Daikin EDLQ036BA6VJU1, EDLQ048BA6VJU1, EDLQ054BA6VJU1, EBLQ036BA6VJU1, EBLQ048BA6VJU1 Installation Manual

...
INSTALLATION MANUAL
Unit for air to water heat pump system
EDLQ036BA6VJU1
Installation manual
Unit for air to water heat pump system
English
EDLQ048BA6VJU1 EDLQ054BA6VJU1
Unité pour système de pompe à chaleur air à eau
Français
EBLQ036BA6VJU1 EBLQ048BA6VJU1 EBLQ054BA6VJU1
Manual de instalación
Unidad para bomba de calor de aire-agua
Español
E E E
E
1A
B2
D2
L1< L2
C
A
L2
D1
L1
H B1
L2< L1
L1≤ H
L1< L2
H< L1
L2≤ H
L2< L1
L1≤ H
0 <L1 ≤ 1/ 2H
0 <L1 ≤ 1/ 2H
0 <L2 ≤ 1/ 2H
1/2H < L2 ≤H
1
H<L2 L2≤ H
B2
L1< L2
C
D2
L1
H B1
L2< L1
L1≤ H
L1< L2
H< L1
L1≤ H
0 <L2 ≤ 1/ 2H
1/2H < L2 ≤H
0 <L1 ≤ 1/ 2H
1/2H < L1 ≤H
1
A
L2
D1
L2< L1
L2≤ H
0 <L2 ≤ 1/ 2H
1/2H < L2 ≤H
2
1A (inch)
1B
H< L2
L2≤ H
B2
D2
L1< L2
C
A
L2
D1
L1
H B1
L2< L1
L1≤ H
L1< L2
H< L1
L2≤ H
L2< L1
L1≤ H
0 <L1 ≤ 1/ 2H
0 <L1 ≤ 1/ 2H
0 <L2 ≤ 1/ 2H
1/2H < L2 ≤H
1
H< L2 L2≤ H
B2
L1< L2
C
D2
L1
H B1
L2< L1
L1≤ H
L1< L2
H< L1
L1≤ H
0 <L2 ≤ 1/ 2H
1/2H < L2 ≤H
0 <L1 ≤ 1/ 2H
1/2H < L1 ≤H
1
A
L2
D1
L2< L1
L2≤ H
0 <L2 ≤ 1/ 2H
1/2H < L2 ≤H
2
1B (mm)
H< L2 L2 ≤ H
1
EDLQ036BA6VJU1 EDLQ048BA6VJU1 EDLQ054BA6VJU1
EBLQ036BA6VJU1 EBLQ048BA6VJU1 EBLQ054BA6VJU1
Unit for air to water heat pump system
Installation manual
CONTENTS
Page
READ THESE INSTRUCTIONS CAREFULLY BEFORE
Introduction........................................................................................ 1
INSTALLATION. KEEP THIS MANUAL IN A HANDY
General information ................................................................................... 1
PLACE FOR FUTURE REFERENCE.
Scope of this manual ................................................................................. 2
Model identification .................................................................................... 2
Accessories ....................................................................................... 2
Accessories supplied with the unit ............................................................. 2
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
Safety considerations ........................................................................ 3
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
Before installation .............................................................................. 4
SPECIFICALLY DESIGNED FOR USE WITH THE
Important information regarding the refrigerant used ........................ 4
Selecting installation site ................................................................... 4
Selecting a location in cold climates .......................................................... 5
Precautions on installation................................................................. 5
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
ALL ACTIVITIES DESCRIBED IN THIS MANUAL SHALL
BE CARRIED OUT BY A LICENSED TECHNICIAN.
Installation method for prevention of falling over ........................................ 5
BE SURE TO WEAR ADEQUATE PERSONEL PROTEC-
Installation servicing space ........................................................................ 6
TION EQUIPMENT (PROTECTION GLOVES, SAFETY
Typical application examples ............................................................. 7
GLASSES, ...) WHEN PERFORMING INSTALLATION,
Application 1 .............................................................................................. 7
MAINTENANCE OR SERVICE TO THE UNIT.
Application 2 .............................................................................................. 7
Application 3 .............................................................................................. 8
Application 4 .............................................................................................. 8
Application 5 .............................................................................................. 9
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
Application 6 ............................................................................................ 11
THE UNIT DESCRIBED IN THIS MANUAL IS DESIGNED
Overview of the unit......................................................................... 11
FOR OUTDOOR INSTALLATION.
Opening the unit....................................................................................... 11
Main components..................................................................................... 12
Water pipework ........................................................................................ 13
The English text is the original instruction. Other languages are translations of the original instructions.
Charging water......................................................................................... 16
Piping insulation....................................................................................... 16
Field wiring............................................................................................... 17
Installation of the digital controller............................................................ 22
INTRODUCTION
Start-up and configuration ............................................................... 23
DIP switch settings overview.................................................................... 23
Room thermostat installation configuration.............................................. 23
General information
Pump operation configuration .................................................................. 23
Domestic hot water tank installation configuration ................................... 24
These units are used for both heating and cooling applications. The
Initial start-up at low outdoor ambient temperatures................................ 24
units can be combined with Daikin fan coil units, floor heating
Pre-operation checks ............................................................................... 24
applications, low temperature radiators, domestic hot water tank
Powering up the unit ................................................................................ 25
(option) and solar kit (option).
Setting the pump speed ........................................................................... 25
Field settings............................................................................................ 25
A remote controller is standard supplied with the unit to control your
Field settings table ................................................................................... 35
installation.
Test run and final check................................................................... 37
Heating/cooling units and heating only units
Automatic test run .................................................................................... 37
Test run operation (manual) ..................................................................... 37
The monoblock unit range consists of two main versions: a
Maintenance and service ......................................................................... 37
heating/cooling (EB) version and a heating only (ED) version.
Maintenance and service ................................................................ 37
Troubleshooting ............................................................................... 38
General guidelines ................................................................................... 38
General symptoms................................................................................... 38
Error codes .............................................................................................. 39
Technical specifications ................................................................... 40
General .................................................................................................... 40
Electrical specifications............................................................................ 40
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Installation manual
Unit for air to water heat pump system
4PW56182-1
*
A B 1
2 3 4
TA
P
H
1
2
3
4
2
Both versions are delivered with an integrated backup heater for
Operation range
additional heating capacity during cold outdoor temperatures. The backup heater also serves as a backup in case of malfunctioning of
Heating mode Cooling mode
the unit and for freeze protection of the outside water piping during
A A
winter time. The backup heater factory set capacity is 6 kW, however, depending on the installation, the installer can limit the backup heater
DB DB
35 95
46 115
capacity to 3 kW. The backup heater capacity decision is a mode based on the equilibrium temperature, see scheme below.
PH
0 32
10 50
3
1
2
20
4
41
5
59 7277 15 2225
104
40
( )
131
55
B
41
5
72 22
B
Outdoor temperature Leaving water temperature
4
TA
No heat pump operation, back up heater only
Heat pump capacity
(*) The models have a freeze prevention function using the pump and
back up heater to keep the water system safe from freezing in all
Required heating capacity (site dependent)
conditions. In case accidental or intentional power shutdown is likely to happen
Additional heating capacity provided by the backup heater
we recommend to use glycol. (Refer to Caution: "Use of glycol" on
Equilibrium temperature (can be set through the user interface,
page 16) refer to "Field settings" on page 25) Ambient (outdoor) temperature
Connection to a benefit kWh rate power supply
Heating capacity
This equipment allows for connection to benefit kWh rate power
supply delivery systems. Full control of the unit will remain possible Domestic hot water tank EKHW* (option) An optional EKHW* domestic hot water tank with integrated
3 kW electrical booster heater can be connected to the unit. The
only in case the benefit kWh rate power supply is of the type that
power supply is not interrupted. Refer to "Connection to a benefit
kWh rate power supply" on page 21 for more details. domestic hot water tank is available in two sizes: 50 and
80 gallons (200 and 300 litre).
Scope of this manual
Room thermostat (option) An optional room thermostat EKRTWA can be connected to the
unit.
This installation manual describes the procedures for installing and
connecting all EDL and EBL outdoor unit models. Solar kit for domestic hot water tank (option)
An optional solar kit EKSOLHW can be connected to the unit. Model identification Contact your dealer for more allowed solar kits.
Remote alarm kit (option)
EDL Q 036 BA 6 VJU
Digital I/O PCB kit (option)
Power supply:
An optional EKRP1HB digital I/O PCB can be connected to the
2~, 208 V/230 V
indoor unit and allows:
Backup heater capacity (kW)
remote alarm output
Model changes
heating/cooling ON/OFF output
bivalent operation (permission signal for the auxiliary boiler)
Indication of heating capacity (kBtu/h)(a)
Refrigerant R410A
EDL = Monoblock outdoor heating only
Refer to the operation manual of the indoor unit and to the
EBL = Monoblock outdoor heat pump
installation manual of the digital I/O PCB for more information.
(a) For exact values, refer to "Technical specifications" on page 40.
Refer to the wiring diagram or connection diagram for connecting this PCB to the unit.
To obtain more information concerning these option kits, please refer
ACCESSORIES
to dedicated installation manuals of the kits.
Accessories supplied with the unit
1
1x
2
1x
3
2x
4
1x
Installation manual Operation manual
Wiring diagram sticker (inside unit cover doors 1 and 2) User interface kit
(digital remote controller, 4 fixing screws and 2 plugs)
Installation manual
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
4PW56182-1
■ ■ ■ ■ ■
■ ■ ■
■ ■ ■ ■ ■
or fire.
■ ■ ■
3
S
AFETY
CONSIDERATIONS
Make certain that all electrical work is carried out by qualified personnel according to the local laws and regulations and this
The precautions listed here are divided into the following two types.
installation manual, using a separate circuit.
Both cover very important topics, so be sure to follow them carefully. Insufficient capacity of the power supply circuit or improper
electrical construction may lead to electric shocks or fire.
Meanings of DANGER, WARNING, CAUTION and NOTE symbols.
Be sure to install a ground fault circuit interrupter according to
DANGER
local laws and regulations.
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Failure to install a ground fault circuit interrupter may cause electric shocks and fire.
WARNING
Make sure that all wiring is secure, using the specified wires and
ensuring that external forces do not act on the terminal Indicates a potentially hazardous situation which, if not connections or wires. avoided, could result in death or serious injury.
Incomplete connection or fixing may cause a fire. CAUTION When wiring the power supply, form the wires so that the
Indicates a potentially hazardous situation which, if not
frontside panel can be securely fastened. avoided, may result in minor or moderate injury. It may also
If the frontside panel is not in place, overheat of the terminals, be used to alert against unsafe practices.
electric shocks or a fire may be caused.
NOTE
After completing the installation work, check to make sure that
there is no leakage of refrigerant gas. Indicates situations that may result in equipment or
property-damage accidents only.
Never directly touch any accidental leaking refrigerant. This
could result in severe wounds caused by frostbite.
Danger
Do not touch the refrigerant pipes during and immediately after
Before touching electric terminal parts, turn off power switch. When service panels are removed, live parts can be easily
operation as the refrigerant pipes may be hot or cold, depending
on the condition of the refrigerant flowing through the refrigerant
piping, compressor and other refrigerant cycle parts. Your hands
touched by accident.
may suffer burns or frostbite if you touch the refrigerant pipes. To
Never leave the unit unattended during installation or servicing
avoid injury, give the pipes time to return to normal temperature
when the service panel is removed.
or, if you must touch them, be sure to wear proper gloves.
Do not touch water pipes during and immediately after operation
Do not touch the internal parts (pump, backup heater, etc.)
as the pipes may be hot. Your hand may suffer burns. To avoid
during and immediately after operation.
injury, give the piping time to return to normal temperature or be
Your hands may suffer burns if you touch the internal parts. To
sure to wear proper gloves.
avoid injury, give the internal parts time to return to normal
Do not touch any switch with wet fingers. Touching a switch with
temperature or, if you must touch them, be sure to wear proper
wet fingers can cause electrical shock.
gloves.
Before touching electrical parts, turn off all applicable power supply.
Caution
For use of units in applications with temperature alarm settings it
Warning
is advised to foresee a delay of 10 minutes for signalling the
Tear apart and throw away plastic packaging bags so that children will not play with them.
Children playing with plastic bags face danger of death by suffocation.
alarm in case the alarm temperature is exceeded. The unit may
stop for several minutes during normal operation for "defrosting
of the unit" or when in "thermostat-stop" operation.
Ground the unit.
Safely dispose of packing materials. Packing materials, such as nails and other metal or wooden parts, may cause stabs or other
Grounding resistance should be according to local laws and
regulations
injuries.
Do not connect the ground wire to gas or water pipes,
Ask your dealer or qualified personnel to carry out installation work.
lightning conductor or telephone ground wire.
Do not install the machine by yourself.
Incomplete grounding may cause electric shocks.
Improper installation may result in water leakage, electric shocks Gas pipe. or fire. Ignition or explosion may occur if the gas leaks.
Perform installation work in accordance with this installation
Water pipe.
manual.
Hard vinyl tubes are not effective grounds.
Improper installation may lead to water leakage, electric shocks
Lightning conductor or telephone ground wire. Electric potential may rise abnormally if struck by a lightning
Be sure to use only the specified accessories and parts for
bolt.
installation work.
Install the power wire at least 3 feet (1 meter) away from
Failure to use the specified parts may result in water leakage,
televisions or radios to prevent image interference or noise.
electric shocks, fire, or the unit falling.
(Depending on the radio waves, a distance of 3 feet (1 meter)
Install the unit on a foundation that can withstand its weight.
may not be sufficient to eliminate the noise.)
Insufficient strength may result in the fall of equipment and
Do not rinse the unit. This may cause electric shocks or fire.
causing injury.
Do not install the unit in places such as the following:
Carry out the specified installation work in consideration of strong winds, hurricanes, or earthquakes.
Where there is mist of mineral oil, oil spray or vapour.
Plastic parts may deteriorate, and cause them to fall out or Improper installation work may result in accidents due to fall of water to leak. equipment.
Where corrosive gas, such as sulphurous acid gas, is produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Installation manual
Unit for air to water heat pump system
4PW56182-1
1
2
unit.
(1)
4
Where there is machinery which emits electromagnetic waves.
S
ELEC TI NG
INSTALLATION SITE
Electromagnetic waves may disturb the control system, and cause malfunction of the equipment. Make sure to provide for adequate measures in order
Where flammable gases may leak, where carbon fibre or ignitable dust is suspended in the air or where volatile
to prevent that the outdoor unit be used as a shelter by small animals.
ammables, such as thinner or gasoline, are handled.
Small animals making contact with electrical parts can
Such gases may cause a fire.
cause malfunctions, smoke or fire. Please instruct the
Where the air contains high levels of salt such as that near
customer to keep the area around the unit clean.
the ocean.
Select an installation site where the following conditions are
■ Where voltage fluctuates a lot, such as that in factories. satisfied and that meets with your customer's approval.
In vehicles or vessels.
- Places which are well-ventilated.
Where acidic or alkaline vapour is present.
- Places where the unit does not bother next-door neighbours.
- Safe places which can withstand the unit's weight and vibration and where the unit can be installed level.
B
EFORE
INSTALLATION
- Places where there is no possibility of flammable gas or
product leak.
- The equipment is not intended for use in a potentially
Installation explosive atmosphere.
Be sure to confirm the model name and the serial no. of the
- Places where servicing space can be well ensured.
outer (front) plates when attaching/detaching the plates to avoid
- Places where the units' piping and wiring lengths come within
mistakes.
the allowable ranges.
When closing the service panels, take care that the tightening torque does not exceed 3.03 lbs·ft (4.1 N·m).
- Places where water leaking from the unit cannot cause
damage to the location (e.g. in case of a blocked drain pipe).
- Places where the rain can be avoided as much as possible.
Handling - Do not install the unit in places often used as workplace.
Due to relatively large dimensions and high weight, the handling of the unit is only to be done by means of
lifting tools with slings. These slings can be fitted into specially for this
In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.
- Do not place any objects or equipment on top of the unit (top
plate)
- Do not climb, sit or stand on top of the unit.
purpose foreseen sleeves at the
- Be sure that sufficient precautions are taken, in accordance
base frame.
with relevant local laws and regulations, in case of refrigerant
leakage.
To avoid injury, do not touch the air inlet or aluminium fins of the
When installing the unit in a place exposed to strong wind, pay special attention to the following.
Strong winds of 16 ft/sec (5 m/sec) or more blowing against the
Do not use the grips in the fan grills to avoid
damage.
unit's air outlet causes short circuit (suction of discharge air), and this may have the following consequences:
- Deterioration of the operational capacity.
Unit is top heavy! Prevent the unit from falling due to inclination during
handling. Centre of gravity is indicated on the unit.
- Frequent frost acceleration in heating operation.
- Disruption of operation due to rise of high pressure.
- When a strong wind blows continuously on the face of the
unit, the fan can start rotating very fast until it breaks.
Refer to the figures for installation of this unit in a place where the wind direction can be foreseen.
IMPORTANT INFORMATION REGARDING THE
REFRIGERANT USED
Turn the air outlet side toward the building's wall, fence or screen.
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type: R410A GWP
(1)
value: 1975
GWP = global warming potential
The refrigerant quantity is indicated on the unit name plate
Make sure there is enough room to do the installation
Installation manual
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
4PW56182-1
13
14
4i
0.
(2
■ ■ ■
3
A
6
B
C
7
NOTE
■ ■ ■
C
1 2 A
B
C
5
Set the outlet side at a right angle to the direction of the wind.
P
RECAUTIONS
ON INSTALLATION
Check the strength and level of the installation ground so that
Strong wind
the unit will not cause any operating vibration or noise after installation.
In accordance with the foundation drawing in the figure, fix the unit securely by means of the foundation bolts. (Prepare four
sets of 1/2 inch (M12) foundation bolts, nuts and washers each which are available on the market.)
Blown air
Strong wind
It is best to screw in the foundation bolts until their length are
0.8 inch (20 mm) from the foundation surface.
Prepare a water drainage channel around the foundation, to drain waste water from around the unit.
C
A
C
4 If the water drainage of the unit is not easy, please build up the
B
unit on a foundation of concrete blocks, etc. (the height of the foundation should be maximum 6 inch (150 mm)).
9.44 9.44
5 If you install the unit on a frame, please install a waterproof plate
within 6 inch (150 mm) of the underside of the unit in order to
(240) 37.60 (955)
56.50 (1435)
(240)
prevent the invasion of water from the lower direction.
Discharge side
When installing the unit in a place frequently exposed to snow,
Bottom view inch (mm)
pay special attention to elevate the foundation as high as
Drain hole
possible. If you install the unit on a building frame,
please install a waterproof plate (field supply) (within 6 inch (150 mm) of the underside of the unit) in order to avoid the drainwater dripping. (See figure).
NOTE
If drain holes of the unit are covered by a mounting base or by floor surface, raise the unit in order to provide a free
space of more than 4 inch
Selecting a location in cold climates
(100 mm) under the unit.
Refer to "Handling" on page 4.
When operating the unit in a low outdoor ambient
Installation method for prevention of falling over
temperature, be sure to follow the instructions described below.
If it is necessary to prevent the unit from falling over, install as shown
To prevent exposure to wind, install the unit with its suction side facing the wall.
Never install the unit at a site where the suction side may be exposed directly to wind.
in the figure.
prepare all 4 wires as indicated in the drawing
unscrew the top plate at the 4 locations indicated A and B
put the screws through the nooses and screw them back tight
To prevent exposure to wind, install a baffle plate on the air discharge side of the unit.
A
B
In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is not affected by the snow (if necessary construct a lateral canopy).
Construct a large canopy. Construct a pedestal.
Install the unit high enough off the ground to prevent burying in snow.
Location of the 2 fixation holes on the front side of the unit Location of the 2 fixation holes on the rear side of the unit
Wires: field supply
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Installation manual
Unit for air to water heat pump system
4PW56182-1
≥4i
(≥1 ≥4i
(≥1
1.
1
2.
2
A
H
1.
2.
6
Installation servicing space
(C) In case of multiple-row installation (for roof top use, etc.)
In case of installing one unit per row. The numerical figures used in the figures represent the dimensions in mm.
(Refer to "Precautions on installation" on page 5)
Precaution (A) In case of non-stacked installation figure 1A and figure 1B
≥4 inch (≥100 mm)
Suction side obstacle
Obstacle is present
≥80 inch (≥2000 mm)
≥8 inch (≥200 mm)
Discharge side obstacle
In these cases, close the bottom of the installation
≥40 inch (≥1000 mm)
Left side obstacle
frame to prevent the discharged air from being bypassed
In case of installing multiple units (2 units or more) in lateral
connection per row.
Right side obstacle
In these cases, only 2 units can be installed.
Top side obstacle
This situation is not allowed
NOTE
Minimum distance B1 in figure 1A and figure 1B
L
mentions the space required for correct operation of the unit. Required space for servicing though is 12 inch (300 mm).
≥120 inch (≥3000 mm)
(B) In case of stacked installation
≥24 inch (≥600 mm)
≥60 inch (≥1500 mm)
In case obstacles exist in front of the outlet side.
Relation of dimensions of H, A and L are shown in the table below.
L A
A
L≤H
0<L≤1/2H
1/2H<L
10 (250) 12 (300)
≥40 inch (≥1000 mm)
In case obstacles exist in front of the air inlet.
A
≥12 inch (≥300 mm)
Do not stack more than one unit. About 4 inch (100 mm) is required as the dimension for laying the
upper unit's drain pipe. Get the portion A sealed so that air from the outlet does not bypass.
H<L Installation not allowed
Installation manual
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
4PW56182-1
only.
1 2 1
9
3 4 T
2 3 5
I 4 5
6
7 8 I
7
T
YPICAL
APPLICATION EXAMPLES
Application 2
The application examples given below are for illustration purposes
Space heating only application without room thermostat connected to
the unit. The temperature in each room is controlled by a valve on
each water circuit. Domestic hot water is provided through the
Application 1
domestic hot water tank which is connected to the unit.
Space heating only application with a room thermostat connected to the unit.
I
1 2 3 4
6
5
7
I
T
M
T1 T2 T3
1 2 3 4
5
8
M1
9
FHL1
M2
FHL2
M3
FHL3
FHL1
FHL2
FHL3
10
Unit FHL1..3 Floor heating loop Heat exchanger
(field supply)
Unit Heat exchanger coil Pump Shut-off valve
Room thermostat (optional)
Heat exchanger
Pump
10 Domestic hot water tank
(optional)
Collector (field supply) User interface
Shut-off valve FHL1..3 Floor heating loop
Unit operation and space heating
Collector (field supply)
(field supply)
When a room thermostat (T) is connected to the unit and when there
Motorised 3-way valve
(optional)
T1..3 Individual room
thermostat (field supply)
is a heating request from the room thermostat, the unit will start operating to achieve the target leaving water temperature as set on
By-pass valve
(field supply)
M1..3 Individual motorised
valve to control loop
the user interface.
Booster heater
FHL1 (field supply)
When the room temperature is above the thermostat set point, the
User interface
unit will stop operating.
Pump operation
Make sure to connect the thermostat wires to the correct
With no thermostat connected to the unit (1), the pump (3) can be
terminals (see "Connection of the thermostat cable" on
configured to operate either as long as the unit is on, or until the
page 20) and to configure the DIP switch toggle switches
required water temperature is reached.
correctly (see "Room thermostat installation configuration" on page 23).
NOTE
Details on pump configuration can be found under "Pump operation configuration" on page 23.
Space heating
The unit (1) will operate to achieve the target leaving water temperature as set on the user interface.
When circulation in each space heating loop (FHL1..3) is controlled by remotely controlled valves (M1..3), it is important to provide a by-pass valve (7) to avoid the flow switch safety device from being activated.
The by-pass valve should be selected as such that at all time the minimum water flow as mentioned under "Water
pipework" on page 13 is guaranteed.
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Installation manual
Unit for air to water heat pump system
4PW56182-1
page 7.
5
I
1
1 5 2 3 4 2 3
4
6
T
5
7
8 9 I
I
8
Domestic water heating
Pump operation and space heating and cooling
When domestic water heating mode is enabled (either manually by According to the season, the customer will select cooling or heating the user, or automatically through a schedule timer) the target on the room thermostat (T). This selection is not possible by
domestic hot water temperature will be achieved by a combination of operating the user interface. the heat exchanger coil and the electrical booster heater.
When space heating/cooling is requested by the room thermostat
When the domestic hot water temperature is below the user
(T), the pump will start operating and the unit (1) will switch to
configured set point, the 3-way valve will be activated to heat the
"heating mode"/"cooling mode". The unit (1) will start operating to
domestic water by means of the heat pump. In case of large domestic
achieve the target leaving cold/hot water temperature.
hot water demand or a high domestic hot water temperature setting,
In case of cooling mode, the motorised 2-way valve (11) will close as
the booster heater (8) can provide auxiliary heating.
to prevent cold water running through the floor heating loops (FHL).
It is possible to connect either a 2-wire or a 3-wire 3-way
Make sure to connect the thermostat wires to the correct
valve (6). Make sure to fit the 3-way valve correctly. For
terminals (see "Connection of the thermostat cable" on
more details, refer to "Wiring the 3-way valve" on page 20.
page 20) and to configure the DIP switch toggle switches
correctly (see "Room thermostat installation configuration"
NOTE
The unit can be configured so that at low outdoor
on page 23).
temperatures the domestic water is exclusively heated by the booster heater. This assures that the full
Wiring of the 2-way valve (11) is different for a NC (normal
capacity of the heat pump is available for space
closed) valve and a NO (normal open) valve! Make sure to
heating.
connect to the correct terminal numbers as detailed on the
Details on domestic hot water tank configuration for
wiring diagram.
low outdoor temperatures can be found under "Field settings" on page 25, field settings [5-02] to [5-04].
The ON/OFF setting of the heating/cooling operation is done by the room thermostat and cannot be done by the user interface.
Application 3
Domestic water heating
Domestic water heating is as described under "Application 2" on
Space cooling and heating application with a room thermostat suitable for heating/cooling changeover connected to the unit.
Heating is provided through floor heating loops and fan coil units. Cooling is provided through the fan coil units only.
Application 4
Domestic hot water is provided through the domestic hot water tank which is connected to the unit.
Space cooling and heating application without a room thermostat connected to the unit, but with a heating only room thermostat
controlling the floor heating and a heating/cooling thermostat controlling the fan coil units. Heating is provided through floor heating
loops and fan coil units. Cooling is provided through the fan coil units only.
I
T
5 7
1 2 3 4 6 11
FCU1
FCU2
M M
FCU3
T4 T5 T6
1 2 3 4
11 12
8
9
FHL1
M
T
M
FCU1
5
FCU2
FCU3
FHL2
FHL3
10
FHL1
FHL2
FHL3
Unit 10 Domestic hot water tank Unit 12 Motorised 2-way valve for Heat exchanger Pump Shut-off valve Collector (field supply)
11
FCU1..3 FHL1..3
Motorised 2-way valve
(field supply) Fan coil unit (field supply)
Floor heating loop
Heat exchanger Pump
Shut-off valve
FCU1..3
activation of the room thermostat (field supply)
Fan coil unit with thermostat (field supply)
Motorised 3-way valve (optional)
(field supply) Room thermostat with
Collector (field supply) By-pass valve (field
FHL1..3 Floor heating loop (field
supply)
Booster heater Heat exchanger coil
heating/cooling switch (optional)
User interface
11
supply) Motorised 2-way valve
to shut off the floor
T
T4..6
Heating only room thermostat (optional)
Individual room heating loops during cooling operation (field
supply)
thermostat for fan coil
heated/cooled room
(optional)
User interface
Installation manual
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Unit for air to water heat pump system
4PW56182-1
NOTE
M
2
1
2
I
M
15 17
16
10 11 1 2 4 5 6 17
10
11
9
Pump operation
With no thermostat connected to the unit (1), the pump (3) can be configured to operate either as long as the unit is on, or until the
required water temperature is reached.
CAUTION
Be sure that the boiler and the integration of the boiler in the system is in accordance with relevant local laws
and regulations.
Details on pump configuration can be found under
Always install a 3-way valve, even if no domestic hot
"Pump operation configuration" on page 23.
water tank is installed. This to ensure that the freeze
protection function (see "[4-04] Freeze protection
Space heating and cooling
function" on page 28) can operate when the boiler is
active.
According to the season, the customer will select cooling or heating through the user interface.
The unit (1) will operate in cooling mode or heating mode to achieve the target leaving water temperature.
1
I
With the unit in heating mode, the 2-way valve (11) is open. Hot water is provided to both the fan coil units and the floor heating loops.
With the unit in cooling mode, the motorised 2-way valve (11) is closed to prevent cold water running through the floor heating loops
(FHL).
When closing several loops in the system by remotely controlled valves, it might be required to install a by-pass valve (7) to avoid the flow switch safety device from being activated. See also "Application 2" on page 7.
FHL1 FHL2 FHL3
Wiring of the 2-way valve (11) is different for a NC (normal
Motorised 3-way valve
closed) valve and a NO (normal open) valve! Make sure to
Boiler
connect to the correct terminal numbers as detailed on the wiring diagram.
Daikin can not be put responsible for incorrect or
unsafe situations in the boiler system.
The ON/OFF setting of the heating/cooling operation is done by the user interface.
Application 5
1 2 3 4 6
18
17 5
Space heating with an auxiliary boiler (alternating operation)
Space heating application by either the Daikin unit or by an auxiliary boiler connected in the system. The decision whether either the
E(D/B)* unit or the boiler will operate can be achieved by an auxiliary contact or an E(D/B)* indoor controlled contact.
The auxiliary contact can e.g. be an outdoor temperature thermostat, an electricity tariff contact, a manually operated contact, etc. See
"Field wiring configuration A" on page 10. The E(D/B)* unit controlled contact (also called 'permission signal for
the auxiliary boiler") is determined by the outdoor temperature (thermistor located at the outdoor unit). See "Field wiring configuration B" on page 10.
Bivalent operation is only possible for space heating operation, not for the domestic water heating operation. Domestic hot water in such an application is always provided by the domestic hot water tank
which is connected to the Daikin unit.
FHL1
FHL2
The auxiliary boiler must be integrated in the piping work and in the eld wiring according to the illustrations below.
12
FHL3
Outdoor unit Heat exchanger
12
Domestic hot water tank (optional)
3 Pump
Shut-off valve Collector (field supply) Motorised 3-way valve
(delivered with the domestic hot water tank)
Booster heater Heat exchanger coil
15 15
16
FHL1...3
Boiler (field supply) Aquastat valve
(field supply) Shut-off valve
(field supply) Non-return valve
(field supply) Floor heating loop
(field supply)
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
Installation manual
Unit for air to water heat pump system
4PW56182-1
L
A
A
H
K1A
K2A
X2M
K1A
C
H
Com
K1A
KCR
Field wiring configuration A
NOTE
Configuration A
Make sure that auxiliary contact (A) has sufficient
H
Com
differential or time delay so as to avoid frequent
E(D/B)*/auto / Boiler
E(D/B)*
X2M
Boiler
thermostat input
changeover between the E(D/B)* unit and the boiler. If the auxiliary contact (A) is an outdoor
K 1A
1 2 3 4
K 2A
X Y
temperature thermostat, make sure to install the thermostat in the shade, so that it is not influenced or turned ON/OFF by the sun.
N
K1A K2A
Configuration B
Make sure that the bivalent hysteresis [C-04] has
Boiler thermostat input
Boiler thermostat input
sufficient differential to avoid frequent changeover between the E(D/B)* unit and the boiler. As the
Auxiliary contact (normal closed)
outdoor temperature is measured via the outdoor
Heating demand room thermostat (optional)
unit, air thermistor make sure to install the
Auxiliary relay for activation of E(D/B)* unit (field supply)
outdoor unit in the shade, so that it is not
influenced by the sun.
Auxiliary relay for activation of boiler (field supply)
Frequent switching may cause corrosion of the boiler in an early stage. Contact the manufacturer
Field wiring configuration B
of the boiler.
E(D/B)* EKRP1HB
During heating operation of the E(D/B)* unit, the unit will operate so as to achieve the target
1 2 3 4
KCR
leaving water temperature as set on the user
K1A
X1 X2
interface. When weather dependent operation is active, the water temperature is determined automatically depending on the outdoor
C
Com
H
X Y
temperature.
EKRTW*
Boiler
thermostat input
During heating operation of the boiler, the boiler
Boiler thermostat input
Boiler thermostat input
will operate so as to achieve the target leaving water temperature as set on the boiler controller.
Cooling demand room thermostat (optional) Heating demand room thermostat (optional) Common room thermostat (optional)
Never set the target leaving water temperature set point on the boiler controller above 131°F (55°C).
Make sure to only have 1 expansion vessel in the water circuit. An expansion vessel is already
Auxiliary relay for activation of bolier unit (field supply)
premounted in the Daikin unit.
Permission signal for the auxiliary boiler
NOTE
Make sure to configure the DIP switch SS2-3 on the
Operation
Configuration A
PCB of the E(D/B)* switchbox correctly. Refer to "Room thermostat installation configuration" on
page 23. When the room thermostat requests heating, either the E(D/B)* unit or the boiler starts operating, depending on the position of the auxiliary contact (A).
For configuration B: Make sure to configure the field
settings [C-02, C-03 and C-04] correctly. Refer to
"Bivalent operation" on page 33.
Configuration B
When the room thermostat requests heating, either the E(D/B)*
CAUTION
unit or the boiler starts operating, depending on the outdoor temperature (status of "permission signal for the auxiliary boiler").
Make sure that return water to the E(D/B)* heat exchanger never exceeds 131°F (55°C).
When the permission is given towards the boiler, the space heating operation by the E(D/B)* unit will be automatically
switched off.
For this reason, never put the target leaving water temperature set point on the boiler controller above 131°F (55°C) and install an aquastat(a) valve in the return water
ow of the E(D/B)* unit.
For more details see field setting [C-02~C-04].
Make sure that the non-return valves (field supply) are
correctly installed in the system. Make sure that the room thermostat (th) is not frequently
turned ON/OFF. Daikin shall not be held liable for any damage resulting
from failure to observe this rule.
(a) The aquastat valve must be set for 131°F (55°C) and must operate to close the
return water flow to the unit when the measured temperature exceeds 131°F (55°C). When the temperature drops to a lower level, the aquastat valve must operate to open the return water flow to the E(D/B)* unit again.
Manual permission towards the E(D/B)* unit on the boiler. In case only the E(D/B)* unit should operate in space
heating mode, disable the bivalent operation via setting [C-02].
In case only the boiler should operate in space heating mode, increase the bivalent ON temperature [C-03] to 77°F (25°C).
Installation manual
EDLQ036~054BA6VJU1 + EBLQ036~054BA6VJU1
10
Unit for air to water heat pump system
4PW56182-1
Loading...
+ 28 hidden pages