Contents
Contents
1. Safety Precautions ............................................. 2
2. Accessories ........................................................ 4
3. Remote controller installation procedure ........ 4
4. Functions and menu items of the
remote controller buttons ............................. 10
5. Power-on ........................................................... 12
6. Field settings .................................................... 15
7. Test operation method (SkyAir only) ............. 19
8. Checking procedure of Error History ............. 23
9. Registration method of the
Maintenance Contact information ................ 24
10. Conrmation of registered details ............... 25
11. Clock & Calendar ........................................... 26
12. Language ........................................................ 27
13. Prohibit Buttons ............................................. 28
14. Function Prohibition ...................................... 30
15. Prohibit Mode ................................................. 31
16. External Input Interlock Function ................. 33
17. Single and Dual setpoint mode .................... 39
18. Other Service Settings .................................. 40
19. Software update with Updater ...................... 42
Installation manual BRC2E52C7 / BRC3E52C7
1
2014.02
Safety Precautions

1. Safety Precautions

The original instructions are written in English. All other languages are translations of the original instructions.
 Also see the installation manual attached to the indoor unit.
Please read these Safety Precautions carefully before installing the remote controller.
● This manual classies the precautions into WARNING and CAUTION. They both contain important
information regarding safety. Be sure to follow all the precautions below.
WARNING
CAUTION
● After completing the installation, conduct a trial operation to check for faults and explain to the
customer how to operate the air conditioner with the aid of the operation manual. Ask the customer to store the installation manual along with the operation manual for future reference.
Failure to follow these instructions properly may result in personal
injury or loss of life.
Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the
circumstances.
WARNING
Ask your dealer or qualied personnel to carry out installation work. Do not attempt to install the remote controller yourself. Improper installation may result in water leakage, electric shocks or re.
Consult your local dealer regarding relocation and reinstallation of the remote controller. Improper installation work may result in leakage, electric shocks or re hazards.
Install the remote controller in accordance with the instructions in this installation manual. Improper installation may result in water leakage, electric shocks or re.
Be sure to use only the specied accessories and parts for installation work. Failure to use the specied parts may result in the unit falling down, water leakage, electric shocks or re.
Install the remote controller on a foundation strong enough to withstand the weight of the remote
controller.
Insufcient strength may result in the remote controller falling down and causing injury. Electrical work must be performed in accordance with the relevant local and national regulations and
with the instructions in this installation manual.
Be sure to use a dedicated power supply circuit only. Insufcient power circuit capacity and improper workmanship may result in electric shocks or re.
Always perform installation work with the power turned off. Touching electric parts may result in electric shock.
Do not disassemble, reconstruct or repair. This may result in electric shock and/or re.
Make sure that all wiring is secured, the specied wires are used and that there is no strain on the
terminal connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or re. The choice of materials and installations must comply with the applicable national and international
standards.
BRC2E52C7 / BRC3E52C7 Installation manual 4P368041-1
2014.02
2
Safety Precautions
CAUTION
To avoid leakage and electric shock due to entry of water or insects, ll the wiring through hole with putty.
To avoid electric shocks, do not operate with wet hands. Do not wash the remote controller with water, as this may result in electric shocks or re. Install the indoor and outdoor units, power cord and connection wires at least 1 meter away from
televisions or radios to prevent interference and noise. (Depending on the incoming signal strength, a distance of 1 meter may not be sufcient to eliminate
noise.)
Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts may deteriorate and fall off which could result in water leakage.
2. Where corrosive gas, such as sulphurous acid gas, is produced.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in
malfunctioning of the unit.
4. Where ammable gas may leak, where there is carbon bre or ignitable dust suspensions in
the air or where volatile ammables such as paint thinner or gasoline are handled. Operating the unit in such conditions may result in re.
5. High temperature areas or direct ames.
Overheating and/or re may occur.
6. Moist areas or places which may be exposed to water.
If water enters the remote controller, electric shock may be caused and the inner electronics
may fail.
When the thermostat function of the remote controller is used, select the installation location while considering it should be a place:
● Where the average temperature in the room can be detected.
● Which is not exposed to direct sunlight.
● Which is not near a heat source.
● Which is not affected by the outside air or air draught due to, for example, opening/closing of
doors, the air outlet of the indoor unit or the like.
Installation manual BRC2E52C7 / BRC3E52C7
3
2014.02

2. Accessories

2x
2x
1x
1x
Ø8-10
External view of the remote controller
CAUTION
The following accessories are included.
Wood screw +
wall plugs Small screw Clamp Wiring retainer
(Ø3.5×16) (M4×16)
2x

3. Remote controller installation procedure

3-1 Determine where to install the remote controller.
Make sure to follow "1. Safety Precautions" when determining the location.
3-2 Make a wiring through hole on the wall if the wires are
coming out from the rear.
Ø8-10
Lower case Through hole
40
48.5
Set the center of the wall hole to the center of the wiring through hole on the controller lower case when making the hole.
Accessories
Through hole
BRC2E52C7 / BRC3E52C7 Installation manual 4P368041-1
2014.02
If the hole size is too large or the location is not proper, the hole may come out from the
controller.
4
Remote controller installation procedure
CAUTION
3-3 Determine the direction of the controller wiring outlet (rear
outlet, left outlet, top left outlet, top center outlet).
3-3-1 Rear outlet 3-3-2 Left outlet
Cut off the resin area (hatched area). Cut off the thin area (hatched area) with
nippers or the like and then remove the burrs with a le or the like.
3-3-3 Top left outlet 3-3-4 Top center outlet
Cut off the thin area (hatched area) with nippers or the like and then remove the burrs with a le or the like.
Cut off the thin area (hatched area) with nippers or the like and then remove the burrs with a le or the like.
3-4 Conduct wiring.
1. The switchbox and the transmission wiring should not be attached.
2. Do not directly touch the remote controller PCB.
Wiring Specications
Wiring Type Sheathed vinyl cord or cable Wiring Size 0.75~1.25 mm² Wiring Length Max. 500 m
*This is the total length in the system when using group control.
Installation manual BRC2E52C7 / BRC3E52C7
5
(*)
2014.02
Remote controller installation procedure
±10 mm
Indoor unit
The sheath part in the remote controller case should be stripped following these instructions.
For easy wiring, it is better to
Peel the shield and sheath
Cutting guideline
of the wiring
Sheath stripping length:
● ±150 mm for top left outlet
● ±200 mm for top center outlet
Connect the terminals (P/P1, N/P2) of the remote controller to the terminals (P1, P2) of the indoor unit. (P1 and P2 have no polarities.)
keep ±10 mm difference between the length of the two wires.
3-4-1 Rear outlet
P1
P2
Lower case
Upper case
PCB
Clamp
Wiring fixing point
Clamp
-Cross-section
Secure the wiring at the wiring fixing point by using the attached clamp.
<Wiring fixing guideline>
BRC2E52C7 / BRC3E52C7 Installation manual 4P368041-1
2014.02
6
Remote controller installation procedure
Indoor unit
Upper case
Lower case
Upper case
Wiring retainer
Lower case
Upper case
Indoor unit
3-4-2 Left outlet
3-4-3 Top left outlet
P2P1
PCB
3-4-4 Upper center outlet
Wiring retainer
PCB
Wiring retainer
Wiring
-Cross-section
Indoor unit
P2P1
P2P1
Upper case
Install the attached wiring retainer to prevent wiring pinching as shown to the left.
Lower case
PCB
Installation manual BRC2E52C7 / BRC3E52C7
7
2014.02
Remote controller installation procedure
CAUTION
Wood screws (
(Installation pitch)
46
84
Switchbox for two units (with no cover)
Switchbox (field supply) (Use optional accessory KJB211A)
Small screws (M4×16)
● Do not perform wiring close to a power line in order to avoid electrical noise (external noise).
● Seal the wiring draw-in port securely with putty (eld supply) to prevent the entry of
insects or the like.
3-5 Fixing procedure of the lower case.
In the case of wiring a remote controller through the top center outlet or rear outlet, perform the wiring through the outlet hole in the lower case before it is installed on the wall.
3-5-1 Wall mounting
Secure by using the attached wood screws (2×).
Ø3.5×16)
3-5-2 Switchbox mounting
Secure by using the attached small screws (2×).
BRC2E52C7 / BRC3E52C7 Installation manual 4P368041-1
2014.02
8
Remote controller installation procedure
Switchbox for one unit
Small screws (M4×16)
CAUTION
Insert and twist the screwdriver lightly to remove the upper case.
Screwdriver
Lower case
Upper case
(with no cover)
Switchbox (field supply) (Use optional accessory KJB111A)
84
28
(Installation pitch)
● Select a at surface for installation if possible.
● Do not tighten the installation screws too much to avoid deforming the lower case.
3-6 Attach the upper case.
● Align the upper case with the tabs of the lower case (6 points) and insert the upper case.
● Be careful not to pinch the wiring when attaching.
● Peel off the protective seal which is attached to the upper case.
3-7 Remove the upper case.
Insert a slot screwdriver into the slots in the lower case (2 places) to remove the upper case.
NOTE
● The remote controller PCB is installed on the upper case. Be careful not to damage the PCB with the slot screwdriver.
● Take care that dust or moisture does not touch the PCB of the removed upper
Installation manual BRC2E52C7 / BRC3E52C7
9
case.
2014.02
Functions and menu items of the remote controller buttons

4. Functions and menu items of the remote controller buttons

4-1 Functions and menu items
(1) Operation Mode Selector button (11) LCD (with backlight)
(4) Up button (5) Down button (6) Right button (7) Left button
(9) Operation lamp (8) On/Off button
(3) Menu/Enter button
(10) Cancel button
(2) Fan Speed button
(1) Operation Mode Selector button
● Only available on the BRC2E
● This button is disabled by default for the
BRC3E. To enable, refer to "13. Prohibit
Buttons" on page 28.
● Press this button to select the operation
mode of your preference.
● Available modes may vary with the
connected model.
(2) Fan Speed button
● Used to change the fan speed.
● Available fan speeds may vary with the
connected model.
(3) Menu/Enter button
● This button is disabled by default. To
enable, refer to "4-2 Enable/disable the
Menu/Enter and Cancel button" on page 12.
● Used to display the main menu or enter the
selected item. (For details on the main menu, see the operation manual.)
BRC2E52C7 / BRC3E52C7 Installation manual 4P368041-1
2014.02
Airow Direction Individual Air Direction Quick Start
Ventilation
Energy Saving Options Schedule
Filter Auto Clean Maintenance Information
Conguration
Current Settings
Clock & Calendar Language
* Available menu items are depending on the
connected model.
(4) Up button
● Used to raise the set temperature.
● The next item on the upper side will be
highlighted. (Keep pressing the button to cycle through the values or items.)
● Used to change the selected item.
Main menu*
10
Functions and menu items of the remote controller buttons
CAUTION
(5) Down button
● Used to lower the set temperature.
● The next item on the lower side will be
highlighted. (Keep pressing the button to cycle through the values or items.)
● Used to change the selected item.
(6) Right button
● Used to highlight the next item on the
right-hand side.
● The display contents are changed to the
next screen.
(7) Left button
● Used to highlight the next items on the
left-hand side.
● The display contents are changed to the
previous screen.
(8) On/Off button
● Press to start or stop the air conditioner.
(9) Operation lamp (Green)
● This lamp lights up during operation.
● This lamp will blink if an error occurs.
● This lamp is not lit when the unit operation
is OFF.
(10) Cancel button
● This button is disabled by default. To
enable, refer to "4-2 Enable/disable the
Menu/Enter and Cancel button" on page 12.
● Used to return to the previous screen.
● Press and hold this button for 4 seconds or
longer to display the Service Settings menu.
(11) LCD (with backlight)
● The backlight will be lit for approximately
30 seconds when one of the buttons is pressed.
● The actions linked to the buttons, except for
the On/Off button, are not carried out when the backlight is not lit.
● When two remote controllers are used to
control a single indoor unit, the backlight of the remote controller which is operated rst will be lit.
Service Settings menu*
Test Operation
Maintenance Contact
Field Settings Min Setpoints Differential External Input Interlock Group Address Indoor unit Airnet Address Outdoor unit Airnet Address
Error History
Indoor Unit Status Outdoor Unit Status Forced Fan ON Switch Main Sub Controller Filter Indicator
Test Filter Auto Clean
Brush/Filter Ind Disable Filter Auto Clean
* Available menu items are depending on the
connected model.
● To operate the Up/Down/Left/Right button, always press
● The Menu/Enter and the Cancel button are disabled by default.
To enable, refer to "4-2 Enable/disable the Menu/Enter and Cancel button"
on page 12.
● The Menu/Enter and Cancel button need to be disabled again after changes are made.
● For the BRC3E, the Operation Mode Selector button is locked by default. To unlock, refer to "13. Prohibit Buttons" on page 28.
Installation manual BRC2E52C7 / BRC3E52C7
11
, , , or .
2014.02
4-2 Enable/disable the Menu/Enter and Cancel button
2 2
2 2
Instructions for manipulating the buttons will appear.
<Service Settings>
Highlighted display (selected items)
Test Operation Maintenance Contact
Field Settings
Min Setpoints Differential External Input Interlock Group Address
1/3Service Settings
SettingReturn
CAUTION
To enable the Menu/Enter and Cancel button in the Basic screen, proceed as follow:
12. Keep the button pressed.
13. Push the 3 indicated keys
simultaneously while keeping the
button pressed. To disable the Menu/Enter and Cancel button in the Basic screen, follow the same procedure.
4-3 Description of button operation

5. Power-on

● It is not possible to use two remote controllers and the Digital Input Adapter BRP7A* together.
The Digital Input Adapter will not work and will be in an error state when a sub remote controller is detected.
● When controlling one indoor unit with two remote controllers, one remote controller needs to be set as the main remote controller and one as the sub remote controller. This selection needs to be made once during start up and can be changed afterwards in the Service Settings menu.
Power-on
1
● Check that the indoor/outdoor unit wiring is completed.
● Check that the switchbox cover of the indoor and outdoor units are closed before powering on.
2014.02
BRC2E52C7 / BRC3E52C7 Installation manual 4P368041-1
12
Power-on
If one indoor unit is controlled by a remote controller
Turn on the power.
5-1 5-2 "Checking the connection.
Please stand by." is displayed.
5-3 The Basic screen is displayed.
<Main remote controller>
5-2
Checking the connection. Please stand by.
Main RC
<Basic screen>
5-3
If one indoor unit is controlled by 2 remote controllers
Put on the power. <Main remote controller> <Sub remote controller>
5-4 5-5 "Checking the connection.
Please stand by." is displayed.
5-5
Checking the connection. Please stand by.
NOTE
When the text on the left is displayed, the backlight does not light up when one of the buttons is pressed.
5-5
Checking the connection. Please stand by.
Main RC
Main RC
NOTE
When the above text is displayed, the backlight does not light up when one of the buttons is pressed.
5-6
If the sub remote controller is not set when powering on when one indoor unit is controlled by two remote controllers, "Error code U5" is displayed in the connection checking screen.
5-7 Select the sub remote controller
by pressing the Operation Mode Selector button of either one of
the remote controllers for
4 seconds or longer.
Installation manual BRC2E52C7 / BRC3E52C7
13
5-6
Error Code U5 Checking the connection.
Please stand by.
Main RC
5-6
Error Code U5 Checking the connection.
5-7
Please stand by.
Main RC
Press and hold the Operation mode selector button of the sub remote
controller for 4 seconds or
longer.
2014.02
Loading...
+ 30 hidden pages