Carrier 30HL050, 30HW018-040, 60, 30HK040-060 User Manual

Reciprocating Liquid Chillers
Installation, Start-Up and
Service Instructions
30HK040-060
30HL050,060
30HW018-040
50/60 Hz
CONTENTS
Page
GENERAL ....................................2
SAFETY CONSIDERATIONS .....................2
INSTALLATION ..............................3-25
Location ......................................3
Step 1 — Inspect Shipment .....................3
30HK,HL UNITS
30HW UNITS
Step 3 — Place the Unit
30HK,HL UNITS
30HW UNITS
Step 4 — Check Compressor Mounting and Connections
Step 5 — Make Piping Connections .............13
30HK,HWC,HWS CONDENSER DESCRIPTION
30HL,HWA SYSTEM CONDENSER
30HWB CONDENSER DESCRIPTION
30HK,HWC,HWS CONDENSER(S)
30HWB CONDENSER
30HK,HWB,HWC,HWS UNITS
COOLER DESCRIPTION
COOLER PIPING
Step 6 — Make Electrical Connections
30HK,HL UNITS
30HW UNITS
ALL UNITS
PRE-START-UP
Initial Check .................................25
Check Refrigerant Charge .....................26
LIQUID CHARGING METHOD
Check Oil Charge
TO ADD OIL
• TO REMOVE OIL
START-UP AND OPERATION ..................27-30
Operation Checks ............................27
Operating Limitations .........................27
HIGH COOLER LEAVING CHILLED WATER (FLUID)
TEMPERATURES (LCWT)
LOW COOLER LCWT
MAIN POWER SUPPLY
Check Refrigerant Feed Components
THERMOSTATIC EXPANSION VALVE (TXV)
FILTER DRIER
MOISTURE-LIQUID INDICATOR
LIQUID LINE SERVICE VALVE
DISCHARGE LINE CHECK VALVE
HOT GAS BYPASS VALVE
LIQUID LINE SOLENOID VALVE (30HL ONLY)
PRESSURE RELIEF DEVICES
Compressor and Unit Protective Devices
CIRCUIT BREAKER
..................................3
.............................25-27
........................3
...........19
.............................27
............27
.........28
COMPRESSOR INTERNAL THERMAL PROTECTION
CRANKCASE HEATER
OIL PRESSURE SAFETY SWITCH (OPS)
Check Unit Safeties
CONTROL MODULE
HIGH-PRESSURE SWITCH
LOW-PRESSURE SWITCH
CHILLED FLUID TEMPERATURE CONTROLLER
FREEZE-UP PROTECTION
LOSS-OF-COOLER-FLOW PROTECTION
COMPRESSOR GROUND FAULT SENSOR
UNIT OPERATION
Capacity Control and Operating Sequence .......30
30HK,HL UNITS
30HW UNITS
SERVICE
Compressor Replacement ......................32
Circuit Breaker(s) .............................32
Brazed-Plate Cooler and Condenser
Heat Exchanger Replacement .................32
Brazed-Plate Cooler and Condenser
Heat Exchanger Cleaning .....................32
Shell-and-Tube Condenser Cleaning .............32
Thermistor ...................................33
THERMISTOR REPLACEMENT, 30HK,HL UNITS
THERMISTOR REPLACEMENT, 30HW UNITS
SERVICING COOLER (30HK,HL ONLY)
Tube Plugging ...............................36
RETUBING
Tightening Cooler Head Bolts
GASKET PREPARATION
BOLT TORQUES
TROUBLESHOOTING
Complete Unit Stoppage and Restart ............37
GENERAL POWER FAILURE
UNIT ON-OFF SWITCH IS OPEN
CONTACTS OF ANY AUXILIARY INTERLOCKS ARE
OPEN
CHILLED FLUID PROOF-OF-FLOW SWITCH(ES) OPEN
OPEN LOW-PRESSURE SWITCH
TEMPERATURE CONTROLLER SHUTS UNIT DOWN ON
OUT-OF-RANGE
OPEN HIGH-PRESSURE SWITCH(ES)
OPEN COMPRESSOR INTERNAL THERMAL
PROTECTION
OPEN OIL PRESSURE SWITCH
OPEN CONTACTS ON COMPRESSOR GROUND-
CURRENT SENSOR(S) (Accessory)
OPEN 24-V CONTROL CIRCUIT BREAKER(S)
COOLING LOAD SATISFIED
THERMISTOR FAILURE
START-UP CHECKLIST FOR CHILLER SYSTEMS
..................................32-35
...........................28
...........................30-32
.........36,37
..................36
........................37-39
...................CL-1 to CL-4
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-070 Printed in U.S.A. Form 30H-10SI Pg 1 11-98 Replaces: 30H-8SI
GENERAL
These installation instructions cover the 30HK, HL, HWA, HWB, HWC, and HWS units. The HL and HWA are con­denserless units, and the HK, HWB, HWC, and HWS units are all fluid cooled. In addition, the 30HK and HWC units have a standard mechanically cleanable condenser and the 30HWS unit has a mechanically cleanable condenser spe­cifically designed for sea coast applications.
SAFETY CONSIDERATIONS
Installing, starting up, and servicing this equipment (Fig. 1-3) can be hazardous due to system pressures, elec­trical components, and equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service technicians should install, start up, and service this equipment.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equipment.
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use care in handling, rigging, and setting bulky
equipment.
Be sure all power to equipment is shut off before per­forming maintenance or service. There may be more than one disconnect. Tag all disconnects to alert others not to turn on power until work is completed.
Fig. 2 — 30HWA,B Unit
Fig. 1 — 30HK,HL Unit (30HK Shown)
Fig. 3 — 30HWC,S Unit
2
INSTALLATION
Location—
because of sensitive control mechanisms and electronic devices. Locate unit indoors. See Fig. 4-8 for unit dimen­sional details.
Allow 36 in. (914 mm) in front of the unit for control box access door. Compressor can be removed from either side or the front of the unit. Prior to installation determine which direction compressor will be removed, and leave 3 to 4 ft (914 to 1219 mm) clearance for removal.
On 30HK,HL units leave 7 9 ft (2.7 m) (for 050,060 units) clearance on one side for cooler tube removal. Leave 2 ft (610 mm) clearance on the other side for making fluid connections to cooler and water connections to condenser. See Fig. 4 and 5.
On 30HWA,B units, leave 2 ft (610 mm) on one side for making fluid connections to cooler and water connections to condenser,accessing the thermostatic expansion valve (TXV), and replacing heat exchanger(s) if necessary. See Fig. 6 and 7.
On 30HWC,S units, leave 75 in. (1905 mm) on one side for condenser tube removal and 2 ft (610 mm) on the other side for making fluid connections to cooler and water con­nections to condenser,accessing the TXV, and replacing heat exchanger(s) if necessary. See Fig. 8.
The floor must be strong enough to support the unit op­erating weight (see Tables 1A-2B and Fig. 9 and 10). If nec­essary, add a supporting structure (steel beams or reinforced concrete slabs) to the floor to transfer weight to nearest beams.
Additional weights of factory-installed options (30HW only) are:
Sound enclosure — 75 lb (34 kg)
Hot gas bypass — 15 lb (7 kg)
80-amp non-fused disconnect — 15 lb (6.8 kg)
100-amp non-fused disconnect — 25 lb (11.3 kg)
200-amp non-fused disconnect — 70 lb (31.8 kg)
Be sure interconnecting piping and electrical conduits are suspended freely, and are not in contact with any adjacent walls. Be sure unit capillaries are not rubbing against anything.
Do not store units in an area exposed to weather
1
⁄2ft (2.3 m) (for 040 units) or
Step 1 — Inspect Shipment — Inspectunit for dam-
age or missing parts. If damaged, or if shipment is incom­plete, file a claim immediately with the shipping company.
Step 2 — Rig and Place Unit
30HK,HL UNITS — On each end of cooler, a steel loop is provided for the preferred method of lifting unit. Use spreader
bars to keep cables away from compressor enclosure and control box. If unit is to be moved by forklift truck, use one
of the following two methods:
1. From front or rear, lift under the cooler rails. Unit can be
either on or off skid.
2. When moving from the ends, leave unit on the skid. Lift
from under the skid.
If unit is to be dragged into final position, or moved on
rollers, it is recommended that it be left on the skid. When
dragging or rolling, apply force only to the skid, not to the unit. Lift from above, using the lifting angles provided, to
remove unit from the skid. 30HW UNITS NOTE: If accessory mobility package (Carrier part no.
30HW900008) is to be used, install this accessory after bring­ing unit into building and before moving the unit to its final location per installation instructions provided with the accessory.
Units Equipped WithFactory-Installed Unit Wheels —This factory-installed option consists of 4 swivel-type wheels mounted to the legs of the unit. See Fig. 11. For units equipped with this option, leave the skid on until the unit is in the building. Once in the building, remove the skid, and wheel the unit to its final location.
NOTE: The wheels are equipped with a thumb-screw brake. Units Not Equipped With Factory-Installed Unit Wheels —
Do not remove the skid until the unit has been moved to its final location. The unit may be moved by means of rollers under the skid, a forklift truck, or rig and slings.
Step 3 — Place the Unit
30HK,HL UNITS — When unit is in final position, remove skid, level the unit (using a level), and bolt the unit to floor or pad.
NOTE: These units are not suitable for unprotected outdoor
use.
Carrier recommends that these units be located in the base­ment or on the ground floor. However, if it is necessary to locate the unit on an upper floor, be sure the structure has been designed to support the unit weight. If necessary, add structural support to floor. Also, be sure the surface for in­stallation is level. Refer to Fig. 4 and 5 for space require­ments and Fig. 9 for weight distribution.
Only electrical power connections, water connections for condenser, and fluid connections for cooler are required for 30HK installation. Installation of 30HL units varies only in field piping required for the remote condenser.
30HW UNITS — When the unit is in its final position, re­move the skid (from units not equipped with factory­mounted wheels), or remove the wheels (if equipped). Re-
3
⁄8-in. wheel nuts to remove wheels from unit legs.
move Level the unit (using a level), and bolt the unit to the floor or pad.
If unit is to be mounted on unit external vibration isola­tors, follow the mounting instructions included with the ac­cessory vibration isolator (Carrier part numbers 30HW900­001 and -002).
Step 4 — Check Compressor Mounting and Connections—
by special self-locking nuts (Fig. 12). After unit is installed, loosen the self-locking nuts one at a time until compressor floats freely. Do not remove nuts, as they are self-locking and will hold their locked position.
As shipped, the compressor is held down
3
TOP VIEW
FRONT VIEW RIGHT SIDE VIEW
UNIT
30HK
040
050,060
DIMENSIONS — in. (mm)
ABCD
1
5
4
(133)90(2286)
3
10
4
(273)
108
(2743)
149⁄ (370)
1
20 (510)
16
715⁄ (202)
16
9
13 (344)
LEGEND
COMP — Compressor K.O. Knockout MTG Mounting SAE Society of Automotive Engineers (U.S.A.)
NOTES:
1. Standard unit shown with the sound enclosure accessory.
2. Dimensions are in inches unless otherwise indicated. Dimensions in ( ) are in millimeters.
3. Service clearance for the control box is 36-in.
Fig. 4 — 30HK040-060 (Fluid Cooled)
16
16
LEFT SIDE VIEW
4
TOP VIEW
FRONT VIEW RIGHT SIDE VIEW
LEGEND
CLY Cylinder COMP — Compressor CONN — Connection K.O. Knockout
NOTES:
1. Standard unit shown withthesounden­closure accessory.
2. Dimensions are in inches unless oth­erwiseindicated.Dimensions in ( ) are in millimeters.
LEFT SIDE VIEW
Fig. 5 — 30HL050,060 (Condenserless)
5
LEFT SIDE VIEW
REAR VIEW
UNIT
30HWA
018
025
028
035
040
DISCONNECT
(Amps)
DISC. — Disconnect K.O. Knockout
ABCDEFG
12.58 (320)
12.82 (326)
12.64 (321)
12.87 (327)
12.66 (322)
80
100
200
LEGEND
DIMENSIONS — in. (mm)
19.20 (488)
18.98 (482)
18.31 (465)
18.62 (473)
18.64 (473)
20.48 (520)
20.57 (522)
20.73 (527)
20.81 (529)
21.30 (541)
33.85 (860)
33.85 (860)
33.85 (860)
33.85 (860)
34.15 (867)
11.72 (298)
11.72 (298)
11.72 (298)
11.72 (298)
11.34 (288)
5.75
(146)
5.75
(146)
5.75
(146)
5.75
(146)
8.22
(209)
17.95 (456)
17.95 (456)
17.95 (456)
17.95 (456)
17.36 (441)
RIGHT SIDE VIEW
LOCATION — in. (mm) MODEL 30HWA (See Table Below)
J K L M 018--- 025--- 028--- 035--- 040---
3.33 (85)
4.33
(110)
7.46
(189)
2.98 (76)
4.98
(126)
11.19 (284)
NOTES:
1. Denotes center of gravity.
2. Denotes accessory or factory-installed option.
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
14.44 (367)
14.82 (376)
15.82 (402)
46.50
(1181)
47.50
(1207)
54.50
(1384)
100,200,
600,800,900
500 500,800 800 200,800
500 500 500,800
100,200,
600,900
100,200,
600,900
100,600,900
MODEL VOLT-Hz
100 575-60 200 380-60 500 208/230-60 600 460-60 800 230-50 900 400-50
100,200,
600,900
Fig. 6 — 30HWA018-040 (Condenserless)
6
LEFT SIDE VIEW
REAR VIEW
UNIT
30HWB
018
025
028
035
040
DISCONNECT
COND — Condenser DISC. — Disconnect K.O. Knockout
ABCDEFGHJ
13.14
18.72
(334)
(475)
13.22
18.25
(336)
(464)
13.18
17.71
(335)
(450)
13.45
17.98
(342)
(457)
13.27
17.75
(337)
(451)
(Amps)
80
100
200
LEGEND
DIMENSIONS — in. (mm)
22.02
33.85
11.72
5.75
12.29
17.95
(559)
22.10 (561)
22.39 (569)
22.68 (576)
23.44 (595)
(860)
33.85 (860)
33.85 (860)
33.85 (860)
34.15 (867)
(298)
11.72 (298)
11.72 (298)
11.72 (298)
11.34 (288)
(146)
5.75
(146)
5.75
(146)
5.75
(146)
8.22
(209)
(312)
12.29 (312)
12.29 (312)
12.29 (312)
12.38 (314)
(456)
17.95 (456)
17.95 (456)
17.95 (456)
17.36 (441)
9.28
(236)
9.28
(236)
9.28
(236)
9.28
(236)
8.22
(209)
RIGHT SIDE VIEW
LOCATION — in. (mm) MODEL 30HWB (See Table Below)
K L M N 018--- 025--- 028--- 035--- 040---
3.33 (85)
4.33
(110)
7.46
(189)
2.98 (76)
4.98
(126)
11.19 (284)
14.44 (367)
14.82 (376)
15.82 (402)
46.50
(1181)
47.50
(1207)
54.50
(1384)
100,200,300,
600,800,900
500 500,800 500,800 800
500 500,800
100,200,
600,900
NOTES:
1. Denotes center of gravity.
2. Denotes accessory or factory-installed option.
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
100,200,
600,900
MODEL VOLT-Hz
100,200,
600,900
100 575-60 200 380-60 500 208/230-60 600 460-60 800 230-50 900 400-50
600,900
Fig. 7 — 30HWB018-040 (Fluid Cooled)
100
200,
7
LEFT SIDE VIEW FRONT VIEW
UNIT
30HWC,S
018
025
028
035
040
DISCONNECT
(Amps)
LEGEND
D. Diameter Disc. Disconnect K.O. Knockout SCH.40 — Schedule 40 Pipe
ABCDEFG
80
100
200
47.50
(1206)
48.30
(1227)
48.00
(1219)
48.20
(1224)
47.80
(1214)
9.90
(251)
9.90
(251)
10.00 (254)
10.00 (254)
10.00 (254)
(1971) (2022) (2127)
DIMENSIONS — in. (mm)
14.00 (356)
15.50 (394)
15.80 (401)
15.90 (404)
15.90 (404)
LOCATION — in. (mm) MODEL 30HWC,S (See Table Below)
J K L 018--- 025--- 028--- 035--- 040---
77.61
79.61
83.74
NOTES:
1. Denotes center of gravity.
2. Denotes accessory or factory-installed option.
3. Dimensions are in inches. Dimensions in ( ) are in millimeters.
4.38
(111)
5.00
(127)
10.00 (254)
18.15 (461)
18.15 (461)
18.15 (461)
18.15 (461)
18.45 (469)
17.95 (456)
17.95 (456)
17.95 (456)
17.95 (456)
17.36 (441)
3.33 (85)
4.33
(110)
7.46
(189)
6.69
(170)
6.69
(170)
6.69
(170)
6.69
(170)
6.40
(163)
34.20 (869)
34.20 (869)
34.20 (869)
34.20 (869)
32.94 (837)
100,200,
600,800,900
500 500,800 500,800 800
500 500,800
100,200,
600,900
RIGHT SIDE VIEW
100,200,
600,900
100,200,
600,900
MODEL VOLT-Hz
100 575-60 200 380-60 500 208/230-60 600 460-60 800 230-50 900 400-50
Fig. 8 — 30HWC,S018-040 (Fluid Cooled)
100
200,
600,900
8
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE, 60 HZ UNITS
MOUNTING HOLES
UNIT SIZE
040 710322712323705320703319———————— 050 787 357 789 358 782 355 780 354 519 235 521 236 516 234 514 233 060 838 380 840 381 832 377 830 376 534 242 536 243 531 241 529 240
NOTE: See Fig. 4 and 5 for specific mounting hole location dimensions.
ABCDABCD
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
30HK 30HL
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE, 50 HZ UNITS
MOUNTING HOLES
UNIT SIZE
040 721327723328716325715325———————— 050 838 380 840 381 832 377 830 376 534 242 526 238 531 241 529 240 060 853 387 855 388 847 384 845 383 550 249 551 250 545 247 544 247
NOTE: See Fig. 4 and 5 for specific mounting hole location dimensions.
ABCDABCD
Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg Lb Kg
30HK 30HL
LOCATION OF MOUNTING HOLES
Fig.9—Weight Distribution and Mounting Hole Location; 30HK,HL Units
30HWA,B 30HWC,S
WEIGHT DISTRIBUTION AT EACH MOUNTING HOLE — Lb (kg)
UNIT
30HW
A018 185 (83.9) A025 220 (99.8) A028 240 (108.9) A035 244 (110.7) A040 270 (122.5) B018 199 (90.3) B025 238 (108.0) B028 266 (120.7) B035 271 (122.9)
B040 328 (148.8) C,S018 171 (77.6) 136 (61.7) C,S025 196 (88.9) 144 (65.3) C,S028 211 (95.7) 160 (72.6) C,S035 216 (98.0) 161 (73.0) C,S040 240 (108.9) 185 (83.9)
12345678
MOUNTING HOLE NO.
Fig. 10 — Mounting Hole Weight Distribution; 30HW Units
9
Table 1A — Physical Data; 30HK, HWB, HWC, and HWS Fluid-Cooled Units — English
UNIT 30 HW-018* HW-025* HW-028* HW-035* HW-040* HK040 HK050 HK060 OPERATING WT (Approximate) − lb
HWB 795 950 1065 1085 1310 HWC,S 1231 1358 1484 1508 1702
HK —————
REFRIGERANT — lb R-22
HWB 12.5 15.0 17.5 18.5 23.2 HWC,S 35.0 37.0 42.0 42.0 47.0 HK — Ckt 1 —————35/40† 45/45† 45/45† HK − Ckt 2 —————35/35† 35/45† 45/45†
COMPRESSOR Model No. 06DG537 06E2150** 06E7265 06E7175** 06E7299 06E2150 Nominal Hp 15 20 25 30 35 20 (ea) 20,30 30 (ea)
Quantity 11111 21(ea) 2 Cylinders Per Compressor 646664(ea) 6,4 6 (ea) Capacity Control — Standard No. of Steps 32333 4 4 4 Minimum Step Capacity (%) 33 50 33 33 33 25 20†† 33 Capacity Control — With Optional
Hot Gas Bypass
No. of Steps 43444 5 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10 10
Relief Valve Flow Rate — lb air/min 15.1 15.1 15.1 15.1 15.1 15.1 15.1
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664 Dry Weight — lb 69 81 105 105 145 657 726 726 Fluid Side — psig 300 300 300 300 300 150 150 150 Refrigerant Side — psig 430 430 430 430 430 235 235 235 Net Fluid Volume — Gal. 1.4 1.6 2.1 2.1 3.3 13.1 15.2 15.2
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 1
CONDENSER
30HWB (Water Cooled)
Part No. LL01S- D001 D002 D003 D004 E004 Dry Weight — lb 48 62 79 87 153 Water Side — psig 300 300 300 300 300 Refrigerant Side — psig 430 430 430 430 430 Net Water Volume — Gal. 0.9 1.2 1.6 1.8 3.3
(includes nozzles)
Water Connections — in. Grooved End
Inlet 1 Outlet 11⁄
30HWC (Water Cooled)
Part No. 09RW- 400007 400007 400011 400011 400009 Dry Weight — lb 532 532 560 560 624 Water Side — psig 300 300 300 300 300 Refrigerant Side — psig 365 365 365 365 365 Net Water Volume — Gal. 2.6 2.6 4.0 4.0 7.3 Relief Valve Flow Rate — lb air/min 24.6 24.6 24.6 24.6 24.6 Water Connections — in. Weld
Inlet 2 Outlet 21⁄
30HWS (Water Cooled)
Part No. 09RW- 400017 400017 400019 400019 400018 Dry Weight — lb 532 532 560 560 624 Water Side — psig 300 300 300 300 300 Refrigerant Side — psig 335 335 335 335 335 Net Water Volume — Gal. 2.6 2.6 4.0 4.0 7.3 Relief Valve Flow Rate — lb air/min 22.6 22.6 22.6 22.6 22.6 Water Connections — in. Weld
Inlet 2 Outlet 21⁄
30HK (Water Cooled)
Part No. 09RP- —————022/022† 022/027† 027/027† Dry Weight — lb —————1000 1095 1190 Water Side — psig —————250250250 Refrigerant Side — psig —————385385385 Net Water Volume — Gal. —————4.4/4.4† 4.4/5.2† 5.2/5.2†
(includes nozzles)
Relief Valve Flow Rate — lb air/min —————25.9 25.9 25.9 Water Connections — in. Weld
Inlet —————2 Outlet —————2
LEGEND
ODS — Outside Diameter, Sweat
*Unless otherwise noted, data is for HWB, HWC, and HWS units. †60 Hz/50 Hz units.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2
1
2
1
2 2
1
2 2
1
2 2
11⁄ 11⁄
11⁄ 11⁄
21⁄ 21⁄
21⁄ 21⁄
2 2
2 2
2 2
2 2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
21⁄ 21⁄
21⁄ 21⁄
21⁄ 21⁄
21⁄ 21⁄
2 2
2 2
2 2
2 2
2830/ 2875†
333 333
——— ———
——— ———
——— ———
1
2
1
2
3138/ 3340†
06E6175,
06E2150
1
2
2
1
2
2
3340/
3400†
06E6175
1
2
2
1
2
2
10
Table 1B — Physical Data; 30HK, HWB, HWC, and HWS Fluid-Cooled Units — SI
OPERATING WT (Approximate) − kg
UNIT 30 HW-018* HW-025* HW-028* HW-035* HW-040* HK040 HK050 HK060
HWB 360 431 483 492 594 HWC,S 554 611 668 679 766
HK —————
REFRIGERANT — kg R-22
HWB 5.7 6.8 7.9 8.4 10.5 HWC,S 15.9 16.8 19.1 19.1 21.3 HK — Ckt 1 —————15.9/18.1† 20.4/20.4† 20.4/20.4† HK — Ckt 2 —————15.9/15.9† 15.9/20.4† 20.4/20.4†
COMPRESSOR Model No. 06DG537 06E2150** 06E7265 06E7175** 06E7299 06E2150 Nominal kW 11.1 14.9 18.7 22.4 26.1 14.9 (ea) 14.9,22.4 22.4 (ea)
Quantity 11111 21(ea) 2 Cylinders Per Compressor 646664(ea) 6,4 6 (ea) Capacity Control — Standard No. of Steps 32333 4 4 4 Minimum Step Capacity (%) 33 50 33 33 33 25 20†† 33 Capacity Control — With Hot Gas Bypass
No. of Steps 43444 5 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10 10
Relief Valve Flow Rate — kg air/min 6.8 6.8 6.8 6.8 6.8 6.8 6.8
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 10HA400664 Dry Weight — kg 31.3 36.7 47.6 47.6 65.7 297 330 330 Fluid Side — kPa 2069 2069 2069 2069 2069 1034 1034 1034 Refrigerant Side — kPa 2965 2965 2965 2965 2965 1620 1620 1620 Net Fluid Volume — L 5.3 6.1 8.0 8.0 12.5 49.9 57.5 57.5
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 11⁄
CONDENSER
30HWB (Water Cooled)
Part No. LL01S- D001 D002 D003 D004 E004 Dry Weight — kg 21.8 28.1 35.8 39.5 69.4 Water Side — kPa 2069 2069 2069 2069 2069 Refrigerant Side — kPa 2965 2965 2965 2965 2965 Net Water Volume — L 3.4 4.5 6.1 6.8 12.5
(includes nozzles)
Water Connections — in. Grooved End
Inlet 1 Outlet 1
30HWC (Water Cooled)
Part No. 09RW- 400007 400007 400011 400011 400009 Dry Weight — kg 241 241 254 254 283 Water Side — kPa 2069 2069 2069 2069 2069 Refrigerant Side — kPa 2517 2517 2517 2517 2517 Net Water Volume — L 9.8 9.8 15.4 15.4 27.6 Relief Valve Flow Rate — kg air/min 11.2 11.2 11.2 11.2 11.2 Water Connections — in. Weld
Inlet 2 Outlet 2
30HWS (Water Cooled)
Part No. 09RW- 400017 400017 400019 400019 400018 Dry Weight — kg 241 241 254 254 283 Water Side — kPa 2069 2069 2069 2069 2069 Refrigerant Side — kPa 2310 2310 2310 2310 2310 Net Water Volume — L 9.8 9.8 15.4 15.4 27.6 Relief Valve Flow Rate — kg air/min 10.3 10.3 10.3 10.3 10.3 Water Connections — in. Weld
Inlet 2 Outlet 2
30HK (Water Cooled)
Part No. 09RP- —————022/022† 022/027† 027/027† Dry Weight — kg —————454497540 Water Side — kPa —————1724 1724 1724 Refrigerant Side — kPa —————2655 2655 2655 Net Water Volume — L —————17/17† 17/20† 20/20†
(includes nozzles)
Relief Valve Flow Rate — kg air/min —————11.711.711.7 Water Connections — in. Weld
Inlet —————2 Outlet —————2
LEGEND
ODS — Outside Diameter, Sweat
*Unless otherwise noted, data is for HWB, HWC, and HWS units.
†60 Hz/50 Hz units.
**For 025 50 Hz units, compressor number is 06E2250, for 035 50 Hz units
compressor number is 06E7275.
††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2 2
1
2
1
2
1
2
1
2
1
2
1
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
11⁄
2
11⁄
2
11⁄
2
11⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
NOTES:
1. Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
2. 30HK,HWB,HWC, and HWS units are shipped with full operating charge.
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
21⁄
2
1284/ 1305†
333 333
——— ———
——— ———
——— ———
1
2
1
2
1424/ 1514†
06E6175,
06E2150
1
2
2
1
2
2
1514/ 1542†
06E6175
1
2
2
1
2
2
11
Table 2A — Physical Data; 30HL, HWA Condenserless Units — English
UNIT 30 HWA018 HWA025 HWA028 HWA035 HWA040 HL050 HL060 OPERATING WT (Approximate) − lb 740 880 960 975 1080 REFRIGERANT† — lb R-22
1.6 2.0 2.4 2.4 3.0 6.3/4.2** 5.3/5.3**
COMPRESSOR
Model No. 06DG537 06E2250 06E7265 06E7275 06E7299 Nominal Hp 15 20 25 30 35 25,20 30 (ea)
Quantity 111111(ea) 2 Cylinders Per Compressor 646666,4 6 Capacity Control — Standard No. of Steps 32333 4 4 Minimum Step Capacity (%) 33 50 33 33 33 20†† 33 Capacity Control — With Optional
Hot Gas Bypass
No. of Steps 43444 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10
Relief Valve Flow Rate — lb air/min 15.1 15.1 15.1 15.1 15.1 15.1
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 Dry Weight — lb 69 81 105 105 145 726 726 Fluid Side — psig 300 300 300 300 300 150 150 Refrigerant Side — psig 430 430 430 430 430 235 235 Net Fluid Volume — Gal. 1.4 1.6 2.1 2.1 3.3 13.1 15.2
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 11⁄
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS Discharge Line ODS 11⁄
LEGEND
ODS — Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown. **Ckt 1/Ckt 2. ††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2 2
7
8
8
11⁄ 11⁄
11⁄
2 2
7
8
8
11⁄
2
11⁄
2
7
8
13⁄
8
NOTE: Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
11⁄
2
11⁄
2
7
8
13⁄
8
21⁄
2
21⁄
2
7
8
15⁄
8
2070/ 2120*
06E6275,
06E2250
33 33
7
8
13⁄
8
2130/
2190*
06E6275
7
8
13⁄
8
Table 2B — Physical Data; 30HL, HWA Condenserless Units — SI
UNIT 30 HWA018 HWA025 HWA028 HWA035 HWA040 HL050 HL060
OPERATING WT (Approximate) − kg 335 399 435 442 490
REFRIGERANT† — kg R-22
0.7 0.9 1.1 1.1 1.4 2.9/1.9** 2.4/2.4**
COMPRESSOR
Model No. 06DG537 06E2250 06E7265 06E7275 06E7299 Nominal kW 11.2 14.9 18.7 22.4 26.1 18.7,14.9 22.4 (ea)
Quantity 111111(ea) 2 Cylinders Per Compressor 646666,4 6 Capacity Control — Standard No. of Steps 32333 4 4 Minimum Step Capacity (%) 33 50 33 33 33 20†† 33 Capacity Control — With Optional Hot Gas Bypass
No. of Steps 43444 5 5 Minimum Step Capacity (%) 10 10 10 10 10 10 10
Relief Valve Flow Rate — kg air/min 6.8 6.8 6.8 6.8 6.8 6.8
COOLER
Part No. LL01SB006 LL01SB007 LL01SB009 LL01SB009 LL01SC005 10HA400654 10HA400664 Dry Weight — kg 31.3 36.7 47.6 47.6 65.7 330 330 Fluid Side — kPa 2069 2069 2069 2069 2069 1034 1034 Refrigerant Side — kPa 2965 2965 2965 2965 2965 1620 1620 Net Fluid Volume — L 5.3 6.1 8.0 8.0 12.5 49.9 57.5
(includes nozzles)
Fluid Connections — in. Grooved End
Inlet 1 Outlet 1
CONDENSER CONNECTIONS
Refrigerant Connections — in.
Liquid Line ODS Discharge Line ODS 11⁄
LEGEND
ODS — Outside Diameter, Sweat
*60 Hz/50 Hz units.
†30HWA and HL units (condenserless) are shipped with a refrigerant holding
charge. Approximate cooler operating charge is shown. **Ckt 1/Ckt 2. ††Withtransferswitch set tocompressor no. 2 position;40% with transfer switch
set to compressor no. 1 position.
1
2
1
2
11⁄
2
11⁄
2
7
8
8
11⁄
2
11⁄
2
NOTE: Operating weight includes refrigerant operating charge and weight of fluid in the heat exchangers.
11⁄
2
11⁄
2
7
8
13⁄
8
21⁄ 21⁄
15⁄
2 2
7
8
8
938/ 961†
06E6275,
06E2250
33 33
7
8
13⁄
8
966/
993†
06E6175
7
8
13⁄
8
12
THUMB-SCREW BRAKE
Fig. 11 — Factory-Installed Unit Wheels (4)
Fig. 12 — Compressor Mounting
Step 5 — Make Piping Connections — See
Fig. 13 and 14 for typical piping applications. 30HK, HWC, HWS CONDENSER DESCRIPTION — All
30HWC and HWS units use a shell-and-tube condenser with removable heads for easy tube servicing. Refrigerant is con­tained within the shell, and water flows through the tubes. The 30HK and HWC units use a steel shell condenser(s) with steel tube sheets and copper tubes. The 30HWS units are designed for sea coast applications and use a steel shell con­denser with cupronickel tube sheets and tubes. In addition, the 30HWS water heads utilize ‘‘sacrificial’’ zinc anodes for condenser corrosion protection.
IMPORTANT:Inspect the zinc anodes every 3 months for deterioration and replace as needed. Galvanic pro­tection of the condenser is lost if the anodes are not replaced prior to complete deterioration.
The number of tubes in the condenser(s) varies depending on the unit size.The condensers have internal subcoolers which provide approximately 8 F (4.4 C) for 30HK, HL units or 13 F (7.2 C) for 30HW units subcooling at ARI (Air Condition­ing and Refrigeration Institute, U.S.A.) rating conditions.
30HL, HWA SYSTEM CONDENSER — For detailed con­denser piping installation instructions for 30HL and HWA systems, refer to separate instructions packaged with the re­mote condenser unit(s).
Condenser refrigerant piping for 30HLandHWAunitsshould be sized to minimize the amount of refrigerant required.
The 30HL and HWA units that use an air-cooled evapo­rative condenser(s) must have adequate means for head pres­sure control when operating below 60 F (15.6 C).
Carrier recommends that a field-supplied pressure relief device be installed after the muffler in each discharge line. Most local codes require the relief valve to be vented di­rectly to the outdoors. The vent must not be smaller than the relief valve outlet.
30HWB CONDENSER DESCRIPTION —All 30HWB units use a brazed-plate heat-exchanger-type condenser. These heat exchangers are made of embossed plates of acid-resistant stain­less steel. Every other plate is reversed so that the ridges of the herringbone pattern intersect one another on adjacent plates, forming a lattice of contact points. These plates are vacuum­brazed together to form a compact and pressure-resistant heat exchanger.
After brazing, the impressions in the plates form 2 sepa­rate systems of channels where the refrigerant and water flows are counter-current. The number of plates varies depending on unit tonnage. The condensers provide approximately 14° to 18° F (8° to 10° C) liquid subcooling at the standard Air Conditioning and Refrigeration Institute (ARI) rating condition.
30HK, HWC, HWS CONDENSER(S) — When facing the front of the unit, the condenser(s) is in the uninsulated shell(s) located across the bottom of the unit. The water connections are such that the water inlet is located on the left-hand side (30HK) or right-hand side (30HW) of the unit. The water inlet mustALWAYS be on the bottom of the condenser(s) to provide the proper subcooling. The water outlet is located on the right-hand side (30HK) or left-hand side (30HW) of the unit. The water connections can be reversed by rotating the heads and gaskets 180 degrees ON BOTH ENDS OF THE CONDENSER(S).
IMPORTANT: THE WATER INLET MUST AL­WAYS BE ON THE CONDENSER HEAD(S) THAT HAS THE NOZZLE CONNECTION AT THE BOT­TOM OF THE HEAD. Incorrect inlet connection will result in poor system performance due to incorrect subcooling.
The LIQUID-IN and LIQUID-OUT labels indicate water connections AS SUPPLIED FROM THE FACTORY.
It is recommended that strainer with a minimum of 20 mesh be installed ahead of the condenser water inlet(s) to prevent debris from clogging or damaging the heat exchanger(s).
There is a pressure-relief device on the condenser(s) of all 30HK, HWC, and HWS units. Most local codes require that this relief be vented directly to the outdoors.
NOTE: The relief line must not be smaller than the relief valve outlet. Be sure to provide a way of draining and ser­vicing the unit.
13
LEGEND
Airflow Through Condenser
Airflow Through Air
Handling Unit
Power Wiring
Control Wiring
Chilled Water Piping
ST — Field-Supplied Starter
Flow Switch
FD — Field-Supplied Disconnect
FS — Field-Supplied Differential
*Field Supplied.
14
to maintain proper compressor oil return.
levelly
2. Wiring and piping shown are general points-of-connection guides only and are not intended for a specific installation. Wiring and piping
NOTES:
1. Chiller must be installed
shown are for a quick overview of system and are not in accordance with recognized standards.
of Heating, Refrigeration, and Air Conditioning Engineers) handbook for details.
3. All wiring must comply with applicable local and national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual or appropriate ASHRAE (American Society
Fig. 13 — Typical Piping with Fluid-Cooled 30HWB Unit Shown
volume.
5. See Table 3 on page 17 for minimum system fluid volume. This system may require the addition of a holding tank to ensure adequate
NOTES:
1. Chiller must be installed sor oil return.
2. Wiring andpipingshown are general points-of-connectionguides only and are not intended for a specific installation. Wiring and piping shown are for a quick overview of system and are not in accordance with recognized standards.
3. All wiring must complywithapplicablelocaland national codes.
4. All piping must follow standard piping techniques. Refer to Carrier System Design Manual part 3, Carrier E20-IIT soft­ware Refrigerant Piping program, or appropriate ASHRAE (American Society of Heating, Refrigeration, and Air Condi­tioningEngineers)handbookfordetailsonproperpipingsizes and design.
5. See Table 3 on page 17 for minimum system fluid volume. This system may require the addition of a holding tank to en­sure adequate volume.
6. Hot gas lines should rise above refrigerant level in condenser circuit. Double riser may be required; check compressor mini­mum capacity.
7. Trap should be installed on hot gas lines to prevent con­denser oil and refrigerant vapor migration from accumulating on compressor heads during off cycle.
8. Pitch all horizontal lines downward in the direction of refrig­erant flow.
9. For piping lengths greater than 50 ft, provide support to liquid and gas lines near the connections to the condenser coil.
10. For pressure relief requirements, see latest revision of ASHRAE Standard 15, Safety Code for Mechanical Refrigeration.
levelly
to maintain proper compres-
Fig. 14 — Typical Piping with Air-Cooled 30HWA with Remote 09DK Unit Shown
15
30HWB CONDENSER — When facing the back of the unit, the condenser is the uninsulated heat exchanger located on the right-hand side. The water connections are on the right­hand side of the heat exchanger with the LIQUID-IN con­nection at the bottom, and the LIQUID-OUT connection at the top.
A strainer with a minimum of 20 mesh must be installed
ahead of the condenser water inlet to prevent debris from clogging or damaging the heat exchanger.
To install the grooved end coupling (see Fig. 15):
1. Lubricate the gasket lips and stretch the gasket over the end of the pipe. Avoid twisting the gasket when installing.
2. Bring the pipe and heat exchanger coupling ends to­gether into alignment. Slide the gasket so that it is cen­tered over the ends. Apply a light film of lubricant to the gasket, or to the gasket recess of the coupling housing. Avoid twisting the gasket during installation.
3. Seat the coupling halves over the gasket and install the nuts and bolts. Tighten the nuts equally on both sides.
4. Alternately tighten the nuts with a wrench to draw the coupling halves together uniformly. The joint is now complete.
30HK, HWB, HWC, HWS UNITS — In order to minimize the water pressure drop in the system, use as few bends as possible in the field water piping, and run the lines as short as possible. Size the water lines according to the available pump pressure (not necessarily the connection size), espe­cially on cooling tower applications. See Carrier System De­sign Manual, Part 3, Piping Design. See Fig. 16 for condenser pressure drops.
Set water regulating valve to maintain design head pres­sure. Do not adjust to compensate for high head pressures caused by fouled condenser tubes, excess refrigerant, or the presence of noncondensables. Due to changes in water temperature, it may be necessary to adjust the valve season­ally.After adjusting for design head pressure, shut unit down. The water regulating valve should shut off the flow of water in a few minutes. If it does not, raise head pressure setting. Make sure that the capillary tube from each water regulating valve is connected to the proper condenser purge valve.
Provide a means for draining the system in the winter (if
not used) and for maintenance.
Accessory steel manifold packages for inlet and outlet con­denser water are available for 30HK units. Each manifold is furnished in 2 sections, to be field welded as shown in Fig. 4. Manifolds should not be used where regulating valves are required because separate valves must be used on each condenser circuit.
Retighten all condenser head bolts before filling system with water. Torque bolts to a maximum of 40 to 45 ft-lb.
Water leaving the condenser is under pressure and should not be connected directly into sewer lines. Check local codes. A 3/8-in. drain plug is located in the head at each condenser end.
Refer to Pressure Relief Devices and Discharge Line Check Valve sections on page 28, concerning piping connections for these components.
COOLER DESCRIPTION 30HK, HL Units — The cooler is a direct-expansion type
with removable heads and is partitioned for multi-pass re­frigerant flow. Fluid flow across the tube bundle is directed by baffles designed for minimum fluid-pressure drop. The tubes have integral internal fins for maximum heat transfer efficiency.
Viewed from unit front, the return chilled fluid enters at the left end of the cooler and leaves at the right end. The sensing bulb for the factory-supplied fluid temperature con­troller is in the leaving-fluid nozzle; the leaving-fluid tem­perature being the control point.
The cooler is insulated with a flexible, closed-cell plastic foam insulation of suitable thickness. Fluid vapor cannot pen­etrate the cellular structure to condense either within cells or on the cooler shell. Thus, the insulation itself is a vapor bar­rier.Because of the toughness of insulation, a protective sheet metal covering is not necessary.
Special modification may be necessary for brine chillers. Contact your Carrier representative for details. For calcium or sodium chloride brines, it is important that the proper in­hibitors be carefully selected for protection of the copper tubes. Refer to the publications of the Calcium Institute or the Mutual Chemical Division of Allied Chemical Corporation for information on corrosion control for calcium or sodium chloride systems.
30HW Units — All 30HW units use a brazed-plate heat­exchanger type cooler.The heat exchanger is constructed es­sentially the same as the brazed-plate condenser used on 30HWB units. See 30HWB Condenser Description section on page 13 for more details. Similar to the condenser, the cooler can only be chemically cleaned.
COOLER PIPING — Plan cooler fluid piping for minimum number of changes in elevation, and for the fewest number of bends as possible. Install manual or automatic vent valve at high points in the line. Maintain system pressure by using a pressure tank or a combination or relief and reducing valves.
A strainer with a minimum of 20 mesh must be installed ahead of the cooler fluid inlet to prevent debris from clog­ging or damaging the heat exchanger.
See Carrier System Design Manual, Part 3, Piping Design, for chilled fluid piping details.
Fig. 15 — Installed Coupling Fastening Grooved
Pipe Ends
16
The cooler fluid inlet and outlet connections are grooved­end. On 30HW units, the fluid enters at the top connection and leaves at the bottom connection. Procedures for making the grooved-end connections are the same as for the 30HWB condensers. See 30HWB Condenser section on page 16 for more details.
Run the pump for 10 minutes, then clean the strainer be­fore starting the unit.
A cooler flow switch must be field-installed on all units. This should be a differential pressure switch that is installed between the cooler fluid inlet and outlet. The switch should be set to open when the cooler fluid flow drops below the values shown in Table 3. Use the cooler water pressure drop curves (Fig. 16) to determine correct setting for each unit size. Use Carrier accessory flow switch, part number 30HW900003. See Table 3 for Minimum Flow rates and loop volumes.
See Step 6 — Make Electrical Connections section on page 19 for flow switch wiring details.
30HK, HL Units — The thermistor used for sensing fluid temperature is factory-installed in the cooler leaving fluid line.
30HW Units — The thermistor used for sensing the fluid temperature is inside the cooler leaving-water cavity.
Table 3 — Minimum Cooler and Condenser Flow
Rates Minimum Loop Volume
UNIT SIZE
30HK040 56.0 3.5 67 4.23 120 454.2 30HK,HL050 68.0 4.3 76 4.79 148 560.2 30HK,HL060 68.0 4.3 83 5.24 174 658.6
30HW018 22.5 1.4 22.5 1.4 44 167 30HW025 30.0 1.9 30.0 1.9 59 223 30HW028 37.5 2.4 37.5 2.4 76 288 30HW035 45.0 2.8 45.0 2.8 85 322 30HW040 57.0 3.6 57.0 3.6 113 428
ARI — Air Conditioning and Refrigeration Institute N—Liters per kW V—Gallons per ton
*30HK, HWB, HWC and HWS only.
†Minimum system fluid volumes. NOTES:
Gallons=VxARIcapacity in tons. Liters=NxARIcapacity in kW.
Normal Air Conditioning 3 3.25
Process Type Cooling 6 to 10 6.5 to 10.8
Low Ambient Operation 6 to 10 6.5 to 10.8
COOLER CONDENSER*
Gal./Min L/s Gal./Min L/s Gal. L
LEGEND
APPLICATION V N
MINIMUM COOLER
LOOP VOLUME†
COOLER PRESSURE DROP — 30HW UNITS COOLER PRESSURE DROP — 30HK, HL UNITS
NOTE: Ft of water = 2.31 x change in psig.
Fig. 16 — Cooler and Condenser Water Pressure Drop
17
CONDENSER PRESSURE DROP —
30HK UNITS
CONDENSER PRESSURE DROP —
30HWB UNITS
NOTE:Ftof water = 2.31xchange in psig.
CONDENSER PRESSURE DROP —
30HWC AND 30HWS UNITS
Fig. 16 — Cooler and Condenser Water Pressure Drop (cont)
18
Step6 — Make Electrical Connections— All field
wiring must comply with local code requirements. Electrical data for the complete unit and for the compressors is shown in Tables 4A and 4B. See Fig. 17 and 18 for field wiring connections.Afield-supplied branch circuit disconnect switch that can be locked in either OPEN or OFF position must be installed.
30HK, HL UNITS — On all 60 Hz units, a fused (15 amp maximum), 115 v control circuit must be supplied by either a separate power source or by using a minimum 300 va trans­former. On 208/230 and 460 v units, control circuit power can be supplied by accessory transformer part no. 07EA900051. Check to be sure that installation of the 115 v control power source meets all local codes.
On all 50 Hz units, a fused (15 amp maximum), 230 v control circuit must be field supplied. On 200-3-50 units, power for the control circuit can be supplied by connecting a field­supplied fuse (15 amp maximum) between TB1 and TB2 for L1 overcurrent protection. On 400-3-50 units, power for the control circuit can be supplied by connecting a field­supplied fuse (15 amp maximum) between TB1 and a neu­tral leg from TB2 for L1 overcurrent protection. On all units, check to be sure that installation of the 230 v control power source meets all local codes.
30HW UNITS — Control circuit power is 24 v and 115 v on all units, and is supplied by factory-installed control transformers.
ALL UNITS — Inside the control box are terminals for field power and ground (earth) wiring, as well as a terminal for a neutral wire when needed (380-3-60 and 400-3-50 units only). A ground wire must be installed with each field power sup­ply.Compressor are wired standard from the factory for across­the-line start. As a factory-installed option, all 025-060 sizes are available wired for part-wind start (special order option on 30HK, HL unit).
Refer to Tables 4A and 4B for electrical data. Flow Switch — A cooler flow switch is required for all units,
and must be field-installed. The Carrier flow switch acces­sory (part number 30HW900003), is available for this pur­pose. Flow switch wiring terminals are located in the field wiring compartment of the control box. The flow switch should be wired between terminals TB3-1 and TB3-7 for 30HK, HL units or between terminals TB2-7 and TB2-13 for 30HW units. The factory jumper wire between these 2 terminals must be removed for proper operation of the flow switch.
Control Box, Power Section — The electrical power supply is brought in through the top left-hand side (30HK, HL) or right-hand side (30HW) of the control box (see Fig. 19 and
20). The knockout accepts up to a 3-in. (76 mm) conduit for 30HK, HL units, and a 13⁄4-to21⁄2-in. (44 to 64 mm) conduit for 30HW units. Pressure-lug connections on the terminal blocks are suitable for copper, copper-clad aluminum, or alu­minum conductors.
The control box power section contains the following components:
• power terminal block
• compressor circuit breaker(s)
• compressor contactor(s)
• high-voltage transformer (30HW units only)
• control-circuit circuit breaker for 24-v circuit
• unit ON-OFF switch
• unit service light
• ground lug
• neutral terminal (380-3-60 and 400-3-50 units)
• terminal block for ground current sensing accessory
Control Box, Controls Section — The control box controls section contains the following components:
• temperature controller
• control relay(s)
• control module(s)
• low-voltage control transformer(s)
• terminal block for ground current sensing accessory Control Box, Field Control Wiring Section — Inside this
section is a 10-terminal (30HK, HL) or 14-terminal (30HW), low-voltage, field-wiring terminal strip. All low-voltage field­wiring connections are made to this terminal block. Seven
3
⁄4-in. (19 mm) knockouts are provided for field wiring in this section. Connections for chilled fluid flow switch, chilled fluid pump interlock, condenser pump interlock, remote alarm output, and ground current sensor accessory are made at this location. The remote condenser relay connections are made to a separate 4-terminal (30HK, HL) or 3-terminal (30HW) field wiring strip. See Fig. 17-20 for specific location of connections.
Unbalanced 3-Phase Supply Voltage — Never operate a com-
pressor where a phase imbalance in the supply voltage is greater than 2%. Use the following formula to determine
the percent voltage imbalance:
% Voltage Imbalance =
max voltage deviation from average voltage
100 x
average voltage
Example: Supply voltage is 240-3-60
AB = 243 v BC = 236 v AC = 238 v
Average Voltage =
243 + 236 + 238
3
= 239 v Determine maximum deviation from average voltage: (AB) 243 - 239=4v
(BC) 239 - 236=3v (AC) 239 - 238=1v
Maximum deviation is 4 v. Determine percent voltage imbalance:
% Voltage Imbalance = 100 x
4
239
= 1.7%
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local utility company immediately.
19
Table 4A — Electrical Data — 30HK, HWB, HWC, HWS Fluid-Cooled Units
UNIT SIZE
30-
HK040
HK050
HK060
HWB,C,S018
HWB,C,S025
HWB,C,S028
HWB,C,S035
HWB,C,S040
UNIT COMPRESSOR (ea)
Volts Voltage*
Nameplate (3 ph) Hz Min Max PW XL PW XL PW XL
208/230 60 187 253 129 340 175 150 57 283 89
460 60 414 518 59 168 80 70 26 142 40 575 60 518 632 54 122 70 60 24 98 42
220 50 198 253 142 390 200 175 75/48** 342/201** 116/74** 400 50 342 440 71 249 100 90 36/26** 223/142** 56/40**
208/230 60 187 253 161 503 225 200 83/57** 446/283** 89/64**
460 60 414 518 75 249 110 90 39/26** 223/142** 56/40** 575 60 518 632 73 188 110 90 39/24** 164/ 88** 54/37**
220 50 198 253 169 417 225 200 75 342 116 400 50 342 440 81 259 110 100 36 223 56
208/230 60 187 253 187 529 250 225 83 446 64
460 60 414 518 88 262 125 100 39 223 56 575 60 518 632 88 203 125 100 39 164 54
220 50 198 253 225 600 300 250 100 545 156 400 50 342 440 131 403 175 150 58 345 90
208/230 60 187 253 62 266 110 80 49 266 89
380 60 342 418 35 145 60 45 28 145 40 460 60 414 508 28 120 50 35 23 120 33 575 60 518 632 24 96 40 30 19 96 25
230 50 198 253 58 200 100 70 46 200 63
380/415 50 342 440 34 115 60 45 27 115 41 208/230 60 187 253 72 170 283 125 90 57 170 283 88 88
380 60 342 418 43 85 142 70 60 34 85 142 52 52 460 60 414 508 34 85 142 60 45 27 85 142 40 42 575 60 518 632 28 59 98 45 35 22 59 98 33 33
230 50 198 253 67 150 250 110 80 53 150 250 80 80
380/415 50 342 440 38 104 173 60 45 30 104 173 44 44 208/230 60 187 253 89 268 446 150 110 71 268 446 104 104
380 60 342 418 54 134 223 90 70 43 134 223 66 66 460 60 414 508 44 134 223 70 60 35 134 223 50 52 575 60 518 632 35 98 164 60 45 28 98 164 41 42
230 50 198 253 85 205 342 150 110 68 205 342 98 98
380/415 50 342 440 54 134 223 90 70 43 134 223 60 60 208/230 60 187 253 102 268 446 175 125 81 268 446 120 120
380 60 342 418 59 134 223 100 80 47 134 223 70 70 460 60 414 508 48 134 223 80 60 38 134 223 52 57 575 60 518 632 39 98 164 60 50 31 98 164 42 42
230 50 198 253 94 220 366 150 125 75 220 366 112 112
380/415 50 342 440 54 152 253 90 70 43 152 253 66 66 208/230 60 187 253 145 414 690 250 175 116 414 690 180 180
380 60 342 418 84 207 345 150 110 67 207 345 98 98 460 60 414 508 69 207 345 110 90 55 207 345 78 84 575 60 518 632 55 165 276 90 70 44 165 276 63 66
230 50 198 253 135 327 545 225 175 108 327 545 166 166
380/415 50 342 440 78 207 345 125 100 62 207 345 98 98
MCA
ICF
MFA
Rec
Fuse
RLA
LRA MTA
20
UNIT SIZE
30-
HL050
HL060
HWA018
HWA025
HWA028
HWA035
HWA040
Table 4B — Electrical Data — 30HL and HWA Condenserless Units
Nameplate (3 ph) Hz Min Max PW XL PW XL PW XL
Volts Voltage*
208/230 60 187 253 190 571 250 225 100/65** 506/315** 78/50**
460 60 414 518 84 282 125 100 44/29** 253/173** 68/45** 575 60 518 632 75 203 110 90 38/27** 176/128** 58/42**
200 50 198 253 187 449 250 225 83 366 128 400 50 342 440 99 297 125 110 44 253 68
208/230 60 187 253 225 606 300 250 100 506 78
460 60 414 518 99 297 125 110 44 253 68 575 60 518 632 86 214 110 100 38 176 58
200 50 198 253 261 616 350 300 116 545 180 400 50 342 440 138 406 175 175 61 345 95
208/230 60 187 253 72 266 125 90 57 266 89
380 60 342 418 40 145 70 50 32 145 45 460 60 414 508 34 120 60 45 27 120 41 575 60 518 632 28 96 45 35 22 96 33
230 50 198 253 58 200 100 70 46 200 63
380/415 50 342 440 34 115 60 45 27 115 41 208/230 60 187 253 79 207 345 125 100 63 207 345 98 98
380 60 342 418 47 104 173 80 60 37 104 173 52 52 460 60 414 508 38 104 173 60 45 30 104 173 42 45 575 60 518 632 30 72 120 50 40 24 72 120 33 37
230 50 198 253 67 150 250 110 80 53 150 250 80 80
380/415 50 342 440 38 104 173 60 45 30 104 173 44 44 208/230 60 187 253 107 268 446 175 150 85 268 446 124 124
380 60 342 418 60 134 223 100 80 48 134 223 70 70 460 60 414 508 54 134 223 90 70 43 134 223 52 60 575 60 518 632 42 98 164 70 50 33 98 164 42 52
230 50 198 253 85 205 342 150 110 68 205 342 98 98
380/415 50 342 440 54 134 223 90 70 43 134 223 60 60 208/230 60 187 253 119 304 506 200 150 95 304 506 144 144
380 60 342 418 67 152 253 110 80 53 152 253 80 80 460 60 414 508 54 152 253 90 70 43 152 253 66 66 575 60 518 632 44 106 176 70 60 35 106 176 50 52
230 50 198 253 94 220 366 150 125 75 220 366 112 112
380/415 50 342 440 54 152 253 90 70 43 152 253 66 66 208/230 60 187 253 167 414 690 300 200 133 414 690 204 204
380 60 342 418 95 207 345 150 125 76 207 345 106 106 460 60 414 508 78 207 345 125 100 62 207 345 95 98 575 60 518 632 63 165 276 110 80 50 165 276 73 76
230 50 198 253 135 327 545 225 175 108 327 545 166 166
380/415 50 342 440 78 207 345 125 100 62 207 345 98 98
UNIT COMPRESSOR (ea)
MCA
ICF
MFA
Rec
Fuse
RLA
LRA MTA
LEGEND FOR TABLES 4A AND 4B
ICF Maximum instantaneous current flow during starting. For these kcmil — Thousand circular mils
LRA — Locked rotor amps. First value is for part-wind start. Larger value MCA — Minimum circuit amps (for wire sizing). Complies with NEC, MFA — Maximum fuse amps (225% of compressor RLA). Size down to MTA — Must-trip amps (compressor circuit breaker).
NEC — National Electrical Code (U.S.A.)
1. All units have one field power terminal block.
2. Maximum incoming wire size:
3. Any field modification of factory wiring must be in compliance with all ap-
4. Usecopper,copper-clad aluminum, oraluminum conductors for field wiring.
5. For all30HW units, control circuit power supplyis 115-v singlephase for 50-
6. Across-the-line start is standard on all units. Part-wind start is available as
single-compressor units, ICF is the compressor LRA.
is the full LRA. Section 430-24. the next standard fuse size.
NOTES FOR TABLES 4A AND 4B
a. 350 kcmil for unit sizes 040-060; 208/230-3-60, 230-3-50, and 400-3-50
voltages.
b. 2/0 for all other unit sizes; all voltages. plicable codes. Field-installed power wires must be rated 75 C minimum.
and 60-Hz units. Control power is supplied by the factory-installed control transformer.Additional control circuit power is not required for 30HW units.
a factory-installed option on 025-060 sizes (not available on 018 size; spe­cial order option on 30HK,HL units).
PW Part wind Rec Fuse — Recommended dual element fuse amps (150% of
RLA Rated load amps XL Across the line
*Supply Range — Units are suitable for use on electrical systems where volt-
age suppliedto the unit terminalsis not below or abovethe listed range limits.
†Contact your local Carrier representative for part-wind details.
**Compressor no. 1/Compressor no. 2.
7. For all 30HK,HL units, control circuit MCA is 7.2, and control circuit MFA is
15. For 30HK,HL 60 Hz units, a separately-fused (15 amp maximum) 115v, single-phase, 60 Hz, power supply or accessory transformer is required. For 30HK,HL50 Hz units, a field-supplied, separately fused (15ampsmaxi­mum), 230 v, single-phase, 50 Hz power supply is required.
compressor RLA). Size up to the next standard fuse size.
(30HK, HL, HWA, HWB, (30HK, HL, HWA, HWB,
HWC 60 Hz Only) HWC 60 Hz Only)
21
FIELD POWER WIRING, 60 Hz UNITS FIELD CONTROL WIRING, 50 Hz UNITS
COM — Common CR Compressor Relay CWP — Chilled Water Pump DLS — Demand Limit Switch GCS — Ground Current Sensing NC Normally Closed NO Normally Open TB Terminal Block TC Temperature Control
NOTE: Manual lead/lag selector switch must be disconnected when using automatic lead/ lag accessory.
FIELD ACCESSORY WIRING
Fig. 17 — Field Wiring Diagram; 30HK, HL Units
22
LEGEND
Field Wiring Factory Wiring Accessory
NOTE: Factory wiring is in accordance with the National Electrical
Code (U.S.A.). Any field modifications or additions must be in com-
pliance with all applicable codes. Field installed power wires must be
rated 75° C minimum.
LEGEND
A—Alarm
C—Contactor, Compressor
COM Common
EQUIP — Equipment
GND Ground
NC Normally Closed
NO Normally Open
R—Relay
TB Terminal Block
TOR Torroid,Accessory Ground Fault
Interrupt
Field Wiring
Factory Wiring
Fig. 18 — Field Wiring Diagram; 30HW Units
23
PRI Primary (Transformer)
S—Suction
LEGEND
GCS — Ground Current Sensing
GND — Ground
SEC Secondary (Transformer)
SW Switch
T—Thermistor
TB Terminal Block
TC Temperature Control
HGS — Hot Gas Solenoid
HPS — High-Pressure Switch
LLSV — Liquid Line Solenoid Valve
LPS Low-Pressure Switch
NC Normally Closed
TDR Time Delay Relay
THERM — Thermistor
TRAN Transformer
NEC — National Electrical Code (U.S.A.)
NO Normally Open
OPS — Oil Pressure Switch
TSW Transfer Switch
U—Unloader
PL Plug
Fig. 19 — 30HK, HL Control Box
24
A—Alarm
C—Contactor
CB Circuit Breaker
CH Crankcase Heater
CM Control Module
COM Common
COMP — Compressor
CWFS — Chilled Water (Fluid) Flow Switch
CWP Chilled Water (Fluid) Pump
D—Discharge
DLS Demand Limit Switch
C—Contactor CB Circuit Breaker CM Control Module COM — Common CR Control Relay
Fig. 20 — 30HW Control Box Components Label
GCS Ground Current Sensor GND — Ground NC Normally Closed NEUT — Neutral NO Normally Open
LEGEND
SW Switch TB Terminal Block TDR Time Delay Relay THERM — Termistor TRAN Transformer
PRE-START-UP
IMPORTANT: Before beginning Start-Up, complete Start-Up Checklist on pages CL-1 to CL-4. This check­list assures proper start-up of a unit, and provides a record of unit condition, application requirements, sys­tem information, and operation at initial start-up.
ELECTRIC SHOCK HAZARD Open all disconnects before servicing this
equipment. There may be more than one disconnect.
Initial Check
IMPORTANT: Electrical power source must agree with unit nameplate rating. Do not start the chiller, even momentarily, until the following checks have been completed.
1. Check all auxiliary components, such as cooling tower (if used), chilled liquid and condenser water pumps, air­handling equipment, or other equipment to which the chiller supplies liquid. Consult manufacturer’s instructions.
2. Be sure flow switch is properly installed and set. See instructions packaged with flow switch accessory.
3. Set the temperature controller deadband as specified in Tables 5 and 6. Set point should be at the desired cooler leaving fluid temperature. Refer to Chilled Fluid Tem­perature Controller section on page 29 for additional dead­band setting information.
4. Backseat (open) compressor suction and discharge shut­offvalves. Crack open valves (one turn in) to allow some pressure to each test gage (if installed).
5. Backseat (open) liquid line shutoff valve(s).
6. Open valve to capillaries from fluid regulating valve (when used).
7. Fill chilled fluid liquid circuit with clean water or other noncorrosive fluid to be cooled. Bleed all air out of the high points of the system. Set flow rate according to job requirements. See Table 3. If the chilled water is to be maintained at a temperature below 40 F (4.4 C), a brine of sufficientconcentration must be used to prevent freeze-up at anticipated suction temperatures.
8. Open supply valve (or fill cooling tower, if used) for condenser water.
9. Check tightness of all electrical connections.
25
Table5—Typical Deadband Requirements
UNIT
CAPACITY
STEPS
2 1.3 (0.7) 2.5 (1.4) 3.8 (2.1) 3 0.8 (0.4) 1.7 (0.9) 2.5 (1.4) 4 0.6 (0.3) 1.3 (0.7) 1.9 (1.1)
COOLER DESIGN RANGE, F (C)
5.0 (2.8) 10.0 (5.6) 15.0 (8.3)
If there is no refrigerant vapor pressure in the system, the entire system must be leak tested.After repairing leaks, evacu­ate the system before recharging. Follow approved evacu­ation procedures when removing refrigeration. Release re­maining pressure to an approved evacuated cylinder.
The liquid charging method is recommended for com­plete charging or when additional charge is required.
Table 6 — Deadband Setting
MIN. REQUIRED DEADBAND
FC
0.5 to 1.5 0.28 to 0.83 1.0
2.0 1.11 2.0
2.5 1.39 2.5
3.0 1.67 2.8
3.5 1.94 3.0
4.0 2.22 3.7
4.5 2.50 4.0
DEADBAND SETTING (F)
10. Check compressor oil charge (should be visible in oil sight glass). Refer to Check Oil Charge section on page 27.
11. Be sure the compressor crankcase heater is warm (heater should be on for 24 hours before starting the compres­sor). The crankcase heater must be firmly locked into the compressor crankcase.
12. Be sure the compressor is floating freely on the com­pressor springs (see Step 4 — Check Compressor Mount­ing and Connections section on page 3).
13. For 30HL and HWAunits with remote condenser, check the condenser fans for correct rotation. See instructions shipped with the condenser.
14. Be sure the unit is fully charged with refrigerant (see Check Refrigerant Charge section below).
15. If unit is a brine unit, check to ensure proper brine con­centration is used to prevent freezing.
Check Refrigerant Charge
When adding or removing refrigerant charge, circulate water through condenser and cooler at all times to pre­vent freezing. Freezing damage is considered abuse and is not covered by Carrier warranty.
The 30HK, HWB, HWC, and HWS units are shipped with a full refrigerant charge (see Tables 1A-2B). However, if it is necessary to add refrigerant, operate the unit for some time at full capacity and then add charge until the sight glass is clear of bubbles. For maximum liquid subcooling, liquid level should be up to condenser end (30HK, HWC, HWS units only). This usually requires additional refrigerant charge be­yond the amount to clear sight glass.
The 30HL and HWAunits (condenserless) are shipped with a refrigerant holding charge only. After chiller assembly is completed in the field, system must be fully charged. While the unit is running at full capacity, add refrigerant until the sight glass is clear. R-22 is the normal refrigerant.
Do not open the liquid valve or the compressor discharge valve until there is a charge in remainder of system. A posi- tive pressure indicates a charge in system. With the unit op­erating at full load, check liquid line sight glass to be sure the unit is fully charged (bubbles in the sight glass indicate the unit is not fully charged).
Be careful not to overcharge the system. Overcharging results in higher discharge pressure with higher cooling water consumption, possible compressor damage, and higher power consumption.
LIQUID CHARGING METHOD — Add charge to the unit through the liquid line service valve. Never charge liquid
into the low-pressure side of the system.
1. Frontseat (close) condenser liquid line shutoff valve.
2. Connect a refrigerant cylinder loosely to the charging valve connection of the liquid line shutoffvalve. Purge the charg­ing hose and tighten the connections.
3. Open the charging valve.
4. If the system has been dehydrated and is under vacuum, break the vacuum with refrigerant gas. For R-22, build up system pressure to 58 psig and 32 F (400 kPa and 0° C). Invert the refrigerant cylinder so that the liquid refrigerant will be charged.
5. a. For complete charge of 30HK, HWB, HWC, and HWS
units, follow charging by weight procedure. When charge is nearly full, complete the process by observing the sight glass for clear liquid flow. The use of sight glass
charging is valid only when unit is operating at full capacity (no unloaders energized).
b. For complete charge of 30HL and HWAunits or where
refrigerant cylinder cannot be weighed, follow charg­ing by sight glass procedure. The use of sight glass
charging is valid only when unit is operating at full capacity (no unloaders energized).
6. a. The 30HL and HWA condenserless units are shipped
with a holding charge only.After installation with the field-supplied system high side, the complete system should be charged until the sight glass is clear (with the unit running at full capacity). To achieve maxi­mum system capacity, add additional charge equal to the difference between the condenser optimal charge and the condenser minimum charge, which can be ob­tained from the charge data provided in the condenser installation instructions.
b. To ensure maximum performance of 30HWB units,
raise the compressor saturated discharge temperature (SDT) to approximately 105 F (40.6 C) by throttling the condenser water intake. Add charge until there is approximately 15 to 17° F (8.3 to 9.4° C) of system subcooling (SDT minus actual temperature entering the thermostatic expansion valve).
c. Toensure maximum performance of 30HK, HWC, and
HWS units, raise the compressor saturated discharge temperature (SDT) to approximately 103 F (39.4 C) by throttling the condenser water intake. Add charge until there is approximately 8 to 10° F (4.4 to 5.6° C) for 30HK units or 12 to 14° F (6.7 to 7.8° C) for 30HWC, HWS units of system subcooling (SDT minus actual temperature entering the thermostatic expansion valve).
26
Check Oil Charge — The compressor(s) is factory-
charged with oil. If oil is visible in the compressor sight glass(es), check the unit for operating readiness as described in Initial Check section (page 25), then start the unit. Ob­serve oil level and add oil, if required, to bring the oil level in the compressor crankcase(s) to between1⁄8and3⁄8of the sight glass(es) during steady operation.
TO ADD OIL
1. Close the suction shutoff valve and pump the compressor crankcase down to between zero and 2 psig (zero to
13.8 kPa) (the low-pressure switch must be jumpered). Wait a few minutes and repeat as needed until the pres­sure remains between zero and 2 psig (zero to 13.8 kPa).
2. Close the discharge shutoff valve.
3. Remove the oil-fill plug above the compressor sight glass, add oil through the plug hole, and replace the plug.
4. After opening the suction and discharge service valves, remove low-pressure switch jumper, run the compressor for about 20 minutes, and check the oil level.
Use only Carrier-approved compressor oil:
Petroleum Specialties, Inc. ................Cryol 150*
Texaco, Inc. .........................Capella WF-32
Witco Chemical Co. .....................Suniso 3GS
*Factory charge.
Do not reuse drained oil, and do not use any oil that has
been exposed to the atmosphere.
TO REMOVE OIL
The crankcase will be under slight pressure. Be careful not to lose the entire oil charge. Gloves and eye pro­tection must be worn.
Pump down the compressor to between zero and 2 psig (zero to 13.8 kPa). Loosen the oil drain valve located in the compressor base to allow the oil to seep out past plug threads. Be careful not to remove plug; the entire oil charge may be lost. Small amounts of oil can be removed through oil pump discharge connection.
START-UP AND OPERATION
OperationChecks —
under supervision of an experienced refrigeration techni­cian. Refer to Start-Up Checklist on pages CL-1 to CL-4. Remove and save the checklist for future reference.
1. Crankcase heater must be energized for at least 24 hours
before the chiller is started.
2. Open all system valves that may have been closed during
or after charging.
3. Check air-handling equipment, chilled water (fluid) and
condenser pumps, and any other equipment connected to the chiller.
4. Start the unit by moving the ON-OFF switch to the ON
position.
5. Check all controls for proper operation. Follow Start-Up
Checklist procedures in these instructions.
6. Adjust the water regulating valve (where used) to obtain
the most economical head pressure (based on the relative cost of water and electricity). Head pressure is normally 200 to 230 psig (1379 to 1586 kPa) for 30HK,HL units, and 195 to 226 psig (1344 to 1558 kPa) for 30HW units when using R-22 refrigerant.
7. Check the cooler leaving chilled water temperature to see
that it remains well above 32 F (0° C), or the brine freez­ing point if the unit is a medium temperature brine unit.
Start-up should be performed only
8. Recheck compressor oil level (see Check Oil Charge sec­tion on this page). Add or remove oil to achieve the level required during steady operation.
Operating Limitations
Do not operate with cooler leaving chiller water (fluid) temperature (LCWT) below 40 F (4.5 C) for the stan­dard units, or below 15 F (−9.4 C) for units factory built for medium temperature brine.
HIGH COOLER LEAVING CHILLED WATER (FLUID) TEMPERATURES (LCWT) — During start-up with cooler LCWT above approximately 60 F (16 C), the unit expansion valve will limit suction pressure to approximately 90 psig (620 kPa) to avoid overloading the compressor.
LOW COOLER LCWT — For standard units, the LCWT must be no lower than 40 F (4.5 C). If the unit is the factory­installed optional medium temperature brine unit, the cooler LCWT can go down to 15 F (−9.4 C).
MAIN POWER SUPPLY — Minimum and maximum ac­ceptable supply voltages are listed in Tables 4A and 4B.
Unbalanced 3-Phase Supply Voltage — Never operate a mo-
tor where a phase imbalance between phases is greater than 2%. To determine percent voltage imbalance, see Unbal-
anced 3-Phase Supply Voltage section on page 19.
Check Refrigerant Feed Components
THERMOST ATICEXPANSION VALVE(TXV) — The TXV controls the flow of liquid refrigerant to the cooler by main­taining constant superheat of vapor leaving the cooler. There is one valve per refrigerant circuit. The valve(s) is activated by a temperature-sensing bulb(s) strapped to the suction line(s).
The valve(s) is factory-set to maintain between 8° and 10° F (4.4° and 5.6° C) of superheat leaving the cooler. Check the superheat during operation after conditions have stabi­lized. If necessary, adjust the superheat to prevent refriger­ant floodback to the compressor.
FILTER DRIER — The function of the filter drier is to main­tain a clean, dry system. The moisture indicator (described below) indicates any need to change the filter drier. The fil­ter drier is a sealed-type drier. When the drier needs to be changed, the entire filter drier must be replaced.
NOTE: The 30HK, HL units have 2 filter driers; one per circuit.
MOISTURE-LIQUID INDICATOR — The indicator is lo­cated immediately ahead of the TXV to provide an indica­tion of the refrigerant moisture content. It also provides a sight glass for refrigerant liquid. Clear flow of liquid refrig­erant (at full unit loading) indicates sufficient charge in the system. Bubbles in the sight glass (at full unit loading) in­dicate an undercharged system or the presence of noncon­densables. Moisture in the system, measured in parts per million (ppm), changes the color of the indicator as follows:
Blue (safe) — Moisture is below 45 ppm Light Violet (caution) — 45 to 180 ppm Pink (wet) — above 180 ppm
The unit must be in operation at least 12 hours before the moisture indicator gives an accurate reading, and must be in contact with liquid refrigerant. At the first sign of moisture in the system, change the corresponding filter drier.
NOTE: The 30HK, HL units have 2 indicators; one per circuit.
LIQUID LINE SERVICE VALVE — This valve provides a refrigerant charging port and, in combination with the com­pressor discharge service valve(s), allows the refrigerant to be pumped into the high side of the system.
27
DISCHARGE LINE CHECK VAL VE— On all 30HL, HWA units, a factory-supplied check valve is shipped with the unit (two valves are provided for 30HL units). The check valve(s) should be installed in the discharge line(s) downstream from, but close to, the compressor muffler. Install the valve in any position except bonnet down.
The check valve(s) prevents backwards-migration of re­frigerant from the condenser(s) to the compressor(s) and cooler during the compressor off cycle.
HOT GAS BYPASS VALVE — On units equipped with the factory-installed capacity reduction option (30HW only), a hot gas bypass valve is located between the discharge line and the cooler entering-refrigerant line. A solenoid valve is installed in the equalizer line of the hot gas valve to allow the temperature control to cycle the hot gas bypass function.
The amount of capacity reduction achieved by the hot gas bypass valve may be altered by adjusting the spring tension of the hot gas bypass valve. The total unit capacity should not be reduced below 10% of the nominal rating.
LIQUID LINE SOLENOID VALVE (30HL ONLY) — The solenoid valve closes when its circuit is inoperative, either from capacity control or from any safety trip.
PRESSURE RELIEF DEVICES — All 30HK, 30HL, and 30HW units are equipped with a compressor pressure relief valve located on the crankcase of the 06E compressor units (except for the 30HW018 units which have a compressor displacement less than 50 cfm). The pressure relief valve opens at 450 psig (3103 kPa).
The 30HK,HWC, and HWS units are also equipped with a high-side refrigerant pressure relief valve on the shell and tube condenser. The valve is set to open at the working pres­sure of the condenser, as shown in Table 7.
The 30HWB does not have a condenser pressure relief valve, because the brazed-plate condenser is not considered a pressure vessel, as defined in ANSI/ASHRAE 15 (Ameri­can National Standards Institute/American Society of Heat­ing, Refrigerating, and Air Conditioning Engineers) safety code requirements.
For 30HL and HWA condenserless units, pressure relief devices designed to relieve at 450 psig (3103 kPa), must be field-supplied and installed in the discharge line piping after the muffler in accordance with ANSI/ASHRAE 15 safety code requirements. Additional pressure relief valves, properly se­lected, must be field-supplied and installed to protect high side equipment and may be required by applicable codes.
Most codes require that a relief valve be vented directly to the outdoors. The vent line must not be smaller than the
relief valve outlet. The condenser relief valves have a
5
⁄8-in. SAE (Society of Automotive Engineers, U.S.A.) flare connec­tion. The compressor relief valves have a3⁄8-in. SAE Flare connection. Consult ANSI/ASHRAE 15 for detailed infor-
mation concerning layout and sizing of relief vent lines.
All units have a factory-installed fusible plug in the suc­tion line which relieves on a temperature rise at 170 F (77 C) and one in the liquid line which relieves at 210 F (99 C).
Table 7 — Pressure Relief Valve Settings
UNIT
30HK 385 2655
30HWC 365 2517
30HWS 335 2310
PRESSURE RELIEF VALVE SETTINGS
Psig kPa
Compressor and Unit Protective Devices
CIRCUIT BREAKER — There is a single circuit breaker per compressor in each unit. The circuit breaker(s) protects the compressor(s) against overloading, locked rotor condi­tions, and primary single phasing. If the circuit breaker(s) trips, determine the cause and correct it before resetting the breaker(s).
COMPRESSOR INTERNAL THERMALPROTECTION — On the 30HW018 units, there is a sensor imbedded in the compressor windings to detect an overtemperature condition.
The thermostat opens and shuts off the compressor if the discharge gas temperature exceeds 295 ± 5° F (146 ± 2.8° C). The thermostat will reset when the temperature drops to ap­proximately 250 F (121 C). However, the control module will keep the unit locked off until control power is manually cycled off, then back on.
NOTE: Compressor overtemperature protection for 30HK, HL units is accomplished by high and low pressure switches and circuit breakers which are external to the compressors.
CRANKCASE HEATER
Never open or disconnect any switch that energizes the crankcase heater, unless the unit is being serviced or will be shut down for an extended period. After service or shutdown, energize the crankcase heater for 24 hours before starting the compressor.
IMPORTANT: The crankcase heater is located in the bottom corner of the compressor and held in place by a bracket. The heater must be tight to prevent it from backing out of the heater well. The heater eventually burns out if exposed to the air for an extended period.
The heater in each compressor prevents absorption of liq­uid refrigerant by the compressor oil when the compressor is not operating. The heater is wired into the normally closed contacts of the compressor control relay so that it energizes only when the compressor is not operating. The heater is 125 w, 115 v on all 60 Hz units; 230 v on 50 Hz 30HK, HL units; and 115 v on 50 Hz 30HW units.
OILPRESSURE SAFETY SWITCH (OPS) — One OPS per compressor is standard on all 30HL and HWA units, and on all units equipped with the medium temperature brine op­tion. One is located in each compressor terminal box with capillaries to the crankcase and oil pump. The switch is also offeredasan accessory (part number 30HW900006) for stand­ard 30HK, HWB, HWC, and HWS units. When used, the OPS is monitored by the unit control module. If at any time after the compressor is started, the OPS is open for more than 2 minutes, the compressor shuts down and is locked off until control power is manually cycled to OFF, then back to the ON position. The OPS cuts out at5±1psig (34.5 ±
6.9 kPa), and has a maximum cut-in of 9.5 psig (65.5 kPa).
Check Unit Safeties
CONTROL MODULE — The unit control module is lo­cated in the control section of the control box. See Fig. 19 and 20. It performs several functions. The control module has a built-in compressor anti-short-cycle timer which will not allow a compressor to restart until 5 minutes have elapsed since the previous shutdown.
On 30HL and HWA units (and 30HK, HWB, HWC, and HWS units equipped with the oil pressure safety switch [OPS] accessory), the compressor oil pressure and low-pressure switch(es) (LPS) are monitored through the control module. The unit is allowed to remain operational as long as the OPS and/or LPS have not been open for more than 2 minutes af­ter a compressor has started.After start-up, if the OPS and/or LPS are open for more than 2 minutes, the control module shuts down the compressor and places the unit in a lockout condition. The control module activates the fault indication circuit, and the unit service lamp is illuminated. The unit cannot be restarted until control power is manually cycled to OFF, then to ON.
28
The control module also monitors the high-pressure switch(es) and compressor internal thermal protection (30HW). If at any time one or both of these switches opens, the con­trol module shuts down the compressor and places the unit in a lockout condition. The control module activates the fault indication circuit, and the unit service lamp is illuminated. The unit cannot be restarted until control power is manually cycled to OFF, then to ON.
If the unit shuts down on an automatic reset switch, such as the temperature controller, the compressor will be al­lowed to restart when the switch closes and the control mod­ule anti-short-cycle time has elapsed.
For Servicing Only — To speed up the 5-minute anti-short cycle, a jumper may be placed between terminals T1 and T6 of the control module.
This jumper must be removed after servicing is complete. Failure to remove this jumper is considered abusive treat­ment and will void the Carrier warranty.
HIGH-PRESSURE SWITCH — A high-pressure switch is provided to protect each compressor and refrigeration sys­tem from unsafe high pressure conditions. See Table 8 for high-pressure switch settings.
The high-pressure switch is mounted in the discharge side of each compressor.A snubber is provided between the com­pressor discharge manifold and the high-pressure switch to prevent pressure pulsations from damaging the switch.
If an unsafe, high-pressure condition should exist, the switch opens and shuts off the affectedcompressor.The unit control module prevents the unit from restarting. The unit will not restart until control power is manually cycled off, then on.
To check operation of the switch, slowly close the com­pressor discharge shutoff valve until the compressor shuts down. The switch should open at the pressure corresponding to the appropriate switch setting as shown in Table 8.
Table 8 — Factory Settings, High-Pressure Switch
(Fixed)
UNIT
30
HK, HWS 280 ± 10 1931 ± 69 180 ± 20 1241 ± 138
HL, HWB, HWC 375 ± 10 2585 ± 69 275 ± 20 1896 ± 138
HWA 395 ± 10 2723 ± 69 298 ± 20 2054 ± 138
CUTOUT CUT-IN
Psig kPa Psig kPa
Reopen the compressor discharge shutoff valve, and cycle the unit ON-OFF switch to OFF, then ON. The unit should restart after the compressor anti-short-cycle delay, built into the unit control module, expires.
LOW-PRESSURESWITCH —Alow-pressure switch is pro­vided to protect each compressor and system from a loss of refrigerant. The low-pressure switch(es) also provides freeze protection for the cooler. The low-pressure switch(es) is non­adjustable. See Table 9 for low-pressure switch settings. One switch is used for standard units, and a different switch is used for units with the brine option.
Table 9 — Factory Settings, Low-Pressure Switch
(Fixed)
T ocheckoperation of the low-pressure switch, slowly close the suction service valve and allow the affected compressor to pump down. The compressor should cut out when the suc­tion pressure falls below the low-pressure switch cutout set­ting. Open the suction service valve. The compressor should restart after the low-pressure switch closes, and the com­pressor anti-short-cycle delay expires.
CHILLED FLUID TEMPERATURECONTROLLER — All units are equipped with a temperature controller (see Fig. 21) which is capable of controlling up to 4 steps of ca­pacity. A thermistor installed inside the cooler supplies the input to the controller. The temperature controller can op­erate a system with cooling ranges (entering cooler fluid tem­perature minus leaving cooler fluid temperature) of 5° to 15° F (2.8° to 8.3° C), and with a range of set points from 40 to 60 F (4.4 to 15.5 C) for standard units, and 15 to 39 F (−9.4 to 3.9 C) for units with the medium temperature brine option.
The set point of the temperature controller should be ad­justed to the desired leaving cooler fluid temperature, and verified by using a thermometer placed in the leaving-cooler piping. The amount of deadband around the set point value is adjusted through the use of the deadband adjustment knob on the temperature controller.See Tables 5 and 6 for the cor­rect setting of the deadband.
The unit should then control the average leaving-fluid tem­perature to this setting. If the leaving-fluid temperature does not correspond to the desired set point, slightly readjust the controller set point knob until the desired leaving-fluid tem­perature is obtained. The temperature controller has an ad­justable 30-second (HI position) to 3-minute (LO position) sample rate knob. The sample rate knob should always be set at LO position (fully clockwise) for 30HK, HL units, and at HI position (fully counterclockwise) for 30HW units.
Do not force the knob dials past the stops. This could cause loss of control point and damage to the controller.
UNIT
TYPE
STANDARD 42±3 290±21 57±5 393±34
BRINE 27±3 186±21 44±5 303±34
CUTOUT CUT-IN
Psig kPa Psig kPa
LEGEND
COM — Common NC Normally Closed NO Normally Open
Fig. 21 — Temperature Controller
29
If rapid cycling of the capacity steps occurs, the deadband setting is too low and should be raised to the point that rapid cycling will cease.
If a cooler design range other than those shown in Table 5 is desired, determine the setting by using the fol­lowing formula and Table 6:
Minimum Required Unit Deadband: Minimum Deadband = (Cooler Design D
(2 x no. of Capacity Steps)
= F (C)
The lights on the temperature controller will indicate the status of the control. If the green light labeled ABOVE SET POINT is illuminated, the controller will add steps of ca­pacity, if additional steps are available. If the yellow light labeled BELOW SET POINT is illuminated, the controller removes steps of capacity.
The temperature controller also has a red light labeled OUT OF RANGE that indicates the system load was reduced faster than the controller could remove stages. If this occurs, the unit shuts down to avoid cooler freeze-up.
Once the temperature rises back into the control band, the unit restarts automatically. This also occurs if the therm­istor fails in the open mode. In the case of a thermistor fail­ure, the unit does not restart until the thermistor is replaced.
FREEZE-UP PROTECTION
On medium temperature brine units, the brine must be properly mixed to prevent freezing at a temperature of at least 15 F (8.3 C) below the leaving-fluid temperature set point. Failure to provide the proper brine mixture is considered abuse and may void the Carrier warranty.
All units have the following 2 modes of freeze-up protection.
1. Thetemperature controller protects the system from freeze-up
due to rapid loss of load and from low fluid flow by rap­idly removing all steps of capacity and shutting down the compressor if an out-of-range condition exists. This nor­mally occurs if the leaving-fluid temperature drops 6 to 7° F (3.3 to 3.9° C) below the temperature controller set point. Set point range is 40 to 60 F (4.4 to 15.6 C) for standard units and 15 to 39 F (−9.4 to 3.9 C) for units with medium temperature brine option.
2. The low-pressure switch provides a back-up cooler freeze-up
protection system. The low-pressure switch shuts down the unit when the suction temperature drops to a point where the cooler will freeze up.
LOSS-OF-COOLER-FLOW PROTECTION — A proof-of­cooler-flow device (accessory flow switch) must be used with all 30HK, HL, HW chillers. The device should be a differ­ential pressure type device and should be set to shut the unit off if cooler gpm drops below 1.5 times the nominal unit tonnage. Carrier accessory flow switch, part number 30HW900003 is available for this purpose. See page 19 and Fig. 17 and 18.
COMPRESSOR GROUND FAULTSENSOR— The ground fault sensor accessory (Part No. 30HW900004) monitors all
phases of the 3-phase power supply to the compressor. If a short to ground is sensed by the sensor, the compressor au­tomatically shuts down. This prevents contamination of the refrigeration system from acid formation. The compressor shuts down when a 2.5 ± 2 amps ground current is sensed by a toroid installed around the compressor power leads. The unit control module locks the compressor off until the circuit power is cycled to OFF, and then ON. For installation de­tails, see the instructions included with the accessory package.
NOTE: Two accessory packages are required for 30HK, HL units.
UNIT OPERATION
Capacity Control and Operating Sequence —
The 30HW units have a multiple-step temperature control­ler, factory set to maintain capacity control through leaving chilled fluid temperature. The controller has 4 capacity steps. All 30HK, HL units have 4 capacity steps as standard. The 30HW018 and 028-040 units have 3 steps as standard, with a fourth step available as a factory-installed option. The 30HW025 units have 2 steps of capacity as standard with a third step available as a factory-installed option. All units have electric solenoid operated unloaders. See Tables10 and 11 for capacity control steps of each unit.
At initial start-up, assume that all safety devices are sat-
isfied and there is a call for cooling. 30HK,HL UNITS — Close the compressor circuit breaker
and turn the ON-OFF switch to the ON position.
In approximately 5 minutes, the lead compressor starts and the unloaders are energized (compressor unloads when com­pressor unloader solenoid is energized). On 30HL units, the liquid line solenoid valve will remain closed for the first 10 seconds of compressor operation. The low-pressure and oil pressure switches are bypassed for 2 minutes. At the end of the 2-minute bypass period, the low-pressure and oil pres­sure switches are active in the control circuit.
Approximately 30 seconds (high setting) or 3 minutes (low setting) later, depending on the sample rate setting, the lag compressor starts and the unloaders are energized (compres­sor unloads when compressor unloader solenoid is ener­gized). On 30HL units, the liquid line solenoid valve will remain closed for the first 10 seconds of compressor opera­tion. The low-pressure and oil-pressure switches are by­passed for 2 minutes. At the end of the 2-minute bypass pe­riod, the low-pressure and oil-pressure switches are active in the control circuit.
Approximately 30 seconds (high setting) or 3 minutes (low setting) later, depending on the sample rate setting, the lead compressor is loaded (unloader solenoids deenergized).
Approximately 30 seconds (high setting) or 3 minutes (low setting) later, depending on the sample rate setting, the lag compressor is loaded (unloader solenoids deenergized).
When the load is satisfied and the leaving fluid tempera­ture falls below the set point, the last stage activated is dropped immediately. If the leaving fluid temperature still remains below the set point, then the control drops an additional stage every 30 (high setting) or 180 (low setting) seconds, de­pending on the sample rate setting.
30
Once the compressor is shut off, the control system pre­vents the compressor from restarting within 5 minutes of when it was last shut down. Once this period has elapsed and the leaving fluid temperature rises above the set point, the com­pressor will start within 5 seconds.
If the unit is equipped with field-installed hot gas bypass, the hot gas bypass valve opens only when stage 1 is active.
If the unit trips out on high pressure, low pressure, ground current (accessory), or low oil pressure, the control module locks the unit off and must be manually reset (turn the ON­OFF switch to OFF and then back to ON). If the unit trips out on low fluid temperature, chilled fluid flow switch, or chilled fluid pump switch, it restarts automatically when the condition is corrected.
30HW UNITS — Close the compressor circuit breaker and move ON-OFF switch to the ON position. The switch should light up. In approximately 3 seconds, the compressor starts unloading. For 2 minutes the low-pressure switch is bypassed and the unloaders are energized (compressor un­loads when compressor unloader solenoid is energized). At end of 2-minute bypass period, the low-pressure switch ac­tivates the control circuit and the temperature controller regu­lates the capacity steps based on leaving cooler fluid tem­perature, set point and deadband settings on the temperature controller.
Table 10 — Capacity Control Steps — 30HK, HL Standard Units
If system load drops to the point where the unit is fully unloaded and the fluid temperature is below the lower dead­band limit, the compressor shuts off and is not able to restart until the 5-minute anti-short cycle has expired. If during nor­mal operation, the fluid temperature rises above the upper deadband limit, the temperature controller adds a step of ca­pacity (assuming a step is left to be added).
On condenserless units (30HWA),or on fluid-cooled units (30HWB,C, and S) equipped with the accessory oil safety switch, the control module provides a 2-minute bypass of the oil safety switch.
If the unit is equipped with hot gas bypass option, the hot gas bypass valve closes before unloaders are deactivated.
If the unit trips out on high pressure, ground current (ac­cessory), or low oil pressure, the control module locks the unit off and must be manually reset (by turning the ON-OFF switch to OFF, then back to ON). If the unit trips out on low pressure, low fluid temperature, the chilled fluid flow switch, or the chilled fluid pump switch, it restarts automatically when the condition is corrected.
UNIT
30HK040
30HK,HL050
30HK,HL060
LEGEND
Ckt Circuit Disp. — Displacement
CONTROL
TRANSFER SWITCH COMPRESSOR
STEPS
1 25 2 2 25 2 2 2 50 4 2 2 50 4 2 2 3 75 6 4 2 75 6 2 4 4 100 8 4 4 100 8 4 4
1 40 4 4 20 2 2 2 60 6 4 2 60 6 4 2 3 80 8 6 2 80 8 4 4 4 100 10 6 4 100 10 6 4
1 33 4 4 33 4 4 2 66 8 4 4 66 8 4 4 3 8810 6 4 8810 4 6 4 100 12 6 6 100 12 6 6
%
Disp.
NO. 1 POSITION*
Operating Cylinder
Total Ckt 1 Ckt 2 Total Ckt 1 Ckt 2
*Manually operated. NOTE: Circuits are designated from left to right when viewed from front of unit.
TRANSFER SWITCH COMPRESSOR
%
Disp.
NO. 2 POSITION*
Operating Cylinder
31
Table 11 — Capacity Control Steps —
30HW Standard Units
UNIT CAPACITY CONTROL CAPACITY OPERATING
30HW STEPS* % CYLINDERS
018
025
028
035
040
*Factory-installed hot gas bypass option adds an additional capacity
step to that shown in this table.
1 33.3 2 2 66.7 4 3 100.0 6
1 50.0 2 2 100.0 4
1 33.3 2 2 66.7 4 3 100.0 6
1 33.3 2 2 66.7 4 3 100.0 6
1 33.3 2 2 66.7 4 3 100.0 6
SERVICE
ELECTRIC SHOCK HAZARD To avoid the possibility of electrical shock,
turn off all power to unit before servicing.
Do not attempt to bypass, short-out, or modify the con­trol circuit or electronic boards in any way to correct a problem. This could result in component failures or a hazardous operating condition.
Compressor Replacement — If a replacement
6-cylinder compressor has a center-bank cylinder head with discharge valve pad facing the pump end, remove head and install reverse flange head from original compressor (dis­charge valve pad toward the motor end). Center-bank cyl-
inder head cannot be rotated 180 degrees.
Be sure all the hardware from the old compressor is removed and installed on the new compressor, including the high-pressure switch snubber, the discharge gas thermo­stat (30HW025-040), the oil pressure safety switch (if equipped), and the low-pressure switch.
The compressor can be removed from either the front or the sides of the unit, depending on where clearance space was allowed during unit installation. The compressor and mount­ing hardware are mounted on a plate which is screwed down to the unit basepan. Remove the 4 screws holding the plate to the basepan and the plate should easily slide out of the unit. Mount the replacement compressor to the plate, slide the plate back into the unit and secure with the 4 screws.
CircuitBreaker(s) — The breaker(s) provides 3-leg over-
load protection. Do not bypass connections or increase the size of the circuit breaker(s) to correct trouble. Determine the cause of the trouble and correct it before resetting the breaker(s).Atripped breaker must be manually reset by mov­ing the circuit breaker handle to OFF, then ON position. See Tables 4A and 4B for must-trip amps (MTA).
NOTE: One circuit breaker is provided per compressor.
Brazed-Plate Cooler and Condenser Heat Ex­changer Replacement —
ers cannot be repaired if they develop a leak. If a leak (re­frigerant or water) develops, the heat exchanger must be replaced. To replace a brazed plate heat exchanger:
1. Disconnect the liquid-in and liquid-out connections at the heat exchanger.
2. Check that the replacement heat exchanger is the same as the original heat exchanger. For the condensers, compare part numbers on the heat exchangers. For the coolers, in­sulation covers the manufacturer’s part number.Make sure the depths of the replacement and original cooler heat ex­changers are the same.
3. Reclaim the refrigerant from the system, and unsolder the refrigerant-in and refrigerant-out connections.
1
4. Remove the four to the brackets. Save the nuts.
5. Install the replacement heat exchanger in the unit and attach to the bracket using the four in Step 4.
6. Carefully braze the refrigerant lines to the connections on the heat exchanger.Lines should be soldered using silver as the soldering material with a minimum of 45% silver. Keep the temperature below 1472 F (800 C) under nor­mal soldering conditions (no vacuum) to prevent the cop­per solder of the brazed plate heat exchanger from changing its structure. Failure to do so can result in internal or external leakage at the connections which cannot be repaired.
7. Reconnect the water/brine lines.
8. Dehydrate and recharge the unit. Check for leaks.
⁄2-in. nuts holding the heat exchanger
Brazed-plate heat exchang-
1
⁄2-in. nuts removed
Brazed-Plate Cooler and Condenser Heat Ex­changerCleaning —
be cleaned chemically.Aprofessional cleaning service skilled in chemical cleaning should be used. Use a weak acid (5% phosphoric acid, or if the heat exchanger is cleaned fre­quently,5% oxalic acid). Pump the cleaning solution through the exchanger, preferably in a backflush mode. After clean­ing, rinse with large amounts of fresh water to dispose of all the acid. Cleaning materials must be disposed of properly.
The mesh screens in front of the water/brine inlets of the heat exchangers should be cleaned periodically, depending on condition of the chiller water/brine.
Brazed-plate heat exchangers must
Shell-and-Tube Condenser Cleaning— The shell-
and-tube condenser tubes can be cleaned either mechani­cally or chemically. To clean them chemically, follow the procedure described in Brazed-Plate Cooler and Condenser Heat Exchanger Cleaning section above.
To clean the condenser tubes manually:
1. Order tubing brushes (Carrier part no. KC21AH105).
2. Close the valves on the condenser and relieve condenser
water pressure. BE SURE TO PROVIDE DRAINAGE TO PREVENT WATER DAMAGE.
3. Remove the condenser heads and brush the tubes clean,
removing scale and other deposits.
4. Inspect the head gaskets and replace if necessary.
5. Clean all gasket surfaces prior to reassembly.
6. Replace the water heads and torque the head bolts to
90 ft-lb (122 N-m). Allow the gaskets to set overnight and re-torque the bolts to ensure proper sealing.
32
Thermistor— The resistance at various temperatures for
the thermistor are given in Tables 12A and 12B. THERMISTOR REPLACEMENT, 30HK, HL UNITS
Thermistors are installed directly in fluid circuit. Drain fluid before removing.
Proceed as follows (see Fig. 22):
1. Remove and discard original thermistor and coupling.
IMPORTANT:Do not diassemble new coupling. In­stall as received.
2. Apply pipe sealant to1⁄4-in. NPT threads on replacement coupling and install in place of original. Do not use a pack­ing nut to tighten coupling. This damages the ferrules (see Fig. 22).
3. Insert thermistor T1 into coupling body to its full depth. Tighten packing nut finger tight to position ferrules, then tighten 1
1
⁄4turns more using a back-up wrench. Ferrules are not attached to the sensor, which can be withdrawn from coupling for service.
THERMISTOR REPLACEMENT, 30HW UNITS — To re­place the thermistor, follow these steps:
1. Disconnect the existing thermistor from the S1 and S2 terminals of the temperature controller (located in the con­trol section of the control box).
2. Remove the thermistor from the well in the cooler leaving­fluid cacity.
3. Insert the replacement thermistor into the thermistor well.
4. Run thermistor wires into the control box and connect to the S1 and S2 terminals of the temperature controller.
Fig. 22 — Thermistor
33
Table 12A — Sensor Temperature (F) vs Resistance
TEMPERATURE RESISTANCE
(F) (OHMS)
-25 98,010
-24 94,707
-23 91,522
-22 88,449
-21 85,485
-20 82,627
-19 79,871
-18 77,212
-17 74,648
-16 72,175
-15 69,790
-14 67,490
-13 65,272
-12 63,133
-11 61,070
-10 59,081
-9 57,162
-8 55,311
-7 53,526
-6 51,804
-5 50,143
-4 48,541
-3 46,996
-2 45,505
-1 44,066 0 42,678 1 41,339 2 40,047 3 38,800 4 37,596 5 36,435 6 35,313 7 34,231 8 33,185 9 32,176
10 31,201 11 30,260 12 29,351 13 28,472 14 27,624 15 26,804 16 26,011 17 25,245 18 24,505 19 23,789 20 23,096 21 22,427 22 21,779 23 21,153 24 20,547 25 19,960 26 19,392 27 18,843 28 18,311 29 17,796 30 17,297 31 16,814 32 16,346 33 15,892 34 15,453 35 15,027 36 14,614 37 14,214 38 13,826 39 13,449 40 13,084 41 12,730 42 12,387 43 12,053 44 11,730 45 11,416 46 11,111 47 10,816 48 10,529 49 10,250 50 9,979 51 9,717 52 9,461 53 9,213 54 8,973 55 8,739 56 8,511 57 8,291 58 8,076 59 7,868 60 7,665 61 7,468 62 7,277
TEMPERATURE RESISTANCE
(F) (OHMS)
63 7,091 64 6,911 65 6,735 66 6,564 67 6,399 68 6,237 69 6,081 70 5,929 71 5,781 72 5,637 73 5,497 74 5,361 75 5,229 76 5,101 77 4,976 78 4,855 79 4,737 80 4,622 81 4,511 82 4,403 83 4,298 84 4,195 85 4,096 86 4,000 87 3,906 88 3,814 89 3,726 90 3,640 91 3,556 92 3,474 93 3,395 94 3,318 95 3,243 96 3,170 97 3,099 98 3,031
99 2,964 100 2,898 101 2,835 102 2,773 103 2,713 104 2,655 105 2,598 106 2,542 107 2,488 108 2,436 109 2,385
110 2,335 111 2,286 112 2,238 113 2,192 114 2,147 115 2,103 116 2,060 117 2,018 118 1,977
119 1,937 120 1,898 121 1,860 122 1,822 123 1,786 124 1,750 125 1,715 126 1,680 127 1,647 128 1,614 129 1,582 130 1,550 131 1,519 132 1,489 133 1,459 134 1,430 135 1,401 136 1,373 137 1,345 138 1,318 139 1,291 140 1,265 141 1,239 142 1,214 143 1,189 144 1,165 145 1,141 146 1,118 147 1,095 148 1,072 149 1,050 150 1,028
TEMPERATURE RESISTANCE
(F) (OHMS)
151 1,007 152 986 153 965 154 945 155 925 156 906 157 887 158 868 159 850 160 832 161 815 162 798 163 782 164 765 165 749 166 734 167 719 168 705 169 690 170 677 171 663 172 650 173 638 174 626 175 614 176 602 177 591 178 581 179 570 180 560 181 551 182 542 183 533 184 524 185 516 186 508 187 501 188 494 189 487 190 480 191 473 192 467 193 461 194 456 195 450 196 444 197 439 198 434 199 429 200 424 201 419 202 415 203 410 204 405 205 401 206 396 207 391 208 386 209 382 210 377 211 372 212 366 213 361 214 356 215 350 216 344 217 338 218 332 219 325 220 318 221 311 222 304 223 297 224 289 225 282
34
Table 12B — Sensor Temperature (C) vs Resistance
TEMPERATURE RESISTANCE
(C) (OHMS)
-32.0 100 049
-31.5 97 006
-31.0 94 061
-30.5 91 209
-30.0 88 449
-29.5 85 777
-29.0 83 191
-28.5 80 687
-28.0 78 264
-27.5 75 918
-27.0 73 648
-26.5 71 451
-26.0 69 324
-25.5 67 265
-25.0 65 272
-24.5 63 344
-24.0 61 477
-23.5 59 670
-23.0 57 921
-22.5 56 228
-22.0 54 589
-21.5 53 003
-21.0 51 467
-20.5 49 980
-20.0 48 541
-19.5 47 148
-19.0 45 799
-18.5 44 492
-18.0 43 228
-17.5 42 003
-17.0 40 817
-16.5 39 668
-16.0 38 556
-15.5 37 478
-15.0 36 435
-14.5 35 424
-14.0 34 444
-13.5 33 495
-13.0 32 576
-12.5 31 685
-12.0 30 821
-11.5 29 984
-11.0 29 173
-10.5 28 386
-10.0 27 624
- 9.5 26 884
- 9.0 26 168
- 8.5 25 472
- 8.0 24 798
- 7.5 24 144
- 7.0 23 509
- 6.5 22 893
- 6.0 22 296
- 5.5 21 716
- 5.0 21 153
- 4.5 20 606
- 4.0 20 076
- 3.5 19 561
- 3.0 19 061
- 2.5 18 575
- 2.0 18 103
- 1.5 17 645
- 1.0 17 199
- 0.5 16 766
0.0 16 346
0.5 15 937
1.0 15 539
1.5 15 153
2.0 14 777
2.5 14 412
3.0 14 057
3.5 13 711
4.0 13 375
4.5 13 048
5.0 12 730
5.5 12 420
6.0 12 119
6.5 11 826
7.0 11 541
7.5 11 263
8.0 10 992
8.5 10 729
9.0 10 472
9.5 10 223
10.0 9 979
10.5 9 742
11.0 9 512
11.5 9 287
12.0 9 068
12.5 8 855
13.0 8 647
13.5 8 444
14.0 8 247
14.5 8 055
15.0 7 868
15.5 7 685
TEMPERATURE RESISTANCE
(C) (OHMS)
16.0 7507
16.5 7334
17.0 7165
17.5 7000
18.0 6840
18.5 6683
19.0 6531
19.5 6382
20.0 6237
20.5 6096
21.0 5959
21.5 5825
22.0 5694
22.5 5566
23.0 5442
23.5 5321
24.0 5203
24.5 5088
25.0 4976
25.5 4867
26.0 4760
26.5 4656
27.0 4555
27.5 4457
28.0 4360
28.5 4267
29.0 4175
29.5 4086
30.0 4000
30.5 3915
31.0 3832
31.5 3752
32.0 3674
32.5 3597
33.0 3523
33.5 3450
34.0 3379
34.5 3310
35.0 3243
35.5 3177
36.0 3113
36.5 3051
37.0 2990
37.5 2931
38.0 2873
38.5 2816
39.0 2761
39.5 2707
40.0 2655
40.5 2603
41.0 2553
41.5 2504
42.0 2457
42.5 2410
43.0 2364
43.5 2320
44.0 2276
44.5 2234
45.0 2192
45.5 2152
46.0 2112
46.5 2073
47.0 2035
47.5 1997
48.0 1961
48.5 1925
49.0 1890
49.5 1856
50.0 1822
50.5 1789
51.0 1757
51.5 1725
52.0 1694
52.5 1663
53.0 1634
53.5 1604
54.0 1575
54.5 1547
55.0 1519
55.5 1492
56.0 1465
56.5 1438
57.0 1412
57.5 1387
58.0 1362
58.5 1337
59.0 1313
59.5 1289
60.0 1265
60.5 1242
61.0 1219
61.5 1197
62.0 1175
62.5 1153
63.0 1132
63.5 1111
TEMPERATURE RESISTANCE
(C) (OHMS)
64.0 1090
64.5 1070
65.0 1050
65.5 1030
66.0 1011
66.5 992
67.0 973
67.5 955
68.0 937
68.5 919
69.0 902
69.5 885
70.0 868
70.5 852
71.0 836
71.5 820
72.0 805
72.5 790
73.0 775
73.5 761
74.0 746
74.5 733
75.0 719
75.5 706
76.0 693
76.5 681
77.0 669
77.5 657
78.0 645
78.5 634
79.0 623
79.5 613
80.0 602
80.5 592
81.0 583
81.5 573
82.0 564
82.5 556
83.0 547
83.5 539
84.0 531
84.5 524
85.0 516
85.5 509
86.0 502
86.5 496
87.0 489
87.5 483
88.0 477
88.5 472
89.0 466
89.5 461
90.0 456
90.5 451
91.0 446
91.5 441
92.0 436
92.5 432
93.0 427
93.5 423
94.0 419
94.5 415
95.0 410
95.5 406
96.0 402
96.5 398
97.0 393
97.5 389
98.0 385
98.5 380
99.0 376
99.5 371
100.0 367
100.5 362
101.0 357
101.5 352
102.0 346
102.5 341
103.0 335
103.5 330
104.0 324
104.5 318
105.0 312
105.5 305
106.0 299
106.5 292
107.0 285
35
SERVICING COOLER (30HK,HL ONLY)
NOTE: The cooler on 30HW units is not serviceable.
When cooler heads and partition plates are removed, tube
sheets are exposed showing tube ends as shown in Fig. 23.
Four tubes in the bundle are secured inside cooler at baffles and cannot be removed. These are identified on the tube sheets by a drill mark horizontally adjacent to each of the 4 tubes. See Fig. 23. If leakage occurs in any of these
tubes, plug as described in Tube Plugging section below.
Tube Plugging — Leaky tube(s) can be plugged until
retubing can be done. The number of plugged tubes deter­mines how soon the cooler must be retubed. If several tubes require plugging, check with your local Carrier representa­tive to find out how number and location will affect unit capacity.
Figure 24 shows an Elliott tube plug and a cross-sectional view of a plug in place. Table 13 lists the components for plugging.
Use extreme care when installing plugs to prevent dam­aging the tube sheet sections between holes.
Clean parts with Locquic ‘‘N’’solution (or equivalent) and apply a few drops of Loctite No. 675 sealant (or equivalent) to obtain a tight seal without using too much force to set the pin.
Usually plugs can be removed by heating the projecting end of pin to approximately 1000 F (538 C) and chilling quickly with water.Apply heating flame to side of the pin to prevent overheating tube sheet.
RETUBING (See Table 13) — When retubing is to be done, obtain the service of qualified personnel experienced in boiler maintenance and repair.Most standard procedures can be fol­lowed when retubing the 10HA coolers. A 6% crush is rec­ommended when rolling replacement tubes into the tube sheet. A6% crush can be achieved by setting the torque on the gun at 48 to 50 in.-lb (780 to 815 N-m).
*
*
The following Elliott Co. tube rolling tools are required:
B3400 Expander Assembly B3401 Cage B3405 Mandrel B3408 Rolls
Place one drop of Loctite No. 675 sealant (or equivalent)
on top of the tube prior to rolling. Tube information:
in. mm
• Tube sheet hole diameter ............0.631 16.03
•TubeOD ......................0.625 15.87
• Tube ID after rolling ..............0.581 14.76
(includes expansion due to to to clearance) 0.588 14.94
IMPORTANT:Tubes next to gasket webs must be flush with tube sheet (both ends).
Tightening Cooler Head Bolts
GASKET PREPARATION — When reassembling, use new gaskets. Compressed non-asbestos/neoprene gaskets (Carrier Material Specification ZA00-32) are to be momen­tarily dipped in compressor break-in oil prior to assembly.
Do not soak gaskets in oil, as gasket deterioration results. Use dipped gaskets within 30 minutes to prevent deteriora­tion.
BOLT TORQUES — Apply the following torques during bolt tightening sequence described below:
5
⁄8-in. 16-mm) diameter flange
bolts .............150to170ft-lb (203 to 230 N-m)
1
⁄2-in. (13-mm) diameter center-stud
nuts ................70to90ft-lb (95 to 122 N-m)
Bolt Tightening Sequence (Fig. 25) — The recommended bolt tightening sequence is:
Step 1 — Tighten all
1
⁄2-in. (13-mm) center nuts finger tight.
Step 2 — Following sequence shown in Fig. 25, tighten the bolts and nuts to approximately 50% of specified torque.
Step 3 — Starting at top (12 o’clock) tighten flange bolts to specified torque (see Bolt Torques section on this page) con­secutively in a clockwise direction.
Step 4 — Tighten center nuts to specified torque. Step 5 — No less than one hour later, retighten center nuts. Step 6 — After refrigerant is restored to cooler, check center
studs and exposed gasket edges for refrigerant leaks with soap solution or a Halide device.
Table 13 — Plugs and Tubes
5
⁄8-in. (16-mm) flange bolts and
*
*Fourfixedtubes(cannot be removed) identified by adjacentdrillpoints.
Fig. 23 — Typical Tube Sheet
*
COMPONENTS FOR
PLUGGING
For Tubes
Brass Pin 853103-500* Brass Ring 853002-570*
For Holes without Tubes
Brass Pin 853103-1*
Brass Ring 853002-631* Loctite No. 675† Locquic ‘‘N’’†
*Order directly from Elliott Tube Co., Dayton, Ohio. †Can be obtained locally.
36
PART NUMBER
Fig. 24 — Elliott Tube Plug
HEAD BOLT TIGHTENING SEQUENCE
Fig. 25 — Typical Tube Sheet
TROUBLESHOOTING
Complete Unit Stoppage and Restart —
sible causes for unit stoppage and reset methods are (also see Table 14):
GENERAL POWER FAILURE — After power is restored, restart is automatic through the normal timer cycle.
UNIT ON-OFF SWITCH IS OPEN — When the switch is opened, the unit stops immediately. If the switch is closed immediately after it was opened, the unit restarts automati­cally after the 5-minute timer cycle is completed. If the switch is closed after an extended off-period, the unit restarts au­tomatically in approximately 3 seconds.
CONTACTS OF ANY AUXILIARY INTERLOCKS ARE OPEN — After the problem has been corrected, restart is automatic after completion of the 5-minute timer cycle.
CHILLED FLUID PROOF-OF-FLOW SWITCH(ES) OPEN — After the problem causing the loss of flow has been cor­rected, restart is automatic after completion of the 5-minute timer cycle.
OPEN LOW-PRESSURESWITCH— If a low-pressure switch remains open for more than 2 minutes during unit operation, the compressor(s) shuts down and is locked off.The unit ser­vice light is illuminated. Determine and correct the cause of the failure. The switch automatically resets, but the unit must be manually reset by cycling the unit control power (move the ON-OFF switch to OFF, then to ON). The unit restarts
Pos-
after completion of the 5-minute timer cycle unless the re­frigerant charge is either very low or lost. If this is the case, determine the cause of the loss of charge, correct the prob­lem, and recharge the unit before restarting.
TEMPERATURE CONTROLLER SHUTS UNIT DOWN ON OUT-OF-RANGE (See Fig. 21) — Check the ther­mistor for an open circuit failure. See Tables 12A and 12B for temperature-resistance values. If thermistor is damaged, replace it. If thermistor is not damaged, the unit restarts automatically after completion of the 5-minute timer cycle, and after the leaving cooler chilled fluid temperature rises above the upper deadband limit of the temperature controller.
OPEN HIGH-PRESSURE SWITCH(ES) — The unit ser­vice light is illuminated. Determine and correct the cause of the failure. The switch(es) automatically resets but the unit must be manually reset by cycling the control power (move ON-OFF switch to OFF, then back to ON). The unit restarts after completion of 5-minute timer cycle.
OPEN COMPRESSOR INTERNALTHERMAL PROTEC­TION (30HW UNITS) — This is compressor overtempera­ture protector on 30HW018 units and the discharge gas ther­mostat (DGT) on 30HW025-040 units. The unit service light is illuminated. Determine and correct cause of problem. The switch resets automatically but unit must be reset by cycling the control power (move ON-OFF switch to OFF, then back to ON). The unit restarts after completion of 5-minute timer cycle.
OPEN OIL PRESSURE SWITCH — If oil pressure switch(es) opens for more than 2 minutes during unit operation, the unit shuts down and is locked off. The unit service light is illu­minated. Determine and correct cause of failure. Unit must be reset by cycling the control power (move ON-OFF switch to OFF, then back to ON). Unit restarts after completion of 5-minute timer cycle.
OPEN CONTACTS ON COMPRESSOR GROUND­CURRENT SENSOR(S) (Accessory) — The light-emitting diode (LED) on the ground current accessory board (located in field control wiring section of control box) is illuminated. See Fig. 17-20. Unit service light is also illuminated. Check
the compressor motor windings for a short to ground.
Determine and correct cause of the failure. The unit must be reset by cycling the control power (move ON-OFF switch to OFF, then back to ON). Unit restarts after completion of the 5-minute timer cycle.
OPEN 24-V CONTROL CIRCUIT BREAKER(S) — De­termine the cause of the failure and correct. Reset circuit breaker(s). Restart is automatic after completion of 5-minute timer cycle.
37
COOLING LOAD SATISFIED — Unit shuts down if cool­ing load is satisfied. Unit restarts if required after comple­tion of 5-minute timer cycle.
THERMISTORFAILURE— If thermistor fails in open mode, the temperature controller shuts down the unit in an out-of­range condition. Replace the thermistor. Unit restarts auto­matically after completion of a 5-minute timer cycle, and when the leaving cooler chilled fluid temperature rises above the upper deadband limit of the temperature controller.
Table 14 — Troubleshooting
SYMPTOMS CAUSE REMEDY
Compressor does not run
Compressor cycles off on loss of charge
Compressor cycles off on out of range condition
Compressor cycles control steps rapidly
Compressor shuts down on high­pressure control
Unit operates too long or continuously
Unusual or loud system noises
Power line open Reset circuit breaker. Control fuse or circuit breaker opens Check control circuit for ground or short. Reset breaker
Compressor overtemperature sensor open Find cause of high temperature and reset controls. Tripped power breaker Check the controls. Find the cause of trip and
Condenser circulating pump not running Power off — restart.
Loose terminal connection Check connections. Improperly wired controls Check wiring and rewire if necessary. Low line voltage Check line voltage — determine location of voltage drop
Compressor motor defective Check motor winding for open or short. Replace Seized compressor Replace compressor.
Loss of charge control erratic in action Repair leak and recharge.
Low refrigerant charge Add refrigerant. Low suction temperature Raise cooler leaving fluid temperature set point. Compressor suction valve leaking Replace valve plate. Plugged compressor suction strainer Clean or replace strainer. Compressor suction shutoff valve partially closed Open valve. Thermistor failure Replace thermistor. System load was reduced faster than
controller could remove stages Temperature controller deadband setting is
too low High-pressure control acting erratically Replace control. Compressor discharge valve partially closed Open valve or replace (if defective). Air in system Purge system. Condenser scaled/dirty Clean condenser. Receiver not properly vented — refrigerant
backs up into evaporator condenser Condenser water pump or fans not operating Start pump — repair or replace if defective. System overcharged with refrigerant Reduce charge. Low refrigerant charge Add refrigerant. Control contacts fused Replace control. Air in system Purge system. Partially plugged or plugged expansion valve
or filter drier Defective insulation Replace or repair as needed. Service load Keep doors and windows closed. Inefficient compressor Check valves, and replace if necessary. Piping vibration Support piping as required.
Expansion valve hissing Add refrigerant.
Compressor noisy Check valve plates for valve noise.
NOTE: If the thermistor fails in closed mode, the tempera­ture controller keeps trying to load up.
If unit stoppage occurs more than once as a result of any of the safety devices listed, determine and correct cause before attempting another restart.
and replace fuse.
reset breaker.
Pump binding — free pump. Incorrect wiring — rewire. Pump motor burned out — replace.
and remedy deficiency. compressor if necessary.
Replace control.
Unit will restart after fluid temperature rises back into the control band. Avoid rapidly removing system load.
Raise deadband setting.
Repipe as required to provide adequate venting.
Clean or replace as needed.
Check for loose pipe connections.
Check for plugged liquid line filter drier.
Replace compressor (worn bearings). Check for loose compressor holddown bolts.
38
Table 14 — Troubleshooting (cont)
SYMPTOMS CAUSE REMEDY
Compressor loses oil
Hot liquid line Shortage of refrigerant due to leak Repair leak and recharge. Frosted liquid line Shutoff valve partially closed or restricted Open valve or remove restriction.
Frosted suction line Expansion valve admitting excess refrigerant Adjust expansion valve. Replace valve if defective. Compressor will
not unload
Compressor will not load
System noises Piping vibration Support piping as required.
Freeze-up Improper charging Make sure a full quantity of fluid is flowing through the
Leak in system Repair leak. Mechanical damage (blown piston or broken
discharge valve) Oil trapped in line Check piping for oil traps. Crankcase heater not energized
during shutdown
Restricted filter drier Replace filter drier.
Burned-out coil Replace coil. Defective capacity control valve Replace valve. Miswired solenoid Rewire correctly. Weak, broken, or wrong valve body spring Replace spring. Miswired solenoid Rewire correctly. Defective capacity control valve Replace valve. Plugged strainer (high side) Clean or replace strainer. Stuck or damaged unloader piston or piston ring(s) Clean or replace the necessary parts.
Expansion valve hissing Add refrigerant.
Compressor noisy Check valve plates for valve noise.
Improperly set safety thermostat Check safety thermostat for proper setting at beginning of Operating with safety thermostat bypassed If thermostat was bypassed for checking, be sure it is back Improper circulation of condenser water Use adequately sized cleanable strainer in the condenser
System not drained for winter shutdown Remove drain plugs at end of cooling season. Blow out any
Loose Thermistor Tighten thermistor to pipe and reinsulate (30HW).
Repair damage or replace compressor as needed.
Check wiring and crankcase heater contacts on the temperature controller, and replace heater if necessary.
Check for loose pipe connectors.
Check for plugged liquid line strainer.
Replace compressor (worn bearings). Check for loose compressor holddown bolts.
cooler while charging, and suction pressure in cooler is equal to or greater than pressure corresponding to 32 F (0° C) (58 psig [400 kPa] for Refrigerant 22).
each season. in circuit before starting unit. water circuit. Make sure strainer is clean. It may sometimes
be necessary to chemically treat the water to prevent for­mation of deposits.
residual water. Instead of draining, a suitable anti-freeze may be added to the water.
ing is considered abuse and is not covered by warranty.
Damage to chiller due to freez-
39
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equip­ment discussed in this manual, including:
• Unit Familiarization
• Installation Overview
A large selection of product, theory, and skills programs are available, using popular video-based for­mats and materials. All include video and/or slides, plus companion book.
Classroom Service Training which includes ‘‘hands-on’’ experience with the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks. Course descriptions and schedules are in our catalog.
CALL FOR FREE CATALOG 1-800-962-9212
[ ] Packaged Service Training [ ] Classroom Service Training
• Maintenance
• Operating Sequence
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-070 Printed in U.S.A. Form 30H-10SI Pg 40 11-98 Replaces: 30H-8SI
START-UP CHECKLIST FOR CHILLER SYSTEMS
(Remove and use for job file)
A. Preliminary Information
JOB NAME LOCATION INSTALLING CONTRACTOR DISTRIBUTOR START-UP PERFORMED BY
EQUIPMENT: Chiller: MODEL # SERIAL # COMPRESSORS:
CIRCUIT #1 CIRCUIT #2 (30HK,HL ONLY)
MODEL # SERIAL # SERIAL # MOTOR # MOTOR #
CONDENSER (30HK, HWB, HWC, HWS ONLY):
MODEL # SERIAL #
COOLER:
MODEL # SERIAL # DATE
MANUFACTURED BY
MODEL #
AIR-HANDLING EQUIPMENT:
MANUFACTURER MODEL # SERIAL # ADDITIONAL AIR-HANDLING UNITS AND ACCESSORIES
B. Preliminary Equipment Check (YES or NO)
IS THERE ANY SHIPPING DAMAGE?
WILL THIS DAMAGE PREVENT UNIT START-UP? CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions) ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? (refer to Installation Instructions) HAS THE GROUND WIRE BEEN CONNECTED? ARE ALL TERMINALS TIGHT? ON 30HW UNITS, IS THE THERMISTOR SECURELYSTRAPPED TO THE COOLER LEAVING CHILLED FLUID LINE, AND
IS IT PROPERLY INSULATED? ON 30HW UNITS, IS YELLOW WIRE GOING TO TRANSFORMER 1 (POWER TRANSFORMER) ON THE CORRECT
TERMINAL (TERMINAL H2 FOR 208 V AND 575 V; TERMINAL H3 FOR 230 V, 380 V, AND 400 V, TERMINAL H4 FOR 460 V)?
IF UNIT IS A MEDIUM TEMPERATURE BRINE UNIT, IS TEMPERATURE CONTROLLER SET FOR BRINE AND NOT FOR WATER? IF UNIT IS NOT A BRINE UNIT, IS TEMPERATURE CONTROLLER SET FOR WATER AND NOT FOR BRINE?
HAVE TEMPERATURE CONTROLLER, CONTROL MODULE AND CONTROL RELAY CONNECTIONS BEEN CHECKED FOR TIGHTNESS?
IF SO, WHERE
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-070 Printed in U.S.A. Form 30H-10SI Pg CL-1 11-98 Replaces: 30H-8SI
B. Preliminary Equipment Check (YES or NO) (cont)
HAVE POWER SIDE ELECTRICAL COMPONENT CONNECTIONS BEEN CHECKED FOR TIGHTNESS? ON 30HK,HL UNITS, IS THE PROPER CONTROL VOLTAGE SUPPLIED TO TB2-1 AND TB2-3? ON 30HK,HL 50 HZ UNITS, IS THE BLACK WIRE GOING TO TRAN1 AND TRAN2 CONNECTED TO THE RED LEAD FROM
THE TRANSFORMER? CHECK AIR SYSTEMS (YES OR NO)
ARE ALL AIR HANDLERS OPERATING? ARE ALL CHILLED FLUID VALVES OPEN? IS THE FLUID PIPING CONNECTED PROPERLY? HAS ALL AIR BEEN VENTED FROM THE COOLER LOOP? IS THE CHILLED WATER (FLUID) PUMP (CWP) OPERATING? IS THE CWP ROTATION CORRECT? CWP MOTOR AMPERAGE: Rated
(refer to air-handling equipment Installation and Start-Up Instructions)
Actual
C. Unit Start-Up (insert check mark as each item is completed)
HAS THE CHILLER BEEN PROPERLY INTERLOCKED WITH THE AUXILIARY CONTACTS OF THE CONDENSER WATER PUMP STARTER?
ASSURE THAT UNIT IS SUPPLIED WITH CORRECT CONTROL VOLTAGE POWER. ASSURE CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR A MINIMUM OF 24 HOURS PRIOR TO
START-UP. ASSURE COMPRESSOR OIL LEVEL IS CORRECT. ASSURE LIQUID LINE SERVICE VALVE(S) IS BACKSEATED. ASSURE COMPRESSOR DISCHARGE SERVICE VALVE(S) IS BACKSEATED. ASSURE COMPRESSOR SUCTION SERVICE VALVE(S) IS BACKSEATED. LOOSEN COMPRESSOR SHIPPING ISOLATOR LOCKNUTS. OPEN GAGE PANEL SERVICE VALVES. BE SURE TEMPERATURE CONTROLLER DEADBAND AND SAMPLE RATE SETTINGS ARE SET. SET POINT SHOULD BE ADJUSTED TO THE DESIRED COOLER LEAVING FLUID TEMPERATURE. (refer to installation
instructions) LEAK CHECK THOROUGHLY: COMPRESSOR(S), CONDENSER FITTINGS, TXV(s), SOLENOID VALVE(S), FILTER
DRIER(S), FUSIBLE PLUG(S), AND COOLER HEAD(S), WITH GENERAL ELECTRIC H-10-B ELECTRONIC LEAK DETECTOR.
LOCATE, REPAIR, AND REPORT ANY R-22 LEAKS.
CHECK VOLTAGE IMBALANCE: AB AC BC AB + AC + BC (divided by 3) = AVERAGE VOLTAGE = V MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =
VOLTAGE IMBALANCE = x 100 = % VOLTAGE IMBALANCE IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START CHILLER!
CALL LOCAL POWER COMPANY FOR ASSISTANCE. ASSURE THAT INCOMING POWER VOLTAGE TO CHILLER IS WITHIN RATED UNIT VOLTAGE RANGE.
SYSTEM FLUID VOLUME IN LOOP: TYPE SYSTEM: AIR CONDITIONING — MINIMUM 3 GAL. (3.25 L) PER NOMINAL TON (kW) = PROCESS COOLING — MINIMUM 6 GAL. (6.5 L) PER NOMINAL TON (kW) =
(MAX. DEVIATION)
AVERAGE VOLTAGE
GAL. (L)
GAL. (L)
CL-2
C. Unit Start-Up (cont)
COOLER LOOP PROTECTION IF REQUIRED:
GALLONS (LITERS) OF BRINE ADDED: PIPING INCLUDES ELECTRIC TAPE HEATERS.
CHECK PRESSURE DROP ACROSS COOLER.
FLUID ENTERING COOLER: FLUID LEAVING COOLER: (PSIG DIFFERENCE) x 2.31 = FT OF FLUID PRESSURE DROP = (kPa DIFFERENCE) x .335 = FT OF FLUID PRESSURE DROP = PLOT COOLER PRESSURE DROP ON PERFORMANCE DATA CHART (LOCATED IN PRODUCT DATA LITERATURE)TO
DETERMINE TOTAL GPM (L/s). TOTAL GPM (L/s) = GPM (L/s) PER TON = UNIT’S RATED MIN. PRESSURE DROP =
JOB’S SPECIFIED GPM (L/s) (if available) NOTE: IF UNIT HAS LOW FLUID FLOW,FIND SOURCE OF PROBLEM: CHECK FLUID PIPING, IN-LINE FLUID STRAINER,
SHUT-OFF VALVES, CHILLED FLUID PUMP ROTATION, ETC.
COOLER LOOP PROTECTION:
GAL. (L) OF BRINE ADDED (IF REQUIRED). IN-LINE WATER STRAINER INSTALLED ADJACENT TO COOLER FLUID INLET. (REQUIRED FOR 30HW COOLERS.)
PSIG (kPa) PSIG (kPa)
UNIT’S RATED MIN. GPM (L/s) =
(Refer to product data literature.)
YES NO
CONDENSER PROTECTION:
IN-LINE MINIMUM 20-MESH STRAINER INSTALLEDADJACENT TO THE CONDENSER WATER INLET. YES
TO START THE CHILLER: (insert check mark as each item is completed) PLACE ON-OFF SWITCH IN THE ON POSITION. ASSUMING THERE IS A CALL FOR CHILLED FLUID, THE COMPRESSOR WILL START UNLOADED AFTER A6-SECOND
TO 5-MINUTE DELAY (DEPENDING ON THE TIMING LOGIC). THE LOW-PRESSURE SWITCH (ALL UNITS)AND OIL-PRESSURE SWITCH (30HL, HWAUNITS — ACCESSORYON 30HK,
HWB, HWC, HWS UNITS) ARE BYPASSED FOR 2 MINUTES. IF ADDITIONAL CAPACITY IS REQUIRED AFTER THE 2-MINUTE PERIOD, COMPRESSOR WILL LOAD UP.
MEASURE THE FOLLOWING: WHILE MACHINE IS IN STABLE OPERATING CONDITION. SUCTION PRESSURE SUCTION LINE TEMP. SUCTION SUPERHEAT DISCHARGE PRESSURE DISCHARGE LINE TEMP. DISCHARGE SUPERHEAT
NO
CHECK AND ADJUST SUCTION SUPERHEAT (9 to 11 F [5 to 6 C]).
CL-3
NOTES:
Copyright 1998 Carrier Corporation
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 2 Tab 5c
PC 903 Catalog No. 533-070 Printed in U.S.A. Form 30H-10SI Pg CL-4 11-98 Replaces: 30H-8SI
Loading...