Burnham 8H Series, 805H, 806H, 807H, 808H Installation And Operation Manual

...
Page 1
DNAGNITAREPO,NOITALLATSNI
ROFSNOITCURTSNIECIVRES
SEIRES 8H
RELIOBDERIF-SAG
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp
rebmuNledoMrelioB rebmuNlaireSrelioB etaDnoitallatsnI
____-_____8_ _______6
rotcartnoCgnitaeH rebmuNenohP
sserddA
Commercial Boilers
3050579
81416021R3-6/10
www.burnhamcommercialcastiron.com
Price - $5.00
1
Page 2
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment must be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The following terms are used throughout this manual to bring attention to the presence of
hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
CAUTION
NOTICE
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other
appliance.
If you smell gas vapors, DO NOT try to operate any appliance - DO NOT touch any electrical switch or use any phone in the building. Immediately, call the gas supplier from a remotely located phone. Follow the
gas supplier’s instructions or if the supplier is unavailable, contact the re department.
DO NOT install this boiler on combustible ooring, carpet, concrete over combustible ooring or wood,
nor on concrete over any heat affected material such as plastic piping or wiring without a properly in-
stalled combustible oor shield.
All Series 8H cast iron boilers are designed, built, marked and tested in accordance with the ASME Boiler and Pressure Vessel Code, Section IV, Heating Boilers. An ASME Data Label is factory applied to each 8H jacket, which indicates the boiler Maximum Allowable working Pressure (MAWP). Each cast iron section is permanently marked with the MAWP listed on the boiler’s ASME Data Label. The MAWP for all Series 8H Boiler is 50 psi (Water Only). It is common and acceptable practice to install these boilers in lower pressure systems, below the boiler MAWP. Therefore, in addition to Safety Relief Valves set for 50 psi, Burnham also offers Safety Relief Valves set for 30 psi (By Special Order Only).
2
NOTICE
Page 3
WARNING
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Read and understand the entire manual before attempting installation, start-up operation, or service. Installation and service must be performed only by an knowledgeable, experienced, and skilled installer or service agency.
This boiler must be properly vented.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
The interior of the venting system must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed venting system is necessary to allow noxious fumes that could cause injury or loss of life
to vent safely and will contribute toward maintaining the boiler’s efciency.
Installation is not complete unless a pressure relief valve is installed into the tapping located on the top of boiler - See the Water Trim and Piping Section of this manual for details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler.
This boiler contains components which become very hot when the boiler is operating. Do not touch any components unless they are cool.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing
or working nearby the appliance. Failure to follow all instructions in the proper order can cause personal injury or death. Read all instructions,
including all those contained in component manufacturers manuals which are provided with the boiler before installing, starting up, operating, maintaining or servicing.
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors or liquids.
Do not operate boiler with control which has been subject to water. All cover plates, enclosures and guards must be in place at all times.
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is complete.
USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been specially
oriced to reduce gas input rate 4 percent per 1,000 feet above sea level per the National Fuel Gas Code, NFPA 54/ANSI Z223.1, Section 8.1.2 and Appendix F. Canadian boilers’ orice sizing is indicated on the
rating label.
NOTICE
3
Page 4
Table of Contents
I. Pre-Installation .............................................................6
II. Boiler Assembly ...........................................................
III. Gas Control System Assembly ..................................
(Knockdown Boilers)
IV. Water Trim and Piping ...............................................
V. Gas Piping ..................................................................
VI. Venting .......................................................................
VII. Electrical ....................................................................
VIII. System Start-up ..........................................................
IX. Service .......................................................................
8
15
25
29
31
34
52
61
X. Repair Parts ................................................................
4
67
Page 5
Figure 1: Dimensional Data
Table 1: Dimensional Data
Dimensions (Inches)
Boiler
Model
D E
A B C
Recommended
Chimney Size
(Round)
USA Canada USA Canada
805H 20 10 7 24-13/16 24-13/16 16-1/8 16-1/8 7” dia. x 15 ft. 11.9 705
806H 23-3/4 11-7/8 8 27-13/16 25-3/4 18 16 8” dia. x 15 ft. 13.9 785
807H 27-1/2 13-3/4 9 28-13/16 25-3/4 18 16 8” dia. x 15 ft. 15.9 890
808H 31-1/4 15-5/8 9 30-13/16 26-11/16 20 16 8” dia. x 15 ft. 17.9 1000
809H 35 17-1/2 10 33-1/2 26-7/16 22 15 10” dia. x 15 ft. 19.9 1100
810H 38-3/4 19-3/8 10 33-1/2 26-7/16 22 15 10” dia. x 15 ft. 21.9 1220
Water
Content
(Gallons)
Weight (LB.)
Approx.
Shipping
5
Page 6
I. Pre-Installation
WARNING
Carefully read all instructions before installing boiler. Failure to follow all instructions in proper order can cause personal injury or death.
A. Inspect shipment carefully for any signs of damage.
All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to carrier in good condition. Any claim
for damage or shortage in shipment must be led
immediately against carrier by consignee. No claims for variances or shortages will be allowed by Boiler Manufacturer, unless presented within sixty (60) days after receipt of equipment.
B. Installation must conform to the requirements of
the authority having jurisdiction. In the absence of such requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/CSA B149.1 Installation Codes. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME No CSD-1.
C. Provide clearance between combustible material and
boiler jacket (following clearances are minimums):
1. USA, 805H-807H: listed for Alcove installation
a. Front: 18”
b. Top: 36”
c. Draft hood, rear, sides and ue connector: 6”
WARNING
Appliance is design certied for installation on noncombustible ooring only. For installation on combustible ooring only when installed on
special base listed in Table 2. Boiler must not be installed on carpeting. When boiler is installed on concrete which is over a material that is subject to melting (PVC, PEX radiant tubing, etc.), the special base must be used. A concrete pad is not
sufcient to protect combustible ooring.
Table 2: Special Base Required for Installation on
Combustible Flooring
Boiler Model Special Base Part Number
805H 61816055
806H 61816065
807H 61816075
808H 61816085
809H 61816095
810H 61816105
6
2. USA, 808H-810H: for installation in room which is large in comparison with size of boiler.
a. Front: 18”
b. Top: 51½”
c. Draft hood, rear, sides, and ue connector: 6”
3. Canada, 805H-810H:
a. Top and front: 18” (45.7 cm)
b. Flue, rear and sides: 6” (15.2 cm)
D. Provide clearance for servicing and proper operation
(following clearances are recommended and may be reduced to minimum clearances shown above):
1. Single boiler, 805H-807H, Front/Top: 24” (61.0 cm)
2. Single boiler, 808H-810H, Front/Top: 48”
(122.0 cm)
3. Multiple/modular boiler, USA /Canada, Sides: 1” (2.5 cm)
E. Install boiler on level oor as close to chimney as
possible. For basement installation provide a solid base
such as concrete or masonry construction if oor is not level or if water may be encountered on oor around
boiler.
F. Protect gas ignition system components from
water (dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, control replacement, etc.).
G. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes, or the National Fuel Gas Code, NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation; or CAN/ CSA B149.1, Venting Systems and Air Supply for Appliances.
WARNING
Adequate combustion and ventilation air must be
provided to assure proper combustion.
The following guideline is based on the
Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through permanent openings not furnished with doors) are considered part of space.
Volume [ft3] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
a. If result is greater than or equal to 50 ft3 per
1,000 BtuH, space is considered an unconned
space.
National Fuel
Page 7
b. If result is less than 50 ft3 per 1,000 Btuh, space
is considered a conned space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and
b. Weather-stripping has been added on openable
windows and doors, and
c. Caulking or sealants applied in joints around
window and door frames, between sole
plates and oors, between wall-ceiling joints,
between wall panels, at plumbing and electrical penetrations, and at other openings.
5. For boiler located in an unconned space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally
provided by fresh air inltration through cracks
around windows and doors.
6. For boiler located in an unconned space in a building of unusually tight construction or in a conned space, provide outdoor air through permanent opening(s) which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Minimum dimension of air opening(s) is 3” (7.6 cm).
a. Two permanent openings: Locate one opening
within 12 inches (30.5 cm) of top of space. Locate remaining opening within 12 inches (30.5 cm) of bottom of space. Size each opening per following:
i. Direct communication with outdoors.
Minimum free area of each opening must be 1 square inch per 4,000 Btu per hour input of all equipment in space.
ii. Vertical ducts. Minimum free area of each
opening must be 1 square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
iii. Horizontal ducts. Minimum free area of each
opening must be 1 square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
b. One permanent opening shall be permitted where
the boiler has clearances of at least 1” (2.5 cm) from the sides and rear and 6” (15.2 cm) from the front. Locate the opening within 12 inches (30.5 cm) of top of space. Size opening per following:
i. Minimum free area of 1 square inch per
3,000 Btu per hour input of all equipment in space.
ii. Free area shall not be less than the sum
of the areas of all vent connectors in the
conned space.
Alternate method for boiler located within conned
space. Use indoor air if two permanent openings communicate directly with additional space(s) of
sufcient volume such that combined volume of all spaces meet criteria for unconned space. Size each
opening for minimum free area of 1 square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects
and rodents. Louvers and grilles must be xed in
open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
8. For Specially Engineered Installations. The above requirements shall be permitted to be waived where special engineering, consistent with good engineering practice and approved by the authority having jurisdiction, provides an adequate supply of
air for combustion, ventilation, and dilution of ue
gases.
WARNING
Do not install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
NOTICE
Mis-sizing of the boiler with regard to the heating system load will result in excessive boiler cycling and accelerated component failure. Burnham DOES NOT warrant failures caused by mis-sized boiler applications. DO NOT oversize the boiler to the system. Modular/multiple boilers greatly reduce the likelihood of boiler oversizing.
7
Page 8
II. Boiler Assembly
A. Remove Crate
1. Remove all fasteners at crate skid.
2. Lift outside container and remove with all other inside protective spacers and bracing.
B. Remove boiler from skid. See Figure 2. Exercise care
to avoid dropping boiler.
1. Place boiler in approximate location. Refer to Section I: Pre-Installation. Remove base hold down bolts.
2. Using pry bar under rear corner of Base End Panel, raise boiler and install 1½” wood blocks under rear corners. Install ¾” pipe roller between Base and skid.
3. Remove 1½” wood blocks. Place 3” pipe roller on
oor behind skid.
4. Roll boiler off skid. Move skid out of way.
5. Roll boiler until 3” roller is located as shown. Use pry bar to install wood blocks under front corners of base. Remove 3” roller.
Figure 2: Skid Removal
Table 3: Purpose of Tappings
Tapping Size Purpose
8
Figure 3: Tapping Locations
A 2” Supply
B 2” Return
C 3/4” Relief Valve
D 3/4” Limit
E 3/4” Auxiliary Limit
F 3/4” Washout
G 3/4” Drain
Page 9
6. Lift boiler with pry bar. Remove wood blocks. Lower boiler.
C. For Packaged Boiler only, proceed to Paragraph E.
D. Test Section Assembly for leaks before connecting to
system and installing controls, trim and jacket. Refer to Figure 3 and Table 3.
1. Plug Tappings C & E (¾ NPT) and Return Tapping B (2 NPT).
2. Insert ¾” NPT x ¼” NPT bushing in Tapping D. Install pressure gauge capable of indicating 50 psi.
3. Insert 2” NPT x ¾” NPT bushing in Supply Tapping A. Install purge valve with a hose that runs to a drain.
4. Connect ll valve and piping to Drain Tapping G.
WARNING
Do not use air to leak test boiler.
5. Fill boiler completely with water by venting air through purge valve. Close purge valve and apply
water pressure of at least 10 psi but less than 50 psi gauge pressure.
6. Examine boiler for leaks or damage due to shipment or handling.
7. Remove plugs from Return Tapping B, Tapping C, and Tapping E (if second limit or operating control
is used). Also remove ll valve and piping, purge
valve and piping, and pressure gauge.
E. Install special base if installation is on combustible
ooring. See Figure 4. Floor shield adds 4¾” to boiler
height.
1. Place special base on combustible oor with surface
marked “FRONT” in upward position.
2. Locate special base with spacing to combustible materials as shown in Figure 4.
3. Place boiler on special base. Boiler must rest inside locating brackets. Boiler jacket panels will overhang special base.
4. Do not enclose boiler (including special base) on all four sides. Models 805H - 807H may be enclosed on three sides (alcove) while maintaining clearances shown in Figure 4.
Figure 4: Installation of Special Base for Combustible Flooring
9
Page 10
Figure 5: General Assembly (Knockdown Boilers)
F. Move boiler to permanent location by sliding or
walking. Do not drop.
For Packaged Boiler, proceed to Paragraph L.
G. Conrm that one (1) Flue Bafe is properly
positioned in each Boiler Flueway. Tabs at the top
of each Flue Bafe should be resting on top row of Flue
Pins on each adjoining section.
H. Install Canopy on section assembly. See Figure 5.
Canopy and hardware are located in Combination Boiler Parts and Control Carton.
1. Position Canopy on top of Section Assembly. Locate between end sections and sealing ledge on front and back of each section.
2. Fasten each end with ¼” - 20 x 1” carriage bolts, washers and nuts.
3. Seal between Canopy and Section Assembly with furnace cement.
I. Inspect joints between sections. They were factory
sealed. If any openings resulted during shipment or
handling, reseal with furnace cement. Conrm tie rods
are only hand tight to allow for thermal expansion.
J. Install Base Front Panel. See Figure 5. Panel and
hardware located in Combination Boiler Parts and Control Carton.
10
1. Attach Base Front Panel to Section Assembly using ¼” - 20 x 1¼” carriage bolts, washers and nuts.
2. Seal between top of Base Front Panel and Section Assembly with furnace cement (shipped in Combination Boiler Parts and Control Carton).
3. Seal between top of Base Rear Panel and Section Assembly with furnace cement.
K. Install Pilot/Main Burner Assembly. See Figure 7.
Assembly is located in Combination Boiler Parts and Control Carton. Verify assembly is properly located on support bracket in Base Rear Panel, seated on Main
Burner Orice, and secured with hitch pin clip.
L. Adjust Burner Air Shutters on all Burners. See
Figure 7. (On Packaged Boilers, Front Door and Burner Access Panel(s) must be removed to make adjustments.) Distance between front edge of Burner Air Shutter and burner mounting ring should be approximately 11/16”. To adjust this distance, loosen screw at top of air shutter and slide into correct position. Then tighten screw. (Replace Burner Access Panel(s) and Front Door on Packaged Boilers.)
For Packaged Boiler, proceed to Section IV: Water Trim
and Piping.
Page 11
Figure 6: Flame Roll-out Switch Installation
Figure 7: Burner/Burner Access Panel Installation
11
Page 12
M. Attach Flame Roll-out Switch to Burner Access Panel.
See Figure 6. Flame Roll-out Switch and hardware are located in Combination Boiler Parts and Control Carton. Flame Roll-out Switch is a single use device
- do not test with heat - switch cannot be reset.
1. Cut insulation from semicircular notch at right end of the burner access panel. Models 808H
- 810H have two (2) burner access panels. Remove insulation from notch of right side burner access panel only.
2. Attach Flame Roll-out Switch Mounting Bracket to burner access panel with (1) #8 x ½” lg. sheet metal screw.
3. Attach Flame Roll-out Switch to mounting bracket with (1) #8 x ¾” lg. sheet metal screw.
N. Install Burner Access Panel(s). Locate Burner Access
Panel(s) in Combination Boiler Parts and Control Carton. Engage Burner Access Panel holes with projections on Base Front Panel. See Figure 5.
O. Install Immersion Well(s).
1. Remove Immersion Well(s) from Combination Boiler Parts and Control Carton..
2. Insert Immersion Well in Tapping D. See Figure 3.
3. If second limit or operating control is used, insert immersion well in Tapping E. If vertical gas piping is to be installed inside of boiler jacket, it is recommended that second limit be installed in system piping.
P. Install Jacket. See Figure 8.
1. Locate four (4) Jacket Attachment Brackets in Combination Boiler Parts and Control Carton. Attach to Front Base Panel and Rear Base Panels with #8 sheet metal screws. See Figure 5.
2. Hang Left Side Panel and Right Side Panel onto Jacket Attachment Brackets.
3. Attach Lower Rear Panel to Left and Right Side Panels. Do not tighten sheet metal screws.
4. Attach Upper Rear Panel to Lower Rear Panel. Do not install three (3) upper screws.
5. Remove Rating Label from envelope marked “RATING LABEL ENCLOSED”. Remove
Combustible Clearance Label from Combination Boiler Parts and Controls Carton. Attach to Vestibule Panel in locations shown.
6. Attach Vestibule Panel to Left Side and Right Side Panels.
7. Attach Lower Front Tie Bar to Left Side and Right Side Panels.
8. Engage Upper Front Panel in slots on Left Side and Right Side Panels. Place Top Panel in position. Attach Top Panel to Left Side, Right Side and Upper Rear Panels.
9. Tighten all jacket screws.
10. Afx Lighting/Operating Instructions Label and
Wiring Diagram Label to inside of Front Removable Door. Labels are located in Combination Boiler Parts and Control Carton.
Q. Install Junction Box. See Figure 8. Attach junction
box to inside of Left Side Panel with ¼” - 20 x ¼” lg. machine screw (located in Combination Boiler Parts and Control Carton).
R. Install Limit Control. Locate limit in Combination
Boiler Parts and Control Carton. Insert limit probe into left immersion well as far as possible. Tighten set screw.
S. Install Auxiliary Limit or operating control (if used).
Insert control probe into right immersion well as far as possible. Tighten set screw.
T. Install Gas Control Assembly. Refer to Section III,
Gas Control System Assembly (Knockdown Boilers).
U. EP and OP System: See Figure 9.
1. Install pre-wired EP/OP Control Cabinet Assembly to right front corner of jacket top panel.
2. Install Honeywell RM7890 Control (located in RM7890 Control Carton).
3. Remove RM7890’s Dust Cover. With a pair of side cutters, carefully snip both wire leads to the brown resistor labelled “JR2” and discard it. Replace Dust Cover.
4. Install Honeywell R7847 Flame Amplier.
5. Install heat shield.
12
Page 13
Figure 8: Jacket Assembly
13
Page 14
14
Figure 9: EP/OP Control Installation
Page 15
III. Gas Control System Assembly (Knockdown Boilers)
A. 24V Standing Pilot Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 10. Use thread (joint) compound (pipe dope)
resistant to action of liqueed petroleum gas.
2. Install pilot burner piping and controls. See Figure
10.
3. Connect Thermocouple Lead to Gas Valve.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4” nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
B. EI (Intermittent Ignition)
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 11. Use thread (joint) compound (pipe dope)
resistant to action of liqueed petroleum gas.
2. Install pilot burner piping and controls.
a. Honeywell EI
i. USA - See Figure 12. ii. Canada - See Figure 13.
3. Install Ignition Module.
a. Attach Ignition Control Mounting Bracket to
Jacket Vestibule Panel using two (2) #8 x ½” sheet metal screws.
b. Attach Honeywell Ignition Module to Mounting
Bracket using two (2) #8 x ½” sheet metal screws.
c. Connect pilot ground wire and ignitor/sensor
lead(s) to ignition module. Refer to “Section VII: Electrical” for connection details.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box. See Figure 8.
a. Canada only - loop 4” nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
C. OP Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 14. Use thread (joint) compound (pipe dope)
resistant to action of liqueed petroleum gas.
2. Install pilot burner piping and controls. See Figure
14.
3. Connect Thermocouple Lead to Gas Valve.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4” nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
D. OP-CSD-1 Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 15. Use thread (joint) compound (pipe dope)
resistant to action of liqueed petroleum gas.
2. Mount pilot switch.
3. Install pilot burner piping and controls. See Figure
15.
4. Connect Thermocouple lead to pilot switch.
5. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
6. Attach transformer/control center to junction box.
E. EP Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 16.
2. Install pilot burner piping and controls. See Figure
16.
3. Install Ignition Transformer.
a. Attach Ignition Transformer to Jacket Vestibule
Panel using four (4) #8 x ½” lg. sheet metal screws.
b. Connect Ignition Lead from Pilot to Ignition
Transformer.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4” nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
15
Page 16
F. EP-CSD-1 Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 17.
2. Install pilot burner piping and controls. See Figure
17.
3. Install Ignition Transformer.
a. Attach Ignition Transformer to Jacket Vestibule
Panel using four (4) #8 x ½” lg. sheet metal screws.
b. Connect Ignition Lead from Pilot to Ignition
Transformer.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4” nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
16
Page 17
Figure 10: Schematic Gas Piping, 24V Standing Pilot, 806H & 807H
17
Page 18
18
Figure 11: Main Gas Piping, Intermittent Ignition (EI)
Page 19
Figure 12: Schematic Pilot Piping (Honeywell EI), USA
19
Page 20
20
Figure 13: Schematic Pilot Piping (Honeywell EI)
Canada: Natural Gas, 805H - 810H; LP Gas, 806H - 807H
Page 21
Figure 14: Schematic Gas Piping, OP Control System, 806H - 810H
21
Page 22
22
Figure 15: Schematic Gas Piping, OP-CSD-1 Control System, 808H - 810H
Page 23
Figure 16: Schematic Gas Piping, EP Control System (Natural Gas Only), 806H - 810H
23
Page 24
24
Figure 17: Schematic Gas Piping, EP-CSD-1 Control System, 808H - 810H
Page 25
IV. Water Trim and Piping
WARNING
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler failure. Burnham’s Warranty does not cover problems caused by oxygen contamination of
boiler water or scale (lime) build-up caused by frequent addition of water.
A. Design and install boiler and system piping to
prevent oxygen contamination of boiler water and frequent water additions.
1. There are many possible causes of oxygen contamination such as:
a. Addition of excessive make-up water as a result
of system leaks.
b. Absorption through open tanks and ttings.
c. Oxygen permeable materials in the distribution
system.
2. In order to insure long product life, oxygen sources must be eliminated. This can be accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing ttings which allow
oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
f. Use properly designed and operating air
elimination devices in water piping.
B. Design boiler piping and ow rate to obtain proper
temperature rise though the boiler. (See Table 4)
Table 4: Flow Rate, Temperature Rise, and
Pressure Drop
Boiler
Model
805H
806H
807H
808H
809H
810H
Flow Rate
(GPM)
21 14 10
26 17 13
31 20 15
36 24 18
40 27 20
45 30 22
Temp. Rise Thru Boiler
20° F 30° F 40° F
20° F 30° F 40° F
20° F 30° F 40° F
20° F 30° F 40° F
20° F 30° F 40° F
20° F 30° F 40° F
Min. Boiler
Piping NPT
1½” 1¼” 1¼”
1½” 1½” 1¼”
2” 1½” 1¼”
2” 1½” 1½”
2”
2” 1½”
2”
2” 1½”
Boiler
Pressure
Drop
3’ 2’ 1’
3’ 2’ 1’
3’ 2’ 1’
3’ 2’ 1’
3’ 2’ 1’
3’ 2’ 1’
WARNING
Pressure relief valve discharge piping must be piped such that the potential of severe burns is eliminated. DO NOT pipe in any area where freezing could occur. DO NOT install any shut off valves, plugs or caps. Consult Local Codes for proper discharge piping arrangement.
C. Install Safety Relief Valve. See Figure 18.
Components are located in Water Trim Carton. Safety Relief Valve must be installed with spindle in vertical position.
1. Install ¾” NPT x 3½” lg. nipple in tapping “C”. See Figure 3.
2. Install safety relief valve on ¾” NPT nipple.
Figure 18: Safety Relief Valve Installation
25
Page 26
Figure 19: Drain Piping Installation
D. Install Drain Valve in rear of Left End Section,
Tapping “G”. See Figure 19. Components are located in Water Trim Carton.
E. Install Temperature-Pressure Gauge. Components
are located in Water Trim Carton.
1. Standard Temperature - Pressure Gauge Piping. See Figure 20.
Figure 21: Alternate Temperature-Pressure Gauge
Installation
b. Install 2 NPT x ¾ NPT x 2 NPT Tee (provided)
or 2 NPT x 2 NPT x ¾ NPT Tee (installer furnished). ¾ NPT leg should face forward.
c. Install ¾ NPT x ¼ NPT Bushing.
d. Insert Temperature-Pressure Gauge. Tighten
by applying pressure to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE CASE since this may ruin gauge calibration.
F. Connect system supply and return piping to boiler.
See Figure 23. Also consult I=B=R Installation and Piping Guides. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
1. If boiler is used in connection with refrigeration systems, boiler must be installed with chilled medium piped in parallel with heating boiler using appropriate valves to prevent chilled medium from entering boiler. See Figure 22. Also consult I=B=R Installation and Piping Guides.
Figure 20: Temperature-Pressure Gauge
Installation
a. Install 2” NPT x 10” lg. nipple with gauge
tapping into Supply Tapping “A”. See Figure 3. Gauge tapping should face forward.
b. Insert Temperature-Pressure Gauge. Tighten
by applying pressure to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE CASE since this may ruin gauge calibration.
2. Alternate Temperature-Pressure Gauge Piping. See Figure 21.
a. Install 2 NPT x 10” Nipple into Supply Tapping
“A”. See Figure 3.
26
Figure 22: Recommended Piping for Combination
Heating & Cooling (Refrigeration) System
Page 27
2. If boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with
ow control valves to prevent gravity circulation of
boiler water during cooling system operation.
3. The piping diagrams shown (Figure 23, Detail “A” and Detail “B”) are recommended for optimum operation and long term reliability.
Burnham Commercial recommends maintaining
temperature differential (drop) across the system
at 40°F or less, and return water temperature at minimum of 135°F.
Continued boiler operation for prolonged periods of
time under conditions when temperature differential across the system exceeds 40°F and/or return water temperature stays below 135°F, may result in
premature boiler failure due to ue gas condensation
and/or thermal shock.
Pump ow rates and minimum boiler supply and
return pipe sizes are shown in Table 4.
Figure 23: Recommended Boiler Piping for Circulator Zoned Heating Systems
Detail “A”: Blend Pump Piping
Detail “B”: Primary/Secondary Piping
with By-Pass
27
Page 28
a. A boiler by-pass is recommended for any
installation for improved system temperature balance, while serving to protect the boiler from sustained condensing operation. The by-pass also provides some measure of low return water
temperature protection by reducing ow through
the boiler. See Figure 23.
b. A blend pump is recommended to divert hot
supply water into the return when system return temperatures can periodically dip below 135°F or when delta T’s rise beyond 40°F because of control schemes that shut off zone pumps for extended periods. See Figure 23, Detail “A”.
c. Primary/secondary piping with a by-pass is
recommended to provide two points of mixing when dual temperature systems are used (i.e. baseboard and radiant heat, outdoor reset and domestic hot water production, systems incorporating night setback or multiple zone pumps on clock schedules). See Figure 23, Detail “B”.
d. If system three-way valves are used for
temperature modulation, or if the system will
continuously run below 135°F for extended periods (due to low temperature applications like snowmelt, heat pump systems or others), primary/secondary boiler piping with a three­way valve and return temperature sensor is recommended. Refer to Burnham RTC Return Temperature Control Manual and Tekmar Essay #021 “Mixing Methods and Sizing of Variable Speed Injection Pumps” for more information on mixing devices and boiler protection from low return water temperature.
4. A hot water boiler installed above radiation level must be provided with a low water cutoff device as part of installation.
5. A start-up strainer is recommended for all installations (new and replacement alike) to prevent system debris and sediment from ending up in the boilers where it will inhibit heat transfer and may eventually cause a cast iron section to crack from overheating.
G. Alliance SL™ Water Heater (if used). Refer to
Alliance SL™ Installation, Operating and Service Instructions for additional information. Install in same manner as space heating zone.
WARNING
Burnham Commercial recommends maintaining temperature differential (drop) across the system at 40°F or less and return water temperature at minimum of 135°F.
Continued boiler operation for prolonged periods of time under conditions when temperature differential across the system exceeds 40°F and/or return water temperature stays below 135°F, may result in premature
boiler failure due to ue gas condensation and/or thermal shock.
If the above conditions exist, to protect a boiler from sustained ue gas condensation and/or thermal
shock, the above-recommended temperatures may be maintained by employing common industry-accepted mixing methods to provide boiler protection.
Some common methods are boiler by-pass piping, blend pumps, primary secondary piping with a by­pass, mixing valves and/or variable speed injection pumps.
28
Page 29
V. Gas Piping
WARNING
Failure to properly pipe gas supply to boiler may result in improper operation and damage to the boiler or structure. Always assure gas piping is absolutely leak free and of the proper size and type for the connected load.
An additional gas pressure regulator may be needed. Consult gas supplier.
A. Size gas Piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum allowable gas valve inlet pressure is indicated on rating label.
2. Maximum gas demand. Table 5 lists boiler input rate. Also consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment).
3. Length of piping and number of ttings. Refer to
Table 6 for maximum capacity of Schedule 40 pipe.
Table 7 lists equivalent length for standard ttings.
Table 5: Rated Input
Boiler
Model
805H 252 100.8 1
806H 315 126 1
807H 374 149.6 1
808H 433 173.2 1
809H 491 196.4 1
810H 550 220 1
Rated Capacity
(cubic feet per hour)
Natural LP / Propane
Gas
Connection
Size
4. Specic gravity of gas. Gas piping systems for gas with a specic gravity of 0.70 or less can be
sized directly from Table 6, unless authority having
jurisdiction species a gravity factor be applied. For specic gravity greater than 0.70, apply gravity factor from Table 8. If exact specic gravity is not
shown choose next higher value.
For materials or conditions other than those listed
above, refer to the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/CSA B149.1 Installation Codes, or size system using standard engineering methods acceptable to authority having jurisdiction.
WARNING
Failure to use proper thread compounds on all
gas connectors may result in leaks of ammable
gas.
WARNING
Gas supply to boiler and system must be absolutely shut off prior to installing or servicing boiler gas piping.
B. Connect boiler gas valve to gas supply system.
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or CAN/CSA B149.1 Installation Codes.
2. Use thread (joint) compound (pipe dope) resistant to
action of liqueed petroleum gas.
3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas valve and outside jacket. See Figure 24.
4. All above ground gas piping upstream from manual gas valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as a grounding electrode. Refer to the National Electrical Code, ANSI/NFPA 70 and/or CSA C22.1 Electrical Code.
USA boilers built for installation at altitudes greater than 2,000 feet above sea level have been specially
oriced to reduce gas input rate 4 percent per 1,000 feet above sea level per the National Fuel Gas Code, NFPA 54/ANSI Z223.1, Section 8.1.2 and Appendix F. Canadian boilers’ orice sizing is indicated on the rating label. High altitude boiler models are identiable by the model number’s tenth digit on the rating label.
(4=2000’ - 4500’, 5= 2000’ - 5000’)
NOTICE
29
Page 30
Table 6: Maximum Capacity of Schedule 40 Pipe in CFH for Gas Pressures of 0.5 psig or Less
Length
(Feet)
10 132 278 520 1,050 175 360 680 1,400
20 92 190 350 730 120 250 465 950
30 73 152 285 590 97 200 375 770
40 63 130 245 500 82 170 320 660
50 56 115 215 440 73 151 285 580
60 50 105 195 400 66 138 260 530
70 46 96 180 370 61 125 240 490
80 43 90 170 350 57 118 220 460
90 40 84 160 320 53 110 205 430
100 38 79 150 305 50 103 195 400
0.3 Inch w.c. Pressure Drop 0.5 Inch w.c. Pressure Drop
½ ¾ 1 ½ ¾ 1
Table 7: Equivalent Lengths of Standard Pipe Fittings & Valves
Pipe Size
½” 0.622 0.35 18.6 9.3 4.3 1.6 0.78 1.0 3.1
¾” 0.824 0.44 23.1 11.5 5.3 2.1 0.97 1.4 4.1
1” 1.049 0.56 29.4 14.7 6.8 2.6 1.23 1.8 5.3
1¼” 1.380 0.74 38.6 19.3 8.9 3.5 1.6 2.3 6.9
I.D.
(Inches)
Gate Globe Angle
Valves (Fully Open) Threaded Fittings
Swing
Check
90°
Elbow
45°
Elbow
90° Tee, Flow
Through Run
90° Tee, Flow
Through Branch
Table 8: Specic Gravity Correction Factors
Specic
Gravity
0.50 1.10 1.30 1.07
0.55 1.04 1.40 1.04
0.60 1.00 1.50 1.00
0.65 0.96 1.60 0.97
0.70 0.93 1.70 0.94
0.75 0.90 --- ---
0.80 0.87 --- ---
Correction
Factor
Specic
Gravity
Correction
Factor
C. Pressure Test. The boiler and its gas connection must
be leak tested before placing boiler in operation.
1. Protect boiler gas valve. For all testing over ½ psig, boiler and its individual shut-off valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply piping by closing boiler’s individual manual shut-off valve.
2. Locate leaks using approved combustible gas
detector, soap and water, or similar nonammable
solution.
WARNING
Do not use matches, candles, open ames, or
other ignition source.
Figure 24: Recommended Gas Piping
30
Page 31
VI. Venting
A. Install vent system in accordance with local building
codes; or local authority having jurisdiction; or National Fuel Gas Code, ANSI Z223.1/NFPA 54, Part 7, Venting of Equipment and/or CAN/CSA B149.1, Venting Systems and Air Supply for Appliances. Install any of the following for this Series 8H Category I, draft hood equipped appliance:
1. Type B or Type L gas vent. Install in accordance with listing and manufacturer’s instructions.
2. Masonry or metal chimney. Build and install in accordance with local building codes; or local authority having jurisdiction; or Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, ANSI/NFPA 211 and/or National Building Code of Canada.
Masonry chimney must be lined with approved
clay ue lining or listed chimney lining system
except as provided in ANSI Z223.1/NFPA 54, Paragraph 7.5.4(a): Exception: Where permitted by
the authority having jurisdiction, existing chimneys shall be permitted to have their use continued when an appliance is replaced by an appliance of similar
type, input rating, and efciency.
3. Single wall metal vent. Allowed by ANSI Z223.1/ NFPA 54 under very restrictive conditions.
B. Inspect chimney and remove any obstructions or
restrictions. Clean chimney if previously used for solid
or liquid fuel-burning appliances or replaces.
1. Uncoil power cord.
2. Position mounting bracket onto lower edge of Draft Hood skirt. Locate center tooth (with #10 sheet metal screw) on outside and other two teeth inside Draft Hood skirt. See Figure 25.
3. Slide mounting bracket tight against lower edge of Draft Hood skirt. Position #10 sheet metal screw above skirt’s stiffening rib.
4. Secure bracket in position by tightening #10 sheet metal screw against outer surface of Draft Hood skirt.
5. Insert excess power cord through Jacket Right Side Panel hole. Remove slack.
6. Position strain relief bushing around power cord. Pinch bushing’s two halves together and snap back into hole in Jacket Right Side Panel.
7. Verify power cord, mounting bracket, and Blocked Vent Switch are secure and located as shown in Figure 25.
WARNING
Do not operate boiler without Blocked Vent Switch Properly installed.
DANGER
Inspect existing chimney before installing boiler. Failure to clean or replace perforated pipe or tile lining will cause severe injury or death.
C. Install Draft Hood on canopy outlet. Maintain height
from Jacket Top Panel to Draft Hood skirt as shown in Figure 1. DO NOT ALTER, CUT, OR MODIFY DRAFT HOOD.
WARNING
Do not alter boiler draft hood or place any obstruction or non-approved damper in the breeching or vent system. Flue gas spillage can occur. Unsafe boiler operation will occur.
D. Install Blocked Vent Switch. The Blocked Vent
Switch Assembly consists of a strain relief bushing, power cord, and switch attached to mounting bracket. On Packaged boilers, the assembly is shipped attached to top of boiler. On Knocked Down boilers, the assembly is located in Combination Boiler Parts and Control Carton.
Figure 25: Blocked Vent Switch Installation
31
Page 32
E. Boiler Equipped With Vent Damper. See Figure 26.
1. Open Vent Damper Carton and remove Installation Instructions. Read Installation Instructions thoroughly before proceeding.
CAUTION
Do not use one vent damper to control two or more heating appliances.
2. Vent damper must be same size as draft hood outlet. See Figure 1. Unpack vent damper carefully. Forcing vent damper open or closed may damage gear train and void warranty. Vent damper assembly includes pre-wired connection harness with polarized plug.
3. Mount vent damper assembly on draft hood without
modication to either (Refer to instructions packed with vent damper for specic instructions). Vent
damper position indicator to be visible to users.
WARNING
Provide adequate clearance for servicing -
provide 6” minimum clearance between damper and combustible construction.
F. Install Vent Connector from draft hood or vent
damper to chimney. See Figure 27.
1. Do not connect into same leg of chimney serving an
open replace.
2. Where two or more appliances vent into a common vent, the area of the common vent should at least equal the area of the largest vent plus 50 % of the area of the additional vents. Do not connect the vent of this appliance into any portion of mechanical draft system operating under positive pressure.
3. Vent connector should have the greatest possible initial rise above the draft hood consistent with the head room available and the required clearance from adjacent combustible building structure.
4. Install vent connector above bottom of chimney to prevent blockage - inspect chimney for obstructions or restrictions and remove - clean chimney if necessary.
5. Vent connector should slope upward from draft hood to chimney not less than one inch in four feet. No portion of vent connector should run downward or have dips or sags. Vent connector must be securely supported.
6. Use thimble where vent connector enters masonry
chimney - keep vent connector ush with inside of ue liner.
7. Do not install Non-listed (AGA, CGA, CSA, ETL, or UL) vent damper or other obstruction in vent pipe.
8. Locate Boiler as close to Chimney as possible consistent with necessary clearances. See Section I: Pre-Installation.
32
Figure 26: Vent Damper Installation
Page 33
9. Design vent system for sea level input.
10. Provide adequate ventilation of Boiler Room. See Section I: Pre-Installation.
11. Never pass any portion of vent system through a circulating air duct or plenum.
WARNING
When an existing boiler is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
G. If an Existing Boiler is Removed:
At the time of removal of an existing boiler,
the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, or other
deciencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common
venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close
replace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after
5 minutes of main burner operation. Use the ame
of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers and
any other gas-burning appliance to their previous condition of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 7 and Part 11 in the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Figure 27: Typical Vent System
33
Page 34
VII. Electrical
DANGER
Positively assure all electrical connections are unpowered before attempting installation or service of electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock once power is turned off.
WARNING
Failure to properly wire electrical connections to the boiler may result in serious physical harm.
Electrical power may be from more than one source. Make sure all power is off before attempting any electrical work.
Each boiler must be protected with a properly sized fused disconnect. Never jump out or make inoperative any safety or operating controls. The wiring diagrams contained in this manual are for reference purposes only. Each boiler is shipped with
a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any controls used with the boiler. Read, understand and follow all wiring instructions supplied with the controls.
A. Install Boiler Wiring
1. Knockdown boilers only. Locate wiring harnesses in Combination Boiler Parts and Control Carton. Refer to Table 10 and connect wiring as shown on the appropriate wiring diagram.
2. Connect supply wiring and electrically ground boiler in accordance with requirements of authority having jurisdiction, or in absence of such requirements the National Electrical Code, ANSI/NFPA 70 and/or CSA C22.1 Electrical Code.
B. Wire Vent Damper (if used; required on 805H,
optional on 806H - 810H). See Figure 26.
1. Attach Vent Damper Harness to mounting hole in Jacket Left Side Panel. Install Cable Clamp around
exible conduit and attach to Jacket Top Panel.
2. Remove factory installed Jumper Plug from Vent Damper Receptacle on Vestibule Wiring Harness and discard.
3. Plug Vent Damper Harness Plug into Vent Damper Receptacle. See Figure 26.
C. Install thermostat. Locate on inside wall
approximately 4 feet above oor. Do not install on outside wall, near replace, or where inuenced by drafts or restricted air ow, hot or cold pipes, lighting xtures, television, or sunlight. Allow free air
movement by avoiding placement of furniture near thermostat.
Set heat anticipator to match control system
requirements. Refer to Table 9.
D. Wire thermostat. Provide Class II circuit between
thermostat and boiler. Refer to appropriate wiring diagram for control system being used.
Figure 28: Vent Damper Schematic Wiring Diagram
34
Page 35
E. Alliance SL™ Water Heater (if used). May be used
with Intermittent Circulation only.
Refer to Alliance SL™ Installation, Operating
and Service Instructions for wiring, piping and additional information.
F. Vent Damper Sequence of Operation. See Figure 28
for schematic wiring diagram.
1. The Vent Damper is continuously powered at Terminal 1.
2. When there is a call for heat, the damper relay coil is energized through Terminal 5 if all limits ahead of
the damper are satised.
3. The relay coil closes contacts which energize the damper motor, causing the damper to open.
4. When the damper blade reaches the fully open position, power is sent back to the ignition circuit
through Terminal 2 and the damper motor is de­energized.
5. When the call for heat is satised, the damper
relay coil is de-energized - closing contacts which energize the damper motor. This causes the damper to close. When the damper blade reaches the fully closed position, the damper motor is de-energized.
POWER FAILURE - The damper blade will stop in the
position it was in when power failed. (Combustion can never take place unless the damper blade is in the fully open position).
G. Sequence of Operation and Wiring. Refer to Table
10 for the appropriate control system.
H. Optional Low-Water Cut-Off Wiring. See Figures 45
through 48.
Table 9: Heat Anticipator Settings
Control System
24V Standing Pilot 1.1 0.3
24V Electronic Ignition
* If room is heated above thermostat temperature setting, reduce heat anticipator setting by 0.1 or
0.2 amps. If boiler short cycles without room reaching desired temperature, increase heat anticipator by 0.1 or 0.2 amps.
Continuous Circulation Intermittent Circulation
USA: 0.9
Canada: 1.2
Heat Anticipator Setting *
0.3
35
Page 36
Table 10: Sequence of Operation and Wiring Diagrams
Ignition System Country Fuel Boiler Sizes
Standing Pilot (24V)
Standing Pilot
(OP - 120V)
Standing Pilot
(OP-CSD-1 - 120V
Intermittent Ignition
(Honeywell EI - 24V)
Intermittent Ignition
(EP - 120V)
Intermittent Ignition (EP-CSD-1 - 120V)
USA &
Canada
USA &
Canada
USA LP Gas 8 - 10 Sec. Figure 31 Figure 32 Page 39
USA
Canada
USA &
Canada
USA Natural Gas 8 - 10 Sect. Figure 37 Figure 38 Page 47
Natural Gas
6 & 7 Sect. Figure 29 Figure 30 Page 36
LP Gas
Natural Gas
6 - 10 Sect. Figure 31 Figure 32 Page 39
LP Gas
Natural Gas
5 - 10 Sect. Figure 33 Figure 34
LP Gas
Natural Gas 5 - 10 Sect.
LP Gas 5 - 7 Sect.
Natural Gas 6 - 10 Sect. Figure 37 Figure 38 Page 47
LP Gas Not Available
Wiring Diagram Figure
Continuous Intermittent
Figure 35 Figure 36
Sequence of
Operation
Page 42
1. Standing Pilot (24) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat. Vent Damper (if used) opens.
ii. Gas valves are energized allowing main gas
ow and ignition of main burners.
iii. Call or heat ends. Gas valves are de-
energized, extinguishing main ame. Vent
Damper (if used) closes.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat, Vent Damper (if used) closes. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when
excessive ue gas spillage occurs.
Circulator continues to operate and Vent Damper (if used) remains open with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when
ames or excessive heat are present in
vestibule. Circulator continues to operate and Vent Damper (if used) remains open with call for heat. Control is single use
device. If ame roll-out switch is activated,
do not attempt to place boiler in operation.
Correct cause of spillage and replace ame
roll-out switch.
iv. Thermocouple: Senses pilot ame and
causes gas valves to turn off main burner
and pilot burner gas ow should pilot burner ame extinguish. Circulator continues to
operate and Vent Damper (if used) remains open with call for heat.
36
Page 37
Figure 29: Wiring Diagram, Standing Pilot (24V), USA and Canada, Continuous Circulation
37
Page 38
Figure 30: Wiring Diagram, Standing Pilot (24V), USA and Canada, Intermittent Circulation
38
Page 39
2. Electronically Supervised Standing Pilot (OP) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat.
ii. Terminal #6 of RM7890C Burner Control
is energized, initiating a microcomputer monitored circuit test.
iii. Pilot Flame Establishing Period (PFEP)
begins.
iv. After pilot ame is proven, terminal #9 of
RM7890C is energized, allowing main gas
ow and ignition of main burners. “Main”
gas light will be illuminated.
v. Call for heat ends. Terminal #6 of
RM7890C is de-energized, in turn de­energizing gas valves and extinguishing
main ame. “Main” gas light is de-
energized.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when
excessive ue gas spillage occurs.
Circulator continues to operate with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when
ames or excessive heat are present in
vestibule. Circulator continues to operate with call for heat. Control is single use
device. If ame roll-out switch is activated,
do not attempt to place boiler in operation.
Correct cause of spillage and replace ame
roll-out switch.
iv. RM7890C Burner Control: Automatically
interrupts main burner operation if a pilot
ame is not detected during the four or ten second pilot ame establishing period. The
RM7890C will lockout or recycle based on jumper settings. “Alarm” light will be illuminated. Refer to instructions supplied with RM7890C for additional control information.
3. Electronically Supervised Standing Pilot (OP-CSD-1) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat.
ii. Terminal #6 of RM7890C Burner Control
is energized, initiating a microcomputer monitored circuit test.
iii. Pilot Flame Establishing Period (PFEP)
begins.
iv. After pilot ame is proven, terminal #9 of
RM7890C is energized, allowing main gas
ow and ignition of main burners. “Main”
gas light will be illuminated.
v. Call for heat ends. Terminal #6 of
RM7890C is de-energized, in turn de­energizing gas valves and extinguishing
main ame. “Main” gas light is de-
energized.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when
excessive ue gas spillage occurs.
Circulator continues to operate with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when
ames or excessive heat are present in
vestibule. Circulator continues to operate with call for heat. Control is single use
device. If ame roll-out switch is activated,
do not attempt to place boiler in operation.
Correct cause of spillage and replace ame
roll-out switch.
iv. RM7890C Burner Control: Automatically
interrupts main burner operation if a pilot
ame is not detected during the four or ten second pilot ame establishing period. The
RM7890C will lockout or recycle based on jumper settings. “Alarm” light will be illuminated. Refer to instructions supplied with RM7890C for additional control information.
v. Pilot Safety Switch: Automatically de-
energizes main gas valve and interrupts pilot
gas supply if pilot ame is not detected at
any time.
39
Page 40
Figure 31: Wiring Diagram, OP/OP-CSD-1 Ignition System, Continuous Circulation
40
Page 41
Figure 32: Wiring Diagram, OP/OP-CSD-1 Ignition System, Intermittent Circulation
41
Page 42
4. Honeywell EI Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat. Vent Damper (if used) opens.
ii. Ignition Module Terminals PV, MV/PV
and the Ignition Terminal are energized. Terminals PV and MV/PV power the Pilot Valve in the Gas Valve supplying gas to the Pilot. The Ignition Terminal supplies voltage to the Ignition Electrode creating an electric spark to ignite the Pilot.
iii. The sensing Circuit between the Q348
Pilot Burner and the IGNITION MODULE proves the presence of the Pilot Flame Electronically and the Ignition Terminal is de-energized.
iv. Terminals MV and MV/PV of the
IGNITION MODULE are energized and supply power to the Main Gas Valve. The Gas Valve is energized allowing main gas
ow, and ignition of Main Burners.
v. Call for heat ends. Ignition module is de-
energized, de-energizing gas valve, and
extinguishing pilot and main ame. Vent
Damper (if used) closes.
b. Safety Shutdown
i. Limit: Automatically interrupts power
to the Ignition Module and Gas Valve(s),
extinguishing pilot and main ame, when
water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat, Vent Damper (if used) closes. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when
excessive ue gas spillage occurs.
Circulator continues to operate and Vent Damper (if used) remains open with call for heat. If blocked vent switch is activated do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out switch: Automatically
interrupts main burner operation when
ames or excessive heat are present in
vestibule. Circulator continues to operate, Vent Damper (if used) remains open with call for heat. Control is single use device.
If ame roll-out switch is activated, do not
attempt to place boiler in operation. Correct
cause of spillage and replace ame roll-out
switch. iv. Pilot – Pilot failure can occur during the start-up or
the operating cycle of the boiler. Any pilot
failure of the Q348 Electronic Pilot, after
ignition of pilot ame will close the main
gas valve in 0.8 seconds. – For approximately 90 seconds after failure
of the Q348 pilot, the module through the
ignition terminal will try to reestablish
pilot ame. If no pilot ame can be sensed
by the ame rod circuit, terminals PV and
MV/PV are de-energized and the module
will lock out on safety. Five to six minutes
after shutdown, the IGNITION MODULE
restarts the ignition sequence. The ignition
trial, shutdown, and wait sequence continues
until either the pilot lights or the Thermostat
is set below room temperature (to end the
call for heat). The ignition sequence can be
reset by setting down the Thermostat for one
minute.
c. Trouble Shooting Guide. See Page 66.
42
Page 43
Figure 33: Wiring Diagram, Honeywell EI, USA, Continuous Circulation
43
Page 44
Figure 34: Wiring Diagram, Honeywell EI, USA, Intermittent Circulation
44
Page 45
Figure 35: Wiring Diagram, Honeywell EI, Canada, Continuous Circulation
45
Page 46
Figure 36: Wiring Diagram, Honeywell EI, Canada, Intermittent Circulation
46
Page 47
6. Electronically Supervised Intermittent Ignition (EP/EP-CSD-1) Sequence of Operation
a. Normal Operation
i. Thermostat or operating control calls for
heat.
ii. Terminal #6 of RM7890A Burner Control
is energized, initiating a microcomputer monitored circuit test.
iii. The pilot valve (terminal 8) and ignition
transformer (terminal 10) are energized. The pilot valve opens and the ignition electrode sparks, igniting the pilot.
iv. After the pilot ame is proven, the ignition
terminal (10) is de-energized and the main valve terminal (9) is energized, allowing
main gas ow and ignition of main burners.
“Main” gas light will be illuminated.
v. When the call for heat ends, terminal #6
is de-energized, extinguishing the pilot
and main ames. “Main” gas light is de-
energized.
b. Safety Shutdown
i. Limit: Automatically interrupts main burner
operation when water temperature exceeds set point. Maximum allowable temperature is 250°F. Circulator continues to operate with call for heat. Normal operation resumes when water temperature falls below set point.
ii. Blocked Vent Switch: Automatically
interrupts main burner operation when
excessive ue gas spillage occurs.
Circulator continues to operate with call for heat. If blocked vent switch is activated, do not attempt to place boiler in operation. Correct cause of spillage and reset blocked vent switch.
iii. Flame Roll-out Switch: Automatically
interrupts main burner operation when
ames or excessive heat are present in
vestibule. Circulator continues to operate with call for heat. Control is single use
device. If ame roll-out switch is activated,
do not attempt to place boiler in operation.
Correct cause of spillage and replace ame
roll-out switch.
iv. RM7890A Burner Control: Automatically
interrupts main burner operation if a pilot
ame is not detected during the four or ten second pilot ame establishing period. The
RM7890A will lockout or recycle based on jumper settings. “Alarm” light will be illuminated. Refer to instructions supplied with RM7890A for additional control information.
47
Page 48
Figure 37: Wiring Diagram, EP/EP-CSD-1 Ignition System, USA, Continuous Circulation
48
Page 49
Figure 38: Wiring Diagram, EP/EP-CSD-1 Ignition System, USA, Intermittent Circulation
49
Page 50
Figure 39: McDonnell & Miller 750P-MT (120V) L.W.C.O. Wiring for Boilers with 24V Limit Circuits
Figure 40: McDonnell & Miller 750P-MT (120V) L.W.C.O. Wiring for Boilers with 120V Limit Circuits (OP & EP)
50
Page 51
Figure 41: Hydrolevel OEM - 170/550/650/750 (120V) L.W.C.O. Wiring for Boilers with 24V Limit Circuits
Figure 42: Hydrolevel OEM - 170/550/650/750 (120V) L.W.C.O. Wiring for Boilers with 120V Limit Circuits
51
Page 52
VIII. System Start-Up
WARNING
Completely read, understand and follow all instructions in this manual before attempting start-up.
A. Safe operation and other performance criteria were met
with the gas manifold and control assembly provided
on boiler when boiler underwent tests specied in
American National Standard for Gas-Fired Low­Pressure Steam and Hot Water Boilers, ANSI Z21.13.
B. Check Main Burners. Main burners must be properly
located on support bracket in Base Rear Panel, seated
on Main Burner Orices, and secured with hitch pin
clips.
C. Verify that the venting, water piping, gas piping
and electrical system are installed properly. Refer to
installation instructions contained in this manual.
D. Conrm all electrical, water and gas supplies
are turned off at the source and that vent is clear of obstructions.
E. FILL ENTIRE HEATING SYSTEM WITH WATER
and vent air from system. Use following procedure on a Series Loop or multi-zoned system installed as per
Figure 23 to remove air from system when lling.
WARNING
The maximum operating pressure of this boiler is 50 psig. Never exceed this pressure. Do not plug or modify pressure relief valve.
1. Close full port ball valve in boiler supply piping.
2. Isolate all zones by closing zone valves or shut-off valves in supply and return of each zone(s).
3. Attach a hose to the vertical purge valve located prior to the full port ball valve in the system supply
piping. (Note - Terminate hose in ve gallon bucket at a suitable oor drain or outdoor area).
4. Starting with one circuit at a time, open zone valve or shut-off valve in system supply and return piping.
5. Open purge valve.
6. Open ll valve (Make-up water line should be
located directly after full port ball valve in system supply piping between air scoop and expansion tank).
7. Allow water to overow from bucket until discharge
from hose is bubble free for 30 seconds.
8. Close the open zone valve or shut-off valve for the zone being purged of air, then open the zone valve or shut-off valve for the next zone to be purged. Repeat this step until all zones have been purged. At
52
completion, open all zone valves or shut-off valves.
9. Close purge valve, continue lling the system until the pressure gauge reads the desired cold ll pressure. Close ll valve.
(Note - If make-up water line is equipped with
pressure reducing valve, adjust pressure reducing
valve to desired cold ll pressure. Follow ll valve
manufacturer’s instructions).
10. Open isolation valve in boiler supply piping.
11. Remove hose from purge valve.
F. Conrm that the boiler and system have no water
leaks.
G. Prepare to check operation.
1. Obtain gas heating value (in Btu per cubic foot) from gas supplier.
2. Connect manometer to pressure tap on gas valve. Use 1/8 NPT tapping provided.
3. Temporarily turn off all other gas-red appliances.
4. Turn on gas supply to the boiler gas piping.
5. Conrm that the supply pressure to the gas valve is
14 in. w.c. or less.
6. Open the eld installed manual gas shut-off valve
located upstream of the gas valve on the boiler.
7. Using soap solution, or similar non-combustible solution, electronic leak detector or other approved method. Check that boiler gas piping, valves, and all other components are leak free. Eliminate any leaks.
8. Purge gas line of air.
H. Follow Lighting or Operating Instructions to place
boiler in operation. Refer to label on inside of Front Removable Panel or appropriate Figure as listed in Table 11.
DANGER
Do not use matches, candles, open ames or
other ignition source to check for leaks.
Table 11: Lighting and Operating Instructions
Lighting or
Ignition System
Standing Pilot (24) Figure 43 Figure 48
Honeywell EI Figure 44 Figure 49
OP Figure 45 Figure 50
EP Figure 46 Figure 51
OP-CSD-1
EP-CSD-1 Figure 51
Operating
Instructions
Figure 47
Pilot Flame
Illustration
Figure 50
Page 53
Figure 43: Lighting Instructions (24V Standing Pilot)
53
Page 54
54
Figure 44: Operating Instructions (EI)
Page 55
Figure 45: Lighting Instructions (OP)
55
Page 56
Figure 46: Operating Instructions (EP)
56
Page 57
BOILER OPERATING INSTRUCTIONS
TO SHUT DOWN:
1. Close manual main shut-off valve(s) and pilot
valve(s).
2. Turn off main electric switch.
TO START UP:
1. Make sure that both the main manual and the pilot
valve(s) have been off for at least ve minutes.
2. Turn room thermostat and all operating controls to lowest setting.
3. Remove burner access panel(s).
4. Open manual pilot valve(s).
NOTE:
Item (5) applies only to boilers with standing pilot
safety switch(es).
5. Depress button on standing pilot safety switch and hold lighted match to pilot, holding button in for at least one minute or until pilot remains lighted after button is released. Repeat for remaining standing pilots.
6. Turn on main electric switch.
7. Reset safety switch on ame safeguard relay.
8. Immediately light constant burning rectication pilot(s)
Q179D with a lighted match. If pilot is not lighted in 15 seconds, Step (7) must be repeated. Electric pilot valve(s) are automatic, opening after Step (7). (“OP” System).
8a. Intermittent electric ignition rectication pilot(s)
Q179C light up automatically when thermostat or operating control calls for heat. (“EP” System).
9. Replace burner access panel(s).
10. Open manual main shut-off valve(s).
11. Adjust room thermostat and operating controls to desired setting.
Figure 47: Lighting / Operating Instructions (OP/EP-CSD-1)
57
Page 58
Figure 48: Honeywell Q314 Pilot Flame
(24V Standing Pilot)
Figure 50: Honeywell Q179D Pilot Flame (OP)
Figure 51: Honeywell Q179C Pilot Flame (EP)
Figure 49: Honeywell Q348 Pilot Flame
(24V Electronic Ignition)
I. Check pilot burner ame and main burner ames
through observation port.
1. Check pilot ame. Refer to Table 11 for appropriate
pilot detail.
2. Adjust thermostat to highest setting.
3. Check main burner ames. See Figure 52. Flame should have clearly dened inner cones with no
yellow tipping. Orange-yellow streaks caused by dust should not be confused with true yellow tipping.
Yellow-tipping indicates lack of primary air.
Improper burner alignment on Main Burner Orice
will also affect primary air injection. Adjust primary air as follows:
58
Figure 52: Main Burner Flame
Page 59
CAUTION
Avoid operating this boiler in an environment
where saw dust, loose insulation bers, dry wall
dust, etc. are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.
a. Loosen lock screw.
b. Close air adjustment until yellow tips appear on
ames.
c. Slowly open air adjustment until clearly dened
inner cones are visible.
d. Tighten lock screw.
4. Adjust thermostat to normal setting.
J. Check thermostat or operating control operation.
Raise and lower temperature setting to start and stop boiler operation.
K. Check ignition system shut-off.
1. Standing Pilot (24V): Disconnect thermocouple lead at Gas Valve. Gas Valve must close and pilot and main burners extinguish. If not, replace the gas valve.
2. Honeywell EI: Disconnect ignitor/sensor cable from ignition module. Gas valve must close and pilot and main burners extinguish. If not, measure voltage across gas valve terminals “TH” and “TR”.
a. If voltage is not present, replace gas valve.
b. If voltage is present, replace ignition module.
3. EP and OP: Refer to instructions supplied with the Honeywell RM7890 Burner Control.
L. Check Limit(s).
1. Adjust thermostat to highest setting.
2. Observe temperature gauge. When temperature exceeds limit set point main burners should extinguish.
3. Adjust limit to setting above observed reading. Main burners should reignite.
4. Adjust thermostat to lowest setting. Adjust limit to desired setting.
M. Adjust gas input rate to boiler. Natural Gas.
1. Adjust thermostat to highest setting.
2. Check manifold gas pressure. Manifold pressure is listed on rating label. Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure can not be attained, check gas valve inlet pressure. If less than minimum gas supply pressure listed on rating label, contact gas supplier for assistance.
3. Clock gas meter for at least 30 seconds. Use Table
12 to determine gas ow rate in Cubic Feet per
Hour.
Table 12: Input Rate
Seconds
for One
Revolution
30 60 120 240 600
32 56 113 225 563
34 53 106 212 529
36 50 100 200 500
40 45 90 180 450
38 47 95 189 474
40 45 90 180 450
42 43 86 172 430
44 41 82 164 410
46 39 78 157 391
48 37 75 150 375
50 36 72 144 360
52 35 69 138 346
54 33 67 133 333
56 32 64 129 321
58 31 62 124 310
60 30 60 120 300
62 29 58 116 290
64 29 56 112 281
66 29 54 109 273
68 28 53 106 265
70 26 51 103 257
72 25 50 100 250
74 24 48 97 243
76 24 47 95 237
78 23 46 92 231
80 22 45 90 225
One-Half
Cu. Ft.
Size of Gas Meter Dial
One
Cu. Ft.
Two
Cu. Ft.
Five
Cu. Ft.
4. Determine Input Rate. Multiply gas ow rate by gas
heating value.
Warning
Failure to properly adjust gas input rate will result
in over ring or under ring of the appliance.
Improper and unsafe boiler operation may result.
5. Compare measured input rate to input rate stated on rating label.
a. Boiler must not be overred. Reduce input rate
by decreasing manifold pressure. Do not reduce
more than 0.3 inch w.c. If boiler is still overred,
contact your Burnham distributor or Regional
Ofce for replacement Gas Orices.
59
Page 60
b. Increase input rate if less than 98% of rating
plate input. Increase manifold gas pressure no more than 0.3 inch w.c. If measured input rate is still less than 98% of rated input:
i. Remove Main Burners per procedure in
Section IX: Service.
ii. Remove gas orices. Drill one (1) drill size
larger (drill size is stamped on orice, or see
Key No. 4E).
iii. Reinstall gas orices and main burners.
Measure input rate.
6. Recheck Main Burner Flame.
7. Return other gas-red appliances to previous
conditions of use.
N. Adjust gas input rate to boiler. LP/Propane.
1. Set thermostat to highest setting.
2. Adjust tank regulator for gas valve inlet pressure of
13.5 inches w.c. or less.
3. Gas valve has step opening regulator which initially opens to 1.4 or 2.5 inch w.c. and steps to full pressure after approximately 30 seconds. Check manifold pressure after step has occurred. Adjust gas valve pressure regulator as necessary for 10.0 inches w.c. (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If 10.0 inches w.c. can not be attained, check gas valve inlet pressure. If less than
11.0 inches w.c., contact gas supplier for assistance.
O. Clean Heating System
Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or
reworked system should be boiled out, and then
thoroughly ushed. A qualied water treatment
chemical specialist should be consulted for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations.
P. Check Damper Operation - If boiler is equipped with
vent damper, vent damper must be in open position when boiler main burners are operating. Start boiler, refer to instructions on damper to determine if damper is in full open position.
Q. Install Front Removable Panel.
1. Engage top ange (longer of 2 anges) behind
Upper Front Panel.
2. Swing lower portion of door toward boiler.
3. Lower door to engage bottom ange behind Lower
Front Tie Bar.
R. Combustion Chamber Burn-Off
1. The mineral wool combustion chamber panels contain a cornstarch based binder that must be burned out at installation to prevent odors during subsequent boiler operation.
2. Ventilate the boiler room, set the high limit to its maximum setting, set the thermostat to call for heat.
3. Allow the boiler to re for at least an hour or until
the odor from the cornstarch has dissipated.
4. Return the high limit and thermostat to their desired settings.
S. Review User’s Information Manual and system
operation with owner or operator.
60
Page 61
IX. Service
WARNING
Service on this boiler should be undertaken only by trained and skilled personnel from a qualied service agency. Inspections should be performed at intervals specied in this manual. Maintain manual in a
legible condition.
Keep boiler area clear and free of combustible materials, gasoline and other ammable vapors and liquids.
Do not place any obstructions in boiler room that will hinder ow of combustion and ventilation air.
The service instructions contained in this manual are in addition to the instructions provided by the manufacturer of the boiler components. Follow component manufacturer’s instructions. Component manufacturer’s instructions were provided with the boiler. Contact component manufacturer for replace­ment if instructions are missing. Do not install, start up, operate, maintain or service this boiler without reading and understanding all of the component instructions. Do not allow the boiler to operate with altered, disconnected or jumpered components. Only use replacement components identical to those originally supplied by Burnham Commercial.
A. General. Inspection and service must be conducted
annually. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Lighting/ Operating Instructions on inside of Front Removable Door.
WARNING
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
B. Maintenance of Low Water Cut-off (if used). Follow
instructions provided with low water cut-off.
C. Vent System. Check for:
1. obstructions
2. accumulations of soot
3. deterioration of vent pipe or vent accessories due to condensation or other reasons
4. proper support—no sags, particularly in horizontal runs
5. tightness of joints. Remove all accumulations of soot with wire brush and vacuum
Remove all obstructions. Replace all deteriorated parts
and support properly. Seal all joints.
D. Remove Main Burners for cleaning, changing orice
plugs, or repairs.
1. Shut down gas boiler in accordance with Lighting/ Operating Instructions on inside of Front Removable Door. Close Manual Shut-off Valve.
2. Remove Front Removable Door. Raise Lower Front Tie Bar.
3. Disconnect ignition system.
4. Remove burner access panel(s).
5. Mark location of Main Burner with Pilot Bracket on manifold.
6. Remove hitch pin clips from Main Burner Orices.
7. Hold Main Burner on throat. Lift slightly to raise rear of burner. Push to rear of boiler until burner
clears Main Burner Orice. Lift burners out.
8. Check burners to be sure they do not contain foreign matter or restrictions. Clean burners with a soft bristle brush, blow any dirt out with compressed air or use a vacuum cleaner. See Figure 53.
E. Clean Boiler Flueways. See Figure 53.
1. Shut down gas boiler in accordance with Lighting/ Operating Instructions on inside of Front Removable Door. Close Manual Shut-off Valve.
2. Disconnect vent system. Remove Draft Hood.
3. Remove Jacket Top Panel.
4. Remove Canopy from top of boiler.
5. Lift Flue Bafes out of ueways. Remove any
accumulated scale or soot.
6. Thoroughly clean ueways with ue brush,
removing all scale and soot. See Figure 53.
7. Clean boiler heating surface accessible from combustion chamber with straight handle wire brush.
8. Reinsert Blue Bafes into ueways. See Figure 53 for correct bafe orientation. Tabs at top of each bafe should rest o top of Flue Pins.
9. Install Canopy. See Section II: Boiler Assembly, Paragraph G.
10. Install Jacket Top Panel, Draft Hood, Vent Damper (if used) and Vent System.
61
Page 62
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
The Repair Parts list designates parts that contain refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. When exposed to temperatures about 1805°F, such as during direct flame contact, RCF changes into crystalline silica, a known carcinogen. When disturbed as a result of servicing or repair, these substances become airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace RCF parts or attempt any service or repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an airtight plastic bag. RCF and crystalline silica are not classified as hazardous wastes in the United States and Canada.
First Aid Procedures
:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
62
Page 63
F. Clean Combustion Chamber by vacuuming. Exercise
care to avoid damaging Base Insulation.
G. Install Burners by reversing procedures used to
remove burners. Verify Main Burners are properly located on support bracket in Base Rear Panel, seated
on Main Burner Orices, and secured with hitch pin
clips. Verify Main Burner with Pilot Bracket is in proper location. See Table 13.
H. Lubrication. Manufacturers Instruction should be
followed on all parts installed on boiler requiring lubrication. This includes type of lubricant to be used, frequency of lubrication, and points to lubricate.
I. Check operation. Refer to Section VIII: System Start-
up.
Figure 53: Boiler Flueway Cleaning
Table 13: Pilot Burner Location
Boiler Model Pilot Located Between Burners*
805H 4 & 5
806H 5 & 6
807H 6 & 7
808H 6 & 7
809H 7 & 8
810H 8 & 9
* Burners numbered left to right as viewed from front of boiler.
63
Page 64
Honeywell EI Ignition Module Yellow LED Flame Codes
Yellow LED
Flash Code
a
Indicates Recommended Service Action
Heartbeat Normal Flame Signal N/A
Weak Flame Signal -
System will operate reliably but ame signal is less than
2
desired.
Note: This indication may ash temporarily during or
Perform routine maintenance to
assure optimum ame signal.
shortly after lightoff on some applications.
Marginal Flame Signal (less than 1.1 µA) -
System may not operate reliably over time. Service call
1
recommended.
Note: This indication may ash temporarily during or
Check gas supply, pilot burner, ame sense wiring, contamination of ame rod,
burner ground connection.
shortly after lightoff on some applications.
OFF
a
Flash Code Descriptions
below minimum threshold for system operation.
No Flame or Flame Signal -
N/A
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- The ash code number signies that the LED ashes X times at 2Hz, remains off for two seconds, and then repeats
sequence.
64
Page 65
Honeywell EI Ignition Module Green LED Status Codes
Green LED
Flash Code
(X + Y)
a
Indicates Next System Action Recommended Service Action
OFF No “Call for Heat” N/A None
Flash Fast
Startup - Flame sense calibration
N/A None
Heartbeat Normal operation N/A None
If system fails to light on next trial for
5 minute Retry Delay-
2
Pilot ame not detected
during trial for ignition
Initiate new trial for ignition after retry delay completed.
ignition check gas supply, pilot burner,
spark and ame sense wiring, ame rod
contamination or out of position, burner ground connection.
3
Recycle- Flame failed during run
Initiate new trial for ignition. Flash code will remain through the ignition
trial until ame is proved.
If system fails to light on next trial for ignition check gas supply, pilot
burner, ame sense wiring, ame rod
contamination, burner ground connection.
If situation self corrects within 10 seconds, control returns to normal
4
Flame sensed out of sequence
sequence. If ame out of sequence
remains longer than 10 seconds,
control goes to Flash code 6+4 (see
Check for pilot ame. Replace gas valve if pilot ame present. If no pilot ame,
cycle “Call for Heat.” If error repeats, replace control.
below)
7
8
Flame sense leakage to ground
Low secondary voltage supply- (below 15.5 Vac)
5 minute Retry Delay-
6 + 2
On every third retry on same “Call for Heat”
On every 6th ame
6 + 3
failure during run on the same “Call for Heat”
Flame sensed out of
6 + 4
sequence- longer than 10 seconds
Soft lockout due to error
ON
detected during self check sequences
a
Flash Code Descriptions:
Control remains in wait mode. When the fault corrects, control resumes normal operation after a one minute delay.
Control remains in wait mode. When the fault corrects, control resumes normal operation after one minute delay.
Initiate new trial for ignition after retry delay completed.
5 minute retry delay, then initiate new trial for ignition.
Control waits until ame is no
longer sensed and then goes to soft lockout. Flash code continues. Control auto resets from soft lockout after one hour.
Control auto resets from soft lockout after one hour.
Check ame sense lead wire for damage or shorting. Check that ame rod is in proper position. Check ame rod ceramic
for cracks, damage or tracking.
Check transformer and AC line for proper input voltage to the control. Check with full system load on the transformer.
Check gas supply, pilot burner, spark
and ame sense wiring, ame rod
contamination or out of position, burner ground connection.
Check gas supply, pilot burner, ame sense wiring, contamination of ame rod,
burner ground connection.
Check for pilot ame. Replace gas valve if pilot ame present. If no pilot ame,
cycle “Call for Heat.” If error repeats, replace control.
Reset by cycling “Call for Heat.” If error repeats, replace the control
- Flash Fast: rapid blinking
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- A single ash code number signies that the LED ashes X times at 2Hz, remains off for two seconds, and then
repeats the sequence.
- X + Y ash codes signify that the LED ashes X times at 2Hz, remains off for two seconds, ashes Y times at
2 Hz, remains off for three seconds, and then repeats the sequence.
65
Page 66
Honeywell EI Trouble Shooting Guide
66
Page 67
X. Repair Parts
All Series 8H Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance in locating a Burnham Distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact Burnham Customer Service at: (717) 481-8400 or Fax (717) 481-8408.
67
Page 68
Item No. Description Part No.
805H 806H 807H 808H 809H 810H
Quantity
1. Heat Exchanger Assembly
6171605 1 --- --- --- --- ---
6171606 --- 1 --- --- --- ---
1 Complete (Less Flue Bafes)
1A Left End Section 7171601 1 1 1 1 1 1
1B Intermediate Section 7171603 3 4 5 6 7 8
1C Right End Section 7171602 1 1 1 1 1 1
1D Tie Rod
1E Washer 80860600 4 4 4 4 4 4
1F Nut 80860400 4 4 4 4 4 4
1G Slip Nipple, 3” 7066002 8 10 12 14 16 18
1H Flue Bafe 7111622 4 5 6 7 8 9
6171607 --- --- 1 --- --- ---
6171608 --- --- --- 1 --- ---
6171609 --- --- --- --- 1 ---
6171610 --- --- --- --- --- 1
80861032 1 --- --- --- --- ---
80861033 --- 1 --- --- --- ---
80861013 --- --- 1 --- --- ---
80861034 --- --- --- 1 --- ---
80861035 --- --- --- --- 1 ---
80861036 --- --- --- --- --- 1
68
Page 69
Item No. Description Part No.
2. Canopy
2A Canopy
2B Bolt, Carriage, ¼ - 20 x 1” 80860115 2 2 2 2 2 2
2C Washer, ¼” Flat 80860603 2 2 2 2 2 2
2D Nut, ¼” - 20 80860407 2 2 2 2 2 2
Quantity
805H 806H 807H 808H 809H 810H
6111605 1 --- --- --- --- ---
6111606 --- 1 --- --- --- ---
6111607 --- --- 1 --- --- ---
6111608 --- --- --- 1 --- ---
6111609 --- --- --- --- 1 ---
6111610 --- --- --- --- --- 1
69
Page 70
Item
No.
Description Part No.
805H 806H 807H 808H 809H 810H
Quantity
3. Base Assembly
3A Base End Panel 7181601 2 2 2 2 2 2
61816052 2 --- --- --- --- ---
61816062 --- 2 --- --- --- ---
3B Base Channel Assembly
3C Base Rear Panel Assembly
3D Base Front Panel Assembly
3E Burner Access Panel Assembly
3F Jacket Attachment Bracket 7041601 4 4 4 4 4 4
3G Bolt, Carriage, ¼ - 20 x 1¼” 80860106 4 4 4 4 4 4
3H Washer, ¼” Flat 80860603 4 4 4 4 4 4
3J Nut, ¼ - 20 80860407 4 4 4 4 4 4
3K Screw, Self Tapping, ¼ - 20 x ½” 80860700 3 4 4 5 5 6
3L Screw, Cap, Hex Head, 5/16” - 18 x ¾” 80861302 2 2 2 2 2 2
3M Screw, Cap, Hex Head, 5/16 - 18 x 1¼” 80861311 6 6 6 6 6 6
3N Screw, Sheet Metal, #8 x ½” 80860000 8 8 8 8 8 8
3P Washer, 3/8” Flat 80860600 6 6 6 6 6 6
3Q Nut, 5/16” 80860403 6 6 6 6 6 6
3R Screw, Self Tapping, ¼ - 20 x ¾” 80860702 10 10 10 10 10 10
61816072 --- --- 2 --- --- ---
61816082 --- --- --- 2 --- ---
61816092 --- --- --- --- 2 ---
61816102 --- --- --- --- --- 2
61816051 1 --- --- --- --- ---
61816061 --- 1 --- --- --- ---
61816071 --- --- 1 --- --- ---
61816081 --- --- --- 1 --- ---
61816091 --- --- --- --- 1 ---
61816101 --- --- --- --- --- 1
61816053 1 --- --- --- --- ---
61816063 --- 1 --- --- --- ---
61816073 --- --- 1 --- --- ---
61816083 --- --- --- 1 --- ---
61816093 --- --- --- --- 1 ---
61816103 --- --- --- --- --- 1
61816054 1 --- --- --- --- ---
61816064 --- 1 --- --- --- ---
61816074 --- --- 1 --- --- ---
61816084 --- --- --- 2 --- ---
61816094 --- --- --- --- 2 ---
61816104 --- --- --- --- --- 2
70
Page 71
Item
No.
Description Part No.
805H 806H 807H 808H 809H 810H
Quantity
4. Manifold and Main Burners
4A Main Burner 8231602 8 10 12 15 17 19
Main Burner with Pilot Bracket, Standing Pilot (24V) 8231601 --- 1 1 1 1 1
Main burner with Pilot Bracket, Honeywell EI 8231604 1 1 1 1 1 1
4B
Main Burner with Pilot Bracket, OP
Main burner with Pilot Bracket, EP
4C Manifold
4D Pipe Plug, 1/8 NPT (Included with 4C) --- 1 1 1 1 1 1
Main Burner Orice, #39 (Natural Gas Only * 822603
4E
Main Burner Orice, #53 (LP/Propane Only) * 8226002
4F Hitch Pin Clip 822604 9 11 13 16 18 20
* Main burner orice sizes shown for normal altitude (0-2000 feet). For High Altitude consult factory.
8231603 --- 1 1 1 1 1
82216051 1 --- --- --- --- ---
82216061 --- 1 --- --- --- ---
82216071 --- --- 1 --- --- ---
82216081 --- --- --- 1 --- ---
82216091 --- --- --- --- 1 ---
82216101 --- --- --- --- --- 1
9 11 13 16 18 20
71
Page 72
Item
No.
Description Part No. Size Quantity
5-1 Gas Train -- Standing Pilot (24V, OP) 24V: USA & Canada, 6 & 7 Section, Natural & LP Gas OP: USA & Canada, 6 - 10 Section, Natural & LP Gas
Gas Valve, Robertshaw 7000ERHC-S7C, Natural Gas, 1” NPT 81660156
A
Gas Valve, Robertshaw 7000ERHC-LP-S7C, LP Gas, 1” NPT 81660157
Solenoid Gas Valve, Honeywell V8295A1024, ¾” NPT 81660235 806H-807H 1
B
Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT 81660236 808H-810H 1
C Lubricated Manual Shut-Off Valve, Newman-Milliken 200M, 1” NPT 822619
D Hex Bushing, 1” NPT x ¾” NPT 806600501 806H & 807H 1
Nipple, ¾” NPT x 2” Lg. 806600003 806H & 807H USA: 1
E
Nipple, 1” NPT x 2” Lg. 806600004 808H-810H Canada: 2
Street Elbow, 1” NPT x ¾” NPT 806601512 806H - 807H
F
Street Elbow, 1¼” NPT x 1” NPT 806601513 808H - 810H
806H - 810H 1
808H-810H
Canada Only
1
1
72
Page 73
Item
No.
Description Part No. Quantity
5-2 Gas Train -- Standing Pilot (OP-CSD-1) OP-CSD-1: USA Only, 8-10 Section, LP Gas Only
A Gas Valve, Robertshaw 7000GVERHC-S7C, LP Gas, 1” NPT 81660271 1
B Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT 81660236 1
C Lubricated Manual Shut-Off Valve, Conbraco #50-403-02, 1” NPT 822615 1
D Leak Test/Shut-off Valve, Conbraco #56-221-01, 1/8” x 1/8” 822679 2
E Pipe Plug, 1/8” 806603594 2
F Hex Bushing, 1/4” x 1/8” 806600520 1
G Nipple, 1” x 2” Long 806600004 2
H Street Elbow, 90° x 1” 806601514 1
J Close Nipple, 1” 806600033 1
K Malleable Coupling, 1-1/4” x 1” 806602502 1
L Wiring Harness, Gas Valve to Solenoid Valve 6136230 1
M Pilot Outlet Plug, Honeywell #394424 8226051 1
73
Page 74
Item
No.
Description Part No. Size Quantity
5-3 Gas Train -- Intermittent Ignition (EI) USA: 5 - 10 Section, Natural and LP Gas Canada: 5 - 10 Section, Natural Gas 5 - 7 Section, LP Gas
Gas Valve, Robertshaw 7000DERHC, Natural Gas, 1” NPT 81660151 805H-810H
A
Gas Valve, Robertshaw 7000DERHC-LP, LP Gas, 1” NPT 81660158
B Lubricated Manual Shut-Off Valve, Newman-Milliken 200M, 1” NPT 822619
C Nipple, 1’ NPT x 2” Lg. 806600004
Street Elbow, 1” NPT 806601514 805H-807H
D
Street Elbow, 1¼” NPT x 1” NPT 806601513 808H-810H
USA: 805H-810H
Canada: 805H-807H
808H-810H
Canada Only
1
1
1
74
Page 75
Item
No.
Description Part No. Size Quantity
5-4 Gas Train -- Intermittent Ignition (EP) USA & Canada: 6 - 10 Section, Natural Gas Only
A Gas Valve, Robertshaw 7000GVERHC-S7C, Natural Gas, 1” NPT 81660168 806H-810H 1
Solenoid Gas Valve, Honeywell V8295A1024, ¾” NPT 81660235 806H-807H
B
Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT 81660236 808H-810H
C Lubricated Manual Shut-Off Valve, Newman-Milliken 200M, 1” NPT 822619
D Hex Bushing, 1” NPT x ¾” NPT 806600501 806H & 807H 1
Nipple, ¾” NPT x 2” Lg. 806600003 806H & 807H 1
808H-810H
Canada Only
1
1
E
Nipple, 1” NPT x 2” Lg. 806600004 808H-810H
Street Elbow, 1” NPT x ¾” NPT 806601512 806H & 807H
F
Street Elbow, 1¼” NPT x 1” NPT 806601513 808H-810H
USA: 1
Canada: 2
1
75
Page 76
Item
No.
Description Part No. Quantity
5-5 Gas Train -- Intermittent Ignition (EP-CSD-1) USA Only: 8 - 10 Section, Natural Gas Only
A Gas Valve, Robertshaw 7000GVERHC-S7C, Natural Gas, 1” NPT 81660168 1
B Solenoid Gas Valve, Honeywell V8295A1032, 1” NPT 81660236 1
C Lubricated Manual Shut-Off Valve, Conbraco #50-403-02, 1” NPT 822615 1
D Leak Test/Shut-Off Valve, Conbraco #56-221-01, 1/8” x 1/8” 822679 2
E Pipe Plug, 1/8” 806603594 2
F Hex Bushing, 1/4” x 1/8” 806600520 1
G Nipple, 1” x 2” Long 806600004 2
H Street Elbow, 90° x 1” 806601514 1
J Close Nipple, 1” 806600033 1
K Malleable Coupling, 1-1/4” x 1” 806602502 1
L Wiring Harness, Gas Valve to Solenoid Valve 6136230 1
M Pilot Outlet Plug, Honeywell #394424 8226051 1
76
Page 77
Item
No.
Description Part No. Size Quantity
5-6 Pilot Assembly and Piping -- Standing Pilot (24V) USA & Canada: 6 & 7 Section, Natural and LP Gas
Pilot Burner, Honeywell Q314A3687, Natural Gas 8236033
A
B Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead 8236004
C Brass Compression Union, 1/4” OD Tube 8236008 806H & 807H 1
D Regulator, Maxitrol RV12LT, Natural Gas 8226005
E Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT 822630
Canada: 806H & 807H
Natural Gas Only
Canada: 806H & 807H
Natural Gas Only
All 1Pilot Burner, Honeywell Q314A3828, LP Gas 8236034
1
2
77
Page 78
Item
No.
Description Part No. Size Quantity
5-7 Pilot Assembly and Piping -- Intermittent Ignition (Honeywell EI) USA 5 - 10 Section, Natural and LP Gas
Pilot Burner, Honeywell Q348A1002, Natural Gas 8236072U
A
1Pilot Burner, Honeywell Q348A1010, LP Gas 8236081
B Igniter/Sensor Cable, 36” Lg., Honeywell 394803-2 8236121
C Ground Wire Assembly 6136054 1
D Brass Compression Union, 1/4” OD Tube 8236008 1
805H-810H
78
Page 79
Item
No.
Description Part No. Size Quantity
5-8 Pilot Assembly and Piping -- Intermittent Ignition (Honeywell EI) Canada 5 - 10 Section, Natural Gas 5 - 7 Section, LP Gas
Pilot Burner, Honeywell Q348A1002, Natural Gas 8236072U 805H-810H
A
Pilot Burner, Honeywell Q348A1010, LP Gas 8236081 805H-807H
B Igniter/Sensor Cable, 36” Lg., Honeywell 394800-36 8236084
C Ground Wire Assembly 6136054
D Brass Compression Union, 1/4” OD Tube 8236008 805H-807H 1
E Shut-Off Valve, Essex P2L 822645
G Pipe Plug, 1/8” NPT, Sq. Head 806603508
805H-807H Natural Gas 2
H Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT 822630
J Solenoid Gas Valve, Johnson H91WG-6 822666
L Rigid Conduit Nipple, 1/2” NPT x 1-1/2” Lg. 8136019
M Conduit Locknut, 1/2” 8136220 2
N Plastic Insulating Bushing, 1/2” 8136034 1
P Regulator, Maxitrol RV12LT, Natural Gas 8226005
808H-810H Natural Gas 3
805H-807H LP Gas 1
Natural Gas Only
All 1
808H-810H 1F Pipe Tee, 1/8” NPT, Malleable 806601005
All
805H-810H
1
1K Junction Box, 4” Sq. x 1-1/2” Deep 8136259
1
79
Page 80
Item
No.
Description Part No. Size Quantity
5-9 Pilot Assembly and Piping -- Standing Pilot (OP) USA & Canada: 6 - 10 Section, Natural and LP Gas
Pilot Burner, Honeywell Q179D1008, Natural Gas 8236025
A
Pilot Burner, Honeywell Q179D1008 w/388146KD Orice, LP Gas 6236039
B Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead 8236004
C Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg. 71362561
D Rajah Connector, Honeywell 37356 8236021
E Ground Wire Assembly 6136259
F Brass Compression Union, 1/4” OD Tube 8236008
G Regulator, Maxitrol RV12LT, Natural Gas 8226005
H Pipe Tee, 1/8” NPT, Malleable 806601005
K Shut-Off Valve, Essex P2L 822645
L Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT 822630
806H-810H 1
USA: 806H-810H
Canada: 806H & 807H
Canada: 806H-810H
Natural Gas Only
808H-810H
Canada Only
806H & 807H
Natural Gas
808H-810H Natural Gas 3
806H-810H LP Gas 1
1
1
1J Pipe Plug, 1/8” NPT, Sq. Head 806603508
2
80
Page 81
Item
No.
Description Part No. Size Quantity
5-10 Pilot Assembly and Piping -- Standing Pilot (OP-CSD-1) USA Only: 8 - 10 Section, LP Gas Only
A Pilot Burner, Honeywell Q179D1008 w/388146KD Orice, LP Gas 6236039
B Thermocouple, Honeywell Q309A1996 w/36” Lg. Lead 8236004 1
C Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg. 71362561 1
D Rajah Connector, Honeywell 37356 8236021 1
E Ground Wire Assembly 6136259 1
F Brass Compression Union, 1/4” OD Tube 8236008 1
G Regulator, Maxitrol RV12LT, Natural / LPGas 8226005 1
H Pilot Switch, Johnson L62-GB-3C 80160138 1
J Conbraco Leak Test / Shut-Off Valve, 1/8” x 1/8” 822679 1
K Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT 822630 2
808H-810H
1
81
Page 82
Item
No.
Description Part No. Size Quantity
5-11 Pilot Assembly and Piping -- Intermittent Ignition (EP) USA & Canada: 6 - 10 Section, Natural Gas Only
A Pilot Burner, Honeywell Q179C1009, Natural Gas 8236017
B Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg. 71362561 1
C Rajah Connector, Honeywell 37356 8236021 2
D Ignition Lead, Honeywell R1061012, 3 Ft. Lg. 7136247 1
E Ground Wire Assembly 6136259 1
F Brass Compression Coupling, 1/4” OD Tube 8236008
G Shut-Off Valve, Essex P2L 822645
J Pipe Plug, 1/8” NPT, Sq. Head 806603508
K Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT 822630
L Solenoid Gas Valve, Johnson H91WA-4 822662
M Junction Box, 4” Sq. x 1-1/2” Deep 8136259 1
N Rigid Conduit Nipple, 1/2” NPT x 1-1/2” Lg. 8136019 1
P Conduit Locknut, 1/2” 8136220 2
Q Plastic Insulating Bushing, 1/2” 8136034 1
R Regulator, Maxitrol RV12LT, Natural / LP Gas 8226005
806H-810H
806H & 807H
USA & Canada
808H-810H
USA Only
808H-810H
Canada Only
806H & 807H
Canada Only
808H-810H
Canada Only
806H-810H
806H-810H
Canada Only
1
1
1H Pipe Tee, 1/8” NPT, Malleable 806601005
2
3
1
1
82
Page 83
Item
No.
Description Part No. Size Quantity
5-12 Pilot Assembly and Piping -- Intermittent Ignition (EP-CSD-1) USA Only: 10 Section, Natural Gas Only
A Pilot Burner, Honeywell Q179C1009, Natural Gas 8236017
B Flame Rod Lead, Honeywell R1298020, 4 Ft. Lg. 71362561 1
C Rajah Connector, Honeywell 37356 8236021 2
D Ignition Lead, Honeywell R1061012, 3 Ft. Lg. 7136247 1
E Ground Wire Assembly 6136259 1
F Brass Compression Coupling, 1/4” OD Tube 8236008 1
G Conbraco Leak Test / Shut-Off Cock, 1/8” x 1/8” 822679 1
H Brass Compression Adapter, 1/4” OD Tube x 1/8” NPT 822630 2
J Solenoid Gas Valve, Johnson H91WA-4 822662 1
K Junction Box, 4” Sq. x 1-1/2” Deep 8136259 1
L Rigid Conduit Nipple, 1/2” NPT x 1-1/2” Lg. 8136019 1
M Conduit Locknut, 1/2” 8136220 2
N Plastic Insulating Bushing, 1/2” 8136034 1
P Regulator, Maxitrol RV12LT, Natural / LP Gas 8226005 1
808H-810H
1
83
Page 84
84
Page 85
Item
No.
Description Part No.
6. Jacket
6 Complete
6A Jacket Top Panel
6B Jacket Top Panel Insulation
6C Jacket Upper Rear Panel
6D Jacket Upper Rear Panel Insulation
6E Jacket Lower Rear Panel
6F Jacket Upper Front Panel
Quantity
805H 806H 807H 808H 809H 810H
60416111 1 --- --- --- --- ---
60416121 --- 1 --- --- --- ---
60416131 ---- --- 1 --- --- ---
60416141 --- --- --- 1 --- ---
60416151 --- --- --- --- 1 ---
60416161 --- --- --- --- --- 1
70416053 1 --- --- --- --- ---
70416063 --- 1 --- --- --- ---
70416073 --- --- 1 --- --- ---
70416083 --- --- --- 1 --- ---
70416093 --- --- --- --- 1 ---
70416103 --- --- --- --- --- 1
72016058 1 --- --- --- --- ---
72016068 --- 1 --- --- --- ---
72016078 --- --- 1 --- --- ---
72016088 --- --- --- 1 --- ---
72016098 --- --- --- --- 1 ---
72016108 --- --- --- --- --- 1
70416056 1 --- --- --- --- ---
70416066 --- 1 --- --- --- ---
70416076 --- --- 1 --- --- ---
70416086 --- --- --- 1 --- ---
70416096 --- --- --- --- 1 ---
70416106 --- --- --- --- --- 1
72016059 1 --- --- --- --- ---
72016069 --- 1 --- --- --- ---
72016079 --- --- 1 --- --- ---
72016089 --- --- --- 1 --- ---
72016099 --- --- --- --- 1 ---
72016109 --- --- --- --- --- 1
60416056 1 --- --- --- --- ---
60416066 --- 1 --- --- --- ---
60416076 --- --- 1 --- --- ---
60416086 --- --- --- 1 --- ---
60416096 --- --- --- --- 1 ---
60416106 --- --- --- --- --- 1
70416051 1 --- --- --- --- ---
70416061 --- 1 --- --- --- ---
70416071 --- --- 1 --- --- ---
70416081 --- --- --- 1 --- ---
70416091 --- --- --- --- 1 ---
70416101 --- --- --- --- --- 1
85
Page 86
Item
No.
Description Part No.
805H 806H 807H 808H 809H 810H
Quantity
6. Jacket (Continued)
7041605 1 --- --- --- --- ---
7041606 --- 1 --- --- --- ---
6G Jacket Front Removable Panel
6H Jacket Left Side Panel 6041601 1 1 1 1 1 1
6J Jacket Left Side Panel Main Insulation Piece 72016021 1 1 1 1 1 1
6K Jacket Left Side Panel Upper Corner Insulation Piece 72016023 1 1 1 1 1 1
6L Jacket Left Side Panel Lower Corner Insulation Piece 72016022 1 1 1 1 1 1
6M Jacket Right Side Panel 6041602 1 1 1 1 1 1
6N Jacket Right Side Panel Main Insulation Piece 72016011 1 1 1 1 1 1
6P Jacket Right Side Panel Lower Corner Insulation Piece 72016012 1 1 1 1 1 1
6Q Jacket Vestibule Panel
6R Jacket Vestibule Panel Upper Insulation Piece
6S Jacket Vestibule Panel Lower Insulation Piece
6T Jacket Lower Front Tie Bar
7041607 --- --- 1 --- --- ---
7041608 --- --- --- 1 --- ---
7041609 --- --- --- --- 1 ---
7041610 --- --- --- --- --- 1
70416055 1 --- --- --- --- ---
70416065 --- 1 --- --- --- ---
70416075 --- --- 1 --- --- ---
70416085 --- --- --- 1 --- ---
70416095 --- --- --- --- 1 ---
70416105 --- --- --- --- --- 1
72016057 1 --- --- --- --- ---
72016067 --- 1 --- --- --- ---
72016077 --- --- 1 --- --- ---
72016087 --- --- --- 1 --- ---
72016097 --- --- --- --- 1 ---
72016107 --- --- --- --- --- 1
72016056 1 --- --- --- --- ---
72016066 --- 1 --- --- --- ---
72016076 --- --- 1 --- --- ---
72016086 --- --- --- 1 --- ---
72016096 --- --- --- --- 1 ---
72016106 --- --- --- --- --- 1
70416052 1 --- --- --- --- ---
70416062 --- 1 --- --- --- ---
70416072 --- --- 1 --- --- ---
70416082 --- --- --- 1 --- ---
70416092 --- --- --- --- 1 ---
70416102 --- --- --- --- --- 1
86
Page 87
Item
No.
Description Part No.
805H 806H 807H 808H 809H 810H
Quantity
7. Trim and Miscellaneous Controls
Limit, 140-220°F, Honeywell L4080D1218 (EI & Standing Pilot);
A
L4080B1212 (EP * OP)
Immersion Well, ¾” NPT x 1½” Insul. Depth 80160426 1 1 1 1 1 1
B Limit, Manual Reset, Honeywell L4006E1133 80160703 1 1 1 1 1 1
B1 Immersion Well, ¾” NPT x 3” Insul. Depth 80160452 1 1 1 1 1 1
C Temperature - Pressure Gauge 100282-01 1 1 1 1 1 1
C1 Nipple, 2 NPT x 10” w/Gauge Tapping 8061601 1 1 1 1 1 1
D Safety Relief Valve, ¾ NPT, 50 psi 81660302 1 1 1 1 1 1
D1 Nipple, ¾ NPT x 3½” 806600038 1 1 1 1 1 1
E Drain Valve, ¾ NPT, Conbraco 35-302-03 806603061 1 1 1 1 1 1
E1 Nipple, ¾ NPT x 3½” 806600038 1 1 1 1 1 1
E2 Coupling, ¾ NPT 806602561 1 1 1 1 1 1
F Blocked Vent Switch Replacement Assembly 6016058 1 1 1 1 1 1
G Flame Roll-out Switch 80160044 1 1 1 1 1 1
G1 Flame Roll-out Switch Mounting Bracket 7181612 1 1 1 1 1 1
H Junction Box 8136010 1 1 1 1 1 1
Control Center, Honeywell R8285D500
J
(Intermittent Circulation builds)
K Transformer, 50VA (Continuous Circulation builds) 80160249 1 1 1 1 1 1
L Ignition Module, Honeywell S8610M3009 100958-01 1 1 1 1 1 1
Vestibule Wiring Harness, Complete with Vent Damper Bypass
M
Plug (EI and Standing Pilot) (Not Depicted)
80160251 80160474
80160155U 1 1 1 1 1 1
81316010 1 1 1 --- --- ---
81316011 --- --- --- 1 1 1
1 1 1 1 1 1
87
Page 88
Item
No.
Description Part No.
805H 806H 807H 808H 809H 810H
8. Draft Hood and Automatic Vent Damper
8111605 1 --- --- --- --- ---
8111604 --- 1* --- --- --- ---
8111607 --- 1** --- --- --- ---
8111603 --- --- 1* --- --- ---
8A Draft Hood
Automatic Vent Damper, 7”
Efkal RVGP-7 8116324 1 --- --- --- --- ---
Automatic Vent Damper, 8”
Efkal RVGP-8 8116325 --- 1 --- --- --- ---
8B
Automatic Vent Damper, 9”
Efkal RVGP-9 8116326 --- --- 1 1 --- ---
Automatic Vent Damper, 10”
Efkal RVGP-10 8116327 --- --- --- --- 1 1
All components for use in both USA and Canada, unless marked with * for USA Only or ** for Canada Only.
8111608 --- --- 1** --- --- ---
8111602 --- --- --- 1* --- ---
8111608 --- --- --- 1** --- ---
8111601 --- --- --- --- 1* 1*
8111609 --- --- --- --- 1** 1**
Quantity
88
Page 89
SERVICE RECORD
DATE SERVICE PERFORMED
89
Page 90
SERVICE RECORD
DATE SERVICE PERFORMED
90
Page 91
SERVICE RECORD
DATE SERVICE PERFORMED
91
Page 92
92
Loading...