Campbell Hausfeld Vertical Operating Instrctions

Stationary Air Compressor
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
Description
Air compressor units are intended to provide compressed air to power pneumatic tools and operate spray guns. The pumps supplied are oil lubricated. A small amount of oil carryover is present in the compressed air stream. Applications requiring air free of oil or water should have the appropriate filter installed. The air compressor unit must be mounted as described in the instructions on a solid floor. Any other use of these units will void the warranty and the manufacturer will not be responsible for problems or damages resulting from such misuse.
Safety Guidelines
This manual contains information that is very important to know and understand. This information is provided for SAFETY and to PREVENT EQUIPMENT PROBLEMS. To help recognize this information, observe the following symbols.
Danger indicates
an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Warning indicates
a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Caution indicates a
potentially hazardous situation which, if not avoided, MAY result in minor or moderate injury.
Notice indicates
important information, that if not followed, may cause damage to equipment.
Unpacking
After unpacking the unit, inspect carefully for any damage that may have occurred during transit. Make sure to
NOTICE
!
CAUTION
!
WARNING
!
DANGER
Operating Instructions Vertical Models
tighten fittings, bolts, etc., before putting unit into service.
Do not operate
unit if damaged during shipping, handling or use. Damage may result in bursting and cause injury or property damage.
General Safety
Since the air compressor and other components (material pump, spray guns, filters, lubricators, hoses, etc.) used, make up a high pressure pumping system, the following safety precautions must be observed at all times:
1. Read all manuals
included with this product carefully. Be thoroughly familiar with the controls and the proper use of the equipment.
2. Follow all local electrical and safety codes as well as in the United States, the National Electrical Codes (NEC) and Occupational Safety and Health Act (OSHA).
!
WARNING
IN227706AV 2/11© 2011
Breathable Air Warning
This compressor/pump is NOT equipped and should NOT be used “as is” to supply breathing quality air. For any application of air for human consumption, you must fit the air compressor/pump with suitable in-line safety and alarm equipment. This additional equipment is necessary to properly filter and purify the air to meet minimal specifications for Grade D breathing as described in Compressed Gas Association Commodity Specification G 7.1 ­1966, OSHA 29 CFR 1910. 134, and/or Canadian Standards Associations (CSA).
DISCLAIMER OF WARRANTIES In the event the compressor is used for the purpose of breathing air application and proper in-line safety and alarm equipment is not simultaneously used, existing warranties are void, and Campbell Hausfeld disclaims any liability whatsoever for any loss, personal injury or damage.
!
DANGER
3. Only persons well acquainted with these rules of safe operation should be allowed to use the compressor.
4. Keep visitors away and NEVER allow children in the work area.
5. Wear safety glasses and use hearing protection when operating the unit.
6. Do not stand on or use the unit as a handhold.
7. Before each use, inspect compressed air system and electrical components for signs of damage,
MANUAL
Figure 1
REMINDER: Keep your dated proof of purchase for warranty purposes! Attach it to this manual or file it for safekeeping.
See Warranty on page 8 for important information about commercial use of this product.
tank and drops to a preset low level, the pressure switch automatically turns the motor back on. In the "off" position, the compressor will not operate. This switch should be in the "off" position when connecting or disconnecting the power cord from the electrical outlet.
When the pressure switch turns the motor off you will hear air leaking out of the pressure switch unloader valve for a short time. This releases the air pressure from the discharge tube and allows the compressor to restart easier.
For units without a manual switch, whenever the procedures call for turning the switch to the OFF position, use the switch at the disconnect instead.
Unloader - Device on pressure switch which allows pressurized air to vent alleviating motor restarts under load.
Regulator - The regulator controls the amount of air pressure released at the hose outlet (Sold separately).
ASME Safety Valve - This valve automatically releases air if the tank pressure exceeds the preset maximum. Discharge tube - This tube carries
compressed air from the pump to the check valve. This tube becomes very hot during use. To avoid the risk of severe burns, never touch the discharge tube.
General Safety (Con’t)
deterioration, weakness or leakage. Repair or replace defective items before using.
8. Check all fasteners at frequent intervals for proper tightness.
Motors, electrical equipment and controls can cause electrical arcs that will ignite a flammable gas or vapor. Never operate or repair in or near a flammable gas or vapor. Never store flammable liquids or gases in the vicinity of the compressor.
Never operate compressor without a beltguard. This unit can start automatically without warning. Personal injury or property damage could occur from contact with moving parts.
9. Do not wear loose clothing or jewelry that will get caught in the moving parts of the unit.
Compressor parts may be hot even if the unit is stopped.
10. Keep fingers away from a running compressor; fast moving and hot parts will cause injury and/or burns.
11. If the equipment should start to vibrate abnormally, STOP the engine/motor and check immediately for the cause. Vibration is generally a warning of trouble.
12. To reduce fire hazard, keep engine/motor exterior free of oil, solvent, or excessive grease.
An ASME code
safety relief valve with a setting no higher than 150 psi MUST be installed in the tank for this compressor. The ASME safety valve must have sufficient flow and pressure ratings to protect the pressurized components from bursting.
See compressor
specification decal for maximum operating pressure. Do not operate with pressure switch or pilot valves set higher than the maximum operating pressure.
13. Never attempt to adjust ASME
safety valve. Keep safety valve free from paint and other accumulations.
Never use plastic
(PVC) pipe for compressed air. Serious injury or death could result.
!
WARNING
!
CAUTION
!
WARNING
!
CAUTION
!
WARNING
!
WARNING
2
Operating Instructions
Never attempt to repair or modify a tank! Welding, drilling or any other modification will weaken the tank resulting in damage from rupture or explosion. Always replace worn, cracked or damaged tanks.
Drain liquid from tank daily.
14.
Tanks rust from moisture build-up, which weakens the tank. Make sure to drain tank regularly and inspect periodically for unsafe conditions such as rust formation and corrosion
.
15. Fast moving air will stir up dust and debris which may be harmful. Release air slowly when draining moisture or depressurizing the compressor system.
SPRAYING PRECAUTIONS
Do not spray flammable materials in vicinity of open flame or near ignition sources including the compressor unit.
16. Do not smoke when spraying paint, insecticides, or other flammable substances.
17. Use a face mask/ respirator when spraying and spray in a well ventilated area to prevent health and fire hazards.
18. Do not direct paint or other sprayed material at the compressor. Locate compressor as far away from the spraying area as possible to minimize overspray accumulation on the compressor.
19. When spraying or cleaning with solvents or toxic chemicals, follow the instructions provided by the chemical manufacturer.
Introduction
Refer to Figure 2.
INSTALLING A SHUT-OFF VALVE
A shut-off valve should be installed on the discharge port of the tank to control the air flow out of the tank. The valve should be located between the tank and the piping system.
Pressure switch - Auto/Off Switch - In the "auto" position, the compressor shuts off automatically when tank pressure reaches the maximum preset pressure. After air is used from the
!
WARNING
NOTICE
!
DANGER
Drain Petcock
Discharge Tube
Belt Guard
Check
Valve
Safety
Valve
Pressure Switch
Tank Outlet
Figure 2
Tank Drain Valve
Tank Pressure Gauge
PIPING
Never use plastic
(PVC) pipe for compressed air. Serious injury or death could result.
Any tube, pipe, or hose used must have a pressure rating higher then 150 psi. Minimum recommended pipe size:
- up to 50 feet long use 1/2"
- greater than 50ft. long use 3/4"
Larger diameter pipe is always better.
All wiring and
electrical connections must be performed by a qualified electrician. Installations must be in accordance with local and national codes.
GROUNDING
This product must be grounded. If the unit comes with a factory installed cord, plug the cord into a properly sized, grounded outlet. For units that do not have a factory installed cord, install permanent wiring from the electrical source to the pressure switch with a ground conductor connected to the grounding screw on the pressure switch. A properly sized cord with a ground conductor and plug may also be installed by the user.
Improperly grounded motors are shock hazards. Make sure all the equipment is properly grounded.
WIRING
Local electrical wiring codes differ from area to area. Source wiring, plug and protector must be rated for at least the amperage and voltage indicated on the motor nameplate, and meet all electrical codes for this minimum. Use a slow blow fuse type T or a circuit breaker.
Overheating, short
circuiting and fire damage will result from inadequate wiring.
Motor protection should be used when a motor built-in thermal overload protection is not provided. Some 3 phase units require a magnetic starter for thermal protection (See Figure 4).
!
CAUTION
!
DANGER
!
WARNING
!
WARNING
This compressor is
extremely top heavy. The unit must be bolted to the floor with isolation pads or secured with the wall cable (if provided) before operating to prevent equipment damage, injury or death.
WALL CABLE INSTALLATION
(Provided on some 30 gallon models)
On some 30 gallon models a wall cable is provided and should be installed.
Included with the safety cable are two lag screws and washers.
1. Place an isolation pad beneath each
foot of the compressor to minimize vibration.
2. Position the cable through the
baseplate as shown in Figure 3.
3. Place the screws through the
washers then through looped ends of cable.
4. Secure the screws to a stud within a
framed wall. Use anchors if the wall is concrete.
Do not secure the
compressor with toggle bolts into drywall. Drywall sheeting or plaster will not support the weight of the compressor.
Never install a
shut-off valve between the compressor pump and the tank. Personal injury and/or equipment damage may occur.
!
WARNING
!
WARNING
!
WARNING
Vertical Models
3
Introduction (Con’t)
Check valve - One-way valve that
allows air to enter the tank, but prevents air in the tank from flowing back into the compressor pump.
Belt Guard - Covers the belt, motor pulley and flywheel.
Tank Drain Valve - This valve is located on the bottom of the tank. Use this valve to drain moisture from the tank daily to reduce the risk of corrosion.
Reduce tank pressure below 10 psi, then drain moisture from tank daily to avoid tank corrosion. Drain moisture from tank(s) by opening the drain valve located underneath the tank.
Installation
Disconnect, tag and lock out power source, then release all pressure from the system before attempting to install, service, relocate or perform any maintenance.
LOCATION
This compressor is not intended for
outdoor installation.
It is extremely important to install the compressor in a clean, well ventilated area where the surrounding air temperature will not be more than 100°F.
Provide a minimum clearance of 18 inches between the compressor flywheel or fan to the wall and ensure clear access to the drain cock to facilitate condensate drainage.
Do not locate the compressor air inlet near steam, paint spray, sandblast areas or any other source of contamination.
MOUNTING
Never use the
wood shipping
skids for mounting the compressor.
FLOOR MOUNTING
(All Units)
The compressor feet MUST be bolted to a flat, even, concrete floor or separate concrete foundation. Vibration isolators must be used between the tank leg and the floor (Part number MP3445 available separately). Do not draw bolts tight. Allow the pads to absorb vibrations. A flexible coupling should be installed between the tank and service piping.
!
CAUTION
NOTICE
!
WARNING
Figure 3 - Wall Cable Installation
Electrical Installation
HARD WIRED UNITS ONLY
DUAL VOLTAGE MOTORS (SOME MODELS)
The grounding plug must be changed to
convert unit for dual voltage.
Dual voltage motors may be connected for either 120 volts or 240 volts. By comparing the plug on the cord with the receptacles shown below, you can determine for which voltage your compressor is factory wired. Also check motor decal to change from low voltage to high voltage.
All wiring must be
completed by a qualified electrician. Disconnect from power source before changing any wiring.
When converting
to an alternate voltage, be sure the green ground wire of the cord connects to the ground pin of the plug and to the metal body of the pressure switch.
Assembly
ADDITIONAL HARDWARE NEEDED
Purchase hose, regulator and shutoff valve that has a minimum rating of 150 PSI and exceeds the maximum working pressure of the compressor.
OIL DRAIN EXTENSION
Some models include an oil drain extension and cap (found with the owner’s manual). Install the oil drain extension and cap before adding oil to the pump. _To avoid oil leaks, it is highly recommended to apply PTFE thread sealant tape or paste type sealant to the threads on each end of the oil drain extension. Screw the cap onto one end of the extension. Remove the oil drain plug from the base of the pump and install the oil drain extension (See Figure 6).
!
WARNING
!
WARNING
NOTICE
Installation (Con’t)
NOTE: 120 volt, 15 amp units can be
operated on a 120 volt 15 amp circuit under the following conditions:
1. No other electrical appliances or lights are connected to the same branch circuit.
2. Voltage supply is normal.
3. Circuit is equipped with a 15 amp circuit breaker or a 15 amp slow blow fuse type T (For Canada use Type D).
If the above conditions cannot be met or if nuisance tripping of the current protection device occurs, it may be necessary to operate the compressor from a 120 volt 20 amp circuit. Some models convert to 240 volt operation, see DUAL VOLTAGE MOTOR.
GROUNDING INSTRUCTIONS
1. This product is for use on a nominal 120 or 240 volt circuit and has a grounding plug that looks like one of the plugs illustrated in Fig. 5. Make sure product is connected to an outlet having the same configuration as the plug.This product must be grounded. In the event of an electric short circuit, grounding reduces the risk of electrical shock by providing an escape wire for the electric current. This product is equipped with a cord having a grounding wire with an appropriate grounding plug. The plug must be plugged into an outlet that is properly installed and grounded in accordance with all local codes and ordinances.
Improper use of grounding plug can result in a risk of electrical shock. Do not use grounding adapter.
!
DANGER
4
Operating Instructions
2. If repair or replacement of the cord or plug is necessary, do not connect the grounding wire to either flat blade terminal. The wire with insulation having an outer surface that is green with or without yellow stripes is the grounding wire.
3. Check with a qualified electrician or serviceman if the grounding instructions are not completely understood, or if in doubt as to whether the product is properly grounded. Do not modify the plug provided; if it will not fit the outlet, have the proper outlet installed by a qualified electrician.
PLUGS AND RECEPTACLES
1. If the plug on the electrical cord of the unit is unfamiliar to you or will not fit your particular receptacle, Figure 5 will help you understand why by illustrating the different plugs and the voltages they are to be used with.
2. Make sure that the product is connected to an outlet having the same configuration as the plug.
3. The receptacles must be connected to circuits rated to carry at least the voltage and amperages shown.
4. NEVER have a receptacle replaced with one of a higher amperage before determining the change can be made according to all electrical codes affecting your particular area. The installation should be made by a qualified electrician. If the products must be reconnected for use on different types of circuits, the re-connection should be made by qualified personnel.
L1
L2
Pressure
Switch
Thermal Units(3)
L3
T2
Fused Breaker Or Disconnect
X2
Motor
OVER­LOAD
COIL
T3
T1
Three Phase
With Magnetic
Starter
L1
L2
240V
Ground
Pressure
Switch
Line
M
Motor
Single Phase
Figure 4 - Wiring Diagrams
Ground Pin
Grounded Outlet
Grounded Outlet
Ground Pin
120V 20A
120V 15A
240V 20A
240V 15A
Figure 5
Electrical Connection
UNITS WITH LINE CORDS ONLY
Vertical Models
5
Assembly (Con’t)
LUBRICATION
THIS UNIT IS
SHIPPED WITHOUT OIL! Follow lubrication instructions before operating compressor.
Ensure oil drain extension and cap has been installed (if included) then remove the dipstick breather (See Fig. 6) and fill pump oil according to the chart.
See specification label on air tank for pump model number and refer to the chart for the proper oil capacity.
OIL
Use SAE 30 industrial grade air compressor oil or full synthetic motor oil like Mobil 1 10W30. Do not use
regular automotive oil such as 10W-30. Additives in motor oil can
cause valve deposits and reduce pump life. For maximum pump life, drain and replace oil after the first hour of run time. Proper oil fill level is illustrated in Figure 6.
For pumps with an oil sight glass, oil level can be monitored and maintained as shown in Figure 7.
!
CAUTION
Operation
START-UP
Do not attach air
tools to open end of the hose until start-up is completed and the unit checks OK.
Never disconnect
threaded joints with pressure in tank!
1. Remove the breather and fill pump to the proper oil level. See lubrication section.
2. Open the tank drain valve. Turn outlet valve to open air flow.
3. Move pressure switch lever or knob to the OFF position and plug in power cord. Move pressure switch to the AUTO position to run the unit.
4. Run the unit for 30 minutes, under no load, to break in pump parts.
5. Move the pressure switch lever or knob to OFF and turn tank drain valve to shut off air flow. The compressor is now ready for use.
!
WARNING
!
CAUTION
Pump Approx. Oil Capacity
VS260000KB 6 oz VT470200KB 11.5 oz VT470000KB 12 oz VH300000AV 32 oz
MOISTURE IN COMPRESSED AIR
Moisture in compressed air will form into droplets as it comes from an air compressor pump. When humidity is high or when a compressor is in continuous use for an extended period of time, this moisture will collect in the tank. When using a paint spray or sandblast gun, this water will be carried from the tank through the hose, and out of the gun as droplets mixed with the spray material.
IMPORTANT: This condensation will cause water spots in a paint job, especially when spraying other than water based paints. If sandblasting, it will cause the sand to cake and clog the gun, rendering it ineffective.
A filter in the air line, located as near to the gun as possible, will help eliminate this moisture.
Maintenance
Disconnect, tag and lock out power source, then release all pressure from the system before attempting to install, service, relocate or perform any maintenance.
All repairs should be performed by an authorized service representative.
FOR EFFICIENT OPERATION:
Perform the following test to verify free operation of the safety valve weekly and follow maintenance schedule.
1. Pull ring on safety valve and allow the ring to snap back to normal position (See Figure 9). This valve automatically releases air if the tank pressure exceeds the preset maximum.
Do not attempt to
tamper with this valve. This valve should be checked occasionally. If air leaks after the ring has been released, or the valve is stuck and cannot be actuated by the ring, the safety valve must be replaced.
A large amount of
fast moving air will be released if this valve is actuated with pressure in the tank.
2. With motor OFF and unplugged,
clean debris from motor, flywheel, tank, air lines and pump cooling fins.
DRIVE BELT
Belts will stretch in normal use. Properly adjusted, a 5-pound force applied to the belt between the motor pulley and the pump will deflect the belt about 1/2" (See Figure 10).
!
CAUTION
!
DANGER
!
WARNING
Dipstick
Breather
Full
Add
Add Oil
Oil Drain Extension
Cap
Low
Max
Figure 6
Figure 9
A
U
T
O
/
O
F
F
Figure 8
Lever - Off
Lever - Auto
Knob
Auto/Off
1/2" Deflection
Figure 10
* Not included with all models
*
*
Figure 7
Full
Add oil
6
Operating Instructions
Maintenance (Con’t)
TO ADJUST DRIVE BELT:
1. Remove belt guard.
2. Loosen the four fasteners holding the motor to the baseplate.
3. Shift the motor in the proper direction. The belt must be properly aligned when adjustment is made.
4. Adjust flywheel or motor pulley so that the belt runs straight.
5. If necessary, use a gear puller to move the pulley on the motor shaft. Tighten setscrew after pulley is positioned.
6. Attach belt guard.
STORAGE
1. When not in use, hose and compressor should be stored in a cool dry place.
2. Tanks should be drained of moisture. and hose should be disconnected and hung with open ends down to allow any moisture to drain.
3. Protect the electrical cord from possible damage by winding the cord loosely around the handle of the unit or coiling the cord up.
TECHNICAL INFORMATION
For information on the operation or repair, please call 1-800-543-6400. In Ohio or outside the continental U.S., call 513-367-4811.
Operation Daily Weekly Monthly 3 Months
Check Oil Level Drain Tank Check Air Filter Check Safety Valve Clean Unit Check Belt Tightness Change Oil
MAINTENANCE SCHEDULE
Symptom Possible Cause(s) Corrective Action
Low discharge pressure
Pump overheating causes air filter to melt
Excessive noise (knocking)
1. Air demand exceeds pump capacity
2. Air leaks
3. Restricted air intake
4. Blown gaskets
5. Leaking or damaged valves
1. Insulating gasket between filter and head is missing
2. Broken valves/blown gasket
1. Loose motor or compressor pulley
2. Lack of oil in crankcase
3. Worn connecting rod
4. Worn piston pin bores
5. Piston hitting the valve plate
1. Reduce air demand or use a compressor with more capacity.
2. Listen for escaping air. Apply soap solution to all fittings and connections. Bubbles will appear at points of leakage. Tighten or replace leaking fittings or connections.
3. Clean the air filter element.
4. Replace any gaskets proven faulty on inspection.
5. Remove head and inspect for valve breakage, misaligned valves, damaged valve seats, etc. Replace defective parts and reassemble.
Install a new head gasket each time the head is removed
1. Install gasket.
2. Replace valves or install new gasket.
1. Loose motor or compressor pulleys are a very common cause of compressors knocking. Tighten pulley clamp bolts and set-screws.
2. Check for proper oil level; if low, check for possible damage to bearings. Dirty oil can cause excessive wear.
3. Replace connecting rod. Maintain oil level and change oil more frequently.
4. Remove piston assemblies from the compressor and inspect for excess wear. Replace excessively worn piston pin or pistons, as required. Maintain oil level and change oil more frequently.
5. Remove the compressor head and valve plate and inspect for carbon deposits or other foreign matter on top of piston. Replace head and valve plate using new gasket. See Lubrication section for recommended oil.
!
CAUTION
Troubleshooting Chart
Vertical Models
7
Symptom Possible Cause(s) Corrective Action
Excessive noise (knocking) Continued
Large quanity of oil in the discharge air NOTE: In an oil lubricated compressor there will always be a small amount of oil in the air stream.
Water in discharge air/tank
Motor hums and runs slowly or not at all
Reset mechanism cuts out repeatedly or fuses blow repeatedly
Tank does not hold pressure when compressors off and the shut off valve is closed
Pressure switch continuously blows air out the unloader valve
Pressure switch does not release air when the unit shuts off
Excessive vibration
6. Noisy check valve in compressor system
1. Worn piston rings
2. Compressor air intake restricted
3. Excessive oil in compressor
4. Wrong oil viscosity
1. Normal operation. The amount of water increases with humid weather
1. Use of extension cord
2. Malfunctioning check valve or unloader valve
3. Low voltage
4. Malfunctioning pressure switch - contacts will not close
1. Too many devices on same circuit
2. Incorrect fuse size or circuit breaker
3. Malfunctioning check valve
4. Pressure switch set too high
5. Loose wiring
6. Malfunctioning motor
1. Worn check valve
2. Check all connections and fittings for leaks
3. Check tank for cracks or pin holes
1. Malfunctioning check valve
1. Malfunctioning unloader valve on pressure switch
1. Loose fasteners
2. Belt needs replaced
3. Belt alignment
6. Replace.
Do not disassemble check valve with
air pressure in tank
1. Replace with new rings. Maintain oil level and change oil more frequently.
2. Clean filter. Check for other restrictions in the intake system.
3. Drain down to full level.
4. Use Mobil 1
®
10W-30
1. Drain tank more often. At least daily.
2. Add a filter to reduce the amount of water in the air line.
1. Do not use an extension cord. Use longer air hose with larger diameter.
2. Replace check valve, unloader valve or pressure switch.
Do not disassemble check valve with
air pressure in tank
3. Check with voltmeter, check reset switch on motor. If reset switch trips repeatedly, find and correct the cause. See next item.
4. Repair or replace pressure switch.
1. Limit the circuit to the use of only the air compressor.
2. Be sure that fuses or circuit breakers are rated properly.
3. Replace check valve.
Do not disassemble check valve with
air pressure in tank
4. Adjust or replace.
5. Check all electrical connections.
6. Replace motor.
1. Replace check valve.
Do not disassemble check valve with
air pressure in tank
2. Tighten.
3. Replace tank. Never repair a damaged tank.
1. Replace the check valve if the unloader valve bleeds off constantly.
Do not disassemble check valve with
air pressure in tank
1. Replace the pressure switch if it does not release the pressure for a short period of time when the unit shuts off.
Do not disassemble pressure switch with
air pressure in tank
1. Tighten.
2. Replace with correct size.
3. Align flywhell and pulley.
!
DANGER
!
DANGER
!
DANGER
!
DANGER
!
DANGER
!
DANGER
Troubleshooting Chart (Continued)
8
Operating Instructions
Limited Warranty
1. DURATION: From the date of purchase by the original purchaser as follows: One Year, Two Years, Three Years, Four Years, or Five Years as indicated on product specification label.
2. WHO GIVES THIS WARRANTY (WARRANTOR): Campbell Hausfeld / Scott Fetzer Company, 100 Production Drive, Harrison, Ohio, 45030, Telephone: (800) 543-6400
3. WHO RECEIVES THIS WARRANTY (PURCHASER): The original purchaser (other than for purposes of resale) of the Campbell Hausfeld compressor.
4. WHAT PRODUCTS ARE COVERED BY THIS WARRANTY: Any Campbell Hausfeld air compressor.
5. WHAT IS COVERED UNDER THIS WARRANTY: Parts and Labor to remedy substantial defects due to material and workmanship during the first year of ownership with the exceptions noted below. Parts only to remedy substantial defects due to material and workmanship during remaining term of coverage with exceptions noted below.
6. WHAT IS NOT COVERED UNDER THIS WARRANTY: A. Implied warranties, including those of merchantability and FITNESS FOR A PARTICULAR PURPOSE ARE LIMITED FROM THE DATE OF
ORIGINAL PURCHASE AS STATED IN THE DURATION. If the compressor is used for commercial, industrial or rental purposes, the warranty will apply for ninety (90) days from the date of purchase. Two-stage compressors are not limited to a ninety (90) day warranty when used in commercial or industrial applications. Some States do not allow limitations on how long an implied warranty lasts, so the above limitations may not apply to you
B. ANY INCIDENTAL, INDIRECT, OR CONSEQUENTIAL LOSS, DAMAGE, OR EXPENSE THAT MAY RESULT FROM ANY DEFECT, FAILURE,
OR MALFUNCTION OF THE CAMPBELL HAUSFELD PRODUCT. Some States do not allow the exclusion or limitations of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
C. Any failure that results from an accident, purchaser’s abuse, neglect or failure to operate products in accordance with instructions
provided in the owner’s manual(s) supplied with compressor. D. Pre-delivery service, i.e. assembly, oil or lubricants, and adjustment. E. Items or service that is normally required to maintain the product, i.e. lubricants, filters and gaskets, etc. F. Gasoline engines and components are expressly excluded from coverage under this limited warranty. The Purchaser must comply
with the warranty given by the engine manufacturer which is supplied with the product G. Additional items not covered under this warranty:
1. Excluded items pertaining to All Compressors a. Any component damaged in shipment or any failure caused by installing or operating unit under conditions not in accordance
with installation and operation guidelines or damaged by contact with tools or surroundings. b. Pump or valve failure caused by rain, excessive humidity, corrosive environments or other contaminants. c. Cosmetic defects that do not interfere with compressor functionality. d. Rusted tanks, including but not limited to rust due to improper drainage or corrosive environments. e. The following components are considered normal wear items and are not covered after the first year of ownership.
Electric motor, check valve, pressure switch, regulator, pressure gauges, hose, tubing, pipe, fittings and couplers, screws, nuts,
hardware items, belts, pulleys, flywheel, air filter and housing, gaskets, seals, oil leaks, air leaks, oil consumption or usage,
piston rings. f. Tank drain valves. g. Damage due to incorrect voltage or improper wiring. h. Other items not listed but considered general wear parts. i. Pressure switches, air governors, load/unload devices, throttle control devices and safety valves modified from factory settings. j. Damage from inadequate filter maintenance. k. Induction motors operated with electricity produced by a generator.
2. Excluded items specific to Lubricated Compressors: a. Pump wear or valve damage caused by using oil not specified. b. Pump wear or damage caused by any oil contamination. c. Pump wear or damage caused by failure to follow proper oil maintenance guidelines, operation below proper oil level
or operation without oil.
H. Labor, service call, or transportation charges after the first year of ownership of stationary compressors. Stationary compressors are
defined as not including a handle or wheels.
7. RESPONSIBILITIES OF WARRANTOR UNDER THIS WARRANTY: Repair or replace, at Warrantor’s option, compressor or component which is defective, has malfunctioned and/or failed to conform within duration of the warranty period.
8. RESPONSIBILITIES OF PURCHASER UNDER THIS WARRANTY: A. Provide dated proof of purchase and maintenance records. B. Portable compressors or components must be delivered or shipped to the nearest Campbell Hausfeld Authorized Service Center.
Freight costs, if any, must be borne by the purchaser. C. Use reasonable care in the operation and maintenance of the products as described in the owner’s manual(s). D. Repairs requiring overtime, weekend rates, or anything beyond the standard manufacturer warranty repair labor reimbursement
rate. E. Time required for any security checks, safety training, or similar for service personnel to gain access to facility. F. Location of unit must have adequate clearance for service personnel to perform repairs and easily accessible.
9. WHEN WARRANTOR WILL PERFORM REPAIR OR REPLACEMENT UNDER THIS WARRANTY: Repair or replacement will be scheduled and serviced according to the normal work flow at the servicing location, and depending on the availability of replacement parts.
This Limited Warranty applies in the U.S., Canada and Mexico only and gives you specific legal rights. You may also have other rights which vary from State to State or country to country.
Loading...
+ 16 hidden pages