Carnes HBAD Installation Manual

ELECTRONICALLY CONTROLLED STEAM HUMlDlFlERS
DESIGN SERIES “C” & “D”
INSTALLATION, OPERATION
AND MAINTENANCE MANUAL
CARNES COMPANY, P.O. Box 930040,446 S. Main St., Verona, WI. 53593-1499 - Phone: 608/845-6411 Fax: 608/845-6470
“ON” Lamp -
Lamp
Steam Output Control
“ON-OFF-DRA Switch
k---v-
Steam Hose
Hose Clamp
r Cylinder
Retaining
Band
- Steam Cylinder
Optional 1 Circuit Breakers
Brass Cylinder
Fitting
Photo A
(MODEL HBHD SHOWN)
Drain Solenoid
Valve
FORM 16678-8, Page 1
ISSUED : 9/l 5/88
INSTALLATION
UNPACKING AND INSPECTION
1. An envelope attached to the outside of the cabinet contains one cabinet key.
2. Open the cabinet and check for concealed ship­ping damage. Report any damage immediately to
the carrier who delivered shipment.
3. The following components are packed in a ship­ping carton for connection when installing humidifier:
A. Distributor pipe.
6. Steam hose. C. Condensate return line.
4. Optional accessories may be packed with the cabinet or in the same shipping carton. Large
accessories may ship in separate cartons,
5. Inside the cabinet is an envelope containing the
following items: A. Steam hose clamps.
B. Condensate return line clamps. C. Air gap drain fitting. D. Installation instructions.
MOUNTING THE HUMIDIFIER
Mount the humidifier cabinet securely on a level and plumb surface near the ductwork. Allow 6” or more on each side for proper ventilation and a minimum of 16”from the bottom of the cabinet to the floor to allow space for the drain connection. The humidifier must never be mounted outside or where it may be exposed to freezing temperatures. Maximum operating weights for the humidifiers are shown below.
WATER SUPPLY CONNECTION
Use ordinary tap water (20 to 120 psi) hot water, deionized water, or water that has been treated by a water softener without consulting the factory. A 3/8” FPTfitting is provided at the top of the 4 humidifier for connection to tap water supp1y.A shut­off valve, not provided by Carnes, must be installed just ahead of this fitting.
-DO NOT use
DRAIN LINE CONNECTION
1.
Remove the large nut and plastic gasket located on the fitting on the bottom of the cabinet B). The nut and gasket may be used with standard type drain fitting if an air gap drain fitting is not required by local codes.
2. Connect the air gap drain fitting to the cabinet drain connection. Drop plastic insert into the top of ‘ie air gap drain fitting before connecting. It may be necessary to cut off some of the air gap fitting depending on available space.
3. Connect the drain or air gap fitting to S or P Trap. Use plumbing material capable of handling hot water. package is used, follow instructions included with the drain water pump package.
Note:
If the drain water pump accessory
(Photo
Table
I - MAXIMUM OPERATING WEIGHT
MODEL
Table
2 - FASTENER RECOMMENDATION
TYPE OF WALL Wood Studs or Solid Wood
Hollow Plaster Sheet Metal Cement or Masonry
POUNDS
D\rain Line
Connection
Photo B
6 FASTENERS REQUIRED
8 FASTENERS REQUIRED
l/4” Lag Screws, 1” minimum length l/4” Molly Bolts or Toggle Bolts, 3” minimum length l/4” Thread Forming Screws, l/2” minimum length l/4” Lead Type Anchor and Bolts, 1 l/2” minimum length
(Models HBAD, HCAD, HBDD, HCDD,
HBAC, HCAC, HBDC, HCDC)
(All Other Models)
FORM 16678-B, Page 2
STEAM DISTRIBUTOR PIPE LOCATION
Each steam cylinder in multi-cylinder units requires a separate steam distributor pipe, steam hose and condensate return line. The distributor pipes from one humidifier are intended to serve one duct or
multiple ducts if the pressures are the same. Only one humidistat is required for each humidifier as all circuits in multi-cylinder units operate simultaneously.
In a typical installation the humiditier is located below the duct as shown in ommended that the length between the humidifier cabinet and the steam distributor pipe in the duct be
the minimum possible distance. Refer to
maximum lengths that may be insta!led. The maxi­mum length of steam hose that may be installed as shown in over 12 feet refer to
A drain “T”, as shown in remove condensation that occurs in steam hose lengths over 12 feet. It is preferable to have the steam hose rise vertically from the cabinet and then slope
toward the distributor pipe as shown. If sufficient
head room is not available it is possible to install with an upward slope to the hose.
The standard distribution pipe must never be in­stalled vertically. If air flows are vertical, the steam distributor pipe should be installed horizon?ally
(Figure
staggered as shown in
Steam distributor pipes must be located on a plumb surface. This is required so the condensate which forms in the distributor pipe will drain to the return line and back to the unit.
Steam distributor pipes should be mounted in the duct to insure even distribution of steam across the center portion of the duct. The condensate return line must always be kept on the bottom. A minimum clearance of 4” must be maintained between top of the duct and distributor pipe.
The steam distributor pipes are normally located in the supply air stream, downstream of the fan. When installed in packaged units (central station air hand­lers, multizone units, make-up air units, etc.) the distributor pipe should be mounted just downstream of the fan discharge in the primary air stream.
In multizone applications it is preferable to have a separate humidifier serving each zone. However, steam can be introduced into the hot deck upstream of the zone dampers. In this case, good distribution of steam across the entire of the hot deck is very important.
Figure A
is 12 feet. For steam hose lengths
Figure B.
C). In multi-cylinder units the pipes should be
Figure D.
Figure A.
Figure B,
It is rec-
Table 3
must be used to
for
Figu w
Table 3
(
- MAXIMUM STEAM HOSE LENGTHS
FORM 16678-B, Page 3
Loading...
+ 5 hidden pages