SPECIFICATION SHEET
Smoke Detectors — HS-100 Series
Model EXSAE and EXSAF (Ionization),
EXSAL and EXSAM (Photoelectric)
CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax: (608)845-6470 www.carnes.com
COPYRIGHT © 2009 CARNES COMPANY
40019, pg 1
PRODUCT APPLICATION
HS-100 Series duct smoke detectors provide early detection of smoke and products of combustion present in air moving at very low to moderate speeds through an HVAC plenums and duct systems in Commercial, Industrial and Residential applications. These devices are designed to prevent the re-circulation of smoke in areas by air handling system’s fans and blowers. Complete systems may be shut down in the event of smoke detection.
The HS-100 is designed specifically for applications where our standard external mount duct detectors cannot be utilized. Examples include air shafts, plenum spaces or applications requiring extremely low or no air velocity (<
100 ft./min.).
The HS-100 Series smoke detector is fitted with a mounting base that will accept an ionization smoke detector head model 55000-225APO or photoelectric smoke detector head model 55000-328APO. The duct unit supports one set of form “C” alarm contacts, one form “A” alarm contact and one form “B” trouble contact. The trouble contact supervises the presence of the input power and the removal of the smoke detector head.
This detector is not intended for open area protection nor should it be used for early warning detection or replace a regular fire detection system.
FEATURES
• No- and Low-Flow Technology: Ionization model listed for velocities between 0-2,000 ft./min. and Photoelectric model listed for velocities between 0-3,000 ft./min.
• Both models listed for high-temperature applications
• Operating voltages: 230VAC, 115VAC, 24VAC, 24VDC
• Interconnect up to 30 units for common functions
• Compatible for interconnection and operation with Air Products’ SL-2000 and SM-501 Series Duct Smoke Detectors, MSR Series Remote Accessories and MS Series Remote Accessories
• Accessible, discrete terminal blocks for easier wiring
• Flashing LED on detector head indicates normal operation
• Magnet test capabilities (magnet included)
• More wiring space than competitive models
• Footprint allows easy retrofit in many applications
• Unit includes red alarm visual indicator
• CSFM Listing and MEA Acceptance pending
• Compact, lightweight size means easy handling, lower shipping costs
• One set of 10A form “C” alarm contacts
• One set of 2A form “A” alarm contacts
• One set of 10A form “C” trouble contacts
• Large terminal connection screws
• Standard interchangeable “plug-in” UL268 photoelectric or ionization heads
• Advanced detector head design yields internal dust filtering
• Compatible with building automation and fire alarm systems
• Ionization and Photoelectric versions available
• Complete wiring details permanently attached to unit
• Standard 4” square back box mounting allows surface or “pendant” configurations
• Low profile design
• Small-duct application friendly
• Tamper-resistant feature
LISTED
CSFM LISTED
PENDING
MEA ACCEPTED
40019, pg 2
ENGINEERS & ARCHITECTS SPECIFICA
TIONS
• Carnes smoke detectors shall be listed by Underwriters Laboratories per UL 268A.
• The detectors shall operate at air velocities from 0 feet per minute to 2,000 feet per minute (ionization) or 0 feet per minute to 3,000 feet per minute (photoelectric) and at temperatures of no greater than 140°F (60°C).
• Detector head shall not require additional filters or screens which must be maintained, and shall include both a standby and alarm visual indication.
• The unit shall contain a detector base which will accept photoelectric or ionization detector heads.
• Terminal connections shall be of the screw type, a minimum of #6 screw (#12 to #22 AWG compatible). Terminals shall be provided for remote pilot, remote alarm indications, strobe/horn and remote test/reset switch. All wiring must comply with local codes and regulations.
• A method of testing the alarm function with a magnet must be provided.
• A method of smoke testing the detector must be provided.
• All unit, remote accessory and common function connection designations must be permanently affixed to the unit.
• Capability for interconnection of up to 30 units shall be provided for common functions.
PRODUCT SPECIFICA
TIONS
MODEL NUMBER: HS-100-N Ionization: 230VAC, 115VAC, 24VAC, 24VDC
HS-100-P Photoelectric: 230VAC, 115VAC, 24VAC, 24VDC
DETECTOR MODEL NUMBER: HS-100-N 55000-225APO
HS-100-P 55000-328APO
ACCESSORIES: MS- or MSR-Series remote accessories,
TG-1000 aerosol test gas and T-PB power supplies
POWER REQUIREMENTS: (without accessories) 230VAC 18.0 mA
Standby: 115VAC 31.0 mA
24VAC 54.4 mA 24VDC 15.0 mA
Alarm: 230VAC 20.0 mA
115VAC 34.0 mA 24VAC 139.0 mA 24VDC 48.7 mA
RELAY CONTACT RATING:
Alarm Contacts: 1 sets form “C” rated at 10 Amps @ 115VAC resistive
1 form “A” rated at 2 Amps
Trouble Contacts: Resistive load: 1 form “B” rated at 10 Amps @ 115VAC resistive
AIR VELOCITY: HS-100-N 0 to 2,000 ft./min.
HS-100-P 0 to 3,000 ft./min.
AMBIENT TEMPERATURE: HS-100-N 32°F to 158°F (0°C to 70°C)
HS-100-P 32°F to 140°F (0°C to 60°C) HUMIDITY: 0% to 85% RH Non-Condensing / Non-Freezing WIRING: Solid or stranded: #12 to #22 AWG terminals APPROVALS: UL & CUL Listed (UL268A, UROX, UROX7) File # S2829
CSFM Pending
MEA Accepted (73-92-E; VOL. 37) MATERIAL: White plastic base/housing and detector (Makrolon 94V-0) DIMENSIONS: 6” Dia. x 4” H Overall / 2.6” from back box front MAX. NET WEIGHT: 1 lbs. RADIOACTIVE ELEMENTS: For HS-100-N (Ionization) Americium 241; 0.9 Micro-Curie
Do not expose to corrosive atmospheres
MOUNTING: Standard 4” square back box, not included