Carrier 30HH User Manual

Carrier

30HH,HJ
r-
Installation and
30
(o
Maintenance Instructions
in ¡n
\r.
4111111 y I
Jiy nil|FilJ
B
■as
HERMETIC RECIPROCATING
<a
LiaUIO CHILLING PACKAGE
0
Carrier Corporation 1964
LItbo m L’«S.A.
Tab
IS
12-62
INSTALLATION

CONTENTS

PAGE
STALLATION SECTION Dimension Drawings
Preliminary Survey Moving and Placing Unit Unit Specifications
Compressor Physical Data Condenser Physical Data Cooler Physical Data Refrigerant Circuits
Refrigerant Charge Compressor Mounting Condenser Water Piping Cooler Water Piping Refrigerant Piping Leak Testing Dehydrate the System Start-up Procedures Charge with Refrigerant Oil Charge Check the Controls Starters and Overloads Circuit Breakers Water Regulating Valve Temperature Controller Adjustment Wiring Diagrams Electrical Data Capacity Controls 34-35 Sequence of Operation Moisture and Liquid Indicator
3-5
6
6-7
7-10
7 8 9
10 10 10
11-13
14
15-16
17 17-18 18-20 20-21
21
21-23
23
23-24
24 24-26 27-32 33-34
35-36
37
Carrier
AINTENANCE SECTION
Condenser Maintenance 38-39 Trouble Diagnosis Chart Compressor Maintenance Cause and Prevention of Freeze-up
40-42
42 42
INSTALLATION
30HH,HJ
LEFT SiDE VIEW
NOTES;
1. CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR 30HH MODEL ONLY.
2. REMOVABLE PANELS FURNISHED ON UN IT AS FOLLOWS'. ONE PANEL EACH SIDE, PANELS FRONT AND BACK OF COOLER SECTION, PANELS OVER FRONT OF COMPR., STEP CONT AND CONTROL CENTER SECTIONS.
3. SIDE PANELS PROVIDED WITH HOLES FOR CHILLED WATER PIPING.
FRONT VIEW
. TWO HOLES PROVIDED IN REAR PANEL OF CONTROL
BOX FOR CONTROL AND AUXILIARY WIRE ACCESS. CONTROL BULB OF TEMPERATURE CONTROLLER TO
BE FIELD INSTALLED IN INLET CHILLED WATER LINE. STANDARD CON T ROL VOLTAGE IS 230 VOLTS FOR 208,
230 aAOOVOLT UNITS FOR 460 a 575 VOLT UNITS STANDARD CONTROL VOLTAGE IS 115 VOLTS.

Fig. 1 - 30HH,HJ015 Dimensiona! Data

NOTES;
I. CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR
30HH MODEL ONLY.
2 REMOVABLE PANELS FURN ISHED ON UNIT AS FOLLOWSlONE
PANEL EACH SI DE, PANELS FRONT AND BACK OF COOLER
. TWO HOLES PROVIDED IN REAR PANEL OF CONTROL
BOX FOR CONTROL AND AUXILIARY WIRE ACCESS.
. CONTROL BULB OF TEMPERATURE CONTROLLER TO
BE FIELD INSTALLED IN INLET CHILLED WATER LINE.
I
.
I
LEFT SIDE VIEW
FRONT VIEW
Fig. 2 - 30HH,HJ020 Dimensional Data
30HH,HJ INSTALLATION
Carrier
SEE NOTE !
2”FPT water
OUTLET -
CONDENSERS FOR 30HH030
-------------------
CONDENSERS FOR 30HH025
I 2 FPT WATER
INLET—-.,
I2 FPT WATER
OUTLET—
FPT WATER
INLET
NOTES;
I CONDENSER ANDATTACHED PIPING AS SHOWN ARE FOR
30 HH MODEL ONLY.
2. REMOVABLE PANELS FURNfSHEO ON UNITAS FOLLOWS. ONE PANEL EACHSIDE, PANELS FRONT AND BACK OF COOLER
SECTION, PANELS OVER FRONTOF COM PR., STEP CONT AND CONTROL CENTER SECTIONS.
SIDE PANELS PROVIDED WITH HOLES FOR CHILLED WATER PIPING.,,,
COND.
MPT WATER INLET
CONDENSER
(SEE NOTE I )
V..y V
CONTROL BOX
CIRCUIT BREAKERS' y •
COMPR. OVERLOAD RESET BUTTON -
4 TWO HOLES PROVIDED IN REAR PANEL OF CONTROL
BOX FOR CONTROL AND AUXILIARY WIRE ACCESS.
5. CONTROLSULB OF TEMPERATURE CONTROLLER TO BE FIELD INSTALLED IN INLET CHILLEDWATER LINE.
6. STANDARD CONTROL VOLTAGE IS23OV0LTS F0R208. 230 9 400V0LT UNITS. FOR 460 S 575 VOLT UNITS STANDARD CONTROL VOLTAGE IS 115 VOLTS.
STEP CONTROLLER
DISCH CONN.iHJ ONLY) HJ025- I OD HJ030- IffOD___________
SAFETY THERMOSTAT RESET BUTTON
2 DIA. HOLE ELECTRIC
CONN.
_
IDE VIEW
NOTES:
1 CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR
30HH MODEL ONLY.
2 REMOVABLE PANELS FURNISHED ON UNIT AS FOLLOWS: ONE
PANEL EACH SIDE, PANELS FRONT AND BACKOF COOLER SECTION, PANELS OVER FRONT OF COMPR, STEP CONT. AND CONTROL CENTER SECTIONS.
3 SIDE PANELS PROVIDED WITH HOLES FOR CHILLED WATER
PIPING.
FRONT VIEW
Fig. 3 - 30HH,HJ025,030 Dimensional Data
TWO HOLES PROVIDED IN REAR PANEL OF CONTROL
BOX FOR CONTROL AND AUXILIARY WIRE ACCESS.
. CONTROL BULB OF TEMPERATURE CONTROLLER TO
BE FIELD INSTALLED IN INLET CHILLED WATER LINE. STANDARD CONTROL VOLTAGE IS 230 VOLTS FOR
208,230 5 400 VOLT UNITS FOR 460 5 575 VOLT UNITS STANDARD CONTROL VOLTAGE IS 115 VOLTS.
h 5''— 2 ^
I' o.D. LIQUID LINE
Fig, 4 - 30HH,HJ045 Dimensional Data
Carrier
INSTALLATION 30HH,HJ
notes:
1. CONDENSER AND ATTACHED PIPING AS SHOWN ARE FOR 30HH MODEL ONLY.
2. REMOVABLE PANELS FURNISHED ON UNIT AS FOLLOWS. ONE PANEL EACH SIDE, PANELS FRONT AND BACK OF COOLER
SECTION, PANELS OVER FRONT OF COMPR., STEP CONT. AND CONTROL CENTER SECTIONS.
3. SIDE PANELS PROVIDED WITH HOLES FOR CHILLED
WATER PIPING.

Fig. 5 - 30HH055 Dimensional Data

4. TWO HOLES PROVIDED IN REAR PANEL OF CONTROL BOX FOR CONTROL AND AUXILIARY WIRE ACCESS
5. CONTROL BULB OF TEMPERATURE CONTROLLER TO BE FIELD INSTALLED IN INLET CHILLED WATER LINE.
6. STANDARD CONTROL VOLTAGE IS 230 VOLTS FOR 208, 230 8 400 VOLT UNITS FOR 460 8575 VOLT
UNITS STANDARD CONTROL VOLTAGE IS 115
VOLTS.
-3’’DIA.H0LE FOR ELECTRICAL CONN LOCATED IN REAR OF CIRCUIT BREAKER CABINET
Fig. 6 - 30HH,HJ055 Dimensional Data
30HH,HJ
INSTALLATION
PRELIMINARY SURVEY
Before installation is started, a survey should be made to establish the procedures and ma terials required by installation personnel. See cover picture for typical unit.

Storage

Because of the sensitive control mechanisms and electrical devices incorporated in the 30HH,HJ units, they should not be exposed to the weather.

Location

Always locate the unit indoors. In order to pre vent freezing, the unit must be located in a space where the temperature is at least 40 degrees.

Space Requirements and Clearance

Dimensions for the units are given in Table 1.
These dimensions are useful in checking door
clearances for moving the unit in and for deter mining space requirements. A clearance of 2 to
3 feet should be left on each side and on the ends for piping and electrical connections and also to facilitate service operations. Clearance at one end of the unit, equal to the length of the unit, for servicing and removal of chiller tubes must be provided.

Adequate Floor Strength

Approximate weights of units are given in Table
1. Make certain that the floor is strong enough
to support this weight. If necessary, add sup porting structure to the floor for transferring
weight to the nearest beams. This can be done with steel beams or reinforced concrete slabs.

Vibration Isolation

Rubber-in-shear vibration insulators and muf flers are installed on, or furnished with, the compressors of all units beginning with early
1961 production. The inter-connecting piping must be sufficiently flexible to prevent vibra tion transmission, if vibration still exists, vi bration isolators may be used on the unit itself. The field-purchased vibration mountings should be placed under each corner of the package. The weight distribution of all packages except the 30HH015 and 30HJ015 is such that each corner mounting supports one fourth of the operating weight. The weight distribution of the 30HH015 and 30HJ015 units is 55-45 side to side and sym metrical front to back.
All phases of vibration isolation are fully de
scribed in Section 5X-1 of the Product Infor mation book. Consult same for best results.
For additional information see "Compressor Mounting."

MOVING AND PLACING UNIT

Moving

The skids on which the unit is mounted should
not be removed until the unit is at the final loca tion. When handling the unit with a chain hoist,
remove the panels so that they will not be dam
aged by the sling. Do not attach the sling to
Table 1 - Weight and Overall Dimensions - 30HH.HJ Liquid Chiller Package
Shipping
Unit
30HH015 30HH020 30HJ015 1270 ЗОН] 020 30HH025 2200 30HH030 2550 30H]025 30HJ030 2150 30HH045 30HJ045 2455 30HH055 4622 30HH065 4700 30HJ065 3700
Wt. (lbs.)
1430 2200
1700
2100
3010
Operating Wt. (lbs.)
1625 2150 1460 1800 1950 1950 1800 1850 3391 79-1/4 29-1/4 2835 5158 5236 4236
Uncrated Dimensions (Ins.)
Length
72 72 72 72 72 72 22-1/2 72 72 25-1/2
•79-1/4 105-1/4 105-1/4 105-1/4
Crated Dimensions (Ins.)
Width Height
22-1/2 54-3/4 76 30 63 22-1/2 22-1/2 47 25-1/2 47 22-1/2 54-3/4
25-1/2 47
29-1/4 66 83-1/2 33 29-1/4 80-3/8 29-1/4 29-1/4
54-3/4 76
54-3/4
47 79 83-1/2 33
80-3/8 Ó6
Length
76 76 30 76 30 76 30 76 76
109-3/4 33 109-3/4 33 109-3/4
Width Height
30 63 30
30 63
30 63
33
63 63 63 63
84-7/8 84-7/8 86-3/4 86-3/4 86-3/4
Carrier
INSTALLATION
piping or equipment. Move the unit in an upright position, and let it down gently from the truck or rollers. On 30HH,HJ015-030 units the sling can be placed under the frame channels at the main support (Fig. 7). On 30HH,HJ045 thru 065 units, the sling can be placed under the skids.

Placing

To anchor the equipment;
1. Locate the hold down bolts as shown in the dimension drawings. The areas where the four corners will be located should be ap proximately level before the unit is placed.
2. Set the unit in place and level with a spirit level on the frame channels.
3. Bolt the unit to the floor. This is usually de sirable for basement or ground floor instal lations that can transmit vibration to the ground without affecting the building struc
ture.
30HH,HJ
Fig. 7 - Rig Sling to Hoist Unit
(015-030 Shown)
Table 2 - Compressor Motor Physical Data
Unit Size
Compressor Type
Number
Sizes
Cylinder (Total No.)
Speed - 60 Cycle (rpm) 1750 1750 1750
- 50 Cycle (rpm) 1460 1460
Oil Charge (10 pt per compr) (pr) 10 20 20 20
Cylinder Unloading Devices (No.) t 2 1 1 1
*6D7 3 Compressors are used on rhe 30HH models
only. 30HJ Models are supplied with 6D75 com pressors.
30HH, H]
0J5
1 - 6D73» 2 - 6D68 1 - 6D68
6
30HH, H]
020
2 2 2 3 4
12 12 12 18 24
30HH, HJ
025
1 - 6D73*
1460
t Each cylinder unloading device unloads two cylinders
of the compressor when it is energized.
30HH, HJ
030
Hermetic Reciprocating
2 - 6D73* 3 - 6D73* 1 - 6D68
1750 1750 1460
30HH, HJ
1460 1460 1460
045
30 40 40
30HH
055
3 - 6D73
1750
30HH, HJ
4 - 6D73*
065
4
24
1750
1
30HH/HJ INSTALLATION
Table 3 - Condenser Physical Data
Carrier
Unit Size
Condensers (No.)
Condenser Type
Tubes or Coils, each
Effective External Surface, each (sq ft)
Water Side Volume, each (gal)
Nominal Shell Diam (in.)
Shell Length (in.)
Water Connections (Total No.)
Water Connection Size (each cond. )
Coil or Tube Type
Coil or Tube OD (in.)
Nominal Shell Thickness (in.)
Materials
of
Construction
Max. Design Working Press, (psig)
Inlet
Outlet
Shell Coil or Tubes Tube Sheet
Water Side Refrig. Side
30HH015
1
6
82.7
3.5
10-15/16 10-15/16 10-15/16 10-15/16
42-5/8
2 4
1 - 2"
1 - 2"
30HH020
2
4
53.9
2.5
34-5/8
2 - 1-1/2”
2 - 1-1/2"
30HH025
2 2
Shell-and-Coil
1 - 6 1 - 4
1-53.9 1 - 82.7
1 - 2.5 1 - 3.5
1 - 34-5/8 1 - 42-5/8
4 4
1 - 1-1/2” 1 - 2"
1 - 1-1/2" 1 - 2"
Trufin
7/8 3/4
.278
Steel Steel
Copper Copper
Steel Steel
100
385
30HH030
6
82.7
3.5
42-5/8 42-5/8 77 77
2 - 2"
2 - 2” 3 - 2"
30HH045 30HH055
3
6
82.7
3.5
10-15/16
2 4
3 - 2"
2
Sheil-anc -Tube
64 64
165.7 165.7
5.0
10-3/4 10-3/4
2 - 2"
2 - 1-1/2"
Trufin
.307
100 385
30HH065
2
5.0
3
1 - 3"
2 - 2”
Г'
NOTE: The 30HH065 unit is supplied with two subcooiers (one per circuit) to provide 15 F of subcooling.
m
INSTALLATION 30HH,HJ
Tabie 4 - Cooler Physical Data
Unit Size
Refrigerant Circuits (No.)
Tubes (No.) 136
Effective External Tube Surface (sq ft)
Length Between Tube Sheets (in.)
Shell Side Water Volume (gal) 20.4
Baffles (No.)
Baffle Spacing (in.)
Nominal Shell Diam. (in.)
Water Connection Size, IPS (in.)
Cooler Type
Construction
Tube Type and Size (in.) Prime Surface, 3/4 OD
Nominal Shell Thickness (in.) 1/4
Nominal Tube Sheet Thickness (in.)
30 HH, HJ
015
1
125
60-1/4
31
1-7/16
14
2
30HH, HJ
020
2
136
126
60-1/4 60-1/4 60-1/4
20.6
25 21
1-27/32 2-7/32
14
2
30HH, HJ
025
2
136
127
20.8
14 14
2
Shell-and-Tube, Fixed Tubesheet
30HH. HJ
030
2
136
128 179
21.0
17 15
2-3/4 3-1/4
2
Direct Expansion
1-3/8 Min.
30HH. HJ
045
2
188
60-1/4
26.6
16
2
30 HH
055
186
258 258
85-7/8
38.2
4-1/2 4-1/2
30HH, HJ
2
85-7/8
17 17
16 16
3
065
2
186
38.2
3
Materials
of
Construction
Maximum Design Working Press.(psig)
Shell Tubes Tube Sheet Baffles insulation
Water Side Refrig. Side 150
Closed Cell Foam Plastic, Vapor Sealed
Steel
Copper
Steel
Polypropylene
250
30HH,HJ INSTALLATION
Table 5 - Refrigerant Circuits
Carrier
Unit Size
зоны, HJ015
30HH, HJ020
зоны, HJ025 2
ЗОНЫ, HJ030 2
ЗОНН, HJ045
30НН055 2
ЗОНН, HJ065
NOTE: 6D73 Compressors arc used on ЗОНЫ models. 6D75 Compressors are used on 30HJ miodels.
Circuits
1
2
2
2
Description of Refrigerant Circuit
(i) 6D73 or 6D75 Compr, Full Cooler Surface
(1) 6D68 Compr, 1/2 Cooler Surface (1) 6D68 Compr, 1/2 Cooler Surface
(1) 6D68 Compr, 1/2 Cooler Surface (1) 6D73 or 6D75 Compr, 1/2 Cooler Surface
(1) 6D73 or 6D75 Compr, 1/2 Cooler Surface (1) 6D73 or 6D75 Compr, 1/2 Cooler Surface
(1) 6D73 or 6D75 Compr, 1/3 Cooler Surface (2) 6D73 or 6D7S Compr, 2/3 Cooler Surface
(2) 6D73 Compr, 1/2 Cooler Surface (1) 6D73 & (1) 6D68 Compr, 1/2 Cooler Surface 45
(2) 6D73 or 6D75 Compr, 1/2 Cooler Surface
(2) 6D73 or 6D75 Comipr, 1/2 Cooler Surface
Table 6 - Refrigerant Charge
Capacity (%)
100
50 50
40 60
50 50
33 67
55
50 50
Model ЗОНН, HJ
Refrigerant 22 (lb)
NOTES: 1. The refrigerant charges listed above do
not include the additional charge required
for remote condensers and piping with
ЗОН] models.
015
35
020
46

COMPRESSOR MOUNTING

All 30HH,HJ chillers, as shipped, have the com pressor rigidly mounted to the frame with bolts and steel pipe spacers. For proper operation, the following procedure should be followed;
30HH,HJ020 to 030 units (Fig. 8):
1. Loosen the four (4) hold-down bolts on one compressor.
2. Remove one hold-down bolt, lock washer and nut on oil pump end of compressor. Lift
025 030
46 46
2. The 30HH015 and 30HH020 units are shipped fully charged with refrigerant. Other units are shipped with holding charges only.
045 055
69
124
end of compressor and remove pipe spacer.
3. Tighten hold-down bolt which is diagonally opposite spacer which was removed.
4. Install 3/8-16 X 1-1/2" bolt, supplied in bag of fastenings, between compressor foot and bracket. Reinstall lock washer and nut.
5. Loosen hold-down bolt tightened in step No. 3.
6. Repeat steps 2 thru 5 for other oil pump end bolt.
065
140
10
INSTALLATION
30HH,HJ
Fig. 8 - 30HH,HJ015-030 Compressor
Mounting
7. Remove both compressor motor end hold down bolts, nuts, lock washers, and pipe spacers, and replace with 3/8-16 x 1” bolts. Reinstall lock washers and nuts to fasten mounting brackets to resilient mounts.
FRONT
MOTOR END
REAR
PUMP END
Fig. 9 - 30HH,HJ045-065 Compressor
Mounting
6. Repeat steps 5 and 6 for the other motor end fastenings of the compressor.

CONDENSER WATER PIPING

30HH,HJ045 to 065 units (Fig. 9):
The pairs of manifolded compressors are mount
ed on common mounting brackets. Be sure all pipe spacers are removed for proper operation. The mounting of the single compressor on
30HH,HJ045 units is similar.
1. Remove one 3/8-16 x 3-1/2” hold-down bolt, nut, lock washer, and pipe spacer on the pump end of the compressor.
2. Install a 3/8-16 x 1-3/4” bolt, supplied in bag of fastenings, and reinstall nut and lock washer from hold-down bolt, to fasten com pressor to mounting bracket.
3. Repeat steps 1 and 2 for the other pump end fastenings of the compressors.
4. Remove one 3/8-16 x 2-1/2” hold-down bolt, nut, lock washer and pipe spacer on the motor end of the compressor.
5. Install a 3/8-16 x 1” bolt, supplied in bag of fastenings, and reinstall nut and lock washer from hold-down bolt to fasten mounting bracket to resilient mount.
Water supply lines should be as short as condi tions will permit. The size of these lines is not
necessarily the same as those of the water valve
connections. All piping must be sized in accord
ance with tije pressure head available. This is
especially true on cooling tower applications. See the System Design Manual, Part 3- "Piping Design” for methods used in sizing pipe.
For installations using a waste water system, a separate water regulating valve is required for each refrigerant circuit. Water regulating valves are not supplied by Carrier.
NOTE: Provide means for draining the
system in the winter and for repairs. Figure 10 thru 16 show suggested piping connections for each model when used
with waste water or cooling towers.

Frangible Disc Safety Union

Each condenser is provided with a frangible disc that will relieve at 385 psig to protect the system from excessive pressure.
Some local codes require piping from the relief to the outdoors. The relief outlet size on both models is 3/8” male flare.
11
1064

зонн^ш

OUTLET 2" PIPE THD.
INLET 2" PIPE THD.

INSTALLATION

WATER REGULATING VALUE-WASTE WATER SYSTEMS ONLY
Carrier
Fig. 10 - 30HH015 Condenser Piping Fig. 11 - 30HH020 Condenser Piping
Fig. 12 - 30HH025 Condenser Piping
1064
Fig. 13 - 30HH030 Condenser Piping
12
Carrier
INSTALLATION
30HH,HJ
Fig. 14 - 30HH045 Condenser Piping
Fig. 15 - 30HH055 Condenser Piping
13
Fig. 16 - 30HH065 Condenser Piping
1064
30HH,HJ

Drain Connection

Drain connections are generally governed by local codes. Water leaving the condenser is under pressure and should not be connected directly into sewer lines; otherwise water may back up into other fixtures. Local codes nor mally require connections similar to the one
shown in Fig. 17.
INSTALLATION

COOLER WATER PIPING

The cooler of each liquid chilling package is pro vided with stubouts for chilled water piping con nections. The water outlet stubout is provided with a 90 degree elbow which contains the chilled water safety thermostat bulb. Holes are pro vided in both of the side panels for piping to the stubouts.
The chilled water temperature controller is mounted on the front of the unit and has the con trol bulb and capillary tubing wrapped and taped before shipping. It is required that the control bulb be field inserted in the chilled water line. It usually is inserted in the return or inlet chilled water piping. Figure 18 shows a typical chilled water piping arrangement in the vicinity of the cooler. Details of the required remote chilled water piping are outlined in the Carrier System Design Manual, Part 3, "Piping Design."
Plan the piping so it has a minimum number of changes in elevation. A manual or automatic
Fig. 17 - Drain Connections
vent-valve must be installed at the high points in the line to permit venting of air from the
chilled water circuit. Standard practice for in stalling forced water systems must be followed. System pressures may be maintained by using a pressure tank or a combination relief valve and
reducing valve.
It is recommended that thermometers be in
stalled in entering and leaving chilled liquid lines. Provide drain connections at all low points to permit complete drainage of the system. A chiller drain shut-off valve should be connected to the chiller drain line before placing the unit
in operation (Fig. 18).
Insulate piping to prevent heat loss and sweating. Cover the insulation with a moisture seal. Do not insulate piping before all leak testing has been completed.
Fig. 18 - Cooler Water Piping, Front View
14
Carrier
INSTALLATION
30HH,HJ

REFRIGERANT PIPING

For refrigerant piping sizing refer to Part 3 ­’’Piping Design” - of the System Design Manual.
The ЗОНЫ and HJ Packaged Liquid Chillers are leak tested at the factory and provided with a
holding charge of Refrigerant 22.
NOTE: 30HH015,020 fully charged with R 22 at factory.
If the holding charge is still in the system upon arrival at the erection site, the likelihood of leaks is slight. If the unit is not under pressure, test for leaks as outlined under Leak Testing.
NOTE: Be sure to open all stop valves when testing for leaks.
30HJ UNIT
This section also applies to the 30HJ unit which is to be connected to a remote condenser in the field. Figure 19 is a typical refrigerant piping diagram showing the 30HJ020 thru 030 unit and a 9H Evaporative Condenser. Simdlar connections may be used for the 30Ш045 and 065 unit using manifolded compressors. Figure 20-22 illus trate typical refrigerant piping for 30HJ020 thru
065 units and air-cooled condensers. Receivers have been omitted, but it must be recognized that with this arrangement the refrigerant charge is critical. An overcharged or undercharged system can cause a loss of capacity. If a receiver is not Included, an accurate refrigerant charge must be maintained to assure efficient operation.
Figure 20-22 are shown to illustrate a typical installation using 9A or 09DC016 air-cooled con densers. These illustrations are to be used as a guide when designing a system and are not in tended to be used as an actual piping layout. Con sult the ’’System Design Manual” and condenser literature before designing the actual system.
Each 30HJ unit (except -015) consists of two independent refrigerant circuits. Each circuit must be isolated from the other.
Discharge lines and liquid lines are shown mani folded at the units on 30HJ045 and 065 units to permit a minimum amount of piping. Individual discharge lines may be run from each compres sor to the condenser if desirable. Liquid lines must be manifolded as shown to enter the 30HJ065 unit to agree with the unit refrigerant circuit. In dividual liquid line connections are necessary on the 30HJ045 unit.
FROM TABLE - FOR VENTING AS SHOWN
MUFFLERS SHOULD AS POSSISLE.
INSTALLED AS CLOSE TO THE COMPRESSOч
Fig. 19 - Typical Refrigerant Piping 30HJ020-030 Units
with 9H Evaporative Condenser
UNI T 30HU015
3ÛHJ020 30HJ025 15" 30HJ030 30HU0A5
3OHJO65
“X” DIM. *
6"
15" 15"
15"
1 5"
"X" DIM. - THIS IS THE MINIMUM, ELEVATION REQUIRED BETWEEN A CONDENSER COIL OUTLET AND A RECE!VER INLET FOR THE TOTAL LOAD
WHEN RECE;VER 1S
VENTED TO COI I. OUTLET
HEADER (BASED ON 10'
OF HORIZONTAL PIPE, 1 VALVE AND 2 ELBOWS).
APPLIES TO 9H TYPE
EVAP. CONDENSER
- REFRIG. GAS
-REFIG. LIQUID
15
Loading...
+ 34 hidden pages