Carnes EGPA User Manual

CARNES COMPANY 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040 Phone: (608)845-6411 Fax: (608)845-6504 www.carnes.com
COPYRIGHT © 2012 CARNES COMPANY
ALL RIGHTS RESERVED
40082, pg 1
SPECIFICATION SHEET
Combination Fire/Smoke Damper, Class II
Model EGPA - Front Access, Crimped (3V) Blade, w/Sleeve & Thermal Blanket
Tag Qty.
Variations
Width Height
Project Location Arch./Engr. Contractor Representative Date
t Standard Construction
Frame: roll formed galvanized steel hat-section with
staked corners with integral bracing Blades: 16 ga. roll formed, galvanized steel, min. width 4.250”, max. width 7.250”
Bearings: bronze oilite, press-fit into frame Axles: square, plated steel Seals: pressure sensitive 450°F silicone blade edge
seals and flexible metal jamb seals Linkage: concealed in frame, linkage bars are .125” thick plated steel Sleeve: galvanized, wrapped in thermal blanket (typ. 3 sides) Controlled Closure Device: (heat activated) EFL - 165°F standard, 212°, 250°, 350°F available PFL - 165°F standard, 212°F available
Finish: mill galvanized Maximum Velocity: 2000 fpm (10.2 m/s) on all sizes Maximum Pressure: 4” w.c. (1kPa)
Sizes:
Minimum Size: 12”W x 10”H (305mm x 254mm) Max - Single Section: 42”W x 48”H
(1067mm x 1219mm)
Features:
• The EGPA series Combination Fire/Smoke Dampers have been designed and tested to exceed all UL, ULC and NFPA requirements for fire dampers as well as smoke dampers. They are intended for use where building codes call for the fire damper to also operate as a smoke damper.
• EGPA is UL 555 and ULC S112 listed and labeled as a 1-1/2 hour fire damper.
• UL and ULC listed for vertical mounting.
• UL 555S / ULC S112.1 listed and labeled as a Leakage Class II rated Smoke Damper with airflow in both directions. Class II provides for a max. leakage of 20 cfm per sq. ft. at
4.0 inches static pressure. As we are constantly expanding our UL / ULC listings, we suggest you contact the factory for current information.
Suggested Specifications:
The EGPA damper is UL / ULC qualified for mounting outside of the plane of the wall and have concealed actuator access, from grille side, to allow through the grille access to actuator and controls.
Notes:
Sleeved dampers are furnished approximately same size as given
duct dimension plus 3/8” for insulation, unless otherwise noted.
*Wall opening must be oversized by 3/4” to accommodate thermal
blanket thickness.
Not recommended with blades running vertically.
Options:
Factory Sleeve (16” x 20 ga. standard, other gauges and lengths also available)
Retaining Angles Smoke Detector
One Side Ionization
Photoelectric
Transitions DTO/RE w/MS Pkg.
Round Micro Switch Pkg.Oval RCB-1, -2, -3 (EXRA)
Actuator
ElectricPneumatic, 25 psi
Grille Mtg. - 1” Mounted Face Flange, Std.
Shipped Loose (if external actuator)
Mounting
Horizontal Vertical
Fire wall
Front access cover
1” (25mm) Flange
Thermal blanket (typ. 3 sides)
Grille sold separately
Grille sold separately
3” (76mm)
grille depth
16” max. (406mm)
6” max.
(152mm)
6”
(152mm)
*Width
12”
Thermal blanket typ. 3 sides vert., 4 sides horiz.
Top View
UL 555S CLASSIFIED AT
250°F OR 350°F DEPENDING
UPON MOTOR/OPERATOR
Actuator
compartment
6”
(152mm)
Actuator
compartment
40082, pg 2
PERFORMANCE DATA
Pressure drop testing was done by an independent laboratory to the AMCA Standard 500-D, Fig. 5.3 ductwork upstream and downstream.
DAMPER SIZE 36 x 36
VELOCITY THROUGH FACE AREA
PRESSURE DROP - INCHES OF WATER (In. W.C.)
1.0 .9
.8 .7
.6 .5
.4 .3
.25
.2
.15
.1
.09 .08 .07
.06 .05
.04 .03
.025
.02
.015
.01
100
1000
150 200 300 400 500 700 900 15002000 3000 4000
6000
DAMPER SIZE 24 x 24
VELOCITY THROUGH FACE AREA
PRESSURE DROP - INCHES OF WATER (In. W.C.)
1.0 .9 .8 .7
.6 .5
.4 .3
.25
.2
.15
.1
.09 .08
.07 .06 .05
.04 .03
.025
.02
.015
.01
100
1000
150 200 300 400 500 700 900 1500 2000 3000 4000 6000
1.5
2.0
2.5
DAMPER SIZE 12 x 12
VELOCITY THROUGH FACE AREA
PRESSURE DROP - INCHES OF WATER (In. W.C.)
1.0 .9 .8
.7 .6
.5 .4
.3
.25
.2
.15
.1
.09 .08 .07
.06 .05
.04 .03
.025
.02
.015
.01
100
1000
150 200 300 400 500 700 900 1500 2000
3000 4000 6000
1.5
2.0
2.5
Model EGPA - Combination Fire/Smoke Damper, Class II Front Access, Crimped (3V) Blade, w/Sleeve & Thermal Blanket
UL 555 and ULC S112 Listed, UL 555S and ULC S112.1 Listed, 1-1/2 Hour Rated