16. External Input Interlock Function ................. 33
17. Single and Dual setpoint mode .................... 39
18. Other Service Settings .................................. 40
19. Software update with Updater ...................... 42
Installation manual BRC2E52C7 / BRC3E52C7
1
4P368041-1
–
2014.02
Safety Precautions
1. Safety Precautions
The original instructions are written in English. All other languages are translations of the original
instructions.
Also see the installation manual attached to the indoor unit.
Please read these Safety Precautions carefully before installing the remote controller.
● This manual classies the precautions into WARNING and CAUTION. They both contain important
information regarding safety. Be sure to follow all the precautions below.
WARNING
CAUTION
● After completing the installation, conduct a trial operation to check for faults and explain to the
customer how to operate the air conditioner with the aid of the operation manual. Ask the customer
to store the installation manual along with the operation manual for future reference.
Failure to follow these instructions properly may result in personal
injury or loss of life.
Failure to observe these instructions properly may result in property
damage or personal injury, which may be serious depending on the
circumstances.
WARNING
Ask your dealer or qualied personnel to carry out installation work.
Do not attempt to install the remote controller yourself. Improper installation may result in water
leakage, electric shocks or re.
Consult your local dealer regarding relocation and reinstallation of the remote controller.
Improper installation work may result in leakage, electric shocks or re hazards.
Install the remote controller in accordance with the instructions in this installation manual.
Improper installation may result in water leakage, electric shocks or re.
Be sure to use only the specied accessories and parts for installation work.
Failure to use the specied parts may result in the unit falling down, water leakage, electric shocks
or re.
Install the remote controller on a foundation strong enough to withstand the weight of the remote
controller.
Insufcient strength may result in the remote controller falling down and causing injury.
Electrical work must be performed in accordance with the relevant local and national regulations and
with the instructions in this installation manual.
Be sure to use a dedicated power supply circuit only. Insufcient power circuit capacity and improper
workmanship may result in electric shocks or re.
Always perform installation work with the power turned off.
Touching electric parts may result in electric shock.
Do not disassemble, reconstruct or repair.
This may result in electric shock and/or re.
Make sure that all wiring is secured, the specied wires are used and that there is no strain on the
terminal connections or wires.
Improper connections or securing of wires may result in abnormal heat build-up or re.
The choice of materials and installations must comply with the applicable national and international
To avoid leakage and electric shock due to entry of water or insects, ll the wiring through hole with
putty.
To avoid electric shocks, do not operate with wet hands.
Do not wash the remote controller with water, as this may result in electric shocks or re.
Install the indoor and outdoor units, power cord and connection wires at least 1 meter away from
televisions or radios to prevent interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter may not be sufcient to eliminate
noise.)
Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen).
Plastic parts may deteriorate and fall off which could result in water leakage.
2. Where corrosive gas, such as sulphurous acid gas, is produced.
Corroding of copper pipes or soldered parts may result in refrigerant leakage.
3. Near machinery emitting electromagnetic radiation.
Electromagnetic radiation may disturb the operation of the control system and result in
malfunctioning of the unit.
4. Where ammable gas may leak, where there is carbon bre or ignitable dust suspensions in
the air or where volatile ammables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in re.
5. High temperature areas or direct ames.
Overheating and/or re may occur.
6. Moist areas or places which may be exposed to water.
If water enters the remote controller, electric shock may be caused and the inner electronics
may fail.
When the thermostat function of the remote controller is used, select the installation location while
considering it should be a place:
● Where the average temperature in the room can be detected.
● Which is not exposed to direct sunlight.
● Which is not near a heat source.
● Which is not affected by the outside air or air draught due to, for example, opening/closing of
doors, the air outlet of the indoor unit or the like.
Installation manual BRC2E52C7 / BRC3E52C7
3
4P368041-1
–
2014.02
2. Accessories
2x
2x
1x
1x
Ø8-10
External view of the remote controller
CAUTION
The following accessories are included.
Wood screw +
wall plugsSmall screwClampWiring retainer
(Ø3.5×16)(M4×16)
2x
3. Remote controller installation
procedure
3-1 Determine where to install the remote controller.
Make sure to follow "1. Safety Precautions" when determining the location.
3-2 Make a wiring through hole on the wall if the wires are
coming out from the rear.
Ø8-10
Lower case
Through hole
40
48.5
Set the center of the wall hole
to the center of the wiring
through hole on the controller
lower case when making the
hole.
● Do not perform wiring close to a power line in order to avoid electrical noise (external
noise).
● Seal the wiring draw-in port securely with putty (eld supply) to prevent the entry of
insects or the like.
3-5 Fixing procedure of the lower case.
In the case of wiring a remote controller through the top center outlet or rear outlet, perform the
wiring through the outlet hole in the lower case before it is installed on the wall.
Airow Direction
Individual Air Direction
Quick Start
Ventilation
Energy Saving Options
Schedule
Filter Auto Clean
Maintenance Information
Conguration
Current Settings
Clock & Calendar
Language
* Available menu items are depending on the
connected model.
(4) Up button
● Used to raise the set temperature.
● The next item on the upper side will be
highlighted.
(Keep pressing the button to cycle through
the values or items.)
● Used to change the selected item.
Main menu*
10
Functions and menu items of the remote controller buttons
CAUTION
(5) Down button
● Used to lower the set temperature.
● The next item on the lower side will be
highlighted.
(Keep pressing the button to cycle through
the values or items.)
● Used to change the selected item.
(6) Right button
● Used to highlight the next item on the
right-hand side.
● The display contents are changed to the
next screen.
(7) Left button
● Used to highlight the next items on the
left-hand side.
● The display contents are changed to the
previous screen.
(8) On/Off button
● Press to start or stop the air conditioner.
(9) Operation lamp (Green)
● This lamp lights up during operation.
● This lamp will blink if an error occurs.
● This lamp is not lit when the unit operation
is OFF.
(10) Cancel button
● This button is disabled by default. To
enable, refer to "4-2 Enable/disable the
Menu/Enter and Cancel button" on
page 12.
● Used to return to the previous screen.
● Press and hold this button for 4 seconds or
longer to display the Service Settings menu.
(11) LCD (with backlight)
● The backlight will be lit for approximately
30 seconds when one of the buttons is
pressed.
● The actions linked to the buttons, except for
the On/Off button, are not carried out when
the backlight is not lit.
● When two remote controllers are used to
control a single indoor unit, the backlight of
the remote controller which is operated rst
will be lit.
Service Settings menu*
Test Operation
Maintenance Contact
Field Settings
Min Setpoints Differential
External Input Interlock
Group Address
Indoor unit Airnet Address
Outdoor unit Airnet Address
Error History
Indoor Unit Status
Outdoor Unit Status
Forced Fan ON
Switch Main Sub Controller
Filter Indicator
Test Filter Auto Clean
Brush/Filter Ind
Disable Filter Auto Clean
* Available menu items are depending on the
connected model.
● To operate the Up/Down/Left/Right button, always press
● The Menu/Enter and the Cancel button are disabled by default.
To enable, refer to "4-2 Enable/disable the Menu/Enter and Cancel button"
on page 12.
● The Menu/Enter and Cancel button need to be disabled again after changes are made.
● For the BRC3E, the Operation Mode Selector button is locked by default. To unlock, refer to "13. Prohibit Buttons" on page 28.
Installation manual BRC2E52C7 / BRC3E52C7
11
, , , or .
4P368041-1
–
2014.02
4-2 Enable/disable the Menu/Enter and Cancel button
2
2
2
2
Instructions for manipulating
the buttons will appear.
<Service Settings>
Highlighted display (selected items)
Test Operation
Maintenance Contact
Field Settings
Min Setpoints Differential
External Input Interlock
Group Address
1/3Service Settings
SettingReturn
CAUTION
To enable the Menu/Enter and Cancel button in
the Basic screen, proceed as follow:
12. Keep the button pressed.
13. Push the 3 indicated keys
simultaneously while keeping the
button pressed.
To disable the Menu/Enter and Cancel button in
the Basic screen, follow the same procedure.
4-3 Description of button operation
5. Power-on
● It is not possible to use two remote controllers and the Digital Input Adapter BRP7A* together.
The Digital Input Adapter will not work and will be in an error state when a sub remote
controller is detected.
● When controlling one indoor unit with two remote controllers, one remote controller needs to
be set as the main remote controller and one as the sub remote controller.
This selection needs to be made once during start up and can be changed afterwards in the
Service Settings menu.
Power-on
1
● Check that the indoor/outdoor unit wiring is completed.
● Check that the switchbox cover of the indoor and outdoor units are closed before powering on.
If one indoor unit is controlled by a remote controller
Turn on the power.
5-1
5-2 "Checking the connection.
Please stand by." is displayed.
5-3 The Basic screen is displayed.
<Main remote controller>
5-2
Checking the connection.
Please stand by.
Main RC
<Basic screen>
5-3
If one indoor unit is controlled by 2 remote controllers
Put on the power.<Main remote controller><Sub remote controller>
5-4
5-5 "Checking the connection.
Please stand by." is displayed.
5-5
Checking the connection.
Please stand by.
NOTE
When the text on the
left is displayed, the
backlight does not
light up when one of
the buttons is pressed.
5-5
Checking the connection.
Please stand by.
Main RC
Main RC
NOTE
When the above text is displayed, the backlight
does not light up when one of the buttons is
pressed.
5-6
If the sub remote controller is not
set when powering on when one
indoor unit is controlled by two
remote controllers, "Error code U5"
is displayed in the connection
checking screen.
5-7 Select the sub remote controller
by pressing the Operation Mode
Selector button of either one of
the remote controllers for
4 seconds or longer.
Installation manual BRC2E52C7 / BRC3E52C7
13
5-6
Error Code U5
Checking the connection.
Please stand by.
Main RC
5-6
Error Code U5
Checking the connection.
5-7
Please stand by.
Main RC
Press and hold the
Operation mode selector
button of the sub remote
controller for 4 seconds or
4P368041-1
longer.
–
2014.02
Loading...