Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precautions in the li terature, ta gs and label s attached t o the uni t, and
other safety precautions that apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations.
Ensure voltage listed on unit data plate agrees with electrical supply provided for the unit.
Disconnect gas piping from unit when leak
testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve
damage resulting in hazardous condition. If
gas valve is subjected to pressure greater than
1
/
2
pressure testing field-supplied gas piping at
pressures of
such piping must be isolated by manually closing the gas valve.
Before performing service or maintenance operations on
unit, turn off main power switch to unit and install lockout
tag. Electrical shock could cause personal injury.
Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from side
duct opening covers and remove covers. Using the same
screws, install covers on vertical duct openings with the insulation side down. Seals around duct openings must be tight. See
Fig. 1.
Step 1 — Provide Unit Support
ROO F CU R B — Assemble and instal l acces sory roof curb in
accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as
Ductwork must be attached to curb, not to the unit. The
shown.
accessory thru-the-bottom power and gas connection package
must be installed before the unit is set on the roof curb.
installed (thru-the-roof curb) gas connections are desired, use
factory-supplied
mount the thru-the-roof curb connection to the roof curb. Gas
connections and power connections to the unit must be field installed after the unit is installed on the roof curb.
If electric and control wiring is to be routed through the
basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions.
IMPORTANT: The gasketing of th e unit to the roof curb
is critical for a watertight seal. Install gasket supplied
with the roof curb as shown in Fig. 2. Improperly
applied gasket can also r esult in air or water leaks and
poor unit performance.
3
must
psig, it
be replaced before use. When
1
/2 psig or less, a unit connected to
INSTALLATION
If field-
/4 in. pipe coupling and gas plate assembly to
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Ta b 1 a 6 a
PC 111Catalog No. 534-774Printed in U.S.A.Form 48TJ-18SIPg 110-00Replaces: 48TJ-16SI
Fig. 1 — Horizontal Conversion Panels
(Viewed from Duct End)
Curb should be level. Unit leveling tolerances are shown in
Fig. 3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
SLAB MOUNT (Horizontal Units Only) — Provide a level
concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to
prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Step 2 — Field Fabricate Ductwork —
ducts to roof curb and building structure on vertical units.
not connect ductwork to unit.
supplied flanges should be attached to horizontal discharge
openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof
openings with counter flashing and mastic in accordance with
applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with applicable fire codes.
A minimum clearance is not required around ductwork.
Cabinet return air static shall not exceed –.30 in. wg with
EconoMi$er, or –.35 in. wg with Durablade Economizer, or
–.45 in. wg without economizer.
These units are designed for a m inimum continuous returnair temperature of 50 F (dry bulb), or an intermittent operation
down to 45 F (dry bulb) (in heating mode), such as when used
with a night set-back thermostat.
For horizontal applications, field-
Secure all
Do
Step 3 — Install External Trap for Condensate
Drain —
located on the bottom and side of the unit. Unit discharge
connections do not determine the use of drain connections;
either drain connection can be used with ve rtical or horiz ontal
applications.
When using the standard side drain connection, make sure
the plug (Red) in the alternate bottom connection is tight before
installing the unit.
To use the bottom drai n connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom
connection to the side connection. See Fig. 4. The piping for
the condensate drain and external trap can be completed after
the unit is in place.
All units must have an external trap for condensate drainage. Install a trap at least 4-in. deep and protect against fr eezeup. If drain line is installed downstream from the external trap,
pitch the line away from the unit at 1 in. per 10 ft of run. Do not
use a pipe size smaller than the unit connection (
Step 4 — Rig and Place Unit —
transportation damage. File any claim with transportation
agency. Keep unit upright and do not drop. Spreader bars are
not required if top crating is left on unit. Rollers may be used to
move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional information.
Lifting holes are provided in base rails as shown in Fig. 6.
Refer to rigging instructions on unit.
All panels must be in place when rigging and lifting.
The unit’s 3/4-in. condensate drain connections are
3
/4 in.).
Inspect unit for
2
‘‘B’’‘‘C’’
11
1′-9
/16″
[551]
1′-4″
[406]
‘‘D’’ ALT
DRAIN HOLE
13/4″
[44.5]
‘‘E’’
Gas
3
″
/
4
[19] NPT
1
″
/
2
[12.7] NPT
3
/4″
[19] NPT
“F”
Powe r
3
/4″
[19] NPT
1
1
″
/
4
[31.7]
3
″
/
4
[19] NPT
11/4″
[31.7]
“G”
Control
1
/2″
[12.7] NPT
CONNECTOR
PKG ACY
CRBTMPWR001A00
CRBTMPWR002A00
CRBTMPWR003A00
CRBTMPWR004A00
ROOF CURB
ACCESSORY
CRRFCURB001A00
CRRFCURB002A00
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels:
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on
curb).
6. Service clearance 4′ on each side.
‘‘A’’
1′-2″
[356]
2′-0″
[610]
UNIT SIZE
48TJ
004-007
7.Direction of airflow.
8. Connector packages CRBTMPWR001A00 and
2A00 are for thru-the-curb type. Packages
CRBTMPWR003A00 and 4A00 are for the thruthe-bottom type connections.
TO ENSURE AIRTIGHT CONNECTION
PLACE UNIT AS CLOSE TO
END AS POSSIBLE.
TO ENSURE AIRTIGHT CONNECTION
PLACE UNIT AS CLOSE TO
END AS POSSIBLE.
Fig. 2 — Roof Curb Dimensions
3
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 3 — Unit Leveling Tolerances
CONDENSATE PAN (SIDE VIEW)
DRAIN PLUG
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Internal Trap Condensate Drain
POS ITION ING — Maintain cleara nce around and above unit
to provide minimum distance from combustible materials,
proper airflow, and service access. See Fig. 6. A properly positioned unit will have the following clearances between unit and
roof curb:
1
/4-in. clearance between roof curb and ba se rails on
each side and duct end of unit; 1/4-in. clearance between roof
curb and condenser coil end of unit. (See Fig. 2, section C-C.)
Do not install unit in an indoor location. Do not locate unit
air inlets within 10 ft of exhaust vents or other sources of contaminated air or as local codes require.
Be sure that unit is installed so that snow will not block the
combustion intake or flue outlet.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from
higher level runoff and overhangs.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and
gas relief equipment.
Minimum distance between unit and other electrically live
parts is 48 inches.
Flue gas can deteriorate building materials. Orient unit such
that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), and ANSI
(American National Standards Institute) Z223.1, and NFPA
(National Fire Protection Association) 54 TIA-54-84-1.
In Canada, installation must be in accordance with the
CAN1- B149 installation codes for gas burning appliances.
After unit is in position, remove rigging skids and shipping
materials.
Step 5 — Install Flue Hood —
Flue hood is shipped
screwed to the burner compartment access panel. Remove
from shipping location and using screws provided, install flue
hood and screen in location shown in Fig. 7.
For units size 004-006 being installed in California Air
Quality Management Districts, which require NOx emissions
of 40 nanograms/joule or less, a field-installed low NOx kit
must be used.
Step 6 — Install Gas Piping —
Unit is equipped for
use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1 entitled National Fuel Gas Code. In Canada, installation must be
in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas
connection must not be less than 4 in. wg or greater than
13.0 in. wg while unit is operating. On 48TJ005,006,007 high
heat units, the gas pressure at unit gas connection must not be
less than 5 in. wg or greater t han 13 in. wg while the unit is
operating. For propane applications, the gas pressure must not
be less than 5 in. wg or greater than 13 in. wg at the unit
connection.
Size gas sully piping for 0.5 in. wg maximum pressure drop.
Do not use supply pipe small than unit gas connection. Support
gas piping as shown in the table in Fig. 8. For example, a
3
/4-in.
gas pipe must have one field-fabricated support beam every
8 ft. Therefore, an 18-ft long gas pipe would have a minimum
of 2 support beams, a 48-ft long pipe would have a minimum
of 6 support beams.
See Fig. 8 for typical pipe guide and locations of external
manual main shutoff valve.
4
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in
detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
3. Unit weights do not include economizer. See Table 1 for economizer weights.
Unit cabinet must have an uninterrupted, unbroken elect rical ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code), ANSI/NFPA, latest edition, and local electrical
Do not use gas piping as an electrical ground.
codes.
ure to follow this warning could result in the installer being
liable for personal injury of others.
DISCONNECT BOX LOCATION — The field-supplied disconnect box may be mounted on the unit’s end panel or on the
corner post. Mount disconnect box on the left side of the rating
plate when mounting on the unit’s end panel.
disconnect box over the unit rating plate.
Do not mount the
When mounting
disconnect box on corner post, secure disconnect box to corner
post and condenser coil top cover. See Fig. 7.
A disconnect box mounting space is available when an optional or accessory condenser coil grille is used. Mount the disconnect on the sheet metal provided with t he condenser coil
grille. The sheet metal is loc ated adjacent to the corner post on
the left side of the power wiring access panel.
Fail-
FIELD POWER SUPPLY — All units except 208/230-v
units are factory wired for the voltage shown on the nameplate.
If the 208/230-v unit is to be connected to a 208-v power supply, t he transformer
must
be rewired by disconnecting the black
wire from the 230-v terminal wire on the transformer and connecting it to the 200-v red terminal of the transformer.
Refer to unit label diagram for additional information. Wiring leads are provided for field service. Use copper conductors
only when splice connectors are used.
When installing units, provide a disconnect per NEC.
All field wiring must comply with NEC and local requirements. In Canada, electrical connections must be in accordance
with CSA (Canadian Standards Association) C22.1 Canadian
Electrical Code Part One.
Install field wiring as follows:
1. Connect ground lead to chassis ground connection when
using separate ground ties.
2. Install conduit between disconnect and side panel. Insert
conduit through power supply knockout opening. See
Fig. 9.
3. Connect power lines to power wiring leads.
4. Pigtails are provided for field power connections and are
located inside the burner access panel. See Fig. 10 and 11.
Use factory-supplied splices or Underwriters’ Laboratories (UL) approved copper connector .
5
Table 1 — Physical Data
UNIT SIZE 48TJE/F004D/E/F005D/E/F006D/E/F007
NOMINAL CAPACITY (tons)3456
OPERATING WEIGHT (lb)
4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal discharge units, field-supplied flanges should be attached to horizontal discharge openings, and all
ductwork should be attached to the flanges.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Between unit, flue side and combustible surfaces, 36 inches.
b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.
Bottom of base rail to combustible surfaces (when not using curb) 0 inches.
c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater
clearance is optional.
d. Overhead, 60 in. to assure proper condenser fan operation.
e. Between units, control box side, 42 in. per NEC.
f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.
per NEC.
h. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustion side as stated in notes
5a, b and c, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering
material if set on base rail.
8. The ver tical ce nter of gravity is 1′-6″ [457] up from the bottom of the base rail.
CORNER
WEIGHT
(D)
BOTTOM POWER CHART, THESE HOLES REQUIRED FOR
USE WITH ACCESSORY PACKAGES — CRBTMPWR001A00,
(POWER AND CONTROL) AND CRBTMPWR003A00
(POWER, CONTROL, AND GAS)
THREADED
CONDUIT SIZE
1
″″″″
/
2
3
″″″″
/
4
1
″″″″
/
FPT
2
WIRE
USE
24 V
Powe r11/
Gas11/
HOLE SIZES (MAX.)
REQURED
7
/
[22.2]
″″″″
8
[28.4]
″″″″
8
[31.8]
″
″
″ ″
4
Fig. 6 — Base Unit Dimensions
8
CONDENSER
COIL
TOP COVER
CORNER POST
INTAKE
LOUVERS
FLUE HOOD
Fig. 7 — Flue Hood Details
END PANEL
Fig. 9 — Conduit Installation
LEGEND
NFGC —
*Field supplied.
NOTE: Follow all local codes.
National Fuel Gas Code
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL
DIAMETER
(in.)
1
/
2
3
or 1
/
4
1
1
or larger
/
4
X
DIMENSIONS
(feet)
6
8
10
Fig. 8 — Gas Piping Guide (With Accessory
Thru-the-Curb Service Connections)
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate (see Table 2).
On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula shown
in the legend for Table 2, Note 2 to determine the percent of
voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate
any applicable Carrier warranty.
FIELD CONTR OL WIRING — Install a Carrier-approved
accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat
assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation
instructions. Connect thermostat wires to terminal board.
Route thermostat cable or equivalent single leads of colored
wire from subbase terminals through connector on unit to lowvoltage connections (shown in Fig. 12).
LEGEND
IGC —
LED —
Integrated Gas Unit Controller
Light-Emitting Diode
Fig. 10 — Component Location
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C minimum). All
wire larger than no. 18 AWG cannot be directl y connected to
the thermostat and will require a junction box and splice at the
thermostat.
Feed control wires through the raceway located between the
condenser coil top cover and burner side panel. See Fig. 10.
Connect control wires to corresponding screw terminals, the
low-voltage connections located inside low-voltage access
panel. See Fig. 12 for connections. The low-voltage connections provide the UL required clearance between high- and
low-voltage wiring.
HEAT ANTICIPATOR SETTINGS — Set heat anticipator
settings at .14 amp for the first stage and .14 amp for secondstage heating, when available.
9
208/230-1-60
208/230-3-60
460-3-60
(SIZE 007 ONLY)
LEGEND
C—
COMP —
NEC—
TB—
Contactor
Compressor
National Electrical Code
Terminal Block
575-3-60
(SIZE 007 ONLY)
208/230-3-60
575-3-60, 460-3-60
(SIZES 004-006)
Fig. 11 — Power Wiring Connections
LEGEND
AHA —
Adjustable Heat Anticipator
Field Wiring
Factory Wiring
Fig. 12 — Low-Voltage Connections
10
Table 2 — Electrical Data
UNIT
48TF
NOMINAL
V-P h- Hz
208/230-1-60
VOLTAGE
IFM
TYPE
RANGE
Min MaxRLALRAQty Hp FLAMCAMOCP†FLALRA
Std
187 25416.296.01
Alt4.926.6/26.635/3526/26111/111
COMPRESSOR
(ea)
Std
208/230-3-60
187 25410.275.01
Alt4.919.1/19.125/2519/1990/90
High5.219.4/19.425/2519/19109/109
004
460-3-60
Std
414 5084.440.01
Alt2.18.415848/48
High2.68.915957/57
Std
575-3-60
518 6323.731.01
Alt2.16.915837
High2.67.315745
208/230-1-60
Std
187 25423.3118.01
Alt4.935.4/35.445/4534/34133/133
Std
208/230-3-60
187 25415.490.01
Alt4.925.6/25.630/3025/25105/105
High5.225.9/25.930/3025/25124/124
005
460-3-60
Std
414 5088.345.01
Alt2.113.3201353
High2.613.8201362
Std
575-3-60
518 6326.436.01
Alt2.110.3151142
High2.610.7151050
208/230-1-60
Std
187 25428.8147.01
Alt6.644.0/44.060/6042/42184/184
Std
208/230-3-60
Alt5.226.6/26.635/3526/26148/148
187 25416.3114.01
High7.528.9/28.935/3529/29174/174
006
460-3-60
Std
414 5087.464.01
Alt2.612.7151281
High3.413.5201394
Std
575-3-60
Alt3.010.5151066
518 6326.262.01
High3.412.6151176
Std
187 25423.6146.01
High7.532.5/32.540/4032/32205/205
Std
414 50810.673.01
High3.416.12016103
Std
518 6328.558.41
High3.412.9201482
007
208/230-3-60
460-3-60
575-3-60
LEGEND
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM— Indoor (Evaporator) Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor (Condenser) Fan Motor
RLA — Rated Load Amps
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker. Canadian
units may be fuse or circuit breaker.
2.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
of voltage imbalance.
Use the following formula to determine the percent
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
OFM
(ea)
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/41.4
1
/40.8
1
/40.8
1
/41.4
1
/40.6
1
/40.6
IFM
FLA
3.5
3.5
COMBUSTION
FAN MOTOR
FLA
.6
POWER
SUPPLY
24.5/24.530/3023/23106/106
17.7/17.725/2517/1785/85
DISCONNECT
SIZE*
.6
1.3
7.615748/48
.3
1.3
6.315735
.3
3.5
3.5
.6
34.0/34.040/4032/32129/129
24.2/24.230/3023/23101/101
.6
1.8
13.0201351
.3
1.8
10.1151041
.3
5.9
5.9
.6
43.3/43.360/6042/42161/161
27.3/27.335/3529/29128/128
.6
3.1
13.2201372
.3
3.1
10.9151158
.3
5.2
2.6
2.6
.6
.3
.3
30.2/30.235/3529/29180/180
15.4201590
12.3151372
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
452 + 464 + 455
1371
=
3
= 457
3
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
7
457
= 1.53%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT:
than 2%, contact your local electric utility company immediately.
If the supply voltage phase imbalance is more
11
Step 8 — Make Outdoor-Air Adjustments and
Install Outdoor-Air Hood
MANUAL OUTDOOR-AIR DAMPER — The outdoor-air
hood and screen are attached to the base pan at the bottom of
the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws.
See Fig. 13.
3. Separate hood and screen from basepan by removing the
4 screws securing them. Save all screws.
4. Replace outdoor air opening panel.
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
5. Place hood on front of outdoor air opening panel. See
Fig. 14 for hood details. Secure top of hood with the
4 screws removed in Step 3. See Fig. 15.
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. See Fig. 14 and 15. Secure
hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper bl ade by
adjusting the manual outdoor-air adjustment screws on
the front of the damper blade. See Fig. 13. Slide blade
vertically until it is in the appropriate position determined
by Fig. 16. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws. See
Fig. 15.
Fig. 13 — Damper Panel with Manual Outdoor-Air
Damper Installed
Fig. 15 — Outdoor-Air Damper with
Hood Attached
Fig. 14 — Outdoor-Air Hood Details
Fig. 16 — Position Setting
12
OPTIONAL DURABLADE ECONOMIZER — The option-
ECONOMIZER
CONTROL
BOARD
BAROMETRIC
RELIEF
DAMPER
ECONOMIZER
PLUG
ECONOMIZER
MOTOR
SHIPPING
SCREW
Fig. 18 — Outdoor-Air Hood Details
Fig. 19 — Horizontal Durablade
Economizer Installation
Fig. 17 — Typical Access Panel Locations
al economizer hood assembly is packaged and shipped in the filter section. Dampe r blades an d cont rol boa rds are ins talled at th e
factory and the ec onomizer is shipped in the vertical di scharge
position.
NOTE: Horizontal discharge block-off plate is shipped with
the air hood package. If unit is to be used for vertical discharge
application, discard this plate.
NOTE: Be sure to engage Durablade economizer flange under
tabs in return-air opening of the unit base.
Assembly:
1. Determine if ventilation air is re quired in building. If so,
determine the minimum amount to be supplied by ea ch
unit and record quantity of ventilation air needed for use
in Step 6.
2. Remove filter access panel by raising panel and swinging
panel outward. Panel is now disengaged from track and
can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 17. Remove optional economizer
and outdoor-air damper hood package from filter section.
3. Assemble outdoor-air hood top and side plates as shown
in Fig. 18. Install seal strips on hood top and sides. Put
aside screen retainer and screws for later assembly.
not attach hood to unit at this time.
4. To convert to horizontal discharge application:
a. Rotate economizer 90 degrees until the econo-
mizer motor faces the condenser section (see
Fig. 19).
b. Re move screws and t ape fr om da mper t hen r otate
the barometric relief damper hinge 90 degrees.
Barometric relief damper should open vertically to
operate properly.
c. Install horizontal discharge block-off plate over
the opening on the access panel. (Block-off plate
MUST be installed before installing hood assembly.) See Fig. 20. Remove 12-pin blue and yellow
wire jumper plug and store.
5. Insert economizer plug into economizer harness. Remove
tape from barometric relief damper. See Fig. 21. Remove
shipping screw (see Fig. 19).
6. If ventilation air is not required, proceed to Step 7. If ventilation air is required, determine the minimum position
setting for required airflow. See Fig. 22. Adjust minimum
position setting by adjusting the screws on the position
setting bracket. Slide bracket until the top screw is in the
position determined by Fig. 22. Tighten screws.
7. Remove tape from outdoor-air thermostat (OAT). Fasten
OAT to inside of hood using screws and speed c lips provided. See Fig. 23. Make sure OAT terminals are positioned up.
8. Replace outdoor-air opening panel using screws from
Step 2. Replace filter a ccess panel. Ensure the filter ac cess panel slides along the tracks and is securely engaged.
9. Fasten hood top and side plate assembly (Fig. 18) to
outdoor-air opening panel with screws provided.
10. Place knob supplied with economizer on OAT. See
Fig. 23. Set OAT for 3° F below indoor room thermostat
setting. If accessory enthalpy control (EC) is used in
place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 23.
11. Connect OAT per Fig. 24.
12. Slide outdoor-air inlet screens into screen track on hood
side plate. While holding screen in place, fasten screen retainer to hood using screws provided.
NOTE: Refer to Fig. 25 for economizer barometric relief
damper characteristics.
Do
13
BLOCK-OFF PLATE
Fig. 20 — Horizontal Discharge Block-Off Plate
U-SHAPED
HOLE
(NOT
SHOWN)
ECONOMIZER
CONTROL
BOARD
ECONOMIZER
PLUG
WIRING
HARNESS
BAROMETRIC
RELIEF DAMPER
SHIPPING
SCREW
ECONOMIZER
MOTOR
POSITION SETTING
BRACKET
TOP
SCREW
Fig. 21 — Durablade Economizer Installed in Unit
ENTHALPY
CONTROL
HOOD
TOP
OUTSIDE AIR
SCREEN
OPEN
P
P1
T
Y
10
50
OUTDOOR TEMP
55
60
65
70
.
7
°
5
F
80
85
OAT
(TERMINALS ARE UP)
UNIT
RE
B
V
.
POSITION
MINIMUM
1
3
T
5
2
T1
4
CONT
CONT
OR UNPOWERED ST
R
%
1
H
U
U
M
9
I
D
I
S
8
90
A
H
8
70
ACT RA
CTS SHO
60
1
A
30
DAMPER
OPEN
.
V
E
R
CLOSED
97
3
8
T
CW
2
A
D
4
V
–SETPOINTS
TINGS: 1.5A
C
A
W
C
N IN H
B
2
A
A
3 m
TE
IGH ENTHALPY
A
RUN, 3.5A IN
M
–CCW
IN. A
1
DAMPER
T 1
1 VDC
2
7
6
-3
B
C
TR
D
S
S
O
ENTHALPY CONTROL
TR
2
4
V
A
C
TR1
Example:
Given — Negative Pressure. . . . . . . . . . . . . . . . . . . . . . . 0.2 in. wg
OPTIONAL ECONOMI$ER — See Fig. 26 for EconoMi$er
component locations.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. Remove
the indoor coil access panel and discard. See Fig. 27.
If installing an optional Power Exhaust Assembly, refer to
EconoMi$er Power Exhaust Installation Instructions
the
Controller should be mounted in vertical position as
shown in Fig. 26.
2. Assemble the hood assembly as follows:
Remove the EconoMi$er hood from its packaging.
Remove shipping brackets holding hood package to
EconoMi$er. Locate the outdoor-air opening panel. See
Fig. 28. Remove hood assembly shipping brackets located on the back (sloped) side of the EconoMi$er assembly.
These brackets are used to retain the hood assembly during shipping only .
3. Install the
1
/8 x 3/4-in. seal strip on the exhaust air hood
side panels and the bottom bracket. Assemble the exhaust
air hood to the outdoor-air opening panel as shown in
Fig. 28, using the screws provided.
assembly to unit at this time.
4. Instal l the
top and side panels. Assemble the outdoor-air hood to the
outdoor-air opening panel as shown in Fig. 29, using the
screws provided.
at this time.
1
/8 x 3/4-in. seal strip on the outdoor-air hood
Do not attach hood assembly to the unit
500600
700
Do not attach hood
800
.
15
5. Slide the outdoor-air inlet screens into the screen track on
WIRING
HARNESS
OUTDOOR
AIR
BLOCK-OFF
PLATE
Fig. 32 — EconoMi$er Installed
Fig. 31 — Rear EconoMi$er Flange Installation
Fig. 30 — Completed Hood Assembly
the hood side panels. While holding the screens in pl ace,
fasten the screen retainer to the hood using the screws
provided. Repeat the process for the barometric exhaust
air screen.
Do not attach completed (Fig. 30) hood as-
sembly to unit a t this ti me.
6. Slide the EconoMi$er assembly into the rooftop unit. See
Fig. 31 and 32.
NOTE: Be sure to engage rear EconoMi$er flange under tabs in
return-air opening of the unit base. See Fig. 31.
7. Install the outdoor-air block-off plate, then secure the
EconoMi$er with the screws provided. See Fig. 32.
8. Remove and discard the 12-pin jumper plug from the unit
wiring harness located in the upper left corner and insert
the EconoMi$er plug into the unit wiring harness. Refer
to wiring diagrams Fig. 33 and 34. Also refer to Fig. 35 if
installing an accessory power exhaust.
9. Install the complete hood assembly on the unit and secure
using the screws provided.
10. Remove the indoor fan motor access panel. See Fig. 36.
11. Mount the supply-air temperature sensor to the lower
left portion of the indoor blower housing with the
two (2) screws provided (see Fig. 37). Connect the vi olet
and pink wires to the corresponding connections on the
supply-air temperature sensor. Replace the indoor fan
motor access panel.
UNIT FILTER
RACK
UNIT BASE
ECONOMI$ER CLIP
HVAC UNIT
ECONOMI$ER
ECONOMI$ER REAR
FLANGE
OUTDOOR AIR
OPENING
PANEL
ASSEMBLED
EXHAUST HOOD
Fig. 29 — Outdoor-Air Hood Assembly
SEAL STRIP
SEAL STRIP
OUTDOOR AIR
HOOD SIDES
OUTDOOR AIR
HOOD TOP
SCREEN
RETAINER
OUTDOOR AIR
INLET
SCREENS
16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.