Carnes HBAE Installation Manual

ELECTRONICALLY CONTROLLED STEAM HUMIDIFIER
DESIGN SERIES “E”
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
CARNES COMPANY,
448 S. Main St.,
External Disconnect or Circuit Breaker
(Not Provided by Carnes)
P. 0. Box 930040, Verona,
\
WI 53593-0040 - Phone:
Water Shutoff Valve
(Not Provided by Carnes)
I
Fax: 608/845-6470
Copyrighl 0 1996
Overflow
‘Sensor
Terminal
‘Connectors
-Steam Cylinder
Power Contactors
LBrass Cylinder
Fittings
Photo A
(Model HBHE
-Cylinder
Retaining Band
LDrain Solenoid
Valve
Shown)
FORM 16699
REVISED: 05-96
UNPACKING AND INSPECTION
1. An envelope attached to the outside of the cabinet contains one cabinet key.
2. Open the cabinet and check for concealed shipping damage. Report any damage immediately to the carrier who delivered the shipment.
3. The following components are packed in a shipping carton for connection when installing humidifier. A. Distribution pipe.
6. Steam hose. C. Condensate return line.
4. Optional accessories may be packed with the cabinet or in the same shipping carton. Large accessories may ship in separate cartons.
5. Inside the cabinet is an envelope containing the following items: A. Steam hose clamps. B. Condensate return line clamps. C. Air gap drain fitting. D. Installation instructions.
MOUNTING THE HUMIDIFIER Mount the humidifier cabinet securely on a level and plumb
surface near the ductwork. Allow 6” or more on each side for proper ventilation and minimum of 16”from the bottom of the cabinet to the floor to allow space for the drain connec­tion. The humidifier must never be mounted outside or where it may be exposed to freezing temperatures.
Maximum operating weights for the humidifier are shown
below.
WATER SUPPLY CONNECTION Use ordinary tap water (20 to 120 psi) - DO NOT use hot water, deionized water, or water that has been treated by a water softener without consulting the factory. A 3/8” FPT fitting is provided at the top of the humidifier for connection to tap water supply. A shutoff valve, not provid­ed by Carnes, must be installed just ahead of this fitting.
DRAIN LINE CONNECTION
I. Remove the large nut and plastic gasket located on
the fitting on the bottom of the cabinet. (phofo B).The
nut and gasket may be used with standard type drain
fiiing if an air
gap
fitting is not required by local
codes.
2. Connect the air gap drain fitting to the cabinet drain connection. It may be necessary to cut off some of
the air gap fitting depending on available space.
3. Connect the drain or air gap fitting to S or P trap. Use plumbing material capable of handling hot water. Note: If the
used, follow instructions included with the drain water
pump
drain wafer pump accessory package is
package.
Table 7 - MAXIMUM OPERATING WEIGHT
Model
HBAE.
I
Tab/e
HBDE, HCDE HBGE, HCGE HBHE, HCHE 185
2 - FASTENER RECOMMENDATION
HCAE
I I
I
TYPE OF WALL Wood Studs or Solid Wood
Hollow Plaster Sheet Metal
Pounds
80 a5
105
I
\
Drain Line Connection
Photo B
6 FASTENERS REQUIRED (Models HBAE, HCAE, HBDE, HCDE) 6 FASTENERS REQUIRED (All Other Models)
l/4” Lag Screw, 1” Minimum Length l/4” Molly Bolts or Toggle Bolts, 3” Minimum Length 1/4”Thread Forming Screws, l/2” Minimum Length
Cement or Masonry
l/4” Lead Type Anchor and Bolts, 1 -l/2” Minimum Length
2
STEAM DISTRIBUTOR PIPE LOCATION
Each steam cylinder in two-cylinder units require a separate
steam distributor pipe, steam hose, and condensate return
line. In a typical installation, the humidifier is located below the
duct as shown in Figure
length between the humidifier cabinet and the steam dis-
tributor pipe in the duct be the minimum possible distance.
Refer to Table 3for maximum lengths that may be installed.
A.
It is recommended that the
The maximum length of steam hose that may be installed as shown in Figure A is 12 feet. For a steam hose length over
12 feet refer to Figure 8.
A drain “T”, as shown in Figure B, must be used to remove condensation that occurs in steam hose lengths over 12 feet. It is preferable to have the steam hose rise vertically from the cabinet and the slope toward the distributor pipe as shown. If sufficient head room is not available, it is possible to install with an upward slope to the hose.
Figure A
4” MIN.
Figure B
r
TO
DRAIN
If airflow is vertical, the steam distributor pipe should be installed horizontally
Figure
c
(Figure
C).
MAXIMUM STEAM HOSE LENGTH
(Table 3)
Duct Static
Pressure “wg”
Maximum Steam
Hose Length (Ft.)
0 1 2 3 4 5
4. 35 30 25 15 10
In two-cylinder units the pipes should be staggered as shown
3
(Figure 0).
Figure D
STEAM DISTRIBUTOR PIPE LOCATION (Continued)
Steam distributor pipes must be located on a plumb surface. This is required so the condensate which forms in the dis­tributor pipe will drain to the return line and back to the unit.
Steam distributor pipes should be mounted in the duct to
insure even distribution of steam across the center portion
of the duct.The condensate return line must always be kept
on the bottom. A minimum clearance of 4” must be main­tained between top of the duct and distributor pipe. The steam distributor pipe should be located in the supply
air stream, downstream of the fan. When installed in pack-
aged units (central station air handlers, multizone units,
make-up air units, etc.) the distributor pipe should be
mounted just downstream of the fan discharge in the pri-
mary air stream.
In multizone applications it is preferable to have a separate
humidifier serving each zone. However, steam can be intro­duced into the hot deck upstream of the zone dampers. In this case, good distribution of steam across the entire hot deck is very important. The steam distributor pipe may be located below the humid-
ifier if the installation is made in accordance with Figure
E.
A trap must be installed as shown to prevent steam from flowing back through the condensate return line.
If it is difficult to install the steam hose to prevent sags, it is recommended that copper tube be used as a substitute. If copper tube is used, a minimum of one inch of insulation
must be applied to prevent excess condensation, A short
length of steam hose should be used to connect to the cylin­der in the humidifier and another short length to connect to the steam distributor pipe. Size 3/4” copper tube should be
used with steam cylinders having output rates up to 30
pounds of steam per hour. Size l-1/2” copper tube should
be used with steam cylinders over 30 pounds per hour.The
condensate return line which connects the outlet on the
steam distributor pipe to the inlet on the top of the humidifi-
er also must be supported to prevent sags that would
restrict the flow of water,
INSTALL STEAM DISTRIBUTOR PIPE
EACH CYLINDER REQUIRES SEPARATE STEAM HOSE,
CONDENSATE RETURN LINE, AND STEAM DISTRIBU­TOR PIPE.
1. Steam distributor pipe must be mounted on a plumb surface. When on a plumb surface the standard distributor pipe is inclined upward.This is required so
the condensate which forms in the distributor pipe will drain to the return line and back to the unit.
2. Insert distributor pipe into duct and secure with four sheet metal screws, not provided by Carnes.
3. Special distributor pipes are shipped with specific instructions on how to mount them.
4. If the optional fan distribution unit is to be used, follow the instructions included with the unit.
Figure E
It is preferable to locate the steam distributor pipes down­stream from any obstructions in the ductwork so that air can absorb moisture before it impinges on a surface and accu­mulates. There must be a minimum of six feet between the steam distributor pipes and any fans, coils, filters, zone dampers, elbows or outlets which may be installed down­stream of the distributor pipe. However, in all cases, the steam distributor pipes should be located as far upstream from any such obstruction as possible.
It is very important that the steam hose is installed so that sags in the hose are prevented. Because the steam is at very low pressure it cannot overcome resistance caused by water standing in the steam hose. The steam hose is flexi-
ble so it must be supported adequately to prevent any low
point from occurring. The steam hose and condensate
return line must have a continuous pitch so that standing water will not develop.
CONNECTTHE STEAM HOSE COPPER OR BRASS TUBE IS THE ONLY ACCEPTABLE SUBSTITUTE FOR CARNES STEAM HOSE OR CON­DENSATE HOSE.
1. The steam hose should be installed so there is a continuous rise from the humidifier to the distributor
pipe. Support the steam hose at intermediate points
to prevent dips or pockets.
2. Any turns should have a minimum radius of 8” to
prevent the hose from kinking.
3. Fasten the steam hose to the distributor pipe with one of the hose clamps provided.
4. Push the steam hose through the opening on the top
of the humidifier cabinet and slip over the outlet stub on the top of the cylinder. Fasten the hose clamp provided.
CONDENSATE RETURN LINE
1. Fasten the condensate return line to the distributor pipe with the hose clamp provided.
2. Follow the steam hose to the humidifier cabinet and secure the return line to the steam hose.
3. Connect the return line to the condensate return inlet
with hose clamp provided.
4. If it is impossible to maintain a drop to the top of the cabinet, it is necessary to run the condensate return line directly to the air gap drain fitting or some other drain.
4
Loading...
+ 8 hidden pages