Indoor Unit AHQ71AV1
G
B
DE
C
F
A
Dimension
Model
A B C D E F G
AHQ71AV1 1080 65 630 400 230 218 928
Indoor Unit AHQ100/125AV1
All dimensions are in mm
A
B
E
C
D
F
G
Dimension
Model
A B C D E F G
AHQ100AV1 1490 1308 74 1538 268 635 259
AHQ125AV1 1738 1556 74 1786 268 635 259
OUTLINE AND DIMENSIONS
All dimensions are in mm
English
Original Instruction
1-1
INSTALLATION MANUAL
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference.
This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
This appliance is not intended for use by persons, including children, with reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
SAFETY PRECAUTIONS
English
Installation and maintenance should be performed by qualiÞ ed
! WARNING ! CAUTION
•
persons who are familiar with local code and regulation, and
experienced with this type of appliance.
All Þ eld wiring must be installed in accordance with the national
•
wiring regulation.
Ensure that the rated voltage of the unit corresponds to that of
•
the name plate before commencing wiring work according to
the wiring diagram.
The unit must be GROUNDED to prevent possible hazard due
•
to insulation failure.
All electrical wiring must not touch the refrigerant piping, or
•
any moving parts of the fan motors.
ConÞ rm that the unit has been switched OFF before installing
•
or servicing the unit.
Disconnect from the main power supply before servicing the
•
air conditioner unit.
DO NOT pull out the power cord when the power is ON. This
•
may cause serious electrical shocks which may result in Þ re
hazards.
Keep the indoor and outdoor units, power cable and transmission
•
wiring, at least 1m from TVs and radios, to prevent distorted
pictures and static. {Depending on the type and source of the
electrical waves, static may be heard even when more than 1m
away}.
Please take note of the following important points when installing.
Do not install the unit where leakage of ß ammable gas may occur.
•
If gas leaks and accumulates around the unit, it may cause
Þ re ignition.
•
Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it may
cause water leakage which will dampen the furniture.
•
Do not overcharge the unit.
This unit is factory pre-charged.
Overcharge will cause over-current or damage to the
compressor.
•
Ensure that the unit’s panel is closed after service or
installation.
Unsecured panels will cause the unit to operate noisily.
•
Sharp edges and coil surfaces are potential locations which
may cause injury hazards.
Avoid from being in contact with these places.
•
Before turning off the power supply, set the remote
controller’s ON/OFF switch to the “OFF” position to prevent
the nuisance tripping of the unit. If this is not done, the unit’s
fans will start turning automatically when power resumes, posing
a hazard to service personnel or the user.
•
Do not operate any heating apparatus too close to the air
conditioner unit. This may cause the plastic panel to melt or
deform as a result of the excessive heat.
•
Do not install the units at or near doorway.
•
Do not operate any heating apparatus too close to the air
conditioner unit or use in room where mineral oil, oil vapour
or oil steam exist, this may cause plastic part to melt or
deform as a result of excessive heat or chemical reaction.
•
When the unit is used in kitchen, keep ß our away from going
into suction of the unit.
•
This unit is not suitable for factory used where cutting oil
mist or iron powder exist or voltage ß uctuates greatly.
•
Do not install the units at area like hot spring or oil reÞ nery
plant where sulphide gas exists.
•
Ensure the color of wires of the outdoor unit and the terminal
markings are same to the indoors
•
IMPORTANT: DO NOT INSTALL OR USE THE AIR
CONDITIONER UNIT IN A LAUNDRY ROOM.
Don’t use joined and twisted wires for incoming power supply.
•
Avoid direct contact of any coil treatment cleaners on plastic part. This
•
may cause plastic part to deform as a result of chemical reaction.
For any enquiries on spare parts please contact your
•
authorized dealer.
The equipment is not intended for use in a potentially
•
explosive atmosphere.
respectively.
Disposal requirements
NOTICE
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted
household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other
parts must be done by a qualiÞ ed installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed
of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or
local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.
1-3
Air Filters
(Inside Air Intake Grille)
TO OUTDOR UNIT
Wrap the Insulated pipe with the
Þ nishing tape from bottom to top
Air Discharge Louver
Air Intake Grille
INSTALLATION DIAGRAM (AHQ71AV1)
Top Panel
Bottom Panel
Figure A
Preliminary Site Survey
Voltage supply ß uctuation must not exceed ±10% of the
rated voltage. Electricity supply lines must be independent
of welding transformers which can cause high supply
ß uctuation.
Ensure that the installation location is convenient for wiring
and piping.
•
•
Standard Mounting
Ensure that the overhead supports are strong enough to hold
the weight of the unit. Position the hanger rods (wall mounting
bracket for ß oor standing), and check for its alignment with
the unit as shown in Figure A. Also, check that the hangers
are secured and the base of the fan coil unit is leveled in both
horizontal directions, taking into account
the gradient for
drainage ß ow as recommended in Figure B.
A
BC
H G
E D
F
Figure B
10mm or more
All dimensions are in mm
INSTALLATION OF THE INDOOR UNIT (AHQ71AV1)
Thermal insulation
Dimension
Model
A B C D E F G H
AHQ71AV1 1073 534 268 135 336 630 145 485
1-4
Please ensure that the following steps are taken:
400mm
or more
250mm or more
1m or more
Floor Standing Type
250mm or more
Utensils, furnitures or built-in
architectural features must not
protrude more than 250mm
Drainage Pipe
250mm or less
300mm
(Min.)
500mm or more
10mm
Indoor Unit
Hanger Bracket
Nut
Washer
Washer
Nut
Floor
2300mm or more
Ceiling
Figure C
Unit installation should be tilted at least 10mm as recommended in Figure B.
•
The drain pipe slope shall be kept at least 1:100.
•
Provide clearance for easy servicing and optimal air ß ow as shown in Figure C.
•
•
The indoor unit must be installed such that there is no short circuit of the cool discharge air with the warm return air.
•
Do not install the indoor unit where there is direct sunlight shining on the unit. The location should be suitable for piping
and drainage installation. The unit must be a large distance away from the door.
English
1-5
Install the Suspension Bolts
Install the suspension bolts so that it can support the indoor unit.
Adjust distance to ceiling before installation.
Refer to the dimension given to install the unit.
Install the Indoor Units
Insert the suspension bolts into the Þ ttings of the hanger bracket.
Set the nuts and washer on the both side of the metal Þ ttings.
Secure it with nuts.
Attach the hanger cover (4 pcs) to the units.
1.
2.
3.
1.
2.
3.
4.
Suspension Bolt
Hanger Cover
Hanger Cover
Suspension Bolt
Hanger Rod
Installation Floor Standing Type
28mm
479mm
547mm or more
Mounting Bracket
509mm
458mm
301mm or more
759mm or more
Rear Piping Hole
Floor
123mm
78mm
40mm
307mm
Installation Ceiling Type
UNDER CEILING INSTALLATION (AHQ71AV1)
1-6