IMPORTANT NOTE: The information contained in this document supercedes
all previously published information regarding this product. Product
specifications are subject to change without prior notice.
Ku-Band Solid-State Power Amplifier
KPA-020IN, KPA-040, KPA-080, KPA-100
Installation and Operation Manual
Part Number MN/KPA.IOM Revision 0
Comtech EF Data is an ISO 9001
Registered Company.
KPA
Ku-Band Solid-State Power Amplifier
KPA-020IN, KPA-040, KPA-080, KPA-100
Installation and Operation Manual
Part Number MN/KPA.IOM
Revision 0
September 30, 2005
Comtech EF Data, 2114 West 7th Street, Tempe, Arizona 85281 USA, 480.333.2200, FAX: 480.333.2161.
2.2.1Prime Power Connection............................................................................................................................. 2-2
3.2 Prime Power Switch .................................................................................................................................. 3-5
3.3
Dimensional and Outline Diagrams......................................................................................................... 3-5
Revision 0 iii
Ku-Band Solid-State Power Amplifier Revision 0
Preface MN/KPA.IOM
Front Panel .................................................................................................................................................. 4-1
4.2.1.1 SELECT: CONFIGURATION MENU ........................................................................................................ 4-8
4.2.1.2 SELECT: MONITOR STATUS MENU .................................................................................................... 4-10
4.2.1.3 Current Faults Menu................................................................................................................................... 4-13
4.2.1.4 SELECT: STORED FAULTS MENU ....................................................................................................... 4-15
4.2.1.6 Current Faults Menu................................................................................................................................... 4-13
5.2.1 Control Cabling for a 1:1 System................................................................................................................ 5-2
5.2.2
Control Cabling for a 1:2 System................................................................................................................ 5-3
5.2.3Gain Equalization of Redundant Units........................................................................................................ 5-4
6.8.2End of Message ........................................................................................................................................... 6-8
Figure 4-1. Menu Tree.............................................................................................................................................. 4-6
Figure 5-1. Control Cabling of a 1:1 System............................................................................................................ 5-2
Figure 5-2. Control Cabling of a 1:2 System............................................................................................................ 5-3
Ku-Band Solid-State Power Amplifier Revision 0
Preface MN/KPA.IOM
About this Manual
This manual provides installation and operation information for the Comtech EF Data
Ku-Band Solid-State Power Amplifier, KPA-020IN, KPS-040, KPA080, and KPA100.
This is a technical document intended for earth station engineers, technicians, and operators
responsible for the operation and maintenance of the KPA.
Conventions and References
Cautions and Warnings
CAUTION indicates a hazardous situation that, if not avoided, may result in
minor or moderate injury. CAUTION may also be used to indicate other
CAUTION
WARN ING
unsafe practices or risks of property damage.
WARNING indicates a potentially hazardous situation that, if not avoided,
could result in death or serious injury.
Safety Notices
This equipment has been designed to minimize exposure of personnel to hazards. The operators
and technicians must:
CAUTION
WARN ING
IMPORTANT
• Know how to work around, with, and on high voltage and high RF power
level equipment.
• Exercise every precaution to ensure personnel safety.
• Exercise extreme care when working near high voltages/high RF power
level equipment.
• Be familiar with the warning presented in this manual.
• Disconnect the power supply cord before servicing the SSPA.
Lithium Battery Replacement: There is a damage that the Lithium battery
on the M&C assembly will explode if the battery is incorrectly replaced.
Replace only with the same or equivalent type battery recommended by the
manufacturer. Dispose of used batteries according to the Lithium battery
manufacturer’s instructions.
Indicates information critical for proper equipment function.
vii
Ku-Band Solid-State Power Amplifier Revision 0
Preface MN/KPA.IOM
Metric Conversion
Metric conversion information is located on the inside back cover of this manual. This
information is provided to assist the operator in cross-referencing Non-Metric to Metric
conversions.
Military Standards
References to “MIL-STD-188” apply to the 114A series (i.e., MIL-STD-188-114A), which
provides electrical and functional characteristics of the unbalanced and balanced voltage digital
interface circuits applicable to both long haul and tactical communications. Specifically, these
references apply to the MIL-STD-188-114A electrical characteristics for a balanced voltage
digital interface circuit, Type 1 generator, for the full range of data rates. For more information,
refer to the Department of Defense (DOD) MIL-STD-188-114A, “Electrical Characteristics of Digital Interface Circuits.”
Recommended Standard Designations
Recommended Standard (RS) Designations is equivalent to the new designation of the Electronic
Industries Association (EIA). All references in the manual will be shown either has the EIA
designations (EIA-232, EIA-485, etc.) or the RS designations..
Trademarks
Windows is a trademark of the Microsoft Corporation.
Other product names mentioned in this manual may be trademarks or registered trademarks of
their respective companies and are hereby acknowledged.
Reporting Comments or Suggestions Concerning this Manual
Comments and suggestions regarding the content and design of this manual will be appreciated.
To submit comments, please contact the Comtech EF Data Customer Support Department:
tpubs@comtechefdata.com
viii
Ku-Band Solid-State Power Amplifier Revision 0
Preface MN/KPA.IOM
European EMC Directive
In order to meet the European Electro-Magnetic Compatibility (EMC) Directive (EN55022,
EN50082-1), properly shielded cables for DATA I/O are required. More specifically, these cables
must be shielded from end-to-end, ensuring a continuous ground shield.
The following information is applicable for the European Low Voltage Directive (EN60950):
<HAR> Type of power cord required for use in the European Community.
CAUTION: Double-pole/Neutral Fusing
!
International Symbols:
ACHTUNG: Zweipolige bzw. Neutralleiter-Sicherung
Alternating Current.
Fuse.
Safety Ground.
Chassis Ground.
Note: For additional symbols, refer to “Cautions and Warnings” listed earlier in this preface.
ix
Ku-Band Solid-State Power Amplifier Revision 0
Preface MN/KPA.IOM
Warranty Policy
This Comtech EF Data product is warranted against defects in material and workmanship for a
period of 2 years from the date of shipment. During the warranty period, Comtech EF Data will,
at its option, repair or replace products that prove to be defective.
For equipment under warranty, the customer is responsible for freight to Comtech EF Data and all
related custom, taxes, tariffs, insurance, etc. Comtech EF Data is responsible for the freight
charges only for return of the equipment from the factory to the customer. Comtech EF Data will
return the equipment by the same method (i.e., Air, Express, Surface) as the equipment was sent
to Comtech EF Data.
Limitations of Warranty
The foregoing warranty shall not apply to defects resulting from improper installation or
maintenance, abuse, unauthorized modification, or operation outside of environmental
specifications for the product, or, for damages that occur due to improper repackaging of
equipment for return to Comtech EF Data.
No other warranty is expressed or implied. Comtech EF Data specifically disclaims the implied
warranties of merchantability and fitness for particular purpose.
Exclusive Remedies
The remedies provided herein are the buyer's sole and exclusive remedies. Comtech EF Data shall
not be liable for any direct, indirect, special, incidental, or consequential damages, whether based
on contract, tort, or any other legal theory.
Disclaimer
Comtech EF Data has reviewed this manual thoroughly in order that it will be an easy-to-use
guide to your equipment. All statements, technical information, and recommendations in this
manual and in any guides or related documents are believed reliable, but the accuracy and
completeness thereof are not guaranteed or warranted, and they are not intended to be, nor should
they be understood to be, representations or warranties concerning the products described.
Further, Comtech EF Data reserves the right to make changes in the specifications of the products
described in this manual at any time without notice and without obligation to notify any person of
such changes.
If you have any questions regarding your equipment or the information in this manual, please
contact the Comtech EF Data Customer Support Department.
x
Ku-Band Solid-State Power Amplifier Revision 0
Preface MN/KPA.IOM
NOTES:
xi
Chapter 1. Introduction
1.1 Overview
The Ku-Band Solid-State High Power Amplifier (KPA) is designed for use in
communication systems, or in satellite up-link data systems. The KPA (Figure 1-1)
operates over the RF input frequency range of 14.0 to 14.5 GHZ.
1.2 Functional Description
The KPA is designed to be hard mounted in a standard 19-inch (48 cm) rack or cabinet,
or to be rack mounted using Comtech EF Data slide mechanisms provided with the SSPA
to allow it to be serviced without its removal from the rack. Two internally mounted
exhaust fans are mounted on the chassis for cooling. An AC power connector, with an
On/Off switch, is located on the rear on the chassis. A six-foot AC power cord is supplied
with the unit.
All operator controls, indicators, and displays for local and remote operation as well as
the RF Input and Output sample test ports are located on the front panel of the unit.
Connectors for the external interface connections are located on the rear of the unit
chassis.
The KPA (Figures 1-2, 1-3, or 1-4) consists of a chassis, power supply, fan assembly,
front panel assembly, monitor/control processor (MCP) and a Comtech EF Data solidstate power amplifier (SSPA) module. The KPA is designed using a Comtech EF Data
low loss combining technique and an MCP based temperature versus gain compensation.
The front panel contains a user-friendly LCD menu display and cursor control key in
order to display status or change parameters. The front panel also has LEDs for quick
reference to binary status points and both input and output sample ports at –20 dBc and
–40 dBc for easy test point access.
1-1
Ku-Band Solid-State Power Amplifier Revision 0
Introduction MN/KPA.IOM
Each unit has the ability to function as a 1+1 or 1+2 redundancy controller in the backup
mode. The optional redundancy configuration is implemented by attaching a ganged
Waveguide/coax transfer switch (es) to input and output connectors of the amplifiers with
a combination coaxial cable and Waveguide kit.
When the backup KPA is commanded into the controller mode, it monitors the online
KPA’s for faults. A faulted online unit may be disconnected and replaced without
affecting the online power amplifier.
KPA-020IN
KPA-040
KPA-080
KPA-100
Figure 1-1. Family of KU-Band Solid-State Power Amplifiers
1-2
Ku-Band Solid-State Power Amplifier Revision 0
Introduction MN/KPA.IOM
Figure 1-2. Block Diagram of KPA-020IN
1-3
Ku-Band Solid-State Power Amplifier Revision 0
Introduction MN/KPA.IOM
Figure 1-3. Block Diagram of KPA-040
1-4
Ku-Band Solid-State Power Amplifier Revision 0
Introduction MN/KPA.IOM
OUTPUT
SAMPLE
INPUT
SAMPLE
RF INPUT
AC
POWER
INPUT
J9
J8
J1
CUST.
GAIN
CTRL
9V #1
9V #2
-5Vdc
Interloc k
Keypad
&
Display
J6COM1
-5Vdc
9V #19V #2
PS #1 9Vdc
J3
Interloc k
-5V -12V 12V
PS #2 9Vdc
-5V-5V9V9V
POWER CONDITIONING & CONTROL
MONITOR & CONTROL
BLOCK DIAGRAM
TEMP.
COMP.
CONTROL
& MONITOR
FAN1
FAN2
28Vdc PS
+12V
-12V
AUX. P S
& SWITCH
CONTROL
OUTPUT
POWER
DETECTOR
REFLECTED
POWER
DETECTOR
RF
J2
OUTPUT
(W/G)
REDUND.
J4
LOOP
DISCRETE
J5
CONTROL
REDUND.
SWITCH
J7
CONTROL
Figure 1-4. Block Diagram of KPA-080 /-100
1-5
Ku-Band Solid-State Power Amplifier Revision 0
Introduction MN/KPA.IOM
• Inspect the shipping container for damage. The shipping container and packing
materials should be retained for possible reshipment.
• Check to determine that all parts, materials and documentation have been shipped
with the KPA. The KPA should be inspected for possible damage, and then tested for
proper operation.
• If the shipment exhibits any of the following, contact Comtech EF Data Customer
Support:
♦ Incomplete
♦ Mechanical damage
♦ Inoperable
If there is damage to the shipping container, notify the carrier. Retain all shipping
materials for inspection by the carrier.
2-1
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
2.2 Installation
The KPA is designed for installation to mount in a standard 19-inch (48 cm) rack cabinet
or enclosure. The KPA chassis requires 8.75 inches (22 cm) of panel height space.
Adequate air ventilation should be provided to the rack mounted equipment. Cool
air is taken in through the front panel and exhausted out the rear panel.
Locate the KPA so the input and output airflow paths are not obstructed or
restricted. This will minimize the amplifier operating temperature.
• If the KPA is to be mounted on slides, the slides must be the Comtech EF
Data rack slides provided with the KPA. Proceed as follows:
Mount the slides on the sides of the KPA chassis with the provided
mounting hardware.
Install the slide rails on the rack cabinet enclosure.
Secure the KPA to the cabinet with four screws inserted through the
KPA front panel slotted holes.
2.2.1 Prime Power Connection
The On/Off prime power switch is located on the rear of the chassis adjacent to the prime
power input connector. The circuit breaker is rated for 30 Amps.
The detachable power cord mates with the AC Prime power receptacle on the rear of the
KPA chassis.
Power Cord
For KPA-020IN only:
For KPA-040 only:
For KPA-080/100 only:
A power cord for connection to 90 to 135 VAC, 47 to 63 Hz, power
sources is provided with the KPA.
A power cord for connection to 90 to 270 VAC, 47 to 63 Hz, power
sources is provided with the KPA.
A power cord for connection to 180 to 270 VAC, 47 to 63 Hz, power
sources is provided with the KPA.
2-2
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
2.2.2 Cable Connections
The cable signal functions are shown in Table 2-1.
Table 2-1. Cable Connections
Connector Function
J1 KPA RF Input (RF). Mating connector: Type SMA Female
J2 KPA RF Output (RF). Mating connector: WR75G
J3 AC Prime Power (Cord provided with KPA)
J4 Redundant Loop Interface (for use in redundant configurations)
J5 Customer Discrete Control
J6 COM 1: Serial Communications Interface, RS-232 or RS-485
communications links
Mating connector: Type DB9M
J7 Waveguide Switch Interface (for use in redundant configurations)
2.2.3 Optional: Redundancy Kit Installation
Comtech EF Data KPAs are easily configured for redundant systems by using one of the
optional Redundant Cable Kits. These kits include all the necessary controls, semi-rigid,
and waveguide cabling, and appropriate waveguide/coax switches and terminations.
Figure 2-1 shows the typical 1:1 installation and Table 2-2 shows the associated parts list.
The primary and backup KPAs shall be installed next to each other in a standard 19-inch
(48 cm) equipment rack. Because of the configuration of the dual WG-Coax Switch, the
upper KPA will always act as the backup.
Install a gasket between each waveguide interface. If both waveguide
surfaces are grooved, use a “thick” gasket. If only one surface is grooved,
IMPORTANT
use a “thin” gasket.
2-3
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
Figure 2-1. Redundancy Installation
1
2-4
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
Table 2-2. Redundancy Kit (AS/0435)
Item No.Part No. QTYNomenclature
10 CA/RF0075 1 Cable, SW P3 to Upper J1, Red Kit, 1:1
20 CA/RF0076 1 Cable, SW P2 to Lower J1, Red Kit, 1:1
30 CA/RF0065 1 Cable, SW P4 to Isolator, Red Kit. 1:1
40 CA/WR0006 1 Cable, Redundant Loop
50 CA/WR0007 1 Cable, Waveguide Switch to B-UP J7
60 CN/CX2001-6501-00 1 Connector, OSM, SMS, Plug Termination
70 FP/BR0042 1 Bracket, Mounting, Isolator, Red Kit 1:1
80 FP/WG0045 1 Waveguide, WR75, Upper, 90, Red Kit 1:1
90 FP/WG0046 1 Waveguide, WR75, Lower, 90, Red Kit 1:1
100 FP/WG0024 1 Waveguide, WR75, Elbow, 90, Red Kit 1:1
110 FP/WG0025 1 Waveguide, WR75, Termination, 150W, Red Kit, 1:1
120 GA/GSKT,WR75,FULL 7 Gasket, WR75, Full THK
130 HW/080/3/16PHMS 2 0-80 x 3/16 PHM Screw, SS
140 HW/632X3/8SHCS-B 32 Screw, 6-32 x 3/8 SHCS, Black
150 HW/06LOCK 32 #6 Lock Washer, SS
160 RF/ISHF037306-001 1 RF-ISO, 13-16G, SMS-FF
170 SW/WG-754A0 1 SW-WR75, O-Ring, Dual WGSMA
180 XX/P-SUPER O-LUBE AR Parker Super, O-Lube, 2 oz
Table 2-3. Redundancy Kit (KPS-040)
Item No.Part No. QTYNomenclature
10 CA/RF0063 1 Cable, SW P3 to Upper J1, Red Kit, 1:1
20 CA/RF0064 1 Cable, SW P2 to Lower J1, Red Kit, 1:1
30 CA/RF0065 1 Cable, SW P4 to Isolator, Red Kit. 1:1
70 FP/BR0042 1 Bracket, Mounting, Isolator, Red Kit 1:1
80 FP/WG0022 1 Waveguide, WR75, Upper, 90, Red Kit 1:1
90 FP/WG0023 1 Waveguide, WR75, Lower, 90, Red Kit 1:1
100 FP/WG0024 1 Waveguide, WR75, Elbow, 90, Red Kit 1:1
110 FP/WG0025 1 Waveguide, WR75, Termination, 100W, Red Kit, 1:1
120 GA/GSKT,WR75,FULL 7 Gasket, WR75, Full THK
130 HW/1.6 MM 2 1.6MM Screw
140 HW/632X3/8SHCS-B 32 Screw, 6-32 x 3/8 SHCS, Black
150 HW/06LOCK 32 #6 Lock Washer, SS
160 RF/ISQC140145-1FF 1 RF-ISO, 13-16G, SMS-FF
170 SW/WG-3SAG 1 SW-WR75, O-Ring, Dual WGSMA
180 XX/P-SUPER O-LUBE AR Parker Super, O-Lube, 2 oz
2-5
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
Perform the installation as follows:
Step Procedure
1 Assemble the waveguide load and bend to the proper port of the switch.
2 Attach the rigid lower waveguide arm, using the supplied screws. The switch should be
installed with “Port 1” facing outward.
3 The upper Waveguide (flexible arm) along with the isolator bracket should be installed
next.
4 Complete the installation by attaching the coaxial cables, coaxial load, and control
cables.
5 Note that the installation of the control cables determines which unit will function as the
backup KPA. Due to the nature of the dual WG-coax switch, this will always be the
upper unit. Therefore, the end of the redundant loop cable (40, Figure 2-1) labeled “BU
SSPA,” should be connected to J4 of the upper (back-up) unit.
6 The appropriate end of the control cable attaching to the Waveguide switch (50) should
also be attached to the backup unit (J7).
Note: Redundancy kits with all the cabling and switches for a 1:2 configuration also are
available, and are usually designed to a particular customer’s specifications. Contact
Comtech EF Data for 1:2 redundancy kits and installation diagrams.
2-6
Chapter 3. CONNECTOR PINOUTS
3.1 External Connections
Figure 3-1. Rear Panel (KPA-040, 080, or 100, KPA-020IN Not Shown)
Connector Description Mating Connecting
J1 RF Input (RF IN) Type SMA (f)
J2 RF Output (RF OUTPUT) WR75G
J3 AC Prime Power Input (AC IN)
J4 Redundant Loop Interface
J5 Customer Discrete Control
J6 COM1 Port (RS-232/RS-485) (COM1) DB9M
J7 Waveguide Switch Interface
AC Power On/Off Switch
3-1
Table 3-1. Rear Panel Connectors
MS3116F14-19P
(REDUND LOOP)
MS 3116F14-19P
(DISCRETE CONTROL)
MS3116F12-10P
(RF SWITCH)
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
3.1.1 Redundant Loop Interface, Connector J4
The Redundant Loop Interface connector J4 is a 19-pin circular connector, type
MS3112E14-19S. The pin-out specification is contained in Table 3-2. This connector is
used only in redundant configurations.
Table 3-2. Redundant Loop Interface, Connector J4
Pin # Description Pin # Description
A Loop In 1 L Sumflt 2 NO
B ADDR 2 M SumFlt 2 Common
C Loop In 2 N Local Loop Out
D Loop Out 2 P Sumflt 1 NO
E ADDR Common R Sumflt 1 Common
F ADDR 1 S Local Sumflt Common
G Loop Out 1 T Local Sumflt NO
H HSB +RX/TX U No Connect
J HSB – RX/TX V No Connect
K Local Loop In
3.1.2 Customer Discrete Control, Connector J5
The Customer Discrete Control connector J5 is a 19-pin circular connector, type
MS3112E14-19S. The pin-out specification is contained in Table 3-3 or Table 3-3a..
A Auto Select Momentary short to pin F to force entire subsystem to
Auto Mode.
B BU-1 Command Momentary short to pin F to force backup of KPA #1.
C Priority 2 Sel Not applicable for 1:1 system
D BU-2 Command Not applicable for 1:1 system
E 2 Online NO Not applicable for 1:1 system
F Remote Common Control – Remote Common.
G Online Common Online Status Common.
H BU Online NO Open when Online, all other conditions tied to Pin G.
J Manual Select Momentary short to pin F to force entire subsystem to
Manual Mode.
K 1 Online NO Open when Online, all other conditions tied to Pin G.
L 2 Fault NO Not applicable for 1:1 system
M Priority 1 SEL Momentary short to pin F to set KPA #1 as High priority.
N Fault Common Fault Status Common.
P BU Fault NO Open when faulted, else tied to Pin N.
R BU Offline CMD Momentary short to pin F to force backup KPA Offline.
S 1 Fault NO Open when faulted, else tied to Pin N.
3-2
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
A Auto Select Momentary short to pin F to force entire subsystem to
Auto Mode.
B BU-1 Command Momentary short to pin F to force backup of KPA #1.
C Priority 2 Sel Momentary short to pin F to set KPA #2 as HIGH priority.
D BU-2 Command Momentary short to pin F to force backup of KPA #2.
priority.
E 2 Online NO Open when Omnline, all other conditions tied to pin G.
see Note 1.
F Remote Common Control – Remote Common.
G Online Common Online Status Common.
H BU Online NO Tied to pin G when Redundancy functioning correctly, all
other conditions OPEN. See Note 2.
J Manual Select Momentary short to pin F to force entire subsystem to
Manual Mode.
K 1 Online NO Open when Online, all other conditions tied to Pin G. see
Note 1.
L 2 Fault NO Open when faulted, else tied to Pin N.
M Priority 1 SEL Momentary short to pin F to set KPA #1 as HIGH priority.
N Fault Common Fault Status Common.
P BU Fault NO Open when faulted, else tied to Pin N.
R BU Offline CMD Momentary short to pin F to force backup KPA Offline.
S 1 Fault NO Open when faulted, else tied to Pin N.
Notes:
1. Online status subject to state of Pin H.
2. When Open, can indicate loss of power or cabling problem. Online State of
unit not determinable when open.
3-3
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
3.1.3 RS-232/RS-485 Interface, Connector J6
The RS-232/RS-485 Interface connector J6 is a 9-pin D type DB9F connector socket. The
pin-out specifications are contained in Table 3-4. The mating connector is a DB9M.
Table 3-4. RS-232/RS-485 Interface, Connector J6
Pin # RS-232 RS-485 4-Wire RS-485 2-Wire
1 No Connect Ground (GND) Ground (GND)
2 Transmit Data (TD) No Connect No Connect
3 Receive Data (RD) No Connect No Connect
4 No Connect +TX Signal +RX/TX Signal
5 Ground (GND) -TX Signal -RX/TX Signal
6 Unit Ready – always high
(DSR)
7 Request to Send. Looped
to CTS (RTS)
8 Clear to Send (CTS) +RX Signal +RX/TX Signal
9 No Connect -RX Signal -RX/TX Signal
No Connect No Connect
No Connect No Connect
3.1.4 Waveguide Switch Interface, Connector J7
The waveguide switch interface connector J7 is a 10-pin circular connector, type
MS3112E12-10S. The pin-out specification is contained in Table 3-5. This connector is
used only in redundant configurations.
A Command BU-1
B Command Common
C Command 1 Online
D IND 1 Online
E IND Common
F IND BU Online
G Command BU-2
H Command BU-2
J IND 2 Online
K No Connect
3-4
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
3.2 Prime Power Switch
The On/Off Prime Power Switch is located on the rear of the chassis adjacent to the
Prime Power input connector. The circuit breaker is rated for 30 amps.
3.3 Dimensional and Outline Diagrams
KPA-020IN: Refer to Figure 3-2 for the Dimensional Diagram (all measurements shown
in inches)
KPA-080/100 only. Refer to Figure 3-3for the Dimensional Diagram (all measurements
shown in inches) and to Figure 3-4 for the Redundancy Outline Diagram.
3-5
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
NOTES:
3-6
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
Comtech EF Data reserves the right to make changes to specifications of
products described in this document at any time without notice and without
obligation to notify any person of such changes.
1.50
24.00
14-19S
.92
SMA (F)
SWITCH
1.66
7.28
2.50
A
C ENTRY
AC IN
J3
O
I
RF IN
REDUNDANT LOOP
J4
J1
6.65
1.31
Ku-Band Solid-State Power Amplifier Revision 0
Installation MN/KPA.IOM
3-10
Figure 3-4. KPA080/100 Redundancy Outline Diagram
Comtech EF Data reserves the right to make changes to specifications of
products described in this document at any time without notice and without
obligation to notify any person of such changes.
BLOCK DIAGRAM
RF IN
4
COAX
RF OUT
SSPA
#1
3
2
1
SWITCH
2
4
31
WG
BU
SSPA
DISCRETE C ONT RO L
COM1
RF SWITCH
COM1
DISCRETE C ONT RO L
RF SWITCH
RF OUT
REDUNDANT LOOP
REDUNDANT LOOP
RF OUT
AC IN
J3
O
I
RF IN
J1
RF IN
1
2
3
4
AC IN
J3
RF IN
J4
J1
PORT 1
19.0
7.8
J2
RF OUT
J7
J6
J5
17.5
J7
J6
J5
6.1
A
C IN
J3
O
REDUNDANT LOOP
I
RF IN
J1
A
C IN
J3
REDUNDANT LOOP
RF IN
J4
J1
PORT 1
J2
RF SWITCH
J7
DISCRETE C ONTROL
COM1
J6
J5
RF SWITCH
J7
DISCRETE C ONTROL
COM1
J6
J5
(CONTROL CABLES N OT SHOWN IN THIS VIEW)
4.1 General
The front panel of the KPA has a keypad for the operator input commands, an LCD
Display, LED status indicators, and connector test sample ports to monitor the RF input
and output signals.
4.1.1 Front Panel
The front panel contains a User Interface keypad which is used by a local operator to
input commands to the KPA. The keypad is used to select the configuration for operating
and monitoring the status of the KPA.
In conjunction with the front panel two line, 24-character, LCD display, the keypad
allows the operator to select one of five configurations. The configuration functions are:
• Configuration Menu
• Monitor Status Menu
• Currents Faults Menu
• Stored Faults Menu
• Utility Functions Menu
Chapter 4. Operation
Revision 0 4-1
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
Refer to Table 4-1 for logical function of each keypad entry:
Table 4-1. Operating Functions
Item Function Description Reference
[ENTER] Enters commands into the converter. ENT
CLR Clears commands and data selected and not entered. CLR
Arrow Key Selects functions and the menu operating data.
Arrow key Selects functions and the menu operating data.
Arrow Key Selects functions and the menu operating data.
Arrow Key Selects functions and the menu operating data.
LCD Display Displays commands and data entered into the keypad.
GREEN Indicator Prime Power is applied when the light is On. POWER ON
YELLOW Indicator Transmit function operating when the light is On. TRANSMIT ON
YELLOW Indicator In REMOTE CONTROL Mode, when the light is ON. REMOTE
YELLOW Indicator Operating On-Line to RX data when the light is On. ON-LINE
RED Indicator Fault condition exists when the light is On. FAULT
RED Indicator Faults stored and logged when the light is On. STORED FAULT
Input Sample Type N connector test point to sample RF input. SAMPLE INPUT
Output Sample Type N connector test point to sample RF output. SAMPLE OUTPUT
→
←
↑
↓
4-2
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.1.2 Front Panel Indicators
There are six LED indicator lights on the front panel which indicate the status of the KPA
and provide summary fault information. Refer to Table 4-2 for description of the LED
lamps:
Table 4-2. Front Panel Indicators
LED Lamp Condition
Fault Red Indicates that a fault condition exists when the LED light is
On.
Stored Fault Red Indicates that the fault has been logged and stored When
the LED light is On. The fault may, or may not, be active.
Power Status Green Indicates that power is applied to the KPA when the LED
light is On.
TX ON Yellow Indicates that the transmit function of the KPA is on when
the LED light is On. The indicator light reflects the actual
condition of the transmit function.
Online Yellow Indicates that the KPA is operating on-line to transmit data.
Remote Yellow Indicates that the KPA is being operated in the remote
control mode where commands and data are transferred via
an RS-485 (RS-232 is optional) serial communications
link.
4-3
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.1.3 Switching On
Prior to positioning the Prime Power Switch to On, perform the following:
1. Check to ensure that the installation is complete.
2. Verify that the KPA is connected to the proper prime power source, RF input,
and RF output.
3. Switch the On/Off Prime Power Switch on the rear panel to On.
4. Verify that the cooling fans are operating, and that the POWER ON LEDSTATUS indicator light is On.
5. After the PRIME POWER is switched on, the STATUS indicators should be as
follows:
POWER ON ON
TRANSMIT OFF
REMOTE ON
ON LINE ON
FAULT OFF
STORED FAULT OFF
After the AC power is switched on and prior to pressing the buttons on the keypad, the
LCD display message should read as follows:
KPAXXX-4045-I
SW VER X.XX SN4045 XXXX
4-4
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.2 Operation
Local control of the unit is controlled by operator input commands initiated through the
six button keypad on the front panel. The keypad is the local operator’s interface to
control, configure and monitor the status of the KPA. Operator inputs and commands
entered into the keypad are displayed by the front panel, 24-character, 2-line LCD
display.
There are five operating functions:
• Configuration
• Monitor Status
• Current Faults
• Stored Faults
• Utility Functions
Flow charts for selecting the commands, operating menus, and data inputs are shown in
Figure 4-1 through Figure 4-6.
4-5
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
TOTAL FAULTS STORED
CLEAR ALL STORED FAULTS
STORED FAULTS
ATTENUATION
AMPLIER ON/ MUTE OFF
REDUNDANCY
SSPA #/ BU
OPERATING MODE
MANUAL
SSPA # 1
OFFSET/ACTIVATE
UTILITY
TIME/DATE
SERIAL MODE
SERIAL PORT DATA
DISPLAY CONTRAST
FORWARD
REVERSE
LAMP TEST
SERIAL MODE
ADDR=XXX-BAUD=YYY-P=ZZZ
SERIAL PORT DATA
7-DATA, -2-STOP, -PARITY-
FORWARD
OFFSET +0.0 dBm
REVERSE
OFFSET +0.0 dBm
PRINCIPLE MENU TREE
Figure 4-1. Menu Tree
4-6
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.2.1 KPA Commands
When the prime power is turned On, the LCD display will contain a message indicating
the KPA model number and the version number of the firmware installed in the KPA.
To select a Command Function press the <ENT> button on the keypad. The LCD display
will indicate:
SELECT
CONFIGURATION MENU
This will provide the local operator access to the Command Function Menus, which is the
top level structure to start the selection of Command Function Menus to input into the
KPA.
To sequence to the next Command Function Menu press a ↓ or ↑ arrow button on the
keypad. The KPA will step to the next Command Function Menu each time a ↓ or ↑
arrow button is pressed. The current Command Function Menu will be displayed on the
LCD display. The Command Function Menus are shown in Figure 4-1.
To select a specific Command Function Menu press the <ENT> keypad button. If a
function is selected in error, press the clear <CLR> button which will return the KPA to
the main command menus to allow the selection of another function. Any one of the five
Command Function Menus can be selected using this procedure.
Once a Command Function has been selected, use the → or ← arrow key-pad buttons to
sequence through the Operating Mode Commands. Each of the modes will be displayed
on the LCD display. A specific operating mode is selected by pressing the <ENT>
button. If a mode is selected in error, press the clear <CLR> button which will return the
KPA to the operating menus to allow the selection of another mode.
When an operating mode is selected, a parameter or a digit within the parameter will be
flashing on the LCD display. Use the → and ← arrows buttons to sequence through the
parameters or digits to select the next parameter or digit. A specific parameter or value is
selected by pressing the <ENT> button. If a parameter or value is selected in error, press
the <CLR> button which will return the KPA to the original parameter or value to allow
another selection.
After selecting a parameter or digit, use the ↓ or ↑ arrow buttons to select the next
parameter, or to increment or decrement the value of a digit. A specific new parameter or
new value is selected by pressing the <ENT> button. If a parameter or value is selected in
error, press the <CLR> button which will return the KPA to the original parameter or
value to allow another selection.
Each time the clear ("CLR") button is pressed, the KPA will return to the menu level
prior to the last "ENT" command.
4-7
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.2.1.1 SELECT: CONFIGURATION MENU
SELECT: CONFIGURATION MENU: ATTENUATION
ATTENUATION-=-10.00-Db-AMPLIFIER=-ON--MUTE=-OFF
The default setting is 10.00 dB.
Attenuation
(ATTN):
Amplifier Control supply voltage to RF FETS. The default mode is On
Mute Provide KPA mute control. The default is OFF.
Input and displays the KPA attenuation setting which is selected between
0.00 to 20.00 in 0.25 dB steps.
For KPA-020IN Only: SELECT: CONFIGURATION MENU:
AMPLIFIER
AMPLIFIER
ON
Amplifier Control supply voltage to RF FETS. The Amplifier display is either ON, MUTE, or
OFF. The default mode is ON.
Mute Provide KPA MUTE control. The default is OFF.
SELECT: CONFIGURATION MENU: ENTRY MODE
---ENTRY—MODE-=-REMOTE
------------------------
The Entry Mode is Local or Remote. The default is Local.
4-8
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
SELECT: CONFIGURATION MENU: FAULT RECOVERY
-FAULT-RECOVERY:-MANUAL-
------------------------
Fault Recovery is MANUAL or AUTO. The default is AUTO.
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
SELECT: MONITOR STATUS MENU: RF FET
--RF-FET----Q1-=-XXXmA
--RF-FET----Q2-=-XXXmA
--RF-FET----Q3-=-X.X-AMPS
--RF-FET----Q4-=-X.X-AMPS
--RF-FET----Q5-=-X.X-AMPS
--RF-FET----Q6-=-X.X-AMPS
--RF-FET----QX-=-X.X-AMPS
--RF-FET----QX-=-X.X-AMPS
--RF-FET----Q26-=-X.X-AMPS
--RF-FET----Q27-=-X.X-AMPS
4-12
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.2.1.3 Current Faults Menu
---------SELECT---------
--CURRENT-FAULTS-MENU---
Displays the status of the current fault conditions. The LCD display will indicate “FT”
when a fault condition exists. The display will indicate “OK” when a fault has not
occurred.
KPA-020IN Only:
SELECT: CURRENT FAULTS: POWER FAULTS
Power–Faults:----+12V=OK
-12V=OK-VCC=OK---5V=OK-
-----28-VDC-PS-=-OK-----
------9-VDC-PS-=-OK-----
Displays the DC voltage power supply faults. The DC voltage displayed are:
• +12 VDC
• -12 VDC
• VCC
• -5 VDC
• +28 VDC
• +9 VDC
SELECT: CURRENT FAULTS: SSPA TEMPERATURE FAULT
Displays status of both FAN #1 and FAN #2.
Fan Faults
4-13
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
KPA-040/-080/-100 ONLY:
SELECT: CURRENT FAULTS: POWER FAULTS
Power–Faults:----+12V=OK
-12V=OK-VCC=OK---5V=OK-
-----28-VDC-PS-=-OK-----
------9-VDC-PS-=-OK-----
Displays the DC voltage power supply faults. The DC voltage displayed are:
• +12 VDC
• -12 VDC
• VCC
• -5 VDC
• +28 VDC
• +9 VDC
SELECT: CURRENT FAULTS: AMPLIFIER
---AMPLIFIER-TEMP-=-OK=-
-FAN-1-=-OK-FAN-2-=-OK-
A temperature fault is indicated if the unit is ≤ -20°C (≤ -4°F) or ≥ 85°C (≥ 185°F). This
creates a summary fault and will cause the unit to mute itself and switchover to the backup
unit. However, the 9V supply to the FET transistors will remain on until the unit reaches the
termal shutdown temperature of ≥ 90°C (194°F). For protection reasons, the unit will
shutdown the 9V supply to the power transistors at temperatures ≥ 90°C (194°F).
Displays an KPA temperature fault condition.
Displays status of Fan #1 and Fan #2.
--M&C-PROCESSORS-=-OK---
------------------------
Status only.
SSPA Over Temperature Fault
Fan Faults
M&C Processors
Displays a SSPA temperature fault condition.
Displays status of both FAN #1 and FAN #2.
Displays M&C fault condition.
4-14
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.2.1.4 SELECT: STORED FAULTS MENU
The KPA displays a total of 100 faults with a date/time stamped and stored in memory as
they occur. The stored faults remain in memory until a Clear commanad is entered.
SELECT: STORED FAULTS MENU: TOTAL STORED FAULTS
TOTAL-FAULTS-STORED: 100
LAST-19:20:05---02/15/95
Displays the total number of faults stored. The most recent fault stored is displayed on the
LCD display.
SELECT: STORED FAULTS MENU: CLEAR ALL STORED
FAULTS
----CLEAR-ALL-STORED----
------FAULTS?-NO--------
Displays the total number of faults stored. The most recent fault stored is displayed on the
LCD display.
SELECT: STORED FAULTS MENU: DISPLAY STORED FAULTS
ST-FAULT-XX-----19:20:05
OK-FINE-LOCK----02/15/95
The local operator can sequence through the stored faults starting with the most recent
fault. The Fault number, time, description, and date are displayed on the LCD display.
4-15
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
4.2.1.5 SELECT: UTILITY FUNCTIONS MENU
---------SELECT---------
--UTILITY-FUNCTION-MENU--
The local operator can input commands to the following Utility Functions Menu which
are displayed on the LCD display.
SELECT: UTILITY FUNCTIONS MENU: TIME/DATE
----TIME:-10:20:05Am----
-----date—09/15/94------
Military time is displayed in Hours, Minutes, and Seconds. The date is displayed in
Month, Day, and Year.
SELECT: UTILITY FUNCTIONS MENU: SERIAL MODE
---SERIAL-MODE=RS232C--ADDR=XXX-BAUD=YYYY-p=ZZ
Communications Link.
Serial Interface RS-232, RS-485(2-Wire), RS-485(4-Wire)
Physical Address The default address starts from 001.
Baud (Rate) The default baud rate is 9600.
Parity Even (EV) is the default.
Odd (OD) can be selected.
NA appears when the 8, N, 1 Stop Bit, with No Parity.
Note: This can only be changed via the front panel menu system.
SELECT: UTILITY FUNCTIONS MENU: SERIAL PORT DATA
SERIAL-PORT-DATA-FORMAT=
-7-DATA,-2-STOP,-PARITY-
The default is 7 Data, 2 Stop Bits, with Parity.
An optional format is 8 Data, 1 Stop Bit, with Parity.
Note: This can only be changed via the fron panel menu system.
4-16
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
SELECT: UTILITY FUNCTIONS MENU: DISPLAY CONTRAST
-DISPLAY-CONTRAST-=XX—
DISPLAY-BRIGHTNESS-=-XX-
The default is 15, with values range of 0 to 30.
Brightness default is 15 with values ranging from 0 to 30.
SELECT: UTILITY FUNCTIONS MENU: FORWARD
FORWARD –RF-POWER-MONITOR
----OFFSET-=-+0.OdBm
This function allows the operator to calibrate (fine tune) the RF Power Monitor for a
specific carrier frequency. The RF Power Monitor is calbrated in the factory at the KPA
center frequency. The operator can adjust (offset) the display level using this function.
SELECT: UTILITY FUNCTIONS MENU: REVERSE
REVERSE-RF-POWER-MONITOR
----OFFSET-=-+0.0dBm----
This function allows the operator to calibrate (fine tune) the RF Power Monitor for a
specific carrier frequency. The RF Power Monitor is calbrated in the factory at the KPA
center frequency. The operator can adjust (offset) the display level using this function.
The range is within: -6.0 to +6.0 dBm, in 0.1 dBm steps.
KPA-0202IN only: SELECT: UTILITY FUNCTIONS MENU: LAMP
TEST
---------LAMP TEST-------
----------OFF-----------
The default is Off.
4-17
Ku-Band Solid-State Power Amplifier Revision 0
Operation MN/KPA.IOM
All Comtech EF Data KPAs are designed to operate in both stand-alone and redundant
configurations. Every KPA contains the circuitry and logic necessary to perform all the functions
of a backup controller in both a 1:1 and 1:2 configuration. This includes the ability to monitor and
control up to two RF waveguide switch assemblies. In addition, the KPA has been designed to
automatically detect whether it is in a stand-alone or redundancy system. These features greatly
simplify redundancy configurations from both the cost and operational complexity standpoint.
5.2 Redundancy Operation
Configuration
Refer to Figure 2-1 for a full installation diagram of a typical redundant system.
Normal Operation
Controller Mode
Fault
Waveguide
Two control cable assemblies are required to setup either the 1:1 or a 1:2 system. Other RF
coaxial cables and waveguides are required .
Incoming RF signals are routed through the primary online SSPA (1:1), or SSPA (1:2) to the
system output(s) by the combination waveguide/coax switch(es).
With the backup SSPA in the controller mode, it monitors the online unit(s) for faults.
When a fault occurs in an online unit, the backup SSPA automatically configures itself with
the settings of the faulted online unit. (These now active settings also incorporated any user
defined offsets that may have been programmed into the backup unit.)
The position of the waveguide/coax switch also is automatically changes to oute the signal
through the backup unit, thereby minimizing the loss of traffic.
5-1
Ku-Band Solid-State Power Amplifier Revision 0
Redundant Configuration MN/KPA.IOM
5.2.1 Control Cabling for a 1:1 System
Figure 5-1. Control Cabling of a 1:1 System
The position of the waveguide/coax switch also is automatically changed to route the signal
through the backup unit, thereby minimizing the loss of traffic.
Control cable assemblies are required to set up either a 1:1 or a 1:2 system (other RF coaxial
cables and waveguides are required as shown in Figure 5-1).
Figure 5-1 shows the control cabling for a 1:1 system. The redundant loop cable connecting the
two KPAs together provides a number of functions.
• This cable assembly is not a straight through cable.
• The cable assembly is labeled “backup” on one end, and KPA #1 on the other end.
• The cable assembly is wired so that when connected to two KPAs, one KPA will
automatically configure itself as the Backup Controller and the other KPA will
automatically configure itself as the ‘Primary KPA’.
The backup KPA communicates to the primary KPA via a serial interface also provided by this
redundant loop cable assembly. This interface is used by the Backup KPA to acquire
configuration information from KPA #1. In addition, this interface provides the link for virtual
addressing as described in this manual.
Summary fault relay contacts also are included in this cable assembly and are used by the backup
KPA as an input to its switching logic. The second cable assembly is a six-wire assembly
between the backup KPA and the Waveguide Switch Assembly. Figure 5-2 shows the cabling for
a 1:2 system. Note that the functionality describes for the 1:1 cable assembly is directly
applicable for the 1:2 cable assembly. The only difference is that there is now a third connector
daisy-chained onto the cable assembly.
5-2
Ku-Band Solid-State Power Amplifier Revision 0
Redundant Configuration MN/KPA.IOM
This connector is labeled KPA #2. When connected to a Comtech EF Data KPA, the KPA will
automatically configure itself as Primary KPA #2.
The second control cable attaches from the Backup Unit J7 to the Waveguide switch.
5.2.2 Cabling for a 1:2 System
Figure 5-2. Control Cabling of a 1:2 System
See Figure 5-2.
Note: The functionality described for the 1:1 Redundant System applies to the 1:2 System.
The difference is that there is a third connector dasily-chained onto the cable. This connector is
labled, “SSPA#2.” When connected to a Comtech EF Data SSPA, the SSPA will automatically
configure itself as “Primary SSPA#2.”
5-3
Ku-Band Solid-State Power Amplifier Revision 0
Redundant Configuration MN/KPA.IOM
5.2.3 Gain Equalization of Redundant Units
Typical procedures to equalize the gain between the Backup Unit and the Online Unit(s) via the
Gain Offset adjustment in the backup unit’s CONFIGURATION Menu are as follows:
Note: Make sure all connections are made as outlined previously in Sections 2 and 4.)
Determine the relative gain of the Backup Unit vs the Online unit(s).
Make sure the Online Unit is “online” and transmitting. This can be verified through the
CONFIGURATION Menu, and the front panel LEDs.
Step Procedures
1 Apply an RF signal to the RF redundancy input isolator. Monitor the output
power level at the waveguide switch output. (Make sure not to apply too
large of an input signal which will saturate the amplifiers. Also be sure to
have a properly rated load to measure the output power.)
2 Adjust the input signal power level and attenuation of the Online Unit to
arrive at the desired output power level.
3 Record the output level of the Online Unit in dBm.
4 Force the backup unit to be the active path as outlined in the
CONFIGURATION Menu. Ensure the Offset Value at this point is 0.0 dBm.
Record the output level in dBm of the back-up unit.
5 If the output levels are equal, no more adjustment is necessary. Otherwise
proceed as follows.
Case 1. Backup < Online unit(s).
1. Ensure the online
to the difference in levels measured above.
2. With the backup unit forced to be the active unit, adjust the Offset Value in the
CONFIGURATION Menu to approximately the difference measured above.
This will be a (-) negative
3. Toggle between the online and backup units as being the active path by forcing
and un-forcing a back-up through the back-up unit CONFIGURATION Menu
settings. Ensure the output levels measured are equal. If necessary, re-adjust the
Offset Value until equal levels are measured. (Note that the back-up unit total
attenuation level as now indicated in the CONFIGURATION Menu will be
equal to the setting of the online unit less
unit attenuation is set to a value in dB greater than or equal (≥ )
number.
the Offset Value.)
5-4
Ku-Band Solid-State Power Amplifier Revision 0
Redundant Configuration MN/KPA.IOM
For Example:
Online Unit Output Level
Backup Unit Output Level
Backup Unit Offset Value
Online Attenuation Setting
AFTER TOGGLING AND ADJUSTING:
Backup Offset Value
New Equalized Output Level
Backup Attenuation Setting
47.0 dBm
45.25 dBm
0.00 dBm
3.00 dB (must be > 1.75 dB)
-1.75 dB
47.0 dBm
1.25 dB (3+(-1.75)=1.25)
Case 2. Backup > Online unit(s).
1. With the backup unit forced to be the active unit, adjust the Offset Value in the
CONFIGURATION Menu to roughly the difference measured above. This will
be a (+) positive
number.
2. Toggle between the online and backup units as being the active path by forcing
and un-forcing a back-up through the back-up unit CONFIGURATION Menu
settings. Make sure the output levels measured are equal. If necessary, re-adjust
the Offset Value until equal levels are measured. (Note that the back-up unit total
attenuation level as now indicated in the CONFIGURATION Menu will be
equal to the setting of the online unit plus
the Offset Value.)
For Example:
Online Unit Output Level
Backup Unit Output Level
Backup Unit Offset Value
Online attenuation setting
AFTER TOGGLING AND
ADJUSTING:
Backup Offset Value
New Equalized Output Level
Backup Attenuation Setting
= 47.00 dBm
= 48.75 dBm
= 0.00 dBm
= 3.0 dBm
= +1.75 dB
= 47.00 dBm
= 4.75 dB (3+(+1.75)=4.75)
5-5
Ku-Band Solid-State Power Amplifier Revision 0
Redundant Configuration MN/KPA.IOM
NOTES:
5-6
Chapter 6. Remote Control
6.1 General
The backup KPA in the redundancy subsystem automatically monitors the configuration
and status for each of the primary (chained) KPAs. This information is communicated via
the dedicated serial interface between the KPAs.
• If a primary KPA fails, the backup detects this event and automatically
reconfigures itself to the proper attenuation setting and positions the
waveguide switch to provide minimal loss of traffic.
A result of this design is to greatly lessen the throughput requirements (i.e. polling rate)
of earth station monitor and control systems. The backup KPA handles all of the time
critical tasks allowing the earth station monitor and control system to focus on less
intelligent subsystems.
Specification
6-1
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.2 Electrical Interface
The remote control interface supports either RS-485 (2-wire), RS-485 (4-wire ) or
RS-232. The default port is RS-485 (2-wire). Selection of the interface type is made
via front panel menu selection. The three interface types are impletemented alternately
through the same 9-pin connector.
RS-232
RS-485
Levels, pulse shapes and impedances conform to EIA standards for asynchronous operation.
Levels, pulse shapes and impedances conform to EIA standards.
6.3 Interface Connector
All three interface types (2-wire RS-485, 4-wire RS-485 and RS-232) are implemented
alternately through the same 9-pin connector. The remote control port is a female DB-9
connector located on the rear of the KPA.
RS-232
Pin Name Function
2 TD KPA Transmit Data
3 RD KPA Receive Data
5 GND Ground
6 DSR Unit Ready. Always high.
7 RTS Request to Send (Looped to CTS)
8 CTS Clear to Send
RS-485 (2-Wire)
Pin Name Function
1 GND Ground
4 +RX/TX Signal Loop In
5 -RX/TX Signal Complement Loop In
8 +RX/TX Signal Loop Out
9 -RX/TX Signal Complement Loop Out
RS-485 (4-Wire)
Pin Name Function
1 GND Ground
4 +TX Transmit Signal
5 -TX Transmit Signal Complement
8 +RX Receive Signal
9 -RX Receive Signal Complement
6-2
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.4 Cables
RS-232
The remote control port is configured with pin 2 as the TX data signal (TD) and pin 3 as
the RX data signal. This arrangement allows straight connection (pin 2 to pin 2 and pin 3
to pin 3) between the KPA and most standard serial ports using any standard RS-232
cable (i.e. no need to swap pins 2 and 3).
RS-485
RS-485 cabling can be implemented with a single ribbon cable using IDC Mass
Terminated style connectors or with discrete wires using solder-cup style connectors. A
sufficient length of ribbon cable must be allowed to reach the system monitor and control
computer.
RS-232
RS-485
2-wire
4-wire
The Comtech EF Data KPA does not require the hardware handshaking
provided by the DSR, RTS, and CTS signals. These signals are provided for
customers that are using interface terminals that require this handshaking. Most
of today’s PC’s are provided with RS-232 serial ports that do not require the
hardware handshaking. In these instances, the interface can be reduced to three
signals; TD, RD, and GND.
Both 2-wire and 4-wire applications are supported. The 4-wire interface
provides independent signal wires for each of the RX (+RX) signal and its
complement (-RX) as well as the TX (+TX) signal and its complement (-TX).
In the 2-wire interface, the RX signal and the TX signal (+RX/TX) share one
wire and likewise the complement signals (-RX/TX) share one wire. Choice of
2-wire vs 4-wire is based on the customer’s interface equipment and the cabling
between this equipment and the KPA(s).
Each signal pair (+RX/TX and –RX/TX) is provided on two pins. This is done
to provide customers who are using solder-cup type DB-9 connector the ability
to more easily daisy chain the signals to multiple devices while maintaining one
wire per solder-cup. Customers who use IDC Mass Terminated style DB-9
connectors (Ribbon cable types) need only use three signals.
All five signals are required.
6-3
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.5 Protocol
Refer to Table 6-1 for protocol description. Protocol is divided into six subjects:
• Transmission Mode
• Baud Rate
• Format
• Character Set
• Response Timeout
• Bus Inactivity Requirements
Table 6-1. Protocol Description
Transmission Mode
Baud Rate
Character Set
Response Timeout
Bus Inactivity
Requirement
The transmission mode is half-duplex implemented in
Command/Response convention. This method requires the external
system monitor and control unit to initiate all communications by
command and the KPA to respond with either confirmation or an error
message. The confirmation may contain status information.
The default serial port Baud Rate is 9600.
Baud rates of 4800, 2400, 1200, and 300 also are supported.
The character set implemented is ASCII.
A minimum of 500 milliseconds should be provided before declaring a
No Reponse instance, at which time the command should be
re-transmitted.
Comtech EF Data recommends that a minimum of 50 milliseconds bus
inactivity be provided by the user between the receipt of a response
from an addressed KPA and issuing the next command on the serial
bus.
6.5.1 Format
The following parameters are the default character format:
Start Bit
Parity Bit
Stop Bits
Data Bits
An optional character format that can be selected is:
Note: This can only be selected from the Front Panel Menu.
Parity Bit
Start Bit
Stop Bit
Data Bits
1
1 (Selectable, Even or Odd, via the front panel menu or remote interface
2
7
0
1
1
8
6-4
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.6 Access Methods
The KPA may be accessed directly by using a physical address or indirectly through a
backup KPA in a redundant configuration using a virtual address.
6.6.1 Direct Access
KPAs may be directly accessed by the RS-232 interface or by the RS-485 interface in a
buss configuration.
RS-485
RS-232
In this control network, the KPA is paralleled on a common RS-485 cable, and has a unique
physical address. Only one RS-485 port is required on the system's monitor and control
computer.
For RS-232 control, a direct RS-232 cable connection is made to each KPA to be accessed.
If an external Monitor and Control Computer is used, one RS-232 port per KPA is required.
6.6.2 Indirect Access
KPAs in Redundancy Mode may be addressed indirectly by adding a virtual address to
the backup KPA’s physical address. The virtual address corresponds to the KPA’s
position in the redundant subsystem. The backup KPA recognizes the virtual address and
executes the command via the dedicated serial link between itself and the targeted KPA.
This addressing mode is provided to reduce cabinet wiring complexity by allowing
remote access to either both KPAs (in a 1:1 redundant subsystem) or all three KPAs (in a
1:2 redundant subsystem) using a single RS-232 or RS-485 connection to the backup
KPA.
Note: Due to memory limitations, virtual addressing is not
fully functional in a KPA 1:2
system. Contact the factory for specific information. Virtual addressing is fully functional
in a KPA 1:1 system.
6-5
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.7 Addressess
All KPAs are addressed in a command by the Device Address. The Device Address
consists of a physical address or a physical address plus a virtual address.
6.7.1 Physical Address
Each KPA in the system must have a unique physical address regardless of the access
method used. The physical address consists of a string of 1, 2 or 3 numbers from 1 to
256. The physical address is entered into a KPA via the front panel. For Direct Access,
the physical address is the only address required to command a KPA. A backup KPA or a
stand-alone KPA can only be accessed with a physical address.
For Example: 10 Addresses KPA whose physical address is 10.
6.7.2 Virtual Address
In order to access an KPA controlled by a backup KPA indirectly, a virtual address is
required. A virtual address is appended to the physical address of the backup KPA with a
“V”. The virtual address is either the number “1" or “2" corresponding to the KPA’s
designation in a redundant subsystem.
For Example: 10V2 Addresses second KPA in a 1:2
redundant subsystem controlled by
the backup KPA whose physical address is 10.
6.7.3 Message Structure
The structure of either a Command, Response, or Error Message is as follows:
• Start Character
• Device Address
• Command or Response
• End of Message String
6.7.4 Start Character
The Start Character begins each message:
For Example: < Start of a user Command.
> Start of a KPA response.
6-6
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.7.5 Device Address
The Device Address consists of a Physical Address. For this document DEV is used for
the generic case examples.
For Example; <10 direct addressing
<10V2 indirect addressing
6.7.6 Command
A Command is a variable length character string beginning with a / and containing either
an instruction or an instruction and data for an KPA to act upon.
• If data is passed by command, it is appended to the instruction by an
underscore( _ ).
• If data is retrieved by command, underscore follows the instruction flagging
the KPA to supply data in a response.
• In this document /COM is used for the generic case examples.
For Example: <DEV/COM_xxx'cr' Sends data to an KPA.
For Example: <DEV/COM_'cr' Requests information from an
KPA.
6.8 Confirmation Response
A confirmation will change the start character, and echo the Device Address and
Command. Any requested data will be appended to the Command.
For Example: >DEV/COM_xxx'cr''lf']
6.8.1 Error Response
If an KPA cannot execute a Command or detects a protocol violation, an error response is
generated. An error is flagged by changing the "/" command designator in the response to
a "?". Following the "?" error symbol are two characters which are unique error symbols
useful for computer analysis. The two error symbols are followed by a text string
explaining the error for the convenience of a human operator. For this document ER is
used for the generic case examples response.
For Example: >DEV?COM ER Error Message 'cr''lf']
6-7
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.8.2 End Of Message
End of message strings were devised in such a way that an orderly screen presentation
would result when KPAs are controlled by simple ASCII terminals.
6.8.2.1 Command Ending
The end of message for a command is a carriage return. For this document 'cr' is used for
the carriage return.
For Example: <DEV/COM'cr'
6.8.2.2 Response Ending
End of message for a response is a carriage return, line feed and a bracket: 'cr''lf'].
For Example: >DEV/COM'cr''lf']
6-8
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
Where: XXXXXXX …XXXXX =
Message, maximum 48 characters
The Application Identification (AID)
command allows a free form message to
be created. It is intended to identify either
the satellite transponder, beam,
destination or other aspects of the
application that may be significant to
operations. The message length
corresponds to capability of the LCD and
is 48 characters in total. The second line
begins at character 25, therefore, blanks
must be used after line 1 information in
order to space to line 2. A carriage return
ends the command. Trailing blanks will be
generated to fill the LCD field. The AID
display will alternate with the Equipment
type display by use of the clear function
key on the front panel. The default is “AID
MESSAGE.”
Where: x= 0 for Local or 1 for Remote
6.9.2 Configuration Commands
Amplifier On/OFF Amplifier Control:
Confirmation:
Retrieve AMP Status:
Confirmation:
Mute Mute Output:
Confirmation:
Retrieve Mute Status:
Confirmation:
Attenuator Set Attenuator:
Confirmation:
Retrieve Attenuator:
Confirmation:
<DEV/AMP_xxx'cr'
>DEV/AMP_xxx'cr'' lf']
<DEV/AMP_'cr'
>DEV/AMP_xxx'cr'' lf']
<DEV/MUT_xxx'cr'
>DEV/MUT_xxx'cr'' lf']
<DEV/MUT_'cr'
>DEV/MUT_xxx'cr'' lf']
<DEV/ATT_yy.yy'cr'
>DEV/ATT_yy.yy'cr'' lf']
<DEV/ATT_'cr'
>DEV/ATT_yy.yy'cr'' lf']
6-10
Where: xxx = On or Off
The default is On.
The Comtech EF Data KPA provides the user
direct control of the 9VDC supply voltage to
the solid-state RF power FETs. This feature
provides the ability to put the KPA into a low
power consumption mode when the unit is
offline.
Where: xxx = On or Off
The default is On.
The user is provider output mute control via
the remote interface using this command.
Where: yy.yy = 0.0 to 20.0 dB in 0.25 steps.
The default is 10 dB.
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
Auto Fault
Recovery
Set Fault Recovery:
Confirmation:
Retrieve Status:
Confirmation:
<DEV/AFR_xxx'cr'
>DEV/AFR_xxx'cr'' lf']
<DEV/AFR_xxx'cr'
>DEV/AFR_xxx'cr'' lf']
Where xxx = On or Off
The default is Off.
The KPA output automatically muted in the
event of a detected fault. Auto Fault Recovery,
if enabled, will cause the output signal to go
active (unmuted) if all faults clear. If disabled,
the output will remain muted even after all
faults clear until a MUT_OFF command is
received.
6.9.3 Mode Commands
Note : There are two modes of operation that may intersect: Redundancy Mode and
Automatic Mode.
Redundancy Mode Comtech EF Data’s KPA family is designed to automatically sense and configure into redundancy mode when the
Automatic/Manual
Mode
Backup Mode Initiate a Backup:
Priority Select Set Prority:
redundant loop cable is connected. Polling on the dedicated redundancy buss will not begin until the redundancy loop
cable is connected. Each KPA’s designation in a redundant subsystem is determined automatically via the
redundancy interface cable connected between the two (1:1 subsystem) or three (1:2 subsystem) KPAs in the
redundant subsystem.
Select Automatic Mode:
Confirmation:
Automatic Status:
Confirmation:
Confirmation:
Retrieve Backup Status:
Confirmation:
Confirmation:
Retrieve Prority Status:
Confirmation:
<DEV/SAM_y'cr' xxx
>DEV/SAM_y'cr'' lf']
<DEV/SAM_'cr'
>DEV/SAM_y'cr'' lf']
<DEV/FBU_x_y'cr'
>DEV/FBU_x_y'cr'' lf']
<DEV/FBU_'cr'
>DEV/FBU_zzzzz'cr'' lf']
<DEV/PRI_x'cr'
>DEV/PRI_x'cr'' lf']
<DEV/PRI_'cr'
>DEV/PRI_x'cr'' lf']
Where: y = A for Auto
M for Manual
The default is Off.
This command provides for automatic
switching by the backup KPA if both units are
in the Redundancy Mode. This command is
only accepted by the backup KPA. If a primary
KPA is set in Manual Mode and a fault occurs,
the backup KPA will log the occurrence and
not act upon further information from the KPA
until put into Automatic Mode.
Where: x = 1 or 2 KPA number.
Y = F to force a backup
N = to remove a backup
zzzzz = NONE, if no backup active.
ACTIVE, if an automatic backup
has occurred.
FORCED, if a forced backup is
active.
This command allows the user to force a
backup condition for mainternace and test
purposes. This command must be sent to the
KPA designated as the backup KPA to
configure the Waveguide switch to a position
such that the backup KPA is Online and the
primary KPA is Offline.
Where x = 1 or 2
This command allows the user to assign
prority when operating in a 1:2 redundant
subsystem. This command provides
arbitration in the event that both primary KPAs
are faulted simulataneously.
6-11
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
FET1 current in milliamps
FET2 current in milliamps
FET3 current in amps
FET4 current in amps
FET5 current in amps
FET6 current in amps
FET7 current in amps
FET8 current in amps
FET9 current in amps
Where :
FET1 current in milliamps
FET2 current in amps
FET3 current in amps
FET4 current in amps
FET5 current in amps
FET6 current in milliamps
FET7 current in amps
FET8 current in amps
FET9 current in amps
FET10 current in amps
FET11 current in amps
FET12 current in amps
FET13 current in amps
FET14 current in amps
Where :
FET1 current in milliamps
FET2 current in milliamps
FET3 current in amps
FET4 current in amps
FET5 current in amps
FET6 current in amps
FET7 current in amps
FET8 current in amps
FET9 current in amps
FET10 current in amps
FET11 current in amps
FET12 current in amps
FET13 current in amps
FET14 current in amps
FET15 current in amps
FET16 current in amps
FET17 current in amps
FET18 current in amps
FET19 current in amps
FET20 current in amps
FET21 current in amps
FET22 current in amps
FET23 current in amps
FET24 current in amps
FET25 current in amps
FET26 current in amps
FET27 current in amps
6-13
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
Note: A temperature fault is indicated if
the unit is ≤ -12°C or ≥ +80°C. This
creates a summary fault and will cause
the unit to mute itself and switchover to
the back-up unit. However, the 9V
supply to the FET transistors will
remain on until the unit reaches the
thermal shutdown temperature of ≥
89°C. For protection reasons, the unit
will shutdown the 9V supply to the
power transistors at temperatures ≥
+89°C.
6-14
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
+ 5 VDC Fault
– 5 VDC Fault
+ 9_1_xx'cr'
+ 9_2_xx'cr'
TEMP_xx'cr'
Over Temperature Shutdown
FAN1_xx'cr'
FAN2_xx'cr'' lf']
Note: A temperature fault is indicated if
the unit is ≤ -20°C or ≥ 85°C. This
creates a summary fault and will cause
the unit to mute itself and switchover to
the back-up unit. However, the 9V
supply to the FET transistors will
remain on until the unit reaches the
thermal shutdown temperature of ≥
90°C. For protection reasons, the unit
will shutdown the 9V supply to the
power transistors at temperatures at ≥
90°C.
Where: xx = Ok or FT
Summary Alarm is set to Fault (FT), if any
of items in Alarm Status are faulted.
Where: nnn = Yes or No
The TSC_ command can be used to
determine if the status of the terminal has
changed since it was last polled. If any of
the parameters listed in the RCS or RUS
commands have changed as a result of
user oprerations or if any new fault
conditions occur the TSC_ command will
return YES. The TSC_ command will then
continue to return YES until any of the
following commands are received: RCS_,
RUS_, RAS_, PACRCS_, PACRUS_, or
PACRAS_.
6-15
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
Where:
aa = FET1 current in Hex, formular:
FET1 = (aa * 3) mamps
bb = FET2 current in Hex, scaled 100mV
per count
cc = FET3 current in Hex, scaled 100mV
per count
dd = FET4 current in Hex, scaled 100mV
per count
ee = FET5 current in Hex, scaled 100mV
per count
ff = FET6 current in Hex, scaled 100mV
per count
gg = FET7 current in Hex, scaled 100mV
per count
hh = FET8 current in Hex, scaled 100mV
per count
ii = FET9 current in Hex, scaled 100mV
per count
jj = FET10 current in Hex, scaled 100mV
per count
kk = FET11 current in Hex, scaled 100mV
per count
ll = FET12 current in Hex, scaled 100mV
per count
mm = FET13 current in Hex, scaled
100mV
per count
nn = FET14 current in Hex, scaled
100mV per count
6-17
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
Where:
aa = FET1 current in Hex, formular:
FET1 = (aa * 3) mamps
bb = FET2 current in Hex, formular:
FET2 = (aa * 3) mamps
cc = FET3 current in Hex, scaled 100mV
per count
dd = FET4 current in Hex, scaled 100mV
per count
ee = FET5 current in Hex, scaled 100mV
per count
ff = FET6 current in Hex, scaled 100mV
per count
gg = FET7 current in Hex, scaled 100mV
per count
hh = FET8 current in Hex, scaled 100mV
per count
ii = FET9 current in Hex, scaled 100mV
per count
jj = FET10 current in Hex, scaled 100mV
per count
kk = FET11 current in Hex, scaled
100mV per count
ll = FET12 current in Hex, scaled 100mV
per count
mm = FET13 current in Hex, scaled
100mV per count
nn = FET14 current in Hex, scaled
100mV per count
oo = FET15 current in Hex, scaled
100mV per count
pp = FET16 current in Hex, scaled
100mV per count
qq = FET17 current in Hex, scaled
100mV per count
rr = FET18 current in Hex, scaled
100mV per count
ss = FET19 current in Hex, scaled
100mV per count
tt = FET20 current in Hex, scaled
100mV per count
uu = FET21 current in Hex, scaled
100mV per count
vv = FET22 current in Hex, scaled
100mV per count
ww = FET23 current in Hex, scaled
100mV per count
xx = FET24 current in Hex, scaled
100mV per count
yy = FET25 current in Hex, scaled
100mV per count
zz = FET26 current in Hex, scaled
100mV per count
a1 = FET27 current in Hex, scaled
100mV per count
6-18
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
Where:
a = COM1 Mode; 0 =RS-232,
1 = RS-485-2; 2 = RS-485-4
bb = Address in Hex (01 to FF)
c = 0 if Baud Rate = 9600
1 if Baud Rate = 4800
2 if Baud Rate = 2400
3 if Baud Rate = 1200
4 if Baud Rate = 300
d = 0 if Parity Even, 1 if Parity Odd
ee = LCD Contrast (0 to 30)
ff = LCD Brightness (0 to 30)
Where:
a = 1 if +28 Fault, else 0
b = 1 if +12 Fault, else 0
c = 1 if –12 Fault, else 0
d = 1 if + 5 Fault, else 0
e = 1 if – 5 Fault, else 0
f = 1 if + 9 PS#1 Fault, else 0
g = 1 if + 9 PS#2 Fault, else 0
h = 1 if TEMP Fault, else 0
I = 1 if SHTD Fault, else 0
j = 1 if FAN1 Fault, else 0
k = 1 if FAN2 Fault , else 0
l = 1 if PROC Fault, else 0
6.9.5 Stored Alarms
The 100 alarms are date/time stamped and stored in memory as they occur. The alarm
entry also is updated with its date/time of clearance. The entry remains in memory until it
is removed by command.
<DEV/LAA_'cr'
>DEV/LAA'cr'
xxx yyyyyyyyyyy hh:mm:ss mm /dd/yy'cr'
xxx yyyyyyyyyyy hh:mm:ss mm/dd/yy'cr'
xxx yyyyyyyyyyy hh:mm:ss mm /dd/yy'cr'
xxx yyyyyyyyyyy hh:mm:ss mm/dd/yy'cr'
xxx yyyyyyyyyyy hh:mm:ss mm /dd/yy'cr'
xxx yyyyyyyyyyy hh:mm:ss mm/dd/yy'cr'' lf']
This command retrieves the total number
of stored alarms and the time and date of
the most recent alarm.
Where :
xxx = stored fault number
yyyyyyyyyyy = fault description
hh:mm:ss = fault time
mm/dd/yy = fault date
6-19
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.9.6 Error Processing
The following Error Responses may be generated by any command instead of a
confirmation.
General Error Message:
>DEV?COM CU COMMAND UNRECOGNIZED'cr'' lf']
>DEV?COM IP INVALID PARAMETER'cr'' lf']
>DEV?COM PE PARITY ERROR'cr'' lf']
6.9.7 Configuration Errors
The following Error Responses may be generated by configuration commands.
Configuration Error Message:
>DEV?COM LO DEVICE IN LOCAL MODE'cr'' lf']
6.9.8 Time-Outs
A time-out should be assumed if there is no response in 1.0 seconds. The station monitor
and control computer should try at least three times. Possible sources of time-outs are
listed in Table 6-2:
Table 6-2. Possible Time-Out Sources
Incorrect Device Address
Faulty Cable
Faulty Connector
I/O fault on remote interface
I/O fault on monitor and control computer
6-20
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
6.10 Command Summaries
Table 6-3 and Table 6-4 summarize the remote control commands and commands
supported by virtual addressing mode.
Table 6-3. Remote Control Summary
Commands Display Reference
Utility
Set Time <DEV/TIM_hh:mm:ss'cr' 6.9.1
Set Date <DEV/DAT_mm/dd/yy'cr' 6.9.1
Set Physical Address <DEV/SPA_xxx'cr' 6.9.1
Set Baud Rate <DEV/SBR_xxxx'cr' 6.9.1
Set Parity Rate <DEV/SPB_xxxx'cr' 6.9.1
Set LCD Contrast <DEV/CON_xx'cr' 6.9.1
Set LCD Brightness <DEV/LCD_xx'cr' 6.9.1
Lamp Test (KPA-020IN) <DEV/LAM_xxx’cr’ 6.9.1
Retrieve Equipment type <DEV/RET_'cr' 6.9.1
Set Application ID Message <DEV/AID_xxx…xxx'cr' 6.9.1
Set Local/Remote Mode
(KPA-040)
Set Amplifier On/OFF <DEV/AMP_xxx'cr' 6.9.2
Mute/Unmute <DEV/MUT_xxx'cr' 6.9.2
Set Attenuation <DEV/ATT_xx.xx'cr' 6.9.2
Select Auto Fault Recovery <MDEV/AFR_xxx'cr' 6.9.2
Retrieve Configuration Status <DEV/RCS_'cr' 6.9.4
Retrieve Maintenance <DEV/RMS_'cr' 6.9.4
Retrieve FET Status <DEV/RFS_'cr' 6.9.4
Retrieve Utility Status <DEV/RUS_'cr' 6.9.4
Retrieve Alarm Status <DEV/RAS_'cr' 6.9.4
Summary Alarm Status <DEV/SAS_'cr' 6.9.4
Terminal Status Change <DEV/TSC_'cr' 6.9.4
Packed Configuration Status <DEV/PACRCS_'cr' 6.9.4
Packed Maintenance Status <DEV/PACRMS_'cr' 6.9.4
Packed FET Status <DEV/PACRFS_'cr' 6.9.4
Packed Utility Status <DEV/PACRUS_'cr' 6.9.4
Packed Alarm Status <DEV/PACRAS_'cr' 6.9.4
Retrieve Total Stored Alarms <DEV/TSA_'cr' 6.9.5
Clear All Stored Alarms <DEV/CAA_YES'cr' 6.9.5
List All Stored Alarms <DEV/LAA_'cr' 6.9.5
<DEV/LRS_x'cr' 6.9.1
Configuration Commands
Redundancy Mode Commands
Status Commands
Stored Alarm Commands
6-21
Ku-Band Solid-State Power Amplifier Revision 0
Remote Control MN/KPA.IOM
Table 6-4. Commands Supported by Virtual Addressing Mode
Commands Display Reference
Utility Commands
Retrieve Equipment Type <DEV/RET_'cr' 6.9.1
Configuration Commands
Set Amplifier On/Off <DEV/AMP_xxx'cr' 6.9.2
Mute/Unmute <DEV/MUT_xxx'cr' 6.9.2
Set Attenuation <DEV/ATT_xx.xx'cr' 6.9.2
Select Auto Fault Recovery <DEV/AFR_xxx'cr' 6.9.2
Status Commands
Retrieve Configuration Status <DEV/RCS_'cr' 6.9.4
Retrieve Maintenance Status <DEV/RMS_'cr' 6.9.4
Retrieve FET Status <DEV/RFS_'cr' 6.9.4
Retrieve Utility Status <DEV/RUS_'cr' 6.9.4
Retrieve Alarm Status <DEV/RAS_'cr' 6.9.4
Summary Alarm Status <DEV/SAS_'cr' 6.9.4
Terminal Status Change <DEV/TSC_'cr' 6.9.4
Packed Configuration Status <DEV/PACRCS_'cr' 6.9.4
Packed Maintenance Status <DEV/PACRMS_'cr' 6.9.4
Packed FET Status <DEV/PACRFS_'cr' 6.9.4
Packed Utility Status <DEV/PACRUS_'cr' 6.9.4
Packed Alarm Status <DEV/PACRAS_'cr' 6.9.4
6-22
Chapter 7. Maintenance and
7.1 General
Refer to the block diagram in Section 1 for interconnecting cables and general
troubleshooting help.
Troubleshooting
7-1
Ku-Band Solid-State Power Amplifier Revision 0
Maintenance and Troubleshooting MN/KPA.IOM
7.2 Maintenance Testing
For KPA080: The KPA is a Ku-Band KPA with an RF output level of +48.5 dBm at
1 dB compression.
For KPA100: The
1 dB compression.
KPA is a Ku-Band KPA with an RF output level of +49.5 dBm at
7.2.1 Test Point Samples
The RF input and output can be monitored at the RF Sample Test Points on the front
panel. Type N connectors are provided. The sample RF input level is -20 dBc nominal,
and the RF output level is -40 dBc nominal. Actual measured data for these sample ports
is located on the front panel.
7.3 Troubleshooting
Refer to Table 7-1.
KPA operating problems can be identified by first observing the status indicators on the
front panel. When a fault condition is indicated, the specific fault, or faults, can be
identified in the Current Faults Function Menu (Chapter 4) which is accessed through
the local operation keypad and displayed on the LCD display located on the front panel.
The status of
KPA functions is displayed in the Monitor Status Functions Menu.
Refer to Section 4, Operation, for a description of the KPA command functions; also,
check the status of the mute condition in the configuration menu (i.e.: Mute = “On”
means that the amplifier will be muted.)
7-2
Ku-Band Solid-State Power Amplifier Revision 0
Maintenance and Troubleshooting MN/KPA.IOM
Table 7-1. Troubleshooting
Symptom Possible Cause Solution
Unit does not turn On
(No display, No front
panel lights, No fans)
Fan(s) do not turn On. Faulty wiring or bad
Firmware not properly
Faulty 28V power supply. Check the output voltage of the 28V power
Failed fan or faulty control
Display not turning On,
Missing text, or Incorrect
backlighting.
1. Check power cord
connections.
2. Faulty wiring to 28V
power supply.
3. 28V power supply fault.
connections.
seated.
circuitry.
1. Firmware not properly
seated.
2. Faulty wiring or bad
connections.
3. Failed display or display
control card.
4. circuitry on AS/0200 or
AS/0206 PCB.
1. Ensure power cord is connected.
2. With input power cord disconnected, check
wiring and connections to 28V power supply.
Reconnect power cord.
3. Check output of 28 VDC power supply.
Remove and replace 28V power supply.
At power-up, the fans are sequenced on. In
Normal operation, the second fan does not turn
on until 3 seconds (approximately) after the first
fan.
1. Check AS/0206 PCB to ensure the
connections at P4 and P5 are not loose.
2. Check cable connection at the fans. There
should be 24 VDC (approximately) between
the two pins at the fan.
3. Check cable wiring if fautly or return to
factory for repair.
Fans are microprocessor controlled and
monitored.
1. Ensure U11 and U12 on AS/0200 are
properly seated.
2. Remove and replace AS/0200 PCB if
damaged.
supply.
1. Either via the front panel Monitort menu or
using a voltmeter.
2. Ensure that 28V is present.
Fan defective.
1. Replace fan.
2. Return to factory for repair re replacement.
1. Ensure U11 and U12 on AS/0200 are
properly seated.
2. Ensure good cable connections from M&C
cards AS/0200 and AS/0206 to display card
located behind front panel. Check cable
wiring and if required return cables to factory.
3. Return to factory for repair.
4. Return to factory for repair.
7-3
Ku-Band Solid-State Power Amplifier Revision 0
Maintenance and Troubleshooting MN/KPA.IOM
Table 7-1. Troubleshooting (Continued)
Symptom Possible Cause Solution
No RF output or ≤ output
level.
Failed KPA amplifier
module.
No remote control
communication
1. Mute fuction activated.
2. Amplification = Off
feature activated.
3. Large customer
attenuation values
selected.
4. Input power level not
correct.
5. Faulty input connections
from 9V supplies.
6. Fault KPA control cable
or connection.
This can usually be
determined by using the
Monitor menu to check the
DC current levels being
drawn by each transistor
inside the amplifier module.
Any transitor (QX) current
that is 50% more or less
than normal would
probably indicate a failure.
1. Incorrect cable
connections.
2. Improper
communication settings
between KPA and
controlling terminal.
3. Entry mode of unit set
to LOCAL.
1. Check the configuration menu to determine if
mute functions has been activated. Mute = On
Means that the unit is muted. Turn Mute
feature to Off to allow RF amplification of
the input signal.
2. The amplification = Off feature allows for
lower currect draw from the prome power
source under standby conditions. To obtain
RF output, ensure that this feature is set to
amplification = On.
3. Check the Attenuation = XX setting in the
configuration menu. Lower value to get more
gain.
4. Use the input sample port on the front panel
to determine that the input power level is as
specified. Remove and replace the input
cable.
5. Use the Monitor menu to check the internal
level of the PS1 and PS2. The levels should
be near 9V. If not correct, use a voltmeter to
measure the voltage where the #8 wires enter
the amplifier unit. With Unit Off, tighten
connections if necessary.
6. Check the 25-pin ribbon cable connection at
the amplifier module and at AS/0200 PCB.
Tighten as necessary.
Nominal Values:
Q1 = 20mA
Q2 = 100 mA
Q3, Q4 = 1.0 A
Q5, Q6, Q7 = 2.0 A
Q8 to Q19 = 2.25 A
Q20 to Q27 = 5.5 A
There are no user serviceable parts inside the
amplifier module. Return to factory for repair.
1. Ensure cable is connected properly.
2. Check settings of KPA along with remote
control terminal software.
3. Change entry mode setting in Configuration
menu to Remote.
7-4
Ku-Band Solid-State Power Amplifier Revision 0
Maintenance and Troubleshooting MN/KPA.IOM
Table 7-1. Troubleshooting (Continued)
Symptom Possible Cause Solution
Amplifier Temperature
Fault
1. Operating temperature
9V power supply fault
(PS1 and/or PS2)
Faulty/Improper
Redundancy Switch
Operation
Note: KPA module contains as internal temperature monitor that wilkl shut off
the unit (i.e. turn off the 9V supplies) if the Heatsink temperature becomes
excessive. This prevents the transistors from overheating and destruction. After
cooling down below the tripo point, the unit will automatically restart.
limits exceeded.
2. Air intake or air exhaust
paths obstructed.
3. Fan failed.
4. Defective transistors in
amplifier module.
1. Faulty wire or
connection.
2. Excessive current draw
from transistor inside
amplifier module.
3. Faulty power supply.
1. Faulty wiring or
connections.
2. Improper settings.
1. Do not exceed 50°C (122°F) ambient input
air temperature.
2. Remove obvstructions to ensure adequate air
flow and proper amplifier cooling.
3. Check fan operation. Remove and replace
fan(s) as required.
4. Use Monitor menu to check transistor
currents. Compare readings with the
specified nominal values. Report excessive
readings to the manufacturer for repair.
There are no user serviceable parts inside
the KPA amplifier module.
1. Check cable and connections from PS1 and
PS2 to amplifier module. On outside of
module, measure voltage.
Reading should be = 9.0 ± 0.5 VDC.
2. Use Monitor menus to check transistor
currents. Record excessive values and return
entire unit to manufacturer for repair.
3. Return failed power supply for repair.
Replace with the new power supply.
1. Ensure that the RF and control cables are
connected. Poor RF performances would
tend to indicate a faulty KPA
cable/connector.
a. Improper switch control would indicate
a problem with the control cables.
b. Ensure the ends of the cables labeled
backup are connected to the backup
unit.
2. Check redundancy setup in Configuration
menu.
7-5
Ku-Band Solid-State Power Amplifier Revision 0
Maintenance and Troubleshooting MN/KPA.IOM
NOTES:
7-6
Ku-Band Solid-State Power AmplifierRevision 0 SpecificationsMN/KPA.IOM
Appendix A. Specifications
A.1 General
The following tables are individual specifications for:
• KPA-020IN
• KPA-040
• KPA-080
• KPA-100
A-1
Ku-Band Solid-State Power Amplifier Revision 0
Specifications MN/KPA.IOM
Table A-1. KPS-020IN Specifications
Parameters Specifications
Input
Level -10dBm Typical
Impedance
50Ω
Noise Figure 10 dB Typical, 15 dB max at max gain
VSWR 1.25: 1 maximum
Connector SMA Female
Output
Frequency 14.0 to 14.5 GHz
Power 42.5 dBm minimum at 1 dB Compression
Mute 60 dB
VSWR 1.25:1 maximum
Connector WR75G Waveguide
Gain
Linear 50 dB minimum, 53 dB Typical
Adjust 20 dB in 0.25 dB steps
Fill Band
Per 40 MHz
50Ω
Noise Figure 10dB Typical, 15 dB max at max gain Data Entry Cursor Control Keypad
VSWR 1.25: 1 maximum Output Sample
Connector SMA Female Input Sample
Output Remote Control
Frequency 14.0 to 14.5 GHz COM Port RS-232 or RS-485
Power 48.5 dBm minimum at 1 dB Compression Protocol ASCII
Mute 60 dB Alarms
Impedance
50Ω
VSWR 1.25: 1 maximum LED
Connector WR75G Waveguide Power On Green
Gain Fault Red
Linear 61 dB minimum, 64 db Typical Stored Fault Red
Adjust 20 dB in 0.25 dB steps TX On Yellow
Full Band
Per 40 MHz
0 to +50°C
(32 to 122°F)
± 0.75 dB
± -0.25 dB
± 0.50 dB at center frequency
± 1.00 dB full band
Third Order Intermodulation Envelop 8.75H x 19W x 24D inches
Products -30 dBc Typical, -25 dBc maximum
@ 3 dB total backoff
(2 tones, ∆F = 1 MHz)
AM to PM Conversion Enviromental
Output 2.0 degrees typical, 3.0 max @ rated output Temperature:
Group Delay (per 40 MHz) Humidity:
Linear
Parabolic
± 0.03 ns/MHz
± 0.003 ns/MHz
2
Ripple 1.0 ns Peak-to-Peak VAC 180 to 270 VAC, 47 to 63 Hz
Display 20 x 2 LCD
Type N (f), 50Ω, -40 dBc nominal
Type N (f), 50Ω, -20 dBc nominal
Display 20 x 2 LCD
Noise Figure 10dB Typical, 15 dB max at max gain Data Entry Cursor Control Keypad
VSWR 1.25: 1 maximum Output Sample
Connector SMA Female Input Sample
Type N (f), 50Ω, -40 dBc nominal
Type N (f), 50Ω, -20 dBc nominal
Level -10 dBm Typical
Output Remote Control
Frequency 14.0 to 14.5 GHz COM Port RS-232 or RS-485
Power 49.5 dBm minimum at 1 dB Compression Protocol ASCII
Mute -60 dB Alarms
Impedance
50Ω
Summary Fault Form C
VSWR 1.25: 1 maximum LED
Connector WR75G Waveguide Power On Green
Gain Fault Red
Linear 65 dB minimum, 70 db Typical Stored Fault Red
Adjust 20 dB in 0.25 dB steps TX On Yellow
Full Band
Per 40 MHz
0 to +50°C
(32 to 122°F)
± 0.75 dB
± 0.25 dB
± 0.50 dB at center frequency
± 1.00 dB full band
Online Yellow
Remote Yellow
Mechanical
Third Order Intermodulation Envelop 8.75H x 19W x 24D inches
(22.22H x 48.26W x 60.96D cm)
Products -30 dBc Typical, -25 dBc maximum
Weight 75 lbs (34 kg)
@ 3 dB total backoff
(2 tones, ∆F = 1 MHz)
AM to PM Conversion Enviromental
Output 2.0 degrees typical, 3.0 max @ rated output Temperature:
Operating
Storage
Group Delay (per 40 MHz) Humidity:
Operating
Storage
Linear
± 0.03 ns/MHz
Shock Normal Commercial
0 to 50°C (32 to 122°F)
-40 to 70°C (-40 to 158°F)
10 to 95% Noncondensing
0 to 100% Noncondensing
Shipping and Handling
Parabolic
± 0.003 ns/MHz
2
Power Requirements
Ripple 1.0 ns Peak-to-Peak VAC 180 to 270 VAC, 47 to 63 Hz