Burkert 8098 Operating Instructions Manual

Type 8098
FLOWave
SAW Flowmeter
Operating Instructions
Software version A.02.00.00 and higher
We reserve the right to make technical changes without notice.
© Bürker t SAS, 2015 - 2018
Operating Instructions 1809/03 _EU-EN 00567647 / Original EN
Type 8098
General contents
General information ..........................................................................................................................................................................5
Description.................................................................................................................................................................................................11
technical Data ........................................................................................................................................................................................19
installation in the pipe ..................................................................................................................................................................33
electrical installation .................................................................................................................................................................45
DoinG the settinGs ..............................................................................................................................................................................67
menu DISPLAY .............................................................................................................................................................................................85
menu GENERAL SETTINGS .................................................................................................................................................................93
menu SAW SENSOR - PARAMETER ............................................................................................................................................131
menu SAW SENSOR - DIAGNOSTICS ........................................................................................................................................193
menu SAW SENSOR - MAINTENANCE .......................................................................................................................................199
menu OUTPUTS .......................................................................................................................................................................................219
menu INDUSTRIAL COMMUNICATION ......................................................................................................................................237
troubleshootinG, maintenance, transport, storaGe .............................................................................. 249
English
3
Type 8098
General contents
4
English
Type 8098

General information

1 ABOUT THESE OPERATING INSTRUCTIONS ....................................................................................................................6
1.1 Symbols used .........................................................................................................................................................................6
1.2 Definition of the word device ..........................................................................................................................................6
1.3 Definition of the word büS ................................................................................................................................................7
1.4 Validity of the Operating Instructions .........................................................................................................................7
2 INTENDED USE ....................................................................................................................................................................................7
3 BASIC SAFETY INFORMATION ....................................................................................................................................................8
4 GENERAL INFORMATION .............................................................................................................................................................10
4.1 Manufacturer's address and international contacts .........................................................................................10
4.2 Warranty conditions ...........................................................................................................................................................10
4.3 Information on the Internet ............................................................................................................................................10
English
5
Type 8098
About these Operating Instructions

1 ABOUT THESE OPERATING INSTRUCTIONS

The Operating Instructions describe the entire life cycle of the device. Please keep the Operating Instructions in a safe place, accessible to all users and any new owners.
The Operating Instructions contain important safety information.
Failure to comply with these instructions can lead to hazardous situations. Pay attention in particular to the chapters 3 Basic safety information and 2 Intended use.
▶ Irrespective of the device version, the Operating Instructions must be read and understood.

1.1 Symbols used

DanGer
Warns against an imminent danger.
▶ Failure to observe this warning results in death or in serious injury.
WarninG
Warns against a potentially dangerous situation.
▶ Failure to observe this warning can result in serious injury or even death.
caution
Warns against a possible risk.
▶ Failure to observe this warning can result in substantial or minor injuries.
notice
Warns against material damage.
Indicates additional information, advice or important recommendations.
Refers to information contained in these Operating Instructions or in other documents.
▶ Indicates an instruction to be carried out to avoid a danger, a warning or a possible risk.
→ Indicates a procedure to be carried out.
A highlighted term is related to a menu or a menu item.
Indicates the result of a specific instruction.
1.2 Definition of the term device
The term "device" used in these Operating Instructions always refers to the Type 8098 flowmeter.
6
English
Type 8098
About these Operating Instructions
1.3 Definition of the term büS
The term "büS" used in these Operating Instructions refers to the industrial communication, developed by Bürkert, based on the CANopen protocol.
→ For more information on büS, read the cabling guide available in English and German (Cabling_guide_for_
büS_networks.pdf) at www.buerkert.com search for "Guide for planning büS networks".
→ For more information on CANopen which is related to the device, refer to the Operating Instructions
"CANopen Network configuration" at www.buerkert.com.

1.4 Validity of the Operating Instructions

The Operating Instructions are valid for the devices from software version A02.00.00.
To read out the version number of the device software, do the following:
→ Go to the CONFIGURATION view.
General settings
Confirm to access the Parameter view.
→ Go to the MAINTENANCE view.
Device information
Software version
Go back to the parent menu.

2 INTENDED USE

Use of the device that does not comply with the instructions could present risks to people, nearby installations and the environment.
The Type 8098 flowmeter is intended to measure the flow rate of clean liquids, non emulsified (homo­geneous liquids) and free of air bubbles and free of gas bubbles and free of solids, using the Surface Acoustic Wave (SAW) measurement principle.
▶ Use the device in compliance with the characteristics and the conditions of commissioning and use specified
in the contractual documents and in the Operating Instructions.
▶ Protect the device against electromagnetic interference, ultraviolet rays and, when installed outdoors, against
the effects of climatic conditions.
▶ Only operate a device in perfect working order.
▶ Properly transport, store, install and operate the device. ▶ Only use the device as intended.
7
English
Type 8098
Basic safety information

3 BASIC SAFETY INFORMATION

This safety information does not take into account any contingencies or occurrences that may arise during instal­lation, use and maintenance of the product.
The operating company is responsible for the respect of the local safety regulations, including staff safety.
Risk of injury due to electrical voltage.
▶ Before carrying out work on the system, disconnect the electrical power for all the conductors and isolate it.
▶ Observe all applicable accident protection and safety regulations for electrical equipment.
Risk of injury due to high pressure in the installation.
▶ Before any intervention in the installation, stop the circulation of fluid, cut off the pressure and drain the pipe.
▶ Before any intervention in the installation, make sure there is no pressure in the pipe.
▶ Observe the dependency between the fluid temperature and the fluid pressure for the fitting used.
If switched on for a prolonged time, risk of burns or fire due to hot device surfaces
▶ Do not touch with bare hands.
▶ Keep the device away from highly flammable substances and fluids.
Risk of burns due to high fluid temperatures.
▶ Do not touch with bare hands the parts of the device that are in contact with the fluid.
▶ Use safety gloves to handle the device.
▶ Before opening the pipe, stop the circulation of fluid and drain the pipe.
▶ Before opening the pipe, make sure the pipe is completely empty.
Risk of injury due to the nature of the fluid.
▶ Respect the prevailing regulations on accident prevention and safety relating to the use of dangerous fluids.
General dangerous situations
To avoid injury:
▶ Do not use the device in explosive atmospheres.
▶ Do not use the device in an environment incompatible with the materials it is made of.
▶ Do not use fluid that is incompatible with the materials the device is made of.
▶ Do not subject the device to mechanical loads.
▶ Do not make any modifications to the device.
▶ Prevent any unintentional power supply switch-on.
▶ Only qualified and skilled staff may carry out installation and maintenance work.
▶ Ensure a defined or controlled restarting of the process after a power supply interruption.
▶ Observe the general technical rules.
8
English
Type 8098
Basic safety information
caution
Risk of injury due to a heavy device.
A heavy device can fall down during transport or during installation and cause injuries.
▶ Transport, install and dismantle a heavy device with the help of another person.
▶ Use appropriate tools.
notice
The device may be damaged by the measured fluid.
▶ Systematically check the chemical compatibility of the component materials of the device and the fluids likely
to come into contact with the materials (for example: alcohols, strong or concentrated acids, aldehydes, alka­line compounds, esters, aliphatic compounds, ketones, halogenated aromatics or hydrocarbons, oxidants and chlorinated agents).
notice
Elements/components sensitive to electrostatic discharges
▶ This device contains electronic components that are sensitive to electrostatic discharges. They may be dam-
aged if they are touched by an electrostatically charged person or object. In the worst case scenario, these components are instantly destroyed or disabled as soon as they are activated.
▶ To minimise or even avoid any damage caused by an electrostatic discharge, take all the precautions
described in standard EN 61340-5-1.
▶ Also make sure that you do not touch any of the live electrical components.
English
9
Type 8098
General information

4 GENERAL INFORMATION

4.1 Manufacturer's address and international contacts

To contact the manufacturer of the device, use the following address:
Bürkert SAS
Rue du Giessen
BP 21
F-67220 TRIEMBACH-AU-VAL
You may also contact your local Bürkert sales office.
The addresses of our international sales offices are available on the internet at:
www.burkert.com

4.2 Warranty conditions

The condition governing the legal warranty is the conforming use of the device in observance of the operating conditions specified in the Operating Instructions.

4.3 Information on the Internet

You can find the operating instructions and the technical data sheets for Type 8098 at:
www.burkert.com
10
English
Type 8098

Description

5 DESCRIPTION ....................................................................................................................................................................................12
5.1 Knowing the device ...........................................................................................................................................................12
5.1.1 Wi-Fi module .......................................................................................................................................13
5.1.2 Unlocking magnetic key ....................................................................................................................14
5.2 Understanding the rating plates .................................................................................................................................14
5.3 Marking with the MAC address ...................................................................................................................................16
5.4 Description of the device status LED .....................................................................................................................17
English
11
Type 8098
Description

5 DESCRIPTION

5.1 Knowing the device

The Type 8098 flowmeter is made up of a Type SE98 transmitter and a Type S097 flow sensor.
The following pictures describe the main versions of the Type 8098 flowmeter:
• Fig. 1 describes a device with 2 M20x1,5 cable glands in stainless steel (or in nickel plated brass) and 1 5-pin M12 male connector.
• Fig. 2 describes the Ethernet version of the device, i.e. a device with 2 4-pin M12 female connectors and 1 5-pin M12 male connector.
Blind cover
Type SE98
transmitter
Type 8098 flowmeter
Type S097 flow
sensor
or display module (Type ME31)
Device status LED indicating the status of the device, and seal
Transmitter housing, including the electronic modules
Cable glands in nickel plated brass, with blind plugs
or cable glands in stainless steel, with blind plugs
Seal
5-pin M12 male connector, with screwed plug
Functional earth
Seal
Blind cover
12
Process connection
Pressure compensating element
1) The process connections can be either clamp connections or flange connections.
Sensor housing
Sensor measurement tube
Fig. 1: Description of the device with 2 M20x1,5 cable glands and 1 5-pin M12 male connector
English
1)
Type SE98
transmitter
Type 8098
Description
Blind cover
or display module (Type ME31)
Device status LED indicating the status of the device, and seal
Transmitter housing, including the electronic modules
Seal
Type 8098 flowmeter
Type S097 flow
sensor
1) The process connections can be either clamp connections or flange connections.
4-pin M12 female connectors with plugs
5-pin M12 male connector, with screwed plug
Functional earth
Blind cover
Pressure compensating element
Seal
Sensor housing
Process connection
Sensor measurement tube
1)
Fig. 2: Description of an Ethernet version of the device, with 2 4-pin M12 female connectors and 1 5-pin M12 male
connector

5.1.1 Wi-Fi module

The device can be equipped with a Wi-Fi module in place of or in addition to the display module. The Wi-Fi module has the Type number ME31, too. The Wi-Fi module has the same functional scope as the display module.
The Wi-Fi module is intended for use in Europe, the USA, and Canada.
The module can be integrated into an existing WLAN infrastructure. The wireless range is approximately 10 m.
English
13
Type 8098
21
911
13
10
3
12
Description
The module provides a web server which can be accessed if the following requirements are met:
• Windows 7/8.1/10: IE11, Edge, Google Chrome, from version 53.
• Android with Google: Chrome, from version 53.
• Apple: Safari, from iOS 9.3.5.

5.1.2 Unlocking magnetic key

The device is delivered with a magnetic key to unlock the display module or the blind cover. See Fig. 3.
Fig. 3: Unlocking magnetic key
The device operates on a 4-wire system and needs a 12...35 V DC power supply.
The device has three outputs:
• 1 analogue output,
• 1 digital output,
• 1 output, which can be configured as an analogue output or as a digital output.

5.2 Understanding the rating plates

8098 FLOWave Flowmeter Supply: 12-35 5W Max. IP65 / IP67 Temp. ambient: -10 to 70°C NEMA 4X Not evaluated by UL
88888888 SN 999999
F-67220 Triembach
W49MN
28-04
1. Supply voltage
CAN_H GND
34
5 CAN_L
21
CAN shield
Made in France
V+
8. Construction code
4 5 6
7
8
14
2. Type of the device
3. Power consumption
4. IP Protection class of the device
5. Ambient temperature range
6. Protection class of the device
7. Pin assignment of the 5-pin M12 male connector
Fig. 4: Rating plate of the Type 8098 flowmeter (example of a UL device)
English
9. Serial number
10. Conformity marking
11. Article number
12. Warning: Before using the device, take into account the technical specifications given in the Operating Instructions.
13. Certification
Type 8098
21
68
10
7
9
1
7
Description
28-04
8098 FLOWave Flowmeter IP65 / IP67 / NEMA 4X Temp. ambient: -10 to 55°C
88888888 SN 999999
CAN_H GND
34
5 CAN_L
F-67220 Triembach
W49MN
CAN shield
Made in France
21
V+
3
4
5
1. Protection class of the device
2. Type of the device
3. Ambient temperature range
7. Conformity marking
8. Article number
9. Warning: Before using the device, take into account the technical specifications given in the Operating
4. Pin assignment of the 5-pin M12 male connector
5. Construction code
Instructions.
10. Certification
6. Serial number
Fig. 5: Rating plate of the Type 8098 flowmeter (example of a non-UL Ethernet device)
SE98 FLOWave Transmitter Supply: 12-35V 5W max Housing: 304 / 1.4301 Slot 5: Indust. communication Slot 4: 1AO-1DO-1AO/DO ME31 - Display module ME31 - WIFI module
F-67220 Triembach
W49MN
Made in France
2 3
4
5
6
1. Type of the transmitter
2. Power supply and maximum power consumption
3. Housing material
4. Communication type and available outputs
5. Communication modules
6. Construction code
7. Conformity marking
Fig. 6: Rating plate of the Type SE98 transmitter (example of an Ethernet device with display module and Wi-Fi
module)
English
15
Type 8098
1
7
Description
S097 FLOWave Flow sensor Pipe: 316L/1.4435 Housing: 304/1.4301 DIN 11866 C / Clamp D50.5 DIN 32676 B DN15 PN25bar Max. flow:10 m3/h Temp. medium : -20 to 110°C
F-67220 Triembach
W4ZMN
Made in France
2 3
4 5
6
1. Type of the flow sensor
2. Material of the pipe and material of the housing
3. Standard the pipe conforms to; type of process connection, external diameter of the clamp and standard the process connection conforms to; DN of the measurement tube
4. Pressure class of the device and maximum flow rate
5. Fluid temperature range
6. Construction code
7. Conformity marking
Fig. 7: Rating plate of the Type S097 flow sensor (example)

5.3 Marking with the MAC address

The marking with the MAC address can be seen by opening the front of the transmitter.
→ To open the front of the transmitter, see chpt. 8.10, page 53.
DC-B0-58-FF-FF-FF
Fig. 8: Marking with the MAC address of the device (example)
16
English
Type 8098
Description

5.4 Description of the device status LED

Ex works, the LED that indicates the state of the device changes its colour and state based on the NAMUR NE 107 recommendation.
If several states exist simultaneously, the state with the highest priority is displayed. The priority is determined by the severity of the deviation from standard operation (red LED = failure, error or malfunction = highest priority).
Device status LED Colour code
(for a PLC)
Colour
State
Red 5 Failure, error,
Orange 4 Function check Ongoing work on the device (for example,
Yellow 3 Out of
Blue 2 Maintenance
Green 1 Diagnostics active No event has been generated. Status changes are
White 0 Diagnostics
ON - Device is in oper-
Flashing rapidly
- Identification Serves as identification of a device in the
Description Meaning
Due to a malfunction of the device or its periphery,
malfunction
specification
required
the measured values can be incorrect.
checking the correct behaviour of the outputs by simulating measurement values); the output signal is temporarily invalid (e.g. frozen).
The ambient conditions or process conditions for the device are outside the permitted ranges.
Device internal diagnostics point to problems in the device or with the process properties.
The device continues to measure but a function is temporarily restricted.
→ Do the required maintenance operation.
shown in colour.
Messages are listed and possibly transmitted via any connected fieldbus.
Device is switched on.
inactive
ating state.
Status changes are not shown.
Messages are neither listed nor transmitted via any connected fieldbus.
Device is in standard operation.
büS network.
The device was selected using the Bürkert Com­municator software.
Table 1: Device status LED - colours and states in accordance with NAMUR NE 107, edition 2006-06-12
English
17
Type 8098
18
English
Type 8098

Technical data

6 TECHNICAL DATA .............................................................................................................................................................................20
6.1 Operating conditions ........................................................................................................................................................20
6.2 Conformity to standards and directives .................................................................................................................20
6.3 Conformity to the Pressure Equipment Directive ..............................................................................................20
6.4 UL certification .....................................................................................................................................................................21
6.5 EHEDG certification ...........................................................................................................................................................21
6.6 Fluid data .................................................................................................................................................................................22
6.7 Measurement data .............................................................................................................................................................24
6.8 Electrical data .......................................................................................................................................................................25
6.9 Mechanical data ...................................................................................................................................................................26
6.10 Specifications of the Ethernet Industrial communication ............................................................................28
6.10.1 Modbus TCP protocol .......................................................................................................................28
6.10.2 PROFINET protocol ...........................................................................................................................28
6.10.3 EtherNet/IP protocol ..........................................................................................................................29
6.10.4 EtherCAT protocol .............................................................................................................................31
English
19

6 TECHNICAL DATA

6.1 Operating conditions

Ambient temperature
• Device with 2 M20x1,5 cable
glands and 1 5-pin M12 connector
• Device with 2 4-pin M12 female
connectors and 1 5-pin M12 con-
nector (Ethernet version) Air humidity < 85%, non condensing Height above see level max. 2000 m Installation category Category I according to UL 61010-1 Degree of pollution Degree 2 according to EN 61010-1 Protection class according to
EN 60529
Protection class according to NEMA250
(not evaluated by UL)
• –10...+70 °C
• –10...+55 °C
IP65, IP67, if the device is wired and if the cable glands are tightened and the covers are screwed tight. Unused cable glands must be sealed with the stopper gaskets provided (mounted upon delivery of the device). An unused M12 connector must be protected by the screwed plug.
4X, if the device is wired and if the cable glands are tightened and the covers are screwed tight. Unused cable glands must be sealed with the stopper gaskets provided (mounted at the delivery of the device). An unused M12 connector must be protected by the screwed plug.
Type 8098
Technical data

6.2 Conformity to standards and directives

The applied standards, which verify conformity with the EU Directives, can be found on the EU Type Examination Certificate and/or the EU Declaration of Conformity (if applicable).

6.3 Conformity to the Pressure Equipment Directive

→ Make sure the device materials are compatible with the fluid.
→ Make sure the pipe DN is adapted for the device.
The device conforms to Article 4, Paragraph 1 of the Pressure Equipment Directive 2014/68/EU under the fol­lowing conditions:
• Device used on a pipe (PS = maximum admissible pressure; DN = nominal diameter of the pipe)
Type of fluid Conditions
Fluid group 1, Article 4, Paragraph 1.c.i DN≤25
Fluid group 2,Article 4, Paragraph 1.c.i
Fluid group 1, Article 4, Paragraph 1.c.ii
DN≤32
or PSxDN≤1000 DN≤25
or PSxDN≤2000
20
English
Type 8098
Measuring Equipment EXXXXXX
®
Technical data
Type of fluid Conditions
DN≤200
Fluid group 2, Article 4, Paragraph 1.c.ii
or PS≤10
or PSxDN≤5000

6.4 UL certification

The devices with variable key PU01 or PU02 are UL-certified devices and comply also with the following standards:
• UL 61010-1
• CAN/CSA-C22.2 n°61010-1
Identification on the device Certification Variable key
UL recognized PU01
UL listed PU02

6.5 EHEDG certification

• EL class I
• The following versions are EHEDG certified:
Process connections Diameters
• Clamp
connections according to ASME BPE
• 3/4'', 1'', 1 1/2'', 2''
1)
(DIN 32676 series C)
• Clamp connections according to DIN 11864-3
• 3/4'', 1'', 1 1/2'', 2''
series C
• Flange connections according to DIN 11864-2
• 3/4'', 1'', 1 1/2'', 2''
series C
1)
• Clamp
connections according to
DIN 32676 series B
1)
• Clamp
connections according to
• DN15 (except variants with a clamp diameter of
34.0 mm) DN25, DN40, DN50
• DN15, DN25, DN40, DN50
DIN 32676 series A
• Clamp connections according to DIN 11864-3
• DN15, DN25, DN40, DN50
series A, DIN 11864-3 series B
• Clamp
connections according to SMS 3017 /
• DN25, DN40, DN50
1)
ISO 2852 for pipes according to SMS 3008
• Flange connections according to DIN 11864-2
• DN15, DN25, DN40, DN50
series A, DIN 11864-2 series B
1)
The EHEDG compliance is only valid if used in combination with EHEDG-compliant gaskets from Combifit
International B.V.
The manufacturer of the device does not supply any gaskets for the process connections.
→ To make sure you use EHEDG-compliant gaskets, refer to the "EHEDG Position Paper" available on the
EHEDG website.
21
English

6.6 Fluid data

80 140
°C
°C
0204060 100 120-20
-1
80 140
°C
°C
0204060 100 120-20
-1
Ambient temperature
70 60
40
Type 8098
Technical data
20
Temperatures authorized for a limited duration
0
0
Fluid temperature
Fig. 8: Dependency between the fluid temperature and the ambient temperature, device with 2 M20x1,5 cable glands
and 1 5-pin M12 male connector
Ambient temperature
70
55
40
20
Temperatures authorized for a limited duration
0
0
Fluid temperature
Fig. 9: Dependency between the fluid temperature and the ambient temperature, device with 2 4-pin M12 female
connectors and 1 5-pin M12 male connector (Ethernet version)
Fluid temperature –20...+110 °C, with clamp process connections. Up to 140 °C for maximum
60 minutes for a sterilisation process.
Maximum temperature gradient: 10 °C/s [measured by the sensor integrated in the device]
The maximum fluid temperature can be restricted by the ambient operating temperature. Depending on the version of your device, see Fig. 8 or Fig. 9
Type of fluids Non-dangerous liquids according to Article 4, Paragraph 1 of Directive 2014/68/EU
22
English
Type 8098
Technical data
Size of the process
connection
Type of process connection
clamp
DN15, DN25
flange
DN25 clamp
clamp
3/4'', 1'', 1 1/2''
flange DIN 11864-2 series C PN25
clamp
DN40
Standards the process connections
conform to
• DIN 11864-3 series A
• DIN 11864-3 series B
• DIN 32676 series A
• DIN 32676 series B
• DIN 11864-2 series A
• DIN 11864-2 series B SMS 3017 / ISO 2852 for pipes
according to SMS 3008
• ASME BPE (DIN 32676 series C)
• DIN 11864-3 series C
• DIN 11864-3 series B
• DIN 32676 series B
• DIN 11864-3 series A
• DIN 32676 series A
• SMS 3017 / ISO 2852 for pipes according to SMS 3008
PN
PN25
PN25
PN25
PN25
PN16
PN25
DIN 11864-2 series B PN16
flange
DIN 11864-2 series A PN25
• DIN 11864-3 series A
• DIN 11864-3 series B
DN50
clamp
• DIN 32676 series A
• DIN 32676 series B
PN16
• SMS 3017 / ISO 2852 for pipes according to SMS 3008
• DIN 11864-2 series A
flange
PN16
• DIN 11864-2 series B
• ASME BPE (DIN 32676 series C)
2''
clamp
• DIN 11864-3 series C
PN16
flange DIN 11864-2 series C PN16
Table 2: Fluid pressure, depending on the pipe diameter, the type of process connections and the process connection
standard
English
23

6.7 Measurement data

Flow rate measurement
Type 8098
Technical data
• Measurement range • 0...7 m
1) 2)
• Measurement deviation
for a flow rate
• ±0.4% of the measured value
3
/h to 0...90 m3/h, depending on the DN of the sensor
between 10% of the full scale and the full scale
• Measurement deviation
for a flow rate
• < ±0.08% of the full scale
1) 2)
between 1% of the full scale and 10% of the full scale
• Repeatability
2)
for a flow rate between 10% of
• ±0.2% of the measured value
the full scale and the full scale
• Repeatability
for a flow rate between 1% of
• ±0.04% of the full scale
2)
the full scale and 10% of the full scale
• Refresh time
• Adjustable, see chpt. 14.11 Setting the refresh time.
Temperature measurement
• Measurement range • –20...+140 °C
• Measurement deviation
for temperatures up
• ±1 °C
1)
to 100 °C
• Measurement deviation
for temperatures
• ±1.5%
1)
between 100 °C and 140 °C
• Refresh time • 1 s
Density factor measurement (optional feature)
• Measurement range • 0,8...1,3
• Resolution • 0,00001
• Repeatability • ±0.5% of the measured value
• Refresh time
• Adjustable, see chpt. 14.11 Setting the refresh time.
Acoustic transmission factor measurement (optional feature)
• 10...120%
• Measurement range
• Resolution • 0,01%
• Repeatability • ±2% of the measured value
• Refresh time
1) "Measurement bias" as defined in standard JCGM 200:2012.
2) Determined under the following reference conditions: fluid = water, free of gas bubbles and solids; water and ambient
temperatures = 23 °C, refresh time of 190 ms, applying the minimum inlet (40xDN) and minimum outlet (1xDN) straight pipe lengths, appropriate pipe dimensions.
• Adjustable, see chpt. 14.11 Setting the refresh time.
24
English
Type 8098
Technical data

6.8 Electrical data

Ambient temperature °C
80
70
60
50
40
30
20
10
0
-20 0 20 40 60 80 100 120 140 160
-10
-20
Voltage not allowed Temperature authorized for a limited duration
Supply voltage V DC
35
30
25
20
15
10
5
Fluid temperature °C
Fig. 10: Minimum supply voltage depending on the ambient temperature and the fluid temperature, device with 2
M20x1,5 cable glands and 1 5-pin M12 male connector
Voltage not allowed
Ambient temperature °C
80
70
60
50
40
30
20
10
0
-20 0 20 40 60 80 100 120 140 160
-10
-20
Temperature authorized for a limited duration
Supply voltage V DC
35
30
25
20
15
10
5
Fluid temperature °C
Fig. 11: Minimum supply voltage depending on the ambient temperature and the fluid temperature, device with 2 4-pin
M12 female connectors and 1 5-pin M12 male connector (Ethernet version)
Operating voltage • 12...35 V DC; the minimum voltage to be supplied
depends on the fluid temperature and on the ambient operating temperature: depending on the version of your device, see Fig. 10 or Fig. 11
• Current consumption: max. 2 A
• Filtered and regulated
• Tolerance: ±10%
• SELV circuit, at a non-dangerous energy level
Energy source (not supplied) Limited energy source according to paragraph 9.4 of
standard EN 61010-1
English
25
Power consumption (without the consumption of the outputs)
Type 8098
Technical data
• Device with 2 M20x1,5 cable glands and 1
5 W
5-pin M12 connector
• Device with 2 4-pin M12 female connectors
8 W
and 1 5-pin M12 connector (Ethernet version)
Polarity reversal Protected
Analogue output 1, also output 3 if configured as
• 4...20 mA current; 3.6 mA or 22 mA to indicate an error
an analogue output
• Uncertainty: ±0.04 mA
• Resolution: 0.8 µA
• Open loop detection through diagnostics software function
• Any connection mode, in sink or source mode
• Galvanically isolated, passive
• Protected against polarity reversal
• Maximum loop impedance 1300W at 35 V DC, 1000W at 30 V DC, 700W at 24 V DC, 450W at 18 V DC
Digital output 2, also output 3 if configured as a
• Transistor
digital output
• Any connection mode, in NPN or PNP mode
• Pulse (by default), can be changed by the user
• 0...2000 Hz
• 5...35 V DC, max. 700 mA
• Galvanically isolated, passive
• Overload information through diagnostics software function
• Protected against overloads
• Protected against polarity reversals

6.9 Mechanical data

Dimensions and weight of the device: refer to the technical data sheet regarding Type 8098 available at
www.buerkert.com
Table 3: Materials in contact with ambient air
Component Material
Transmitter housing
Cable glands / Blind plugs (depending on the version of your device)
1)
, sensor housing Stainless steel 304 / 1.4301, outer surface finish Ra < 1.6 µm
Stainless steel / PA6
Nickel plated brass / Black polyoxymethylene (POM)
26
English
Type 8098
Technical data
Component Material
5-pin M12 male connector / Screwed plug (depending on the version of the device)
Stainless steel / Stainless steel
Nickel plated brass / Nickel plated brass
4-pin M12 female connector / Blind plug Stainless steel / Stainless steel
Pressure compensating element Stainless steel
External M4 screw for earth connection Stainless steel A4
Display Float glass, stainless steel 304 / 1.4301
Seals VMQ silicone
Rating plate Polyester
1)
The housing may have slight machining marks due to the manufacturing process. These marks do not affect the
operation of the device and are not a manufacturing defect.
Table 4: Materials in contact with the fluid
Component Material
• Sensor measurement tube Stainless steel 316L / DIN 1.4435 BN2
• Pipe connections
Table 5: Available surface finish
Component Surface finish according to ISO 4288
Ra < 0.8 µm
Measurement tube (inner surface)
or Ra < 0.4 µm
• Measurement tube (outer surface) Ra < 1,6 µm (excluding welding seams)
• Housing
English
27
Type 8098
Technical data

6.10 Specifications of the Ethernet Industrial communication

Table 6: Specifications of the industrial communication module
Network speed 10/100 mbps Auto negotiation Yes Auto MDI/MDI-X Yes Switch function Yes Network diagnostics Yes, via error telegram
MAC-ID
Device name Ethernet (factory setting) FLOWave (name can be changed)

6.10.1 Modbus TCP protocol

Individual identification number, stored in the module and on the outside of the device (see rating plate)
TCP port 502
Protocol Internet protocol, version 4 (IPv4)
Network topology • Tree
• Star
• Line (open daisy chain)
IP configuration • Static IP address
• Not supported:
- BOOTP (Bootstrap Protocol)
- DHCP (Dynamic Host Configuration Protocol)
Transmission speed 10 and 100 MBit/s
Data transport layer EtherNet II, IEEE 802.3
Modbus function codes 1, 2, 3, 4, 15, 16, 23
Read/write register Maximum 125 read registers and 123 write registers per telegram
Message mode Server
Input (Target to Originator)
• All diagnostics and errors information has the highest priority and can be read by a PLC (refer to the concerned protocol file available at www.burkert.com).
• PDO: value, status, unit
• Device and modules: status
• Functions: value, status
28
PDO = Process Data Object, Target = Server, Originator = Client.

6.10.2 PROFINET protocol

Product type Compact field IO device
PROFINET IO specification V2.3
English
Type 8098
Technical data
Network topology • Tree
• Star
• Ring (closed daisy chain)
• Line (open daisy chain)
Network management • LLDP (Link Layer Discovery Protocol)
• SNMP V1 (Simple Network Management Protocol)
• MIB-II (Management Information Base)
• Physical device
Additional supported features • DCP (Discovery and Configuration Protocol)
• VLAN- and priority tagging
• Shared device
• RTC (Real Time Cyclic) protocol: Class 1
• Not supported:
- IRT (In Real Time)
Transmission speed 100 MBit/s full duplex
Data transport layer EtherNet II, IEEE 802.3
Maximum supported conformance class CC-B
Media Redundancy (for ring topology) MRP client is supported
Minimum cycle time 10 ms
Input cyclic data (device to IO-controller or device to IO-supervisor)
• All diagnostics and errors information has the highest priority and can be read by a PLC (refer to the concerned protocol file available at www.burkert.
com).
• PDO: value, status, unit
• Device and modules: status
• Functions: value, status
Application Relations (AR) The device can simultaneously process up to
2 IO-ARs, 1 Supervisor AR and 1 Supervisor DA AR.
GSDml file
Available at / Download from: www.burkert.com
PDO = Process Data Object

6.10.3 EtherNet/IP protocol

Protocol Internet protocol, version 4 (IPv4) Network topology • Tree
• Star
• DLR (Device Level Ring) for closed daisy chain
• Linear for open daisy chain
IP configuration • Static IP address
• BOOTP (Bootstrap Protocol)
• DHCP (Dynamic Host Configuration Protocol)
CIP reset services (Common Industrial Protocol)
Transmission speed 10 and 100 MBit/s
Reset service (type 0 or type 1) of the Identity object
29
English
Type 8098
Technical data
Duplex modes Half duplex, full duplex, auto-negotiation Data transport layer EtherNet II, IEEE 802.3 MDI modes
MDI, MDI-X, auto-MDI-X
(Medium Dependant Interface) Predefined standard objects • Identity (0x01)
• Message Router (0x02)
• Assembly (0x04)
• Connection Manager (0x06)
• DLR (0x47)
• QoS (0x48)
• TCP/IP Interface (0xF5)
• EtherNet Link (0xF6)
Additional supported features • ACD (Address Conflict Detection
• Integrated switch
RPI (Requested Packet Interval) • minimum: 100 ms
• maximum: 9999 ms
Input (Consumer to Producer or Adapter to Scanner)
• All diagnostics and errors information has the highest priority and can be read by a PLC (refer to the con­cerned protocol file available at www.burkert.com).
• PDO: value, status, unit
• Device and modules: status
• Functions: value, status
EDS file
Available at / Download from: www.burkert.com
PDO = Process Data Object, Consumer = Server, Producer = Client, Adapter = Server, Scanner = Client.
30
English
Loading...
+ 250 hidden pages