Burnham 8B Series, 805B, 806B, 810B, 807B Installation, Operating And Servicing Instructions

...
Page 1
SEIRESB8
RELIOBDERIF-SAG
DNAGNITAREPO,NOITALLATSNI
ROFSNOITCURTSNIECIVRES
,reliobnonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp
rebmuNledoMrelioBrebmuNlaireSrelioBetaDnoitallatsnI
____-_____8________6
rotcartnoCgnitaeH rebmuNenohP
8141602R13-7/03
1
Price - $5.00
Page 2
IMPORTANT INFORMATION - PLEASE READ THIS PAGE CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
This Series 8B Boiler has been approved by the Massachusetts Board of Plumbers and Gas Fitters: Approval No. G1-0202-11A. The Commonwealth of Massachusetts requires this product to be installed by a licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
REGNAD
noitautissuodrazahyltnenimminasetacidnI
,htaednitluserlliw,dediovatonfi,hcihw
ytreporplaitnatsbusroyrujnisuoires
.egamad
.egamad
GNINRAW
noitautissuodrazahyllaitnetopasetacidnI
,htaednitluserdluoc,dediovatonfi,hcihw
ytreporplaitnatsbusroyrujnisuoires
.egamad
NOITUAC
noitautissuodrazahyllaitnetopasetacidnI
nitluseryam,dediovatonfi,hcihw
ytreporproyrujnironimroetaredom
ECITON
nosnoitcurtsnilaicepssetacidnI
ecnanetniamro,noitarepo,noitallatsni
otdetalertontubtnatropmierahcihw
.sdrazahyrujnilanosrep
REGNAD
rosihtfoytinicivehtnisdiuqilrosropavelbammalfrehtoroenilosagesuroerotsTONOD
.ecnailpparehtoyna
lacirtceleynahcuotTONOD-ecnailppaynaetarepootyrtTONOD,sropavsagllemsuoyfI
yletomeramorfreilppussagehtllac,yletaidemmI.gnidliubehtnienohpynaesurohctiws
,elbaliavanusireilppusehtfirosnoitcurtsnis'reilppussagehtwolloF.enohpdetacol
.tnemtrapederifehttcatnoc
elbitsubmocrevoetercnoc,teprac,gniroolfelbitsubmocnoreliobsihtllatsniTONOD
rognipipcitsalpsahcuslairetamdetceffataehynarevoetercnocnoron,doowrogniroolf
.dleihsroolfelbitsubmocdellatsniylreporpatuohtiwgniriw
2
Page 3
GNINRAW
ehtwolloF.ylefasetarepootecivresdnaecnanetniamralugerseriuqerreliobsihT
.launamsihtnideniatnocsnoitcurtsni
ytreporpesuacnacecnanetniamroecivres,noitaretla,tnemtsujda,noitallatsnireporpmI
erofeblaunameritneehtdnatsrednudnadaeR.efilfossolroyrujnilanosrep,egamad
ebtsumecivresdnanoitallatsnI.ecivresro,noitarepopu-trats,noitallatsnignitpmetta
.ycnegaecivresrorellatsnidelliksdna,decneirepxe,elbaegdelwonkaybylnodemrofrep
.detnevylreporpebtsumreliobsihT
snoisivorperaerehtosdellatsniebtsumdnanoitarepoefasrofriahserfsdeenreliobsihT
.rianoitalitnevdnanoitsubmocetauqedarof
ehtfotratsehterofebdenaelcdnadetcepsniebtsummetsysgnitnevehtforoiretniehT rofnosaesgnitaehehttuohguorhtyllacidoirepdetcepsniebdluohsdnanosaesgnitaeh
suoixonwollaotyrassecensimetsystnevdetcurtsbonudnanaelcA.snoitcurtsboyna
drawotetubirtnoclliwdnaylefastnevotefilfossolroyrujniesuacdluoctahtsemuf
.ycneiciffes'reliobehtgniniatniam
gnippatehtotnidellatsnisievlavfeilererusserpasselnuetelpmoctonsinoitallatsnI
roflaunamsihtfonoitceSmirTdnagnipiPretaWehteeS-reliobfopotehtnodetacol
.sliated
dnanwodtuhsotreliobehtesuacyamhcihwsecivedytefashtiwdeilppussireliobsihT
gnitaeheht,ytilibissopasisepipnezorfoteudegamadfI.ecivrestuohtiwtrats-erton
dnasdraugefasetairporpparo;rehtaewdlocnidednettanutfelebtondluohsmetsys
sireliobehtfiegamadtneverpotmetsysgnitaehehtnodellatsniebdluohssmrala
.evitareponi
sgnittifepipynawercsnutonoD.erusserphgihrednuretawtohyrevsniatnocreliobsihT
ehtgnirussaylevitisoptuohtiwreliobsihtfostnenopmocynatcennocsidottpmettaron
nehwtnempiuqednagnihtolcevitcetorpraewsyawlA.erusserponsahdnaloocsiretaw
ehtnoylertonoD.seirujnidlacstneverpotreliobsihtgnicivresropugnitrats,gnillatsni
.reliobehtfoerusserpdnaerutarepmetehtenimretedotseguagerutarepmetdnaerusserp
oD.gnitareposireliobehtnehwtohyrevemocebhcihwstnenopmocsniatnocreliobsihT
.loocerayehtsselnustnenopmocynahcuotton
,animulaniatnocleufehtdnanoitsubmocfostcudorp,noitcurtsnocfoslairetamrelioB
rocixotrehtoro/dnasedyhedla,sedixonegortin,edixonomnobrac,slatemyvaeh,acilis
ehtotnwonkerahcihwdnayrujnisuoiresrohtaedesuacnachcihwsecnatsbuslufmrah
esusyawlA.mrahevitcudorperrehtodnastcefedhtrib,recnacesuacotainrofilaCfoetats
ehtybraengnikrowrognicivresnehwtnempiuqednasrotaripser,gnihtolcytefasreporp
.ecnailppa
.htaedroyrujnilanosrepesuacnacredroreporpehtnisnoitcurtsnillawollofoteruliaF
slaunamsrerutcafunamtnenopmocnideniatnocesohtllagnidulcni,snoitcurtsnilladaeR
rogniniatniam,gnitarepo,pugnitrats,gnillatsnierofebreliobehthtiwdedivorperahcihw
.gnicivres
elbammalfrehtodnaenilosag,slairetamelbitsubmocmorfeerfdnaraelcaerareliobpeeK
.sdiuqilrosropav
.retawottcejbusneebsahhcihwlortnochtiwreliobetarepotonoD
.semitllataecalpniebtsumsdraugdnaserusolcne,setalprevocllA
ECITON
.launamsihtfokcabehtnodetnirpsihcihwfoypoca,ytnarrawdetimilasahreliobsihT
yltcerroceraslortnocllatahteesotrotcartnocgnillatsniehtfoytilibisnopserehtsitI
.etelpmocsinoitallatsniehtnehwylreporpgnitarepoeradnadellatsni
evahlevelaesevobateef000,2nahtretaergsedutitlatanoitallatsniroftliubsreliobASU
replevelaesevobateef000,1reptnecrep4etartupnisagecuderotdecifiroyllaicepsneeb
naidanaC.FxidneppAdna2.1.8noitceS,1.322ZISNA/45APFN,edoCsaGleuFlanoitaNeht
.lebalgnitarehtnodetacidnisignizisecifiro'sreliob
3
Page 4
Table of Contents
I. Pre-Installation ................................................ 6
II. Boiler Assembly ................................................ 8
III. Gas Control System Assembly ....................... 15
(Knockdown Boilers)
IV. Water Trim and Piping .................................... 27
V. Gas Piping ....................................................... 31
VI. Venting ............................................................33
VII. Electrical .......................................................... 36
VIII. System Start-up ............................................... 59
IX. Service ............................................................. 68
X. Repair Parts ..................................................... 75
4
Page 5
Table 1: Dimensional Data
Figure 1: Dimensional Data
relioB
ledoM
ABC
.oN
B50802017 61/31-4261/31-428/1-618/1-61.tf51x.aid"79.11096 B6084/3-328/7-118 61/31-724/3-528161.tf51x.aid"89.31077 B7082/1-724/3-319 61/31-824/3-528161.tf51x.aid"99.51578 B8084/1-138/5-519 61/31-0361/11-620261.tf51x.aid"99.71089 B908532/1-71012/1-3361/7-622251.tf51x.aid"019.910801 B0184/3-838/3-91012/1-3361/7-622251.tf51x.aid"019.120021
)1(
.)"4/1-73silenap )2( )3( )4(
)sehcnI(snoisnemiD
DE
ASUadanaCASUadanaC
TPN1:ezisnoitcennocsaG
)ylnOretaW(isp05:erusserPgnikroWelbawollAmumixaM
.rellatsniybdeilppussenilneddihninwohssmetI
5
dednemmoceR
eziSyenmihC
)dnuoR(
retaW
tnetnoC
)snollaG(
.xorppA gnippihS
thgieW
)BL(
pottekcajotroolf(thgiehreliobot"4/3-4sdda;gniroolfelbitsubmocnosnoitallatsnirofderiuqeresablaicepS
Page 6
I. Pre-Installation
GNINRAW
erofebsnoitcurtsnilladaerylluferaC
llawollofoteruliaF.reliobgnillatsni
esuacnacredroreporpnisnoitcurtsni
.htaedroyrujnilanosrep
A. Inspect shipment carefully for any signs of damage.
All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to carrier in good condition. Any claim for damage or shortage in shipment must be filed immediately against carrier by consignee. No claims for variances or shortages will be allowed by Boiler Manufacturer, unless presented within sixty (60) days after receipt of equipment.
B. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/ or CAN/CGA B149 Installation Codes. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME No. CSD-1.
C. Provide clearance between combustible material
and boiler jacket (following clearances are minimums):
1. USA, 805B-807B: listed for Alcove installation
a. Front: 18" b. Top: 36" c. Draft hood, rear, sides and flue connector: 6"
2. USA, 808B-810B: for installation in room which is large in comparison with size of boiler. a. Front: 18" b. Top: 51½" c. Draft hood, rear, sides, and flue connector: 6"
3. Canada, 805B-810B: a. Top and front: 18" (45.7cm) b. Flue, rear and sides: 6" (15.2cm)
D. Provide clearance for servicing and proper operation
(following clearances are recommended and may be reduced to minimum clearances shown above):
1. Single boiler, 805B-807B, Front/Top: 24" (61cm)
2. Single boiler, 808B-810B, Front/Top: 48" (122cm)
3. Multiple/modular boiler, USA/Canada, Sides: 1" (2.5cm)
E. Install boiler on level floor as close to chimney as
possible. For basement installation provide a solid base such as concrete or masonry construction if floor is not level or if water may be encountered on floor around boiler.
F. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, control replacement, etc.).
GNINRAW
noitallatsnirofdeifitrecngisedsiecnailppA
roF.ylnogniroolfelbitsubmocnonno
ylnogniroolfelbitsubmocnonoitallatsni
elbaTnidetsilesablaicepsnodellatsninehw .gnitepracnodellatsniebtontsumrelioB.2 sihcihwetercnocnodellatsnisireliobnehW
gnitlemottcejbussitahtlairetamarevo
laicepseht,).cte,gnibuttnaidarXEP,CVP(
tonsidapetercnocA.desuebtsumesab
.gniroolfelbitsubmoctcetorpottneiciffus
Table 2: Special Base Required for Installation on
Combustible Flooring
.oNledoMrelioBrebmuNtraPesaBlaicepS
B50855061816 B60856061816 B70857061816 B80858061816 B90859061816 B01850161816
G. Provide combustion and ventilation air in
accordance with applicable provisions of local building codes, or the National Fuel Gas Code, NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation; or CAN/CGA B149 Installation Codes, Part 5, Venting Systems and Air Supply for Appliances.
GNINRAW
rianoitalitnevdnanoitsubmocetauqedA
reporperussaotdedivorpebtsum
.noitsubmoc
The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through permanent openings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
6
Page 7
a. If result is greater than or equal to 50 ft³ per 1,000
Btuh, space is considered an unconfined space.
b. If result is less than 50 ft³ per 1,000 Btuh, space is
considered a confined space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and
b. Weather-stripping has been added on openable
windows and doors, and
c. Caulking or sealants applied in joints around
window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings.
5. For boiler located in an unconfined space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally provided by fresh air infiltration through cracks around windows and doors.
6. For boiler located in an unconfined space in a
building of unusually tight construction or in a confined space, provide outdoor air through
permanent opening(s) which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Minimum dimension of air opening(s) is 3" (7.6cm).
a. Two permanent openings: Locate one opening
within 12 " (30.5cm) of top of space. Locate remaining opening within 12" (30.5cm) of bottom of space. Size each opening per following:
i. Minimum free area of 1 square inch per 3,000
Btu per hour input of all equipment in space.
ii. Free area shall not be less than the sum of
the areas of all vent connectors in the confined space.
Alternate method for boiler located within confined space. Use indoor air if two permanent openings
communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and grilles must be fixed in open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
8. For Specially Engineered Installations. The above requirements shall be permitted to be waived where special engineering, consistent with good engineering practice and approved by the authority having jurisdiction, provides an adequate supply of air for combustion, ventilation, and dilution of flue gases.
i. Direct communication with outdoors.
Minimum free area of each opening must be 1 square inch per 4,000 Btu per hour input of all equipment in space.
ii. Vertical ducts. Minimum free area of each
opening must be 1 square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
iii. Horizontal ducts. Minimum free area of
each opening must be 1 square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
b. One permanent opening shall be permitted where
the boiler has clearances of at least 1" (2.5cm) from the sides and rear and 6" (15.2cm) from the front. Locate the opening within 12 " (30.5cm) of top of space. Size opening per following:
GNINRAW
rehtoroenilosagerehwreliobllatsnitonoD
fosecruosro,sdiuqilrosropavelbammalf
,srenaelc,sehcaelb.e.i(snobracordyh
cirbaf,srevomertniap,syarps,slacimehc
.derotsrodesuera).cte,srenetfos
ECITON
ehtotdragerhtiwreliobehtfognizis-siM
evissecxenitluserlliwdaolmetsysgnitaeh
tnenopmocdetareleccadnagnilcycreliob
tnarrawTONSEODmahnruB.eruliaf
reliobdezis-simybdesuacseruliaf
otreliobehtezisrevoTONOD.snoitacilppa
yltaergsreliobelpitlum/raludoM.metsyseht
.gnizisrevoreliobfodoohilekilehtecuder
7
Page 8
II. Boiler Assembly
A. Remove Crate (Semi-Pak and Packaged Only)
1. Remove all fasteners at crate skid.
2. Lift outside container and remove with all other inside protective spacers and bracing.
B. Remove boiler from skid. See Figure 2. Exercise care
to avoid dropping boiler.
1. Place boiler in approximate location. Refer to Section I: Pre-Installation. Remove base hold down bolts.
2. Using pry bar under rear corner of Base End Panel, raise boiler and install 1½" wood blocks under rear corners. Install ¾" pipe roller between Base and skid.
3. Remove 1½" wood blocks. Place 3" pipe roller on floor behind skid.
4. Roll boiler off skid. Move skid out of way.
Figure 2: Skid Removal
Table 3: Purpose of Tappings
gnippaTeziSesopruP
A"2ylppuS B"2nruteR C"¾evlaVfeileR D"¾timiL E"¾timiLyrailixuA F"¾tuohsaW G"¾niarD
Figure 3: Tapping Locations
8
Page 9
5. Roll boiler until 3" roller is located as shown. Use pry bar to install wood blocks under front corners of base. Remove 3" roller.
6. Lift boiler with pry bar. Remove wood blocks. Lower boiler.
C. For Packaged Boiler only, proceed to Paragraph E.
D. Test Section Assembly for leaks before connecting to
system and installing controls, trim and jacket. Refer to Figure 3 and Table 3.
1. Plug Tappings C & E (¾ NPT) and Return Tapping B (2 NPT).
2. Insert ¾" NPT x ¼" NPT bushing in Tapping D. Install pressure gauge capable of indicating 50 psi.
3. Insert 2" NPT x ¾" NPT bushing in Supply Tapping A. Install purge valve with a hose that runs to a drain.
4. Connect fill valve and piping to Drain Tapping G.
GNINRAW
.reliobtsetkaelotriaesutonoD
5. Fill boiler completely with water by venting air through purge valve. Close purge valve and apply water pressure of at least 10 psi but less than 50 psi gauge pressure.
6. Examine boiler for leaks or damage due to shipment or handling.
7. Remove plugs from Return Tapping B, Tapping C, and Tapping E (if second limit or operating control is used). Also remove fill valve and piping, purge valve and piping, and pressure gauge.
E. Install special base if installation is on combustible
flooring. See Figure 4. Floor shield adds 4¾" to boiler height.
1. Place special base on combustible floor with surface marked "FRONT" in upward position.
2. Locate special base with spacing to combustible materials as shown in Figure 4.
3. Place boiler on special base. Boiler must rest inside locating brackets. Boiler jacket panels will overhang special base.
4. Do not enclose boiler (including special base) on all four sides. Models 805B - 807B may be enclosed
Figure 4: Installation of Special Base for Combustible Flooring
9
Page 10
Figure 5: General Assembly (Knockdown Boilers)
on three sides (alcove) while maintaining clearances shown in Figure 4.
F. Move boiler to permanent location by sliding or
walking. DO NOT DROP.
For Packaged Boiler proceed to Section IV: Trim and Piping.
G. Install Canopy on section assembly. See Figure 5.
Canopy and hardware are located in Combination Boiler Parts and Control Carton.
1. Position Canopy on top of Section Assembly. Locate between end sections and sealing ledge on front and back of each section.
2. Fasten each end with ¼" - 20 x 1" carriage bolts, washers and nuts.
3. Seal between Canopy and Section Assembly with furnace cement.
H. Inspect joints between sections. They were factory
sealed. If any openings resulted during shipment or handling, reseal with furnace cement. Confirm tie rods are only hand tight to allow for thermal expansion.
I. Install Base Front Panel. See Figure 5. Panel and
hardware located in Combination Boiler Parts and Control Carton.
1. Attach Base Front Panel to Section Assembly using ¼" - 20 x 1¼" carriage bolts, washers and nuts.
2. Seal between top of Base Front Panel and Section Assembly with furnace cement (shipped in Combination Boiler Parts and Control Carton).
3. Seal between top of Base Rear Panel and Section Assembly with furnace cement.
J. Install Pilot/Main Burner Assembly. See Figure 7.
Assembly is located in Combination Boiler Parts and Control Carton. Verify assembly is properly located on support bracket in Base Rear Panel, seated on Main Burner Orifice, and secured with hitch pin clip.
K. Attach Flame Roll-out Switch to Burner Access
Panel. See Figure 6. Flame Roll-out Switch and hardware are located in Combination Boiler Parts and Control Carton. Flame Roll-out Switch is a single use device - do not test with heat - switch cannot be reset.
10
Page 11
Figure 6: Flame Roll-out Switch Installation
Figure 7: Burner/Burner Access Panel Installation
11
Page 12
1. Cut insulation from semicircular notch at right end of the burner access panel. Models 808B - 810B have two (2) burner access panels. Remove insulation from notch of right side burner access panel only.
2. Attach Flame Roll-out Switch Mounting Bracket to burner access panel with (1) #8 x ½" lg. sheet metal screw.
3. Attach Flame Roll-out Switch to mounting bracket with (1) #8 x ¾" lg. sheet metal screw.
L. Install Burner Access Panel(s). Locate Burner
Access Panel(s) in Combination Boiler Parts and Control Carton. Engage Burner Access Panel holes with projections on Base Front Panel. See Figure 6.
M. Install Immersion Well(s).
1. Remove Immersion Well(s) from Combination Boiler Parts and Control Carton..
2. Insert Immersion Well in Tapping D. See Figure 3.
3. If second limit or operating control is used, insert immersion well in Tapping E. If vertical gas piping is to be installed inside of boiler jacket, it is recommended that second limit be installed in system piping.
7. Attach Lower Front Tie Bar to Left Side and Right Side Panels.
8. Engage Upper Front Panel in slots on Left Side and Right Side Panels. Place Top Panel in position. Attach Top Panel to Left Side, Right Side and Upper Rear Panels.
9. Tighten all jacket screws.
10. Affix Lighting/Operating Instructions Label and Wiring Diagram Label to inside of Front Removable Door. Labels are located in Combination Boiler Parts and Control Carton.
O. Install Junction Box. See Figure 8. Attach junction
box to inside of Left Side Panel with ¼" - 20 x ¼" lg. machine screw (located in Combination Boiler Parts and Control Carton).
P. Install Limit Control. Locate limit in Combination
Boiler Parts and Control Carton. Insert limit probe into left immersion well as far as possible. Tighten set screw.
Q. Install Auxiliary Limit or operating control (if used).
Insert control probe into right immersion well as far as possible. Tighten set screw.
N. Install Jacket. See Figure 8.
1. Locate four (4) Jacket Attachment Brackets in Combination Boiler Parts and Control Carton. Attach to Front Base Panel and Rear Base Panels with #8 sheet metal screws. See Figure 5.
2. Hang Left Side Panel and Right Side Panel onto Jacket Attachment Brackets.
3. Attach Lower Rear Panel to Left and Right Side Panels. Do not tighten sheet metal screws.
4. Attach Upper Rear Panel to Lower Rear Panel. Do not install three (3) upper screws.
5. Remove Rating Label and Combustible Clearance Label from Combination Boiler Parts and Control Carton. Attach to Vestibule Panel in locations shown.
6. Attach Vestibule Panel to Left Side and Right Side Panels.
R. Install Gas Control Assembly. Refer to Section III,
Gas Control System Assembly (Knockdown Boilers).
S. EP and OP System: See Figure 9.
1. Install pre-wired EP/OP Control Cabinet Assembly to right front corner of jacket top panel.
2. Install Honeywell RM7890 Control (located in RM7890 Control Carton).
3. EP Only: Remove RM7890's Dust Cover. With a pair of side cutters, carefully snip both wire leads to the brown resistor labelled "JR2" and discard it. Replace Dust Cover.
4. Install Honeywell R7847 Flame Amplifier.
5. Install heat shield.
12
Page 13
Figure 8: Jacket Assembly
13
Page 14
Figure 9: EP/OP Control Installation
14
Page 15
III. Gas Control System Assembly (Knockdown Boilers)
A. 24V Standing Pilot Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 10. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Install pilot burner piping and controls. See Figure
10.
3. Connect Thermocouple Lead to Gas Valve.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
B. EI (Intermittent Ignition)
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 11. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Install pilot burner piping and controls.
a. Honeywell EI
i. USA - See Figure 12.
ii. Canada - See Figure 13.
b. Johnson EI
i. USA - See Figure 14.
ii. Canada - See Figure 15.
3. Install Ignition Module.
a. Attach Ignition Control Mounting Bracket to
Jacket Vestibule Panel using two (2) #8 x ½" sheet metal screws.
b. Attach Johnson Ignition Module to Mounting
Bracket using two (2) #6 x ¾" sheet metal screws or attach Honeywell Ignition Module to Mounting Bracket using two (2) #8 x ½" sheet metal screws.
c. Connect pilot ground wire and ignitor/sensor
lead(s) to ignition module. Refer to "Section VII: Electrical" for connection details.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box. See Figure 8.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
C. OP Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 16. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Install pilot burner piping and controls. See Figure
16.
3. Connect Thermocouple Lead to Gas Valve.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
D. OP-CSD-1 Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 17. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Mount pilot switch.
3. Install pilot burner piping and controls. See Figure
17.
4. Connect Thermocouple lead to pilot switch.
5. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
6. Attach transformer/control center to junction box.
E. EP Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 18.
2. Install pilot burner piping and controls. See Figure
18.
3. Install Ignition Transformer.
a. Attach Ignition Transformer to Jacket Vestibule
Panel using four (4) #8 x ½" lg. sheet metal screws.
b. Connect Ignition Lead from Pilot to Ignition
Transformer.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
15
Page 16
b. Attach transformer/control center to junction
box.
Panel using four (4) #8 x ½" lg. sheet metal screws.
F. EP-CSD-1 Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 19.
2. Install pilot burner piping and controls. See Figure
19.
3. Install Ignition Transformer.
a. Attach Ignition Transformer to Jacket Vestibule
b. Connect Ignition Lead from Pilot to Ignition
Transformer.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
16
Page 17
Figure 10: Schematic Gas Piping, 24V Standing Pilot, 806B & 807B
17
Page 18
Figure 11: Main Gas Piping, Intermittent Ignition (EI)
18
Page 19
Figure 12: Schematic Pilot Piping (Honeywell EI), USA
19
Page 20
Figure 13: Schematic Pilot Piping (Honeywell EI)
Canada: Natural Gas, 805B - 810B; LP Gas, 806B - 807B
20
Page 21
Figure 14: Schematic Pilot Piping (Johnson EI), USA
21
Page 22
Figure 15: Schematic Pilot Piping (Johnson EI)
Canada: Natural Gas, 805B - 810B; LP Gas, 806B - 807B
22
Page 23
Figure 16: Schematic Gas Piping, OP Control System, 806B - 810B
23
Page 24
Figure 17: Schematic Gas Piping, OP-CSD-1 Control System, 808B - 810B
24
Page 25
Figure 18: Schematic Gas Piping, EP Control System (Natural Gas Only), 806B - 810B
25
Page 26
Figure 19: Schematic Gas Piping, EP-CSD-1 Control System, 808B - 810B
26
Page 27
IV. Water Trim and Piping
.erutcurts
.retawfonoitidda
GNINRAW
roreliobotegamaddnanoitareporeporpminitluseryamreliobepipylreporpoteruliaF
reliobleetsdnanorifonoisorrocesuaclliwretawreliobfonoitanimatnocnegyxO
smelborprevoctonseodytnarraWs'mahnruB.eruliafreliobotdaelnacdna,stnenopmoc
tneuqerfybdesuacpu-dliub)emil(elacsroretawreliobfonoitanimatnocnegyxoybdesuac
A. Design and install boiler and system piping to prevent
oxygen contamination of boiler water and frequent water additions.
1. There are many possible causes of oxygen contamination such as:
a. Addition of excessive make-up water as a result
of system leaks.
b. Absorption through open tanks and fittings.
c. Oxygen permeable materials in the distribution
system.
2. In order to insure long product life, oxygen sources must be eliminated. This can be accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing fittings which allow
oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
f. Use properly designed and operating air
elimination devices in water piping.
B. Design system to obtain a 20°F temperature rise through
the boiler (see Table 4). If a temperature rise greater than 40°F is desired, consult Burnham.
C. Install Safety Relief Valve. See Figure 20. Components
are located in Water Trim Carton. Safety Relief Valve must be installed with spindle in vertical position.
1. Install ¾" NPT x 3½" lg. nipple in tapping "C". See Figure 3.
2. Install safety relief valve on ¾" NPT nipple.
GNINRAW
.tnemegnarragnipip
Table 4: Flow Rate, Temperature Rise, and
Pressure Drop
RELIOB
EZIS
B508
B608
B708
B808
B908
B018
WOLF
ETAR
)MPG(
12 41 01
62 71 31
13 12 51
73 42 81
24 82 12
74 13 32
.PMET
ESIR
URHT
RELIOB
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
.NIM
RELIOB
GNIPIP
)TPN(
"½1 "¼1 "¼1
"½1 "½1 "¼1
"2
"½1 "¼1
"2
"½1 "½1
"2 "2
"½1
"2 "2
"½1
tsumgnipipegrahcsidevlavfeilererusserP
erevesfolaitnetopehttahthcusdepipeb
ynaniepipTONOD.detanimilesisnrub
TONOD.ruccodluocgnizeerferehwaera
.spacrosgulp,sevlavffotuhsynallatsni
egrahcsidreporprofsedoClacoLtlusnoC
RELIOB
ERUSSERP
PORD
'3 '2 '1
'3 '2 '1
'3 '2 '1
'3 '2 '1
'3 '2 '1
'3 '2 '1
27
Page 28
Figure 20: Safety Relief Valve Installation
Figure 21: Drain Piping Installation
b. Insert Temperature-Pressure Gauge. Tighten by
applying pressure to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE CASE since this may ruin gauge calibration.
2. Alternate Temperature-Pressure Gauge Piping. See Figure 23.
a. Install 2 NPT x 10" Nipple into Supply Tapping
"A". See Figure 3.
b. Install 2 NPT x ¾ NPT x 2 NPT Tee (provided) or
2 NPT x 2 NPT x ¾ NPT Tee (installer furnished). ¾" NPT leg should face forward.
c. Install ¾ NPT x ¼ NPT Bushing.
d. Insert Temperature-Pressure Gauge. Tighten by
applying pressure to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE
CASE since this may ruin gauge calibration.
F. Connect system supply and return piping to boiler. See
Figure 25. Also consult I=B=R Installation and Piping Guides. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
1. If boiler is used in connection with refrigeration systems, boiler must be installed with chilled medium piped in parallel with heating boiler using appropriate valves to prevent chilled medium from entering boiler. See Figure 24. Also consult I=B=R Installation and Piping Guides.
2. If boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with flow control valves to prevent gravity circulation of boiler water during cooling system operation.
3. Use boiler bypass if boiler is operated in system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.). See Figure 25.
4. A hot water boiler installed above radiation level must be provided with a low water cutoff device as part of installation.
D. Install Drain Valve in rear of Left End Section, Tapping
"G". See Figure 21. Components are located in Water Trim Carton.
E. Install Temperature-Pressure Gauge. Components are
located in Water Trim Carton.
1. Standard Temperature - Pressure Gauge Piping. See Figure 22.
a. Install 2" NPT x 10" lg. nipple with gauge tapping
into Supply Tapping "A". See Figure 3. Gauge tapping should face forward.
5. A start-up strainer is recommended for practically all modular installations (new and replacement alike) to prevent system debris and sediment from ending up in the boilers where it will inhibit heat transfer and may eventually cause a cast iron section to crack from overheating.
G. Alliance Water Heater (if used). Refer to Alliance
Installation, Operating and Service Instructions for additional information. Install in same manner as space heating zone.
28
Page 29
Figure 22: Temperature-Pressure Gauge
Installation
Figure 23: Alternate Temperature-Pressure
Gauge Installation
Figure 24: Recommended Piping for Combination
Heating & Cooling (Refrigeration) System
29
Page 30
Figure 25: Recommended Boiler Piping for Circulator Zoned Heating Systems
30
Page 31
V. Gas Piping
GNINRAW
.daoldetcennoc
.reilppussagtlusnoC.dedeeneb
Size gas Piping. Design system to provide adequate
A.
gas supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum allowable gas valve inlet pressure is indicated on rating label.
2. Maximum gas demand. Table 5 lists boiler input rate. Also consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment)
3. Length of piping and number of fittings. Refer to Table 6 for maximum capacity of Schedule 40 pipe. Table 7 lists equivalent length for standard fittings.
4. Specific gravity of gas. Gas piping systems for gas with a specific gravity of 0.70 or less can be sized
otylppussagepipylreporpoteruliaF
dnanoitareporeporpminitluseryamreliob
syawlA.erutcurtsroreliobehtotegamad
eerfkaelyletulosbasignipipsagerussa
ehtrofepytdnaezisreporpehtfodna
yamrotalugererusserpsaglanoitiddanA
directly from Table 6, unless authority having jurisdiction specifies a gravity factor be applied. For specific gravity greater than 0.70, apply gravity factor from Table 8. If exact specific gravity is not shown choose next higher value.
For materials or conditions other than those listed above, refer to the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/CGA B149 Installation Codes, or size system using standard engineering methods acceptable to authority having jurisdiction.
B. Connect boiler gas valve to gas supply system.
GNINRAW
nosdnuopmocdaerhtreporpesuoteruliaF
foskaelnitluseryamsrotcennocsaglla
.sagelbammalf
GNINRAW
ebtsummetsysdnareliobotylppussaG
rognillatsniotroirpffotuhsyletulosba
.gnipipsagreliobgnicivres
Table 5: Rated Input
relioB
ledoM
rebmuN
B5084625.5011 B6080332311 B7086935.8511 B80826457.4811 B90882552.1121 B0184955.7321
larutaNenaporP/PL
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow the National
yticapaCdetaR
]ruohrepteefcibuc[
saG
noitcennoC
eziS
Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/ CGA B149 Installation Codes.
2. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas valve and outside jacket. See Figure 26.
4. All above ground gas piping upstream from manual gas valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as a grounding electrode. Refer to the National Electrical Code, ANSI/NFPA 70 and/or CSA C22.1 Electrical Code.
ECITON
neebevahlevelaesevobateef000,2nahtretaergsedutitlatanoitallatsniroftliubsreliobASU
ehtreplevelaesevobateef000,1reptnecrep4etartupnisagecuderotdecifiroyllaiceps
'sreliobnaidanaC.FxidneppAdna2.1.8noitceS,1.322ZISNA/45APFN,edoCsaGleuFlanoitaN
ehtybelbaifitnedierasledomreliobedutitlahgiH.lebalgnitarehtnodetacidnisignizisecifiro
)'0005-'0002=5,'0054-'0002=4(.lebalgnitarehtnotigidhtnins'rebmunledom
31
Page 32
Table 6: Maximum Capacity of Schedule 40 Pipe in CFH for Gas Pressures of 0.5 psig or Less
htgneL
]teeF[
01231872025050,1571063086004,1 0229091053037021052564059 033725158209579002573077 043603154200528071023066 056551151204437151582085 060550159100466831062035 07646908107316521042094 08340907105375811022064 09044806102335011502034
001839705150305301591004
Table 7: Equivalent Lengths of Standard Pipe Fittings & Valves
½¾ 1 ¼1½¾1¼1
porDerusserP.c.whcni3.0porDerusserP.c.whcni5.0
)nepOylluF(sevlaVsgnittiFdedaerhT
epiP
eziS
.D.I
sehcnIetaGebolGelgnA
gniwS
kcehC
°09
woblE
°54
woblE
wolF,eeT°09
nuRhguorhT
wolF,eeT°09
hcnarBhguorhT
"½226.053.06.813.93.46.187.00.11.3 "¾428.044.01.325.113.51.279.04.11.4 "1940.165.04.927.418.66.232.18.13.5
"¼1083.147.06.833.919.85.36.13.29.6
Table 8: Specific Gravity Correction Factors
cificepS
ytivarG
05.001.103.170.1
55.040.104.140.1
06.000.105.100.1
56.069.006.179.0
07.039.007.149.0
57.009.0
08.078.0
noitcerroC
rotcaF
cificepS
ytivarG
noitcerroC
rotcaF
.ecruosnoitingirehtoro
C. Pressure Test. The boiler and its gas connection must
be leak tested before placing boiler in operation.
1. Protect boiler gas valve. For all testing over ½ psig, boiler and its individual shut-off valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply piping by closing boiler's individual manual shut-off valve.
2. Locate leaks using approved combustible gas detector, soap and water, or similar nonflammable solution.
Figure 26: Recommended Gas Piping
32
GNINRAW
,semalfnepo,seldnac,sehctamesutonoD
Page 33
VI. Venting
A. Install vent system in accordance with local building
codes; or local authority having jurisdiction; or National Fuel Gas Code, ANSI Z223.1/NFPA 54, Part 7, Venting of Equipment and/or CAN/CGA B149 Installation Codes, Part 5, Venting Systems and Air Supply for Appliances. Install any of the following for this Series 8B Category I, draft hood equipped appliance:
1. Type B or Type L gas vent. Install in accordance with listing and manufacturer's instructions.
2. Masonry or metal chimney. Build and install in accordance with local building codes; or local authority having jurisdiction; or Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, ANSI/NFPA 211 and/or National Building Code of Canada.
Masonry chimney must be lined with approved clay flue lining or listed chimney lining system except as provided in ANSI Z223.1/NFPA 54, Paragraph
7.5.4(a): Exception: Where permitted by the
authority having jurisdiction, existing chimneys shall be permitted to have their use continued when an appliance is replaced by an appliance of similar type, input rating, and efficiency.
3. Single wall metal vent. Allowed by ANSI Z223.1/ NFPA 54 under very restrictive conditions.
B. Inspect chimney and remove any obstructions or
restrictions. Clean chimney if previously used for solid or liquid fuel-burning appliances or fireplaces.
top of boiler. On Knocked Down boilers, the assembly is located in Combination Boiler Parts and Control Carton.
1. Uncoil power cord.
2. Position mounting bracket onto lower edge of Draft Hood skirt. Locate center tooth (with #10 sheet metal screw) on outside and other two teeth inside Draft Hood skirt. See Figure 27.
3. Slide mounting bracket tight against lower edge of Draft Hood skirt. Position #10 sheet metal screw above skirt's stiffening rib.
4. Secure bracket in position by tightening #10 sheet metal screw against outer surface of Draft Hood skirt.
5. Insert excess power cord through Jacket Right Side Panel hole. Remove slack.
6. Position strain relief bushing around power cord. Pinch bushing's two halves together and snap back into hole in Jacket Right Side Panel.
7. Verify power cord, mounting bracket, and Blocked Vent Switch are secure and located as shown in Figure 27.
GNINRAW
tneVdekcolBtuohtiwreliobetarepotonoD
.dellatsniylreporphctiwS
REGNAD
gnillatsnierofebyenmihcgnitsixetcepsnI
detarofrepecalperronaelcoteruliaF.reliob
.htaed
C. Install Draft Hood on canopy outlet. Maintain height
from Jacket Top Panel to Draft Hood skirt as shown in Figure 1. DO NOT ALTER, CUT, OR MODIFY DRAFT HOOD.
GNINRAW
ynaecalprodoohtfardreliobretlatonoD
ehtnirepmaddevorppa-nonronoitcurtsbo
egallipssageulF.metsystnevrognihceerb
lliwnoitareporeliobefasnU.rucconac
.rucco
D. Install Blocked Vent Switch. The Blocked Vent Switch
Assembly consists of a strain relief bushing, power cord, and switch attached to mounting bracket. On Packaged boilers, the assembly is shipped attached to
royrujnierevesesuaclliwgninilelitroepip
Figure 27: Blocked Vent Switch Installation
33
Page 34
E. Boiler Equipped With Vent Damper. See Figure 28.
1. Open Vent Damper Carton and remove Installation Instructions. Read Installation Instructions thoroughly before proceeding.
NOITUAC
owtlortnocotrepmadtnevenoesutonoD
.secnailppagnitaeheromro
2. Vent damper must be same size as draft hood outlet. See Figure 1. Unpack vent damper carefully. Forcing vent damper open or closed may damage gear train and void warranty. Vent damper assembly includes pre-wired connection harness with polarized plug.
3. Mount vent damper assembly on draft hood without modification to either (Refer to instructions packed with vent damper for specific instructions). Vent damper position indicator to be visible to users.
NOITUAC
-gnicivresrofecnaraelcetauqedaedivorP neewtebecnaraelcmuminim"6edivorp .noitcurtsnocelbitsubmocdnarepmad
F. Install Vent Connector from draft hood or vent damper
to chimney. See Figure 29. For modular or multiple boiler installations, review "Multiple-Modular Manual for Series 8B Gas Boilers", P/N 8141615.
1. Do not connect into same leg of chimney serving an open fireplace.
2. Where two or more appliances vent into a common vent, the area of the common vent should at least equal the area of the largest vent plus 50 % of the area of the additional vents. Do not connect the vent of this appliance into any portion of mechanical draft system operating under positive pressure.
3. Vent connector should have the greatest possible initial rise above the draft hood consistent with the head room available and the required clearance from adjacent combustible building structure.
4. Install vent connector above bottom of chimney to prevent blockage - inspect chimney for obstructions or restrictions and remove - clean chimney if necessary.
5. Vent connector should slope upward from draft hood to chimney not less than one inch in four feet. No portion of vent connector should run downward or have dips or sags. Vent connector must be securely supported.
6. Use thimble where vent connector enters masonry chimney - keep vent connector flush with inside of flue liner.
7. Do not install Non-listed (AGA, CGA, CSA, ETL, or UL) vent damper or other obstruction in vent pipe.
8. Locate Boiler as close to Chimney as possible consistent with necessary clearances. See Section I: Pre-Installation.
Figure 28: Vent Damper Installation
34
Page 35
9. Design vent system for sea level input.
10. Provide adequate ventilation of Boiler Room. See Section I: Pre-Installation.
11. Never pass any portion of vent system through a circulating air duct or plenum.
G. If an Existing Boiler is Removed:
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system
GNINRAW
nommoceht,metsysgnitnevnommoc
.tiotdetcennoc
placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, or other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common
venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after
amorfdevomersireliobgnitsixenanehW
rofegralootebotylekilsimetsysgnitnev
gniniamersecnailppaehtfognitnevreporp
5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 7 and Part 11 in the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Figure 29: Typical Vent System
35
Page 36
VII. Electrical
.mrah
REGNAD
ecivresronoitallatsnignitpmettaerofebderewopnuerasnoitcennoclacirtcelellaerussaylevitisoP sexoblacirtcelellatuokcoL.gnidliubroreliobehtfosnoitcennocrostnenopmoclacirtcelefo
.ffodenrutsirewopecnokcoldaphtiw
GNINRAW
lacisyhpsuoiresnitluseryamreliobehtotsnoitcennoclacirtceleeriwylreporpoteruliaF
erofebffosirewopllaerusekaM.ecruosenonahterommorfebyamrewoplacirtcelE
.krowlacirtceleynagnitpmetta
.tcennocsiddesufdezisylreporpahtiwdetcetorpebtsumreliobhcaE
.slortnocgnitareporoytefasynaevitareponiekamrotuopmujreveN
reliobhcaE.ylnosesoprupecnereferroferalaunamsihtnideniatnocsmargaidgniriwehT
ehtdnamargaidsihtotrefeR.roodtnorfehtotdehcattamargaidgniriwahtiwdeppihssi
gniriwllawollofdnadnatsrednu,daeR.reliobehthtiwdesuslortnocynafomargaidgniriw
.slortnocehthtiwdeilppussnoitcurtsni
A. Install Boiler Wiring
1. Knockdown boilers only. Locate wiring harnesses in Combination Boiler Parts and Control Carton. Refer to Table 10 and connect wiring as shown on the appropriate wiring diagram.
2. Connect supply wiring and electrically ground boiler in accordance with requirements of authority having jurisdiction, or in absence of such requirements the National Electrical Code, ANSI/NFPA 70 and/or CSA C22.1 Electrical Code.
B. Wire Vent Damper (if used; required on 805, optional
on 806-810). See Figure 28.
1. Attach Vent Damper Harness to mounting hole in Jacket Left Side Panel. Install Cable Clamp around flexible conduit and attach to Jacket Top Panel.
2. Remove factory installed Jumper Plug from Vent Damper Receptacle on Vestibule Wiring Harness and discard.
3. Plug Vent Damper Harness Plug into Vent Damper Receptacle. See Figure 28.
C. Install thermostat. Locate on inside wall approximately
4 feet above floor. Do not install on outside wall, near fireplace, or where influenced by drafts or restricted air flow, hot or cold pipes, lighting fixtures, television, or sunlight. Allow free air movement by avoiding placement of furniture near thermostat.
Set heat anticipator to match control system requirements. Refer to Table 9.
D. Wire thermostat. Provide Class II circuit between
thermostat and boiler. Refer to appropriate wiring diagram for control system being used.
Figure 30: Vent Damper Schematic Wiring Diagram
36
Page 37
E. Alliance Water Heater (if used). May be used with
Intermittent Circulation only.
Refer to Alliance Installation, Operating and Service Instructions for wiring, piping and additional information.
F. Vent Damper Sequence of Operation. See Figure 30 for
schematic wiring diagram.
1. The Vent Damper is continuously powered at Terminal 1.
2. When there is a call for heat, the damper relay coil is energized through Terminal 5 if all limits ahead of the damper are satisfied.
3. The relay coil closes contacts which energize the damper motor, causing the damper to open.
4. When the damper blade reaches the fully open position, power is sent back to the ignition circuit
through Terminal 2 and the damper motor is de­energized.
5. When the call for heat is satisfied, the damper relay coil is de-energized - closing contacts which energize the damper motor. This causes the damper to close. When the damper blade reaches the fully closed position, the damper motor is de-energized.
POWER FAILURE - The damper blade will stop in the position it was in when power failed. (Combustion can never take place unless the damper blade is in the fully open position.)
G. Sequence of Operation and Wiring. Refer to Table 10
for the appropriate control system.
H. Optional Low-Water Cut-Off Wiring. See Figures 45
through 48.
Table 9: Heat Anticipator Settings
metsySlortnoC
toliPgnidnatSV421.13.0
)IE(noitingIcinortcelEV42
* ybgnittesrotapicitnataehecuder,gnitteserutarepmettatsomrehtevobadetaehsimoorfI
gnitteSrotapicitnAtaeH *
noitalucriCsuounitnoCnoitalucriCtnettimretnI
9.0:ASU
3.0
2.1:adanaC
esaercni,erutarepmetderisedgnihcaermoortuohtiwseclyctrohsreliobfI.spma2.0ro1.0
.spma2.0ro1.0ybgnittesrotapicitnataeh
37
Page 38
Table 10: Sequence of Operation and Wiring Diagrams
metsySnoitingIyrtnuoCleuFseziSrelioB
)V42(toliPgnidnatS
toliPgnidnatS
)V021--PO(
toliPgnidnatS
)V021--1-DSC-PO(
noitingItnettimretnI
)V42--IEllewyenoH(
noitingItnettimretnI )V42--IEnosnhoJ(
noitingItnettimretnI
)V021--PE(
&ASU
adanaC
&ASU
adanaC
ASUsaGPL.tceS01-833erugiF43erugiF14egaP
ASU
adanaC
ASU
adanaC
&ASU
adanaC
saGlarutaN
saGPL
saGlarutaN
saGPL
saGlarutaN
saGPL
saGlarutaN.tceS01-5
saGPL.tceS7-5
saGlarutaN
saGPL
saGlarutaN.tceS01-5
saGPL.tceS7-5
saGlarutaN.tceS01-634erugiF44erugiF45egaP
saGPLelbaliavAtoN
erugiFmargaiDgniriW
suounitnoCtnettimretnI
.tceS7&613erugiF23erugiF83egaP
.tceS01-633erugiF43erugiF14egaP
.tceS01-553erugiF63erugiF
73erugiF83erugiF
.tceS01-593erugiF04erugiF
14erugiF24erugiF
foecneuqeS
noitarepO
44egaP
94egaP
noitingItnettimretnI
)V021--1-DSC-PE(
ASUsaGlarutaN.tceS01-834erugiF44erugiF45egaP
1. Standing Pilot (24) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat. Vent Damper (if used) opens.
ii. Gas valves are energized allowing main gas
flow and ignition of main burners.
iii. Call or heat ends. Gas valves are de-
energized, extinguishing main flame. Vent Damper (if used) closes.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat, Vent Damper (if used) closes. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when excessive flue gas spillage occurs. Circulator
continues to operate and Vent Damper (if used) remains open with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when flames or excessive heat are present in vestibule. Circulator continues to operate and Vent Damper (if used) remains open with call for heat. Control is single use device. If flame roll-out switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and replace flame roll-out switch.
iv. Thermocouple: Senses pilot flame and
causes gas valves to turn off main burner and pilot burner gas flow should pilot burner flame extinguish. Circulator continues to operate and Vent Damper (if used) remains open with call for heat.
38
Page 39
Figure 31: Wiring Diagram, Standing Pilot (24), USA and Canada, Continuous Circulation
39
Page 40
Figure 32: Wiring Diagram, Standing Pilot (24V), USA and Canada, Intermittent Circulation
40
Page 41
2. Electronically Supervised Standing Pilot (OP) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat.
ii. Terminal #6 of RM7890C Burner Control is
energized, initiating a microcomputer monitored circuit test.
iii. Pilot Flame Establishing Period (PFEP)
begins.
iv. After pilot flame is proven, terminal #9 of
RM7890C is energized, allowing main gas flow and ignition of main burners. "Main" gas light will be illuminated.
v. Call for heat ends. Terminal #6 of RM7890C
is de-energized, in turn de-energizing gas valves and extinguishing main flame. "Main" gas light is de-energized.
3. Electronically Supervised Standing Pilot (OP-CSD-1) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat.
ii. Terminal #6 of RM7890C Burner Control is
energized, initiating a microcomputer monitored circuit test.
iii. Pilot Flame Establishing Period (PFEP)
begins.
iv. After pilot flame is proven, terminal #9 of
RM7890C is energized, allowing main gas flow and ignition of main burners. "Main" gas light will be illuminated.
v. Call for heat ends. Terminal #6 of RM7890C
is de-energized, in turn de-energizing gas valves and extinguishing main flame. "Main" gas light is de-energized.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when excessive flue gas spillage occurs. Circulator continues to operate with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when flames or excessive heat are present in vestibule. Circulator continues to operate with call for heat. Control is single use device. If flame roll-out switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and replace flame roll-out switch.
iv. RM7890C Burner Control: Automatically
interrupts main burner operation if a pilot flame is not detected during the four or ten second pilot flame establishing period. The RM7890C will lockout or recycle based on jumper settings. "Alarm" light will be illuminated. Refer to instructions supplied with RM7890C for additional control information.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when excessive flue gas spillage occurs. Circulator continues to operate with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when flames or excessive heat are present in vestibule. Circulator continues to operate with call for heat. Control is single use device. If flame roll-out switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and replace flame roll-out switch.
iv. RM7890C Burner Control: Automatically
interrupts main burner operation if a pilot flame is not detected during the four or ten second pilot flame establishing period. The RM7890C will lockout or recycle based on jumper settings. "Alarm" light will be illuminated. Refer to instructions supplied with RM7890C for additional control information.
v. Pilot Safety Switch: Automatically de-
energizes main gas valve and interrupts pilot gas supply if pilot flame is not detected at any time.
41
Page 42
Figure 33: Wiring Diagram, OP/OP-CSD-1 Ignition System, Continuous Circulation
42
Page 43
Figure 34: Wiring Diagram, OP/OP-CSD-1 Ignition System, Intermittent Circulation
43
Page 44
4. Honeywell EI Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat. Vent Damper (if used) opens.
ii. Ignition Module Terminals PV, MV/PV
and the Ignition Terminal are energized. Terminals PV and MV/PV power the Pilot Valve in the Gas Valve supplying gas to the Pilot. The Ignition Terminal supplies voltage to the Ignition Electrode creating an electric spark to ignite the Pilot.
iii. The sensing Circuit between the Q348 Pilot
Burner and the IGNITION MODULE proves the presence of the Pilot Flame Electronically and the Ignition Terminal is de-energized.
iv. Terminals MV and MV/PV of the
IGNITION MODULE are energized and supply power to the Main Gas Valve. The Gas Valve is energized allowing main gas flow, and ignition of Main Burners.
v. Call for heat ends. Ignition module is de-
energized, de-energizing gas valve, and extinguishing pilot and main flame. Vent Damper (if used) closes.
b. Safety Shutdown
i. Limit: Automatically interrupts power to
the Ignition Module and Gas Valve(s), extinguishing pilot and main flame, when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat, Vent Damper (if used) closes. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when
excessive flue gas spillage occurs. Circulator continues to operate and Vent Damper (if used) remains open with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out switch: Automatically
interrupts main burner operation when flames or excessive heat are present in vestibule. Circulator continues to operate, Vent Damper (if used) remains open with call for heat. Control is single use device. If flame roll-out switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and replace flame roll-out switch.
iv. Pilot
Pilot failure can occur during the start-up or
the operating cycle of the boiler. Any pilot failure of the Q348 Electronic Pilot, after ignition of pilot flame will close the main gas valve in 0.8 seconds.
For approximately 90 seconds after failure
of the Q348 pilot, the module through the ignition terminal will try to reestablish pilot flame. If no pilot flame can be sensed by the flame rod circuit, terminals PV and MV/PV are de-energized and the module will lock out on safety. Five to six minutes after shutdown, the IGNITION MODULE restarts the ignition sequence. The ignition trial, shutdown, and wait sequence continues until either the pilot lights or the Thermostat is set below room temperature (to end the call for heat). The ignition sequence can be reset by setting down the Thermostat for one minute.
c. Trouble Shooting Guide. See Page 71.
44
Page 45
Figure 35: Wiring Diagram, Honeywell EI, USA, Continuous Circulation
45
Page 46
Figure 36: Wiring Diagram, Honeywell EI, USA, Intermittent Circulation
46
Page 47
Figure 37: Wiring Diagram, Honeywell EI, Canada, Continuous Circulation
47
Page 48
Figure 38: Wiring Diagram, Honeywell EI, Canada, Intermittent Circulation
48
Page 49
5. Johnson EI Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat. Vent Damper (if used) opens.
ii. Ignition Module Terminals 1, GND and the
Ignition Terminal are energized. Terminals 1 and GND power the Pilot Valve in the Gas Valve supplying as to the Pilot. The Ignition Terminal supplies voltage to the Ignition Electrode creating an electric spark to ignite the Pilot.
iii. The sensing Circuit between the J991 Pilot
Burner and the IGNITION MODULE proves the presence of the Pilot Flame electronically and the Ignition Terminal is de-energized.
iv. Terminals 3 and GND of the IGNITION
MODULE are energized and supply power to the Main Gas Valve. The Gas Valve is energized allowing main gas flow, and ignition of Main Burners.
v. Call for heat ends. Ignition module is de-
energized, de-energizing gas valve, and extinguishing pilot and main flame. Vent Damper (if used) closes.
b. Safety Shutdown
i. Limit: Automatically interrupts power to the
Ignition Module and Gas Valve(s), extinguishing pilot and main flame, when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat, Vent Damper (if used) closes. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when
excessive flue gas spillage occurs. Circulator continues to operate, Vent Damper (if used) remains open with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out switch: automatically
interrupts main burner operation when flames or excessive heat are present in vestibule. Circulator continues to operate, Vent Damper (if used) remains open with call for heat. Control is single use device. If flame roll-out switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and replace flame roll-out switch.
iv. Pilot:
– Pilot failure can occur during the start-up or the operating cycle of the boiler. Any pilot failure of the J991 Electronic Pilot, after ignition of pilot flame will close the main gas valve.
– For approximately 90 seconds after failure of the J991 pilot, the module through the ignition terminal will try to reestablish pilot flame. If no pilot flame can be sensed by the flame rod circuit, terminals 1 and GND are de­energized and the module will lock out on safety. Five to six minutes after shutdown, the IGNITION MODULE restarts the ignition sequence. The ignition trial, shutdown, and wait sequence continues until either the pilot lights or the Thermostat is set below room temperature (to end the call for heat). The ignition sequence can be reset by setting down the Thermostat for one minute.
c. Trouble Shooting Guide. See Pages 72 and 73.
49
Page 50
Figure 39: Wiring Diagram, Johnson EI, USA, Continuous Circulation
50
Page 51
Figure 40: Wiring Diagram, Johnson EI, USA, Intermittent Circulation
51
Page 52
Figure 41: Wiring diagram, Johnson EI, Canada, Continuous Circulation
52
Page 53
Figure 42: Wiring Diagram, Johnson EI, Canada, Intermittent Circulation
53
Page 54
6. Electronically Supervised Intermittent Ignition (EP/EP-CSD-1) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat.
ii. Terminal #6 of RM7890A Burner Control is
energized, initiating a microcomputer monitored circuit test.
iii. The pilot valve (terminal 8) and ignition
transformer (terminal 10) are energized. The pilot valve opens and the ignition electrode sparks, igniting the pilot.
iv. After the pilot flame is proven, the ignition
terminal (10) is de-energized and the main valve terminal (9) is energized, allowing main gas flow and ignition of main burners. "Main" gas light will be illuminated.
v. When the call for heat ends, terminal #6 is
de-energized, extinguishing the pilot and main flames. "Main" gas light is de­energized.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with
call for heat. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when excessive flue gas spillage occurs. Circulator continues to operate with call for heat. If blocked vent switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when flames or excessive heat are present in vestibule. Circulator continues to operate with call for heat. Control is single use device. If flame roll-out switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and replace flame roll-out switch.
iv. RM7890A Burner Control: Automatically
interrupts main burner operation if a pilot flame is not detected during the four or ten second pilot flame establishing period. The RM7890A will lockout or recycle based on jumper settings. "Alarm" light will be illuminated. Refer to instructions supplied with RM7890A for additional control information.
54
Page 55
Figure 43: Wiring Diagram, EP/EP-CSD-1 Ignition System, USA, Continuous Circulation
55
Page 56
Figure 44: Wiring Diagram, EP/EP-CSD-1 Ignition System, USA, Intermittent Circulation
56
Page 57
Figure 45: McDonnell & Miller PS-851 (120V) L.W.C.O. Wiring for Boilers with 24V Limit Circuits
Figure 46: McDonnell & Miller PS-851 (120V) L.W.C.O. Wiring for Boilers with 120V Limit Circuits (OP & EP)
57
Page 58
Figure 47: Hydrolevel OEM - 170/550/650/750 (120V) L.W.C.O. Wiring for Boilers with 24V Limit Circuits
Figure 48: Hydrolevel OEM - 170/550/650/750 (120V) L.W.C.O. Wiring for Boilers with 120V Limit Circuits
58
Page 59
VIII. System Start-up
GNINRAW
llawollofdnadnatsrednu,daeryletelpmoC
erofeblaunamsihtnisnoitcurtsni
.putratsgnitpmetta
A. Safe operation and other performance criteria were met
with the gas manifold and control assembly provided on boiler when boiler underwent tests specified in
American National Standard for Gas-Fired Low­Pressure Steam and Hot Water Boilers, ANSI Z21.13.
B. Check Main Burners. Main burners must be properly
located on support bracket in Base Rear Panel, seated on Main Burner Orifices, and secured with hitch pin clips.
C. Verify that the venting, water piping, gas piping and
electrical system are installed properly. Refer to installation instructions contained in this manual.
D. Confirm all electrical, water and gas supplies are
turned off at the source and that vent is clear of obstructions.
E. FILL ENTIRE HEATING SYSTEM WITH WATER
and vent air from system. Use following procedure on a Series Loop or multi-zoned system installed as per Figure 25 to remove air from system when filling.
GNINRAW
sihtfoerusserpgnitarepomumixamehT
.erusserpsihtdeecxereveN.gisp05sireliob
.evlavfeilererusserpyfidomrogulptonoD
At completion, open all zone valves or shut-off valves.
9. Close purge valve, continue filling the system until the pressure gauge reads the desired cold fill pressure. Close fill valve.
(Note - If make-up water line is equipped with pressure reducing valve, adjust pressure reducing valve to desired cold fill pressure. Follow fill valve manufacturer’s instructions).
10. Open isolation valve in boiler supply piping.
11. Remove hose from purge valve.
F. Confirm that the boiler and system have no water leaks.
G. Prepare to check operation.
1. Obtain gas heating value (in Btu per cubic foot) from gas supplier.
2. Connect manometer to pressure tap on gas valve. Use 1/8 NPT tapping provided.
3. Temporarily turn off all other gas-fired appliances.
4. Turn on gas supply to the boiler gas piping.
5. Confirm that the supply pressure to the gas valve is 14 in. w.c. or less.
6. Open the field installed manual gas shut-off valve located upstream of the gas valve on the boiler.
7. Using soap solution, or similar non-combustible solution, electronic leak detector or other approved method. Check that boiler gas piping, valves, and all other components are leak free. Eliminate any leaks.
8. Purge gas line of air.
1. Close full port ball valve in boiler supply piping.
2. Isolate all zones by closing zone valves or shut-off valves in supply and return of each zone(s).
3. Attach a hose to the vertical purge valve located prior to the full port ball valve in the system supply piping. (Note - Terminate hose in five gallon bucket at a suitable floor drain or outdoor area).
4. Starting with one circuit at a time, open zone valve or shut-off valve in system supply and return piping.
5. Open purge valve.
6. Open fill valve (Make-up water line should be located directly after full port ball valve in system supply piping between air scoop and expansion tank).
7. Allow water to overflow from bucket until discharge from hose is bubble free for 30 seconds.
8. Close the open zone valve or shut-off valve for the zone being purged of air, then open the zone valve or shut-off valve for the next zone to be purged. Repeat this step until all zones have been purged.
REGNAD
H. Follow Lighting or Operating Instructions to place boiler
in operation. Refer to label on inside of Front Removable Panel or appropriate Figure as listed in Table 11.
Table 11: Lighting and Operating Instructions
rognithgiL
metsySnoitingI
toliPgnidnatS
)V42(
IEllewyenoH
IEnosnhoJ65erugiF PO15erugiF75erugiF PE25erugiF85erugiF
1-DSC-PO 1-DSC-PE85erugiF
59
gnitarepO
snoitcurtsnI
94erugiF45erugiF
05erugiF
35erugiF
rosemalfnepo,seldnac,sehctamesutonoD
.skaelrofkcehcotecruosnoitingirehto
emalFtoliP
noitartsullI
55erugiF
75erugiF
Page 60
Figure 49: Lighting Instructions (24V Standing Pilot)
60
Page 61
Figure 50: Operating Instructions (EI)
61
Page 62
Figure 51: Lighting Instructions (OP)
62
Page 63
Figure 52: Operating Instructions (EP)
63
Page 64
.1tolipdna)s(evlavffo-tuhsniamlaunamesolC
.2.hctiwscirtceleniamffonruT
.1tolipehtdnalaunamniamehthtobtahterusekaM
.2otslortnocgnitarepolladnatatsomrehtmoornruT
.3.)s(lenapsseccarenrubevomeR
SNOITCURTSNIGNITAREPORELIOB
:NWODTUHSOT
.)s(evlav
:PUTRATSOT
.setunimeviftsaeltarofffoneebevah)s(evlav
.gnittestsewol
.4
:ETON
.5dnahctiwsytefastolipgnidnatsnonottubsserpeD
.6.hctiwscirtceleniamnonruT .7.yalerdraugefasemalfnohctiwsytefasteseR .8noitacifitcergninrubtnatsnocthgilyletaidemmI
.a8)s(tolipnoitacifitcernoitingicirtceletnettimretnI
.9.)s(lenapsseccarenrubecalpeR
.)s(evlavtoliplaunamnepO
tolpgnidnatshtiwsreliobotylnoseilppa)5(metI
.)se(hctiwsytefas
tarofninottubgnidloh,tolipothctamdethgildloh
retfadethgilsniamertoliplitnuroetunimenotsael
gnidnatsgniniamerroftaepeR.desaelersinottub
.stolip
tonsitolipfI.hctamdethgilahtiwD971Q)s(tolip .detaeperebtsum)7(petS,sdnoces51nidethgil retfagninepo,citamotuaera)s(evlavtolipcirtcelE
.)metsyS"PO"(.)7(petS
rotatsomrehtnehwyllacitamotuaputhgilC971Q
.)metsyS"PE"(.taehrofsllaclortnocgnitarepo
.01.)s(evlavff-tuhsniamlaunamnepO
.11otslortnocgnitarepodnatatsomrehtmoortsujdA
Figure 53: Lighting / Operating Instructions (OP/EP-CSD-1)
.gnittesderised
64
Page 65
Figure 54: Honeywell Q314 Pilot Flame
(24V Standing Pilot)
Figure 57: Honeywell Q179D Pilot Flame (OP)
Figure 55: Honeywell Q348 Pilot Flame
(24V Electronic Ignition)
Figure 56: Johnson J991 Pilot Flame
(24V Electronic Ignition)
Figure 58: Honeywell Q179C Pilot Flame (EP)
I. Check pilot burner flame and main burner flames
through observation port.
1. Check pilot flame. Refer to Table 11 for appropriate pilot detail.
2. Adjust thermostat to highest setting.
3. Check main burner flames. See Figure 59. Flame should have clearly defined inner cones with no yellow tipping. Orange-yellow streaks caused by dust should not be confused with true yellow tipping.
65
Page 66
NOITUAC
tnemnorivnenanireliobsihtgnitarepodiovA
yrd,srebifnoitalusniesool,tsudwaserehw
sireliobfI.tneserpera.cte,tsudllaw
renrubeht,snoitidnocesehtrednudetarepo
dnadenaelcebtsumstropdnaroiretni
.noitareporeporperusniotyliaddetcepsni
Yellow-tipping indicates lack of primary air. Improper burner alignment on Main Burner Orifice will also affect primary air injection. Adjust primary air as follows:
a. Loosen lock screw.
b. Close air adjustment until yellow tips appear on
flames.
Figure 59: Main Burner Flame
c. Slowly open air adjustment until clearly defined
inner cones are visible.
d. Tighten lock screw.
4. Adjust thermostat to normal setting.
J. Check thermostat or operating control operation.
Raise and lower temperature setting to start and stop boiler operation.
K. Check ignition system shut-off.
1. Standing Pilot (24V): Disconnect thermocouple lead at Gas Valve. Gas Valve must close and pilot and main burners extinguish. If not, replace the gas valve.
2. Honeywell EI: Disconnect ignitor/sensor cable from Terminal (9) of ignition module. Gas valve must close and pilot and main burners extinguish. If not, measure voltage across gas valve terminals "TH" and "TR".
a. If voltage is not present, replace gas valve.
b. If voltage is present, replace ignition module.
3. Johnson EI: Disconnect sensor cable from Terminal 4 (SENSE). Gas valve must close and pilot and main burner extinguish. If not, measure voltage across gas valve terminals "TH" and "TR".
a. If voltage is not present, replace gas valve.
b. If voltage is present, replace ignition module.
4. EP and OP: Refer to instructions supplied with the Honeywell RM7890 Burner Control.
L. Check Limit(s).
1. Adjust thermostat to highest setting.
2. Observe temperature gauge. When temperature exceeds limit set point main burners should extinguish.
3. Adjust limit to setting above observed reading. Main burners should reignite.
4. Adjust thermostat to lowest setting. Adjust limit to desired setting.
M. Adjust gas input rate to boiler. Natural Gas.
1. Adjust thermostat to highest setting.
2. Check manifold gas pressure. Manifold pressure is listed on rating label. Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure can not be attained, check gas valve inlet pressure. If less than minimum gas supply pressure listed on rating label, contact gas supplier for assistance.
3. Clock gas meter for at least 30 seconds. Use Table 12 to determine gas flow rate in Cubic Feet per Hour.
4. Determine Input Rate. Multiply gas flow rate by gas heating value.
GNINRAW
lliwetartupnisagtsujdaylreporpoteruliaF
ehtfognirifrednurognirifrevonitluser
reliobefasnudnareporpmI.ecnailppa
.tluseryamnoitarepo
5. Compare measured input rate to input rate stated on rating label.
a. Boiler must not be overfired. Reduce input rate
by decreasing manifold pressure. Do not reduce more than 0.3 inch w.c. If boiler is still overfired, contact your Burnham distributor or Regional Office for replacement Gas Orifices.
66
Page 67
b. Increase input rate if less than 98% of rating plate
input. Increase manifold gas pressure no more than 0.3 inch w.c. If measured input rate is still less than 98% of rated input:
i. Remove Main Burners per procedure in
Section IX: Service.
ii. Remove gas orifices. Drill one (1) drill size
larger (drill size is stamped on orifice, or see Key No. 4E).
iii. Reinstall gas orifices and main burners.
Measure input rate.
6. Recheck Main Burner Flame.
7. Return other gas-fired appliances to previous conditions of use.
N. Adjust gas input rate to boiler. LP/Propane.
1. Set thermostat to highest setting.
2. Adjust tank regulator for gas valve inlet pressure of
13.5 inches w.c. or less.
3. Gas valve has step opening regulator which initially opens to 1.4 or 2.5 inch w.c. and steps to full pressure after approximately 30 seconds. Check manifold pressure after step has occurred. Adjust gas valve pressure regulator as necessary for 10.0 inches w.c. (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If 10.0 inches w.c. can not be attained, check gas valve inlet pressure. If less than 11.0 inches w.c., contact gas supplier for assistance.
O. Clean Heating System
Oil, grease, and other foreign materials which accumulate in new hot water boilers and a new or reworked system should be boiled out, and then thoroughly flushed. A qualified water treatment chemical specialist should be consulted for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations.
P. Check Damper Operation - If boiler is equipped with
vent damper, vent damper must be in open position when boiler main burners are operating. Start boiler, refer to instructions on damper to determine if damper is in full open position.
Q. Install Front Removable Panel.
1. Engage top flange (longer of 2 flanges) behind Upper Front Panel.
2. Swing lower portion of door toward boiler.
3. Lower door to engage bottom flange behind Lower Front Tie Bar.
Table 12: Input Rate
sdnoceS
enOrof
noituloveR
0306021042006 2365311522365 4335601212925 6305001002005 837459981474 045409081054 243468271034 441428461014 649387751193 847357051573 056327441063 255396831643 453376331333 652346921123 851326421013 060306021003 269285611092 469265211182 669245901372 868235601562 076215301752 275205001052 47428479342 67427459732 87326429132 08225409522
flaH-enO
.tF.uC
enO
.tF.uC
owT
.tF.uC
R. Combustion Chamber Burn-Off
1. The mineral wool combustion chamber panels contain a cornstarch based binder that must be burned out at installation to prevent odors during subsequent boiler operation.
2. Ventilate the boiler room, set the high limit to its maximum setting, set the thermostat to call for heat.
3. Allow the boiler to fire for at least an hour or until the odor from the cornstarch has dissipated.
4. Return the high limit and thermostat to their desired settings.
S. Review User's Information Manual and system
operation with owner or operator.
laiDreteMsaGfoeziS
eviF
.tF.uC
67
Page 68
IX. Service
GNINRAW
amorflennosrepdelliksdnadeniartybylnonekatrednuebdluohsreliobsihtnoecivreS
sihtnideificepsslavretnitademrofrepebdluohssnoitcepsnI.ycnegaecivresdeifilauq
.noitidnocelbigelanilaunamniatniaM.launam
elbammalfrehtodnaenilosag,slairetamelbitsubmocfoeerfdnaraelcaerareliobpeeK
.sdiuqildnasropav
dnanoitsubmocfowolfrednihlliwtahtmoorreliobnisnoitcurtsboynaecalptonoD
.rianoitalitnev
snoitcurtsniehtotnoitiddanieralaunamsihtnideniatnocsnoitcurtsniecivresehT
s'rerutcafunamtnenopmocwolloF.stnenopmocreliobehtforerutcafunamehtybdedivorp
.reliobehthtiwdedivorperewsnoitcurtsnis'rerutcafunamtnenopmoC.snoitcurtsni
,llatsnitonoD.gnissimerasnoitcurtsnifitnemecalperrofrerutcafunamtnenopmoctcatnoC
follagnidnatsrednudnagnidaertuohtiwreliobsihtecivresroniatniam,etarepo,putrats
detcennocsid,deretlahtiwetarepootreliobehtwollatonoD.snoitcurtsnitnenopmoceht
yllanigiroesohtotlacitnedistnenopmoctnemecalperesuylnO.stnenopmocderepmujro
.mahnruBybdeilppus
A. General. Inspection and service must be conducted
annually. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Lighting/Operating Instructions on inside of Front Removable Door.
GNINRAW
nehwnoitcennocsidotroirpseriwllalebaL esuacnacsrorregniriW.slortnocgnicivres
yfireV.noitareposuoregnaddnareporpmi
.gnicivresretfanoitareporeporp
B. Maintenance of Low Water Cut-off (if used). Follow
instructions provided with low water cut-off.
C. Vent System. Check for:
1. obstructions
2. accumulations of soot
3. deterioration of vent pipe or vent accessories due to condensation or other reasons
4. proper support—no sags, particularly in horizontal runs
5. tightness of joints. Remove all accumulations of soot with wire brush and vacuum
Remove all obstructions. Replace all deteriorated parts and support properly. Seal all joints.
D. Remove Main Burners for cleaning, changing orifice
plugs, or repairs.
1. Shut down gas boiler in accordance with Lighting/ Operating Instructions on inside of Front Removable Door. Close Manual Shut-off Valve.
2. Remove Front Removable Door. Raise Lower Front Tie Bar.
3. Disconnect ignition system.
4. Remove burner access panel(s).
5. Mark location of Main Burner with Pilot Bracket on manifold.
6. Remove hitch pin clips from Main Burner Orifices.
7. Hold Main Burner on throat. Lift slightly to raise rear of burner. Push to rear of boiler until burner clears Main Burner Orifice. Lift burners out.
8. Check burners to be sure they do not contain foreign matter or restrictions. Clean burners with a soft bristle brush, blow any dirt out with compressed air or use a vacuum cleaner. See Figure 60.
E. Clean Boiler Flueways.
1. Shut down gas boiler in accordance with Lighting/ Operating Instructions on inside of Front Removable Door. Close Manual Shut-off Valve.
2. Disconnect vent system. Remove Draft Hood.
3. Remove Jacket Top Panel.
4. Remove Canopy from top of boiler.
5. Thoroughly clean flueways with flue brush, removing all scale and soot. See Figure 60.
6. Clean boiler heating surface accessible from combustion chamber with straight handle wire brush.
7. Install Canopy. See Section II: Boiler Assembly, Paragraph G.
8. Install Jacket Top Panel, Draft Hood, Vent Damper (if used) and Vent System.
68
Page 69
noitamrofnIytefaStcudorPtnatropmI
tcudorPrebiFcimareCyrotcarfeR
Warning:
This product contains refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. After this product is fired, RCF may, when exposed to extremely high temperature (>1800F), change into a known human carcinogen. When disturbed as a result of servicing or repair, RCF becomes airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace previously fired RCF (combustion chamber insulation, target walls, canopy gasket, flue cover gasket, etc.) or attempt any service or repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing
machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an air tight plastic bag.
First Aid Procedures:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
69
Page 70
Figure 60: Boiler Flueway Cleaning
F. Clean Combustion Chamber by vacuuming. Exercise
care to avoid damaging Base Insulation.
G. Install Burners by reversing procedures used to
remove burners. Verify Main Burners are properly located on support bracket in Base Rear Panel, seated on Main Burner Orifices, and secured with hitch pin clips. Verify Main Burner with Pilot Bracket is in proper location. See Table 13.
H. Lubrication. Manufacturers Instruction should be
followed on all parts installed on boiler requiring lubrication. This includes type of lubricant to be used, frequency of lubrication, and points to lubricate.
I. Check operation. Refer to Section VIII: System Start-
up.
Table 13: Pilot Burner Location
B5085&4 B6086&5 B7087&6 B8087&6 B9087&6 B0188&7
.reliobfo
70
.oNledoMrelioB
*srenruB
neewteBdetacoLtoliP
tnorfmorfdeweivsathgirottfelderebmunsrenruB*
Page 71
Honeywell EI Trouble Shooting Guide
71
Page 72
Johnson EI Trouble Shooting Guide
72
Page 73
73
Page 74
SERVICE RECORD
DATE SERVICE PERFORMED
74
Page 75
SERVICE RECORD
DATE SERVICE PERFORMED
X. Repair Parts
All Series 8B Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408.
75
Page 76
metI
.oN
noitpircseD.oNtraP
B508B608B708B808B908B018
ytitnauQ
ylbmessAregnahcxEtaeH.1
50617161--------------­6061716---1-----------­7061716------1---------
1etelpmoC
8061716---------1-----­9061716------------1---
0161716---------------1 A1noitceSdnEtfeL1061717 111111 B1noitceSetaidemretnI3061717345678 C1noitceSdnEthgiR2061717 111111
doReiT230168081--------------­doReiT33016808---1------------
D1
E1rehsaW00606808 444444 F1tuN00406808 444444 G1"3,elppiNpilS200660780121416181
doReiT31016808------1--------­doReiT43016808---------1-----­doReiT53016808------------1--­doReiT63016808---------------1
76
Page 77
metI
.oN
noitpircseD.oNtraP
B508B608B708B808B908B018
ytitnauQ
yponaC.2
50611161-------------------­6061116----1----------------
A2yponaC
B2"1x02-¼,egairraC,tloB51106808 222222 C2talF"¼,rehsaW30606808 222222 D202-"¼,tuN70406808 222222
7061116--------1-----------­8061116------------1-------­9061116----------------1---­0161116--------------------1
77
Page 78
metI
.oN
noitpircseD.oNtraP
B508B608B708B808B908B018
ytitnauQ
.3ylbmessAesaB
A3lenaPdnEesaB1061817222222
250618162--------------­26061816---2------------
B3ylbmessAlennahCesaB
C3ylbmessAlenaPraeResaB
D3ylbmessAlenaPtnorFesaB
E3ylbmessAlenaPsseccArenruB
F3tekcarBtnemhcattAtekcaJ1061407444444 G3"¼1x02-¼,egairraC,tloB60106808444444 H3talF"¼,rehsaW30606808444444
J302-¼,tuN70406808444444
K3"½x02-¼,gnippaTfleS,wercS00706808344556
27061816------2--------­28061816---------2-----­29061816------------2--­20161816---------------2 150618161--------------­16061816---1-----------­17061816------1--------­18061816---------1-----­19061816------------1--­10161816---------------1 350618161--------------­36061816---1-----------­37061816------1--------­38061816---------1-----­39061816------------1--­30161816---------------1 450618161--------------­46061816---1-----------­47061816------1--------­48061816---------2-----­49061816------------2--­40161816---------------2
L3"¾x81-"61/5,daeHxeH,paC,wercS20316808222222
M3"¼1x81-"61/5,daeHxeH,paC,wercS11316808666666
N3"½x8#,lateMteehS,wercS00006808888888 P3talF"8/3,rehsaW00606808666666 Q381-"61/5,tuN30406808666666 R3"¾x02-¼,gnippaTfleS,wercS20706808010101010101
78
Page 79
metI
.oN
noitpircseD.oNtraP
B508B608B708B808B908B018
ytitnauQ
.4srenruBniaMdnadlofinaM
A4renruBniaM206132880121517191
gnidnatS,tekcarBtoliPhtiwrenruBniaM
)V42(toliP
IEllewyenoH,tekcarBtoliPhtiwrenruBniaM
B4
PO,tekcarBtoliPhtiwrenruBniaM
PE,tekcarBtoliPhtiwrenruBniaM
C4dlofinaM
D4)C4htiwdedulcnI(TPN8/1,gulPepiP--- 111111 E4
F4pilCniPhctiH40622891131618102
IEnosnhoJ,tekcarBtoliPhtiwrenruBniaM
*)ylnOsaGlarutaN(73#,ecifirOrenruBniaM106228 *)ylnOenaporP/PL(25#,ecifirOrenruBniaM146228
1061328---11111
4061328 111111
3061328---11111
150612281--------------­16061228---1-----------­17061228------1--------­18061228---------1-----­19061228------------1--­10161228---------------1
91131618102
* .yrotcaftlusnocedutitlAhgiHroF.)teef0002-0(edutitlalamronrofnwohssezisecifirorenrubniaM
79
Page 80
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
)PO,V42(toliPgnidnatS--niarTsaG1-5
saGPL&larutaN,noitceS7&6,adanaC&ASU:V42
saGPL&larutaN,noitceS01-6,adanaC&ASU:PO
A
TPN"¾,4201A5928VllewyenoH,evlaVsaGdioneloS 53206618B708-B608
B
TPN"1,2301A5928VllewyenoH,evlaVsaGdioneloS 63206618B018-B808
C TPN"1,M002nekilliM-namweN,evlaVffO-tuhSlaunaMdetacirbuL 916228
DTPN"¾xTPN"1,gnihsuBxeH 105006608B708&B6081
.gL"2xTPN"¾,elppiN 300006608B708&B6081
E
.gL"2xTPN"1,elppiN 400006608B018-B808
TPN"¾xTPN"1,woblEteertS 215106608B708&B608
F
TPN"1xTPN"¼1,woblEteertS 315106608B018-B808
TPN"1,saGlarutaN,C7S-CHRE0007wahstreboR,evlaVsaG 65106618
TPN"1,saGPL,C7S-PL-CHRE0007wahstreboR,evlaVsaG 75106618
B018-B6081
1
B018-B808
ylnOadanaC
1
1:ASU
2:adanaC
1
80
Page 81
METI
.ON
NOITPIRCSEDREBMUNTRAPYTITNAUQ
)1-DSC-PO(toliPgnidnatS--niarTsaG2-5
ylnOsaGPL,noitceS01,ylnOASU:1-DSC-PO
ATPN"1,saGPL,C7S-CHREVG0007wahstreboR,evlaVsaG 172066181
BTPN"1,2301A5928VllewyenoH,evlaVsaGdioneloS 632066181 CdetacirbuLffO-tuhSlaunaMevlaVTPN"1,20-304-05#oCarBnoC,5162281 D"8/1x"8/1,10-122-65#oCarBnoC,evlaVffo-tuhS/tseTkaeL 9762282
E"8/1,gulPepiP 4953066082
F"8/1x"4/1,gnihsuBxeH 0250066081 GgnoL"2x"1,elppiN 4000066082
H"1x°09,woblEteertS 4151066081
J"1,elppiNesolC 3300066081
K"1x"4/1-1,gnilpuoCelbaellaM 2052066081
LevlaVdioneloSotevlaVsaG,ssenraHgniriW 03263161 M424493#llewyenoH,gulPteltuOtoliP 15062281
81
Page 82
METI
.ON
NOITPIRCSED
)IE(noitingItnettimretnI-niarTsaG3-5
saGPLdnalarutaN,noitceS01-5:ASU
saGlarutaN,noitceS01-5:adanaC
saGPL,noitceS7-5
TPN"1,saGlarutaN,CHRED0007wahstreboR,evlaVsaG 15106618B018-B508
A
BacirbuLTPN"1,M002nekilliM-namweN,evlaVffO-tuhSlaunaMdet 916228 C.gL"2xTPN"1,elppiN 400006608
TPN"1,saGPL,PL-CHRED0007wahstreboR,evlaVsaG 85106618
TRAP
REBMUN
EZISYTITNAUQ
B018-B508:ASU
B708-B508:adanaC
B018-B808
ylnOadanaC
1
1
D
TPN"1,woblEteertS 415106608B708-B508
1
TPN"1xTPN"¼1,woblEteertS 315106608B018-B808
82
Page 83
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
)PE(noitingItnettimretnI-niarTsaG4-5
ylnOsaGlarutaN,noitceS01-6:adanaC&ASU
A TPN"1,saGlarutaN,C7S-CHREVG0007wahstreboR,evlaVsaG 86106618B018-B6081
B
C TPN"1,M002nekilliM-namweN,evlaVffO-tuhSlaunaMdetacirbuL 916228
DTPN"¾xTPN"1,gnihsuBxeH 105006608B708&B6081
.gL"2xTPN"¾,elppiN 300006608B708&B6081
E
.gL"2xTPN"1,elppiN 400006608B018-B808
TPN"¾xTPN"1,woblEteertS 215106608B708&B608
F
TPN"1xTPN"¼1,woblEteertS 315106608B018-B808
TPN"¾,4201A5928VllewyenoH,evlaVsaGdioneloS 53206618B708-B608
TPN"1,2301A5928VllewyenoH,evlaVsaGdioneloS 63206618B018-B808
1
B018-B808
ylnOadanaC
1
1:ASU
2:adanaC
1
83
Page 84
METI
.ON
NOITPIRCSEDREBMUNTRAPYTITNAUQ
)1-DSC-PE(noitingItnettimretnI-niarTsaG5-5
ylnOsaGlarutaN,noitceS01-8,ylnOASU
ATPN"1,saG.taN,C7S-CHREVG0007wahstreboR,evlaVsaG 861066181 BTPN"1,2301A5928VllewyenoH,evlaVsaGdioneloS 632066181 CdetacirbuLffO-tuhSlaunaMevlaVTPN"1,20-304-05#oCarBnoC,5162281 D"8/1x"8/1,10-122-65#oCarBnoC,evlaVffo-tuhS/tseTkaeL 9762282 E"8/1,gulPepiP 4953066082 F"8/1x"4/1,gnihsuBxeH 0250066081 GgnoL"2x"1,elppiN 4000066082 H"1x°09,woblEteertS 4151066081
J"1,elppiNesolC 3300066081
K"1x"4/1-1,gnilpuoCelbaellaM 2052066081
LevlaVdioneloSotevlaVsaG,ssenraHgniriW 03263161
M424493#llewyenoH,gulPteltuOtoliP 15062281
84
Page 85
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
)V42(toliPgnidnatS--gnipiPdnaylbmessAtoliP6-5
saGPLdnalarutaN,noitceS7&6:adanaC&ASU
A
BdaeL.gL"63/w6991A903QllewyenoH,elpuocomrehT4006328
CebuTDO"¼,noinUnoisserpmoCssarB8006328B708&B6081
DsaGlarutaN,TL21VRlortixaM,rotalugeR5006228
ETPN"8/1xebuTDO"¼,retpadAnoisserpmoCssarB036228
saGlarutaN,7863A413QllewyenoH,renruBtoliP3306328
llA1saGPL,8283A413QllewyenoH,renruBtoliP4306328
B708&B608:adanaC
ylnOsaGlarutaN
B708&B608:adanaC
ylnOsaGlarutaN
1
2
85
Page 86
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
ASU)IEllewyenoH(noitingItnettimretnI-gnipiPdnaylbmessAtoliP7-5
saGPLdnalarutaN,noitceS01-5
A
B2-308493llewyenoH,.gL"63,elbaCrosneS/retingI 12163281 CylbmessAeriWdnuorG 45063161 DebuTDO"¼,noinUnoisserpmoCssarB 80063281
saGlarutaN,2001A843QllewyenoH,renruBtoliP U2706328
1
saGPL,0101A843QllewyenoH,renruBtoliP 1806328
B018-B508
86
Page 87
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
adanaC)IEllewyenoH(noitingItnettimretnI--gnipiPdnaylbmessAtoliP8-5
saGlarutaN,noitceS01-5
saGPL,noitceS7-5
A
B63-008493llewyenoH,.gL"63,elbaCrosneS/retingI4806328 CylbmessAeriWdnuorG4506316 DebuTDO"¼,noinUnoisserpmoCssarB8006328B708-B5081 EL2PxessE,evlaVffo-tuhS546228
GdaeH.qS,TPN"8/1,gulPepiP805306608
HTPN"8/1xebuTDO"¼,retpadAnoisserpmoCssarB036228
J6-GW19HnosnhoJ,evlaVsaGdioneloS666228
L.gL"½1xTPN"½,elppiNtiudnoCdigiR9106318
M"½,tunkcoLtiudnoC02263182
N"½,gnihsuBgnitalusnIcitsalP43063181
PsaGlarutaN,TL21VRlortixaM,rotalugeR5006228
saGlarutaN,2001A843QllewyenoH,renruBtoliPU2706328B018-B508
saGPL,0101A843QllewyenoH,renruBtoliP1806328B708-B508
1
llA1
B018-B8081FelbaellaM,TPN"8/1,eeTepiP500106608
saGlarutaNB708-B5082 saGlarutaNB018-B8083
saGPLB708-B5081
1KpeeD"½1x.qS"4,xoBnoitcnuJ9526318
llA
B018-B508
ylnOsaGlarutaN
1
87
Page 88
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
ASU)IEnosnhoJ(noitingItnettimretnI--gnipiPdnaylbmessAtoliP9-5
saGPLdnalarutaN,noitceS01-5
saGlarutaN,5227WYL199JnosnhoJ,renruBtoliP
)daeLnoitingIsedulcnI(
A
saGPL,D0489WYL199JnosnhoJ,renruBtoliP
)daeLnoitingIsedulcnI( BC-AA57YnosnhoJ,eborPgnisneS 04063281 C63-HA75YnosnhoJ,daeLrosneS 15063281 DylbmessAeriWdnuorG 45063161 EebuTDO"¼,noinUnoisserpmoCssarB 80063281
0506328
1
6806328
B018-B508
88
Page 89
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
adanaC)IEnosnhoJ(noitingItnettimretnI--gnipiPdnaylbmessAtoliP01-5
saGlarutaN,noitceS01-5
saGPL,noitceS7-5
A
BC-AA57YnosnhoJ,eborPgnisneS 0406328 C63-HA75YnosnhoJ,daeLrosneS 15063281 DylbmessAeriWdnuorG 45063161
EebuTDO,noinUnoisserpmoCssarB 8006328B708-B5081
FL2PxessE,evlaVffo-tuhS 546228 GelbaellaM,TPN"8/1,eeTepiP 5001066081
HdaeH.qS,TPN"8/1,gulPepiP 8053066081
JTPN"8/1xebuTDO,retpadAnoisserpmoCssarB 036228
K6-GW19HnosnhoJ,evlaVsaGdioneloS 666228
LpeeD1x.qS"4,xoBnoitcnuJ 95263181 M.gL"½1xTPN"½,elppiNtiudnoCdigiR 91063181
N"½,tunkcoLtiudnoC 02263182
P"½,gnihsuBgnitalusnIcitsalP 43063181
QsaGlarutaN,TL21VRlortixaM,rotalugeR 5006228
)daeLnoitingIsedulcnI(
)daeLnoitingIsedulcnI(
saGlarutaN,5227WYL199JnosnhoJ,renruBtoliP
saGPL,D0489WYL199JnosnhoJ,renruBtoliP
0506328B018-B508
6806328B708-B508
1
1
llA
1
B018-B808
saG
larutaNB708-B508
larutaNB018-B808
saG
saGPLB708-B5081
llA
B018-B508
ylnOsaGlarutaN
2
3
1
1
89
Page 90
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
)PO(toliPgnidnatS--gnipiPdnaylbmessAtoliP11-5
saGPLdnalarutaN,noitceS01-6:adanaC&ASU
saGlarutaN,8001D971QllewyenoH,renruBtoliP5206328
A
saGPL,ecifirO
DK641883/w8001D971QllewyenoH,renruBtoliP
9306326
1
B
C.gL.tf4,0208921RllewyenoH,daeLdoRemalF165263171 D65373llewyenoH,rotcennoChajaR12063281 EylbmessAeriWdnuorG95263161
FebuTDO"¼,noinUnoisserpmoCssarB8006328
GsaGlarutaN,TL21VRlortixaM,rotalugeR5006228
HelbaellaM,TPN"8/1,eeTepiP500106608
JdaeH.qS,TPN"8/1,gulPepiP8053066081
KL2PxessE,evlaVffo-tuhS5462281
LTPN"8/1xebuTDO"¼,retpadAnoisserpmoCssarB036228
daeL
.gL"63/w6991A903QllewyenoH,elpuocomrehT
40063281
B018-B608
B018-B608:ASU
B708&B608:adanaC
B018-B608:adanaC
ylnOsaGlarutaN
B018-B808
ylnOadanaC
B708&B608
saGlarutaN
saGlarutaNB018-B8083
saGPLB018-B6081
1
1
1
2
90
Page 91
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
)1-DSC-PO(toliPgnidnatS--gnipiPdnaylbmessAtoliP21-5
ylnOsaGPL,noitceS01-8:ylnOASU
A BdaeL.gL"63/w6991A903QllewyenoH,elpuocomrehT 40063281 C.gL.tf4,0208921RllewyenoH,daeLdoRemalF 165263171 D65373llewyenoH,rotcennoChajaR 12063281 EylbmessAeriWdnuorG 95263161 FebuTDO"¼,noinUnoisserpmoCssarB 80063281 GsaGPL/.taN,TL21VRlortixaM,rotalugeR 50062281 HC3-BG-26LnosnhoJ,hctiwStoliP 831061081
J"8/1x"8/1,evlaVffO-tuhS/tseTkaeLoCarBnoC 9762281
KTPN"8/1xebuTDO"¼,retpadAnoisserpmoCssarB 0362282
saGPL,ecifirODK641883/w8001D971QllewyenoH,renruBtoliP 9306326
1
B018-B808
91
Page 92
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
)PE(noitingItnettimretnI--gnipiPdnaylbmessAtoliP31-5
ylnOsaGlarutaN,noitceS01-6:adanaC&ASU
AsaGlarutaN,9001C971QllewyenoH,renruBtoliP 7106328 B.gL.tf4,0208921RllewyenoH,daeLdoRemalF 165263171 C65373llewyenoH,rotcennoChajaR 12063282 D.gL.tf3,2101601RllewyenoH,daeLnoitingI 74263171 EylbmessAeriWdnuorG 95263161
FebuTDO"¼,gnilpuoCnoisserpmoCssarB 8006328
GL2PxessE,evlaVffo-tuhS 546228 HelbaellaM,TPN"8/1,eeTepiP 5001066081 JdaeH.qS,TPN"8/1,gulPepiP 8053066081
KTPN"8/1xebuTDO"¼,retpadAnoisserpmoCssarB 036228
L4-AW19HnosnhoJ,evlaVsaGdioneloS 266228
MpeeD"½1x.qS"4,xoBnoitcnuJ 95263181
N.gL"½1xTPN"½,elppiNtiudnoCdigiR 91063181 P"½,tunkcoLtiudnoC 02263182
B018-B608
B708&B608
adanaC&ASU
B018-B808
ylnOASU
B018-B808
ylnOadanaC
B708&B608 ylnOadanaC
B018-B808
ylnOadanaC
B018-B608
1
1
1
2
3
1
Q"½,gnihsuBgnitalusnIcitsalP 43063181
RsaGlarutaN,TL21VRlortixaM,rotalugeR 5006228
B018-B608
ylnOadanaC
1
92
Page 93
METI
.ON
NOITPIRCSED
TRAP
REBMUN
EZISYTITNAUQ
)1-DSC-PE(noitingItnettimretnI--gnipiPdnaylbmessAtoliP41-5
ylnOsaGlarutaN,noitceS01:ylnOASU
A,renruBtoliP9001C971QllewyenoHsaGlarutaN,7106328 B.gL.tF4,0208921RllewyenoH,daeLdoRemalF 165263171 C65373llewyenoH,rotcennoChajaR 12063282 D.gL.tF3,2101601RllewyenoH,daeLnoitingI 74263171 EylbmessAeriWdnuorG 95263161
FnoisserpmoCssarBebuTDO"4/1,gnilpuoC80063281
G"8/1x"8/1,kcoCffO-tuhS/tseTkaeLoCarBnoC 9762281
B018-808
HTPN"8/1xebuTDO"¼,retpadAnoisserpmoCssarB 0362282
JsaG4-GW19HnosnhoJ,evlaVdioneloS2662281
KpeeD"½1x.qS"4,xoBnoitcnuJ 95263181
L.gL"½1xTPN"½,elppiNtiudnoCdigiR 91063181
M"½,tunkcoLtiudnoC 02263182
N"½,gnihsuBgnitalusnIcitsalP 43063181 PlarutaN,TL21VRlortixaM,rotalugeRPL/saG50062281
1
93
Page 94
94
Page 95
metI
.oN
6etelpmoC
noitpircseD.oNtraP
B508B608B708B808B908B018
ytitnauQ
tekcaJ.6
150614061--------------­16061406---1-----------­17061406------1--------­18061406---------1-----­19061406------------1--­10161406---------------1 350614071--------------­36061407---1------------
A6ylbmessAlenaPpoTtekcaJ
B6lenaPraeRreppUtekcaJ
C6lenaPraeRrewoLtekcaJ
37061407------1--------­38061407---------1-----­39061407------------1--­30161407---------------1
550614061--------------­56061406---1------------
57061406------1--------­58061406---------1-----­59061406------------1--­50161406---------------1
650614061--------------­66061406---1------------
67061406------1--------­68061406---------1-----­69061406------------1--­60161406---------------1
450614061--------------­46061406---1------------
D6lenaPtnorFreppUtekcaJ
E6lenaPelbavomeRtnorFtekcaJ
47061406------1--------­48061406---------1-----­49061406------------1---
40161406---------------1 50614071--------------­6061407---1------------
7061407------1--------­8061407---------1-----­9061407------------1--­0161407---------------1
95
Page 96
metI
.oN
noitpircseDoNtraP.
B508B608B708B808B908B018
ytitnauQ
deunitnoC(tekcaJ.6)
F6lenaPediStfeLtekcaJ1061406 111111
G6lenaPediSthgiRtekcaJ2061406 111111
350614061-------------------­36061406----1---------------­37061406--------1------------
H6lenaPelubitseVtekcaJ
38061406------------1-------­39061406----------------1---­30161406--------------------1 250614071-------------------­26061407----1----------------
J6raBeiTtnorFrewoLtekcaJ
27061407--------1-----------­28061407------------1-------­29061407----------------1---­20161407--------------------1
96
Page 97
97
Page 98
metI
.oN
noitpircseD.oNtraP
B508B608B708B808B908B018
ytitnauQ
slortnoCsuoenallecsiMdnamirT.7
AllewyenoH,F°022-041,timiL
;)toliPgnidnatS&IE(8121D0804L
)PO&PE((2121B0804L
htpeD.lusnI"½1xTPN"¾,lleWnoisremmI 62406108 111111
B3311E6004LllewyenoH,teseRlaunaM,timiL30706108 111111
1BhtpeD.lusnI"3xTPN"¾,lleWnoisremmI 25406108 111111
CeguaGerusserP-erutarepmeTU9616508 111111
1CgnippaTeguaG/w"01xTPN2,elppiN1061608 111111
Disp05,TPN¾,evlaVfeileRytefaS20306618 111111
1D"½3xTPN¾,elppiN830006608 111111
E30-203-53oCarBnoC,TPN4/3,evlaVniarD160306608 111111
1E"½3xTPN¾,elppiN830006608 111111
2ETPN¾,gnilpuoC165206608 111111 FylbmessAtnemecalpeRhctiwStneVdekcolB8506106 111111 GhctiwStuo-lloRemalF44006108 111111
1GtekcarBgnitnuoMhctiwStuo-lloRemalF2161817 111111
HxoBnoitcnuJ0106318 111111
J
K)sdliubnoitalucriCsuounitnoC(AV05,remrofsnarT94206108 111111
)sdliubnoitalucriCtnettimretnI(
005D5828RllewyenoH,yaleR/remrofsnarT
15206108
111111
47406108
U55106108 111111
L
M
3001M0168SllewyenoH,eludoMnoitingI61106108
1-AGR577GnosnhoJ,eludoMnoitingIetanretlA48106108
repmaDtneVhtiwetelpmoC,ssenraHgniriWelubitseV
)detcipeDtoN()toliPgnidnatSdnaIE(gulPssapyB
111111
01061318111--------­11061318--------- 111
98
Page 99
metI
.8repmaDtneVcitamotuAdnadooHtfarD
A8dooHtfarD
B8
.oN
noitpircseD.oNtraP
B508B608B708B808B908B018
50611181--------------­4061118---*1-----------­7061118---**1-----------­3061118------*1--------­8061118------**1--------­2061118---------*1-----­8061118---------**1-----­1061118------------*1*1 9061118------------**1**1
"7,repmaDtneVcitamotuA
7-SK-PGVRlakiffE64161181---------------
"8,repmaDtneVcitamotuA
8-SK-PGVRlakiffE7416118---1------------
"9,repmaDtneVcitamotuA
9-SK-PGVRlakiffE8416118------11------
"01,repmaDtneVcitamotuA
01-SK-PGVRlakiffE9416118------------11
ytitnauQ
.ylnOadanaCrof**roylnO.A.S.Urof*htiwdekramsselnu,adanaCdna.A.S.UhtobniesurofstnenopmocllA
99
Page 100
TT
en Year Limited Warrantyen Year Limited Warranty
T
en Year Limited Warranty
TT
en Year Limited Warrantyen Year Limited Warranty
COMMERCIAL CAST IRON BOILERS — SERIES 5B, 8B, V9 and V11
Burnham Commercial™ hereby warrants to the original owner (“Owner”) of each Series 5B, 8B, V9, and V11 commercial cast iron boiler ( a “Boiler”) manufactured by Burnham Commercial, as follows:
First Year - Limited Warranty: Burnham Commercial warrants that each Boiler will comply, at the time of manufacture, with recognized hydronics industry regulatory standards and requirements as then in effect and will be free from defects in material and workmanship under normal usage for a period of one year from the date of original installation. Subject to all of the terms and conditions set forth below, if any Boiler, cast iron section, or component part covered by this warranty is found not to conform with this warranty during the one year warranty period, Burnham Commercial will, at its option, repair or replace the non-conforming Boiler, cast iron section, or covered component part.
Second through 10th Year - Limited Warranty for Cast Iron Sections: Burnham Commercial warrants that the cast iron sections of each Boiler will be free from defects in material and workmanship under normal usage for a period of ten years from the date of original installation. Subject to all of the terms and conditions set forth below, if any cast iron section covered by this warranty is found not to conform with this warranty during the warranty period, Burnham Commercial will, at its option, repair or replace the non-conforming cast iron section. The foregoing warranties are subject to the following terms and conditions:
Applicability. These warranties extend only to the original Owner at the
1.
original installation site and may not be assigned or otherwise transferred or extended to any other person or entity.
Claim Procedure. Owner must contact the original installer and provide
2.
the installer with a detailed description of the claimed defect. If the original installer is unable to resolve the matter to Owner’s satisfaction, Owner must notify Burnham Commercial in writing at Burnham Commercial, P.O. 3939, Lancaster, PA 17605, which notice must be received by Burnham Commercial prior to the expiration of the applicable warranty period. Owner must make the Boiler available for inspection by Burnham Commercial and, if requested to do so by Burnham Commercial, must return the Boiler, cast iron section or defective component part to Burnham Commercial, at Owner’s expense, for inspection and/or repair. Owner must cooperate with Burnham Commercial and take all commercially reasonable efforts to resolve and settle any dispute arising in connection with a warranty claim before resorting to legal remedies in court.
Conditions. The foregoing warranties are subject to the following
3.
conditions:
Installation Location. The Boiler must be installed within the
a.)
continental limits of the United States and Canada.
Proper Installation. The Boiler must be installed by a qualified heating
b.)
contractor (whose principal business is the sale, installation and maintenance of commercial boilers and related equipment) in strict accordance with the Installation and Operating Instructions Manual furnished with the Boiler and must not have been damaged prior to or during installation.
Annual Service. The Boiler (including its related burner, controls, and
c.)
other components and accessories) must be serviced annually by a qualified heating contractor (whose principal business is the sale, installation and maintenance of commercial boilers and related equipment) and proof of such service must be provided with each warranty claim. The required annual service must include all service and maintenance procedures specified in the Installation and Operating Instructions Manual furnished with the Boiler and all service and maintenance procedures specified in any instruction manual or similar document prepared by the manufacturer of the burner, controls and other components and accessories. Such annual service must also be performed in accordance with all applicable industry standards and procedures.
d.)
Proper Operation and Maintenance. The Boiler must be operated and
maintained in strict accordance with the Installation and Operating Instructions Manual furnished with the Boiler and all applicable industry standards and procedures.
No Alterations. The Boiler must not have been modified, altered or
e.)
changed in any manner.
f.) Proper Application. The Boiler must be used exclusively for purposes of commercial space heating or domestic hot water generation through a heat exchanger (or for a combination of such purposes).
Exclusions. The foregoing warranties do not cover claims arising from or
4.
relating to any of the following:
Component Parts and Accessories. Claims relating to component
a.)
parts and accessories manufactured by others are not covered by these warranties and will be subject only to the manufacturer’s warranty, if any.
Improper Installation. Claims arising from or relating to improper
b.)
installation are not covered by these warranties.
Natural Disasters. Claims arising from or relating to damage caused
c.)
by natural disasters, including, but not limited to, lightening, fire, earthquake, hurricane, tornado, or floods are not covered by these warranties.
Alterations. Claims arising from or relating to any alteration or other
d.)
modification not authorized by Burnham Commercial in writing are not covered by these warranties.
Misuse. The following claims are not covered by these warranties:
e.)
claims arising from or relating to (i) misuse, abuse, mishandling, accident, neglect or improper service or operation of a Boiler, including, but not limited to, improper burner adjustment, control setting or maintenance and thermal shock from low water temperatures; (ii) operation of a Boiler over its rated capacity; (iii) operation of a Boiler with insufficient water, excessive fresh make-up water or inadequately deareated water; (iv) freezing of a Boiler or any part or component thereof; (v) operation with combustion air contaminated externally by chemical vapors or other contaminants, (vi) use of improper fuel additives; or (vii) operation of a Boiler with inadequately or improperly treated water that causes deposit build-up in the cast iron sections or other Boiler components.
Subsequently Installed Accessories. Claims arising from or relating to
f.)
Boiler accessories (including, but not limited to, circulators, air elimination devices, deaerators, flow controls and low water cutoffs) which are installed by Owner after delivery of the Boiler are not covered by these warranties.
Exclusive Remedy. If any Boiler, cast iron section or covered
5.
component part fails to conform to these warranties, Owner’s exclusive remedy shall be to accept, at the option of Burnham Commercial, repair or replacement of the non-conforming Boiler, cast iron section or other component part. These warranties do not cover labor and other costs and expenses associated with the removal and replacement of a non-conforming Boiler, cast iron section or other component part, which costs and expenses shall be the sole responsibility of Owner.
Limitation of Damages. Under no circumstances shall Burnham
6.
Commercial be liable to Owner or to any other person for any indirect, incidental, special, consequential, or punitive damages of any kind whatsoever under these warranties or otherwise (including, without limitation, injury or damage to persons or property, loss of time or labor expense involved in repairing or replacing a non-conforming Boiler, loss of the use of the Boiler, and loss of profits, revenues or business, even if Burnham Commercial has been advised of the possibility of such damages), whether such damages are sought based upon breach of warranty, breach of contract, negligence, strict liability or any other legal theory. Burnham’s liability under these warranties shall under no circumstances exceed the purchase price paid by the Owner for the Boiler involved.
Exclusivity and Disclaimer. These warranties are given in lieu of all other
7.
express warranties and set forth the entire obligation of Burnham Commercial with respect to any defective or otherwise non-conforming Boiler and Burnham Commercial shall have no obligations, responsibilities or liabilities of any kind whatsoever, except as set forth herein. EXCEPT AS SET FORTH IN THESE WARRANTIES, BURNHAM MAKES NO OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, ANY IMPLIED WARRANTY OF MERCHANTABILITY, ANY IMPLIED WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE AND ANY OTHER IMPLIED WARRANTY ARISING OUT OF A COURSE OF DEALING OR PERFORMANCE, CUSTOM, USAGE OF TRADE OR OTHERWISE.
No Authority to Expand Warranty. No sales representative, agent or
8.
distributor or has authority to expand or otherwise modify in any way the scope of these warranties or the obligations of Burnham Commercial hereunder. No such modification shall be binding unless set forth in a written document signed by a duly authorized officer of Burnham Commercial.
Effective Date. This statement of warranties is effective as to all Boilers
9.
sold on or after July 17, 2000 and supersedes all prior warranty statements.
03/03
100
Loading...