Carrier 38MHRBQ12AA3 User Manual

38MHRB Outdoor Unit Single Zone Ductless System Sizes 09 to 24
Service Manual
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS 1.........................
INTRODUCTION 1...................................
SPECIFICATIONS 3...................................
DIMENSIONS 5.....................................
CLEARANCES 8.....................................
ELECTRICAL DATA 9................................
WIRING 9...........................................
CONNECTION DIAGRAMS 10.........................
WIRING DIAGRAMS 11...............................
REFRIGERATION CYCLE DIAGRAMS 17................
REFRIGERANT LINES 18.............................
SYSTEM EVACUATION AND CHARGING 19.............
ELECTRONIC FUNCTIONS 18.........................
TROUBLESHOOTING 23..............................
OUTDOOR UNIT DIAGNOSTIC GUIDES 24..............
PCB DIAGRAMS 25..................................
DIAGNOSIS AND SOLUTION 27.......................
DISASSEMBLY INSTRUCTIONS 48.....................
APPENDIX 71.......................................

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air−conditioning equipment can be hazardous due to system pressures, electrical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install, start−up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils. All other operations should be performed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
Follow all safety codes. W ear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
Read this manual thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.
!
Recognize safety information. This is the safety−alert symbol When you see this symbol on the un it and in instructions or manuals, be alert to the potential for personal injury. Understand these signal words: DANGER, W ARNI NG, a nd CAUTION.
!
These words are used with the safety−alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying, or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Do not bury more than 36 in. (914 mm) of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. (152 mm) vertical rise to the valve connections on the outdoor units. If more than the recommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refrigerant slugging and could possibly damage the compressor at start−up.
.
WARNING
!
WARNING
EXPLOSION HAZARD
Failure to follow this warning could result in death, serious personal injury, and/or property damage.
Never use air or gases containing oxygen for leak testing or operating refrigerant compressors. Pressurized mixtures of air or gases containing oxygen can lead to an explosion.
CAUTION

INTRODUCTION

This Service Manual provides the necessary information to service, repair, and maintain the outdoor units. Section 2 of this manual has an appendix with data required to perform troubleshooting. Use the Table of Contents to locate a desired topic.

MODEL/SERIAL NUMBER NOMENCLATURES

Table 1—Unit Sizes
SYSTEM TONS BTUh VOLTAGE - PHASE OUTDOOR MODEL
1.00 12,000 115-1 38MHRBC12AA1
Cooling Only
Heat Pump
38 = OUTDOOR UNIT
1.00 12,000 208/230-1 38MHRBC12AA3
1.50 18,000 208/230-1 38MHRBC18AA3
2.00 24,000 208/230-1 38MHRBC24AA3
1.00 12,000 115-1 38MHRBQ12AA1
0.75 9,000 208/230-1 38MHRBQ09AA3
1.00 12,000 208/230-1 38MHRBQ12AA3
1.50 18,000 208/230-1 38MHRBQ18AA3
2.00 24,000 208/230-1 38MHRBQ24AA3
OUTDOOR UNIT
38 MH 3Q
BR09
A
A
VOLTAGE 1 =115-1-60 3 = 208/230-1-60
MH = MODEL
UNIT TYPE R = OUTDOOR UNIT
MAJOR SERIES
SYSTEM TYPE C = COOLING ONLY Q = HEAT PUMP
Week of Manufacture
Year of Manufacture
01 18
V
V = ALL MODELS
MAXIMUM NUMBER OF FAN COIL UNITS THAT CAN BE CONNECTED TO THE OUTDOOR UNIT
A = 1:1
10001
Sequential Serial Number
VARIATIONS A = STANDARD
NOMINAL CAPACITY 09 - 3/4 TON 12 - 1 TON 18 - 1-1/2 TONS 24 - 2 TONS
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
2

SPECIFICATIONS

System
Electrical
Operating
Range
Piping
Refrigerant
Outdoor Coil
Compressor
Outdoor
Size 12 12 18 24
Outdoor Model 38MHRBC12AA1 38MHRBC12AA3 38MHRBC18AA3 38MHRBC24AA3 Voltage, Phase, Cycle V/Ph/Hz 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 MCA A. 13 11 15 18 MOCP - Fuse Rating A. 20 15 20 25 Cooling Outdoor DB
Min - Max Total Piping Length ft (m) 82 (25) 82 (25) 98 (30) 164 (50) Piping Lift Pipe Connection
Size - Liquid Pipe Connection
Size - Suction Type R410A R410A R410A R410A Charge lbs (kg) 1.30 (0.59) 1.17 (0.53) 1.98 (0.90) 2.56 (1.16) Metering Device EEV EEV EEV EEV Face Area Sq. Ft. 4.15 4.15 4.15 4.78 No. Rows 1 1 2 2 Fins per inch 22 22 22 22 Circuits 2 2 4 6 Type Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter Model ASN98D22UFZ ASK89D29UEZD ASN140D21UFZ ATN150D30UFZA Oil Type VG74 VG74 VG74 VG74 Oil Charge Fl. Oz. 13.0 13.0 15.5 23.6 Rated Current RLA 9.5 6.8 9.0 12.0 Unit Width in (mm) 30.31 (770) 30.31 (770) 30.31 (770) 33.27 (845) Unit Height in (mm) 21.85 (555) 21.85 (555) 21.85 (555) 27.64 (702) Unit Depth in (mm) 11.81 (300) 11.81 (300) 11.81 (300) 14.29 (363) Net Weight lbs (kg) 57.8 (26.2) 53.8 (24.4) 65.9 (29.9) 88.6 (40.2) Airflow CFM 1,170 1,230 1,195 1,825 Sound Pressure dB(A) 52.0 53.6 55.3 58.0
*
T able 2—Specifications (Cooling Only)
°F (°C) 0~122 (-17~50) 0~122 (-17~50) 0~122 (-17~50) 0~122 (-17~50)
ft (m) 33 (10) 33 (10) 66 (20) 66 (20)
in (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52)
in (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 5/8 (16)

Compatibility

High Wall

Performance

Indoor Model 40MHHC12---1 40MHHC12---3 40MHHC18---3 40MHHC24---3
Energy Star NO NO NO NO Cooling System Tons 1.0 1.0 1.4 1.8
High Wall
Cooling Rated Capacity Btu/h 12,000 11,500 17,000 22,000 Cooling Cap. Range Min - Max Btu/h 4,800~13,200 4,800~13,000 5,800~18,600 4,900~24,100 SEER 17.3 19.0 19.0 18.5 EER 10.7 11.2 10.3 11.1
T able 3—Compatibility
Indoor Unit 38MHRBC12AA1 38MHRBC12AA3 38MHRBC18AA3 38MHRBC24AA3
40MHHC12---1 40MHHC12---3 40MHHC18---3 40MHHC24---3
Table 4—Performance
3
SPECIFICATIONS (CONT)
System
Electrical
Operating
Range
Piping
Refrigerant
Outdoor Coil
Compressor
Outdoor
Size 12 9 12 18 24 Outdoor Model 38MHRBQ12AA1 38MHRBQ09AA3 38MHRBQ12AA3 38MHRBQ18AA3 38MHRBQ24AA3 Voltage, Phase, Cycle V/Ph/Hz 115-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 MCA A. 13 8 10 15 18 MOCP - Fuse Rating A. 20 15 15 20 25
Cooling Outdoor DB Min - Max °F (°C)
Heating Outdoor DB Min - Max °F (°C)
Total Piping Length ft (m) 82 (25) 82 (25) 82 (25) 98 (30) 164 (50) Piping Lift Pipe Connection Size - Liquid in (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) Pipe Connection Size - Suction in (mm) 1/2 (12.7) 3/8 (9.52) 1/2 (12.7) 1/2 (12.7) 5/8 (16) Ty pe R410A R410A R410A R410A R410A Charge lbs (kg) 2.12 (0.96) 1.76 (0.80) 2.12 (0.96) 2.82 (1.28) 3.97 (1.80) Metering Device EEV EEV EEV EEV EEV Face Area Sq. Ft. 4.1 4.1 4.1 4.7 5.3 No. Rows 1.6 1 1.6 2 2 Fins per inch 18 18 18 21 18 Circuits 2 2 4 4 6 Ty pe Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter Rotary Inverter Model ASN98D22UFZ ASN98D22UFZ ASN98D22UFZ ASN140D21UFZ ATF235D22UMT Oil Type VG74 VG74 VG74 VG74 VG74 Oil Charge Fl. Oz. 13.0 13.0 13.0 15.5 23.6 Rated Current RLA 10.5 5.5 6.8 10.5 12.0 Unit Width in (mm) 30.31 (770) 30.31 (770) 30.31 (770) 31.50 (800) 33.27 (845) Unit Height in (mm) 21.85 (555) 21.85 (555) 21.85 (555) 21.81 (554) 27.64 (702) Unit Depth in (mm) 11.81 (300) 11.81 (300) 11.81 (300) 13.11 (333) 14.29 (363) Net Weight lbs (kg) 69 (31.3) 63 (28.6) 65.5 (29.7) 79.6 (36.1) 114.2 (51.8) Airflow CFM 1,170 1,170 1,170 1,170 1,765 Sound Pressure dB(A) 54.5 57.2 57.4 57.0 60.2
*
Table 5—Specifications (Heat Pump)
0~ 122
(-17~ 50)
0~ 86
(-17~ 30)
ft (m) 33 (10) 33 (10) 33 (10) 66 (20) 66 (20)
0~ 122
(-17~ 50)
0~ 86
(-17~ 30)
0~ 122
(-17~ 50)
0~ 86
(-17~ 30)
0~ 122
(-17~ 50)
0~ 86
(-17~ 30)
0~ 122
(-17~ 50)
0~ 86
(-17~ 30)

Compatibility

Indoor Unit 38MHRBQ12AA1 38MHRBQ09AA3 38MHRBQ12AA3 38MHRBQ18AA3 38MHRBQ24AA3
High Wall

Performance

Indoor Model 40MHHQ12---1 40MHHQ09---3 40MHHQ12---3 40MHHQ18---3 40MHHQ24---3 Energy Star NO NO NO NO NO Cooling System Tons 1.0 0.8 1.0 1.5 2.0 Cooling Rated Capacity Btu/h 12,000 9,000 12,000 18,000 24,000 Cooling Cap. Range Min - Max Btu/h 3,700~ 13,000 3,400~10,500 3,700~ 13,000 5,500~19,000 8,987~26,585 SEER 19.8 18.5 19.8 19.0 17.3 EER 10 11.2 11.2 11.2 9.7
High Wall
Heating Rated Capacity (47° F) Btu/h 12,000 9,800 12,000 18,000 24,800 Heating Rated Capacity (17° F) Btu/h 8,000 7,500 9,230 11,600 18,000 Heating Maximum Capacity (17° F) Btu/h 8,200 7,850 9,500 11,800 18,300 Heating Maximum Capacity (5° F) Btu/h 9,000 6,070 8,880 10,150 16,760 Heating Cap. Range Min - Max Btu/h 3,500~ 13,500 2,800~11,500 3,500~ 13,500 6,200~19,000 8,371~25,350 HSPF 10.6 10.0 9.6 10.6 9.6 COP (47° F) W/W 2.93 3.27 3.22 3.26 3.13 COP (17° F) W/W 2.58 2.58 2.64 2.64 2.49 COP (5° F) W/W 1.60 1.60 1.60 1.50 1.40
T able 6—Compatibility
40MHHQ12---1 40MHHQ09---3 40MHHQ12---3 40MHHQ18---3 40MHHQ24---3
Table 7—Performance
4

DIMENSIONS

System Size Height (H) in. (mm) Width (W) in. (mm) Depth (D) in. (mm) Weight-Net lbs. (kg)
Cooling
Only
Heat
Pump
12K (115V) 21.85(555) 30.31(770) 11.81(300) 57.8(26.2)
12K (208/230V) 21.85(555) 30.31(770) 11.81(300) 53.8(24.4)
18K (208/230V) 21.85 (555) 30.31 (770) 11.81 (300) 65.9 (29.9)
24K (208/230V) 27.64(702) 33.27(845) 14.29(363) 88.6(40.2)
System Size Height (H) in. (mm) Width (W) in. (mm) Depth (D) in. (mm) Weight-Net lbs. (kg)
12K (115V) 21.85(555) 30.31(770) 11.81(300) 69(31.3)
9K (208/230V) 21.85(555) 30.31(770) 11.81(300) 63(28.6)
12K (208/230V) 21.85(555) 30.31(770) 11.81(300) 65.5(29.7)
18K (208/230V) 21.81(554) 31.50(800) 13.11(333) 79.6(36.1)
24K (208/230V) 27.64(702) 33.27(845) 14.29(363) 114.2(51.8)
T able 8—Dimensions
30.66(779) W3
H
21.85(555)
11.81(300) D
0.47(12)
19.17(487) W1
30.31(770) W
0.98(25) B1
D3
D2
11.26(286)
13.07(322)
2.36(60)
3.54(90) B2
2.42(61.5) A2
H1
H2
.24(6)
0
R
3.66(93)
0.47(12) A1
Unit: inch(mm)
Fig. 1 – Sizes 9K and 12K Heat Pump and Size 18K Cooling Only
2.76(70) W
D1
11.73(298)
5
DIMENSIONS − OUTDOOR (CONT)
H
21.81 (554)
0.47 (1 2)
13.11
(333)
D
20.24 (514)
31.50 (800)
B2
4.17 (1 06)
D3
D2
12.80 (325)
H1
2.36 (6 0)
H2
3.37 (8 5.5)
12.24 (311)
R
0
.
7
9
(R
2
0
)
0.87 (2 2)
A1
2.43 (6 1.6)
A2
W
W1
2.43 (6 1.8)
B1
4
2
.
0
R
)
6
R
(
Unit: inch(mm)
2.76 (7 0)
W2
D1
13.39 (340)
Fig. 2 – Size 18K Heat Pump
6
DIMENSIONS − OUTDOOR (CONT)
Fig. 3 – Size 24K
7
Unit: inch (mm)

CLEARANCES

D
A
B
Air-outlet
Fig. 4 – Outdoor Unit Clearance
Table 9—Clearances
UNIT MINIMUM VALUE in. (mm)
A 24 (610)
B 24 (610)
C 24 (610)
D 4 (101)
E 4 (101)
Air-inlet
E
C
NOTE: The outdoor unit must be mounted at least 2in. (50mm) above the maximum anticipated snow depth.
9.8in (25cm) or more for proper airow 24in (61cm) or more is recommended for service
9.8in (25cm) or more for proper airow 24in (61cm) or more is recommended for service
59in (150cm) or more on a multiple parallel unit arrangement
24in (61cm) or more on a single parallel unit arrangement
24in (60cm) or more
118in (300cm) or more
19in (48cm) or more on a multiple parallel
unit arrangement 4in (10cm) or more on a single parallel unit arrangement
Fig. 5 – Clearances for Multiple Units
8

ELECTRICAL DATA

T able 10—Electrical Data (Cooling Only)
Outdoor Unit Size 12K 12K 18K 24K
Cooling Only
Power Supply
Compressor RLA 9.5 6.8 9 12
Outdoor Fan Motor
Heat Pump
Power Supply
Compressor RLA 10.5 5.5 6.8 10.5 12
Outdoor Fan Motor
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Over-Current Protection
RLA - Rated Load Amps
Volts-PH-Hz (115V) (208/230V) (208/230V) (208/230V)
Max – Min*
Oper. Voltage
MCA 13 11 15 18
MOCP 20 15 20 25
FLA 0.6 0.5 0.6 0.6
Rated HP 0.054 0.054 0.054 0.068
Output 40 40 40 50
127-104 253-187 253-187 253-187
Table 11—Electrical Data (Heat Pump)
Outdoor Unit Size 12K 9K 12K 18K 24K
Volts-PH-Hz (115V) (208/230V) (208/230V) (208/230V) (208/230V)
Max – Min*
Oper. Voltage
MCA 13 8 10 15 18
MOCP 20 15 15 20 25
FLA 0.6 0.4 0.4 0.5 0.6
Rated HP 0.054 0.054 0.054 0.054 0.068
Output 40 40 40 40 50
127-104 253-187 253-187 253-187 253-187

WIRING

All wires must be sized per NEC (National Electrical Code) or CEC (Canadian Electrical Code) and local codes. Use Electrical Data table MCA (minimum circuit amps) and MOCP (maximum over current protection) to correctly size the wires and the disconnect fuse or breakers respectively.
Recommended Connection Method for Power and Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3 stranded wire with ground with a 600 volt insulation rating, power/communication wiring from the outdoor unit to indoor unit consists of four (4) wires and provides the power for the indoor unit. Two wires are line voltage AC power, one is communication wiring (S) and the other is a ground wire. Wiring between indoor and outdoor unit is polarity sensitive. The use of BX wire is NOT recommended.
If installed in a high Electromagnetic field (EMF) area and communication issues exists, a 14/2 stranded shielded wire can be used to replace L2/N and (S) between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Wires should be sized based on NEC and local codes.
!
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
SBe sure to comply with local codes while running wire from
the indoor unit to the outdoor unit.
SEvery wire must be connected firmly. Loose wiring may
cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Ensure all wiring is tightly connected.
SNo wire should touch the refrigerant tubing, compressor or
any moving parts.
SDisconnecting means must be provided and shall be located
within sight and readily accessible from the air conditioner.
SConnecting cable with conduit shall be routed through the
hole in the conduit panel.
9

CONNECTION DIAGRAMS

208/230-1-60 FIELD POWER SUPPLY
L1
L2
S
Indoor Signal High Voltage
GND
Main Power Supply
208/230-1-60
L
N
Indoor Unit Power Supply
115-1-60
Indoor Signal High Voltage
115-1-60
CONNECTING CABLE
FIELD POWER SUPPLY
OUTDOOR TO INDOOR
N
GND
S
Indoor Signal High Voltage
L
N Main Power Supply
115-1-60
GND
S
Ground
L Power to Indoor Unit
115-1-60
L1 L2
Indoor Unit Power Supply
Indoor Signal High
208/230-1-60
Voltage
CONNECTING CABLE OUTDOOR TO INDOOR
GND
S
Ground
Power to Indoor Unit
208/230-1-60
115V Indoor Unit 115V Outdoor Unit 230V Indoor Unit 230V Outdoor Unit
Fig. 6 – Connection Diagrams
Notes:
1. Do not use thermostat wire for any connection between indoor and outdoor units.
2. All connections between indoor and outdoor units must be as shown. The connections are sensitive to polarity and will result in a fault code.
L2
L1
10

WIRING DIAGRAMS (COOLING ONLY)

Fig. 7 – Wiring Diagram Size − Cooling Only Size 12K (115V)
11
WIRING DIAGRAMS (COOLING ONLY (CONTINUED))
Fig. 8 – Wiring Diagram Cooling Only Size 12K (230V)
12
WIRING DIAGRAMS (COOLING ONLY (CONTINUED))
Fig. 9 – Wiring Diagram Cooling Only Sizes 18−24K
13

WIRING DIAGRAMS (HEAT PUMP)

Fig. 10 – Wiring Diagram Heat Pump Size 12K (115V)
14
WIRING DIAGRAMS (HEAT PUMP (CONTINUED))
Fig. 11 – Wiring Diagram Heat Pump Sizes 09, 12, 18 (230V)
15
WIRING DIAGRAMS (HEAT PUMP (CONTINUED))
Fig. 12 – Wiring Diagram Heat Pump Size 24 (230V)
16

REFRIGERATION CYCLE DIAGRAMS

INDOOR OUTDOOR
HEAT EXCHANGE (EVAPORATOR)
T2 Evaporator temp. sensor
T1 Room temp. sensor
LIQUID SIDE
2−WAY VALVE
GAS SIDE
3−WAY VALVE
ACCUMULATOR
CHECK VALVE (Heating Model only)
CAPILIARY TUBE
COMPRESSOR
HEAT EXCHANGE (CONDENSER)
4−WAY VALVE
COOLING HEATING
Fig. 13 – Heat Pumps
17

REFRIGERANT LINES

General Refrigerant Line Sizing

1 The outdoor units are shipped with a full charge of R410A
refrigerant. All charges, line sizing, and capacities are based on runs of 25ft. (7.6 m). For runs over 25 ft. (7.6 m), consult the long−line applications section for the proper charge adjustments.
2 The minimum refrigerant line length between the indoor
and outdoor units is 10 ft. (3 m).
3 Refrigerant lines should not be buried in the ground. If it is
necessary to bury the lines, not more than 36 in (914 mm) should be buried. Provide a minimum 6in (152 mm) vertical rise to the service valves to prevent refrigerant migration.
T able 12 lists the maximum lengths allowed.
T able 12—Piping and Refrigerant Information
System Size 12K (115V) 9K (208-230V) 12K (208-230V) 18K (208-230V) 24K (208-230V)
Min. Piping Length ft. (m) 10(3) 10(3) 10(3) 10(3) 10(3)
Piping
Refrigerant
Standard Piping Length
Max. outdoor-indoor height difference (OU higher than IU)
Max. outdoor-indoor height difference (IU higher than OU)
Max. Piping Length with no additional refrigerant charge per System (Standard Piping length)
Total Max. Piping Length per system
Additional refrigerant charge (between Standard – Max piping length)
Suction Pipe (size - connection type)
Liquid Pipe (size - connection type)
Refrigerant Type Type R410A R410A R410A R410A R410A
Cooling Only Models Charge Amount
Heat Pump Models Charge Amount
ft. (m)
ft. (m)
ft. (m)
ft. (m) 25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5)
ft. (m) 82(25) 82(25) 82(25) 98(30) 164(50)
Oz/ft (g/m) 0.161(15) 0.161(15) 0.161(15) 0.161(15) 0.322(30)
In (mm) 1/2(12.7) 3/8(9.52) 1/2(12.7) 1/2(12.7) 5/8(15.9)
In (mm) 1/4(6.35) 1/4(6.35) 1/4(6.35) 1/4(6.35) 3/8(9.52)
Lbs (kg) 1.30(0.59) N/A 1.17 (0.53) 1.98 (0.9) 2.56 (1.16)
Lbs (kg) 2.12(0.96) 1.76(0.8) 2.12(0.96) 2.82 (1.28) 3.97 (1.8)
25(7.5) 25(7.5) 25(7.5) 25(7.5) 25(7.5)
33(10) 33(10) 33(10) 66(20) 66(20)
33(10) 33(10) 33(10) 66(20) 66(20)
4 Both lines must be insulated. Use a minimum of 1/2in.
(12.7 mm) thick insulation. Closed−cell insulation is recommended in all long−line applications.
5 Special consideration should be given to isolating
interconnecting tubing from the building structure. Isolate the the tubing so vibration or noise is not transmitted into the structure.
IMPORTANT: Both refrigerant lines must be insulated separately.
Long Line Applications,:
1 No change in line sizing is required. 2 Add refrigerant per T able 12.
18
SYSTEM EVACUATION AND
t
CHARGING
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation.
Never use the system compressor as a vacuum pump.
Refrigerant tubes and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. Always break a vacuum with dry nitrogen.

System Vacuum and Charge

Using Vacuum Pump
1 Completely tighten all flare nuts and connect manifold gage
charge hose to a charge port of the low side service valve
(see Fig. 14). 2 Connect the charge hose to the vacuum pump. 3 Fully open the low side of manifold gage (see Fig. 15). 4 Start the vacuum pump 5 Evacuate using the triple evacuation method. 6 After evacuation is complete, fully close the low side of
manifold gage and stop the vacuum pump operation. 7 The factory charge contained in the outdoor unit is good
for up to 25 ft. (8 m) of line length. For refrigerant lines
longer than 25 ft. (8 m), add refrigerant as specified in the
ADDITIONAL REFRIGERANT CHARGE table in this
document. 8 Disconnect the charge hose from the charge connection of
the low side service valve. 9 Fully open service valves B and A.
10 Securely tighten the service valves caps.
Outdoor Unit
Service Valve
500 microns
Low side valve
Charge hose
CAUTION
Refrigerant
Low Side
A
High Side
B
Fig. 14 – Service Valve
Manifold Gage
High side valve
Charge hose
Indoor Uni
C
D
Vacuum pump
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water (see Fig. 16).
5000 4500 4000 3500 3000 2500 2000
MICRONS
1500 1000
500
01234567
MINUTES
LEAK IN SYSTEM
V ACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
Fig. 16 – Deep Vacuum Graph
Triple Evacuation Method
The triple evacuation method should be used. Refer to Fig. 17 and proceed as follows:
1 Pump the system down to 1500 microns and allow the
pump to continue operating for an additional 15 minutes. 2 Close the service valves and shut off the vacuum pump. 3 Connect a dry nitrogen cylinder and regulator to the system
and break vacuum until the system reaches 2 psig. 4 Close the service valve and allow the system to stand for
1hr. During this time, the dry nitrogen can diffuse
throughout the system absorbing moisture. 5 Pump the system down to 1000 microns. 6 Break the vacuum with dry nitrogen (2 psig). 7 Pump the system down to 500 microns. 8 Perform the hold test for 30 minutes.
EVACUATE TO 1500 MICRONS
BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 1000 MICRONS
BREAK VACUUM WITH DRY NITROGEN TO 2 PSIG
EVACUATE TO 500 MICRONS MINIMUM (HOLD FOR 30 MINUTES)
CHECK FOR TIGHT, DRY SYSTEM
(IF IT HOLDS DEEP VACUUM)
RELEASE CHARGE INTO SYSTEM BY OPENING VALVES COMPLETELY
Fig. 17 – Triple Evacuation Method
Final Tubing Check IMPORTANT: Check to be certain factory tubing on both
indoor and outdoor unit has not shifted during shipment. Ensure tubes are not rubbing against each other or any sheet metal. Pay close attention to feeder tubes, making sure wire ties on feeder tubes are secure and tight.
Low side valve
Fig. 15 – Manifold
19

Operation Modes and Functions

FAN Mode
1 Outdoor fan and compressor stop 2 Temperature setting function is disabled, and no setting
temperature is displayed.
3 Indoor fan can be set to high/med/low/auto 4 The louver operates the same in the COOLING mode. 5 Auto fan
Fig. 18 – Auto Fan COOLING Mode Compressor Running Rules:
S When T1*Ts < 28.4_F(*2_C), the compressor stops. S When T1*TS > 31.1_F(*0.5_C), the compressor
activates.
S When the AC runs in the mute mode, the compressor
runs with low frequency.
S When the current is more than setting value, the current
protection function activates, and the compressor stops.
Outdoor Fan Running Rules:
The outdoor unit runs at a different fan speed according to T4. For different outdoor units, the fan speeds differ.
Fig. 20 – Auto Fan
Fig. 21 – Compressor Temperature Protection
When the condenser temperature temperature is higher than the setting value, the compressor stops.
Compressor Running Rules
When T1−Ts>−ΔT, the compressor stops, when
<ΔT−1.5the compressor will be on. ΔT is the
T1−T
S
programmed parameter of temperature compensation. When the AC run in mute mode, the compressor runs with low frequency.
When the current is more than setting value, the current protection function is activated and the compressor stops.
Outdoor Fan Running Rules
The outdoor unit runs at different fan speed according to T4. For different outdoor units, the fan speeds are different.
Fig. 19 – Outdoor Fan Running Rules
The auto fan adheres to the following rules.
Fig. 22 – Outdoor Fan Running Rules
20
Auto Fan Action in HEATING Mode
T1
a
b
c
d
e
Fig. 23 – Auto Fan Action in HEATING Mode
DEFROST Mode
The air conditioner enters the DEFROST mode according to the T3 temperature value and the T3 temperature change value range plus the compressor running time.
During the DEFROST mode, the compressor continues to runs, the indoor and outdoor motors stop, and the indoor unit defrost
lamp illuminates and If any one of the following items is satisfied, the defrosting finishes
and the machine reverts to the normal heating mode.
−−−−T3 rises to be higher than TCDE1
−−−−T3 keeps to be higher than TCDE2
−−−−The machine has run for 15 minutes in defrosting mode.
Evaporator Coil Temperature Protection
appears.
_C.
_C for 80 seconds.
T2
TEstop
TEdown
TEH2
Off
Decrease
Hold Resume
Table 13—Auto Mode
ΔT=T1-Ts Running mode
ΔT2_C
-2≤ΔT≤2_C ΔT<-2_C
The indoor fan runs under auto fan in the relevant mode. The louver operates the sam e i n the r elevant mode . I f the machine switches modes between HEATI NG and COOLING, the compressor stops for 15 minutes and then chooses the mode according to T1−Ts. If the setting temperature is modified, the machine chooses the running function again.
DRY mode Indoor fan speed is fixed at breeze and can not be changed.
The louver angle is the same as in the cooling mode.
Low indoor room temperature protection
In the DRYING mode, if the room temperature is lower than 50_F
_C), the compressor stops and does not resume until the room
(10 temperature exceeds 53.6
Evaporator anti*freezing protection, condenser high temperature protection and outdoor unit frequency limit are active and are the same as that in the cooling mode. The outdoor fan operates the same as in cooling mode.
Forced Operation Function
_F (12_C).
Cooling
Fan-only
Heating
S Enter forced operation function: When the machine is
off, press Touch to engage the the Forced Auto Mode. Press Touch again, within 5 seconds, to engage the Forced Cooling Mode. In Forced Auto, forced cooling or any other operation mode, press the touch button to turn off the unit. In the forced operation mode, all general protections and remote control are available.
Operation rules:
S Forced Cooling Mode: The compressor runs at the F2
frequency and the indoor fan runs as a breeze. After running for 30 minutes, the unit enters the auto mode as
75.2_F (24_C) setting temperature.
S Forced Auto Mode: The forced auto mode is the same
as the normal auto mode with a 75.2_F (24_C) setting temperature.
Fig. 24 – Evaporator Coil Temperature Protection
NOTE: The following applies to Fig. 24:
S Off: Compressor stops S Decrease: Decrease the running frequency to the lower level S Hold: Keep the current frequency S Resume: No limitation for frequency
When the evaporator temperature is higher than the setting protection value, the compressor stops.
Auto−Mode
This mode can be chosen with the remote controller and the setting temperature can be changed between 62.6
In the AUTO mode, the machine chooses the COOLING, HEATING or FAN−ONLY mode according to ΔT (ΔT =T1−Ts).
_F(17_C)~86_F(30_C).
AUTO−RESTART Function
The indoor unit is equipped with the AUTO−REST AR T function, which is carried out through an auto−restart module. In the event of a sudden power failure, the module memorizes the setting conditions prior to the power failure. The unit resumes the previous operation setting (not including the SWING function) automatically three (3) minutes after the power returns.
If the memorization condition is the FORCED COOLING mode, the unit will run in the COOLING mode for 30 minutes and turn to the AUTO mode at the 75.2_F(24_C) setting temperature.
If the air conditioner is off before the power turns off and the air conditioner is required to start up, the compressor delays start up for 1 minute before powering on. In other instances, the compressor waits three (3) minutes before restarts.
Refrigerant Leak Detection
With this new technology, the display area displays “EC” when the outdoor unit detects a refrigerant leak. This function is only active in cooling mode. It can better prevent the compressor being damaged by refrigerant leakage or compressor overload.
Open Condition: When the compressor is active, the value of the Coil temperature o f evaporator T2 has no c hange or v ery little ch ange.
46_F (8_C) Heating
When the compressor is running, the indoor fan motor runs without the ANTI−COLD air function. When the compressor is off, the indoor fan motor is off.
21

Point Check Function

Press the remote controller’s LED DISPLAY or LED or MUTE button three times, and then press the AIR DIRECTION or SWING button three times in ten seconds, the buzzer rings for two seconds. The air conditioner enters into the information enquiry status.
Press the LED DISPLAY or AIR DIRECTION button to check the next or front item’s information. When the air conditioner enters the information enquiry status, it displays the code name in 2 seconds (see Table 14).
T able 14—Information Enquiry
ENQUIRY INFORMATION DISPLAYING CODE MEANING
T1 T1 T1 temp.
T2 T2 T2 temp.
T3 T3 T3 temp.
T4 T4 T4 temp.
T2B Tb T2B temp.
TP TP TP temp.
TH TH TH temp.
Targeted Frequency FT Targeted Frequency
Actual Frequency Fr Actual Frequency
Indoor Fan Speed IF Indoor fan speed
Outdoor Fan Speed OF Outdoor fan speed
EXV Opening Angle LA EXV opening angle
Compressor continuous running time CT Compressor continuous running time
Compressor stop causes ST Compressor stop causes
Reserve A0
Reserve A1
Reserve b0
Reserve b1
Reserve b2
Reserve b3
Reserve b4
Reserve b5
Reserve b6
Reserve dL
Reserve Ac
Reserve Uo
Reserve Td
When the air conditioner enters the information enquiry status, it displays the code value for 25 seconds (see Table 15).
ENQUIRY
INFORMATION
T1,T2,T3,T4,
T2B,TP,TH,
Targeted
Frequency,
Actual
Frequency
Indoor fan speed
/Outdoor fan speed
EXV opening angle 0-FF
Compressor
continuous running
time
Compressor stop
causes
Reserve 0-FF
DISPLAY VALUE MEANING REMARK
-1F,-1E,-1d,-1c,
-1b,-1A
-1999 -1999
A0,A1,A9 100,101,109
b0,b1,b9 110,111,119
c0,c1,c9 120,121,129
d0,d1,d9 130,131,139
E0,E1,E9 140,141,149
F0,F1,F9 150,151,159
0 OFF
1,2,3,4
14-FF
0-FF 0-255 minutes
0-99
T able 15—Information Enquiry
-25,-24,-23,-22,-21,-20
Low speed, Medium speed, High
Actual fan speed = Display value
For the detailed meaning, please
speed, Turbo
turns to decimal value and then
multiply 10. The unit is RPM.
Actual EXV opening value =
Display value turns to decimal
value and then multiply 2.
consult with engineer
1. The displaying temperature is the actual value.
2. The temperature is _C no matter what kind of remote controller is used.
3. T1,T2,T3,T4,T2B display range:-25~70, TP display range:-20~130.
4. Frequency display range: 0~159HZ.
5. If the actual value exceeds the range, it displays the maximum value or minimum value.
For some big capacity motors.
For some small capacity motors, the display value is from 14-FF
(hexadecimal), the corresponding fan speed range
is from 200-2550 RPM.
If the actual value exceeds the range, it displays the maximum value or minimum value.
Decimal display
22

TROUBLESHOOTING

Safety

Electricity power is kept in capacitors even if the power supply is shut off. NOTE: Remember to discharge the electricity power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
Fig. 25 – Electrolytic Capacitors
For other models, please connect discharge resistance (approximately 100 electrolytic capacitor on the contrary side of the outdoor PCB.
Ω 40W) or a soldering iron (plug) between the +, terminals of the
Fig. 26 – Discharge Position
NOTE: Fig. 26 is for reference only. The plug on your unit may differ.
23
Loading...
+ 51 hidden pages