Carrier 40RM, 40RMQ, 40RMS User Manual

Packaged Air-Handling Units
Installation, Start-Up and
Service Instructions
40RM
40RMQ
40RMS
50/60 Hz
CONTENTS
Page
SAFETY CONSIDERATIONS ................. 1
PRE-INSTALLATION ........................ 1
Moving and Storage ........................ 1
Rigging .................................... 1
INSTALLATION ........................... 1-23
General .................................... 1
Accessories ................................ 1
Unit Positioning ............................ 11
Unit Isolation .............................. 12
Refrigerant and Chilled Water
Piping Access ............................. 12
Refrigerant Piping .......................... 12
Chilled Water Piping ....................... 17
Condensate Drain .......................... 18
Fan Motors and Drives ..................... 18
Power Supply and Wiring ................... 19
Connecting Ductwork ...................... 22
Return-Air Filters .......................... 22
START-UP ................................. 23
SERVICE ................................. 23-39
Panels ..................................... 23
Fan Motor Lubrication ...................... 23
Fan Shaft Bearings ......................... 23
Centering Fan Wheel ....................... 24
Fan Shaft Position Adjustment .............. 24
Individual Fan Wheel Adjustment ........... 24
Fan Belts .................................. 24
Fan Rotation ............................... 24
Fan Pulley Alignment ....................... 25
Pulley and Drive Adjustment ................ 25
Condensate Drains ......................... 25
Return-Air Filters .......................... 25
Chilled Water Coil Freeze Protection ........ 25
Coil Removal .............................. 25
Cleaning Cooling Coil ...................... 25
Cleaning Insulation ........................ 25
Replacing Filters ........................... 39
START-UP CHECKLIST ................ CL-1,CL-2
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment can be hazardous due to system pressures, electrical components and equipment location (elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start up, and service this equipment.
Untrained personnel can perform basic maintenance func­tions such as cleaning coils, and cleaning and replacing
filters. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky
equipment.
Be sure all power to equipment is shut off before per­forming maintenance or service. More than one discon­nect may be present.
PRE-INSTALLATION
Moving and Storage —
storage site, use a fork truck. Do not stack units more than 2 high during storage. If unit is to be stored for more than 2 weeks before installation, choose a level, dry storage site free from vibration. Do not remove plastic wraporskidfrom unit until final installation.
To transfer unit from truck to
Rigging — All 40RM Series units can be rigged by us-
ing the shipping skid. Units are shipped fully assembled. Do not remove shipping skids or protective covering until unit is ready for final placement; damage to bottom panels can result. Use slings and spreader bars as applicable to lift unit.
INSTALLATION
General —
service clearanceandairflow.Forunits equipped withan econo­mizer, refer to the accessory installation instructions for ad­ditional clearance requirements. Be sure floor, wall, or ceil­ing can support unit weight (Tables 1A-1F). See Fig. 1A-1C for dimensions.
Allow 21⁄2ft at front and side of unit for
Uncrating — Move unit as near as possible to final lo-
cation before removing shipping skid.
Remove metal banding, top skid, and plastic wrap. Ex­amine unit for shipping damage. If shipping damage is evident, file claim with transportation agency. Remove base skid just prior to actual installation.
Check nameplate information against available power supply and model number description in Fig. 2.
Accessories — Refer to instructions shipped with each
accessory for specific information.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 Tab 3c 2e
PC 111 Catalog No. 534-053 Printed in U.S.A. Form 40RM-9SI Pg 1 11-95 Replaces: 40RM-1SI
Table 1A — 40RM Physical Data, English
UNIT 40RM 007 008 012 014 016 024 028 034
2250­3750
1...11⁄
8
2 2 2 2
1
2
8
10 121⁄
3000­5000
2...11⁄
8
1...11⁄
2
1...11⁄
2
3750-
6250
2...11⁄
2
15 20 25 30
4500­7500
8
2...11⁄
1
⁄4ODM/1 IDF
4...16 x 20 x 2
4...16 x 24 x 2
8
2...5⁄
1...21⁄
1...11⁄
6,000-
10,000
2...11⁄
8
2 2
1...2
1...2
7,500-
12,500
8
2...13⁄
4...20 x 24 x 2
4...20 x 25 x 2
9,000-
15,000
8
2...13⁄
NOMINAL CAPACITY (Tons) 67 OPERATING WEIGHT (lb)
Base Unit with TXV 381 385 405 670 685 690 1020 1030 Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18 Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8,000 10,000 12,000
Airflow Range (cfm) Nominal Motor Hp (Standard Motor)
208/230-1-60 1.3 2.4 208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0 575-3-60 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0 230-3-50, 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725 208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745 575-3-60 1725 1725 1725 1725 1725 1745 1755 1755 230-3-50, 400-3-50 1425 1425 1425 1425 1425 1425 1425 1425
REFRIGERANT R-22
Operating charge (lb) (approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435 Face Area (sq ft) 6.67 8.33 10.0 13.25 17.67 19.88 24.86 29.83 No. of Splits 112222 2 2 No. of Circuits per Split 12 15 9 9 12 13 15 18 Split Type...Percentage Face...50/50 Rows...Fins/in. 3...15 3...15 3...17 3...15 3...15 3...17 3...15 3...15
STEAM COIL
Max Working Pressure (psig at 400 F) 175 Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0 Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150 Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0 Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5 Water Volume
(gal) 8.3 13.9 14.3
3
(ft
) 1.1 1.85 1.90
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1 DX Coil — Liquid Refrigerant (ODF) 1...5⁄ Steam Coil, In (MPT) 1...21⁄ Steam Coil, Out (MPT) 1...11⁄ Hot Water Coil, In (MPT) 1...11⁄ Hot Water Coil, Out (MPT) 1...11⁄ Condensate (PVC) 1...1
1800­3000
3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0
1
8
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 Access Location Either Side
LEGEND TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.
8
2
Table 1B — 40RMQ Physical Data, English
UNIT 40RMQ 008 012 016 NOMINAL CAPACITY (Tons) 7 OPERATING WEIGHT (lb)
Base Unit with TXV 385 427 713 Plenum 97 97 140
FANS
Qty...Diam. (in.) 1...15 1...15 2...15 Nominal Airflow (cfm) 3000 4000 6000 Airflow Range (cfm) 2250-3750 3000-5000 4500-7500 Nominal Motor Hp (Standard Motor)
208/230-1-60 2.4 208/230-3-60 and 460-3-60 2.4 2.4 3.7 575-3-60 2.0 2.0 3.0 230-3-50, 400-3-50 2.4 2.9 2.9
Motor Speed (rpm)
208/230-1-60 1725 208/230-3-60 and 460-3-60 1725 1725 1725 575-3-60 1725 1725 1725 230-3-50, 400-3-50 1425 1425 1425
REFRIGERANT R-22
Operating charge (lb) (approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435 Face Area (sq ft) 8.33 10.0 17.67 No. of Splits 12 2 No. of Circuits per Split 15 9 16 Split Type...Percentage Face...50/50 Rows...Fins/in. 3...15 4...15 4...15
STEAM COIL
Max Working Pressure (psig at 400 F) 175 Total Face Area (sq ft) 6.67 6.67 13.33 Rows...Fins/in. 1...9 1...9 1...10
HOT WATER COIL
Max Working Pressure (psig) 150 Total Face Area (sq ft) 6.67 6.67 13.33 Rows...Fins/in. 2...8.5 2...8.5 2...8.5 Water Volume
(gal) 8.3 13.9
3
(ft
) 1.1 1.85
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1 DX Coil — Liquid Refrigerant (ODF) 1...5⁄ Steam Coil, In (MPT) 1...21⁄ Steam Coil, Out (MPT) 1...11⁄ Hot Water Coil, In (MPT) 1...11⁄ Hot Water Coil, Out (MPT) 1...1 Condensate (PVC) 1...11⁄4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 Access Location Either Side
1
2
10 15
3.0 2.0/2.0 3.0/3.0
1
8
8
2 2 2
1
2
2...11⁄
2...5⁄
1...11⁄
1...11⁄
8
8
1...21⁄
1...11⁄
2 2
2...11⁄
2...5⁄
2 2
1...2
1...2
4...16 x 20 x 2
4...16 x 24 x 2
8
8
LEGEND TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.
3
Table 1C — 40RMS Physical Data, English
UNIT 40RMS 008 010 012 014 016 024 028 034 NOMINAL CAPACITY (Tons) 7 OPERATING WEIGHT (lb)
Base Unit 390 391 391 661 677 683 1035 1042 Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18 Nominal Airflow (cfm) 3000 3400 4000 5000 6000 8000 10,000 12,000 Airflow Range (cfm) 2250-3750 2250-4250 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000 Nominal Motor Hp
(Standard Motor)
208/230-1-60 2.4 2.4 208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0 575-3-60 2.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0 230-3-50 and 400-3-50 2.4 2.4 2.9 2.9 2.9 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725 208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745 575-3-60 1725 1725 1725 1725 1725 1745 1755 1755 230-3-50 and 400-3-50 1425 1425 1425 1425 1425 1425 1425 1425
CHILLED WATER COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure
(psig)
Face Area (sq ft) — Upper 8.3 9.0 4.9 8.3 8.3 11.0 12.4 15.5 Face Area (sq ft) — Lower 4.9 5.5 8.3 8.3 12.4 12.4 Rows...Fins/in. 3...15
STEAM COIL
Max Working Pressure
(psig at 400 F)
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0 Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure
(in. wg)
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0 Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5 Water Volume
(gal) 8.3 13.9 14.3
3
(ft
) 1.1 1.85 1.90
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In 1...1 Chilled Water — Out 1...1 Steam Coil, In (MPT) 1...21⁄ Steam Coil, Out (MPT) 1...11⁄ Hot Water Coil, In (MPT) 1...11⁄ Hot Water Coil, Out (MPT) 1...11⁄ Condensate (PVC) 1...11⁄4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 Access Location Either Side
1
2
81⁄
2
10 121⁄
2
15 20 25 30
435
175
150
3
⁄8ODF 1...13⁄8ODF 2...13⁄8ODF 2...13⁄8ODM 2...13⁄8ODM 2...13⁄8ODM 2...21⁄8ODM 2...21⁄8ODM
3
⁄8ODF 1...13⁄8ODF 2...13⁄8ODF 2...13⁄8ODM 2...13⁄8ODM 2...13⁄8ODM 2...21⁄8ODM 2...21⁄8ODM
2 2 2 2
1...11⁄
1...11⁄
2 2
4...16 x 20 x 2
4...16 x 24 x 2
1...21⁄
1...11⁄
2 2
1...2
1...2
4...20 x 24 x 2
4...20 x 25 x 2
4
Table 1D — 40RM Physical Data, SI
UNIT 40RM 007 008 012 014 016 024 028 034 NOMINAL CAPACITY (kW) 21 26 35 43 52 70 87 105 OPERATING WEIGHT (kg)
Base Unit with TXV 173 175 184 304 311 313 463 467 Plenum 44 44 44 63 63 63 82 82
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457 Nominal Airflow (L/s) 1133 1604 1888 2360 2831 3775 4719 5663 Airflow Range (L/s) 850-1416 1203-2006 1416-2360 1770-2949 2124-3539 2831-4719 3539-5899 4247-7079 Nominal Motor kW (Standard Motor)
208/230-1-60 0.97 1.79 —————— 208/230-3-60 and 460-3-60 1.79 1.79 1.79 2.16 2.76 3.73 5.60 7.46 575-3-60 0.75 1.49 1.49 2.24 2.24 3.73 5.60 7.46 230-3-50, 400-3-50 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Motor Speed (r/s)
208/230-1-60 28.8 28.8 —————— 208/230-3-60 and 460-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.1 29.1 575-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.3 29.3 230-3-50, 400-3-50 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg) (approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag) 2999 Face Area (sq m) 0.62 0.77 0.93 0.93 1.64 1.85 2.30 2.77 No. of Splits 11222222 No. of Circuits per Split 12 15 9 9 12 13 15 18 Split Type...Percentage Face...50/50 Rows...Fins/m 3...591 3...591 3...670 3...591 3...591 3...670 3...591 3...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C) 1207 Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39 Rows...Fins/m 1...355 1...355 1...355 1...394 1...394 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034 Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39 Rows...Fins/m 2...335 2...335 2...335 2...335 2...335 2...335 2...493 2...493 Water Volume
(L) 31.4 52.6 54.1
3
(m
) 0.031 0.052 0.054
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1 DX Coil — Liquid Refrigerant (ODF) 1...5⁄ Steam Coil, In (MPT) 1...21⁄ Steam Coil, Out (MPT) 1...11⁄ Hot Water Coil, In (MPT) 1...11⁄ Hot Water Coil, Out (MPT) 1...1 Condensate (PVC) 1...11⁄4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size 4...406 x 610 x 51 Access Location Either Side
LEGEND TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.
1.36 1.36 0.68/0.68 0.90/0.90 1.13/1.13 1.59/1.59 2.04/2.04 2.27/2.27
1
8
1...11⁄
8
2...11⁄
8
2...11⁄
8
2...11⁄
8
2...11⁄
8
2...13⁄
8
2...13⁄
8
2 2 2
1
2
1...11⁄
1...11⁄
2 2
4...406 x 508 x 51
4...406 x 610 x 51
2...5⁄
1...21⁄
1...11⁄
8
2 2
1...2
1...2
4...508 x 610 x 51
4...508 x 635 x 51
8
5
Table 1E — 40RMQ Physical Data, SI
UNIT 40RMQ 008 012 016 NOMINAL CAPACITY (kW) 26 35 52 OPERATING WEIGHT (kg)
Base Unit with TXV 175 194 323 Plenum 44 44 63
FANS
Qty...Diam. (mm) 1...381 1...381 2...381 Nominal Airflow (L/s) 1604 1888 2831 Airflow Range (L/s) 1203-2006 1416-2360 2124-3539 Nominal Motor kW (Standard Motor)
208/230-1-60 1.79 208/230-3-60 and 460-3-60 1.79 1.79 2.76 575-3-60 1.49 1.49 2.24 230-3-50, 400-3-50 1.79 2.16 2.16
Motor Speed (r/s)
208/230-1-60 28.8 208/230-3-60 and 460-3-60 28.8 28.8 28.8 575-3-60 28.8 28.8 28.8 230-3-50, 400-3-50 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg) (approx per circuit)*
DIRECT-EXPANSION COIL
Max Working Pressure (kPag) 2999 Face Area (sq m) 0.77 0.93 1.64 No. of Splits 12 2 No. of Circuits per Split 15 9 16 Split Type...Percentage Face...50/50 Rows...Fins/m 3...591 4...591 4...591
STEAM COIL
Max Working Pressure (kPag at 204.4 C) 1207 Total Face Area (sq m) 0.62 0.62 1.24 Rows...Fins/m 1...355 1...355 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034 Total Face Area (sq m) 0.62 0.62 1.24 Rows...Fins/m 2...335 2...335 2...335 Water Volume
(L) 31.4 52.6
3
(m
) 0.031 0.052
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil — Suction (ODF) 1...1 DX Coil — Liquid Refrigerant (ODF) 1...5⁄ Steam Coil, In (MPT) 1...21⁄ Steam Coil, Out (MPT) 1...11⁄ Hot Water Coil, In (MPT) 1...11⁄ Hot Water Coil, Out (MPT) 1...1 Condensate (Male PVC) 1...11⁄4ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Quantity...Size 4...406 x 610 x 51 Access Location Either Side
LEGEND TXV — Thermostatic Expansion Valve *Units are shipped without refrigerant charge.
1.36 0.91/0.91 1.36/1.36
1
8
8
2 2 2
1
2
2...11⁄
2...5⁄
1...11⁄
1...11⁄
8
8
2 2
1...21⁄
1...11⁄
2...11⁄
8
2...5⁄
1...2
1...2
8 2 2
4...406 x 508 x 51
4...406 x 610 x 51
6
Table 1F — 40RMS Physical Data, SI
UNIT 40RMS 008 010 012 014 016 024 028 034 NOMINAL CAPACITY (kW) 26 29 35 43 52 70 87 105 OPERATING WEIGHT (kg)
Base Unit 177 177 177 300 307 310 469 473 Plenum 44 44 44 63 63 63 82 82
FANS
Qty...Diam. (mm) 1...381 1...381 1...381 2...381 2...381 2...381 2...457 2...457 Nominal Airflow (L/s) 1416 1605 1888 2360 2831 3775 4719 5663
Airflow Range (L/s) Nominal Motor kW
(Standard Motor)
208/230-1-60 1.79 1.79 ————— 208/230-3-60, 460-3-60 1.79 1.79 1.79 1.79 2.76 3.73 5.60 7.46 575-3-60 1.49 1.49 1.49 1.49 2.24 3.73 5.60 7.46 230-3-50, 400-3-50 1.79 1.79 2.16 2.16 2.16 3.73 5.60 7.46
Motor Speed (r/s)
208/230-1-60 28.8 28.8 ————— 208/230-3-60, 460-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.1 29.1 575-3-60 28.8 28.8 28.8 28.8 28.8 29.1 29.3 29.3 230-3-50, 400-3-50 23.8 23.8 23.8 23.8 23.8 23.8 23.8 23.8
CHILLED WATER COIL
Max Working Pressure
(kPag)
Face Area (sq m) — Upper 0.77 0.84 0.91 0.77 0.77 1.02 1.15 1.44 Face Area (sq m) — Lower 0.51 0.77 0.77 1.15 1.15 Rows...Fins/m 3...591 3...591 3...591 3...591 3...591 3...591 3...591 3...591
STEAM COIL
Max Working Pressure
(kPag at 204.4 C)
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39 Rows...Fins/m 1...355 1...355 1...355 1...355 1...394 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure
(kPag)
Total Face Area (sq m) 0.62 0.62 0.62 1.24 1.24 1.24 1.39 1.39 Rows...Fins/m 2...335 2...335 2...335 2...335 2...335 2...335 2...493 2...493 Water Volume
(L) 31.4 52.6 54.1
3
(m
) 0.031 0.052 0.054
PIPING CONNECTIONS,
Quantity...Size (in.)
Chilled Water — In 1...1 Chilled Water — Out 1...13⁄8ODF 1...13⁄8ODF 2...13⁄8ODF 2...13⁄8ODM 2...13⁄8ODM 2...13⁄8ODM 2...21⁄8ODM 2...21⁄8ODM Steam Coil, In (MPT) 1...21⁄ Steam Coil, Out (MPT) 1...11⁄ Hot Water Coil, In (MPT) 1...11⁄ Hot Water Coil, Out (MPT) 1...11⁄ Condensate (PVC) 1...1
FILTERS Throwaway — Factory Supplied
Quantity...Size (mm) 4...406 x 610 x 51 Access Location Either Side
1062­1770
1204­2006
1416­2360
1770­2949
2124­3539
2831­4719
3539­5899
4247­7079
2999
1207
1034
3
⁄8ODF 1...13⁄8ODF 2...13⁄8ODF 2...13⁄8ODM 2...13⁄8ODM 2...13⁄8ODM 2...21⁄8ODM 2...21⁄8ODM
2 2 2 2
1...11⁄
1...11⁄
2 2
1
⁄4ODM/1 IDF
4...406 x 508 x 51
4...406 x 610 x 51
1...21⁄
1...11⁄
2 2
1...2
1...2
4...508 x 610 x 51
4...508 x 635 x 51
7
TXV — Thermostatic Expansion Valve NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm )
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field installed.
6. 40RMS units may require alternate or ad­ditionalfield-fabricated piping access holes.
Fig. 1A — Dimensions — Sizes 007-012
8
UNIT
40RM007 381 (173) 40RM008 385 (175) 40RM012 405 (184) 40RMQ008 385 (175) 40RMQ012 427 (194) 40RMS008 390 (177) 40RMS010 391 (177) 40RMS012 391 (177)
UNIT WEIGHT
lb (kg)
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field installed.
6. 40RMQ016 and 40RMS units may re­quirealternate or additionalfield-fabricated piping access holes.
Fig. 1B — Dimensions — Sizes 014-024
9
UNIT
40RM014 670 (304) 40RM016 685 (311) 40RM024 690 (313) 40RMQ016 713 (323) 40RMS014 661 (300) 40RMS016 677 (307) 40RMS024 683 (310)
UNIT WEIGHT
lb (kg)
Fig. 1C — Dimensions — Sizes 028,034
10
UNIT
40RM028 1020 (463) 40RM034 1030 (467) 40RMS028 1035 (469) 40RMS034 1042 (473)
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 3 in. (76 mm)
• Front: 2 ft, 6 in. (762 mm)
• Right Side: 2 ft, 6 in. (762 mm)
• Left Side: 2 ft, 6 in. (762 mm)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange isfactory supplied andfield installed.
6. 40RMS units may require alternate or additional field-fabricated piping ac­cess holes.
UNIT WEIGHT
lb (kg)
*YC and WD option codes for all 034 size units and 008, 010 units with 208/230-1-60
power designate standard motor and high-static drive.
NOTE: See the following table for the sizes available for each unit.
UNIT 007 008 010 012 014 016 024 028 034
40RM XX XXXXXX 40RMQ XXX 40RMS XXXXXXXX
Fig. 2 — Model Number Nomenclature
Unit Positioning — The unit can be mounted on the
floor for vertical application with return air entering the face of the unit and supply air discharging vertically through the top of the unit. The unit can also be applied in a horizontal arrangement with return air entering horizontally and the sup­ply air discharging horizontally. When applying the unit in a horizontal arrangement, ensure the condensate drain pan is located at the bottom center of the unit for adequate con­densate disposal. See Fig. 3 for condensate connections for each unit position.
Typical positioning and alternate return air locations are shown in Fig. 3.Alternate return air locations can be used by moving the unit panel from the alternate return air location to the standard return air location.
IMPORTANT: Do NOT attempt to install unit with return air entering top panel of unit. Condensate will not drain from unit.
LEGEND
Accessory Line Alternate Air Intake and Discharge
Air Intake and Discharge
Fig.3—Typical Unit Positioning
11
Unit Isolation — Where extremely quiet operation is
essential, install isolators between floor and base of unit, or between ceiling and top section of unit.
Be sure that unit is level and adequately supported. Use channels at front and sides of unit for reference points when leveling.
Refrigerant and Chilled Water PipingAccess —
The 40RM Series units come with standard knockouts for refrigerant and chilled water piping. These knockouts are lo­cated on both sides of the unit for installation flexibility. The standard knockouts provide sufficientaccess to the unit’s coils for all 40RM and some 40RMQ units, however, for40RMQ016 and 40RMS units, additional holes must be field-fabricated to accommodate the piping. See Fig. 4 for the positions and dimensions of the additional access holes required for these units, including hole diameters and drilling dimensions. Rec­ommended access hole use is also listed for all units. Note that Fig. 4 shows the access holes on the control-box side of the unit; this is the side of the unit with the coil headers, so it is used most often for piping access.
Refrigerant Piping — See Tables 1A, 1B, 1D, 1E for
refrigerant pipe connection sizes. For ease in brazing, it is recommended that all internal solder joints be made before unit is placed in final position.
The 40RM and 40RMQ direct-expansion units have internal factory-installed thermostatic expansion valves (TXVs), distributors, and nozzles for use with R-22. See Table 2 for part numbers. Knockouts are provided in the unit corner posts for 40RM and 40RMQ008 and 012 refrigerant piping. The 40RMQ016 unit requires additional field-fabricated piping access holes. See Fig. 4, which also lists recommended knock­outs and access holes to use for each 40RM and 40RMQ unit size. Recommended fittings are listed in Table 3.
The sensor bulb capillary tubes must be routed from the TXVs inside the unit through one of the piping access holes. Clamp the TXV sensor bulb on a vertical portion of the suc­tion line, outside the unit. See Fig. 5.
UNIT
40RM007,008 40RMQ008
40RM012-034 40RMQ012
40RMS008-012 4, 5 1 40RMS014-024 4, 5, 6, 7 1 40RMQ016 3*, 5, 6, 7 1 40RMS028,034 5, 6, 7, 8 2
*Must be enlarged from 1 NOTE: Access hole knockouts 1-4 are factory-supplied.
USE HOLE
NUMBERS
1,3———— —
1,2,3,4———— —
1
⁄8in. to 13⁄4inches.
FIELD-FABRICATED HOLE DIAMETERS,
No. 5 No. 6 No. 7 No. 8 A B C D
3
⁄4(44.5) 6.25 (158.8)
3
⁄4(44.5) 13⁄4(44.5) 13⁄4(44.5) 3.0 (76.2) 6.0 (152.4) 10.5 (266.7)
1
⁄8(28.6) 11⁄8(28.6) 13⁄4(44.5) 3.25 (82.6) 6.125 (155.6) 10.38 (263.7)
1
⁄2(63.5) 21⁄2(63.5) 21⁄2(63.5) 21⁄2(63.5) 6.0 (152.4) 9.625 (244.5) 13.38 (339.9) 17.0 (431.8)
in. (mm)
Fig. 4 — Refrigerant and Chilled Water Piping Access Holes
12
FIELD-FABRICATED HOLE POSITION
DIMENSIONS, in. (mm)
IMPORTANT: Never attach the sensor to the suction manifold. Do NOT mount the sensor on a trapped por­tion of the suction line.
40RM Series evaporator coils have a face-split design. En­sure that lower circuit of coil is first on/last off when con­nected to the condensing unit and/or system controls. See Fig. 6.
ExternalTXV equalizer connections areprovided and factory­brazed into the coil suction manifolds.
If suction line must be horizontal, clamp bulb to suction line at least 45 degrees above bottom, at approximately the 4 o’clock or 8 o’clock position. See Fig. 7.
NOTE: The 40RMQ units are supplied with factory-installed thermostatic expansion valves and check valve bypasses. No extra piping connections or kits are required to install the 40RMQ with a 38AQS condensing unit in a heat pump system, however, some field supplied components may be required. See the following two sections.
FIRST ON/LAST OFF=B
VERTICAL INSTALLATION
LEGEND TXV — Thermostatic Expansion Valve NOTE: Component location arrangement shown for field installation
of sight glasses,solenoid valves,filter driers,and TXV sensing bulbs. The TXVs and equalizer lines are factory installed.
Fig. 5 — Face-Split Coil Suction and
Liquid Line Piping (Typical)
FIRST ON/LAST OFF=A
HORIZONTAL INSTALLATION
Fig.6—Typical Evaporator Coil Connections
(40RM, 40RMQ)
LEGEND TXV — Thermostatic Expansion Valve NOTE: The 8 o’clock position is shown above.
Fig. 7 — TXV Sensing Bulb Location
13
Table 2 — Factory-Installed Nozzle and Distributor Data
UNIT
40RM007 1...XVE-5 1...1116 12 1...E5 40RM008 1...SVE-8 1...1126 15 1...C6 40RMQ008 1...SVE-8 1...1657 15 1...C6 40RM012 2...XVE-4 2...1115 9 2...E4 40RMQ012 2...XVE-4 2...1655 9 2...E4 40RM014 2...XVE-5 2...1115 9 2...E5 40RM016 2...XVE-8 2...1116 12 2...E6 40RMQ016 2...SVE-8 2...1126 16 2...C6 40RM024 2...XVE-10 2...1116 13 2...E8 40RM028 2...EBSVE-11 2...1126 15 2...C10 40RM034 2...SVE-15 2...1126 18 2...C12
* Feeder tube size is NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.
1
⁄4in. (6.35 mm).
TXV
Qty...Part No.
DISTRIBUTOR
Qty...Part No.
FEEDER TUBES
PER DISTRIBUTOR*
Qty...Size (in.)
38AQS008/40RMQ008 HEATPUMP SYSTEM PIPING — Addition of a liquid solenoid valve (LLSV) is recommended when the piping system length exceeds 75 feet. The LLSV must be a bi-flow type suited for use in heat pump systems. The recommended valve is Sporlan model CB14S2 (5/8-in. ODF, 7/8-in. ODM) available from the Replacement Com­ponents Division as part number EF23JS-214. This solenoid valve requires Sporlan part no. MKC-2 coils that must be purchased locally. Wire the solenoid valve in parallel with the compressor contactor coil.
NOZZLE
Qty...Part No.
The LLSV must be installed at the outdoor unit with the flow arrow pointed toward the outdoor unit (in-flow direction for the heating mode.)
FILTER DRIER REQUIREMENTS FOR 38AQS012/ 40RMQ012 AND 38AQS016/40RMQ016 HEAT PUMP SYSTEMS — The 38AQS012 and 016 units do not in­clude filter driers. Filter driers must be field-supplied and installed in 38AQS012/40RMQ012 and 38AQS016/ 40RMQ016 systems. The filter driers used with these sys­tems must be bi-flow types suited for use in heat pump applications.The Replacement Component Division part num­bers listed in Fig. 8 are recommended and available for field installation.
LEGEND
TXV — Thermostatic Expansion Valve
RECOMMENDED FILTER DRIERS*
(38AQS012,016/40RMQ SYSTEMS)
LIQUID
UNIT
38AQS
012
016
*Available from Carrier Replacement Components Division.
LINE SIZE
PART NO.
(in.)
1
⁄2P504-8084S 2 A
5
⁄8P504-8165S 1 B
1
⁄2P504-8084S 2 A
5
⁄8P504-8085S 2 A
QUANTITY
REQUIRED
REFERENCE
FIGURE
Fig. 8 — Filter Drier Requirements —
38AQS012/40RMQ012 and 38AQS016/40RMQ016
Heat Pump Systems
14