adjust
Result: is displayed on the home pages.
4 If you do NOT press any button for more than 1hour or press
again for more than 4seconds, the installer permission level
switches back to End user.
To set the user permission level to Advanced end user
1 Go to the main menu or any of its submenus: .
2 Press for more than 4seconds.
Result: The user permission level switches to Adv. end user.
Additional information is displayed and "+" is added to the menu title. The user permission level will stay in Adv. end user until set otherwise.
To set the user permission level to End user
1 Press for more than 4 seconds.
Result: The user permission level switches to End user. The user
interface will return to the default home screen.
To modify an overview setting
Example: Modify [1‑01] from 15 to 20.
1 Go to [A.8]: > Installer settings > Overview settings.
2 Go to the corresponding screen of the first part of the setting by
using the and button.
8 Configuration
Result: The system will restart.

8.1.3 To copy the system settings from the first to the second user interface

If a second user interface is connected, the installer must first proceed below instructions for the proper configuration of the 2 user interfaces.
This procedure offers you also the possibility to copy the language set from one user interface to the other one: e.g. from EKRUCBL2 to EKRUCBL1.
1 When power is turned on for the first time, both user interfaces
display:
INFORMATION
An additional 0-digit is added to the first part of the setting when you access the codes in the overview settings.
Example: [1‑01]: "1" will result in "01".
3 Go to the corresponding second part of the setting by using the
and button.
Result: The value to be modified is now highlighted.
4 Modify the value by using the and button.
2 Push for 4seconds on the user interface on which you want
to proceed to the quick wizard. This user interface is now the main user interface.
INFORMATION
During the quick wizard, the second user interface displays Busy and will NOT be possible to operate.
3 The quick wizard will guide you.
4 For proper operation of the system, the local data on the two
user interfaces must be the same. If this is NOT the case, both user interfaces will display:
5 Select the required action:
▪ Send data: the user interface you are operating contains the
correct data and the data on the other user interface will be overwritten.
▪ Receive data: the user interface you are operating does
NOT contain the correct data and the data on the other user interface will be used to overwrite.
6 The user interface requests confirmation if you are sure to
proceed.
5 Repeat previous steps if you have to modify other settings.
6 Push to confirm the modification of the parameter.
7 At installer settings menu, press to confirm the settings.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
35
Page 36
8 Configuration
Language
Select the desired language
Confirm Adjust
1 2013
Jan
Tue
Confirm Adjust Scroll
Date
What is the date today?
00 : 00
What is the current time?
Time
Confirm
Adjust
Scroll
A.2 1
Scroll
Select
System layout
Standard
Options Capacities Confirm layout
Confirm layout Please confirm the system
layout. The system will restart and will be ready for first startup.
OK
Cancel
Confirm
Adjust
7 Confirm the selection on the screen by pushing and all data
(languages, schedules etc.) will be synchronised from the selected source user interface to the other one.
INFORMATION
▪ During the copying, both controllers will NOT allow
operation.
▪ The copy operation can take up until 90 minutes.
▪ It is recommended to change installer settings, or the
configuration of the unit, on the main user interface. If not, it can take up to 5 minutes before these changes are visible in the menu structure.
8 Your system is now set to be operated by the 2 user interfaces.

8.1.4 To copy the language set from the first to the second user interface

See "8.1.3To copy the system settings from the first to the second
user interface"on page35.

8.1.5 Quick wizard: Set the system layout after first power ON

After first power ON of the system, you are guided on the user interface to do initial settings:
▪ language,
▪ date,
▪ time,
▪ system layout.
By confirming the system layout, you can proceed with the installation and commissioning of the system.
1 At power ON, the quick wizard starts as long as the system
layout was NOT confirmed yet, by setting the language.
4 After configuration, select Confirm layout and press .
5 The user interface re-initialises and you can proceed the
installation by setting the other applicable settings and commissioning of the system.
When the installer settings are changed, the system will request to confirm. When confirmation is complete, the screen will shortly turn OFF and "busy" will be displayed for several seconds.

8.2 Basic configuration

8.2.1 Quick wizard: Language / time and date

# Code Description
[A.1] N/A Language
[1] N/A Time and date

8.2.2 Quick wizard: Standard

Space heating settings
The system can heat up a space. Depending on the type of application, the space heating must be made accordingly.
2 Set the current date and time.
3 Set the system layout settings: Standard, Options, Capacities.
For more details, see "8.2Basic configuration"on page36.
# Code Description
[A.2.1.7] [C-07] Unit control method:
▪ 0 (LWT control)(default): Unit
operation is decided based on the leaving water temperature regardless the actual room temperature and/or heating demand of the room.
▪ 1 (Ext RT control): Unit operation is
decided by the external thermostat or equivalent (e.g. heat pump convector).
▪ 2 (RT control): Unit operation is
decided based on the ambient temperature of the user interface.
Installer reference guide
36
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 37
8 Configuration
b
a
a
a
b
a
b c
d
b c
# Code Description
[A.2.1.B] N/A Only if there are 2user interfaces (1
installed in the room, 1 installed at the indoor unit):
▪ a: At unit
▪ b: In room as room thermostat
User interface location:
▪ 0 (At unit): the other user interface is
automatically set to In room and if RT control is selected act as room thermostat.
▪ 1 (In room)(default): the other user
interface is automatically set to At unit and if RT control is selected to act as room thermostat.
# Code Description
[A.2.1.8] [7-02] << continuation
▪ 1 (2 LWT zones): 2 leaving water
temperature zones. The zone with the lowest leaving water temperature (in heating) is called the main leaving water temperature zone. The zone with the highest leaving water temperature (in heating) is called the additional leaving water temperature zone. In practice, the main leaving water temperature zone consists of the higher load heat emitters and a mixing station is installed to achieve the desired leaving water temperature.
▪ a: Add LWT zone
▪ b: Main LWT zone
# Code Description
[A.2.1.8] [7-02] The system can supply leaving water to
up to 2 water temperature zones. During configuration, the number of water zones must be set.
Number of LWT zones:
▪ 0 (1 LWT zone)(default): Only 1
leaving water temperature zone. This zone is called the main leaving water temperature zone.
# Code Description
[A.2.1.9] [F-0D] When the space heating control is OFF
by the user interface, the pump is always OFF. When the space heating control is On, you can select the desired pump operation mode (only applicable during space heating)
Pump operation mode:
▪ 0 (Continuous): Continuous pump
operation, regardless of thermo ON or OFF condition. Remark: continuous pump operation requires more energy than sample or request pump operation.
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: Pump operation
continued >>
▪ a: Main LWT zone
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
continued >>
Installer reference guide
37
Page 38
8 Configuration
a b
d
e
f
c
g b
c
a
d
e
b
b
c
b c
c
# Code Description
[A.2.1.9] [F-0D] << continuation
▪ 1 (Sample)(default): The pump is ON
when there is heating demand and the leaving water temperature has NOT reached the desired temperature yet. When thermo OFF condition occurs, the pump runs every 5 minutes to check the water temperature and demand heating if necessary. Remark: Sample is NOT available in external room thermostat control or room thermostat control.
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: LWT temperature
▪ e: Actual
▪ f: Desired
▪ g: Pump operation
# Code Description
[A.2.1.9] [F-0D] << continuation
▪ 2 (Request): Pump operation based
on request. Example: Using a room thermostat creates thermo ON/OFF condition. When there is no such demand, the pump is OFF. Remark: Request is NOT available in leaving water temperature control.
continued >>
General rule: the units freeze up prevention limit temperature MUST be 10°C lower than the minimum possible brine inlet temperature for the unit.
Example: When the minimum possible brine inlet temperature in a certain application is 0°C, then the unit freeze up prevention limit temperature MUST be set to –10°C or lower. Result will be that the brine mixture may NOT freeze above that temperature. To prevent freezing of the unit, check the type and concentration of the brine carefully.
# Code Description
[A.6.9] [A‑04] Brine freezeup temp
▪ 0: 0°C
▪ 1: –2°C
▪ 2: –4°C
▪ 3: –6°C
▪ 4: –8°C
▪ 5: –10°C
▪ 6: –12°C
▪ 7 (default): –14°C
NOTICE
The setting brine freezing temperature can be modified and the read out is correct in [A.6.9] Brine freezeup temp ONLY after having accessed menu [A.8] Overview settings.
This setting can ONLY be modified and/or saved and the read out is ONLY correct if the communication between hydro module and compressor module is present. The communication between hydro module and compressor module is NOT guaranteed and/or applicable if:
▪ error "U4" appears on the user interface,
▪ the heat pump module is connected to preferential kWh
rate power supply where power supply is interrupted and preferential kWh rate power supply is activated.
Capacity boost
For systems where higher capacity is required, the compressor frequency can be increased. Remark that higher capacity results in higher sound level.
▪ a: Space heating control (user
interface)
▪ b: OFF
▪ c: On
▪ d: Heating demand (by ext RT or
RT)
▪ e: Pump operation
Brine freezing temperature
Depending on the type and concentration of the anti-freeze in the brine system, the freezing temperature will differ. The following parameters set the units freeze up prevention limit temperature. To allow for temperature measurement tolerances, the brine concentration MUST resist to a lower temperature than the defined setting.
Installer reference guide
38
# Code Description
N/A [A‑03] Compressor frequency
▪ 0 (default): normal
▪ 1: boost

8.2.3 Quick wizard: Options

Domestic hot water settings
Following settings must be made accordingly.
# Code Description
N/A [E-05] DHW operation:
▪ 0 (No): N/A
▪ 1 (Yes): Installed. Do NOT change this
setting.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 39
8 Configuration
c f
b
a
g
c
b
a
d f
e g
# Code Description
[A.2.2.A] [D-02] The indoor unit offers the possibility to
connect a field supplied domestic hot water pump (On/OFF type). Depending on the installation and configuration on the user interface, we distinguish its functionality.
DHW pump:
▪ 0 (No)(default): NOT installed.
▪ 1 (Secondary rtrn): Installed for instant
hot water when water is tapped. The end-user sets the operation timing (weekly schedule time) of the domestic hot water pump when it should run. Control of this pump is possible through the indoor unit.
▪ 2 (Disinf. shunt): Installed for
disinfection. It runs when the disinfection function of the domestic hot water tank is running. No further settings are needed.
See also illustrations below.
Domestic hot water pump installed for…
Instant hot water Disinfection
a Indoor unit
b Tank
c Domestic hot water pump (field supply)
d Heater element (field supply)
e Non‑return valve (field supply)
f Shower (field supply)
g Cold water
Thermostats and external sensors
NOTICE
If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on the unit's user interface is turned ON.
See "5Application guidelines"on page8.
# Code Description
[A.2.2.4] [C-05] Contact type main
In external room thermostat control, the contact type of the optional room thermostat or heat pump convector for the main leaving water temperature zone must be set. See "5Application
guidelines"on page8.
▪ 1 (Thermo ON/OFF): The connected
external room thermostat or heat pump convector sends the heating demand by the same signal as it is connected to only 1 digital input (preserved for the main leaving water temperature zone) on the indoor unit (X2M/1). Select this value in case of a connection to the heat pump convector (FWXV).
# Code Description
[A.2.2.5] [C-06] Contact type add.
In external room thermostat control with 2 leaving water temperature zones, the type of the optional room thermostat for the additional leaving water temperature zone must be set. See "5Application
guidelines"on page8.
▪ 1 (Thermo ON/OFF): See Contact
type main. Connected on the indoor unit (X2M/1a).
[A.2.2.B] [C-08] External sensor
When an optional external ambient sensor is connected, the type of the sensor must be set. See "5Application
guidelines"on page8.
▪ 0 (No)(default): NOT installed. The
thermistor in the user interface and in the heat pump module are used for measurement.
▪ 2 (Room sensor): Installed. The
temperature sensor in the user interface is NOT used anymore. Remark: This value has only meaning in room thermostat control.
Digital I/O PCB
Modification of these settings is only needed when the optional digital I/O PCB is installed. The digital I/O PCB has multiple functionality which need to be configured. See "5 Application
guidelines"on page8.
# Code Description
[A.2.2.6.1] [C-02] Ext. backup heat src
Indicates if the space heating is also performed by means of another heat source than the system.
▪ 0 (No)(default): NOT installed.
▪ 1 (Bivalent): Installed. The auxiliary
boiler (gasboiler, oil burner) will operate when the outdoor ambient temperature is low. During the bivalent operation, the heat pump is turned OFF. Set this value in case an auxililary boiler is used. See
"5Application guidelines"on page8.
[A.2.2.6.3] [C-09] Alarm output
Indicates the logic of the alarm output on the digital I/O PCB during malfunctioning.
▪ 0 (Normally open)(default): The alarm
output will be powered when an alarm occurs. By setting this value, a distinction is made between malfunctioning and detection of a power failure of the unit.
▪ 1 (Normally closed): The alarm output
will NOT be powered when an alarm occurs.
Alarm output logic
[C-09] Alarm No alarm No power
supply to unit
0 (default) Closed output Open output Open output
1 Open output Closed output
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
39
Page 40
8 Configuration
Demand PCB
The demand PCB is used to enable the power consumption control by digital inputs. See "5Application guidelines"on page8.
# Code Description
[A.2.2.7] [D-04] Demand PCB
Indicates if the optional demand PCB is installed.
▪ 0 (No)(default)
▪ 1 (Pwr consmp ctrl)
Energy metering
When energy metering is performed by the use of external power meters, configure the settings as described below. Select the pulse frequency output of each power meter in accordance with the power meter specifications. It is possible to connect (up to 2) power meters with different pulse frequencies. When only 1 or no power meter is used, select No to indicate the corresponding pulse input is NOT used.
# Code Description
[A.2.2.8] [D‑08] Optional external kWh meter1:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1pulse/kWh)
▪ 2: Installed (1pulse/kWh)
▪ 3: Installed (10pulse/kWh)
▪ 4: Installed (100pulse/kWh)
▪ 5: Installed (1000pulse/kWh)
[A.2.2.9] [D‑09] Optional external kWh meter2:
▪ 0 (No): NOT installed
▪ 1: Installed (0.1pulse/kWh)
▪ 2: Installed (1pulse/kWh)
▪ 3: Installed (10pulse/kWh)
▪ 4: Installed (100pulse/kWh)
▪ 5: Installed (1000pulse/kWh)

8.2.4 Quick wizard: Capacities (energy metering)

The capacities of all electrical heaters must be set for the energy metering and/or power consumption control feature to work properly. When measuring the resistance value of each heater, you can set the exact heater capacity and this will lead to more accurate energy data.
# Code Description
[A.2.3.2] [6-03] BUH: step 1: The capacity of the first
step of the backup heater at nominal voltage. Nominal value 3kW. Default: 3kW.
Range: 0~10kW (in steps of 0.2kW)
[A.2.3.3] [6-04] BUH: step 2: The capacity difference
between the second and first step of the backup heater. Default: 3kW.
Range: 0~10kW (in steps of 0.2kW)
outdoor temperature. Low outdoor temperatures will result in warmer water and vice versa. During weather-dependent operation, the user has the possibility to shift up or down the target water temperature by a maximum of 5°C.
See the user reference guide and/or operation manual for more details about this function.
Leaving water temperature: Main zone
# Code Description
[A.3.1.1.1] N/A LWT setpoint mode:
▪ Fixed: The desired leaving water
temperature is:
▪ NOT weather-dependent (i.e. does
NOT depend on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
▪ Weather dep. (default): The desired
leaving water temperature is:
▪ weather-dependent (i.e. depends
on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
continued >>
# Code Description
[A.3.1.1.1] N/A << continuation
▪ Fixed/scheduled: The desired leaving
water temperature is:
▪ NOT weather-dependent (i.e.,
does NOT depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions consists of desired shift actions, either preset or custom.
Remark: This value can only be set in leaving water temperature control.
▪ WD/scheduled: The desired leaving
water temperature is:
▪ weather-dependent (i.e., does
depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions consists of desired leaving water temperatures either preset or custom
Remark: This value can only be set in leaving water temperature control.

8.2.5 Space heating control

The basic required settings in order to configure the space heating of your system are described in this chapter. The weather-dependent installer settings define the parameters for the weather-dependent operation of the unit. When weather-dependent operation is active, the water temperature is determined automatically depending on the
Installer reference guide
40
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 41
8 Configuration
[1-03]
[1-02]
T
a
T
t
[1-00] [1-01]
[0-00]
[0-01]
T
a
T
t
[0-03] [0-02]
# Code Description
[7.7.1.1] [1-00]
Set weather-dependent heating:
[1-01]
[1-02]
[1-03]
▪ Tt: Target leaving water temperature
(main)
▪ Ta: Outdoor temperature
# Code Description
[7.7.1.1] [1-00]
[1-01]
[1-02]
[1-03]
<< continuation
▪ [1-00]: Low outdoor ambient
temperature. –40°C~+5°C (default: – 20°C)
▪ [1-01]: High outdoor ambient
temperature. 10°C~25°C (default: 15°C)
▪ [1-02]: Desired leaving water
temperature when the outdoor temperature equals or drops below the low ambient temperature. Range: [9‑01]°C~[9‑00]°C (default: 60°C). Note: This value should be higher than [1-03] as for low outdoor temperatures warmer water is required.
▪ [1-03]: Desired leaving water
temperature when the outdoor temperature equals or rises above the high ambient temperature. Range: [9‑01]°C~min(45, [9‑00])°C (default: 25°C). Note: This value should be lower than [1-02] as for high outdoor temperatures less warm water is required.
continued >>
# Code Description
[A.3.1.2.1] N/A << continuation
▪ Fixed/scheduled: The desired leaving
water temperature is:
▪ NOT weather-dependent (i.e.,
does NOT depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions are On or OFF.
Remark: This value can only be set in leaving water temperature control.
▪ WD/scheduled: The desired leaving
water temperature is:
▪ weather-dependent (i.e., does
depend on the outdoor ambient temperature)
▪ according a schedule. The
scheduled actions are On or OFF.
Remark: This value can only be set in leaving water temperature control.
# Code Description
[7.7.2.1] [0-00]
Set weather-dependent heating:
[0-01]
[0-02]
[0-03]
▪ Tt: Target leaving water temperature
(additional)
▪ Ta: Outdoor temperature
continued >>
Leaving water temperature: Additional zone
Only applicable if 2 leaving water temperature zones are present.
# Code Description
[A.3.1.2.1] N/A LWT setpoint mode:
▪ Fixed: The desired leaving water
temperature is:
▪ NOT weather-dependent (i.e. does
NOT depend on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
▪ Weather dep. (default): The desired
leaving water temperature is:
▪ weather-dependent (i.e. depends
on the outdoor ambient temperature)
▪ fixed in time (i.e., NOT scheduled)
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
continued >>
Installer reference guide
41
Page 42
8 Configuration
4
14
°C
T
t
55 65
Δt
≤65
≤60
bT
t
f
2
1
3
a c
d
e
# Code Description
[7.7.2.1] [0-00]
[0-01]
[0-02]
[0-03]
<< continuation
▪ [0-03]: Low outdoor ambient
temperature. –40°C~+5°C (default: – 20°C)
▪ [0-02]: High outdoor ambient
temperature. 10°C~25°C (default: 15°C)
▪ [0-01]: Desired leaving water
temperature when the outdoor temperature equals or drops below the low ambient temperature. Range: [9‑05]°C~[9‑06]°C (default: 60°C). Note: This value should be higher than [0-00] as for low outdoor temperatures warmer water is required.
▪ [0-00]: Desired leaving water
temperature when the outdoor temperature equals or rises above the high ambient temperature. Range: [9‑05]°C~min(45, [9‑06])°C (default: 25°C). Note: This value should be lower than [0-01] as for high outdoor temperatures less warm water is required.
Leaving water temperature: Delta T source
Temperature difference for entering and leaving water. The unit is designed to support under floor loops operation. The recommended leaving water temperature (set by the user interface) for under floor loops is 35°C. In such case, the unit will be controlled to realize a temperature difference of 5°C which means that the entering water to the unit is around 30°C. Depending on the installed application (radiators, heat pump convector, under floor loops) or situation, it can be possible to change the difference between entering and leaving water temperature. Note that the pump will regulate its flow to keep the Δt.
# Code Description
[A.3.1.3.1] [9-09] Heating: required temperature
difference between entering and leaving water. Range: 3°C~10°C (in steps of 1°C; default value: 8°C).
Specific for installations that require higher water temperatures (e.g., radiators)
For leaving water temperature setpoint>55°C
As soon as the leaving water temperature set point is >55°C, Δt is no longer a constant determined by field setting [9‑09] (default 8°C), but linear in function of the setpoint.
Δt Temperature difference
TtTarget leaving water temperature (main)
For leaving water temperature setpoint>60°C
Installer reference guide
42
Up to leaving water temperature set point 60°C, the heat pump can cover this temperature. If you need a leaving water temperature set points >60°C, the backup heater will assist to reach the requested temperature. Assistance by backup heater is ONLY possible when the ambient temperature is lower than the equilibrium temperature.
a Water from heat emitters b Condenser c Leaving water from condenser d Backup heater e Leaving water
f Water flow 1 By heat pump 2 By backup heater 3 Temperature difference
TtTarget leaving water temperature (main)
To minimize the power consumption, the heat pump ALWAYS tries to reach max possible target leaving water temperature of 60°C. The remaining part is done by the backup heater.
Leaving water temperature: Modulation
Only applicable in case of room thermostat control. When using the room thermostat functionality, the customer needs to set the desired room temperature. The unit will supply hot water to the heat emitters and the room will be heated. Additionally, also the desired leaving water temperature must be configured: when turning on the modulation, the desired leaving water temperature will be calculated automatically by the unit (based on the preset temperatures, if weather-dependent is selected, modulation will be done based on the desired weather-dependent temperatures); when turning off the modulation, you can set the desired leaving water temperature on the user interface. Moreover, with the modulation turned on, the desired leaving water temperature is lowered or raised in function of the desired room temperature and the difference between the actual and the desired room temperature. This results in:
▪ stable room temperatures exactly matching the desired
temperature (higher comfort level)
▪ less On/OFF cycles (lower noise level, higher comfort and higher
efficiency)
▪ water temperatures as low as possible to match the desired
temperature (higher efficiency)
# Code Description
[A.3.1.1.5] [8-05] Modulated LWT:
▪ 0 (No) (default): disabled.
Note: The desired leaving water temperature needs to be set on the user interface.
▪ 1 (Yes): enabled. The leaving water
temperature is calculated according to the difference between the desired and the actual room temperature. This creates a better match between the capacity of the heat pump and the actual required capacity, and results in less start/stop cycles and a more economic operation. Note: The desired leaving water temperature can only be read out on the user interface
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 43
8 Configuration
a
+[8-06]
−[8-06]
b
T
a
T
t
# Code Description
N/A [8-06] Leaving water temperature maximum
modulation:
0°C~10°C (default: 3°C)
Requires modulation to be enabled.
This is the value by which the desired leaving water temperature is increased or lowered.
INFORMATION
When leaving water temperature modulation is enabled, the weather‑dependent curve needs to be set to a higher position than [8-06] plus the minimum leaving water temperature setpoint required to reach a stable condition on the comfort setpoint for the room. To increase efficiency, modulation can lower the leaving water setpoint. By setting the weather‑dependent curve to a higher position, it cannot drop below the minimum setpoint. Refer to the illustration below.
# Code Description
[A.4.1] [6-0D] Domestic hot water Type:
▪ 0 (Reheat only): Only reheat operation
is allowed.
▪ 1 (Reheat + sched.)(default): The
domestic hot water tank is heated according to a schedule and between the scheduled heatup cycles, reheat operation is allowed.
▪ 2 (Scheduled only): The domestic hot
water tank can ONLY be heated according to a schedule.
See "8.3.2 Domestic hot water control: advanced" on page 46 for more details.
INFORMATION
There is a risk of space heating capacity shortage/comfort
problem (in case of frequent domestic hot water operation,
frequent and long space heating interruption will happen)
when selecting [6‑0D]=0 ([A.4.1] Domestic hot water
Type=Reheat only).
Maximum DHWtemperature setpoint
The maximum temperature that users can select for the domestic hot water. You can use this setting to limit the temperatures at the hot water taps.
INFORMATION
a Weather-dependent curve
b Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the room.
Leaving water temperature: Emitter type
Only applicable in case of room thermostat control. Depending on the system water volume and the heat emitters type, the heat up of a space can take longer. This setting can compensate for a slow or a quick heating system during the heat up cycle.
Note: The setting of the emitter type will influence the maximum modulation of the desired leaving water temperature and the possibility for usage of the automatic heating changeover based on the indoor ambient temperature.
Therefore it is important to set this correctly.
# Code Description
[A.3.1.1.7] [9-0B] Emitter type:
Reaction time of the system:
▪ 0 (Quick)(default)
Example: Small water volume and fan coils.
▪ 1 (Slow)
Example: Large water volume, floor heating loops.
During disinfection of the domestic hot water tank, the
DHWtemperature can exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the
applicable legislation.
# Code Description
[A.4.5] [6-0E] Maximum setpoint
The maximum temperature that users can select for the domestic hot water. You can use this setting to limit the temperature at the hot water taps.
Range: 40°C~60°C (default: 60°C)
The maximum temperature is NOT applicable during disinfection function. See disinfection function.

8.2.7 Contact/helpdesk number

# Code Description
[6.3.2] N/A Number that users can call in case of
problems.
8.3 Advanced configuration/

8.2.6 Domestic hot water control

Only applicable in case an optional domestic hot water tank is installed.
Configuring the desired tank temperature
The domestic hot water can be prepared in 3 different ways. They differ from each other by the way the desired tank temperature is set and how the unit acts upon it.

8.3.1 Space heating operation: advanced

Preset leaving water temperature
You can define preset leaving water temperatures:
▪ economic (denotes the desired leaving water temperature which
results in the lowest energy consumption)
▪ comfort (denotes the desired leaving water temperature which
results in the highest energy consumption).
optimization
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
43
Page 44
8 Configuration
T
t
T
A
R
L
0°C
T
t
T
A
R
L
0°C
a b
Preset values make it easy to use the same value in the schedule or to adjust the desired leaving water temperature according to the room temperature (see modulation). If you later want to change the value, you only have to do it in one place. Depending on whether the desired leaving water temperature is weather dependent or not, the absolute desired leaving water temperature should be specified or the desired shift values.
NOTICE
The preset leaving water temperatures are ONLY applicable for the main zone, as the schedule for the additional zone consists of On/OFF actions.
NOTICE
Select preset leaving water temperatures in accordance with the design and selected heat emitters to ensure the balance between desired room and leaving water temperatures.
# Code Description
Preset leaving water temperature for the main leaving water temperature zone in case of NOT weather dependent
[7.4.2.1] [8-09] Comfort (heating)
[9‑01]°C~[9‑00]°C (default: 55°C)
[7.4.2.2] [8-0A] Eco (heating)
[9‑01]°C~[9‑00]°C (default: 45°C)
Preset leaving water temperature (shift value) for the main leaving water temperature zone in case of weather dependent
[7.4.2.5] N/A Comfort (heating)
–10°C~+10°C (default: 0°C)
[7.4.2.6] N/A Eco (heating)
–10°C~+10°C (default: –2°C)
Temperature ranges (leaving water temperatures)
The purpose of this setting is to prevent selecting a wrong (i.e. too hot) leaving water temperature. Thereto the available desired heating temperature range can be configured.
NOTICE
In case of a floor heating application it is important to limit the maximum leaving water temperature at heating operation according to the specifications of the floor heating installation.
# Code Description
Leaving water temperature range for the main leaving water temperature zone (= the leaving water temperature zone with the lowest leaving water temperature in heating operation)
[A.3.1.1.2.2] [9-00] Maximum temp (heating)
37°C~65°C (default: 65°C)
[A.3.1.1.2.1] [9-01] Minimum temp (heating)
15°C~37°C (default: 24°C)
Leaving water temperature range for the additional leaving water temperature zone (= the leaving water temperature zone with the highest leaving water temperature in heating operation)
[A.3.1.2.2.2] [9-06] Maximum temp (heating)
37°C~65°C (default: 65°C)
[A.3.1.2.2.1] [9-05] Minimum temp (heating)
15°C~37°C (default: 24°C)
Leaving water temperature overshoot temperature
This function defines how much the water temperature may rise above the desired leaving water temperature before the compressor stops. The compressor will startup again when the leaving water temperature drops below the desired leaving water temperature.
# Code Description
N/A [9-04] 1°C~4°C (default: 1°C)
Leaving water temperature compensation around 0°C
In heating operation, the desired leaving water temperature is locally increased around an outdoor temperature of 0°C. This compensation can be selected when using an absolute or a weather dependent desired temperature, this compensation can be selected (see illustration below). Use this setting to compensate for possible heat losses of the building when the outdoor temperature is around 0°C (e.g. in cold region countries).
Example: Set the minimum leaving water temperature to 28°C to avoid NOT to be able to heat up the room: leaving water temperatures must be sufficiently higher than the room temperatures (in heating).
Installer reference guide
44
NOTICE
▪ When adjusting the leaving water temperature ranges,
all desired leaving water temperatures are also adjusted to guarantee they are between the limits.
▪ Always balance between the desired leaving water
temperature with the desired room temperature and/or the capacity (according to the design and selection of the heat emitters). The desired leaving water temperature is the result of several settings (preset values, shift values, weather dependent curves, modulation). As a result, too high or too low leaving water temperatures could occur which lead to overtemperatures or capacity shortage. By limiting the leaving water temperature range to adequate values (depending on the heat emitter), such situations can be avoided.
a Absolute desired LWT b Weather dependent desired LWT
TAAmbient temperature (°C)
TtDesired leaving water temperature
# Code Description
N/A [D-03] ▪ 0 (disabled) (default)
▪ 1 (enabled) L=2°C,
R=4°C (−2°C<TA<2°C)
▪ 2 (enabled) L=4°C,
R=4°C (−2°C<TA<2°C)
▪ 3 (enabled) L=2°C,
R=8°C (−4°C<TA<4°C)
▪ 4 (enabled) L=4°C,
R=8°C (−4°C<TA<4°C)
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 45
8 Configuration
[
9-0C
]
a
b
c
d
Leaving water temperature maximum modulation
Only applicable in room thermostat control and when modulation is enabled. The maximum modulation (=variance) on the desired leaving water temperature decided on the difference between the actual and desired room temperature, e.g. 3°C modulation means the desired leaving water temperature can be increased or lowered by 3°C. Increasing the modulation results in better performance (less On/OFF, faster heat up), but note that depending on the heat emitter, there must always be a balance (refer to the design and selection of the heat emitters) between the desired leaving water temperature and the desired room temperature.
# Code Description
N/A [8-06] 0°C~10°C (default: 3°C)
Temperature ranges (room temperature)
Only applicable in room thermostat control. In order to save energy by preventing overheating the room, you can limit the range of the room temperature.
NOTICE
When adjusting the room temperature ranges, all desired room temperatures are also adjusted to guarantee they are between the limits.
# Code Description
Room temp. range
[A.3.2.1.2] [3-06] Maximum temp (heating)
18°C~30°C (default: 30°C)
[A.3.2.1.1] [3-07] Minimum temp (heating)
12°C~18°C (default: 12°C)
Room temperature step
Only applicable in room thermostat control and when the temperature is displayed in °C.
# Code Description
[A.3.2.4] N/A Room temp. step
▪ 1°C (default). The desired room
temperature on the user interface is settable per 1°C.
▪ 0.5°C. The desired room temperature
on the user interface is settable per
0.5°C. The actual room temperature is displayed with an accuracy of 0.1°C.
Room temperature hysteresis
Only applicable in case of room thermostat control. The hysteresis band around the desired room temperature is settable. Daikin recommends NOT to change the room temperature hysteresis as it is set for an optimal use of the system.
a Room temperature
b Actual room temperature
c Desired room temperature
d Time
# Code Description
N/A [9-0C] 1°C~6°C (default: 1°C)
Room temperature offset
Only applicable in case of room thermostat control. You can calibrate the (external) room temperature sensor. It is possible to give an offset to the room thermistor value measured by the user
interface or by the external room sensor. The settings can be used to compensate for situations where the user interface or external room sensor cannot be installed on the ideal installation location (see installation manual and/or installer reference guide).
# Code Description
Room temp. offset: Offset on the actual room temperature measured on the user interface sensor.
[A.3.2.2] [2-0A] –5°C~5°C, step 0.5°C (default: 0°C)
Ext. room sensor offset: Only applicable if the external room sensor option is installed and configured (see [C-08])
[A.3.2.3] [2-09] –5°C~5°C, step 0.5°C (default: 0°C)
Room frost protection
Room frost protection prevents the room from getting too cold. This setting behaves differently depending on the set unit control method ([C‑07]). Perform actions according to the table below:
Unit control method ([C‑07]) Room frost protection
Room thermostat control ([C‑07]=2)
Allow for the room thermostat to take care of room frost protection:
▪ Set [2‑06] to "1"
▪ Set the room antifrost
temperature ([2‑05]).
External room thermostat control ([C‑07]=1)
Allow for the external room thermostat to take care of room frost protection:
▪ Turn ON the leaving water
temperature home page.
▪ Set auto emergency ([A.5.1.2])
to "1".
Leaving water temperature control ([C‑07]=0)
Room frost protection is NOT guaranteed.
INFORMATION
If an U4 error occurs, room frost protection is NOT
guaranteed.
Refer to the sections below for detailed information on room frost protection in relation to the applicable unit control method.
[C‑07]=2: room thermostat control
Under room thermostat control, room frost protection is guaranteed, even if the room temperature home page is OFF on the user interface. When room frost protection ([2‑06]) is enabled and the room temperature drops below the room antifrost temperature ([2‑05]), the unit will supply leaving water to the heat emitters to heat up the room again.
# Code Description
N/A [2-06] Room frost protection
▪ 0: disabled (default)
▪ 1: enabled
N/A [2-05] Room antifrost temperature
4°C~16°C (default: 12°C)
INFORMATION
If an U5 error occurs:
▪ when 1 user interface is connected, room frost
protection is NOT guaranteed,
▪ when 2 user interfaces are connected and the second
user interface used for room temperature control is disconnected (due to miswiring, damage of the cable), then room frost protection is NOT guaranteed.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
45
Page 46
8 Configuration
NOTICE
If Emergency is set to Manual ([A.5.1.2]=0), and the unit is triggered to start emergency operation, the user interface will ask confirmation before starting. Room frost protection is active even if the user does NOT confirm emergency operation.
[C‑07]=1: external room thermostat control
Under external room thermostat control, room frost protection is guaranteed by the external room thermostat, provided that the leaving water temperature home page is ON on the user interface, and the auto emergency setting ([A.5.1.2]) is set to "1".
Additionally, limited frost protection by the unit is possible:
In case of… …then the following applies:
One leaving water temperature zone
Two leaving water temperature zones
NOTICE
For the (limited) frost protection to be possible, auto emergency MUST be set to Automatic ([A.5.1.2]=1).
▪ When the leaving water
temperature home page is OFF and the outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again, and the leaving water temperature setpoint will be lowered by 5°C.
▪ When the leaving water
temperature home page is ON, the external room thermostat is "Thermo OFF" and the outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again and the leaving water temperature setpoint will be lowered by 5°C.
▪ When the leaving water
temperature home page is ON and the external room thermostat is "Thermo ON", then room frost protection is guaranteed by the normal logic.
▪ When the leaving water
temperature home page is OFF, and the outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again, and the leaving water temperature setpoint will be lowered by 5°C.
▪ When the leaving water
temperature home page is ON, the outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again, and the leaving water temperature setpoint will be lowered by 5°C.
Under leaving water temperature control, room frost protection is NOT guaranteed. However, if [2‑06] is set to "1", limited frost protection by the unit is possible:
▪ When the leaving water temperature home page is OFF and the
outdoor ambient temperature drops below 4°C, then the unit will supply leaving water to the heat emitters to heat up the room again, and the leaving water temperature setpoint will be lowered by 5°C.
▪ When the leaving water temperature home page is ON, then the
unit will supply leaving water to the heat emitters to heat up the room according to normal logic.
NOTICE
For the (limited) frost protection to be possible, auto emergency MUST be set to Automatic ([A.5.1.2]=1).
Shut-off valve
The following is only applicable in case of 2 leaving water temperature zones.
The shut-off valve, which is in the main leaving water temperature zone, output is configurable.
Thermo On/OFF: the valve closes, depending on [F-0B] when there is no heating and/or demand of the room in the main zone. Enable this setting to:
▪ avoid leaving water supply to the heat emitters in the main LWT
zone (through the mixing valve station) when there is request from the additional LWT zone.
▪ activate the On/OFF pump of the mixing valve station only when
there is demand. See "5Application guidelines"on page8.
# Code Description
[A.3.1.1.6.1] [F-0B] The shut-off valve:
▪ 0 (No)(default): is NOT influenced by
heating demand.
▪ 1 (Yes): closes when there is NO
heating demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room thermostat request setting (NOT in case of leaving water temperature setting).
Operation range
Depending on the average outdoor temperature, the operation of the unit in space heating is prohibited.
Space heating OFF temp: When the averaged outdoor temperature raises above this value, space heating is turned OFF to avoid overheating.
# Code Description
[A.3.3.1] [4-02] 14°C~35°C (default: 35°C)

8.3.2 Domestic hot water control: advanced

Preset tank temperatures
Only applicable when domestic hot water preparation is scheduled or scheduled + reheat.
You can define preset tank temperatures:
▪ storage economic
▪ storage comfort
▪ reheat
▪ reheat hysteresis
[C‑07]=0: leaving water temperature control
Installer reference guide
46
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 47
8 Configuration
T
DHW
T
a
[0-0C]
[0-0B]
[0-0E] [0-0D]
Preset values make it easy to use the same value in the schedule. If you later want to change the value, you only have to do it in 1 place (see also operation manual and/or user reference guide).
Storage comfort
When programming the schedule, you can make use of the tank temperatures set as preset values. The tank will then heat up until these setpoint temperatures have been reached. Additionally, a storage stop can be programmed. This feature puts a stop to tank heating even if the setpoint has NOT been reached. Only program a storage stop when tank heating is absolutely undesirable.
# Code Description
[7.4.3.1] [6-0A] 30°C~[6‑0E]°C (default: 60°C)
Storage eco
The storage economic temperature denotes the lower desired tank temperature. It is the desired temperature when a storage economic action is scheduled (preferably during day).
# Code Description
[7.4.3.2] [6-0B] 30°C~min(50, [6‑0E])°C (default: 45°C)
Reheat
The desired reheat tank temperature is used:
▪ in reheat mode of scheduled + reheat mode: The guaranteed
minimum tank temperature is set by T
–[6‑08], which is either
HP OFF
[6‑0C] or the weather dependent setpoint, minus the reheat hysteresis. If the tank temperature drops below this value, the tank is heated up.
# Code Description
[7.4.3.3] [6-0C] 30°C~min(50, [6‑0E])°C (default: 45°C)
Reheat hysteresis
Only applicable when domestic hot water preparation is scheduled + reheat.
# Code Description
N/A [6-08] 2°C~20°C (default: 10°C)
Weather dependent
The weather dependent installer settings define the parameters for the weather dependent operation of the unit. When weather dependent operation is active the desired tank temperature is determined automatically depending on the averaged outdoor temperature: low outdoor temperatures will result in higher desired tank temperatures as the cold water tap is colder and vice versa. In case of scheduled or scheduled+reheat domestic hot water preparation, the storage comfort temperature is weather dependent (according to the weather dependent curve), the storage economic and reheat temperature are NOT weather dependent. In case of reheat only domestic hot water preparation, the desired tank temperature is weather dependent (according to the weather dependent curve). During weather dependent operation, the end­user cannot adjust the desired tank temperature on the user interface.
# Code Description
[A.4.6] N/A Desired temperature mode:
▪ Fixed (default): disabled. All desired
tank temperature are NOT weather dependent.
▪ Weather dep.: enabled. In scheduled
or scheduled+reheat mode, the storage comfort temperature is weather dependent. Storage economic and reheat temperatures are NOT weather dependent. In reheat mode, the desired tank temperature is weather dependent. Note: When the displayed tank temperature is weather dependent, it cannot be adjusted on the user interface.
[A.4.7] [0-0E]
Weather-dependent curve
[0-0D]
[0-0C]
[0-0B]
▪ T
: The desired tank temperature.
DHW
▪ Ta: The (averaged) outdoor ambient
temperature
▪ [0-0E]: low outdoor ambient
temperature: –40°C~5°C (default: – 20°C)
▪ [0-0D]: high outdoor ambient
temperature: 10°C~25°C (default: 15°C)
▪ [0-0C]: desired tank temperature when
the outdoor temperature equals or drops below the low ambient temperature: 45°C~[6‑0E]°C (default: 60°C)
▪ [0-0B]: desired tank temperature when
the outdoor temperature equals or rises above the high ambient temperature: 35°C~[6‑0E]°C (default: 45°C)
Limits on heat pump operation
In domestic hot water operation, following hysteresis values can be set for the heat pump operation:
# Code Description
N/A [6-00] The temperature difference determining
the heat pump ON temperature.
Range: 2°C~20°C (default: 2°C)
N/A [6-01] The temperature difference determining
the heat pump OFF temperature.
Range: 0°C~10°C (default: 2°C)
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Example: setpoint (TU)>maximum heat pump temperature–[6‑01] (T
–[6‑01])
HP MAX
Installer reference guide
47
Page 48
8 Configuration
t
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U=TBUH OFF
[6-01] [6-00]
TU= 60°C T
HP MAX
= 50°C [6-01] = 2°C [6-00] = 2°C
HP
BUH
HP
5
10
20
30
40
46
48
50
60
t
[6-00]
HP
5
10
20
30
40
43
45
TU=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
t
1
0
1
0
[8-01] [8-02]
[8-00]
t
T
A
0
[8-01]
[5-03] [4-02]
[8-02]
[8-01]+
[8-04]
BUH Backup heater
HP Heat pump. If heating up time by the heat pump takes too
T
Example: setpoint (TU)≤maximum heat pump temperature–[6‑01] (T
–[6‑01])
HP MAX
long, auxiliary heating by the backup heater can take place Backup heater OFF temperature (TU)
BUH OFF
T
Maximum heat pump temperature at sensor in domestic
HP MAX
hot water tank
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
TUUser set point temperature (as set on the user interface)
HP MAX
HP OFF
−[6-01])
−[6-00])
t Time
# Code Description
N/A [8-01] Maximum running time for domestic hot
water operation. Domestic hot water heating stops even when the target domestic hot water temperature is NOT reached. The actual maximum running time also depends on setting [8-04].
▪ When system layout = Room
thermostat control: This preset value is only taken into account if there is a request for space heating. If there is NO request for space heating, the tank is heated until the setpoint has been reached.
▪ When system layout ≠ Room
thermostat control: This preset value is always taken into account.
Range: 5~95 minutes (default: 30)
N/A [8-02] Anti-recycling time.
Minimum time between two cycles for domestic hot water. The actual anti­recycling time also depends on ambient temperature.
Range: 0~10 hours (default: 0.5) (step:
0.5 hour)
Remark: The minimum time is 1/2 hour even when the selected value is 0.
N/A [8-04] Additional running time for the maximum
running time depending on the outdoor ambient limit temperature [4-02].
Range: 0~95 minutes (default: 95)
HP Heat pump. If heating up time by the heat pump takes too
long, auxiliary heating by the booster heater can take place
T
Maximum heat pump temperature at sensor in domestic
HP MAX
hot water tank
T
Heat pump OFF temperature (T
HP OFF
T
Heat pump ON temperature (T
HP ON
T
Domestic hot water temperature
DHW
TUUser set point temperature (as set on the user interface)
HP MAX
HP OFF
−[6-01])
−[6-00])
t Time
INFORMATION
The maximum heat pump temperature depends on the brine temperature. For more information, see
"14.7Operation range"on page82.
Timers for simultaneous request space and domestic hot water operation
# Code Description
N/A [8-00] Do not change. (default: 1)
Installer reference guide
48
[8-02]: Anti-recycling time
1 Heat pump domestic water heating mode (1=active, 0=not
active)
2 Hot water request for heat pump (1=request, 0=no request)
t Time
[8-04]: Additional running time at [4-02]
TAAmbient (outdoor) temperature
t Time
Anti-recycle time space operation Maximum running time domestic hot water
Disinfection
The disinfection function disinfects the domestic hot water tank by periodically heating the domestic hot water to a specific temperature.
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 49
8 Configuration
00.00 22.00 24.0001.00 23.00 t
T
DHW
T
H
T
U
[2-02]
[2-03]
[2-04]
CAUTION
The disinfection function settings MUST be configured by the installer according to the applicable legislation.
# Code Description
[A.4.4.2] [2-00] Operation day:
▪ 0: Each day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5 (default): Friday
▪ 6: Saturday
▪ 7: Sunday
[A.4.4.1] [2-01] Disinfection
▪ 0: No
▪ 1 (default): Yes
[A.4.4.3] [2-02] Start time: 00~23:00 (default: 23:00),
step: 1:00.
[A.4.4.4] [2-03] Temperature target: 60°C (fixed).
[A.4.4.5] [2-04] Duration: 40~60 minutes, default: 40
minutes.
INFORMATION
In case of error code AH and no interruption of the disinfection function occurred due to domestic hot water tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to program the start-up of the disinfection function at least 4 hours later than the last expected large hot water tapping. This start-up can be set by installer settings (disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage eco 3 hours before the scheduled start-up of the disinfection function to preheat the tank.
INFORMATION
Disinfection function is restarted in case the domestic hot water temperature drops 5°C below the disinfection target temperature within the duration time.
INFORMATION
An AH error occurs if you do the following during disinfection:
▪ Set the user permission level to Installer.
▪ Go to the DHWtank temperature home page (Tank).
▪ Press
to interrupt the disinfection.

8.3.3 Heat source settings

Backup heater
Backup heater operation mode: defines when backup heater operation is disabled, enabled or only allowed during domestic hot water operation. This setting is only overruled when backup heating is required during malfunctioning of the heat pump (when [A.5.1.2] is set on manual or automatic).
# Code Description
[A.5.1.1] [4‑00] Backup heater operation:
T
Domestic hot water temperature
DHW
TUUser set point temperature THHigh set point temperature [2-03]
t Time
[A.5.1.3] [4‑07] Defines whether backup heater second
WARNING
Be aware that the domestic hot water temperature at the hot water tap will be equal to the value selected in field setting [2-03] after a disinfection operation.
When the high domestic hot water temperature can be a potential risk for human injuries, a mixing valve (field supply) shall be installed at the hot water outlet connection
N/A [5‑00] Is backup heater operation allowed
of the domestic hot water tank. This mixing valve shall secure that the hot water temperature at the hot water tap never rise above a set maximum value. This maximum allowable hot water temperature shall be selected according to the applicable legislation.
[A.5.1.4] [5‑01] Equilibrium temperature.
CAUTION
Be sure that the disinfection function start time [A.4.4.3] with defined duration [A.4.4.5] is NOT interrupted by possible domestic hot water demand.
▪ 0: Disabled
▪ 1 (default): Enabled
step is:
▪ 1 (default): Allowed
▪ 0: NOT allowed
In this way it is possible to limit the backup heater capacity.
above equilibrium temperature during space heating operation?
▪ 1 (default): NOT allowed
▪ 0: Allowed
Outdoor temperature below which operation of the backup heater is allowed.
Range: –15°C~35°C (default: 0°C) (step: 1°C)
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
49
Page 50
8 Configuration
T
A
[C-03]
[C-04]
a
b
YC Y1 Y2 Y3 Y4
X1 X2 X3 X4
OFF ON
X2M
SS1
X1M
INFORMATION
Only for systems with integrated domestic hot water tank: If backup heater operation during space heating needs to be limited but can be allowed for domestic hot water operation, then put [4‑00] on 1, [5‑00] on 1, and [5‑01] on – 15°C.
INFORMATION
If the storage temperature set point is higher than 55°C, Daikin recommends NOT to disable the backup heater second step because it will have a big impact on the required time for the unit to heat up the domestic hot water tank.
Auto emergency
When the heat pump fails to operate the backup heater can serve as an emergency heater and either automatically or non-automatically take over the heat load. When auto emergency is set to Automatic and a heat pump failure occurs, the backup heater will automatically take over the heat load. When a heat pump failure occurs and auto emergency is set to Manual the domestic hot water and space heating operations will stop and need to be recovered manually. The user interface will then ask you to confirm whether the backup heater can take over the heat load or not. When the heat pump fails,
will appear on the user interface. If the house is unattended for longer periods, we recommend that setting [A.5.1.2] Emergency shall be set to Automatic.
# Code Description
[A.5.1.2] N/A Defines whether in an emergency
situation the backup heater is allowed to automatically take over the entire heat load or whether manual confirmation is required.
▪ 0: Manual (default)
▪ 1: Automatic
▪ [C‑04] Bivalent hysteresis: defines the temperature difference
between bivalent ON temperature and bivalent OFF temperature.
Permission signal X1–X2 (EKRP1HB)
TAOutdoor temperature
a Closed b Open
CAUTION
Make sure to observe all rules mentioned in application guideline 5 when bivalent operation function is enabled.
Daikin shall NOT be held liable for any damage resulting from failure to observe this rule.
INFORMATION
▪ The bivalent operation function has no impact on the
domestic water heating mode. The domestic hot water is still and only heated by the indoor unit.
▪ The permission signal for the auxiliary boiler is located
on the EKRP1HB (digital I/O PCB). When it is activated, the contact X1, X2 is closed and open when it is deactivated. See illustration below for the schematic location of this contact.
INFORMATION
The auto emergency setting can be set in the menu structure of the user interface only.
INFORMATION
If a heat pump failure occurs and [A.5.1.2] is set to Manual, the room frost protection function, the underfloor heating screed dryout function, and the water pipe antifreeze function will remain active even if the user does NOT confirm emergency operation.
Bivalent
Applies only to installations with an auxiliary boiler (alternating operation, parallel connected). The purpose of this function is to determine — based on the outdoor temperature — which heating source can/will provide the space heating, either the indoor unit or an auxiliary boiler.
The field setting "bivalent operation" apply only the indoor unit space heating operation and the permission signal for the auxiliary boiler.
When the "bivalent operation" function is enabled, the indoor unit will stop automatically in space heating operation when the outdoor temperature drops below "bivalent ON temperature" and the permission signal for the auxiliary boiler becomes active.
When the bivalent operation function is disabled, the space heating by indoor unit is possible at all outdoor temperatures (see operation ranges) and permission signal for auxiliary boiler is ALWAYS deactivated.
▪ [C‑03] Bivalent ON temperature: defines the outdoor temperature
below which the permission signal for the auxiliary boiler will be active (closed, KCR on EKRP1HB) and space heating by indoor unit will be stopped.
# Code Description
N/A [C‑03] ON temperature.
If the outdoor temperature drops below this temperature, the bivalent heat source permission signal will be active.
Range: –25°C~25°C (default: 0°C) (step: 1°C)
N/A [C‑04] Hysteresis.
Temperature difference between bivalent heat source ON and OFF to prevent too much switching.
Range: 2°C~10°C (default: 3°C) (step: 1°C)

8.3.4 System settings

Auto-restart
When power returns after a power supply failure, the auto restart function reapplies the remote controller settings at the time of the power failure. Therefore, it is recommended to always enable the function.
Installer reference guide
50
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 51
8 Configuration
If the preferential kWh rate power supply is of the type that power supply is interrupted, always enable the auto restart function. Continuous indoor unit control can be guaranteed independent of the preferential kWh rate power supply status, by connecting the indoor unit to a normal kWh rate power supply.
# Code Description
[A.6.1] [3‑00] Is the auto restart function of the unit
allowed?
▪ 0: No
▪ 1 (default): Yes
Preferential kWh rate power supply
# Code Description
[A.2.1.6] [D‑01] Connection to a preferential kWh rate
power supply:
▪ 0 (default): The heat pump module is
connected to a normal power supply.
▪ 1: The heat pump module is
connected to a preferential kWh rate power supply. When the preferential kWh rate signal is sent by the electricity company, the contact will open and the unit will go in forced off mode. When the signal is released again, the voltage-free contact will close and the unit will restart operation. Therefore, always enable the auto restart function.
▪ 2: The heat pump module is
connected to a preferential kWh rate power supply. When the preferential kWh rate signal is sent by the electricity company, the contact will close and the unit will go in forced off mode. When the signal is released again, the voltage-free contact will open and the unit will restart operation. Therefore, always enable the auto restart function.
[A.6.2.1] [D‑00] Which heaters are allowed to operate
during preferential kWh rate power supply?
▪ 0 (default): None
[D‑00] Backup heater Compressor
0 (default) Forced OFF Forced OFF
Power consumption control
NOTICE
During periods of excessive capacity demand (example: screed dryout function), the power limitation can be activated in accordance to the dimension of the brine earth collector.
See "5 Application guidelines" on page 8 for detailed information about this functionality.
Pwr consumpt. control
# Code Description
N/A [4-08] Mode:
▪ 0 (No limitation)(default): Disabled.
▪ 1 (Continuous): Enabled: You can
set one power limitation value (in A or kW) to which the system power consumption will be limited for all the time.
▪ 2 (Digital inputs): Enabled: You can
set up to four different power limitation values (in A or kW) to which the system power consumption will be limited when the corresponding digital input asks.
N/A [4-09] Type:
▪ 0 (Current) (default): The limitation
values are set in A.
▪ 1 (Power): The limitation values are
set in kW.
N/A [5-05] Value: Only applicable in case of full
time power limitation mode.
0A~50A, step: 1A (default: 50A)
N/A [5-09] Value: Only applicable in case of full
time power limitation mode.
0kW~20kW, step: 0.5kW (default: 20kW)
Amp. limits for DI: Only applicable in case of power limitation mode based on digital inputs and based on current values.
N/A [5-05] Limit DI1
0A~50A, step: 1A (default: 50A)
N/A [5-06] Limit DI2
0A~50A, step: 1A (default: 50A)
N/A [5-07] Limit DI3
0A~50A, step: 1A (default: 50A)
N/A [5-08] Limit DI4
0A~50A, step: 1A (default: 50A)
kW limits for DI: Only applicable in case of power limitation mode based on digital inputs and based on power values.
N/A [5-09] Limit DI1
0kW~20kW, step: 0.5kW (default: 20kW)
N/A [5-0A] Limit DI2
0kW~20kW, step: 0.5kW (default: 20kW)
N/A [5-0B] Limit DI3
0kW~20kW, step: 0.5kW (default: 20kW)
N/A [5-0C] Limit DI4
0kW~20kW, step: 0.5kW (default: 20kW)
Average timer
The average timer corrects the influence of ambient temperature variations. The weather-dependent set point calculation is done on the average outdoor temperature.
The outdoor temperature is averaged over the selected time period.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
51
Page 52
8 Configuration
[9-0D]=0 [9-0D]=5
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
a (kPa)
b (l/min)
[9-0D]=6 [9-0D]=7
[9-0D]=8
a (kPa)
b (l/min)
# Code Description
[A.6.4] [1-0A] Outdoor average timer:
▪ 0: No averaging (default)
▪ 1: 12hours
▪ 2: 24hours
▪ 3: 48hours
▪ 4: 72hours
Offset temperature remote outdoor ambient sensor
You can calibrate the remote outdoor ambient temperature sensor. It is possible to give an offset to the thermistor value. The setting can be used to compensate for situations where the remote outdoor ambient sensor cannot be installed on the ideal installation location (see installation).
# Code Description
[A.6.5] [2‑0B] –5°C~5°C, step: 0.5°C (default: 0°C)
The weather-dependent leaving water temperature setpoint is calculated based on the outdoor ambient temperature + [2‑0B]. However, the user interface will ONLY display the outdoor ambient temperature (without the addition of [2‑0B]).
Pump operation
When the pump operation function is disabled the pump will stop if the outdoor temperature is higher than the value set by [4‑02]. When the pump operation is enabled, the pump operation is possible at all outdoor temperatures.
# Code Description
N/A [9‑0D] Pump speed limitation
▪ 0: No limitation.
▪ 1~4: General limitation. There is
limitation in all conditions. The required delta T control and comfort are NOT guaranteed.
▪ 5~8 (default: 6): Limitation when no
actuators. When there is no heating output, the pump speed limitation is applicable. When there is heating output, the pump speed is only determined by delta T in relation to the required capacity. With this limitation range, delta T is possible and the comfort is guaranteed.
The maximum values depend on the unit type:
# Code Description
N/A [F‑00] Pump operation:
▪ 0 (default): Disabled if outdoor
temperature is higher than [4‑02].
▪ 1: Possible at all outdoor
temperatures.
Pump operation during flow abnormality [F‑09] defines whether the pump stops at flow abnormality or allow to continue operation when flow abnormality occurs. This functionality is only valid in specific conditions where it is preferable to keep the pump active when Ta<4°C (pump will be activated for 10 minutes and deactivated after 10 minutes). Daikin shall NOT be held liable for any damage resulting this functionality.
# Code Description
N/A [F‑09] Pump continue operation when flow
abnormality:
▪ 0: Pump will be deactivated.
▪ 1 (default): Pump will be activated
when Ta<4°C (10 minutes ON – 10 minutes OFF)
Pump speed limitation
Pump speed limitation [9‑0D] defines the maximum pump speed. In normal conditions, the default setting should NOT be modified. The pump speed limitation will be overruled when the flow rate is in the range of the minimum flow (error 7H).
Installer reference guide
52
a External static pressure b Water flow rate
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 53

8.4 Menu structure: Overview user settings

< >
[1]
[2]
[5]
[6]
[7]
[2]
[6.2]
[6.3]
[6.8]
[7.1]
[7.4]
[7.3]
Set time/date
Date Time Daylight Saving Time Clock type
Holiday
Holiday
Holiday
Holiday
Holiday mode
Holiday mode
Home
Away
From
Until
Until
From
Use day schedule
Operation mode Heating
Select schedules
Room temperature LWT main LWT additional Tank temperature
Information
Sensor information Energy metering Error handling User permission level Actuators Operation modes
Running hours Version
Energy metering
Consumed elec.
Produced energy
Error information
Error history Contact/helpdesk number
Version
User interface Indoor unit Outdoor unit
User settings
Display Temperature lock
Set schedules Preset values Unit of measurement
Display
Contrast
Backlit LCD time User profile Available home pages
Set schedules
Room temp. LWT main LWT additional DHW temp DHW pump
Preset values
Room temperature LWT main Tank temperature
DHW
Set weather dependent
Warning history
[7.7]
Set weather dependent
Main
Additional
[7.7.1]
Main
Set weather-dependent heating
[7.7.2]
Additional
Set weather-dependent heating
8 Configuration
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
INFORMATION
Energy metering functionality is NOT applicable and/or NOT valid for this unit if it is calculated by the unit. If optional external meters are used, energy metering display is valid.
INFORMATION
▪ Indoor unit relates to indoor unit PCB which controls
the hydraulic part of the ground source heat pump.
▪ Outdoor unit relates to outdoor unit PCB which controls
the compressor module of the ground source heat pump.
Installer reference guide
53
Page 54
8 Configuration
[A]
[A.2]
[A.2.1]
[A.2.2]
[A.2.2.6]
[A.3]
[A.3.1]
[A.3.1.1]
[A.3.2]
[A.3.3]
[A.4]
[A.4.4]
[A.5]
[A.5.1]
[A.7]
[A.6]
[A.6.3]
[A.6.2]
Installer settings
Language System layout Space operation Domestic hot water (DHW) Heat sources System operation Commissioning Overview settings
System layout
Standard Options Capacities Confirm layout
Space operation
LWT settings Room thermostat Operation range
Domestic hot water
Type Disinfection Maximum setpoint SP mode Weather-dependent curve
Heat sources
Backup heater
System operation
Auto restart Preferential kWh rate
Pwr consumpt. control Averaging time Ext amb. sensor offset
Commissioning
Test run
UFH screed dryout
Air purge
Actuator test run
Standard
Unit type Compressor type Indoor software type
BUH type Preferential kWh rate Unit control method Number of LWT zones Pump operation mode Power saving possible User interface location
Options
Contact type main Contact type add. Digital I/O PCB Demand PCB External kWh meter External kWh meter DHW pump External sensor
Leaving water
Main Additional Delta T source
Room thermostat
Room temp. range Room temp. offset Ext. room sensor offset
Operation range
Space heating OFF temp
Disinfection
Disinfection Operation day Start time Temperature target Duration
Backup heater
Operation mode Emergency Enable BUH step 2 Equilibrium temp.
Prefer. kWh rate PS
Allowed heaters Forced pump OFF
Pwr consmp ctrl
Mode Type Amp. value
Amp. limits for DI
kW value
kW limits for DI Priority
Digital I/O PCB
Ext. backup heat src Solar kit Alarm output
Main
LWT setpoint mode
Temperature range Modulated LWT Shut-off valve
Emitter type
[A.3.1.2]
Additional
LWT setpoint mode
Temperature range
Room temp. step
Brine freezeup temp
[A.3.1.3]
Delta T source
Heating
INFORMATION
Depending on the selected installer settings, settings will be visible/invisible.

8.5 Menu structure: Overview installer settings

INFORMATION
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed.
INFORMATION
Power saving settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed.
Installer reference guide
54
INFORMATION
Depending on the selected installer settings, settings will be visible/invisible.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 55

9 Commissioning

9 Commissioning

9.1 Overview: Commissioning

This chapter describes what you have to do and know to commission the system after it is configured.
Typical workflow
Commissioning typically consists of the following stages:
1 Checking the "Checklist before commissioning".
2 Performing an air purge.
3 Performing an air purge on the brine circuit.
4 Performing a test run for the system.
5 If necessary, performing a test run for one or more actuators.
6 If necessary, performing an underfloor heating screed dryout.

9.2 Precautions when commissioning

INFORMATION
During the first running period of the unit, the required power may be higher than stated on the nameplate of the unit. This phenomenon is caused by the compressor, that needs a continuous run time of 50 hours before reaching smooth operation and stable power consumption.
NOTICE
NEVER operate the unit without thermistors and/or pressure sensors/switches. Burning of the compressor might result.

9.3 Checklist before commissioning

Do NOT operate the system before the following checks are OK:
You read the complete installation instructions, as described in the installer reference guide.
The indoor unit is properly mounted.
The following field wiring has been carried out according to this document and the applicable legislation:
▪ Between the local supply panel and the indoor unit
▪ Between the indoor unit and the valves (if applicable)
▪ Between the indoor unit and the room thermostat (if
applicable)
The system is properly earthed and the earth terminals are tightened.
The fuses or locally installed protection devices are installed according to this document, and have not been bypassed.
The power supply voltage matches the voltage on the identification label of the unit.
There are NO loose connections or damaged electrical components in the switchbox.
There are NO damaged components or squeezed pipes on the inside of the indoor unit.
There are NO refrigerant leaks.
The correct pipe size is installed and the pipes are properly insulated.
There is NO water and/or brine leak inside the indoor unit.
There are no odour traces noticeable of the used brine.
The space heating air purge valve is open (at least 2 turns).
The pressure relief valves purge to a safe location when opened.
The minimum water volume is guaranteed in all conditions. See "To check the water volume and flow rate of the space heating circuit and brine circuit" in
"6.3Preparing piping"on page18.

9.4 Checklist during commissioning

The minimum flow rate during backup heater/defrost operation is guaranteed in all conditions. See "To check the water volume and flow rate of the space heating circuit and brine circuit" in "6.3Preparing piping"on page18.
To perform an air purge.
To perform an air purge on the brine circuit.
To perform a test run.
To perform an actuator test run.
Underfloor screed dryout function
The underfloor screed dryout function is started (if necessary).

9.4.1 To check the minimum flow rate

1 Confirm according to the hydraulic configuration which space
heating loops can be closed due to mechanical, electronic, or other valves.
2 Close all space heating loops that can be closed (see previous
step).
3 Start the pump test run operation (see "9.4.5 To perform an
actuator test run"on page58).
4 Go to [6.1.8]: > Information > Sensor information > Flow rate
to check the flow rate. During pump test run operation, the unit can operate below this minimum required flow rate that is needed during defrost/backup heater operation.
Bypass valve foreseen?
Yes No
Modify the bypass valve setting to reach the minimum required flow rate + 2l/min
Minimum required flow rate during backup heater operation
12l/min

9.4.2 Air purge function on the space heating circuit

When commissioning and installing the unit, it is very important to remove all air in the water circuit. When the air purge function is running, the pump operates without actual operation of the unit and the remove of air in the water circuit will start.
In case the actual flow rate is below the minimum flow rate (required during defrost/backup heater operation), modifications at hydraulic configuration are required. Increase the space heating loops that can NOT be closed or install a pressure controlled bypass valve.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
55
Page 56
9 Commissioning
01:18
Tue
Air purge
l/min
Low
SHC
0.5
Flow rate Speed Circuit
Stop
Adjust
Scroll
01:18
Tue
Air purge
l/min
Low
SHC
0.5
Flow rate Speed Circuit
Stop
Adjust
Scroll
NOTICE
Before starting the air purge, open the safety valve and check if the circuit is sufficiently filled with water. Only if water escapes the valve after opening it, you can start the air purge procedure.
There are 2 modes to purge air:
▪ Manually: the unit will operate with a fixed pump speed and in a
fixed or custom position of the 3-way valve. The custom position of the 3-way valve is a helpful feature to remove all air from the water circuit in space heating or domestic hot water heating mode. The operation speed of the pump (slow or quick) can also be set.
▪ Automatic: the unit change automatically the pump speed and the
position of the 3-way valve between space heating or domestic hot water heating mode.
Typical workflow
Purging the air from the system should consist of:
1 Performing a manual air purge
2 Performing an automatic air purge
INFORMATION
Start by performing a manual air purge. When almost all the air is removed, perform an automatic air purge. If necessary, repeat performing the automatic air purge until you are sure that all air is removed from the system. During air purge function, pump speed limitation [9‑0D] is NOT applicable.
Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
The air purge function stops automatically after 30minutes.
To perform a manual air purge
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page34.
2 Set the air purge mode: go to [A.7.3.1] > Installer settings >
Commissioning > Air purge > Type.
3 Select Manual and press .
4 Go to [A.7.3.4] > Installer settings > Commissioning > Air
purge > Start air purge and press to start the air purge function.
Result: The manual air purge starts and the following screen appears.
Result: SHC
Result: Tank
To perform an automatic air purge
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page34.
2 Set the air purge mode: go to [A.7.3.1] > Installer settings >
Commissioning > Air purge > Type.
3 Select Automatic and press .
4 Go to [A.7.3.4] > Installer settings > Commissioning > Air
purge > Start air purge and press to start the air purge function.
Result: Air purging will start and the following screen will be shown.
To interrupt air purge
1 Press and press to confirm the interruption of the air
purge function.

9.4.3 Air purge function on the brine circuit

When installing and commissioning the unit, it is very important to remove all air from the brine circuit.
NOTICE
It is required that the brine circuit is filled BEFORE the brine pump test run is activated.
There are 2 ways to perform an air purge:
▪ with a brine filling station (field supply),
▪ with a brine filling station (field supply) in combination with the
unit's own brine pump.
10‑day brine pump operation. If a brine buffer vessel is part of the system, it may be required to let the brine pump run continuously for 10 days after the system is commissioned. If 10‑day brine pump operation is:
▪ ON: The unit operates as normal, except that the brine pump
operates continuously for 10 days, independent of compressor status.
▪ OFF: Brine pump operation is linked to compressor status.
5 Use the and buttons to scroll to Speed.
6 Use the and buttons to set the desired pump speed.
7 If applicable, set the desired position of the 3-way valve (space
8 Use the and buttons to set the desired position of the 3-way
Installer reference guide
56
Result: Low
Result: High
heating/domestic hot water)(space heating/domestic hot water). Use the and buttons to scroll to Circuit.
valve (space heating/domestic hot water).
To perform an air purge with a brine filling station
Follow the instructions included with the brine filling station (field supply).
To perform an air purge with the brine pump and a brine filling station
Prerequisite: Performing an air purge on the brine circuit was NOT
successful using a brine filling station only (see "To perform an air
purge with a brine filling station"on page 56). In this case, use a
brine filling station and the unit's own brine pump simultaneously.
1 Fill the brine circuit.
2 Start the brine pump test run.
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 57
3 Start the brine filling station (MUST be started within a time
a
b
A
B1
B2
1 2 43
>3 s
60 s
30 s
>3 s
A
> > > >
Set time/date Select schedules Information User settings
Select
Scroll
Installer settings
>
7
> > > >
Space operation Domestic hot water (DHW) Heat sources System operation
Select
Scroll
Commissioning
>
A
>
Overview settings
Installer settings
4
> > >
Test run UFH screed dryout Air purge
Select
Scroll
Actuator test run
>
A.7
Commissioning
> > > > >
Backup heater (step 1) Backup heater (step 2) Pump 3-way valve
Select
Scroll
Alarm output
>
A.7.4
Brine pump
Actuator test run
I
Brine pump
Are you sure you want to start the test?
Cancel
OK
Confirm Adjust
01:18
Tue
Test run
Mode
Stop
Brine pump
frame of 5~60seconds after starting the brine pump test run).
a Brine pump test run
b Brine filling station
Time frame of 5~60seconds
Result: The brine pump test run starts running, starting the removal of air from the brine circuit. During the test run, the brine pump operates without actual operation of the unit.
INFORMATION
For details on starting/stopping the brine pump test run, see "9.4.5To perform an actuator test run"on page58.
The brine pump test run stops automatically after 2hours.
To start or stop 10-day brine pump operation
INFORMATION
The 10‑day brine pump operation procedure includes the activation of the brine pump test run. Because the procedure provides limited time for this, it is required that the brine pump test run be activated as fast as possible. For instructions, see "To perform a brine pump test run"on
page57.
Prerequisite: All other commissioning tasks are finished.
1 Start the brine pump test run and leave it on for at least
3seconds.
Result: A 60‑second timer starts counting down.
2 Stop the brine pump test run before the timer has finished.
Result: A 30‑second timer starts counting down.
3 Start the brine pump test run again and leave it on for at least
3seconds.
4 Stop it before the timer has finished.
Result: 10‑day brine pump operation switches (OFF→ON or
ON→OFF).
9 Commissioning
4 Press twice to go to Commissioning and press .
5 Press once to go to Actuator test run and press .
6 Press once to go to Brine pump and press .
7 Select OK and press .
B1 Starting 10‑day brine pump operation B2 Stopping 10‑day brine pump operation
To perform a brine pump test run
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page34.
2 Press
3 Press
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
ON OFF
A Brine pump test run
.
once to go to Installer settings and press .
Result: The brine pump test run starts. It automatically stops when finished. To stop it manually, press , select OK and press .

9.4.4 To perform a test run

Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page34.
2 Go to [A.7.1]:
run.
3 Select a test and press
> Installer settings > Commissioning > Test
. Example: Heating.
Installer reference guide
57
Page 58
9 Commissioning
t
T
A1
25°C (1) 35°C (2)
24h (1) 36h (2)
4 Select OK and press .
Result: The test run starts. It stops automatically when done
(±30min). To stop it manually, press , select OK and press .
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
If the installation of the unit has been done correctly, the unit will start up during test operation in the selected operation mode. During the test mode, the correct operation of the unit can be checked by monitoring leaving water temperature (heating mode) and tank temperature (domestic hot water mode).
To monitor the temperature, go to [A.6] and select the information you want to check.

9.4.5 To perform an actuator test run

Purpose of the actuator test run is to confirm the operation of the different actuators (e.g., when you select pump operation, a test run of the pump will start).
Prerequisite: Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page34.
2 Make sure the room temperature control, the leaving water
temperature control and the domestic hot water control are turned OFF via the user interface.
3 Go to [A.7.4]:
Actuator test run.
4 Select an actuator and press
5 Select OK and press
Result: The actuator test run starts. It automatically stops when
finished. To stop it manually, press
INFORMATION
If the brine pump test run is activated as part of the 10‑day brine pump operation procedure, it is required to activate the test run as fast as possible. For instructions, see "To
perform a brine pump test run"on page57.
Possible actuator test runs
▪ Backup heater (step 1) test
▪ Backup heater (step 2) test
▪ Pump test (space heating)
INFORMATION
Make sure that all air is purged before executing the test run. Also avoid disturbances in the water circuit during the test run.
▪ Brine pump test
▪ 2-way valve test
▪ 3-way valve test
▪ Bivalent signal test
▪ Alarm output test
▪ Circulation pump test
▪ The user interface used to start the test run displays a
status screen.
▪ The other user interface displays a "busy" screen. You
cannot use the user interface as long as the "busy" screen is shown.
> Installer settings > Commissioning >
. Example: Pump.
.
, select OK and press .

9.4.6 Underfloor heating screed dryout

This function will be used to dry-out the screed of an underfloor heating very slowly during the construction of a house. It allows the installer to program and execute this program.
Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
INFORMATION
▪ If Emergency is set to Manual ([A.5.1.2]=0), and the
unit is triggered to start emergency operation, the user interface will ask confirmation before starting. The underfloor heating screed dryout function is active even if the user does NOT confirm emergency operation.
▪ During underfloor heating screed dryout, pump speed
limitation [9‑0D] is NOT applicable.
NOTICE
The installer is responsible for:
▪ contacting the screed manufacturer for the initial
heating instructions to avoid cracking the screed,
▪ programming the underfloor heating screed dryout
schedule according to the above instruction of the screed manufacturer,
▪ checking the proper functioning of the setup on a
regular basis,
▪ selecting the correct program complying with the type
of the used screed of the floor.
NOTICE
Room frost protection is default disabled ([2‑06]=0). Do NOT enable this function until the underfloor screed dryout function is completed successfully. Ignoring this notice can result in cracking of the screed.
NOTICE
For the underfloor heating screed dryout to be able to start, make sure the following settings are met:
▪ [2‑06]=0
▪ [4‑00]=1
▪ [4‑04]=2
▪ [C‑02]=0
▪ [D‑01]=0
▪ [4‑08]=0
▪ [4‑01]≠1
The installer can program up to 20 steps where for each step he needs to enter:
1 the duration by a number of hours up to 72hours,
2 the desired leaving water temperature.
Example:
T Desired leaving water temperature (15~55°C)
t Duration (1~72h)
(1) Action step 1
Installer reference guide
58
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 59

10 Hand-over to the user

15:10
1 14d 12h 25°C
Tue
Screed dryout
Current step
Remaining Desired LWT
Stop
(2) Action step 2
To program an underfloor heating screed dryout schedule
1 Set the user permission level to Installer. See "To set the user
permission level to Installer"on page34.
2 Go to [A.7.2]: > Installer settings > Commissioning > UFH
screed dryout > Set dryout schedule.
3 Use the , , , and to program the schedule.
▪ Use and to scroll through the schedule. ▪ Use and to adjust the selection.
If a time is selected, you can set the duration between 1 and 72hours. If a temperature is selected, you can set the desired leaving water temperature between 15°C and 55°C.
4 To add a new step, select "–h" or "–" on an empty line and
press .
5 To delete a step, set the duration to "–" by pressing .
6 Press to save the schedule.
It is important that there is no empty step in the program. The schedule will stop when a blank step is programmed OR when 20 consecutive steps have been executed.
To perform an underfloor heating screed dryout
INFORMATION
Preferential kWh rate power supply cannot be used in combination with underfloor heating screed dryout.
Prerequisite: Make sure there is ONLY 1 user interface connected to your system to perform an underfloor heating screed dryout.
Prerequisite: Make sure that the leaving water temperature home page, room temperature home page, and domestic hot water home page are turned OFF.
1 Go to [A.7.2]: > Installer settings > Commissioning > UFH
screed dryout.
2 Set a dryout program.
3 Select Start dryout and press .
4 Select OK and press .
Result: The underfloor heating screed dryout starts and following
screen will be shown. It stops automatically when done. To stop it manually, press , select OK and press .
To readout the status of an underfloor heating screed dryout
1 Press .
2 The current step of the program, the total remaining time, and
the current desired leaving water temperature will be displayed.
To interrupt an underfloor heating screed dryout
When the program is stopped by an error, an operation switch off, or a power failure, the U3 error will be displayed on the user interface. To resolve the error codes, see "12.4 Solving problems based on
error codes" on page 63. To reset the U3 error, your User
permission level needs to be Installer.
1 Go to the underfloor heating screed dryout screen.
2 Press .
3 Press to interrupt the program.
4 Select OK and press .
Result: The underfloor heating screed dryout program is stopped.
When the program is stopped due to an error, an operation switch­off, or a power failure, you can read out the underfloor heating screed dryout status.
5 Go to [A.7.2]: > Installer settings > Commissioning > UFH
screed dryout > Dryout status > Stopped at and followed by the last executed step.
6 Modify and restart the execution of the program.
10 Hand-over to the user
Once the test run is finished and the unit operates properly, please make sure the following is clear for the user:
▪ Fill in the installer setting table (in the operation manual) with the
actual settings.
▪ Make sure that the user has the printed documentation and ask
him/her to keep it for future reference. Inform the user that he can find the complete documentation on the url as earlier described in this manual.
▪ Explain the user how to properly operate the system and what to
do in case of problems.
▪ Show the user what to do in relation to maintaining the unit.
▪ Explain the user about energy saving tips as described in the
operation manual.

10.1 To fix the applicable language on the unit name plate

NOTICE
National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official language on the unit. Therefore, an additional multilingual fluorinated greenhouse gases label is supplied with the unit.
1 From the multilingual fluorinated greenhouse gases label peal
off the applicable language.
2 Stick it on top of the marked area on the unit name plate.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
INFORMATION
There is limited access to the menu structure. Only the following menus can be accessed:
▪ Information.
▪ Installer settings > Commissioning > UFH screed
dryout.
Installer reference guide
59
Page 60

11 Maintenance and service

1 3
2
5
4
11 Maintenance and service
NOTICE
Maintenance should preferably be carried out yearly by an installer or service agent.

11.1 Overview: Maintenance and service

This chapter contains information about:
▪ The yearly maintenance of the indoor unit

11.2 Maintenance safety precautions

DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING
NOTICE:Risk of electrostatic discharge
Before performing any maintenance or service work, touch a metal part of the unit in order to eliminate static electricity and to protect the PCB.

11.3 Checklist for yearly maintenance of the indoor unit

Check the following at least once a year:
▪ Fluid pressure of space heating and brine circuit
▪ Filters
▪ Pressure relief valves (1 at brine side, 1 at space heating side)
▪ Relief valve hoses
▪ Pressure relief valve of the domestic hot water tank
▪ Switch box
▪ Descaling
▪ Chemical disinfection
▪ Anode
▪ Brine leakage
Fluid pressure
Check whether the fluid pressure is above 1 bar. If it is lower, add fluid.
Filters
Clean the filters.
NOTICE
Handle the space heating circuit filter with care. Do NOT use excessive force when you reinsert the water filter so as NOT to damage the water filter mesh.
NOTICE
When removing the filter circlip, do NOT drop it.
Pressure relief valve
Open the valve and check the correct operation. Discharge may be very hot!
Checkpoints are:
▪ Fluid flow coming from the relief valve is high enough, no
blockage of the valve or in between piping is suspected.
▪ Fluid coming out from the relief valve and contains debris or dirt:
▪ open the valve until the discharged water does NOT contain dirt
anymore
▪ flush the system and install an additional water filter (a
magnetic cyclone filter is preferably).
It is recommended to do this maintenance more frequently.
Pressure relief valve hose
Check whether the pressure relief valve hose is positioned appropriately to drain. See "7.5.5 To connect the pressure relief
valve to the drain" on page27 and "7.4.5To connect the pressure relief valve to the drain on the brine side"on page26.
Relief valve of the domestic hot water tank (field supply)
Open the valve and check the correct operation. Water may be very hot!
Checkpoints are:
▪ The water flow coming from the relief valve is high enough, no
blockage of the valve or in between piping is suspected.
▪ Dirty water coming out of the relief valve:
▪ open the valve until the discharged water does not contain dirt
anymore
▪ flush and clean the complete tank, including the piping between
the relief valve and cold water inlet.
To make sure this water originates from the tank, check after a tank heat up cycle.
It is recommended to do this maintenance more frequently.
Switch box
▪ Carry out a thorough visual inspection of the switchbox and look
for obvious defects such as loose connections or defective wiring.
▪ Using an ohmmeter, check if contactors K1M, K2M, K3M and K5M
(depending on your installation) operate correctly. All contacts of these contactors must be in open position when the power is turned OFF.
WARNING
If the internal wiring is damaged, it has to be replaced by the manufacturer, its service agent or similarly qualified persons.
Installer reference guide
60
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 61
Descaling
Depending on water quality and set temperature, scale can deposit on the heat exchanger inside the domestic hot water tank and can restrict heat transfer. For this reason, descaling of the heat exchanger may be required at certain intervals.
Chemical disinfection
If the applicable legislation requires a chemical disinfection in specific situations, involving the domestic hot water tank, please be aware that the domestic hot water tank is a stainless steel cylinder containing an aluminium anode. We recommend to use a non­chloride based disinfectant approved for use with water intended for human consumption.
NOTICE
When using means for descaling or chemical disinfection, it must be ensured that the water quality remains compliant with EU directive 98/83EC.
Anode
No maintenance or replacement required.
Brine leakage
Carefully check if brine leakage is noticeable around the inside of the unit.
Open the sound insulation jacket and check if brine leakage is noticeable inside this enclosed volume.

12 Troubleshooting

INFORMATION
To drain the tank, all the hot water tapping points need to be opened to allow air to enter the system.
3 Open the drain valve.

11.4 To drain the domestic hot water tank

Prerequisite: Switch OFF the power supply.
Prerequisite: Turn OFF the cold water supply.
1 Open the front panel.
2 The drain hose is located at the right side of the unit. Cut the tie
wraps or tape and bring the flexible drain hose forward.
12 Troubleshooting

12.1 Overview: Troubleshooting

This chapter describes what you have to do in case of problems.
It contains information about:
▪ Solving problems based on symptoms
▪ Solving problems based on error codes
Before troubleshooting
Carry out a thorough visual inspection of the unit and look for obvious defects such as loose connections or defective wiring.

12.2 Precautions when troubleshooting

WARNING
▪ When carrying out an inspection on the switch box of
the unit, always make sure that the unit is disconnected from the mains. Turn off the respective circuit breaker.
▪ When a safety device was activated, stop the unit and
find out why the safety device was activated before resetting it. NEVER bridge safety devices or change their values to a value other than the factory default setting. If you are unable to find the cause of the problem, call your dealer.
DANGER: RISK OF ELECTROCUTION
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
61
Page 62
12 Troubleshooting
WARNING
Prevent hazard due to the inadvertent resetting of the thermal cut-out: this appliance must NOT be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly turned ON and OFF by the utility.
DANGER: RISK OF BURNING

12.3 Solving problems based on symptoms

12.3.1 Symptom: The unit is NOT heating as expected

Possible causes Corrective action
The temperature setting is NOT correct
The water or brine flow is too low Check and make sure that:
The water volume in the installation is too low
Check the temperature setting on the remote controller. Refer to the operation manual.
▪ All shut-off valves of the water
or brine circuit are completely open.
▪ The water filter is clean. Clean
if necessary.
▪ There is no air in the system.
Purge air if necessary. You can purge air manually (see
"To perform a manual air purge"on page56) or use the
automatic air purge function (see "To perform an automatic
air purge"on page56).
▪ The water pressure is >1 bar.
▪ The expansion vessel is NOT
broken.
▪ The resistance in the water
circuit is NOT too high for the pump.
If the problem persists after you have conducted all of the above checks, contact your dealer. In some cases, it is normal that the unit decides to use a low water flow.
Make sure that the water volume in the installation is above the minimum required value (see
"6.3.3To check the water volume and flow rate of the space heating circuit and brine circuit"on page20).

12.3.2 Symptom: The compressor does NOT start (space heating or domestic water heating)

Possible causes Corrective action
The unit must start up out of its operation range (the water temperature is too low)
The preferential kWh rate power supply settings and electrical connections do NOT match
The preferential kWh rate signal was sent by the electricity company
If the water temperature is too low, the unit uses the backup heater to reach the minimum water temperature first (15°C).
Check and make sure that:
▪ The power supply to the
backup heater is correctly wired.
▪ The backup heater thermal
protector is NOT activated.
▪ The backup heater contactors
are NOT broken.
If the problem persists after you have conducted all of the above checks, contact your dealer.
This should match with the connections as explained in
"6.4Preparing electrical wiring"on page22 and "7.6.6To connect the main power supply"on page30.
Wait for the power to return (2 hours max.).

12.3.3 Symptom: The pump is making noise (cavitation)

Possible causes Corrective action
There is air in the system Purge air manually (see "To
perform a manual air purge"on page56) or use the automatic air
purge function (see "To perform
an automatic air purge"on page56).
The pressure at the pump inlet is too low
Check and make sure that:
▪ The pressure is >1bar.
▪ The manometer is not broken.
▪ The expansion vessel is NOT
broken.
▪ The pre-pressure setting of the
expansion vessel is correct (see "6.3.4 Changing the pre-
pressure of the expansion vessel"on page21).

12.3.4 Symptom: The pressure relief valve opens

Installer reference guide
62
Possible causes Corrective action
The expansion vessel is broken Replace the expansion vessel.
The water or brine volume in the installation is too high
Make sure that the water or brine volume in the installation is below the maximum allowed value (see
"6.3.3To check the water volume and flow rate of the space heating circuit and brine circuit"on page20 and "6.3.4Changing the pre-pressure of the expansion vessel"on page21).
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 63
12 Troubleshooting
Possible causes Corrective action
The water circuit head is too high The water circuit head is the
difference in height between the unit and the highest point of the water circuit. If the unit is located at the highest point of the installation, the installation height is considered 0m. The maximum water circuit head is 10m.
Check the installation requirements.

12.3.5 Symptom: The pressure relief valve leaks

Possible causes Corrective action
Dirt is blocking the water pressure relief valve outlet
Check whether the pressure relief valve works correctly by turning the red knob on the valve counterclockwise:
▪ If you do NOT hear a clacking
sound, contact your dealer.
▪ If the water or brine keeps
running out of the unit, close both inlet and outlet shut-off valves first and then contact your dealer.

12.3.6 Symptom: The space is NOT sufficiently heated at low outdoor temperatures

Possible causes Corrective action
The backup heater operation is not activated
The backup heater equilibrium temperature has not been configured correctly
Check and make sure that:
▪ The backup heater operation
mode is enabled. Go to:
▪ [A.5.1.1] > Installer settings
> Heat sources > Backup heater > Operation mode OR
▪ [A.8] > Installer settings >
Overview settings [4‑00]
▪ The thermal protector of the
backup heater has not been activated. If it has, check:
▪ The space heating and brine
circuit pressure
▪ Whether there is air in the
system
▪ The air purge operation
Press the reset button in the switch box. See
"14.3Components"on page69
for the location of the reset button.
Increase the "equilibrium temperature" to activate the backup heater operation at a higher outdoor temperature. Go to:
▪ [A.5.1.4] > Installer settings >
Heat sources > Backup heater > Equilibrium temp. OR
▪ [A.8] > Installer settings >
Overview settings [5‑01]

12.3.7 Symptom: The pressure at the tapping point is temporarily unusual high

Possible causes Corrective action
Failing or blocked pressure relief valve.
▪ Flush and clean the complete
tank including the piping between pressure relief valve and the cold water inlet.
▪ Replace the pressure relief
valve.

12.3.8 Symptom: Decoration panels are pushed away due to a swollen tank

Possible causes Corrective action
Failing or blocked pressure relief valve.
Contact your local dealer.

12.3.9 Symptom: Tank disinfection function is NOT completed correctly (AH-error)

Possible causes Corrective action
The disinfection function was interrupted by domestic hot water tapping
Large domestic hot water tapping happened recently before the programmed start-up of the disinfection function
The disinfection operation was stopped manually: with the user interface displaying the DHW home page and its user permission level set to Installer, the button was pressed during disinfection operation.
Program the start-up of the disinfection function when the coming 4hours NO domestic hot water tapping is expected.
When the Domestic hot water > Type > Reheat or Reheat + sched. is selected, it is recommended to program the start-up the disinfection function at least 4hours later than the last expected large hot water tapping. This start-up can be set by installer settings (disinfection function).
When the Domestic hot water > Type > Scheduled only is selected, it is recommended to program a Storage eco 3hours before the scheduled start-up of the disinfection function to preheat the tank.
Do NOT press the button while the disinfection function is active.

12.4 Solving problems based on error codes

When a problem happens, an error code appears on the user interface. It is important to understand the problem and to take countermeasure before resetting the error code. This should be done by a licensed installer or by your local dealer.
This chapter gives you an overview of all error codes and the content of the error code as it appears on the user interface.
For a more detailed troubleshooting guideline for each error, please see the service manual.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
63
Page 64
12 Troubleshooting

12.4.1 Error codes: Overview

Error codes of the unit
Error code Detailed error
code
E1 00 OU: PCB defect.
E3 00 OU: Actuation of high pressure
E5 00 OU: Overheat of inverter
E7 62 Brine flow Abnormality
E9 00 Expansion valve abnormality.
H0 01 Brine flow switch malfunction
H3 00 OU: Malfunction of high
H9 00 OU: Malfunction of outdoor
F3 00 OU: Malfunction of discharge
J1 00 High pressure sensor
JA 00 OU: Malfunction of high
J3 00 OU: Malfunction of discharge
J6 00 OU: Malfunction of heat
J7 12 Brine inlet thermistor
J8 07 Brine outlet thermistor
L3 00 OU: Electrical box temperature
Description
Power reset required.
Please contact your dealer.
switch (HPS).
Please contact your dealer.
compressor motor.
Please contact your dealer.
Please contact your dealer.
Please contact your dealer.
Please contact your dealer.
pressure switch (HPS)
Please contact your dealer.
air thermistor.
Please contact your dealer.
pipe temperature.
Please contact your dealer.
abnormality.
Please contact your dealer.
pressure sensor.
Please contact your dealer.
pipe thermistor.
Please contact your dealer.
exchanger thermistor.
Please contact your dealer.
abnormality
Please contact your dealer.
abnormality
Please contact your dealer.
rise problem.
Please contact your dealer.
Error code Detailed error
code
L4 00 OU: Malfunction of inverter
L5 00 OU: Inverter instantaneous
P4 00 OU: Malfunction of radiating
U0 02 Refrigerant shortage
U2 00 OU: Defect of power supply
U4 00 Indoor/outdoor unit
A1 00 Zero cross detection problem.
AA 01 Backup heater overheated.
UA 00 Indoor unit, outdoor unit
7H 01 Water flow problem.
89 01 Heat exchanger frozen.
8H 00 Abnormal increase outlet
8F 00 Abnormal increase outlet
C0 00 Flow sensor/switch malfunction.
U3 00 Under floor heating screed
81 00 Leaving water temperature
Description
radiating fin temperature rise.
Please contact your dealer.
overcurrent (DC).
Please contact your dealer.
fin temperature sensor.
Please contact your dealer.
Please contact your dealer.
voltage.
Please contact your dealer.
communication problem.
Power reset required.
Please contact your dealer.
Power reset required.
Please contact your dealer.
matching problem.
Power reset required.
water temperature.
water temperature (DHW).
Please contact your dealer.
dryout function not completed
correctly.
sensor problem.
Please contact your dealer.
Installer reference guide
64
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 65

13 Disposal

Error code Detailed error
code
C4 00 Heat exchanger temperature
80 00 Returning water temperature
U5 00 User interface
EC 00 Abnormal increase tank
HC 00 Tank temperature sensor
CJ 02 Room temperature sensor
H1 00 External temperature
89 02 Heat exchanger frozen.
A1 01 EEPROM reading error.
AH 00 Tank disinfection function not
Description
sensor problem.
Please contact your dealer.
sensor problem.
Please contact your dealer.
communication problem.
temperature.
problem.
Please contact your dealer.
problem.
Please contact your dealer.
sensor problem.
Please contact your dealer.
completed correctly.
INFORMATION
In case of error code AH and no interruption of the disinfection function occurred due to domestic hot water tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to program the start-up of the disinfection function at least 4 hours later than the last expected large hot water tapping. This start-up can be set by installer settings (disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage eco 3 hours before the scheduled start-up of the disinfection function to preheat the tank.
NOTICE
When the minimum water flow (in relation to the applicable operation mode) is lower than described in the table below, the unit will stop operation and the user interface will display error 7H.
Minimum required flow
Heat pump operation 10l/min
Backup heater operation
INFORMATION
Error AJ-03 is reset automatically from the moment there is a normal tank heat-up.
INFORMATION
In case of an E7‑62 error, brine pump operation stops due to not enough flow in the brine circuit. If 10‑day brine pump operation is running, it will stop running and will only resume once the error is reset. It is only possible to reset the error with the domestic hot water home screen or the leaving water temperature home screen turned ON. To reset the error, press and confirm by pressing .
12l/min
89 03 Heat exchanger frozen.
AJ 03 Too long DHW heat-up time
required.
INFORMATION
▪ Indoor unit relates to indoor unit PCB which controls
the hydraulic part of the ground source heat pump.
▪ Outdoor unit relates to outdoor unit PCB which controls
the compressor module of the ground source heat pump.
13 Disposal
Dismantling of the unit, and treatment of the refrigerant, oil and other parts must comply with the applicable legislation.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
65
Page 66

14 Technical data

820
228
1775
1740
R
210
288
45
199
75
101
189
150
301
225
152
40
75
60
300
728
761
600
g
l n m k i
h
w
s d
y
f
q
e
v
c
o
t
q
x
b
r
a
j
p u
450
199
v
3D081375-1C
5 mm
PH2
8 mm
PH2T25
14 Technical data
Latest information can be found in the technical engineering data.

14.1 Overview: Technical data

This chapter contains information about:
• Dimensions and service space
• Centre of gravity
• Components
• Piping diagram
• Wiring diagram
• Technical specifications
• Operation range
• ESP curve

14.2 Dimensions and service space

14.2.1 Dimensions and service space: Indoor unit

a Pressure gauge brine circuit b Pressure gauge water circuit c Safety valve brine circuit d Safety valve water circuit e Drain valve brine circuit
f Drain valve water circuit g Water filter brine circuit h Water filter water circuit
i Water IN connection 22mm straight j Water OUT connection 22mm straight
Installer reference guide
66
k Tank IN connection 22mm straight
l Tank OUT connection 22mm straight
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 67
14 Technical data
m Brine IN connection 28mm straight
n Brine OUT connection 28mm straight o Control wiring intake (Ø24mm) p Power supply wiring intake (Ø24mm) q Leveling feet
r User interface (option EKRUCBL*)
s Drain valve tank circuit
t Recirculation connection G 1/2 female
u Hole for recirculation piping or option wiring (Ø62mm)
v Drain outlet (unit+safety valve)
w Air purge
x Expansion vessel brine circuit y Expansion vessel water circuit
Centre of gravity. Note: Centre of gravity with an empty tank.
Note1: Typical field installation is according to local and national regulations. Note2: A flexible hose is pre-assembled to the drain outlet. The exit of the flexible hose is at the backside of the unit. The flexible hose can be removed.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
67
Page 68
14 Technical data
≥500
≥300
≥50
≥50
≥10
≥10
3D081380-1A
Installer reference guide
68
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 69

14.3 Components

X5M
YC Y1 Y2 Y3 Y4
A9P
A10P
A1P
A8P
A4P
Q1L
K5M
X1M
X2M
X6Y
F1B
X6YA
X6YB
a n
k
l
i
b
o
j
j
j
r r
f
e
g
p
p
p
c
d
hm qj
s
d

14.3.1 Components: Switch box (indoor unit)

14 Technical data
a Main PCB (water) A1P b Backup heater thermal protector Q1L c Transformer TR1 d Backup heater contactors K1M, K2M and K5M e Backup heater circuit breaker F1B
f Connectors X6YA/X6YB/X6Y g Terminal block X1M (power supply) h Terminal block X2M (high voltage)
i Terminal block X5M (low voltage) j Cable tie mountings
k Main PCB (refrigerant, brine) A9P
l Main PCB (inverter) A10P
m Digital I/O PCB A4P (optional)
n Demand PCB A8P (optional) o Brine pump contactor K6M. Note: Only 4 of the 5 connection points
are used.
p Reactors q PCB fuse A1P (FU1)
r PCB fuse A9P (F1U, F2U) s PCB fuse A10P (F1U)
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
69
Page 70
14 Technical data
Descript ion senso rs
LEGEND:
t >
R2T
t >
R3T
t >
R2T
t >
R1T
t >
R4T
M
PUMP
t >
R5T
t >
R5T
t >
R4T
t >
R3T
t >
R6T
P P
(*)
(*)
(*)
(*)
(*)
NRV
3D081374-1A page 1
(*)
PLATE
HEAT
EXCHANGER
(Evaporator)
PLATE
HEAT
EXCHANGER
(Condenser)
high
pressure
switch
high
pressure
sensor
COMPRESSOR
MUFFLER
Depicted is example, for complete installation requirements, refer to installation manual
To Space Heating
Circuit
EXPANS ION
VESSE L
BLOW
OFF
SAFETY
VALVE
FIELD SUPPLIED
FIELD SUPPLIED
To DHW circuit
SHUT
OFF
VALVE
SHUT
OFF
VALVE
SHUT
OFF
VALVE
SHUT
OFF
VALVE
3-WAY VALVE
indoor
BACK UP
HEATE R
Water si de
Refrigera
nt
PRESSURE
GAUGE
SAFETY
VALVE
BLOW
OFF
indoor
check
valve
Outlet Water Temperature Senso r (LWC) Aft er BUH Temperature Senso r Refrigerant Liquid Temperat ure Sensor Inlet Water Temperature Sensor (EWC) DHW Tank Temperat ure Sensor Ambient Air Sensor discharge senso r suctio n sensor
brine entering water brine leaving water
2 phase sensor (Tx)
R1T in R2T in R3T in R4T in R5T in
R1T out R2T out R3T out R4T out R5T out R6T out
CHECK VALVE
FLARE CONN.
SCREW CONN.
FLANGE CONN.
PINCHED PIPE
SPINNED PIPE
BRAZED CONN.
QUICK COUPLING
flow
sensor
FIELD SUPPLIED
FILLING VALVE
KIT
FIELD SUPPLIED
drain
drain
service port
service port
outdoor
MOTOR
OPERATED
VALVE
indoor
heat sink
inverter PCB
FILTER
indoor
AIR
PURGE
FIELD SUPPLIED
FILL
VALVE
EXPANS ION
VESSE L
EXPANS ION
VESSE L
DHW
TANK
indoor
FILTER
drain
To ground loop
Brine s ide
INSIDE OF UNIT -FACTORY INSTALLED
PRESSURE
GA
UGE
SAFETY
VALVE
BLOW
OFF
flow
switch
drain
FILTER
outdoor
outdoor
PUMP

14.4 Piping diagram

14.4.1 Piping diagram: Indoor unit

Installer reference guide
70
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
Page 71
14 Technical data
A10P
A1P
K1M K2M
K5M
TR1
Q1L
X5M
X7M
X2M
F1B
X1M
X6Y
A9P
A8P
A4P
K6M
L3R
L2R
L1R

14.5 Wiring diagram

14.5.1 Wiring diagram: Indoor unit

See the internal wiring diagram supplied with the unit (on the inside of the indoor unit switch box cover). The abbreviations used are listed below.
Position in switch box
User installed options:
Remote user interface
External indoor thermistor
Digital I/O PCB
Demand PCB
Brine pressure switch connection kit
Main leaving water temperature:
On/OFF thermostat (wired)
On/OFF thermostat (wireless)
External thermistor on On/OFF thermostat (wireless)
Heat pump convector
Additional leaving water temperature:
On/OFF thermostat (wired)
On/OFF thermostat (wireless)
External thermistor on On/OFF thermostat (wireless)
Heat pump convector
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
71
Page 72
14 Technical data
B1L
A4P
SS1
ON
OFF
A8P
1 2 X801M3 4 5
DS1
ON
OFF
1 2 3 4
3 X5M4 7 8 9 10
1 2
A2P
1 2 X5M
P1
P1
P2
P2
A2P
L N
X2M
21 28 29
X1 X2 YC Y2Y1
A1P
5 6 X5M
X6A:1
2
2
R3T
-t°
2
X5A:1
2
R2T
-t°
X8A:1
X7A:1
R4T
-t°
X9A:1
2
R5T
-t°
5 6
4
3
2
X40A:1
10 11 129876543
5
6
4
3
X33A:1
3
2
X4A:1
4
8
7
2
X80A:1
CN2:1
2 3 4 5 6
CN1:1 3
F2U
F1U
S1S
S2S
S3S
S6S
S7S
S8S
S9S
R1T
-t°
R1T
-t°
R1T
-t°
KCR
KHURKHR
2
R6T
-t°
6
5
4
32X85A:1
2
X18A:1
2
X22A:1
X2M.7
X2M.3
4D081377-1A_page 4
ext. indoor ambient sensor option
Demand PCB
User interface
Remote user interface
Ext. heat source (*)
Alarm output(*)
Space C/H On/OFF output(*)
Options: boiler output, alarm output, On/OFF output
Only for demand PCB option
Only for digital I/O PCB option
Digital I/O PCB
Electric pulse meter inputs: 5 V DC pulse detection (voltage supplied by PCB)
Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB)
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage supplied by PCB)
Switch box
Switch box
(*) Max. load
0.3 A - 250 V AC Min. load 20 mA - 5 V DC
Installer reference guide
72
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 73
14 Technical data
A1P
PE
N
L
GND
PWM
NL
1
X2M
3130
1
X2M
30 31
5 6 7
3
3
X2M
34
X2M
35
COM
HC
H
COM
C LPCN
5 6
5
5
65
A3P
X11M
X1M
A3P
A4P
A3P
2129
X2M
NC
N
COM
HC
H
COM
C LPCN
6
6
6
A3P
X11M
X1M
A3P
A4P
A3P
3 4
2a
1a
2
1
%H20 %H20
X2M
R1HR1H
NO
BLK
BLU
BRN
5
6
5
4
32
X25A:1
X16A:5
1
3
X17A:1 3 5 7
X24A:1 3 5 7
Q2DI
1
X1A:3
X19A:1
3 5
X6YA X6Y
X6YB
X6YA
X6Y
X6YB
FU1
X26A:1
2 X31A:1 3
TR1
3
X3A:1
X20A:1
3
5
X2A:1
KCR
M2P
M
1~
X15A:1
3
E
R1T
-t°
R1T
-t°
R2T
-t°
A1
A2
K5M
KPR
FU2
X11A:3
1
X12A:3
1
K2R
M3S
KVR
R1T
-t°
R1T
-t°
R2T
-t°
K6R
3
5
31
32
Q1L
11
12
M2S
M2S
A1
A2
K1M
A1
A2
K2M
X28A:1
2
K1R
M1P
MS
X2M.4
X2M.3
X2M.28
X2M.28
X2M.3
X2M.1
X2M.2
X2M.2
X2M.4
X2M.1
X2M.4
X2M.1a
X2M.2a
X2M.3
X2M.2a
X2M.4
X2M.1a
X2M.4
X2M.4
X2M.1a
X2M.4
X2M.5
X2M.7
X2M.7
L5R
L5R
A9P.X803A.3
A9P.X803A.5
A9P.X803A.3
A9P.X803A.5
X2M.21
X2M.1
X2M.3
4D081377-1A_page 5
only for wireless On/OFF thermostat
only for ext. sensor(floor or ambient)
Heatpump convector
Main LWT zone
Heatpump convector
Add LWT zone
NC valve
NO valve
Shut-off valve
Switch box
3 wire type (SPDT)
DHW pump
only for wired On/OFF thermostat
only for wired On/OFF thermostat
only for wireless On/OFF thermostat
only for ext. sensor(floor or ambient)
1N~, 50 Hz 230 V AC Normal kWh rate power supply
Only for normal power supply (standard)
Only for preferential kWh rate power supply
DHW pump output Max. load: 2 A (inrush) - 230 V AC 1 A (continuous)
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
73
Page 74
14 Technical data
HAP
Z1F Z2F
Z2C N=2
Z4F
Z1C N=1
Z5C N=3
Z3F
V2R
V1R
Z3C N=6
PS
ON OFF
DS1
1
2 3
DS1
1 2
ON OFF
HAP
H1P
H2P
H3P
H4P
H5P
H6P
H7P
BS1
BS2
BS3
BS4
NL1
3N~, 50 Hz 400 V AC
L1
L2 L3
L2 L3 N
X1M
A9P
GRN/YEL
RED WHT BLK BLU
B1PH
WHT
BLK
RED
A10P
11
12
X5M
1 2
Z4C N=2
Z6C N=1
1
3
4
WHT
RED
BLK
RED
WHT
BLK
2 3 321 875 94 6 4 5
6
7
7
1 2
X7M
21 3 4
L1A L2A L3A NA
F1U F2U
L11A L21A L31A
L11B L21B L31B
L1R L2R L3R
X8A:1 753
F3U
F6U
X803A:1 3
5
E1 E
X4A:1
2 3 4 5
L12A L22A L32A
C2C1
M1C
MS
3~
VU W
R1
X103A:1 3 7
K84R
X104A:1 2 3 5
X11A:1
3
X12A:1
2 3 5 64 7 8
X13A:1
2
Q1DI
R2T
-t°
R3T
-t°
R4T
-t°
R5T
-t°
R6T
-t°
K1E
M
X21A:1 2 3 4 5 6
F4U
X32A:1
2
S1PH
P>
X111A:1
2
R10T
-t°
F5U
X28A:1 3
K4R
X18A:1 2 3 4
X17A:1 2 3 4
S1L
R1T
-t°
1 2
K5M
345
6
1 2
K2M
345
6
345
6
1
2
3
456
F1B
II I
E2H
E2H E2H
E1H E1H E1H
X7Y
L5R
1
5
K6M
X77A:1 3
1 2
K1M
Z5F
C3 C4
M3P
M
1~
4
5
X2H X1H X2H
S1L
X1Y
S1P
P<
A1P.X19A.1
A1P.X19A.3
A1P.X19A.5
/ F1B.2 / F1B.4 / F1B.6
X1M.L1
X1M.L2
X1M.L3
4D081377-1A_page 6
Only for brine pressure switch connection kit
5 V DC / 0,05 mA detection (voltage supplied by PCB)
Switch box
Switch box
outdoor ambient sensor
Backup heater as 3 kW / 9 kW
Switch box
Switch box
Switch box
A1P Main PCB (hydrobox)
A2P User interface PCB
A3P * On/OFF thermostat
A3P * Heat pump convector
A4P * Digital I/O PCB
A4P * Receiver PCB (Wireless On/OFF
A8P * Demand PCB
A9P Main PCB (refrigerant, brine)
A10P Main PCB (inverter)
B1L Flow sensor
B1PH High pressure sensor
BS1~BS4 Push button
thermostat, PC=power circuit)
C1~C4 Capacitor
CN* (A4P) * Connector
DS1 (A8P) * DIP switch
DS1 (A9P) DIP switch
DS1 (A10P) DIP switch
E1H Backup heater element (1kW)
E2H Backup heater element (2kW)
F1B Overcurrent fuse backup heater
F1U, F2U (A4P) * Fuse 5A 250V
F1U, F2U (A9P) Fuse 35.5A 500V
F3U~F6U (A9P) Fuse T, 6.3A 250V
FU1 (A1P) Fuse T, 6.3A 250V
H1P~H7P LED
Installer reference guide
74
HAP LED
K1E Electronic expansion valve
K1M, K2M Contactor backup heater
K5M Safety contactor backup heater
K6M Relay
K*R Relay on PCB
L1R~L3R Reactor
L5R Reactor transmission line
M1C Motor (compressor)
M1P Main water supply pump
M2P # Domestic hot water pump
M3P Brine supply pump
M2S # Shut-off valve
M3S 3-way valve for floor heating/domestic hot
PS Switching power supply
water
Q*DI # Earth leakage circuit breaker
Q1L Thermal protector backup heater
R1 Resistor
R1T (A1P) Outlet water heat temperature sensor
R1T (A2P) Ambient sensor user interface
R1T (A3P) * Ambient sensor On/OFF thermostat
R1T (A9P) Ambient air sensor
R2T (A1P) After backup heater temperature sensor
R2T (A3P) * External sensor (floor or ambient)
R2T (A9P) Discharge sensor
(leaving water condenser)
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
EGSQH10S18AA9W
Page 75
R3T (A1P) Refrigerant liquid side thermistor
15
**
/12.2
1
R3T (A9P) Suction sensor
R4T (A1P) Inlet water temperature sensor (entering
water condenser)
R4T (A9P) 2-phase sensor (Tx)
R5T (A1P) Domestic hot water tank temperature sensor
R5T (A9P) Brine entering water
R6T (A1P) * External indoor ambient thermistor
R6T (A9P) Brine leaving water
R10T Heat sink thermistor
R1H (A3P) * Humidity sensor
S1L Brine flow switch
S1P # Water pressure switch brine side
S1PH High pressure switch
S1S # Preferential kWh rate power supply contact
S2S # Electrical meter pulse input 1
S3S # Electrical meter pulse input 2
S6S~S9S # Digital power limitation inputs
SS1 (A4P) * Selector switch
TR1 Power supply transformer
V1R, V2R Insulate gate bipolar transistor power
module
X*H Backup heater connector
X*M Terminal strip
X*Y Connector
Z1C~Z6C Noise filter (ferrit core)
Z1F~Z5F Noise filter
* = Optional
# = Field supply
14 Technical data
Notes to go through before starting the unit
English Translation
X1M Main terminal
X2M Field wiring terminal for AC
X5M Field wiring terminal for DC
Earth wiring
Field supply
Wire number 15
Connection ** continues on page 12 column 2
Several wiring possibilities
Option
Not mounted in switch box
Wiring depending on model
PCB
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
75
Page 76
14 Technical data
1 2
X5M
A2P
P1P2 P1P2
5 6
X5M
7 8 9
10
21
34
X2M
35
5X2M 6 7
A2P
X5M
X1M
3 4
X5M
1
5X2M 6 7
1 2 X2M4
C H
A3P
5
H C
A4P
L N PC
A3P
X1M
5
5 6
A3P
X11M
5
1a 2a
X2M3 4
C H
A3P
6
5 6
A3P
X11M
6
1 X2M4
1a
X2M4
4
3 X2M21
A1P
A8P
1 2X801M 3 4 5
DS1 ON OFF
1 2 3 4
X1 X2
A4P
YC
SS1
ON OFF
Y2Y1
X2M
21 28
29
3
%H20
A3P
6
H C
A4P
L N PC
X1M
1a 2a X2M3 4
%H20
H C
CH
CH
H C
3 4
11
12
X5M
21
L N
R1H
R1H
X5M
3
3
L1 L2 L3 N
30 31
X2M
A1P
X1M
1
L1 L2 L3 N
30 31
X2M
A1P
NL
L1 L2 L3 N
3N~, 50 Hz 400 V AC
L1 L2 L3 N 3N~, 50 Hz
400 V AC
1N~, 50 Hz 230 V AC; 6,3 A
1 2
X7M
A9P
A9P
7
7
1
234
S2S
R6T
-t°
S3S
M2P
M
1~
M2S
M2S
R1T
-t°
R2T
-t°
R1T
-t°
R1T
-t°
X85A:1 2 3
4 5 6
X33A:1 2 3
4 5 6
X80A:1
2 3 4 5 6 7 8 9 10 11 12
CN2:1
2 3 4 5 6 3CN1:1
KCR
KHURKHR
F1U
F2U
S6S
S7S
S8S
S9S
R2T
-t°
R1T
-t°
S1S
R1T
-t°
Q1DI
X6Y
X6YA
X6YB
1 53X1A:3 X19A:1
Q1DI
X6YA
1 53X1A:3 X19A:1
X6Y X6YB
Q2DI
S1L
S1L
X18A:1
2 3 4
X18A:1
2 3 4
-X1Y
S1P
P<
(4)
(2)
(5)
Option PCBs
(1)
(6)
(7)
(8)
COMCOM
COM COM
(3)
User interface
Only for Remote user interface option
Field supplied options
Shut-off valve Electrical meters
Main power connection
Normally closed
5 V DC pulse detection (voltage supplied by PCB)
DHW pump output Max. load: 2 A (inrush) ­230 V AC 1A (continuous)
External room thermostats and heat pump convector
only for heat pump convector
Switch box
(*) Max. load:
0.3 A - 250 V AC Min. load: 20 mA - 5 V DC
Options: boiler output, alarm output, On/OFF output
Alarm output (*)
Space heating On/OFF output (*)
User interface
Outdoor ambient sensor
Ext. heat source (*)
Option external indoor ambient sensor
Switch box
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage supplied by PCB)
Only for digital I/O PCB option
Switch box
Switch box
Switch box
Only for brine pressure switch connection kit
Main LWT zone
only for wired thermostat
only for wireless thermostat
Additional LWT zone
only for wired thermostat
only for external sensor (floor/ambient)
only for wireless thermostat
only for external sensor (floor/ ambient)
Option for brine pressure switch connection kit
Only for normal power supply (standard)
Preferential kWh rate power supply contact: 16 V DC detection (voltage supplied by PCB)
Normal kWh rate power supply
Switch box
Switch box
Only for demand PCB option
only for heat pump convector
Switch box
Switch box
230 V AC supplied by PCB
230 V AC supplied by PCB
5 V DC / 0,05 mA
detection (voltage
supplied by PCB)
Only for preferential kWh rate power supply Use normal kWh rate power supply for hydro PCB
Normally open
Switch box
DHW pump
4P355433-1A_page 4
Installer reference guide
76
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
EGSQH10S18AA9W
Page 77
Electrical meter specification
▪ Pulse meter type / voltage free contact for 5VDC detection by
PCB
▪ Possible number of pulse:
▪ 0.1 pulse/kWh
▪ 1 pulse/kWh
▪ 10 pulse/kWh
▪ 100 pulse/kWh
▪ 1000 pulse/kWh
▪ Pulse duration
▪ minimum On time 40ms
▪ minimum OFF time 100ms
▪ Measurement type (depending on installation):
▪ single phase AC meter
▪ three phase AC meter (balanced loads)
▪ three phase AC meter (unbalanced loads)
Electrical meter installation guideline
▪ General: it is the responsability of the installer to cover the
complete power consumption with electrical meters (combination of estimation and metering is not allowed)
▪ Required number of electrical meters:
14 Technical data
Electrical meter type Regular kWh rate power
supply
1~
3~ balanced 1
3~ unbalanced
Electrical meter type Benefit kWh rate power supply
1~ 1
3~ balanced 1
3~ unbalanced
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
77
Page 78
14 Technical data
A4P: Y1 X2M: 29
A4P: X1-X2
X5M: 3-4
X5M: 11-12
2x0.75
A8P: X801M: 1-5
A8P: X801M: 2-5
A8P: X801M: 3-5
A8P: X801M: 4-5
230 V
X2M: 34-35
X5M: 7-8
X5M: 9-10
X7M : 1 - 2
230 V
230 V
230 V
230 V
X5M: 5-6
230 V
230 V
230 V
230 V
A3P: X1M: com-H
A4P: X1M: H-com X2M: L-N
A3P: X1M: 1-3
X11M: 5-6
X5M: 1-2
2x0.75
230 V
230 V
230 V
2x0.75
2
2
2
1
1
A4P: Y2 X2M: 29
4D081378-1A
Only for normal power supply installation
unit power supply: 400 V + earth
normal kWh rate power supply for indoor unit: 230 V + earth
Preferential kWh rate power supply contact
unit preferential kWh rate power supply: 400 V + earth
Only for preferential kWh rate power supply installation
Power supply
Alarm output
Changeover to
ext. heat source output
X2M: 30-31-earth
X1M: L1-L2-L3-N-earth
2 core
3 core
5 core
5 core
Only for *KRP1HB*
Only for *KGSCONBP1
Field supply
Field supply
External room thermostat / Heat pump convector
2 core signal
2 core
Space heating
On/OFF output
Space heating On/OFF output
Ext. heat source (eg boiler)
alarm indication
Electricity meter pulse input 2
Electricity meter pulse input 1
Circulation pump for DHW
main zone shut off valve
NO valve: X2M: 6-7
Only for KRCS01-1
signal
2 core
2 core
signal
Shut off valve
2 core
2 core
2 core
2 core
signal
Optional part
Optional part
- In case of signal cable: keep minimum distance to power cables > 5 cm
Note:
main: X2M: 1-4
add: X2M: 1a-4
main: X2M: 1-3-4 add: X2M: 1a-3-4
main: X2M: 1-4
add: X2M: 1a-4
2 core
2 core
2 core
2 core
Power limitation demand input 4
Power limitation demand input 3
Power limitation demand input 2
Power limitation demand input 1
Only for *KRP1AHTA
Only for *KRUCBL*
A2P: P1-P2 user interface
A2P: P1-P2 user interface
R2T External sensor (floor or ambient)
(main and/or additional zone)
4 core
2 core
2 core
communication
communication
In case user interface is relocated
Only for (heat pump convector)
Only for *KRTR (wireless room thermostat)
Only for *KRTW (wired room thermostat)
Only for *KRTETS
2 core (3m included)
signal
2 core
2 core
Outdoor ambient sensor *KRSCA1
Indoor unit
Standard parts
Field supply
Pressure swith within brine side
Signal
2 core
External indoor ambient thermistor
2 core
Installer reference guide
78
Daikin Altherma ground source heat pump
4P351748-1C – 2015.10
EGSQH10S18AA9W
Page 79

14.6 Technical specifications

14.6.1 Technical specifications: Indoor unit

Nominal capacity and nominal input
14 Technical data
Indoor unit Heating only
Condition 1
(a)
Heating capacity Minimum 3.11kW
Nominal 10.20kW
Maximum 13.00kW
Power input Nominal 2.34kW
COP Nominal 4.35
Condition 2
(b)
Heating capacity Minimum 2.47kW
Nominal 9.29kW
Maximum 11.90kW
Power input Nominal 2.82kW
COP Nominal 3.29
(a) Entering water temperature (brine)/leaving water temperature (brine) 0°C/3°C – leaving water condenser 35°C (DT=5°C). (b) Entering water temperature (brine)/leaving water temperature (brine) 0°C/3°C – leaving water condenser 45°C (DT=5°C).
Technical specifications
Indoor unit Heating only
Casing
Colour White
Material Precoated sheet metal
Dimensions
Packing (H×W×D) 1930×700×840mm³
Unit (H×W×D) 1732×600×728mm³
Weight
Machine weight 210kg
Gross weight 222kg
Packing
Material Wood, carton, PE wrapping foil
Weight 12kg
PED
Category of unit CategoryI
Most critical part Compressor
Ps*V 135bar
Ps*DN
Main components
Water pump Type DC motor
Nr. of speeds Inverter controlled
Nominal ESP pump
Heating
Heating
(a)
(b)
39kPa
46kPa
Power Input 70W
Water side heat exchanger Type Brazed plated
Quantity 1
Water volume 2.30l
Minimum water flow rate 8.0l/min
Nominal water flow rate
Maximum water
(a)
Heating
Heating
(b)
29.2l/min
26.6l/min
Heating 43.0l/min
flow rate
Insulation material Green felt
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
79
Page 80
14 Technical data
Indoor unit Heating only
Water expansion vessel Volume 10l
Maximum water pressure 3bar
Pre-pressure 1bar
Maximum height above unit 1m
Water filter Diameter perforations 1.0mm
Material Copper + brass + stainless steel
Brine pump Type DC motor
Nr. of speeds 3
Nominal ESP pump
Power Input 140W
Brine heat exchanger Type Brazed plated
Quantity 1
Brine volume 2.30l
Minimum brine flow rate 25.0l/min
Nominal brine flow rate
Maximum brine flow rate
Insulation material
Brine expansion vessel Volume 10l
Maximum brine pressure 3bar
Pre-pressure 1bar
Maximum height above unit 12m
Brine filter Diameter perforations 1.0mm
Material Copper + brass + stainless steel
Tank Water volume 180l
Material Stainless steel (EN1.4521)
Maximum water temperature 60°C
Maximum water pressure 10bar
Insulation material Polyester
Corrosion protection Anode
Heat loss
(d)
Heat exchanger (tank) Quantity 1
Material Stainless steel (EN1.4521)
Surface 1.9m
Internal coil volume 8.9l
3‑way valve (tank) Flow factor space heating/tank
heating
Safety devices
Devices Thermal cut‑out / High pressure switch
Water circuit space heating side
Piping connections Ø 22mm
Safety valve 3bar
Manometer Yes
Drain valve/fill valve Yes
Shut-off valves
Air purge valve Yes
Total water volume
(e)
Minimum water volume 20.0l
Water circuit domestic hot water side
Piping connections Cold water in/hot water out Ø 22mm
Recirculation connection G1/2" female
Brine circuit
Piping connections Ø 28mm
(c)
Heating
Heating
(c)
58kPa
40.0l/min
Heating 54.0l/min
1.4kWh/24h
2
13/8m3/h
23.0l
Installer reference guide
80
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 81
14 Technical data
Indoor unit Heating only
Safety valve 3bar
Manometer Yes
Drain valve/fill valve Yes
Shut-off valves
Air purge valve
Total volume
Minimum brine volume 20.0l
Compressor
Type Hermetically sealed swing compressor
Model 2YC63PXD#C
Starting method Inverter driven
Operation range
Installation space 5~30°C
Brine side –5~20°C
Water side Heating 24~60°C
Sound power level
Nominal 46dBA
Sound pressure level
Nominal 32dBA
Refrigerant
Type R410A
Charge 1.8kg
Control Electronic expansion valve
Nr. of circuits 1
Capacity control method Inverter controlled
Electrical specifications
(e)
Domestic hot water 25~55°C
(a) Entering water temperature (brine)/leaving water temperature (brine) 0°C/3°C – leaving water condenser 35°C (DT=5°C). (b) Entering water temperature (brine)/leaving water temperature (brine) 0°C/3°C – leaving water condenser 45°C (DT=5°C). (c) With 40% propylene glycol. (d) Heat loss according to EN12897 (e) Including piping + plate heat exchanger + backup heater; excluding expansion vessel.
(f) By heat pump. (g) By heat pump + backup heater. (h) By backup heater.
(i) The sound pressure level is measured via a microphone at a 1m distance from the unit. It is a relative value, depending on the distance and
acoustic environment.
8.0l
(f)
/ 24~65°C
(f)
/ 25~60°C
(i)
(g)
(h)
Voltage range
Minimum –10%
Maximum 10%
Wiring connections
Electric meter Quantity of wires 2
Type of wires Minimum 0.75mm2 (5VDC pulse detection)
Preferential kWh rate power supply Quantity of wires Power: 2
Type of wires Power: 6.3A
Power limitation Quantity of wires 5
Type of wires Minimum 0.75mm2 (5VDC pulse detection)
Domestic hot water pump Quantity of wires 2
Type of wires Minimum 0.75mm2 (2A inrush, 1A
continuous)
For connection with outdoor ambient sensor R1T Quantity of wires 2
Type of wires Minimum 0.75mm
For connection with R6T Quantity of wires 2
Type of wires Minimum 0.75mm
For connection with A3P Quantity of wires Note
Type of wires Note
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
(a)
and Note
(a)
2
2
(b)
(c)
Installer reference guide
81
Page 82
14 Technical data
25
20
15
5
10
0
–5
–10
0 10 20 30 40 50 70
4D083081-1A
A (°C)
B (°C)
60
For connection with M2S Quantity of wires 3G
Type of wires Note
(a)
and Note
For connection with user interface Quantity of wires 2
Type of wires 0.75~1.25mm (maximum length 500m)
For connection with optional FWXV (demand input and output)
(a) Select diameter and type according to national and local regulations. (b) Depends on the type of thermostat. See the installation manual of the thermostat. (c) Voltage: 230V / maximum current: 100mA / minimum 0.75mm
Quantity of wires 4
Type of wires Minimum 0.75mm2 (100mA)
2

14.7 Operation range

14.7.1 Operation range: Indoor unit

Space heating
(c)
A Entering brine temperature B Leaving condenser water temperature
Remark: By default settings, the unit will allow operation with
entering brine temperatures to –5°C. As a result, the brine freezing temperature may not be higher than –15°C. For water – ethanol mixtures this corresponds to 29% ethanol (by mass), for water – propylene glycol mixtures this corresponds to 40% propylene glycol (by volume).
If the freezing temperature of the medium is higher than –15°C, then protection level of unit MUST be increased by field setting.
Refer to the installation manual and/or installer reference guide for instructions how to set a different freeze temperature of the medium (Tf) in the controller.
The unit will NOT operate at an entering brine temperature lower than Tf+10K.
Installer reference guide
82
Only backup heater operation if the set point is <24°C. Heat pump operation (assisted by backup heater if capacity shortage) Heat pump + backup heater operation Protect against freezing by adding anti-freeze to brine side. See also remark.
Tf=changeable between 0°C and –15°C.
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 83
Domestic hot water
25
20
15
5
10
0
–5
–10
0 10 20 30 40
4D083082-1B
A (°C)
B (°C)
60 7050
14 Technical data
A Entering brine temperature B Leaving condenser water temperature
Only backup heater operation. Heat pump operation Protect against freezing by adding anti-freeze to brine side. See also remark.
Remark: By default settings, the unit will allow operation with entering brine temperatures to –5°C. As a result, the brine freezing temperature may not be higher than –15°C! For water – ethanol mixtures this corresponds to 29% ethanol (by mass), for water – propylene glycol mixtures this corresponds to 40% propylene glycol (by volume).
If the freezing temperature of the medium is higher than –15°C, then protection level of unit MUST be increased by field setting.
Refer to the installation manual and/or installer reference guide for instructions how to set a different freeze temperature of the medium (Tf) in the controller.
The unit will NOT operate at an entering brine temperature lower than Tf+10K.
Tf = changeable between 0°C and –15°C.
EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
83
Page 84
14 Technical data
80
70
60
50
40
30
20
10
0
0
8
10 20 30 40 50
A (kPa) C (kPa)
B (l/min) B (l/min)
25
100
90
80
70
60
50
40
30
20
10
0
30 35 40 45 50 55 60 65
3D081379-1B

14.8 ESP curve

14.8.1 ESP curve: Indoor unit

A External static pressure (space heating side) B Water flow rate C External static pressure (brine side)
Water Mixture water/propylene glycol (40V%) at entering brine temperature –5°C Mixture water/ethanol (29M%) at entering brine temperature –5°C
Note: Selecting a flow outside the area of operation can cause damage or malfunction of the unit.
Installer reference guide
84
Daikin Altherma ground source heat pump
EGSQH10S18AA9W
4P351748-1C – 2015.10
Page 85
15 Glossary
Dealer
Sales distributor for the product.
Authorized installer
Technical skilled person who is qualified to install the product.
User
Person who is owner of the product and/or operates the product.
Applicable legislation
All international, European, national and local directives, laws, regulations and/or codes that are relevant and applicable for a certain product or domain.
Service company
Qualified company which can perform or coordinate the required service to the product.
Installation manual
Instruction manual specified for a certain product or application, explaining how to install, configure and maintain it.
Operation manual
Instruction manual specified for a certain product or application, explaining how to operate it.
Accessories
Labels, manuals, information sheets and equipment that are delivered with the product and that need to be installed according to the instructions in the accompanying documentation.
Optional equipment
Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Field supply
Equipment not made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.

15 Glossary

EGSQH10S18AA9W Daikin Altherma ground source heat pump 4P351748-1C – 2015.10
Installer reference guide
85
Page 86
1/7
Field settings table
[6.8.2] = .... ID4302/4562
Applicable indoor units
*GSQH10S18AA9W ThermaliaC12*
Notes
-
4P359382-1D - 2015.02
Page 87
2/7
Breadcrumb Field code Range, step
Default valu
e
Date Value
User settings
└─ Preset values
└─ Room temperature
7.4.1.1 R/W [3-07]~[3-06], step: A.3.2.4
21°C
7.4.1.2 R/W [3-07]~[3-06], step: A.3.2.4
19°C
└─ LWT main
7.4.2.1 [8-09] R/W
[9-01]~[9-00], step: 1°C
55°C
7.4.2.2 [8-0A] R/W
[9-01]~[9-00], step: 1°C
45°C
7.4.2.5 R/W -10~10°C, step: 1°C
0°C
7.4.2.6 R/W -10~10°C, step: 1°C
-2°C
└─ Tank temperature
7.4.3.1 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
7.4.3.2 [6-0B] R/W
30~min(50,[6-0E])°C, step: 1°C
45°C
7.4.3.3 [6-0C] R/W
30~min(50,[6-0E])°C, step: 1°C
45°C
└─ Set weather dependent
└─ Main
7.7.1.1 [1-00] Set weather-dependent heating Low ambient temp. for LWT main zone heating WD curve.
R/W
-40~5°C, step: 1°C
-20°C
7.7.1.1 [1-01] Set weather-dependent heating High ambient temp. for LWT main zone heating WD curve.
R/W 10~25°C, step: 1°C
15°C
7.7.1.1 [1-02] Set weather-dependent heating Leaving water value for low ambient temp. for LWT main zone heating WD curve.
R/W
[9-01]~[9-00]°C, step: 1°C
60°C
7.7.1.1 [1-03] Set weather-dependent heating Leaving water value for high ambient temp. for LWT main zone heating WD curve.
R/W [9-01]~min(45,[9-00])°C, step: 1°C
25°C
└─ Additional
7.7.2.1 [0-00] Set weather-dependent heating Leaving water value for high ambient temp. for LWT add zone heating WD curve.
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
7.7.2.1 [0-01] Set weather-dependent heating Leaving water value for low ambient temp. for LWT add zone heating WD curve.
R/W [9-05]~[9-06]°C, step: 1°C
60°C
7.7.2.1 [0-02] Set weather-dependent heating High ambient temp. for LWT add zone heating WD curve.
R/W 10~25°C, step: 1°C
15°C
7.7.2.1 [0-03] Set weather-dependent heating Low ambient temp. for LWT add zone heating WD curve.
R/W
-40~5°C, step: 1°C
-20°C
Installer settings
└─ System layout
└─ Standard
A.2.1.1 [E-00] R/O
0~5
5: Ground sourc
e
A.2.1.2 [E-01] R/O
1: 16
A.2.1.3 [E-02] R/O
1: T
yp
e 2
A.2.1.5 [5-0D] R/O
4: 3PN,
(
1/2
)
A.2.1.6 [D-01] R/W
0: No
1: Active open 2: Active closed
A.2.1.7 [C-07] R/W
0: LWT control
1: Ext RT control 2: RT control
A.2.1.8 [7-02] R/W
0: 1 LWT zone
1: 2 LWT zones
A.2.1.9 [F-0D] R/W 0: Continuous
1: Sample (only possible if [C-07] = 0) 2: Re
q
uest(only possible if [C-07] 0
)
A.2.1.A [E-04] R/O
0: No
A.2.1.B R/W 0: At unit
1: In room
└─ Options
A.2.2.4 [C-05] R/W
1: Thermo ON/OFF
2: C/H re
q
uest
A.2.2.5 [C-06] R/W
1: Thermo ON/OFF
2: C/H re
q
uest
A.2.2.6.1 [C-02] Digital I/O PCB Ext. backup heat src R/W
0: No
1: Bivalent 2: ­3: -
A.2.2.6.2 [D-07] Digital I/O PCB Solar kit R/O
0: No
(#)
A.2.2.6.3 [C-09] Digital I/O PCB Alarm output R/W
0: Normally open
1: Normall
y
closed
A.2.2.7 [D-04] R/W
0: No
1: Pwr consm
p
ctrl
A.2.2.8 [D-08] R/W
0 (No): NOT installed
1: Installed (0.1 pulse/kWh) 2: Installed (1 pulse/kWh) 3: Installed (10 pulse/kWh) 4: Installed (100 pulse/kWh) 5: Installed
(
1000 pulse/kWh
)
A.2.2.9 [D-09] R/W
0 (No): NOT installed
1: Installed (0.1 pulse/kWh) 2: Installed (1 pulse/kWh) 3: Installed (10 pulse/kWh) 4: Installed (100 pulse/kWh) 5: Installed
(
1000 pulse/kWh
)
A.2.2.A [D-02] R/W
0: No
1: Secondary rtrn 2: Disinf. Shunt
A.2.2.B [C-08] R/W
0: No
1: Outdoor sensor (##) 2: Room sensor
A.2.2.D [E-0B] Bi-zone kit Is a bi-zone kit installed? R/O
0: No
(#)
└─ Capacities
A.2.3.2 [6-03] R/W 0~10 kW, step: 0,2 kW
3 kW
A.2.3.3 [6-04] R/W
0~10 kW, step: 0,2 kW
3 kW
Space operation
└─ LWT settings
└────────────────── Main
DHW pump
External sensor
BUH: step 1
BUH: step 2
User interface location
Contact type main
Contact type add.
Demand PCB
External kWh meter 1
External kWh meter 2
BUH type Preferential kWh rate
Unit control method
Number of LWT zones
Pump operation mode
Power saving possible
Field settings table
Installer setting at variance with default value
Comfort (heating)
Eco (heating)
Comfort (heating)
Eco (heating)
Setting name
Comfort (heating)
Eco (heating)
Storage comfort
Storage eco
Reheat
Unit type
Compressor type Indoor software type
4P359382-1D - 2015.02
(#) Setting is not applicable for this unit. Do not change the default value.
(##) Setting is not applicable for this unit.
*GSQH10S18AA9W / ThermaliaC12*
Page 88
3/7
Breadcrumb Field code Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
Setting name
A.3.1.1.1 R/W 0: Fixed
1: Weather dep.
2: Fixed / scheduled 3: WD / scheduled
A.3.1.1.2.1 [9-01] Temperature range Minimum temp (heating) R/W
15~37°C, step: 1°C
24°C
A.3.1.1.2.2 [9-00] Temperature range Maximum temp (heating) R/W
37~65°C, step: 1°C
65°C
A.3.1.1.5 [8-05] R/W
0: No
1: Yes
A.3.1.1.6.1 [F-0B] Shut-off valve Thermo On/OFF R/W
0: No
1: Yes
A.3.1.1.7 [9-0B] R/W
0: Quick
1: Slow
└────────────────── Additional
A.3.1.2.1 R/W 0: Fixed
1: Weather dep.
2: Fixed / scheduled 3: WD / scheduled
A.3.1.2.2.1 [9-05] Temperature range Minimum temp (heating) R/W
15~37°C, step: 1°C
24°C
A.3.1.2.2.2 [9-06] Temperature range Maximum temp (heating) R/W
37~65°C, step: 1°C
65°C
└────────────────── Delta T source
A.3.1.3.1 [9-09] R/W
3~10°C, step: 1°C
8°C
└─ Room thermostat
A.3.2.1.1 [3-07] Room temp. range Minimum temp (heating) R/W 12~18°C, step: A.3.2.4
12°C
A.3.2.1.2 [3-06] Room temp. range Maximum temp (heating) R/W 18~30°C, step: A.3.2.4
30°C
A.3.2.2 [2-0A] R/W -5~5°C, step: 0,5°C
0°C
A.3.2.3 [2-09] R/W -5~5°C, step: 0,5°C
0°C
A.3.2.4 R/W
0: 1°C
1: 0,5°C
└─ Operation range
A.3.3.1 [4-02] R/W 14~35°C, step: 1°C
35°C
└─ Domestic hot water (DHW)
└─ Type
A.4.1 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
└─ Disinfection
A.4.4.1 [2-01] R/W 0: No
1: Yes
A.4.4.2 [2-00] R/W 0: Each day
1: Monday 2: Tuesday 3: Wednesday 4: Thursday
5: Friday
6: Saturday 7: Sunda
y
A.4.4.3 [2-02] R/W 0~23 hour, step: 1 hour
23
A.4.4.4 [2-03] R/W
60°C
A.4.4.5 [2-04] R/W 40~60 min, step: 5 min
40 min
└─ Maximum setpoint
A.4.5 [6-0E] R/W 40~60°C, step: 1°C
60°C
└─ SP mode
A.4.6 R/W
0: Fixed
1: Weather de
p
.
└─ Weather dependent curve
A.4.7 [0-0B] Weather-dependent curve DHW setpoint for high ambient temp. for DHW
WD curve.
R/W
35~[6-0E]°C, step: 1°C
45°C
A.4.7 [0-0C] Weather-dependent curve DHW setpoint for low ambient temp. for DHW
WD curve.
R/W
45~[6-0E]°C, step: 1°C
60°C
A.4.7 [0-0D] Weather-dependent curve High ambient temp. for DHW WD curve. R/W 10~25°C, step: 1°C
15°C
A.4.7 [0-0E] Weather-dependent curve Low ambient temp. for DHW WD curve. R/W
-40~5°C, step: 1°C
-20°C
└─ Heat sources
└─ Backup heater
A.5.1.1 [4-00] R/W 0: Disabled
1: Enabled
2: Onl
y
DHW
A.5.1.2 R/W
0: Manual
1: Automatic
A.5.1.3 [4-07] R/W 0: No
1: Yes
A.5.1.4 [5-01] R/W
-15~35°C, step: 1°C
0°C
└─ System operation
└─ Auto restart
A.6.1 [3-00] R/W 0: No
1: Yes
└─ Preferential kWh rate
A.6.2.1 [D-00] R/O 0: None A.6.2.2 [D-05] R/W 0: Forced off
1: As normal
└─ Pwr consumpt. Control
A.6.3.1 [4-08] R/W
0: No limitation
1: Continuous 2: Di
g
ital inputs
A.6.3.2 [4-09] R/W 0: Current
1: Powe
r
A.6.3.3 [5-05] R/W 0~50 A, step: 1 A
50
A
A.6.3.4 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
Allowed heaters Forced pump OFF
kW value
Operation mode
Emergency
Enable BUH step 2
Equilibrium temp.
Emitter type
LWT setpoint mode
Room temp. offset
Ext. room sensor offset
Operation day
Start time
Temperature target Duration
LWT setpoint mode
Modulated LWT
Heating
Mode
Type
Amp. value
Room temp. step
Space heating OFF temp
Disinfection
(#) Setting is not applicable for this unit. Do not change the default value. (##) Setting is not applicable for this unit. *GSQH10S18AA9W / ThermaliaC12*
4P359382-1D - 2015.02
Page 89
4/7
Breadcrumb Field code Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
Setting name
A.6.3.5.1 [5-05] Amp. limits for DI Limit DI1 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.2 [5-06] Amp. limits for DI Limit DI2 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.3 [5-07] Amp. limits for DI Limit DI3 R/W 0~50 A, step: 1 A
50
A
A.6.3.5.4 [5-08] Amp. limits for DI Limit DI4 R/W 0~50 A, step: 1 A
50
A
A.6.3.6.1 [5-09] kW limits for DI Limit DI1 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2 [5-0A] kW limits for DI Limit DI2 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3 [5-0B] kW limits for DI Limit DI3 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4 [5-0C] kW limits for DI Limit DI4 R/W 0~20 kW, step: 0,5 kW
20 kW
A.6.3.7 [4-01] R/O
0: None
2: BUH
└─ Averaging time
A.6.4 [1-0A] R/W
0: No averaging
1: 12 hours 2: 24 hours 3: 48 hours 4: 72 hours
└─ Ext amb. sensor offset
A.6.5 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
└─ Brine freezeup temperature
A.6.9 [A-04] R/W 0: 0°C
1: -2°C 2: -4°C 3: -6°C 4: -8°C 5: -10°C 6: -12°C
7: -14°C
└─ Overview settings
A.8 [0-00] R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
A.8 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
60°C
A.8 [0-02] R/W 10~25°C, step: 1°C
15°C
A.8 [0-03] R/W
-40~5°C, step: 1°C
-20°C
A.8 [0-04]
8
A.8 [0-05]
12
A.8 [0-06]
35
A.8 [0-07]
20
A.8 [0-0B] R/W
35~[6-0E]°C, step: 1°C
45°C
A.8 [0-0C] R/W
45~[6-0E]°C, step: 1°C
60°C
A.8 [0-0D] R/W 10~25°C, step: 1°C
15°C
A.8 [0-0E] R/W
-40~5°C, step: 1°C
-20°C
A.8 [1-00] R/W
-40~5°C, step: 1°C
-20°C
A.8 [1-01] R/W 10~25°C, step: 1°C
15°C
A.8 [1-02] R/W
[9-01]~[9-00], step: 1°C
60°C
A.8 [1-03] R/W [9-01]~min(45,[9-00]), step: 1°C
25°C
A.8 [1-04]
1
A.8 [1-05]
1
A.8 [1-06]
20
A.8 [1-07]
35
A.8 [1-08]
22
A.8 [1-09]
18
A.8 [1-0A] R/W
0: No averaging
1: 12 hours 2: 24 hours 3: 48 hours 4: 72 hours
A.8 [1-0B]
5
A.8 [1-0C]
5
A.8 [1-0D]
5
A.8 [1-0E]
5
A.8 [2-00] R/W 0: Each day
1: Monday 2: Tuesday 3: Wednesday 4: Thursday
5: Friday
6: Saturday 7: Sunda
y
A.8 [2-01] R/W 0: No
1: Yes
A.8 [2-02] R/W 0~23 hour, step: 1 hour
23
A.8 [2-03] R/W
60°C
A.8 [2-04] R/W 40~60 min, step: 5 min
40 min
A.8 [2-05] R/W
4~16°C, step: 1°C
12°C
A.8 [2-06] R/W
0: Disabled
1: Enabled
A.8 [2-09] R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0A] R/W -5~5°C, step: 0,5°C
0°C
A.8 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
What is the disinfection target temperature? How long must the tank temperature be maintained ?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
--
--
--
--
--
--
-­What is the averaging time for the outdoor temp?
--
--
Low ambient temp. for DHW WD curve.
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
--
--
--
-­Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
--
Priority
4P359382-1D - 2015.02
(#) Setting is not applicable for this unit. Do not change the default value.
(##) Setting is not applicable for this unit.
*GSQH10S18AA9W / ThermaliaC12*
Page 90
5/7
Breadcrumb Field code Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
Setting name
A.8 [3-00] R/W 0: No
1: Yes
A.8 [3-01]
0
A.8 [3-02]
1
A.8 [3-03]
4
A.8 [3-04]
2
A.8 [3-05]
1
A.8 [3-06] R/W 18~30°C, step: A.3.2.4
30°C
A.8 [3-07] R/W 12~18°C, step: A.3.2.4
12°C
A.8 [3-08]
35
A.8 [3-09]
15
A.8 [4-00] R/W 0: Disabled
1: Enabled
2: Only DHW
A.8 [4-01]
0
A.8 [4-02] R/W 14~35°C, step: 1°C
35°C
A.8 [4-03]
3
A.8 [4-04]
2
A.8 [4-05]
0
A.8 [4-06]
0/1
A.8 [4-07] R/W 0: No
1: Yes
A.8 [4-08] R/W
0: No limitation
1: Continuous 2: Di
g
ital inputs
A.8 [4-09] R/W
0: Current
1: Power
A.8 [4-0A]
0
A.8 [4-0B]
1
A.8 [4-0D]
3
A.8 [5-00] R/W 0: Allowed
1: Not allowe
d
A.8 [5-01] R/W
-15~35°C, step: 1°C
0°C
A.8 [5-02]
0
A.8 [5-03]
0
A.8 [5-04]
10
A.8 [5-05] R/W 0~50 A, step: 1 A
50
A
A.8 [5-06] R/W 0~50 A, step: 1 A
50
A
A.8 [5-07] R/W 0~50 A, step: 1 A
50
A
A.8 [5-08] R/W 0~50 A, step: 1 A
50
A
A.8 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0A] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0B] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0C] R/W 0~20 kW, step: 0,5 kW
20 kW
A.8 [5-0D] R/O
4: 3PN,
(
1/2
)
A.8 [5-0E]
1
A.8 [6-00] R/W 2~20°C, step: 1°C
2°C
A.8 [6-01] R/W 0~10°C, step: 1°C
2°C
A.8 [6-02]
0
A.8 [6-03] R/W 0~10 kW, step: 0,2 kW
3 kW
A.8 [6-04] R/W
0~10 kW, step: 0,2kW
3 kW
A.8 [6-05]
0
A.8 [6-06]
0
A.8 [6-07]
0
A.8 [6-08] R/W
2~20°C, step: 1°C
10°C
A.8 [6-09]
0
A.8 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
A.8 [6-0B] R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
A.8 [6-0C] R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
A.8 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
A.8 [6-0E] R/W 40~60°C, step: 1°C
60°C
A.8 [7-00]
0
A.8 [7-01]
2
A.8 [7-02] R/W
0: 1 LWT zone
1: 2 LWT zones
A.8 [7-03] R/W 0~6, step: 0,1
2,5
A.8 [7-04]
0
A.8 [7-05]
0
A.8 [8-00]
1
A.8 [8-01] R/W 5~95 min, step: 5 min
30 min
A.8 [8-02] R/W
0~10 hour, step: 0,5 hour
0
,
5 hour
A.8 [8-03]
50
A.8 [8-04] R/W
0~95 min, step: 5 min
95 min
A.8 [8-05] R/W
0: No
1: Yes
A.8 [8-06] R/W
0~10°C, step: 1°C
3°C
A.8 [8-07]
18
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
--
--
-­Maximum running time for domestic hot water operation.
Anti-recycling time.
-­Additional running time for the maximum running time.
What is the maximum temperature setpoint?
--
-­How many leaving water temperature zones are there?
PE factor
--
What is the hysteresis to be used in reheat mode?
-­What is the desired comfort storage temperature?
What is the desired eco storage temperature?
What is the desired reheat temperature?
What is the desired DHW production type?
-­What is the capacity of the backup heater step 1?
What is the capacity of the backup heater step 2?
--
--
--
What is the requested limit for DI3?
What is the requested limit for DI4?
What type of backup heater installation is used?
-­The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
What is the requested limit for DI2?
Is backup heater or boiler operation allowed above equilibrium temperature during space heating operation? What is the equilibrium temperature for the building?
--
--
--
--
Which power limitation mode is required on the system?
-- (Do not change this value)
Below which outdoor temperature is heating allowed?
Which power limitation type is required?
--
--
What is the BUH operation mode?
--
--
--
--
Enable the second step of the backup heater?
--
-­What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
--
--
Is auto restart of the unit allowed?
--
--
--
(#) Setting is not applicable for this unit. Do not change the default value. (##) Setting is not applicable for this unit. *GSQH10S18AA9W / ThermaliaC12*
4P359382-1D - 2015.02
Page 91
6/7
Breadcrumb Field code Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
Setting name
A.8 [8-08]
20
A.8 [8-09] R/W
[9-01]~[9-00], step: 1°C
55°C
A.8 [8-0A] R/W
[9-01]~[9-00], step: 1°C
45°C
A.8 [8-0B]
13
A.8 [8-0C]
10
A.8 [8-0D]
16
A.8 [9-00] R/W 37~65°C, step: 1°C
65°C
A.8 [9-01] R/W
15~37°C, step: 1°C
24°C
A.8 [9-02]
22
A.8 [9-03]
5
A.8 [9-04] R/W
1~4°C, step: 1°C 1°C
A.8 [9-05] R/W
15~37°C, step: 1°C
24°C
A.8 [9-06] R/W 37~65°C, step: 1°C
65°C
A.8 [9-07]
5
A.8 [9-08]
22
A.8 [9-09] R/W
3~10°C, step: 1°C
8°C
A.8 [9-0A]
5
A.8 [9-0B] R/W
0: Quick
1: Slow
A.8 [9-0C] R/W 1~6°C, step: 0,5°C
1 °C
A.8 [9-0D] R/W 0~8,step:1
6
A.8 [9-0E] 0~8,step:1
6
A.8 [A-00]
1
A.8 [A-01]
0
A.8 [A-02]
0
A.8 [A-03] R/W
0: 148Hz
1: 193Hz
A.8 [A-04] R/W
0: 0°C 1: -2°C 2: -4°C 3: -6°C 4: -8°C 5: -10°C 6: -12°C
7: -14°C
A.8 [B-00]
0
A.8 [B-01]
0
A.8 [B-02]
0
A.8 [B-03]
0
A.8 [B-04]
0
A.8 [C-00]
1
A.8 [C-01]
0
A.8 [C-02] R/W
0: No
1: Bivalent 2: ­3: -
A.8 [C-03] R/W
-25~25°C, step: 1°C
0°C
A.8 [C-04]
R/W
2~10°C, step: 1°C
3°C
A.8 [C-05] R/W
1: Thermo ON/OFF
2: C/H re
q
uest
A.8 [C-06] R/W
0: -
1: Thermo ON/OFF
2: C/H re
q
uest
A.8 [C-07] R/W
0: LWT control
1: Ext RT control 2: RT control
A.8 [C-08] R/W
0: No
1: Outdoor sensor (##) 2: Room sensor
A.8 [C-09] R/W
0: Normally open
1: Normall
y
closed
A.8 [C-0A]
0
A.8 [C-0C]
0
A.8 [C-0D]
0
A.8 [C-0E]
0
A.8 [D-00] R/O
0: Non
e
A.8 [D-01] R/W
0: No
1: Active open 2: Active closed
A.8 [D-02] R/W
0: No
1: Secondary rtrn 2: Disinf. Shunt
A.8 [D-03] R/W
0: Disabled
1: Enabled, shift 2°C (from -2 to 2°C) 2: Enabled, shift 4°C (from -2 to 2°C) 3: Enabled, shift 2°C (from -4 to 4°C) 4: Enabled, shift 4°C
(
from -4 to 4°C
)
A.8 [D-04] R/W
0: No
1: Pwr consm
p
ctrl
A.8 [D-05] R/W 0: Forced off
1: As normal
A.8 [D-07] R/O
0: No
(#)
A.8 [D-08] R/W
0 (No): NOT installed
1: Installed (0.1 pulse/kWh) 2: Installed (1 pulse/kWh) 3: Installed (10 pulse/kWh) 4: Installed (100 pulse/kWh) 5: Installed
(
1000 pulse/kWh
)
Is a solar kit connected? Is an external kWh meter used for power measurement?
Which heaters are permitted if prefer. kWh rate PS is cut? Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
--
--
--
--
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
--
--
-­Is an external backup heat source connected?
Bivalent activation temperature.
-­Maximum heating frequency
What is the brine anti freeze up temperature?
--
--
--
What is the desired delta T in heating?
-­What emitter type is connected to the main LWT zone?
Room temperature hysteresis.
--
--
-­Leaving water temperature overshoot temperature.
What is the mimimum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in heating?
--
--
--
--
-­What is the maximum desired LWT for main zone in heating?
What is the mimimum desired LWT for main zone in heating?
--
-­What is the desired comfort main LWT in heating?
What is the desired eco main LWT in heating?
Pump speed limitation
--
4P359382-1D - 2015.02
(#) Setting is not applicable for this unit. Do not change the default value.
(##) Setting is not applicable for this unit.
*GSQH10S18AA9W / ThermaliaC12*
Page 92
7/7
Breadcrumb Field code Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with default value
Setting name
A.8 [D-09] R/W
0 (No): NOT installed
1: Installed (0.1 pulse/kWh) 2: Installed (1 pulse/kWh) 3: Installed (10 pulse/kWh) 4: Installed (100 pulse/kWh) 5: Installed
(
1000 pulse/kWh
)
A.8 [D-0A]
0
A.8 [D-0B]
2
A.8 [D-0C]
0
A.8 [D-0D]
0
A.8 [D-0E]
0
A.8 [E-00] R/O
0~5
5: Ground sourc
e
A.8 [E-01] R/O
1: 16
A.8 [E-02] R/O
1: T
yp
e 2
A.8 [E-03]
2
A.8 [E-04] R/O
0: No
A.8 [E-05]
1
A.8 [E-06]
1
A.8 [E-07]
1
A.8 [E-08]
0
A.8 [E-09]
0
A.8 [E-0A]
0
A.8 [E-0B] R/O
0
(#)
A.8 [E-0C]
0
A.8 [F-00] R/W
0: Disabled
1: Enabled
A.8 [F-01]
20
A.8 [F-02]
3
A.8 [F-03]
5
A.8 [F-04]
0
A.8 [F-05]
0
A.8 [F-06]
0
A.8 [F-09] R/W 0: Disabled
1: Enabled
A.8 [F-0A]
0
A.8 [F-0B] R/W
0: No
1: Yes
A.8 [F-0C]
1
A.8 [F-0D] R/W 0: Continuous
1: Sample (only possible if [C-07] = 0) 2: Re
q
uest(only possible if [C-07] 0
)
-­What is the pump operation mode?
--
--
--
-­Pump operation during flow abnormality.
-­Close shut-off valve during thermo OFF?
-­Is the power saving function available on the outdoor unit?
--
--
--
Which type of compressor is installed? What is the indoor unit software type?
--
Pump operation allowed outside range.
--
--
Is an external kWh meter used for power measurement?
--
--
--
-­Which type of unit is installed?
--
--
Is a bi-zone kit installed ?
--
--
(#) Setting is not applicable for this unit. Do not change the default value. (##) Setting is not applicable for this unit. *GSQH10S18AA9W / ThermaliaC12*
4P359382-1D - 2015.02
Page 93
Page 94
Page 95
Page 96
4P351748-1C 2015.10
Copyright 2013 Daikin
Loading...