About this Manual ....................................................................................................................................... i
Product Support ......................................................................................................................................... vi
This manual gives installation and operation information for the Comtech EF Data
MDX420 SkyWire™ Satellite Network Gateway. This manual is intended for anyone who
installs or operates the unit.
Patents and Trademarks
See all of Comtech EF Data’s Patents and Patents Pending at
http://patents.comtechefdata.com.
Comtech EF Data acknowledges that all trademarks are the property of the trademark
owners.
Copyright
2013 Comtech EF Data Corp. All rights reserved.
Cautions and Warnings
WARNING indicates a potentially hazardous situation that, if not avoided, could result
in death or serious injury.
CAUTION indicates a hazardous situation that, if not avoided, may result in minor or
moderate injury. CAUTION may also be used to indicate other unsafe practices or
risks of property damage.
IMPORTANT or NOTE indicates information critical for proper equipment function, or a
statement that is associated with the task being performed.
The MDX420 has been shown to comply with the EN 60950-1 Safety of Information
Technology Equipment (including electrical business machines) safety standard.
The equipment is rated for a nominal operating range of 100 - 240 volts AC or an appropriately
equipped DC option, nominal operating range is 48+/-5 volts DC . The unit has a maximum power
consumption of 250 watts.
Battery
WARNING
The modem contains a Lithium Battery. DANGER OF EXPLOSION EXISTS if the
battery is incorrectly replaced. Replace only with the same or equivalent type
recommended by the manufacturer. Dispose of used batteries in accordance
with local and national regulations.
Grounding
Fuses
CAUTION
CORRECT GROUNDING PROTECTION REQUIRED: The installation instructions
require that the integrity of the protective earth must be ensured and that the
equipment shall be connected to the protective earth connection at all times.
Therefore, it is imperative during installation, configuration, and operation that
the user ensures that the unit has been properly grounded using the ground
stud provided on the rear panel of the unit.
In Finland: "Laite on liitettävä suojamaadoituskoskettimilla varustettuun
pistorasiaan."
In Norway: “Apparatet må tilkoples jordet stikkontakt.”
In Sweden: “Apparaten skall anslutas till jordat uttag.”
The MDX420 must not be operated in an environment where the unit is exposed to precipitation;
condensation; humid atmospheres above 95% RH; altitudes (unpressurized) greater than 2000
metres; excessive dust or vibration; flammable gases, corrosive or explosive atmospheres; or
extremes of temperature outside the ambient range 0 to +50°C. Maximum storage temperature
allowed is -20 to +70°C.
Operation in vehicles or other transportable installations that are equipped to provide a stable
environment is permitted. If such vehicles do not provide a stable environment, safety of the
equipment to EN 60950 may not be guaranteed.
Installation
CAUTION
PROPER GROUNDING PROTECTION IS REQUIRED – REFER TO THE
GROUNDING ‘CAUTION’ NOTE PROVIDED ON THE PREVIOUS PAGE. The
MDX420 is designed for connection to a power system that has separate ground,
line and neutral conductors. The equipment is not
power system that has no direct connection to ground.
designed for connection to a
The installation and connection to the line supply must be made in compliance to local or national
wiring codes and regulations.
The MDX420 is shipped with a line inlet cable suitable for use in the country of operation. If it is
necessary to replace this cable, ensure the replacement has an equivalent specification.
Examples of acceptable ratings for the cable include HAR, BASEC and HOXXX-X. Examples of
acceptable connector ratings include VDE, NF-USE, UL, CSA, OVE, CEBEC, NEMKO, DEMKO,
BS1636A, BSI, SETI, IMQ, KEMA-KEUR and SEV.
International Symbols
Symbol Definition Symbol Definition
Alternating Current
Fuse
Telecommunications Terminal Equipment Directive
In accordance with the Telecommunications Terminal Equipment Directive 91/263/EEC, this
equipment should not be directly connected to the Public Telecommunications Network.
Protective Earth
Chassis Ground
CE Mark
Comtech EF Data declares that the MDX420 modem meets the necessary requirements for the
CE Mark.
This unit satisfies (with exemption s) the requirem ents specifie d in the European Uni on Directive on th e
Restriction of Hazardous Substances, Directive 2002/95/EC (EU RoHS).
EMC (Electromagnetic Compatibility)
In accordance with European Directive 2004/108/EEC, the MDX420 has been shown, by
independent testing, to comply with the following standards:
Emissions:EN 55022 Class B - Limits and methods of measurement of radio interference
characteristics of Information Technology Equipment.
(Also tested to FCC Part 15 Class B.)
Immunity:EN 55024 – Information Technology Equipment: Immunity Characteristics,
Limits, and Methods of Measurement.
Additionally, the MDX420 has been shown to comply with the following standards:
EN 61000-3-2 – Harmonic Currents Emission;
EN 61000-3-3 – voltage Fluctuations and Flicker.
Connections to the transmit and receive IF ports should be made using a good quality
coaxial cable. For example, RG58 or RG59 for BNC IF connectors and LMR200,
LMR240 or equivalent for the L-band SMA IF ports.
All 'D' type connectors attached to the rear panel must have back-shells that provide
continuous metallic shielding. Cable with a continuous outer shield (either foil or braid, or
both) must be used, and the shield must be bonded to the back-shell.
The equipment must be operated with its cover on at all times. If it becomes necessary to
remove the cover, the user should ensure that the cover is correctly re-fitted before
normal operation commences.
This manual provides detailed information for the Radyne SkyWire MDX420 Satellite Network Gateway.
When describing the SkyWire gateway, it will be referred to as “the MDX420”, “the gateway”, “the network
gateway”, or “the satellite gateway”. The next few sections will describe theory of operation, setup,
accessing and monitoring the gateway.
The Radyne SkyWire MDX420 Satellite Network Gateway (
Gateway
designed for satellite IP networks.
) is a Closed Network Time Division Multiple Access (TDMA) Satellite Gateway specifically
Figure 1-1 SkyWire Satellie Network
Figure 1-1 SkyWire Satellie Network Gateway
This satellite gateway combines unsurpassed performance with user-friendly remote access. Monitor and
Control (M&C) functions are available through a secure SNMP V1, V2 or V3 interface. Operating
parameters, such as symbol and data rates, FEC code rate, modulation type, IF/RF frequencies, and
three levels of capacity management can be readily set and changed through the user interface by
authorized earth station operations personnel.
The gateway operates over a data rate range of 328kbps to 21.6Mbps with a symbol rate range of
256ksps to 10Msps.
The gateway's data interface is an Ethernet Bridge 10/100/1000 Base-T interface.
The gateway supplies DC power to the LNB. The gateway has an optional feature to supply 24 or 48
volts to the BUC and an optional feature for a high stability 10MHz reference to the BUC and LNB. The
capability to enable and disable the BUC/LNB voltages and 10MHz reference is available via the Ethernet
SNMP control port. In addition, the gateway monitors both the current and the voltage at the output of the
Tx and Rx Ports, thus providing the user verification of overall system status.
The MDX420 satellite gateway is based on a single signal processing printed circuit card desi gned with
one to four optional plug in burst demodulator daughter cards. The minimum configuration consists of a
single signal processing card and a single burst demodulator daughter card with the option to add three
additional burst demodulators for a total of four burst demodulators. The single signal processing printed
circuit board consists of an L-Band burst modulator, the Ethernet interface, and a digital baseband
processor.
Within a SkyWire TDMA satellite network, a gateway has the ability to communicate with up to 32 full
mesh remote sites in a single 1 RU chassis. All units at all locations are based on this sin gle hardware
platform.
Each gateway supports:
One burst Modulator (MOD)
Up to four burst Demods (DEMOD)
Network Control Module for distributed intelligence (NCM)
All gateway IP data traffic passes through a common 10/100/1000 bridge interface.
Optional BUC Power and 10Mhz Reference
MODDEMOD 1DEMOD 4DEMOD 3DEMOD 2
Each gateway can:
Transmit one carrier
Simultaneously receive four carriers that do not need to be of the same configuration.
Support a distributed leaderless TDMA network, meaning that there is no HUB and no
single point of failure. The network administrator can log-in through any gateway in a
share group and change the network parameters of any gateway in the share group
In a traditional Frequency Division Multiple Access (FDMA) system, a transponder resource is shared
between a number of earth stations based on frequency allocations. In a FDMA system, an earth station
will continuously transmit a single carrier on specific frequency broadcasting to a single receiver or
multiple receivers at different earth stations.
In a TDMA system, a frequency allocation is shared between a number of earth stations based on time
‘slots’. Within a TDMA system, the transponder receives a sequential burst of transmissions from multiple
earth stations broadcasting out to multiple receivers. In traditional “non-skywire” TDMA systems, the time
plan for each earth station’s burst is determined by a central control system at a central location.
Time
Frequency
T
RX
T
RX
T
RX
Figure 1-3 TDMA Access Example
Figure 1-3 shows an example of TDMA access of the satellite frequency allocation. In the example
above, 3 remote sites are sharing a frequency allocation with each site transmitting sequentially. As
stated above, in a TDMA platform, multiple sites “time share” their transmission on the same frequency
carrier and data rates. The aggregate transmission will be received by a hub or participating remotes
allowing each remote to determine which data they need to pass on to the local LAN. The aggregate
transmission reflects multiple bursts from all 3 earth stations transmitting their IP data over satellite to the
all sites in the network.
The MDX420 gateway is designed for mesh communications. The gateway will transmit on a fixed carrier
frequency and has the capability to receive up to 4 other carriers either on the same satellite or other
satellites. A TDMA shared carrier can support up to 8 gateways all communicating on the same
frequency allocation.
A SkyWire gateway determines the number of bursts it will transmit over satellite. The number of burst
slots per frame is based on the local LAN needs and the needs of the other remotes in the share group.
The gateway uses this information in conjunction with the operator specified Dedicated Information Rate
(DIR), Committed Information Rate (CIR), and Maximum Information Rate (MIR) to determine how many
burst slots it is allocated per frame.
Dedicated Information Rate - throughput in Kbits per second that cannot be used by anyone except the
assigned gateway.
Committed Information Rate – throughput that is available to the user when ever requested, but is pooled
when not in needed by the assigned gateway.
Maximum Information Rate – maximum throughput allowed by the gateway also referred to as the
burstable throughput.
The MDX420 can support up to four burst demodulators. Each burst demodulator receives a single
carrier or “share group” supporting up to 8 gateways. With two burst demodulators installed into an
MDX420, a mesh network can now support up to 16 gateways with a single satellite hop con nectivity.
Since the MDX420 can have up to 4 burst demodulators installed, a gateway can receive 4 share groups
supporting up to 32 gateways in a mesh network using only 1 burst modulator.
Figure 1-4 SkyWire RX System with Four Share Groups
The example below (Figures 1-7 and 1-8) shows two share groups consisting of 16 gateways. Each
gateway has a single MDX420 consisting of a single burst modulator and two burst demodulators. The
addition of a second burst demodulator allows the network to support 16 gateways with a single hop.
1.4.4 SkyWire Eight Site Hub / Spoke (Star) Network Example
The example below (Figure 1-9) shows an eight site Hub / Spoke network with a 2Mbps outbound shared
carrier and a 4Mbit/s inbound shared carrier. Each gateway has a single MDX420 con sisting of a single
burst modulator and two burst demodulators. Remotes have a 256kbps CIR with burstable through-put
up to 4Mbps.
Figure 1-9 Network Diagram of a HUB / SPOKE (Star) Network
The IP data interface on the MDX420 is a dual port 10/100/1000 Ethernet bridge operating at the data link
layer (layer 2). Refer to Appendix C for technical overview of the Gigabit Ethernet Bridge interface.
IP Data Ethernet interface supports:
Automatic learning & aging (stores forwarding database)
Auto Crossover
Auto Polarity
Auto Negotiation (Flow control)
Embedded Quality of Service
CRC Control
For the Ethernet Bridge interface to operate in a normal condition, there is nothing to configure, simply
connect to one of the ports on the back panel.
The Ethernet Bridge interface allows all higher level protocols like IPv4, IPv6, DHCP, UDP, TCP, HTTP,
and FTP to pass transparently.
1.5.1 Quality of Service (QoS)
Most networks are comprised of various types of real time and non real time services. SkyWire offers
basic layer 2/3 QoS control, allowing the user to prioritize data queues ensuring that higher priority traffic,
like voice and network control, are not backed up behind lower priority traffic. SkyWire also supports
queuing features that allow the user to prioritize queuing in different ways.
SkyWire Quality of Service (QoS) features includes:
Normal - Uses the following formats (IEEE 803.3ac Tag containing IEEE 802.1p priority
information provided by an external device, Type of Service field (RFC 791) or Differentiated
Services field (RFC 2474) contained in an IPv4 header and Traffic Class field (RFC 2460)
contained in an IPv6 header.
Port Based - In this mode, physical port (J3) has the highest priority and physical port (J4)
has the lowest priority. The Port Based priority overrides any other priority
SkyWire QoS QUEUE features include:
Fair Weighted - Selects the queue weighting of 8,4,2,1 allowing higher priority traffic to pass
through more quickly and insures even the lowest priority traffic gets some bandwidth.
Packets are processed in a weighted round robin manner with 8 having the highest priority.
Strict Priority - Ensures that the higher priority traffic will always be transmitted before any
lower priority traffic. With this setting, higher priority traffic will be immediately transmitted
until the buffer is empty starving all lower priority traffic until upper priority traffic is cleared.
In certain circumstances it may be desirable to have the Ethernet Interface to operate in a FIFO like mode
with no reordering of packets. This can be done by using a single port and setting the Ethernet QoS type
to Port Base and the Ethernet QoS Queue to strict priority. This will allow packets to be transmitted in the
exact order in which they are received.
1.5.2 CRC Control Satellite Packet Error Checking
Packet error checking is a standard part of any terrestrial Ethernet system and is performed using the
CRC contained in the layer 2 Ethernet wrapper. The CRC is used as a checksum to detect alteration of
data during transmission. When a CRC error is encountered, the packet is typically discarded by the
router, switch, or hub in which the error was detected.
A similar methodology is utilized over the satellite link where bit errors result in a corrupted packet with a
bad CRC. For most situations, the standard process of discarding these packets when they are
encountered is the preferred methodology as the packet can simply be retransmitted.
However, there are some cases where the end device would rather receive the erred packet than no
packet at all. Scenarios involving cryptography or where the end device has additional error correction
capability are examples of two such situations. For these customers, the gateway provides the ability to
turn off the satellite packet error checking and packets with bit errors will be output with a valid CRC so
that they will properly pass to the connecting router or switch. Checking the CRC Control box in the
Sattelite Demod Configuration GUI (normal operation) will look for a valid CRC and if not found will drop
the Ethernet datagram. Unchecking the CRC control box will append a valid CRC to a potentially corrupt
Ethernet datagram and pass the datagram to the next device in the chain. Note: CRC control only
functions from the flow of satellite to the Ethernet LAN. Ethernet LAN to satellite flow will always drop bad
CRC datagrams regardless of selection.
Regardless of the configuration of the CRC Control function, enabled or disabled, SkyWire maintains and
reports satellite link statistics on total packets, erred packets, and packet error rate (PER).
Hardware and software options are available at time of order. Some options are field
upgradeable.
2.2 Standard Configuration
The MDX420 comes standard with the following features:
AC Power
QPSK modulation with .710 and .793 FEC selection
Standard or Enhanced Eb/No operation
1Mbps maximum transmit data rate
1 Burst Modulator installed
1 Burst Demodulator installed
2.3 Hardware Options
The items below identify specific hardware options and the availability of field upgrade (FLD) or
only at time of order (TOR). Refer to Section 7.3.5, for information on how to view these features
on the MDX420 GUI interface.
DC Input Prime Power (TOR)- Allows for an optional 48 Volt DC Input Power Source.
This is a factory upgrade only.
BUC Power via the IF Output Connector (TOR)- Optional power supply can be added
supporting 24 or 48 Volts to the BUC. This is a factory upgrade only
Additional Burst Demodulators (FLD)- MDX420 comes equipped with 1 burst
demodulator and can be upgraded to add an additional 3 burst demodulator for a
total of 4.
Software upgrades are a simple and quick way of adding new features to an installed gateway.
Software upgrades can be easily installed via the GUI interface. Refer to Appendix A, for
information on how upgrade features are enabled.
Maximum transmit data rate can be upgraded to 5Mbps, 10Mbps, or 20Mbps
8PSK modulation
2.5 Hardware Field Upgrades
Hardware options are purchased parts that can be installed by the customer. Please contact the
Comtech Corporation Sales Department for information on price, availability, and shipping costs.
Plug-In Burst Demodulator Cards: MDX420 can support up to 4 Burst Demodulators
Cards.
CAUTION
Always make sure that power is removed from the unit before any optional modules are
installed. Failure to do so may damage the equipment.
IMPORTANT
Make sure that only authorized service personnel handle and install hardware options.
MN-MDX420 Revision 6 2–2
MDX420 SkyWire™ Satellite Network Gateway Unpacking and Installation
Chapter 3. Unpacking and Installation
This section provides unpacking and installation instructions.
3.1 Installation Requirements
The gateway is designed to be installed within any standard 19-inch (48.26 cm) wide equipment cabinet
or rack. It requires one rack unit (RU) of installation space (1.75 inches/4.45 cm) vertically and 13.0
inches (33.0 cm) of depth. Including cabling, a minimum of 16.0 inches (40.64 cm) of rack depth is
required. The rear panel of the gateway has power entering from the left and IF Cabling entering from the
right (as viewed from the rear of the gateway). Data and Control Cabling can enter from either side.
Please refer to Section 4 for rear panel connector descriptions and pinouts. The gateway can be placed
on a table or suitable surface if required.
WARNING
PROPER GROUNDING PROTECTION
During installation and setup, make sure that the gateway is properly
grounded. The equipment shall be connected to the protective earth
connection through the end user protective earth protection.
Also, make sure that the IF input and output coax cable shielding are correctly
terminated to the Chassis ground.
WARNING
ELECTRICAL SHOCK HAZARD
There are no user-serviceable parts or configuration settings inside the
Chassis. A shock hazard exists internally at the power supply module.
DO NOT open the Chassis under any circumstances.
IMPORTANT
When installing the gateway in an equipment rack or any other method,
adequate ventilation must be provided.
The ambient temperature inside the rack must be between 0
held constant for best equipment operation.
The air available to the rack must be clean and relatively dry.
The gateways must not be placed immediately above a high-heat or EMF
Generator to ensure the output signal integrity and proper receive operation.
DO NOT install the gateway in an unprotected location where there is direct
contact with moisture, rain, snow, wind or sun.
and 50C, and
MN-MDX420 Revision 6 3–1
MDX420 SkyWire™ Satellite Network Gateway Unpacking and Installation
3.2 Unpacking
The gateway was carefully packaged to avoid damage and should arrive complete with the following
items for proper installation:
MDX420 Gateway Unit
Power Cord
Installation and Operation Manual
(GUI) Configuration Software CD
Documentation Package
The gateway is shipped fully assembled. It does not require removal of the covers for any purpose in
installation.
3.3 AC Power Requirements
The power supply is designed for universal AC application. If the available AC mains power at the
installation site requires a different cord set from the one included in the package, then a suitable and
approved cord set (for the country where the equipment is to be installed) will be required before
proceeding with the installation.
Prime Power: 100 to 240VAC, 50 to 60 Hz Auto Sensing
Wattage: Base unit: less than 40 watts; Base unit with BUC Power: less than 200 Watts.
CAUTION
Before applying power to the gateway initially, disconnect the transmit output from the
operating ground station equipment. If the current configuration settings are unknown
when power is applied, incorrect settings could disrupt existing communications traffic.
3.4 Installation Considerations
The only tools required for rack installation are four (4) customer-supplied rack installation screws and the
appropriate screwdriver. Rack installation brackets are an integral part of the front bezel of the gateway
and are not removable.
MN-MDX420 Revision 6 3–2
Loading...
+ 92 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.