Carrier 40WAW009, 40WAW012, 40WAW015, 40WAW018, 40WAW024 Installation And Maintenance Instructions Manual

40WAW007-024
High Wall Mount Indoor Unit for
Mini Variable Refrigerant Flow (VRF) Systems
Installation and Maintenance Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS ..................... 1,2
GENERAL ...................................... 2-4
INSTALLATION ................................. 4-9
PROTECTING UNITS FROM DAMAGE
PREPARING JOBSITE FOR UNIT INSTALLATION
IDENTIFYING AND PREPARING UNITS
GENERAL
CONDENSATE PIPING
REFRIGERANT PIPING
WIRELESS REMOTE CONTROLLER
WIRED REMOTE CONTROLLER
(PROGRAMMABLE)
WIRED REMOTE CONTROLLER
(NON-PROGRAMMABLE)
CENTRAL CONTROLLER
START-UP ....................................... 10
Pre-Start Check ................................. 10
System Operation Check ....................... 10
MAINTENANCE ................................. 10
TROUBLESHOOTING ......................... 10-12
Replacement Parts ............................. 12
WARN1NG signifies hazards that could result in personal inju- ry or death. CAUTION is used to identify unsafe practices, which would result in minor personal injury or product and property damage.
Recognize safety information. This is the safety-alert symbol (z_)- When this symbol is displayed on the unit and in instructions or manuals, be alert to the potential for personal injury.
Electrical shock can cause personal injury and death. Shut off all power to this equipment during installation. There may be more than one disconnect switch. Tag all discon- nect locations to alert others not to restore power until work is completed.
When installing the equipment in a small space, provide adequate measures to avoid refrigerant concentration exceeding safety limits due to refrigerant leak. In case of refrigerant leak during installation, ventilate the space ilmnediately. Failure to follow this procedure may lead to
personal injury.
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service, main- tenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. The qualified installer or agency must use factory-authorized kits or accessories when modifying this product.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use quenching cloth for brazing op- erations. Have fire extinguisher available. Read these instruc- tions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building
codes and the current editions of the National Electrical Code (NEC) ANSI!NFPA (American National Standards Institute/
National Fire Protection Association) 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA (Ca- nadian Standards Association) C22.1.
Understand the signal words -- DANGER. WARN1NG, and CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53400008-01 Printed in U.S.A. Form 40WAW-1SI Pg 1 6-15 Replaces: New
DO NOT USE TORCH to remove any component. System contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog- gles and proceed as follows:
a. Shut off electrical power to unit. b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig- erant in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch any oil that may come out of the lines and as a gage for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal injury or death.
DO NOT re-use compressor oil or any oil that has been exposed to the atmosphere. Dispose of oil per local codes and regulations. DO NOT leave refrigerant system open to air any longer than the actual time required to service the equipment. Seal circuits being serviced and charge with dry nitrogen to prevent oil contamination when timely repairs cannot be completed. Failure to follow these proce- dures may result in damage to equipment. For information about replacement oil type and viscosity, see the Mini VRF
Outdoor Unit installation instructions.
Table I -- 40WAW Physical Data
UNIT 40WAW POWER SUPPLY (V-Ph-Hz) COOLING CAPACITY (Btuh)
HEATING CAPACITY (Btuh) INDOOR FAN MOTOR
Type Input (W)
INDOOR COIL
Number of Rows
Fin Spacing (fins/in.) Fin Type
Tube Diameter, OD (in.) Tube Type
Number of Circuits
INDOOR AIRFLOW (cfm)
Low
Medium High
INDOOR NOISE LEVEL (dBA)
Low
Medium High
UNIT DIMENSIONS (in.)
Width Height
Depth
PACKING DIMENSIONS (in.)
Width Height
Depth
NET/GROSS WEIGHT (Ib) REFRIGERANT TYPE
EXPANSION DEVICE DESIGN PRESSURE, H/L (psig) REFRIGERANT PIPING (in.)
Liquid Side, OD
Suction Side, OD
CONNECTING WIRING
Power Wiring
Signal Wiring
DRAINAGE WATER PIPE DIAMETER, OD (in.)
LEGEND
EXV -- Electronic Expansion Valve NEC -- National Electrical Code
GENERAL
The 40WAW high wall mount unit provides an efficient way to heat or cool a space and an attractive appearance. The equipment is initially protected under the manufacturer's stan- dard warranty; however, the warranty is provided under the condition that the steps outlined in this manual for initial in- spection, proper installation, regular periodic maintenance, and everyday operation of the unit be followed in detail. This man- ual should be fully reviewed in advance before initial installa- tion, start-up and any maintenance. Contact your local sales representative or the factory with any questions BEFORE pro- ceeding.
Table 1lists physical data for each unit size. See Fig. 1 for model number nomenclature. Figures 2and 3 show unit dimen-
sions.
007 I 009 I o12 I o15 I o18 I 024
208/230-1-60
7,500 J. 9,500 12,000 15,000 19,000 24,000 8,500 | 10,900 13,600 17,000 21,000 27,000
AC Motor
35 I 55 I 100
2
16 ] 19
Aluminum with Hydrophilic Coating
9/32
Copper Tube with Inner Groove
3 ] 6
253 282.5 370.8 444 400
282.5 306 444 506 518 309 347 506 544 700
29 34 41
32 38 42 35 40 45
36 42 1/4 49 1/4
11 1/2 121/2 123/4
9 9 9 5/8
40 1/4 46 1/2 53
15 3/8 16 3/8 17 12 1/2 12 1/2 13 1/4
30/37 35/44 44/55
R-410A
EXV (Integrated with the Evaporator)
650/250
1/4 3/8
1/2 %
Sized per NEC and Local Codes Based on Nameplate Electrical Data
3-Core Shielded Wire
3/4
Equipment Type
40 -- indoor Unit
Product Type
WA-- Mini VRF
Model Type W -- High Wail Mount
LEGEND
VRF -- Variable Refrigerant Flow
Fig. 1 -- Model Number Nomenclature
4O
WA W
i Voltage (V-Ph-Hz)
3 -- 208/230-1-60
Blank
Capacity (Btuh)
007-- 7,500 009-- 9,500 012 -- 12,000
015 -- 15,000 018 -- 19,000
024 -- 24,000
C
40WAW UNIT SIZE
007-012 015,018
A
36
42 1/4
NOTE: All dimensions shown in inches,
D A
DIMENSION
B C
11 1/2 9 12 1/2 9
D
28 1/4 35 1/8
Fig. 2- 40WAWO07-018 Dimensions
"7
03
,-,
3-1/2
9-5/8
NOTE: All dimensions shown in inches.
r------q
44-1/2 49-1/4
Fig. 3 -- 40WAW024 Dimensions
" d
I-I
i
oJ
I
INSTALLATION
Step 1 -- Unpack and Inspect Units -- Units are
packaged for shipment to avoid damage during nonnal transit and handling. It is the receiving party's responsibility to inspect the equipment upon arrival. Any obvious damage to the carton and/or its contents should be reported on the bill of lading and a claim should be filed with the transportation company and the factory. Unit should always be stored in a dry place, and in the proper orientation as marked on the carton.
To avoid equipment damage, do not lift unit by the drain
pipe or refrigerant piping. Unit should be lifted using the
mounting brackets.
After determining the condition of the carton exterior, care- fully remove each unit from the carton and inspect for hidden damage. Check to make sure that items such as thermostats, controller etc. are accounted for whether packaged separately or shipped at a later date. Any hidden damage should be re- corded, a claim should be filed with the transportation compa- ny, and the factory should be notified. In the event a claim for shipping damage is filed, the unit, shipping carton, and all packing must be retained for physical inspection by the trans- portation company. All units should be stored in the factory shipping carton with internal packaging in place until installa-
tion. PROTECTING UNITS FROM DAMAGE -- Do not apply
force or pressure to the coil, piping, or drain stub-outs during handling. All units should be handled by the chassis or as close as possible to the unit mounting point locations.
The unit must always be properly supported. Temporary supports used during installation or service must be adequate to hold the unit securely. To maintain warranty, protect units against hostile enviromnents (such as rain, snow or extreme temperature), theft, vandalism, and debris on jobsite. Equip-
ment covered in this manual is not suitable for outdoor installa- tions. Do not allow foreign material to fall into drain pan. Pre-
vent dust and debris from being deposited on motor, fan wheels and coils. Failure to do so may have serious adverse effects on unit operation and in the case of motor and blower assembly, may result in ilrunediate or premature failure. Failure of any
unit caused by deposits of foreign material on the motor or blower wheels will not be covered by the manufacturer's war- ranty. Some units and/or job conditions may require some form of temporary covering during construction.
PREPARING JOBSITE FOR UNIT INSTALLATION -- To save time and to reduce the possibility of costly errors, set
up a complete sample installation in a typical room at jobsite. Check all critical dfinensions such as pipe, wire, and duct con- nections requirements. Refer to job drawings and product dimension drawings as required. Instruct all trades in their parts of the installation. Units must be installed in compliance with all applicable local code requirements.
IDENTIFYING AND PREPARING UNITS -- Be sure power requirements match available power source. Refer to
unit nameplate and wiring diagram. In addition:
Check all tags on unit to determine if shipping screws are
to be removed. Remove screws as directed. Rotate the fan wheel by hand to ensure that the fan is
unrestricted and can rotate freely. Check for shipping damage and fan obstructions. Adjust blower motor as required.
Step 2 -- Position the Unit
Units must not be installed where they may be exposed to
potentially explosive or flmmnable atmosphere. If this
instruction is not followed exactly, a fire or explosion may result, causing property damage, injury, or loss of life.
Select the unit position with the following points in mind:
The unit should be installed on wall studs that are strong enough to support the total weight of the unit, refrigerant piping, and condensate.
The unit should be mounted 8 ft or more from the floor and if possible, centrally located on the wall from both
ends.
Proper clearance should be provided on the side and top as shown in Fig. 4.
t 6 in. MIN.
5in (
5 in.
MIN.
Fig. 4 -- Required Clearances
The unit should not be positioned directly above any
obstruction.
The unit must be installed square and level.
The condensate drain should have sufficient downward slope in the condensate flow direction.
Step 3 E Mount the Unit
When determining the unit mounting location, make sure that there are no water, plumbing, or electrical lines run- ning through the wall. Failure to follow this instruction may result in property damage.
1. Detach the mounting plate from the unit.
2. Place the mounting plate on the wall where the unit will be installed and mark the mounting holes. See Fig. 5.
Be sure the mounting hole marks are positioned over the wall studs.
3. Mark the condensate and refrigerant piping route. If nec- essary, cut hole in wall to route the piping.
4. Secure the mounting plate with screws that can support the weight of the unit. For nominal weight of the unit, see
Table 1.
5.
Make sure the mounting plate is leveled and flush with the wall.
6.
Secure the unit in position by lifting the unit over the mounting plate. Make sure the hook on the mounting
plate aligns with the slot on the back of the unit. To ensure proper fit, slide the unit sideways. If the unit is locked in
the correct position, it should not move.
Step 4 E Connect Piping
GENERAL
1. For condensate and refrigerant piping, lift the unit from bottom, making sure the unit is still attached to the mounting plate at the top. See Fig. 6.
2. Introduce temporary cushioning material to maintain the space needed to connect the piping and to avoid damage to unit and wall. See Fig. 6.
CUSHIONING
HOOK
MATERIAL
Fig. 6 -- Piping Connection
28
UNIT SIZES 007-012 PLATE
28-3/4 _,
311-3/8 MOUNTING
UNIT SIZES 015-018
28-1/4
_ 3_ TING
UNIT SIZE 024
NOTE: All dimensions in inches,
Fig. 5 -- Mounting Plate
I [
!
3. When the piping connections are completed, remove the cushioning material and make sure the unit is flush with
the wall.
CONDENSATE PIPING- The unit is supplied with a
3/4-in. OD drain connection to connect copper or PVC drain
piping. When installing condensate piping, follow these recom-
MOUNTING
co
mendations:
Condensate drain should slope downward in the direc- tion of condensate flow.
DO NOT install any U bends or dump the condensate line in a sump filled with water. See Fig. 7.
PLATE
Fig. 7 -- Condensate Piping, Poor Installation
When multiple units are connected to a colmnon conden- sate drain, ensure that the drain is large enough to accom-
PLATE
modate the volume of condensate from all units. It is also recolmnended to have an air vent in the condensate pip-
ing to prevent any air locks.
Condensate piping must not be installed where it may be exposed to freezing temperatures.
Condensate piping can be routed in one of the four direc- tions shown in Fig. 8.
LEFT BACK PIPING
LEFT PIPING
RIGHT BACK PIPING RIGHT PIPING
Fig. 8 -- Condensate Pipe Routes
REFRIGERANT PIPING
When connecting from an indoor unit to an outdoor unit, the isolation valve at the outdoor unit should be in closed
position throughout the refrigerant piping process. Failure
to follow this procedure may result in equipment damage.
When connecting from an indoor unit to an outdoor unit,
follow these procedures:
Check maximum height drop and length of refrigerant piping between the indoor and outdoor unit. If the differ- ence between them is more than 33 ft, consider mounting
the outdoor unit above indoor unit.
Refrigerant piping connection between indoor and out- door units should be performed once the units are secured at their respective installation locations.
The refrigeration piping starts at the indoor unit and ends at the outdoor unit.
The number of bends in the refrigeration piping must be fewer than 15.
The refrigerant piping should be dry and free of dust and other impurities.
The bending angle of the refrigerant pipe should not exceed 90 degrees and the bending radius should be as large as possible to prevent any breakage in piping.
Use proper cutting and flaring tools to avoid leakage.
Before insulating the suction and liquid refrigeration pipes, perform pressure and leak tests. For details, see the outdoor unit installation manual. Insulating both suc- tion and liquid refrigerant pipes is recmmnended.
Vacuuming and charging of the system should be carried out as described in the outdoor unit installation manual.
Step 5 -- Complete Electrical Connections
Installation of wiring must conform with local building codes and with National Electric Code ANSI!NFPA 70, latest edi-
tions. Units must be electrically grounded in conformance with the code. In Canada, wiring must comply with CSA C22.1, Electrical Code.
All units must be wired strictly in accordance with the wir- ing diagram furnished with the unit. Any wiring different from the wiring diagram could result in personal injury and
property damage.
Any original factory wiring that requires replacement must be replaced with wiring material having a temperature rat- ing of at least 105 C.
Ensure supply voltage to the unit, as indicated on the serial plate, is not more than 10% over the rated voltage or 10% under the rated voltage.
Failure to follow these recolnmendations may result in
equipment damage.
This equipment in its standard form is designed for an elec- trical supply of 208/230-1-60. Any damage to or failure of units caused by incorrect wiring or voltage is not covered by warranty.
Electric wiring must be sized to carry the full load amp draw of the motor, starter, and any other controls that are used
with the unit. See Table 2 for electrical data.
Table 2 -- 40WAW Electrical Data
UNIT
40WAW007 40WAW009 40WAW012 40WAW015 40WAW018 40WAW024
LEGEND
MCA -- Minimum Circuit Amps MOPD -- Maximum Overcurrent
After the pipe work is complete, the electrical supply can be connected by routing the cable through the appropriate casing
holes or knockouts and connecting the supply and ground cables to the unit's power terminal.
Be sure the power wiring and control wiring do not cross, as this might cause disturbance on the controls side. See Fig. 9
and 10 for wiring diagrams.
Protective Device
POWER SUPPLY
MCA MOPD
02 15 02 15
02 15 0,3 15 0,3 15 0,6 15
C JS
Electrical shock can cause personal injury and death. Dis- connect power supply before making wiring connections. There may be more than one disconnect switch. Tag all dis- connect locations to alert others not to restore power until work is completed.
II _ GROUND
" I--] I D| / I x T_ ,w,....
ANION C CS DM EEV FM GM HEAT T1 T2 T2B TR XP1-7 XS1-7 XT1-2
I
ON7
....... ]
0N24 aa
I_EAIN _IEAILa
RED CNI
(WHI TE}
(WHITE) i
MAIN CONTROL
I I
I
........ J
INDOOR POWER
LEGEND
-- Anion Generator
-- Fan Capacitor
-- Water Level Switch
-- Pump Motor
-- Electronic Expansion Valve
-- Indoor Fan
-- Swing Motor
-- Auxiliary Heater
-- Inlet Air Temperature
-- Coil Temperature
-- Evap. Outlet Temperature in Cooling Mode
-- Transformer
-- Plug
-- Jack
-- Terminal Block Optional Component or Field Wiring
CNIO (WHITE)
,j_o4[
BOARD IJ_°_l[
0N17 I
(wHI[E)
ON16 F
oN oN oN (R_L
SWl SW2 J1J2 SW5
(WHITE} 0N8
CN19
[}......................t__,_ozo_,_,L:
XS1 XP1 IWEEKL Y TIMER II
?Z_L°_°.°w__w_°k___w_,,
CONNECT TO " CONNECT TO
W!RE.ECONTROLLE.R: OUTO00_UNIT
Fig. 9- 40WAWO07-018 Typical Wiring Diagram
REMOTE ON/OFF i
V_ ....................................
]x_ (_
0. _
POWER_S
SW6 END1 2
ON10 (WHITE)
1
xP P7
xs_ Xxs7yxs6 3
IT2" T21T1=
_1_"_1I_"_I- I _--_,R_-,
ON'OFF I [ =CONT=R=OL LE,=RI
(YELL0W) _=
(WHI T E)[_--]
"-'_'_ XS XP1r ..............
"WEEKLYTIMER ',
2_.?.c°".L%_.%
AL C CS DM EEV -- FM GM HEAT -- T1 T2 T2B -- TR
XP1-7 --
XS1-7 -- XT1-2 --
,.... -,MAIN
m m
'FD-I'
m
0N24 1
;(w"=,2_)J
L_ (RED)
TR RED ==--==-1(BLUE)
-- -- = __.l
............... i
(YELLn' " HEAT N HEAT L I
: ?? :
m ¥/_
I k :0( -)J _
INDOOR POWER
LEGEND
Alarm
Fan Capacitor
Water Level Switch
Pump Motor Electronic Expansion Valve
Indoor Fan
Swing Motor Auxiliary Heater
Inlet Air Temperature
Coil Temperature
Evap. Outlet Temperature in Cooling Mode
Transformer
Plug
Jack Terminal Block
Optional Component or Field Wiring
CONTROL BOARD
) SWl SW2 SW5 dld2
,
(R ED)_o_'=1
(BLUE)
(WHITE) E
WIRED CONTROLLER',OUTDOOR UN IT
II_ CONNECT TO
XT2
' CONNECT TO
Fig. 10- 40WAW024 Typical Wiring Diagram
Step 6 -- Position and Connect Controller
Controllers are ordered separately.
Wired controllers should be installed in a position that
maintains good temperature control:
Position the thermostat approximately 48 in. above floor level.
Do not position thermostat where it can be directly affected by the unit's discharge airstream.
Avoid external walls and drafts from window and doors.
Avoid positioning near shelves and curtains as these restrict air movement.
Avoid heat sources such as direct sunlight, heaters, dim- mer switches, and other electrical devices.
WIRELESS REMOTE CONTROLLER -- Before installa- tion, operate the remote controller to determine the appropriate
location for reception range. Avoid direct sunlight exposure or heating sources. Use proper mounting screws and controller bracket to mount the controller on the wall (see Fig. 11). For setup instructions, refer to the controller installation manual.
MOUNTING
ca [Z] cs
SCREWS__ __
WIRED REMOTE CONTROLLER (NON-PROGRAM- MABLE) -- To connect wired remote controller (thermostat)
to the indoor unit, use 5-core shielded cable and 5-pin connec- tor from unit display panel (see Fig. 13). For setup instructions,
refer to the controller installation manual.
INDOOR UNIT ELECTRIC CONTROL BOX
N
INDOOR UNIT DISPLAY PANEL
5-CORE CABLE
'_" 5-CORE SHIELDED CABLE
5-CORE CABLE
WIRED CONTROLLER
Fig. 13 -- Wired Remote Controller
(Non-Programmable) Wiring
CENTRAL CONTROLLER-- The central controller is connected to the indoor unit through outdoor unit with 3-core
shielded cable (see Fig. 14). For setup instructions, refer to the controller installation manual.
REMOTE CONTROLLER
REMOTE
CONTROLLER
HOLDER
Fig. 11 -- Wireless Remote Controller
WIRED REMOTE CONTROLLER (PROGRAMMA- BLE) -- To connect a wired remote controller (thermostat) to
the indoor unit, use 4-core shielded cable and 4-pin connector from electrical box of indoor unit (see Fig. 12). For setup in- structions, refer to the controller installation manual.
INDOOR UNIT
ELECTRICAL BOX-_
I LL_ CABLE
7
Fig. 12 -- Wired Remote Controller
(Programmable) Wiring
o o
TO INDOOR UNIT i i I L_ 24 VAC
X2KE _ _ FORCED L EMERGENCY
DAISY cHAi2oT USED_ sOwNITCH sS;IOT%H
Fig. 14 -- Central Controller Wiring
START-UP
Pre-Start Check -- Once installation is complete, make
the following pre-start checks:
1. All indoor and outdoor units are properly installed.
2. All piping and insulation is complete.
3. All electrical connections (both power and control) are properly terminated.
4. All condensate drams are installed correctly.
5. The power supply is of the right voltage and frequency.
6. The units are properly grounded in accordance with cur-
rent electrical codes.
7. Suction and liquid line service valves are in open posi-
tion.
System Operation Check -- Once the installation
and pre-start checks are completed, follow these steps:
1. Using remote controller, select cooling or heating mode to check the operation of the system.
2. While the system is m operation, check the following on indoor umt:
a.
Switches or buttons on the remote controller are easy to push.
b.
Indicator light is showing normal operation and no er-
ror is indicated.
c. Swing mode of air louvers is working (if applicable to
unit).
d. Dram pump operation is normal (if applicable). e. No abnormal vibration or noise is noticed.
3.
While the system is m operation, check the following on outdoor unit:
a. No abnormal vibration or noise is noticed. b. Condenser fan is in operation.
c. Indicator light is showing normal operation and no er-
ror is indicated.
NOTE: If the unit is turned off or restarted, there is a time delay of 3 minutes for the compressor to start from the time the
power is restored.
MAINTENANCE
When servicing or repairing this unit, use only factory- approved service replacement parts. Refer to the rating
plate on the unit for complete unit model number, serial
number and company address. Any substitution of parts or controls not approved by the factory will be at the owner's risk and may result in equipment damage.
To avoid equipment damage, do not attempt to reuse any mechanical or electrical controllers that have been wet.
Replace defective controller.
EVERY 3 MONTHS:
Check the air filter condition. Clean or replace if neces- sary.
EVERY 6 MONTHS -- Follow 3-month maintenance sched- ule. In addition:
Clean condensate tray with suitable cleaning agent.
Clean the grille and panel.
EVERY 12 MONTHS -- Follow 6-month maintenance schedule. In addition:
Be sure all electrical connections are secure.
Check condensate pump operation.
Check the heating and cooling action to confirm proper operation.
TROUBLESHOOTING
Figure 15 shows shows the LED display panels for
40WAW007-018 and 40WAW024 units. See Table 3 for a smmnary of display indicators. Table 4 lists problems, possible
causes, and possible solutions.
OPERATION TIMER
TIMER
Fig. 15 -- 40WAW LED Display Panel
40WAWO07-O 18
OPERATION
DEE/FAN
40WAW024
10
ERROR CODE MODE/STATUS
Operation Light ON Operation Light OFF Operation Light Flashing Slow*
[NO ERROR]
E0 E1
E2 E3 E4
E7 Ed
EE
FE
*Flashing Slow = Flashing once per second. tFlashing Fast = Flashing twice per second.
ERROR DISPLAY
Defrost Light Flashing Fast (Heating/
E0
Cooling Mode Conflict Error) (40WAW024 only)
Timer LightFlashing Fast
E1
(Communication Error)
E2, E3,
Operation Light Flashing Fast
E4
(Sensor Error)
E7
(EEPROM Error) (40WAW024 only)
Alarm Light Flashing Slow (Outdoor
Ed
Unit Error)
(40WAW024 only)
Alarm Light Flashing Fast (Water
EE
Level Error)
(40WAW024 only)
Operation and Timer Lights Flashing
FE
Fast Together
(Address Error)
Timer Light ON Timer Light OFF
Defrost / Fan Light ON (40WAW024 only) Defrost / Fan Light OFF (40WAW024 only)
Defrost / Fan Light Flashing Fastt
40WAW024 only)
Timer Light Flashing Fast
Operation Light Flashing Fast
Defrost / Fan Light Flashing Slow
40WAW024 only) Alarm Light Flashing Slow (40WAW024 only) Outdoor Unit Error Alarm Light Flashing Fast (40WAW024 only) Water Level Error
Operation and Timer Lights Flashing Fast Indoor Unit Turned ON But Does Not Have An Address
Table 3 -- LED Display Indicators
LED DISPLAY
Starting Shutdown
Standby
Timing ON Timing OFF
System Defrost ON System Defrost OFF
Heating / Cooling Mode Conflict Error Communication Error Between Indoor and Outdoor Unit
Check Indoor Ambient Temperature Sensor (T1) Check Evaporator Temperature Sensor (T2) Check Evaporator Outlet Temperature Sensor (T2B)
EEPROM Error (Data Storage)
Table 4 -- Troubleshooting
POSSIBLE CAUSES
System is in cooling or fan only mode and heating signal is received from a unit on the system,
System is in heating mode and cooling sig- nal is received from a unit on the system,
Signal wires are short-circuited or disconnected,
Signal wire order is incorrect, Signal wires crossing over high voltage
_ower wires.
Signal wire close to electromagnetic source.
Signal wire length exceeds 360 ft.
PC board fault. Loose connection at port on PC board.
Sensor is short-circuited.
PC board fault.
Chip or PC board fault.Defrost Light Flashing Slow
Outdoor unit fault. Refer to outdoor unit troubleshooting guide.
Loose connection or disconnected at port
on PC board. Water level float is stuck.
Trap slope is too steep.
Drain pipe is too long. Drain pump faulty.
Indoor unit without address.
All units should be in cooling mode for system to stay in cooling mode,
All units should be in heating mode.
Check or reconnect signal wire.
Correct signal wire order. Separate and distance the signal wire from high
voltage power wires.
Distance signal wires from electromagnetic
source.
Reduce the signal wire length. Replace PC board.
Tighten the connection at port on PC board.
Using multi-meter, measure resistance of the sen-
sor. If the resistance is < 100 ohms, change the sensor.
Replace PC board. Replace PC board.
Tighten the connection or reconnect at port on PC
board.
Inspect the float. Adjust the trap slope. Adjust the length of drain pipe.
Replace the drain pump.
Run automatic addressing option at the outdoor
unit.
Use remote wireless or wired controller to re- address indoor unit.
POSSIBLE SOLUTIONS
]!
Replacement Parts E Quote the unit model number
and unit serial number when ordering replacement parts or contacting the factory about the unit. This information can be found on the serial plate attached to the unit. See Fig. 16.
MODEL 4OWAWOOg---3 USE ONLY REFRIGERANT- R410A SERIAL 2115V40002
FAN MOTOR VOLTS PH HZ FL._ HP WOUT Carder Corporation
._" WALL MOUNTED UNIT CONDENSING UNIT ISREQUIREDTO COMPLETETHE ¢_!'_. f_lgJu_ _o _ 1t50 15 7310 West Morris Street
iNSTALLATIONSUITABLEFOR iNDOOR _I
&l
Indianapo{is, IN 46231 USA
MADEINCHINA 340802-202REV,B
Fig. 16 -- Unit Serial Plate (Example)
© Carrier Corporation 2015
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-534OO008-01 Printed in U.S.A. Form 40WAW-ISI Pg 12 6-15 Replaces: New
Loading...