Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform the basic maintenance
functions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service
personnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. These instructions describe how to install, start up, and
service 62E energy recovery ventilator (ERV) units.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all disconnect locations to alert others not to restore power until work
is completed.
GENERAL
The 62E ERV units recover energy from building exhaust
air and pre-condition ventilation air. See Tables 1A-2B for unit
data. All 62EB-62EU units are configured for vertical discharge (through the bottom). Vertical units may be installed on:
• a stand-alone roof curb
• a combination curb for direct coupled connection to a
rooftop unit
If horizontal supply and return is desired using a vertical
unit, the vertical unit may be installed on a horizontal supply/
return base.
NOTE: The horizontal supply/return base accessory includes a
roof curb. The horizontal supply/return base should NOT be
used with a stand-alone roof curb.
All 62E2-62E7 units are configured for horizontal discharge
(through the side). Horizontal units may be installed on a
stand-alone roof curb.
DIRECT COUPLED APPLICATIONS (Vertical) — The
ERV unit can be installed directly coupled to a RTU (rooftop
unit). For vertical (through the roof) applications, the connection between the 62EB-62EU ERV unit and the RTU may be
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53620007-01Printed in U.S.A.Form 62E-C1SIPg 18-10Replaces: New
made with the use of a combination roof curb or by using the
drop in damper box accessory. The combination roof curb is a
single curb that supports both the ERV and the RTU and as
internal supply and exhaust air transitions. The drop in damper
box provides a means to make the supply and exhaust air transitions below the roof.
Table 1A — Physical Data — SI
UNIT 62EBA/7ABC/7CCC/2CCD/2DCG/2GDD/3DDG/3G
NOMINAL CAPACITY (L/s)165235470425520615755
CAPACITY RANGE (L/s)94-37894-378236-543189-519236-661283-755378-944
MAXIMUM SHIPPING WEIGHT (kg)150152221228228284284
MAXIMUM OPERATING WEIGHT (kg)127130199205205262262
UNIT DIMENSIONS (mm)
Typ e MonolithicSegmented
Size (Diam x Depth) (mm) 483 x 25483 x 51635 x 51635 x 76762 x 76
Nominal Drive Motor kW0.070.070.070.070.07
SUPPLY/EXHAUST FANS
Typ e Centrifugal DWDIBackward Inclined, Single Width Single Inlet
Drive Type DirectEC Motor with Integral Frequency Drive
Fan Option Code
(see fan option table)
FILTERS
Typ e 51 mm Pleated
Exhaust Air – Qty...Size (L x W x D) (mm)1...305 x 610 x 511...356 x 635 x 512…406 x 635 x 51
Outside Air – Qty...Size (L x W x D) (mm)1...305 x 610 x 511...356 x 635 x 512…406 x 635 x 51
AA, BCC
UNIT 62EEB/4BED/4DEF/4FEG/4GHB/5BHD/5DHF/5FHG/5GKD/6DKG/6G
NOMINAL CAPACITY (L/s)660104010401225141521702170259521253680
CAPACITY RANGE (L/s)378-850 519-1227 614-1274 614-1652 661-1700
UNIT 62ELDLGMDMGNDNGPDPG
NOMINAL CAPACITY (L/s) 35854340283051005200650059507080
CAPACITY RANGE (L/s)1650-42502360-56651415-35402595-68452595-6370330-82602830-73153540-9440
MAXIMUM SHIPPING
10…508 x 508 x 518…610 x 610 x 518…635 x 635 x 518…635 x 635 x 51
10…508 x 508 x 518…610 x 610 x 518…635 x 635 x 518…635 x 635 x 51
G, H, J, NH, J, K, N
H, K, J,
N, P, R
K, J, N, P, RH, K, J, N, P, R
3
Table 1B — Physical Data — English
UNIT 62EBA/7ABC/7CCC/2CCD/2DCG/2GDD/3DDG/3G
NOMINAL CAPACITY (cfm) 3505001000900110013001600
CAPACITY RANGE (cfm) 200-800200-900500-1150400-1100500-1400600-1600800-2000
MAXIMUM SHIPPING WEIGHT (lb)331336488502502627627
MAXIMUM OPERATING WEIGHT (lb)281286438452452577577
UNIT DIMENSIONS (in.)
Typ e MonolithicSegmented
Size (Diam x Depth) (in.) 19 x 1.019 x 2.025 x 2.025 x 3.030 x 3.0
Nominal Drive Motor Hp 0.090.090.090.090.09
SUPPLY/EXHAUST FANS
Typ e Centrifugal DWDIBackward Inclined, Single Width Single Inlet
Drive Type DirectEC Motor with Integral Frequency Drive
Fan Option Code
(see fan option table)
FILTERS
Typ e 2 in. Pleated
Exhaust Air – Qty...Size (L x W x D) (in.)1...12 x 24 x 21…14 x 25 x 22…16 x 25 x 2
Outside Air – Qty...Size (L x W x D) (in.)1...12 x 24 x 21…14 x 25 x 22…16 x 25 x 2
UNIT 62EEB/4BED/4DEF/4FEG/4GHB/5BHD/5DHF/5FHG/5GKD/6DKG/6G
NOMINAL CAPACITY (cfm)1,4002,2002,2002,6003,0004,6004,6005,5004,5007,800
Typ e Segmented
Size (Diam x Depth) (in.)36 x 1.536 x 3.036 x 1.536 x 3.052 x 1.552 x 3.052 x 1.552 x 3.064 x 3.0
Nominal Drive Motor Hp1/61/61/61/61/61/61/4
SUPPLY/EXHAUST FANS
Typ eBackward Inclined, Single Width Single Inlet
Drive TypeEC Motor with Integral Frequency Drive
Fan Option Code
10…20 x 20 x 28…24 x 24 x 28…25 x 25 x 28…25 x 25 x 2
10…20 x 20 x 28…24 x 24 x 28…25 x 25 x 28…25 x 25 x 2
9,000-
24,000
G, H, J, NH, J, K, N
8,000-
20,000
11,000-
29,000
9,000-
22,000
H, K, J,
N, P, R
12,000-
31,000
K, J, N, P, RH, K, J, N, P, R
10,000-
25,000
14,000-
36,000
5
Table 2A — Supply/Exhaust Fan Options Physical Data — SI
FAN OPTION CODEABCEFGH
Wheels
Qty...Width (mm)
Nominal Motor kW
(per each fan)
1…128 x 1102…128 x 1101…4001…5002…5003…5004…500
0.450.450.882.702.702.702.70
FAN OPTION
CODE
Wheels
Qty...Width (mm)
Nominal Motor kW
(per each fan)
JKLMNPRS
5…5006…5001…6302…6303…6307…5008…5001…250
2.702.702.902.902.902.702.702.70
Table 2B — Supply/Exhaust Fan Options Physical Data — English
FAN OPTION CODEABCEFGH
Wheels
Qty...Width (in.)
Nominal Motor Hp
(per each fan)
FAN OPTION
CODE
Wheels
Qty...Width (in.)
Nominal Motor Hp
(per each fan)
DIRECT COUPLED APPLICATIONS (Horizontal) — For
horizontal applications (above the roof) using 62EB-EU units,
the horizontal supply/return base and transition accessories
may be used.
For horizontal applications using 62E2-E7 units, a standard
roof curb and transition accessories may be used.
1…5 x 4 1/82…5 x 4 1/81…15 3/41…19 3/42…19 3/43…19 3/44…19 3/4
INSTALL DUCTWORK — Ductwork will be installed in the
curb for combination curb applications. The supply duct will
hang from the top of the curb. The return duct will attach to a
stub duct provided with the combination roof curb.
NOTE: Ductwork must be installed before the RTU is set in
place.
INSTALL GASKETS — The combination curbs come with a
INSTALLATION
Step 1 — Inspect the Unit —
claim with the shipping company if the unit is damaged. Check
the packing list to ensure that the correct items have been
received and notify your Carrier representative of any
discrepancy.
tion roof curb is a single curb that supports both the ERV and
RTU and has internal supply and exhaust air transitions. See
Fig. 1.
NOTE: For horizontal applications with 62E2-E7 units, a standard roof curb and horizontal transition can be used.
LOCATE THE COMBINATION CURB — Prior to locating the combination curb, consider the structural support required for the rooftop system and the duct drop location in relation to the joists. Allow sufficient space for service, clearance,
and locations of vents or other sources of air. Refer to Fig. 2
and 3 for ERV clearance requirements. Refer to the rooftop installation instructions for more information regarding location
considerations.
PREPARE ROOF CURB LOCATION — Cut a hole in the
roof for duct openings. Your local Carrier sales representative
can provide dimensional drawing for the combination curb.
See this drawing for duct opening dimensions. Frame the opening to provide adequate structural support.
SET THE COMBINATION CURB — Set the combination
curb over the roof opening. Level the curb by placing shims
under the bottom flange of the curb. Secure the curb in place by
welding or fastening the curb to the roof.
For 62EB-EU units, the combina-
gasketing package to provide a seal between the RTU and ERV
units and the top perimeter of the combination curb. Install the
gasket around the top perimeter of the curb and around the supply and return opening. Gasket strips must fit tightly together,
leaving no gaps for leakage.
INSTALL ROOFING MATERIALS — Insulate and add a
cant strip to the combination curb. Follow suggested and acceptable roofing procedures for applying roofing materials.
The roofing material should extend up to the wood nailer and
be secured under the counter flashing. Follow all local, national, and industry roofing standards. Refer to Fig. 4 for roofing
recommendations.
signed to fit into the return air openings of the standard factory
curb of Carrier RTUs. The damper box provides connections
for return air from the conditioned space, exhaust air to the
ERV, and ventilation air from the ERV. The ERV would be installed on a stand-alone roof curb and field-supplied ductwork
would be run between the damper box and ERV curb. See
Fig. 5. The maximum length of the field-supplied duct is 100
equivalent feet.
LOCATE THE ERV ROOF CURB — Prior to locating the
ERV roof curb consider the structural support required for the
rooftop system, the duct drop location in relation to the joists,
and the 100 equivalent foot duct length limitation between the
ERV and RTU. Allow sufficient space for service, clearance,
and locations of vents or other sources of air. Refer to Fig. 2
and 3 for ERV clearance requirements. Refer to the rooftop installation instructions for more information regarding location
and installation considerations for the RTU curb.
The drop-in damper box accessories are de-
6
ASSEMBLE THE ERV ROOF CURB — Connect the curb
Fig. 1 — Typical Combination Curb
LEGEND
NOTES:
1. Return air ductwork sits 12 in. below bottom of
curb. (Stub duct provided.)
2. Dimensions shown in inches.
ERV— Energy Recovery Ventilator
RTU— Rooftop Unit
side and the curb end. Insert the tabs on the curb end into the
slots on the curb sides. See Fig. 6. Press firmly until the pieces
lock into place. It may be necessary to exert additional force on
top of the curb to lock the pieces in place. Ensure the curb pieces are locked together prior to proceeding further. Repeat for
other corners of the roof curb.
NOTE: If lifting or moving the roof curb assembly, hammer
the tabs over 90 degrees.
PREPARE ROOF CURB LOCATION — Cut a hole in the
roof for duct openings. See Fig. 7 for duct opening dimensions.
Frame the opening to provide adequate structural support.
SET THE ERV ROOF CURB — Fit the roof curb assembly
by measuring across the corners of the curb to ensure a square
fit. Set the roof curb over the roof opening. Level the curb by
placing shims under the bottom flange of the curb. Secure the
curb in place by welding or fastening the curb to the roof.
INSTALL DUCTWORK — Ductwork will be installed in the
ERV roof curb for applications utilizing the drop-in damper
box. The duct will hang from the top of the curb. Refer to
Fig. 7 to determine the duct size required. Provide fieldmanufactured duct and place into the supply and return openings in the curb.
NOTE: Ductwork must be installed in the ERV curb before the
ERV unit is set in place.
NOTE: Drop-in damper box must be installed in the RTU curb
before the RTU is set in place.
INSTALL GASKETS — The ERV roof curbs come with a
gasketing package to provide a seal between the ERV unit and
the top perimeter of the roof curb. Install the gasket around the
top perimeter of the curb and around the supply and return
opening. Gasket strips must fit tightly together, leaving no gaps
for leakage.
IMPORTANT: Gasket installation is critical for water
integrity. Improperly installed gaskets can result in air or
water leaks, leading to poor unit performance.
INSTALL ROOFING MATERIALS — Insulate and add a
cant strip to the roof curb. Follow suggested and acceptable
roofing procedures for applying roofing materials. The roofing
material should extend up to the wood nailer and be secured
under the counter flashing. Follow all local, national, and industry roofing standards. Refer to Fig. 4 for roofing recommendations.
INSTALL DROP-IN DAMPER BOX — Place the damper
box into the RTU curb. Allow the damper box flanges to rest
on the curb. Secure the damper box in place with 1-in. self-tapping screws. Install ductwork to connect the damper box to the
ERV curb. The upper damper box connection must be ducted
to the ERV supply air, and the lower damper box connection
must be ducted to the ERV exhaust air. See Fig 5. Refer to the
drop-in damper box dimensional sheets to determine the duct
size required. Your local Carrier sales representative can provide you with this dimensional data.
Step 4 — Install Horizontal Base and Transition (62EB-EU and 62E2-E7 Units) —
zontal transition accessory is used to connect the ERV to the
horizontal return of a Carrier rooftop unit. To provide horizontal exhaust and ventilation air connections on 62EB-EU units,
the horizontal base accessory must also be installed. The accessory is not needed on 62E2-E7 units. The rooftop unit must be
installed on a standard 14 in. high roof curb and positioned at a
specific distance relative to the ERV base. A typical arrangement is shown in Fig. 8 and 9. See Fig. 10 for 62E2-E7 unit dimensions. Your local Carrier sales representative can provide
you with dimensional data for the appropriate Carrier RTU and
62E model installation.
LOCATE THE ROOF CURB — Prior to locating the roof
curb consider the structural support required for the rooftop
system. Allow sufficient space for service, clearance, and locations of vent or other sources of air. Refer to Fig. 2, 3, and 10
for ERV clearance requirements. Refer to the rooftop installation instructions for more information regarding location
considerations.
Proper location of the roof curb in relationship to the RTU
roof curb is critical for proper fit of the horizontal transition.
See Fig. 8 and 9. Refer to the ERV unit submittals provided by
your local Carrier sales representative for the correct
dimensions.